BT10C001GB-02 ® TECHNICAL BULLETIN ELFOENERGY LARGE 2 HIGH EFFICIENCY AIR-COOLED LIQUID CHILLER FOR OUTDOOR INSTALLATION WSAT-XEE SERIES Nominal cooling capacity from 97 to 218 kW ELFOEnergy LARGE 2 is a highly energy efficient liquid chiller which is equipped with Scroll compressors, large heat-exchange surfaces and electronically controlled fans. Thanks to its excellent partial-load performance, its ESEER seasonal efficiency is at the top of its category, enabling great savings on management costs over the entire annual cycle. Furthermore, the standard EXCELLENCE version is in energy efficiency Class A at full-load. ELFOEnergy LARGE 2 is also available in the PREMIUM compact version, which has been optimized to reduce on the initial investment. It can be equipped with several built-in accessories, like pump groups, an energy recovery device and an inertial buffer. ELFOEnergy LARGE 2 is, therefore, the centralised solution for all applications which require high performance, working continuity and management costs reduction.

ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

BT10C001GB-02

® TECHNICAL BULLETIN

ELFOENERGY LARGE2

HIGH EFFICIENCY AIR-COOLED LIQUID CHILLER FOR OUTDOOR INSTALLATION WSAT-XEE SERIES Nominal cooling capacity from 97 to 218 kW

ELFOEnergy LARGE2 is a highly energy efficient liquid chiller which is equipped with Scroll

compressors, large heat-exchange surfaces and electronically controlled fans.

Thanks to its excellent partial-load performance, its ESEER seasonal efficiency is at the top of its

category, enabling great savings on management costs over the entire annual cycle. Furthermore, the

standard EXCELLENCE version is in energy efficiency Class A at full-load.

ELFOEnergy LARGE2 is also available in the PREMIUM compact version, which has been optimized

to reduce on the initial investment. It can be equipped with several built-in accessories, like pump

groups, an energy recovery device and an inertial buffer.

ELFOEnergy LARGE2 is, therefore, the centralised solution for all applications which require high

performance, working continuity and management costs reduction.

Page 2: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

2

®

BT10E005GB-02

ELFOENERGY LARGE2

COST OR RELIABILITY?

THE DILEMMA OF MODERN SYSTEM ENGINEERING APPLICATIONS

Air-conditioning systems in trade centres influence both the starting investment and monthly management costs, for the whole

of their working lives.

This theme is even more relevant in residential applications with centralised systems . Furthermore, maximum working

flexibility requirements should be added to that, in serving different users while avoiding wasting energy and thus, money.

Finally, there are several industrial applications which require chilled water as service fluid, process fluid or vector fluid for

operator comfort and for conserving goods and enabling cycles to function correctly.

Furthermore, in all these cases, the working reliability of the system is decisive.

THE HIGH EFFICIENCY HYDRONIC SYSTEMS ARE EXTREMELY VERSATILE, RELIABLE AND WIDESPREAD

CLIVET CHILLERS REDUCE CONSUMPTION

AND ARE COMPACT AND RELIABLE

Despite their apparently low costs, split, multi-split and VRF direct expansion systems have a lot of limits in these applications. For example, they require a separate system for primary air treatment. The pipes that contain the refrigerant cross the served rooms and therefore they are subject to restrictions and use limitations. They cannot operate in the freecooling mode, the high efficiency and convenient mode that allows energy savings. the hydronic systems are certainly more complete and versatile. They make it possible to adopt various types of terminals in the served environment, from fan coil units exposed or integrated in the furnishings, up to radiant or induction systems. They are also irreplaceable in the service and process industrial applications. The main component performances , like air-cooled liquid chiller, are checked and certificated by Eurovent.

With over twenty years of technological evolution, Clivet liquid

chillers and heat pumps represent the state of the art in

air-conditioning in residential, trade and industrial environments.

Their success is based on high energy efficiency, compactness

and management and maintenance simplicity, with wide versatility

in the choice of the most suitable model for the specific use.

