15
1000 Top Sheet Cover Width Brackets Typically @ 1167 166.7 32 Varies - See Table Varies - See Table Please Note: System is fire rated using Knauf Factoryclad 40 ECOSE insulation of minimum thickness 80mm with steel outer sheet only, to achieve 120 minutes Integrity, 15 minutes (min) Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and the wall is 1M or more from the boundary. System can be fire rated using Rockwool insulation of minimum thickness 120mm with steel outer sheet only, with liner stitched at 300mm centres, to achieve 120 minutes Integrity, 30 minutes (min) Insulation. Ensure roll edges are lapped/butted to ensure no gaps. * * * * * *Fixings with an asterix are required on sheet ends and end laps only. * * Elite System 51 Bracket Height Insulation Thickness Insulation Value Overall System Depth U Value at 1.8M Centres 120mm 140mm 150mm 160mm 180mm 200mm 220mm 120mm 140mm 150mm*/160mm 160mm 180mm 200mm 220mm 0.040 0.040 0.040 0.040 0.040 0.040 0.040 153mm 173mm 183mm 193mm 213mm 233mm 253mm 0.35 0.30 0.28 0.27 0.24 0.21 0.20 170mm 180mm 0.040 203mm 0.25 240mm 260mm 280mm 0.040 0.040 0.040 273mm 293mm 313mm 300mm 0.040 333mm * Only available in Rockwool Cladding Roll 240mm 260mm 280mm 300mm 0.18 0.17 0.15 0.14 TITLE: Elite System 51 DWG NO: E51 DRAWN: CD DATE: Jan 2020 CHECK: MP SCALE: NTS ELITE SYSTEMS To be read in conjunction with Elite System specification documents This draft drawing has been supplied by Euroclad Group Ltd for the purpose of guidance free of charge. It is a suggested typical detail and as such should not be assumed suitable for any specific project or application. No responsibility is assumed for errors or misinterpretations resulting from the information contained in the drawing. Details are for illustration only and no liability is accepted. We reserve the right to change the details without notice.The drawing is copyright, it remains our property. Fax: +44 (0)2922 010 122 www.euroclad.com Tel: +44 (0)2922 010 101 1 of 15

Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

1000 Top Sheet Cover Width

Brackets Typically @ 1167

166.7

32

Varies - See Table

Varies - See Table

Please Note:

System is fire rated using Knauf Factoryclad 40 ECOSE insulation of minimum thickness 80mm with steel outer sheet only, to achieve 120 minutes Integrity, 15 minutes

(min) Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and the wall is 1M or more

from the boundary.

System can be fire rated using Rockwool insulation of minimum thickness 120mm with steel outer sheet only, with liner stitched at 300mm centres, to achieve 120

minutes Integrity, 30 minutes (min) Insulation.

Ensure roll edges are lapped/butted to ensure no gaps.

** * *

*

*Fixings with an asterix are required on sheet ends and end laps only.

*

*

Elite System 51

Bracket Height

Insulation

Thickness

Insulation Value

Overall System

Depth

U Value at 1.8M

Centres

120mm

140mm

150mm

160mm

180mm

200mm

220mm

120mm

140mm

150mm*/160mm

160mm

180mm

200mm

220mm

0.040

0.040

0.040

0.040

0.040

0.040

0.040

153mm

173mm

183mm

193mm

213mm

233mm

253mm

0.35

0.30

0.28

0.27

0.24

0.21

0.20

170mm 180mm 0.040 203mm 0.25

240mm

260mm

280mm

0.040

0.040

0.040

273mm

293mm

313mm

300mm 0.040 333mm

* Only available in Rockwool Cladding Roll

240mm

260mm

280mm

300mm

0.18

0.17

0.15

0.14

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

1 of 15

Page 2: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

Min 60

ELITE SYSTEM 51 SIDE LAP DETAIL ELITE SYSTEM 51 END LAP DETAIL

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Euroclad EC 32-167-1000

Wall 32_6Rev 0.5mm steel

50mm x 1mm butyl sealing tape

Quattro bar & bracket to required

depth typically @ 1.167m centres

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Quattro bar & bracket

4mm Bead class A

butyl sealant

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

100

COLOUR SIDE

COLOUR SIDE

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel Side lap

Euroclad EC 32-167-1000

Wall 32_6Rev

0.5mm steel Side lap

STANDARD LAP DETAIL STANDARD LAP DETAIL

0.040 Quilt insulation

Please Note:

