EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 1
Data Sheet
EM-SB3/0/485/CTEnergy Meter
EM-SB3/0/485/CT
Description
Energy meters with an integrated serial RS485 MODBUS interface allow direct reading of all relevant data, such as energy (total and partial), current and voltage, active and reactive power for the three phases.
Main features
▪ 3-phase energy meter, 3 × 230 / 400 VAC 50 Hz ▪ Measurement through a current transformer up to 1500 A ▪ Display of active power, voltage and current for each phase ▪ Display of active power for all phases ▪ MODBUS RTU Interface for up to 247 meters ▪ Reactive power for every and/or all phases available through MODBUS interface
▪ 7-digits display ▪ Lead seal possible with cover accessory (ACCEM-SB3COVER)
▪ Accuracy class B according to EN50470-3, accuracy class 1 according to IEC62053-21
▪ 1 or 2 tarrifs.
Physical (dimensions in mm)
82
27
62
4,5
6
70
65 x 11,7 = (58,5)
768
4,5930,5 9
11
57,7
22,7
35
69,5
3162
70
9
57.7
30.5
22.7
4.5
1135
5 x 11.7 = [58.5] 6
4.5
27
31
4582
69.5
768
6
9
CT Select
EM -
SB3
2 EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013
EM-SB3/0/485/CT Data Sheet
DiSPlay ElEMEnTS
CT Select
10 imp/kWh only for standard version
T1 total Indicates total consumption T1 part Indicates partial consumption. This
value can be reset CT Indicates the setting for the current
transformer ratio Select When bridge Z1-Z2 is open, the
transformer ratio can be adjusted under menu item: Select
P (kW) Indicates the instantaneous output per phase or for all phases
U (V) Indicates voltage per phasei (a) Indicates current per phase10 imp/kWh Pulsates according to the amount of
used power. kWh Indicates the unit kWh for display of
consumption (only for standard version)l1 / l2 / l3 Whenever the display shows P, U, I or
Error, the corresponding phase will be indicated.
Error When phase is absent or current direction is wrong. The corresponding phase will also be indicated.
FUnCTionaliTyError DiSPlay
Example: Connection error at L3
CT Select
10
Example: Connection error at L1 and L3
CT Select
10
EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 3
Data Sheet EM-SB3/0/485/CT
MEnU To DiSPlay ThE ValUES on ThE lCD
kWhkWhkWhkWhEM -
SB3
Cla
ss B
kWhkWhkWhkWhEM -
SB3
Cla
ss B
> 3 s
> 20 s
access control
presence
alarming
energy- management
combined heat and power station
protocol (VISI+)
energy
lift
cooling
heating
ventilation
temperature
setpoint
lighting
shade control
sanitation
sheduler (VISI+)
trending
remote alarming (VISI+)
visualization (VISI+)
building
traffic control
water treatment
IT / Data
Logistic system
tele- communication
graphic editor (VISI+)
kWhkWhkWhkWhEM -
SB30
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB30
Cla
ss B
kWhkWhkWhkWh
CT Select
EM
- SB
3C
lass
B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
> 3 s
> 3 skWhkWhkWhkWh
CT Select
EM -
SB30
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB30
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB30
0C
lass
B
5:5 50:5 100:5 150:5 200:5 250:5 300:5 400:5 500:5 600:5 750:5 1000:5 1250:5 1500:5
kWhkWhkWhkWh
CT Select
EM -
SB30
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB30
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB30
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB3
Cla
ss B
kWhkWhkWhkWh
CT Select
EM -
SB30
Cla
ss B
Start
Start
T1 total
T1 partial (T1 part)
Ratio Current Transformer (CT)
Instan. Power (P)
Voltage (U)
Current (I)
Start
remove bridge E1-E2
rest
ore
brid
ge E
1-E
2
4 EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013
EM-SB3/0/485/CT Data Sheet
MoDBUS
See Specification section, MODBUS
▪ The Interface works only if the Phase 1 is connected. ▪ The communication is ready 30 s after the Power On. ▪ Refresh Time for the Data is 10 s. Therefore the delay between reads of the same Data should be at least 10 s. ▪ The use of Energy meters in Bus with intensive communication can increase the data refresh time. ▪ 247 Devices can be connected to the MODBUS. Over 128 Devices, a repeater should be used. ▪ The Interface does not have a terminal resistor, this should be provided external. ▪ For the following transmission rate changes a restart of the counter is necessary: 1k2 to 57k6, 1k2 to 115k2 and 2k4 to115k2 bps. ▪ For a description of the used Registers please look at the Register Page.