Page 3: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

3

®

BT10E005GB-02

ELFOENERGY LARGE2

ELFOEnergy LARGE2 PROVIDES ALL CLIVET TECHNOLOGICAL

DEVELOPMENTS FOR THEIR MEDIUM CAPACITY HYDRONIC SYSTEMS

High-efficiency Scroll compressors, high-performance heat exchangers, electronically-controlled fans, completely automatic

functions: this is just is some of the technology available in ELFOEnergy LARGE2, in a range of models which are ideal for

trade, residential and industrial medium capacity air-conditioning.

COMPETITIVE ADVANTAGES

High efficiency all year round ELFOEnergy LARGE2 reduces the annual energy consumption thanks to its high partial load efficiency, or the more frequent operating conditions in the system life cycle. So the value of the building served increases. The main components are manufactured in large numbers on industrial scale, with the maximum structural reliability and spare parts availability series.

System simplification All of the features are provided by Clivet already assembled and tested onboard, differently then other manufacturers who make numerous additional components available to be installed on site.

Compact and versatile

Suitable for all types of terminals, from the fan systems to the radiant and chilled beams, also ELFOEnergy LARGE2 has a extremely low noise configuration, hat energy recovery for the production of free domestic hot water, Master-Slave management devices.

The two available versions enable the best

combination to be chosen between initial

investment and entire life cycle system costs.

The EXCELLENCE version has a very high

energy efficiency while working both at part-

load and full-load (Eurovent class A

certificate at full load)

The PREMIUM version has a high-level of

compactness and high-efficiency at partial

load.

Furthermore, ELFOEnergy Large2 with its

numerous configurations, can be completed

with most common system options built-in.

Page 4: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

4

®

BT10E005GB-02

ELFOENERGY LARGE2

ELFOEnergy LARGE2 TECHNOLOGY IS THE ENERGY REFERENCE POINT

FOR LIQUID CHILLERS

MAXIMUM EFFICIENCY IS ASSURED BETWEEN THE 25% AND THE 75% OF THE SYSTEM LOAD

For maximum loads taking place only for a few hours of functioning per year. The high efficiency at partial loads of ELFOEnergy LARGE2 makes it much more competitive and efficient than other solutions.

THE MODULAR SCROLL IS THE EXCELLENT SOLUTION FOR PARTIAL LOAD ELFOEnergy LARGE2 uses Scroll-type high-efficiency compressors, with optimized spirals. Main advantages are:

Compressors manufactured in large numbers at industrial level, with strict quality checks and highest reliability thanks to the elevated production volumes. With two different-sized compressors, in order to achive more adjustment steps. So it is possible to supply for usage only the energy that is actually require. Efficiency increases by over 50% when operating at partial loads, thanks to the larger heat exchange surfaces available.

The electronic expansion valve contributes to the excellent performance (EEV) it adapts rapidly and precisely to the actual load required for usage, and the high performance heat exchangers.

Example refers to a WSAT-XEE 352, EXCELLENCE. Version. External temperature equal to 35°C / 30°C / 25°C, respectively.

VERY HIGH HEAT EXCHANGE EFFICIENCY

Thanks to the external ELFOEnergy LARGE2 coils, equipped with wide frontal surfaces and reduced depth, the following is

obtained:

An improvement in the working temperature of the chiller circuit and, therefore, its efficiency, since the approach between the air temperature and the temperature of the chiller fluid inside the exchanger is reduced; A reduction in consumption by the fans, thanks to the reduced depth of the exchanger which decreases air flow renewal drops. Furthermore, the automatic fan speed control, supplied in series, minimises the air renewal air requirement to function correctly and therefore further reduces consumption; A decrease in the sound level, since greater surfaces enable slower air speed in the exchangers.

* EUROVENT (ESEER) supply times reference and ARI (IPLV) reference for

seasonal efficiency calculations.

COMPLETELY AUTOMATIC FUNCTIONING

The microprocessor controller manages functioning automatically in line with maximum

efficiency criteria, enables up to 6 units to be coordinated in a local network (Master-Slave

function) and includes numerous safety functions and the management of any alarms.

