EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 1 Data Sheet EM-SB3/0/485/CT Energy Meter EM-SB3/0/485/CT Description Energy meters with an integrated serial RS485 MODBUS interface allow direct reading of all relevant data, such as energy (total and partial), current and voltage, active and reactive power for the three phases. Main features 3-phase energy meter, 3 × 230 / 400 VAC 50 Hz Measurement through a current transformer up to 1500 A Display of active power, voltage and current for each phase Display of active power for all phases MODBUS RTU Interface for up to 247 meters Reactive power for every and/or all phases available through MODBUS interface 7-digits display Lead seal possible with cover accessory (ACCEM- SB3COVER) Accuracy class B according to EN50470-3, accuracy class 1 according to IEC62053-21 1 or 2 tarrifs. Physical ( dimensions in mm) 82 6 70 7 68 69,5 62 70 9 57.7 30.5 22.7 4.5 11 35 5 x 11.7 = [58.5] 6 4.5 27 31 45 82 69.5 7 68 6 9 CT Select EM - SB3

EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

  • Upload
    others

  • View
    18

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 1

Data Sheet

EM-SB3/0/485/CTEnergy Meter

EM-SB3/0/485/CT

Description

Energy meters with an integrated serial RS485 MODBUS interface allow direct reading of all relevant data, such as energy (total and partial), current and voltage, active and reactive power for the three phases.

Main features

▪ 3-phase energy meter, 3 × 230 / 400 VAC 50 Hz ▪ Measurement through a current transformer up to 1500 A ▪ Display of active power, voltage and current for each phase ▪ Display of active power for all phases ▪ MODBUS RTU Interface for up to 247 meters ▪ Reactive power for every and/or all phases available through MODBUS interface

▪ 7-digits display ▪ Lead seal possible with cover accessory (ACCEM-SB3COVER)

▪ Accuracy class B according to EN50470-3, accuracy class 1 according to IEC62053-21

▪ 1 or 2 tarrifs.

Physical (dimensions in mm)

82

27

62

4,5

6

70

65 x 11,7 = (58,5)

768

4,5930,5 9

11

57,7

22,7

35

69,5

3162

70

9

57.7

30.5

22.7

4.5

1135

5 x 11.7 = [58.5] 6

4.5

27

31

4582

69.5

768

6

9

CT Select

EM -

SB3

Page 2: EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

2 EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013

EM-SB3/0/485/CT Data Sheet

DiSPlay ElEMEnTS

CT Select

10 imp/kWh only for standard version

T1 total Indicates total consumption T1 part Indicates partial consumption. This

value can be reset CT Indicates the setting for the current

transformer ratio Select When bridge Z1-Z2 is open, the

transformer ratio can be adjusted under menu item: Select

P (kW) Indicates the instantaneous output per phase or for all phases

U (V) Indicates voltage per phasei (a) Indicates current per phase10 imp/kWh Pulsates according to the amount of

used power. kWh Indicates the unit kWh for display of

consumption (only for standard version)l1 / l2 / l3 Whenever the display shows P, U, I or

Error, the corresponding phase will be indicated.

Error When phase is absent or current direction is wrong. The corresponding phase will also be indicated.

FUnCTionaliTyError DiSPlay

Example: Connection error at L3

CT Select

10

Example: Connection error at L1 and L3

CT Select

10

Page 3: EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 3

Data Sheet EM-SB3/0/485/CT

MEnU To DiSPlay ThE ValUES on ThE lCD

kWhkWhkWhkWhEM -

SB3

Cla

ss B

kWhkWhkWhkWhEM -

SB3

Cla

ss B

> 3 s

> 20 s

access control

presence

alarming

energy- management

combined heat and power station

protocol (VISI+)

energy

lift

cooling

heating

ventilation

temperature

setpoint

lighting

shade control

sanitation

sheduler (VISI+)

trending

remote alarming (VISI+)

visualization (VISI+)

building

traffic control

water treatment

IT / Data

Logistic system

tele- communication

graphic editor (VISI+)