Data transmission
▪ Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized. ▪ Up to 20 Registers can be read at a time. ▪ The device supports broadcast messages. ▪ In accordance with the MODBUS protocol, a register R is numbered as R - 1 when transmitted. ▪ The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission rate, etc.)
Exception responses
▪ ILLEGAL FUNCTION [01]: The function code is not implemented. ▪ ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range or more than 20 registers have been requested.
▪ ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.
Change the MoDBUS address direct on device
▪ To modify the MODBUS address, press 3 sec on ► touch ▪ In menu, ▼ increase address by 10, ► increase by 1 ▪ Once the address is selected wait for the root menu to come back
rEgiSTErS
For double registers (4 – 5, 16 – 17, 28 – 29, 30 – 31) the high register is sent first (big_Endian).
The Partial counter (30 – 31) can be resetted by writing 0 in both registers in the same message
r read Write Description Unit1 X Firmware-Version Ex: 11 =FW 1.12 X MODBUS com. Number of supported registers Will give 523 X MODBUS com. Number of supported flags Will give 04–5 X Baudrate Ex: Baudrate High = 1 Baudrate Low = 49664
1 × 65536 + 49664 = 115’200 bps6 X Not Used Will give 07 X Type / ASN function Will give «AW»8 X Type / ASN function Will give «D3»9 X Type / ASN function Will give «D5»10 X Type / ASN function Will give «FW»11 X Type / ASN function Will give «00»12 X Type / ASN function Will give «C»13 X Type / ASN function Will give « »14 X Type / ASN function Will give « »15 X HW vers. Modif. Ex: 11 =HW 1.116–17 X Serial number Unique 32 bit serial number18 X Not Used Will give 019 X Not Used Will give 020 X Not Used Will give 021 X Not Used Will give 022 X Status / Protect 0 = no Problem
1 = problem with last communication request23 X MODBUS Timeout ms24 X X1) MODBUS Address Range 1 to 247
EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 5
Data Sheet EM-SB3/0/485/CT
r read Write Description Unit25 X Error register 0 : No error
1 : Error Phase 12 : Error Phase 23 : Error Phase 1 and 24 : Error Phase 35 : Error Phase 1 and 36 : Error Phase 2 and 37 : Error Phase 1, 2 and 3
26 X Current Transformer Ratio Ex: Transformer 100 / 5 give 2027 X Not Used Will give 028–29 X WT1 total High
Counter Energy Total Tariff 1 High10–1 kWh (multiplier 0,1)Ex: WT1 total High = 13 WT1 total Low = 6038313 × 65536 + 60383 = 912351 = 91235.1 kWh
30–31 X X WT1 partialCounter Energy Partial Tariff 1
10–1 kWh (multiplier 0,1)Ex: WT1 partial High = 13 WT1 partial Low = 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh
32 X Not Used Will give 033 X Not Used Will give 034 X Not Used Will give 035 X Not Used Will give 036 X U(V)RMS phase 1
Effective Voltage of Phase 1VEx: 230 = 230 V
37 X IRMS phase 1Effective Current of Phase 1
A / Except 5/5 = 10–1 AEx: 314 = 314 A
38 X PRMS phase 1Effective active Power of Phase 1
10–1 kW (multiplier 0,1)Ex: 1545 = 154,5 kW
39 X QRMS phase 1Effective reactive Power of Phase 1
10–1 kvar (multiplier 0,1)Ex: 1545 = 154,5 kvar
40 X cos phi phase 1 10–2 (multiplier 0,01)Ex: 67 = 0,67
41 X U(V)RMS phase 2Effective Voltage of Phase 2
VEx: 230 = 230 V
42 X IRMS phase 2Effective Current of Phase 2
A / Except 5/5 = 10–1 AEx: 314 = 314 A
43 X PRMS phase 2Effective active Power of Phase 2
10–1 kW (multiplier 0,1)Ex: 1545 = 154,5 kW
44 X QRMS phase 2Effective reactive Power of Phase 2
10–1 kvar (multiplier 0,1)Ex: 1545 = 154,5 kvar
45 X cos phi phase 2 10–2 (multiplier 0,01)Ex: 67 = 0,67
46 X U(V)RMS phase 3Effective Voltage of Phase 3
VEx: 230 = 230 V
47 X IRMS phase 3Effective Current of Phase 3
A / Except 5/5 = 10–1 AEx: 314 = 314 A
48 X PRMS phase 3Effective active Power of Phase 3
10–1 kW (multiplier 0,1)Ex: 1545 = 154,5 kW
49 X QRMS phase 3Effective reactive Power of Phase 3
10–1 kvar (multiplier 0,1)Ex: 1545 = 154,5 kvar
50 X cos phi phase 3 10–2 (multiplier 0,01)Ex: 67 = 0,67
51 X PRMS totalEffective active Power of all phases
10–1 kW (multiplier 0,1)Ex: 1545 = 15,45 kW
52 X QRMS totalEffective reactive power of all phases
10–1 kvar (multiplier 0,1)Ex: 1545 = 15,45 kvar
1) The MODBUS Address register is not writable with a broadcast message.