The interface terminal is equipped with a backlit graphic display and a multifunction access

keyboard. The multi-level menu is protected by passwords which are differentiated by different

user types. The daily / weekly clock programmer function is standard.

Thanks to its attractive design, the interface terminal can also be positioned inside the rooms

being serviced or in a special system control room.

ECOBREEZE ELECTRONICALLY-CONTROLLED FAN TECHNOLOGY

Using ECOBREEZE the external rotary electric motor is operated by a continuous magnetic

switching of the stator, induced by integrated electronic control. The advantages are:

70% increase in efficiency thanks to the brushless technology and the special electricity supply; Increase in the working life, thanks to the elimination of the brush wear;

Reduction in the electrical consumption by the system, thanks to a drastic reduction of the

inrush current for the fans obtained using the integrated ‗Soft start‘ function.

Note: ECOBREEZE is supplied as standard in the EXCELLENCE version

The external axial fans are equipped with an innovative Winglet blade profile with an integrated deflector, which is able to increase aerodynamic efficiency. This results in a 10% reduction in consumption. The average acoustic emission is 6 dB less then traditional fans.

Page 5: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

5

®

BT10E005GB-02

ELFOENERGY LARGE2

ELFOEnergy LARGE2 TECHNOLOGY ENABLES

THE SYSTEM TO BE INDUSTRIALISED

ELFOEnergy LARGE2 can be supplied complete with system components which are often provided as external to units.

Thus reducing:

Design time: all the accessories are created to guarantee the best overall performance; Installation costs: the accessories which are already connected manually, electrically wired and individually checked are ready to start working immediately; Dimension: integration of system members into the unit reduces technical spaces and increases the space available for other uses. The slim line structure enables it to be positioned even on terraces or in external service corridors.

THE ON-BOARD PUMPS ARE VERSATILE, READY-FOR-USE AND RELIABLE

The various solutions available are:

Standard pump, with a wide range of available heads.

Standard pump with emergency pump. The on-board microprocessor balances its

working hours and in case of any breakdown signals the fault and automatically activates

the reserve pump.

HYDROPACK, the modular solution with two parallel pumps. Automatically reduces

water flow in critical conditions, avoiding blocks due to overloading and consequential

interventions by specialised technical personnel. It is very useful during start-up, during

re-start after a pause in working (e.g. a weekend) or after a long period of inactivity. In

case of any pump breakdowns, the unit continues to function with 60% of the nominal

flow.

FREE HOT WATER Condensation heat recovery:

Partial: recovers around 20% of the available heat (desuperheater);

Total: recovers 100% of available heat.

Free hot water production for :

Supplying hot-water coils for post-heating;

Producing domestic hot water (with the intermediate exchanger);

Other processes or operations.

IT EXPLOITS EXTERNAL AIR FOR COOLING WITHOUT ACTIVATING THE COMPRESSORS

In the FREE-COOLING configuration, as soon as the external conditions enable it, the unit is able to cool the liquid reducing

compressor functioning up to their complete withdrawal. This configuration is particularly useful in applications with a

high number of room loads, since it notably reduces unit energy consumption and compressor wear.

EVEN THE STORAGE TANK AND THE PRIMARY CIRCUIT CAN BE INTEGRATED ON-BOARD A connection to the secondary use circuit is all that's needed. In this way, the system results even more simple and reliable. The units are complete with rapid connections on the hydraulic side, which further reduces set-up times by eliminating pipe threading operations.

Furthermore, other system components are also available as accessories, such as hydraulic attachments reported on the external walls of the unit (as standard with pumps and/or storage tank) and the required water filter.