System is fire rated using Knauf Factoryclad 40 ECOSE insulation of minimum thickness

80mm with steel outer sheet only, to achieve 120 minutes Integrity, 15 minutes (min)

Insulation which meets the requirements of Building Regulations Part B for external walls

where fire attack is from inside the building and the wall is 1M or more from the boundary.

System can be fire rated using Rockwool insulation of minimum thickness 120mm with

steel outer sheet only, with liner stitched at 300mm centres, to achieve 120 minutes

Integrity, 30 minutes (min) Insulation.

Ensure roll edges are lapped/butted to ensure no gaps.

On intermediate supports fixing at each

profile side lap and subsequently in

alternate troughs. Fix all troughs at

sheet ends & end laps

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

2 of 15

Page 3: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

23

94

1

2

9

°

73

32

167 2321

3

9

5

3

9

1000

COLOUR SIDE

COLOUR SIDE

COLOUR SIDE

COLOUR SIDE

167167

104

19

R

4

22

2

8

1

3

7

°

1

0

1000

18

EUROCLAD EC 19-167-1000 Liner 19_2L 0.4mm

LINER

EUROCLAD EC 32-167-1000 Wall 32_6Rev 0.5mm

EXTERNAL SHEET

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

3 of 15

Page 4: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

40

Brackets less than 260mm require

2 fixings diagonally opposite.

Brackets 260mm or more require

4 fixings.

< 260mm

≥ 260mm

40

33

34

60

59

VARIES D

EPEN

DIN

G

ON

BRACKET H

EIG

HT

VARIES D

EPEN

DIN

G

ON

BRACKET H

EIG

HT

SIDE ELEVATION

Maximum bar cantilever at free

ends is 300mm.

Spigot can fall anywhere between

two brackets.

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

4 of 15

Page 5: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

9 x 3mm Class A Butyl Sealant

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Liner flashing sealed to masonry

Class A Butyl Sealant to thickness

required to provide adequate air

sealing to masonry wall.

Quattro Bracket to required

depth typically @ 1167mm centres

Quattro Spacer Rail

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

Class A Butyl Sealant to thickness

required to provide adequate air

sealing to masonry wall.

Flashing stitched at max 450mm centres

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

5 of 15

Page 6: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Quattro Bracket to required

depth typically @ 1167mm centres

Fixings in alternate troughs on intermediate

supports and in all troughs at sheet ends & end laps

9x3mm Mastic Sealant

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Internal Flashing fixed and sealed

to internal elements

9x3mm Mastic Sealant

Door detail by others

External Flashing

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

Timber Packer

Sealant

9 x 3mm Class A Butyl Sealant

Flashing stitched at max 450mm centres

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

6 of 15

Page 7: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

External flashing

9 x 3mm Class A Butyl Sealant

Quattro Bracket to required

depth typically @ 1167mm centres

Quattro Spacer Rail

9 x 3mm Class A Butyl Sealant

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Quattro Spacer Rail

Internal flashing fixed and sealed

to provide air tightness

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

9x3mm Mastic Sealant

Flashing stitched at max 450mm centres

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

7 of 15

Page 8: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Drip Flashing

Drainage Point

Quattro Bracket to required

depth typically @ 1167mm centres

Large amount of sealant to make

allowance for imperfection in concrete and

ensure good airtightness. Seal may be achieved

at flashing or structural element such as ring beam,

depending on project specific details.