6 EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013
EM-SB3/0/485/CT Data Sheet
FiElD MainTEnanCEThe EM-SB3/0/485/CT requires virtually no routine maintenance. The unit should be cleaned with a cloth moistened with water in order to avoid buildup of dust or other contaminents. Disconnect power before carrying out any cleaning.
DiSPoSalCOSHH (Control of Substances Hazardous to Health - UK Government Regulations 2002) ASSESSMENT FOR DISPOSAL OF EM-SB3/0/485/CT .
RECYCLING .
All plastic and metal parts are recyclable. The printed circuit board may be sent to any PCB recovery contractor to recover some of the components for any metals such as gold and silver.
WEEE Directive:
At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.
Do not dispose of with normal household waste.Do not burn.
CoMPaTiBiliTy The meter is compatible with TOPS, TONN, and IQ3.../.../XNC/SER/.. with a MODBUS driver.
orDEr CoDESEM-SB3/0/485/CT :Energy meter for use with current transformers and with MODBUS interfaceaCCa/EM-SB3/CoVEr :Cover to provide lead seal for energy meter
EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 7
Data Sheet EM-SB3/0/485/CT
inSTallaTion
The meter must be mounted inside a panel. See EM-SB3/0/485/CT Installation Instructions TG201307INT for further details.
ConnECTionS
+(A), /D
-(B), D
L1
L2
L3
N
MODBUS over RS485 serial line
max. 1200 m
Fuse: T 250 mA (3x)
The secondary, mains current transformer connection has to be connected to the phase to be measured and therefore the transformer need not be grounded.
3 x
230/
400
VAC
8 EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013
EM-SB3/0/485/CT Data Sheet
Please send any comments about this or any other Trend technical publication to [email protected]
© 2013 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative.
Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.
Trend Control Systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control System USa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com
SPECiFiCaTionMETEr
Precision class :B according to EN50470-3, class 1 according to IEC62053-21
Operating voltage :3 × 230 / 400 VAC, 50 Hz, Tolerance –20% /+15%
Power consumption :Active 0.4 W per phaseCounting range :00,000.00 to 99,999.99 1,000.000 to 9,999.999Display :LCD backlit, digits 6 mm high
MoUnTing
Mounting :On 35 mm rail, according to EN60715TH35
Terminal connectionsmain circuit :Conductor cross-section 1.5 to16 mm2,
screwdriver Pozidrive no. 1, slot no. 2, torque 1.5 to 2 Nm
control circuit :Conductor cross-section max. 2.5 mm2, screwdriver Pozidrive no. 0, slot no. 2, torque 0.8 Nm
Insulation characteristics :4 kV / 50 Hz test according to VDE0435 for energy meters
6 kV 1.2 / 50 µs Surge according to IEC255-4
2 kV / 50 Hz test according to VDE0435 for interface
Device protection class IIAmbient temperature :–10 °C to +55 °CStorage temperature :–30°C to +85 °CRelative humidity :95 % at 25 °C to +40 °C, without
condensation EMC/interference immunity :Surge according to IEC61000-
4-5: on main circuit 4 kV, at MODBUS 1 kV
Burst according to IEC61000-4-4: at main circuit 4 kV, at MODBUS interface 1 kV
ESD according to IEC61000-4-2: Contact 8 kV, air 15 kV
CT MEaSUrEMEnT
CT measurement :5 A to 1500 AReference/max. current :Iref = 5 A, Imax = 6 AStarting/minimum current :Ist = 10 mA, Imin = 0.05 AConverter ratio :5 : 5 50 : 5 100 : 5 150 : 5 200 : 5 250 : 5 300 : 5 400 : 5 500 : 5 600 : 5 750 : 5 1000 : 5 1250 : 5 1500 : 5 Pulses per kWh on display :10 Imp/kWh
MoDBUS
Protocol :MODBUS RTU according to IDA specification
Bus system :RS485 Serial lineTransmission rate (bps) :1k2, 2k4, 4k8, 9k6, 19k2, 38k4, 57k6,
115k2. The transmission baud rate is automatically detected
Bit settings :8 Data bits, Even parity, 1 Stop bitBus cable :Twisted, shielded, 2 × 0.5 mm2, 1200 m
maximum.Response time (to system response) :typ. 5 character times,
maximum 60 ms