ELFOEnergy LARGE2 MAY INCLUDE

MOST OF SYSTEM COMPONENTS

STANDARD RAPID CONNECTIONS

Gasket

Housing

Groove

Bolt/Nut

Page 6: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

6

®

BT10E005GB-02

ELFOENERGY LARGE2

CONFIGURATION CODE

(1) VERSION EXCELLENCE (EXC) standard PREMIUM (PRM) (2) ENERGY RECOVERY Energy recovery: not required (-) standard Partial energy recovery (D) Total energy recovery (R)

(3) LIQUID LOW TEMPERATURE Liquid low temperature : not required (-) standard Liquid low temperature (B) (4) FREE-COOLING Direct FREE-COOLING: not required (-) standard Direct FREE-COOLING (FCD)

(5) ACOUSTIC CONFIGURATION Acoustic configuration with compressor

soundproofing (SC) standard Extremely low noise acoustic configuration (EN) (5) HEAT EXCHANGERS APPROVALS Heat exchangers approvals CE = PED (European Testing) (PED)

standard Heat exchangers approvals C = CLIVET (Internal Testing) (CLV)

standard

WSAT-XEE - 352

-

R

D B

-

FCD

SC

EN

EXC

PRM

PED

PED

CLV

6)((2)

-

(3)

-

(4)

EXC

1)(

SC

5)(

-

INDEX OF THE TECHNICAL SECTION

General technical specification - Electrical data Pag. 20

Operating limit (COOLING) - Sound level Pag. 21

COOLING performance Pag. 21-23

Internal exchanger pressure drop - Admissible water flow rate Pag. 23

► EXCELLENCE Version - Soundproof compressor configuration (SC)

► EXCELLENCE Version - Extremely low noise configuration (EN)

► PREMIUM Version - Soundproof compressor configuration (SC)

► PREMIUM Version - Extremely low noise configuration (EN)

► CONFIGURATIONS Pag. 24-27

► HYDRONIC GROUP ACCESSORIES Pag. 28-31

► HYDROPACK Pag. 32-33

► ACCESSORIES Pag. 34-38

► FOULING CORRECTION FACTOR - CALIBRATION - EXCHANGER OPERATING LIMITS

Pag. 39

► OPTION COMPATIBILITY Pag. 40-41

► DIMENSIONAL Pag. 42-47

General technical specification - Electrical data Pag. 8

Operating limit (COOLING) - Sound level Pag. 9

COOLING performance Pag. 10-11

Internal exchanger pressure drop - Admissible water flow rate Pag. 11

General technical specification - Electrical data Pag. 12

Operating limit (COOLING) - Sound level Pag. 13

COOLING performance Pag. 14-15

Internal exchanger pressure drop - Admissible water flow rate Pag. 15

General technical specification - Electrical data Pag. 16

Operating limit (COOLING) - Sound level Pag. 17

COOLING performance Pag. 18-19

Internal exchanger pressure drop - Admissible water flow rate Pag. 19

Page 7: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

7

®

BT10E005GB-02

ELFOENERGY LARGE2

TECHNICAL UNIT FEATURES - EXCELLENCE VERSION

COMPRESSOR Hermetic orbiting scroll compressor complete with motor over-temperature and over-current devices and protection against excessive gas discharge temperature. Fitted on rubber antivibration mounts and complete with oil charge. A oil heater is automatically switched on at the compressor shut-down to prevent oil dilution by the refrigerant. The compressors are connected in tandem on a single refrigerator circuit. They have bi-phase equalization of the oil and are equipped with cut-off bibcock. STRUCTURE Supporting structure realised in galvanised steel sheet able to supply excellent mechanical features and long-lasting resistance to corrosion. PANELLING External panels in pre-painted aluminium especially indicated in outdoor installation due to its superior resistance to corrosion avoiding periodic painting. Side panels are easily removable and allow complete access to unit

components. Internal sound proof lining reduces sound pressure levels. INTERNAL EXCHANGER Direct expansion heat exchanger, braze-welded AISI 316 stainless steel plates with large exchange surface and complete with external heat and anti-condensate insulation. The exchanger comes complete with: - differential pressure switch, water side - antifreeze heater to protect the water side exchanger, preventing the