kWhkWhkWhkWhEM -

SB30

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB30

Cla

ss B

kWhkWhkWhkWh

CT Select

EM

- SB

3C

lass

B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

> 3 s

> 3 skWhkWhkWhkWh

CT Select

EM -

SB30

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB30

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB30

0C

lass

B

5:5 50:5 100:5 150:5 200:5 250:5 300:5 400:5 500:5 600:5 750:5 1000:5 1250:5 1500:5

kWhkWhkWhkWh

CT Select

EM -

SB30

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB30

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB30

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB3

Cla

ss B

kWhkWhkWhkWh

CT Select

EM -

SB30

Cla

ss B

Start

Start

T1 total

T1 partial (T1 part)

Ratio Current Transformer (CT)

Instan. Power (P)

Voltage (U)

Current (I)

Start

remove bridge E1-E2

rest

ore

brid

ge E

1-E

2

Page 4: EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

4 EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013

EM-SB3/0/485/CT Data Sheet

MoDBUS

See Specification section, MODBUS

▪ The Interface works only if the Phase 1 is connected. ▪ The communication is ready 30 s after the Power On. ▪ Refresh Time for the Data is 10 s. Therefore the delay between reads of the same Data should be at least 10 s. ▪ The use of Energy meters in Bus with intensive communication can increase the data refresh time. ▪ 247 Devices can be connected to the MODBUS. Over 128 Devices, a repeater should be used. ▪ The Interface does not have a terminal resistor, this should be provided external. ▪ For the following transmission rate changes a restart of the counter is necessary: 1k2 to 57k6, 1k2 to 115k2 and 2k4 to115k2 bps. ▪ For a description of the used Registers please look at the Register Page.

Data transmission

▪ Only «Read Holding Registers [03]/ Write Multiple Registers [16]» instructions are recognized. ▪ Up to 20 Registers can be read at a time. ▪ The device supports broadcast messages. ▪ In accordance with the MODBUS protocol, a register R is numbered as R - 1 when transmitted. ▪ The device has a voltage monitoring system. In case of voltage loss, registers are stored in EEPROM (transmission rate, etc.)

Exception responses

▪ ILLEGAL FUNCTION [01]: The function code is not implemented. ▪ ILLEGAL DATA ADDRESS [02]: The address of some requested registers is out of range or more than 20 registers have been requested.

▪ ILLEGAL DATA VALUE [03]: The value in the data field is invalid for the referenced register.

Change the MoDBUS address direct on device

▪ To modify the MODBUS address, press 3 sec on ► touch ▪ In menu, ▼ increase address by 10, ► increase by 1 ▪ Once the address is selected wait for the root menu to come back

rEgiSTErS

For double registers (4 – 5, 16 – 17, 28 – 29, 30 – 31) the high register is sent first (big_Endian).

The Partial counter (30 – 31) can be resetted by writing 0 in both registers in the same message

r read Write Description Unit1 X Firmware-Version Ex: 11 =FW 1.12 X MODBUS com. Number of supported registers Will give 523 X MODBUS com. Number of supported flags Will give 04–5 X Baudrate Ex: Baudrate High = 1 Baudrate Low = 49664

1 × 65536 + 49664 = 115’200 bps6 X Not Used Will give 07 X Type / ASN function Will give «AW»8 X Type / ASN function Will give «D3»9 X Type / ASN function Will give «D5»10 X Type / ASN function Will give «FW»11 X Type / ASN function Will give «00»12 X Type / ASN function Will give «C»13 X Type / ASN function Will give « »14 X Type / ASN function Will give « »15 X HW vers. Modif. Ex: 11 =HW 1.116–17 X Serial number Unique 32 bit serial number18 X Not Used Will give 019 X Not Used Will give 020 X Not Used Will give 021 X Not Used Will give 022 X Status / Protect 0 = no Problem

1 = problem with last communication request23 X MODBUS Timeout ms24 X X1) MODBUS Address Range 1 to 247