Internal Flashing and profile filler sealed to liner

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

Profile Filler

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

8 of 15

Page 9: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

9 x 3mm Class A Butyl Sealant

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Quattro Bracket to required

depth typically @ 1167mm centres

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Internal flashing fixed and sealed

to provide air tightness

9x3mm Mastic Sealant

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

External Flashing

Stitched at max 450mm centres

9x3mm Mastic Sealant

Quattro Bracket to required

depth typically @ 1m centres

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

9 of 15

Page 10: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

Large amount of sealant to make

allowance for imperfection in concrete and

ensure good airtightness. Seal may be achieved

at flashing or structural element such as ring beam,

depending on project specific details.

Closure Flashing

Quattro Bracket to required

depth typically @ 1167mm centres

Closure Flashing fixed and profile filler

sealed to liner to provide air tightness

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Profile Filler

Drip Flashing

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

10 of 15

Page 11: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Quattro Bracket to required

depth typically @ 1167mm centres

Fixings in alternate troughs on intermediate

supports and in all troughs at sheet ends & end laps

9x3mm Mastic Sealant

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Internal Flashing fixed and sealed

to internal elements

9x3mm Mastic Sealant

Vehicle Access Door Detail by others

External Flashing

Packer by others

Sealant

9 x 3mm Class A Butyl Sealant

Flashing stitched at max 450mm centres

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

11 of 15

Page 12: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

40

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

Profile Filler

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Sealant

Drip Flashing

Closure Flashing

Liner Flashing fillers fixed and sealed to liners to

provide air tightness and vapour control

Quattro Bracket to required

depth typically @ 1167mm centres

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Packer by others

Vehicle Access Door Detail by others

Internal Flashing fixed and sealed

to internal elements

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

12 of 15

Page 13: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

40

Profile Filler

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Liner Flashing fillers fixed and sealed to liners to

provide air tightness and vapour control

Window Detail by others

Internal Flashing fixed and sealed

to internal elements

Sealant

Packer by others

Quattro Bracket to required

depth typically @ 1167mm centres

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

13 of 15

Page 14: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

40

Internal Flashing fixed and sealed

to internal elements

Quattro Bracket to required

depth typically @ 1167mm centres

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Packer by others

Window Detail by others

Profile Filler

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Sealant

Drip Flashing

Closure Flashing

Liner Flashing fillers fixed and sealed to liners to

provide air tightness and vapour control

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

14 of 15

Page 15: Elite System 51 - Euroclad Ltd€¦ · Insulation which meets the requirements of Building Regulations Part B for external walls where fire attack is from inside the building and

Euroclad EC 32-167-1000 Wall 32_6Rev

0.5mm steel

Quattro Bracket to required

depth typically @ 1167mm centres

Fixings in alternate troughs on intermediate

supports and in all troughs at sheet ends & end laps

9x3mm Mastic Sealant

Euroclad EC 19-167-1000 Liner

19_2L 0.4mm Steel

Internal Flashing fixed and sealed

to internal elements

9x3mm Mastic Sealant

Window detail by others

External Flashing

Timber Packer

Sealant

9 x 3mm Class A Butyl Sealant

Flashing stitched at max 450mm centres

EUROCLAD ELITE SYSTEM 51 WALL CONSTRUCTION

Insulation excluded for clarity

A range of mineral & glass wool insulations are available for different requirements

TITLE: Elite System 51

DWG NO: E51

DRAWN: CD

DATE: Jan 2020

CHECK: MP

SCALE: NTS

ELITE SYSTEMS

To be read in conjunction with

Elite System specification

documents

This draft drawing has been

supplied by Euroclad Group Ltd

for the purpose of guidance free

of charge. It is a suggested

typical detail and as such should

not be assumed suitable for any

specific project or application.

No responsibility is assumed for

errors or misinterpretations

resulting from the information

contained in the drawing. Details

are for illustration only and no

liability is accepted. We reserve

the right to change the details

without notice.The drawing is

copyright, it remains our

property.

Fax: +44 (0)2922 010 122

www.euroclad.com

Tel: +44 (0)2922 010 101

15 of 15