formation of frost if the water temperature falls below a set value. EXTERNAL EXCHANGER Finned exchanger, made from copper pipes arranged in staggered rows and mechanically expanded for better adherence to the collar of the fins. The fins are made from aluminium with a special corrugated surface, set a suitable distance apart to ensure maximum heat exchange efficiency. The coils are complete with integral subcooling circuit which assures the correct refrigerant feeding of the expansion valve. FAN ECOBREEZE device (STD) Helical fans with sickle-shaped blades with "Winglets" at the end, coupled directly to electronic control (IP 54), driven by the magnetic commutation of the stator. The brushless technology and the special supply increase both the life expectancy and the efficiency. As a result the electric consumption is reduced up to 50%. Fans are housed in aerodynamically shaped structures to increase efficiency and reduce noise level. The assembly is protected by accident prevention guards. The fans have the variable speed control. REFRIGERANT CIRCUIT The circuit is complete with: - replaceable anti-acid solid cartridge dehydrator filter - sight glass with moisture indicator - electronic expansion valve - high pressure switch - low pressure switch - high pressure safety valve - low pressure safety valve - liquid line shut-off valve - compressor discharge shut-off valve ELECTRICAL PANEL The Power Section includes: - main door lock isolator switch - isolating transformer for auxiliary circuit power supply - compressor circuit breaker - fan overload circuit breakers - compressor control contactor

The control section includes: - interface terminal with graphic display - display of the set values, the error codes and the parameter index - ON/OFF and alarm reset buttons - proportional + integral water temperature control - antifreeze protection on the water side - compressor overload protection and timer - pre-alarm function for water anti-ice and high refrigerant gas pressure - self-diagnosis system with immediate display of the error code - automatic compressor start rotation control - compressor operating hour display - remote ON/OFF control - relay for remote cumulative fault signal - input for demand limit (absorbed power limit according to an external signal

0÷10V or 4÷20mA) - Master-Slave function - serial port RS485 with Modbus protocol

TECHNICAL UNIT SPECIFICATIONS - PREMIUM VERSION Technical specifications like EXCELLENCE version, except fan

FAN

Helical fans with sickle-shaped blades with "Winglets" at the end, coupled directly to a three phase electric external rotor motor with thermal protection incorporated in version IP 54. Housed in aerodynamically shaped nozzles to increase efficiency and minimize noise levels. They are fitted with protective safety guard grilles. The fans have the variable speed control. CONSTRUCTIVE CONFIGURATIONS

- D Partial Energy recovery - R Total Energy recovery - B Low temperature liquid

- SC Acoustic configuration with compressor soundproofing

- EN Extremely low noise acoustic configuration - FCD Direct FREE-COOLING ACCESSORIES - HYDRONIC GROUP - Standard pump (note: different type of pumps are available according to the

head) - Standard pump with a reserve pump (note: are type of pumps are available

according to the head) - HYDROPACK (note: type of pumps are available according to the head) - Storage tank

- Storage tank with primary circuit on board (note: only for unit with standard pump / standard pump with reserve pump )

- hydraulic couplings on external panel (note: only for unit with standard pump / standard pump with reserve pump / Hydropack and/ or Storage tank)

- stainless steel mesh mechanical filter (separately provided accessory)

(note: The filter must be installed in the exchanger inlet. Clivet declines all responsibility and the warranty on the equipment automatically expires if it is not provided an suitable mechanical filter within the unit).

ACCESSORIES - Finned coil protection grilles - Anti-hail protection grilles - Copper/aluminium condenser coil with acrylic coating - Copper/aluminium condenser coil with Fin Guard (Silver) treatment - Copper/copper condenser coil

- Spring antivibration mounts (separately provided accessory)

- Electrical panel ventilation - Electrical heating (for electrical panel heating) - Phase monitor - Power factor correction capacitors (cosfi > 0.9) - Breakaway current reducing device (soft start) - High and low pressure gauges - Shut-off valve on compressor suction and discharge - Device for fan consumption reduction of the external section with variable

speed (phase-cutting) (only for the EXCELLENCE version) - Free contacts for compressor state - Free contacts for compressor state and for operation in local/remote mode - Set point compensation with 0-10 V signal - Set point compensation with 4-20 mA signal - Set point compensation with outside temperature probe - Set point compensation according to the outside enthalpy - Kit for remote microprocessor remote control interface

(separately provided accessory)

- BACnet Converter - LonWorks serial converter kit TEST All the units are factory-tested in specific steps, before shipping them. After the approval, the moisture contents present in all circuits are analyzed, in order to ensure the respect of the limits set by the manufacturers of the different components.