Page 5: EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 5

Data Sheet EM-SB3/0/485/CT

r read Write Description Unit25 X Error register 0 : No error

1 : Error Phase 12 : Error Phase 23 : Error Phase 1 and 24 : Error Phase 35 : Error Phase 1 and 36 : Error Phase 2 and 37 : Error Phase 1, 2 and 3

26 X Current Transformer Ratio Ex: Transformer 100 / 5 give 2027 X Not Used Will give 028–29 X WT1 total High

Counter Energy Total Tariff 1 High10–1 kWh (multiplier 0,1)Ex: WT1 total High = 13 WT1 total Low = 6038313 × 65536 + 60383 = 912351 = 91235.1 kWh

30–31 X X WT1 partialCounter Energy Partial Tariff 1

10–1 kWh (multiplier 0,1)Ex: WT1 partial High = 13 WT1 partial Low = 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh

32 X Not Used Will give 033 X Not Used Will give 034 X Not Used Will give 035 X Not Used Will give 036 X U(V)RMS phase 1

Effective Voltage of Phase 1VEx: 230 = 230 V

37 X IRMS phase 1Effective Current of Phase 1

A / Except 5/5 = 10–1 AEx: 314 = 314 A

38 X PRMS phase 1Effective active Power of Phase 1

10–1 kW (multiplier 0,1)Ex: 1545 = 154,5 kW

39 X QRMS phase 1Effective reactive Power of Phase 1

10–1 kvar (multiplier 0,1)Ex: 1545 = 154,5 kvar

40 X cos phi phase 1 10–2 (multiplier 0,01)Ex: 67 = 0,67

41 X U(V)RMS phase 2Effective Voltage of Phase 2

VEx: 230 = 230 V

42 X IRMS phase 2Effective Current of Phase 2

A / Except 5/5 = 10–1 AEx: 314 = 314 A

43 X PRMS phase 2Effective active Power of Phase 2

10–1 kW (multiplier 0,1)Ex: 1545 = 154,5 kW

44 X QRMS phase 2Effective reactive Power of Phase 2

10–1 kvar (multiplier 0,1)Ex: 1545 = 154,5 kvar

45 X cos phi phase 2 10–2 (multiplier 0,01)Ex: 67 = 0,67

46 X U(V)RMS phase 3Effective Voltage of Phase 3

VEx: 230 = 230 V

47 X IRMS phase 3Effective Current of Phase 3

A / Except 5/5 = 10–1 AEx: 314 = 314 A

48 X PRMS phase 3Effective active Power of Phase 3

10–1 kW (multiplier 0,1)Ex: 1545 = 154,5 kW

49 X QRMS phase 3Effective reactive Power of Phase 3

10–1 kvar (multiplier 0,1)Ex: 1545 = 154,5 kvar

50 X cos phi phase 3 10–2 (multiplier 0,01)Ex: 67 = 0,67

51 X PRMS totalEffective active Power of all phases

10–1 kW (multiplier 0,1)Ex: 1545 = 15,45 kW

52 X QRMS totalEffective reactive power of all phases

10–1 kvar (multiplier 0,1)Ex: 1545 = 15,45 kvar

1) The MODBUS Address register is not writable with a broadcast message.

Page 6: EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

6 EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013

EM-SB3/0/485/CT Data Sheet

FiElD MainTEnanCEThe EM-SB3/0/485/CT requires virtually no routine maintenance. The unit should be cleaned with a cloth moistened with water in order to avoid buildup of dust or other contaminents. Disconnect power before carrying out any cleaning.

DiSPoSalCOSHH (Control of Substances Hazardous to Health - UK Government Regulations 2002) ASSESSMENT FOR DISPOSAL OF EM-SB3/0/485/CT .

RECYCLING .

All plastic and metal parts are recyclable. The printed circuit board may be sent to any PCB recovery contractor to recover some of the components for any metals such as gold and silver.

WEEE Directive:

At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre.

Do not dispose of with normal household waste.Do not burn.