Page 8: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

8

®

BT10E005GB-02

ELFOENERGY LARGE2

VERSION: EXCELLENCE

ELFOEnergy LARGE2 GENERAL TECHNICAL SPECIFICATIONS (SERIES WSAT-XEE)

COOLING

Cooling capacity 1 kW 97,4 110 121 131 143 155 174 197 218

Compressor power input kW 27,2 31,4 35,1 36 40,1 43,8 50,5 55,7 62,8

Total power input 2 kW 31,2 35,3 39 41,7 45,8 49,5 56,1 63,2 70,3

Heating capacity total recovery 3 kW 119 139 151 161 176 190 215 242 269

Heating capacity partial recovery 3 kW 31,2 35,3 39 41,7 45,8 49,7 56,1 63,2 70,2

EER 3,12 3,12 3,1 3,14 3,12 3,13 3,1 3,12 3,1

ESEER 4,42 4,48 4,4 4,39 4,44 4,44 4,36 4,5 4,29

COMPRESSOR

Type of compressors Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

N°. of Compressors Nr 2 2 2 2 2 2 2 2 2

Nominal capacity HP 35 40 43 45 50 55 60 70 80

Standard capacity steps Nr 3 3 3 3 3 3 2 3 2

Oil charge l 8 10 12 10 11 13 13 13 13

Refrigerant circuits Nr 1 1 1 1 1 1 1 1 1

INTERNAL EXCHANGER

Type of internal exchanger 4 PHE PHE PHE PHE PHE PHE PHE PHE PHE

Water flow rate (Internal Exchanger) 1 l/s 4,7 5,3 5,8 6,3 6,8 7,4 8,3 9,4 10,4

Internal exchanger pressure drop 1 kPa 30 30 30 35 34 40 40 41 41

Water content l 7 8 9 9 10 10 12 14 17

EXTERNAL SECTION FANS

Type of fans 5 AX AX AX AX AX AX AX AX AX

Number of fans Nr 2 2 2 3 3 3 3 4 4

Standard air flow l/s 12875 12792 12694 19194 19194 19028 18889 25278 25139

CONNECTIONS

Water fittings 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2

POWER SUPPLY

Standard power supply 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50

DIMENSIONS

Length mm 3075 3075 3075 4025 4025 4025 4025 5025 5025

Depth mm 1097 1097 1097 1097 1097 1097 1097 1097 1097

Height mm 1805 1805 1805 1805 1805 1805 1805 1805 1805

STANDARD UNIT WEIGHTS

Shipping weight kg 889 925 1015 1198 1224 1246 1290 1483 1527

Operating weight kg 896 933 1024 1207 1234 1256 1302 1497 1544

(1) data referred to the following conditions : - internal exchanger water = 12/7°C - external exchanger air intake 35°C (2) According to EUROVENT the Total Power Input does not consider the pump share, required to overcome the pressure drop for the solution circulation inside the exchangers.

(3) Option. recovery exchanger water = 40 / 45°C (4) PHE = plates (5) AX = axial-flow fan

SIZE 352 402 432 452 502 552 602 702 802

ELECTRICAL DATA ELFOEnergy LARGE2 (SERIES WSAT-XEE)

SIZE 352 402 432 452 502 552 602 702 802

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS

F.L.A. - Total A 79,3 90,6 100 102,9 110,7 122 131,4 150 164,5

F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION

F.L.I. - Total kW 47,3 52,4 58,8 61 67,4 72,5 79 91,8 102,4

M.I.C. MAXIMUM INRUSH CURRENT

M.I.C. - Value A 264,6 311,6 317,2 378,4 387,8 399,1 405,7 470,2 484,7

Voltage unbalance: max 2 % Power supply: 400/3/50 Hz +/-6% Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)

Page 9: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

9

®

BT10E005GB-02

ELFOENERGY LARGE2

Graph informed to size 352. The detail of each size is shown in tabular date. Ta = external exchanger air intake temperature (dry bulb) To (°C) = internal exchanger water outlet temperature 1. Standard unit: (not with ‗Low temperature liquid‘) 2. ‗Low temperature liquid‘ unit (with ethylene

glycol of 40%) 3. Partial-load unit (automatic capacity control) 4. Full-load unit (automatic air flow modulation)

-10

-5

0

5

10

15

20

-12 -8 -4 0 4 8 12 16 20 24 28 32 36 40 44 48 52

To (°

C)

Ta (°C)

1 11

2 2

34

2

34

SIZE 352 402 432 452 502 552 602 702 802

EXTERNAL EXCHANGER

Max air intake temperature 1 °C 47 46 46 47 47 46 46 47 46

Max air intake temperature 2 °C 50 50 50 50 50 50 50 50 50

Min. air intake temperature 3 °C -10 -10 -10 -10 -10 -10 -10 -10 -10

Min. air intake temperature 4 °C -7 -7 -7 -7 -7 -7 -7 -7 -7

Min. air intake temperature 5 °C -2 -2 -2 -2 -2 -2 -2 -2 -2

Min. air intake temperature 6 °C 11 11 11 11 11 11 11 11 11

INTERNAL EXCHANGER

Max water inlet temperature °C 24 24 24 24 24 24 24 24 24

Min. water outlet temperature 7 °C 5 5 5 5 5 5 5 5 5

Min. water outlet temperature 8 °C -7 -7 -7 -7 -7 -7 -7 -7 -7

Data referred to the following conditions : - internal exchanger water = 12/7°C - external exchanger air 35°C - still air Warning: the still air condition is meant as absence of air flow to the unit. Any wind condition can let air pass through the condenser coil thus worsening the operating limits of the unit. In case of predominant winds, windbreak barriers are necessary.

Note. For correct maintenance (not functioning) with external air temperatures at less than

-10°C, the Standard unit (not the FREE-COOLING configuration) must be equipped with the

"Electric panel anti-freeze protection" option and be continuously supplied with electricity.

The hydraulic circuit must be filled with an adequate percentage of anti-freeze. In this

condition, the minimum external air-temperature which is permitted depends on the chosen

model of "Electric panel anti-freeze protection" option, up to a limit value of -39°C.

The functioning mode can also be extended up to external air temperatures of less than -

39°C, but only with a FREE-COOLING configuration which is complete with an adequately

sized "Electric panel anti-frost protection" option.

In the Standard unit (not the FREE-COOLING configuration) with an empty hydraulic circuit,

which has no electricity supply, correct maintenance (not functioning) is possible up to an

external air temperature of -20°C.

(1) Max inlet temperature - unit at full load (2) Max inlet air temperature - Unit at partial load (3) Min inlet air temperature - Unit at full load and still fresh air (4) Min inlet air temperature - Unit at partial load and still fresh air (5) Min inlet air temperature - unit at partial load and air speed of 0.5 m/s. (6) Min inlet air temperature - unit at partial load and air speed of 1 m/s. (7) Standard unit without low temperature liquid device and external exchanger air intake 35°C (8) Unit with low temperature liquid device and external exchanger air intake 35°C Fluid with ethylene glycol of 40%.

VERSION: EXCELLENCE

OPERATING LIMITS (COOLING)

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)

SIZ

E

Sound Power Level (dB) Sound pressure

level

Sound power level Sound pressure level

63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)

352 90 88 87 84 78 74 66 59 67 85

402 90 87 86 84 79 75 67 59 67 85

432 90 88 87 85 80 77 68 59 68 86

452 91 89 87 85 81 75 68 60 68 86

502 91 89 88 86 81 76 68 60 68 87

552 92 89 89 86 82 77 69 61 69 88

602 91 89 88 86 83 77 69 60 69 88

702 93 91 90 88 84 78 70 62 70 89

802 93 91 90 88 84 78 70 62 70 89

The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field. Measures, according to ISO 3744 regulations, are carried out on a reflecting surface, with respect to the EUROVENT 8/1 certification. Data referred to the following conditions: - internal exchanger water = 12/7°C - outdoor air temperature 35°C