CoMPaTiBiliTy The meter is compatible with TOPS, TONN, and IQ3.../.../XNC/SER/.. with a MODBUS driver.

orDEr CoDESEM-SB3/0/485/CT :Energy meter for use with current transformers and with MODBUS interfaceaCCa/EM-SB3/CoVEr :Cover to provide lead seal for energy meter

Page 7: EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013 7

Data Sheet EM-SB3/0/485/CT

inSTallaTion

The meter must be mounted inside a panel. See EM-SB3/0/485/CT Installation Instructions TG201307INT for further details.

ConnECTionS

+(A), /D

-(B), D

L1

L2

L3

N

MODBUS over RS485 serial line

max. 1200 m

Fuse: T 250 mA (3x)

The secondary, mains current transformer connection has to be connected to the phase to be measured and therefore the transformer need not be grounded.

3 x

230/

400

VAC

Page 8: EM-SB3/0/485/CT Energy Meter Data Sheet - Honeywell · 2020. 3. 13. · 60383 13 × 65536 + 60383 = 912351 = 91235.1 kWh 30–31 X X WT1 partial Counter Energy Partial Tariff 1 10–1

8 EM-SB3/0/485/CT Energy Meter Data Sheet TA201311 Issue 2, 31-Jul-2013

EM-SB3/0/485/CT Data Sheet

Please send any comments about this or any other Trend technical publication to [email protected]

© 2013 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division of Honeywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative.

Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems limitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.comTrend Control System USa6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com

SPECiFiCaTionMETEr

Precision class :B according to EN50470-3, class 1 according to IEC62053-21

Operating voltage :3 × 230 / 400 VAC, 50 Hz, Tolerance –20% /+15%

Power consumption :Active 0.4 W per phaseCounting range :00,000.00 to 99,999.99 1,000.000 to 9,999.999Display :LCD backlit, digits 6 mm high

MoUnTing

Mounting :On 35 mm rail, according to EN60715TH35

Terminal connectionsmain circuit :Conductor cross-section 1.5 to16 mm2,

screwdriver Pozidrive no. 1, slot no. 2, torque 1.5 to 2 Nm

control circuit :Conductor cross-section max. 2.5 mm2, screwdriver Pozidrive no. 0, slot no. 2, torque 0.8 Nm

Insulation characteristics :4 kV / 50 Hz test according to VDE0435 for energy meters

6 kV 1.2 / 50 µs Surge according to IEC255-4

2 kV / 50 Hz test according to VDE0435 for interface

Device protection class IIAmbient temperature :–10 °C to +55 °CStorage temperature :–30°C to +85 °CRelative humidity :95 % at 25 °C to +40 °C, without

condensation EMC/interference immunity :Surge according to IEC61000-

4-5: on main circuit 4 kV, at MODBUS 1 kV

Burst according to IEC61000-4-4: at main circuit 4 kV, at MODBUS interface 1 kV

ESD according to IEC61000-4-2: Contact 8 kV, air 15 kV

CT MEaSUrEMEnT

CT measurement :5 A to 1500 AReference/max. current :Iref = 5 A, Imax = 6 AStarting/minimum current :Ist = 10 mA, Imin = 0.05 AConverter ratio :5 : 5 50 : 5 100 : 5 150 : 5 200 : 5 250 : 5 300 : 5 400 : 5 500 : 5 600 : 5 750 : 5 1000 : 5 1250 : 5 1500 : 5 Pulses per kWh on display :10 Imp/kWh

MoDBUS

Protocol :MODBUS RTU according to IDA specification

Bus system :RS485 Serial lineTransmission rate (bps) :1k2, 2k4, 4k8, 9k6, 19k2, 38k4, 57k6,

115k2. The transmission baud rate is automatically detected

Bit settings :8 Data bits, Even parity, 1 Stop bitBus cable :Twisted, shielded, 2 × 0.5 mm2, 1200 m

maximum.Response time (to system response) :typ. 5 character times,

maximum 60 ms