SOUND LEVELS

Page 10: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

10

®

BT10E005GB-02

ELFOENERGY LARGE2

COOLING PERFORMANCE

SIZE

352

402

432

452

502

552

602

To (ºC)

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C

25 30 35 40 44 46

kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe

102,0 22,2 96,9 24,4 91,6 26,8 86,0 29,3 81,3 31,5 78,9 32,7

105,2 22,4 100,0 24,6 94,5 27,0 88,7 29,5 83,9 31,7 81,5 32,9

108,5 22,6 103,1 24,8 97,4 27,2 91,5 29,8 86,6 31,9 84,1 33,1

111,7 22,8 106,2 25,0 100,4 27,4 94,3 30,0 89,3 32,2 86,8 33,3

115,0 23,0 109,3 25,3 103,3 27,7 97,2 30,2 92,1 32,4 89,5 33,5

118,3 23,2 112,4 25,5 106,3 27,9 100,1 30,5 94,9 32,6 92,3 33,7

114,7 25,7 109,1 28,2 103,1 30,9 96,8 33,8 91,5 36,3 88,7 37,5

118,5 25,9 112,7 28,4 106,5 31,1 100,0 34,0 94,5 36,5 91,6 37,7

122,2 26,2 116,2 28,7 109,8 31,4 103,1 34,3 97,4 36,7 94,5 37,9

125,9 26,4 119,6 29,0 113,0 31,6 106,1 34,5 100,3 36,9 97,3 38,1

129,4 26,7 123,0 29,2 116,2 31,9 109,1 34,7 103,1 37,1 100,1 38,3

132,9 26,9 126,3 29,4 119,3 32,1 112,0 34,9 105,9 37,3 102,8 38,5

127,0 28,7 120,6 31,5 113,9 34,6 106,9 37,9 101,2 40,8 98,2 42,3

131,1 29,0 124,5 31,8 117,6 34,8 110,4 38,2 104,5 41,1 101,5 42,6

135,2 29,3 128,4 32,1 121,3 35,1 113,9 38,5 107,8 41,3 104,7 42,8

139,3 29,6 132,2 32,4 124,9 35,4 117,4 38,7 111,2 41,6 108,0 43,1

143,3 29,9 136,1 32,7 128,6 35,7 120,9 39,0 114,6 41,8 111,4 43,3

147,4 30,2 139,9 33,0 132,3 36,0 124,4 39,3 118,0 42,1 114,8 43,5

136,5 29,2 130,0 32,2 123,2 35,5 115,9 39,0 109,8 42,1 106,7 43,7

141,0 29,5 134,3 32,5 127,2 35,7 119,7 39,3 113,5 42,3 110,2 43,9

145,5 29,8 138,5 32,7 131,2 36,0 123,5 39,5 117,1 42,5 113,8 44,1

149,9 30,0 142,8 33,0 135,3 36,2 127,3 39,8 120,7 42,8 117,3 44,3

154,4 30,3 147,0 33,3 139,3 36,5 131,1 40,0 124,3 43,0 120,8 44,5

158,8 30,5 151,2 33,5 143,3 36,8 134,9 40,3 127,9 43,2 124,3 44,7

148,9 32,6 141,7 35,8 134,2 39,4 126,4 43,5 119,9 47,0 116,6 48,8

153,8 32,9 146,3 36,1 138,6 39,7 130,5 43,8 123,8 47,3 120,4 49,1

158,6 33,2 150,9 36,4 142,9 40,1 134,6 44,1 127,7 47,5 124,2 49,4

163,5 33,5 155,5 36,8 147,3 40,4 138,8 44,4 131,7 47,8 128,1 49,7

168,3 33,8 160,1 37,1 151,7 40,7 142,9 44,7 135,7 48,1 132,0 49,9

173,1 34,2 164,7 37,4 156,0 41,0 147,1 45,0 139,7 48,4 - -

160,7 35,7 153,1 39,2 145,2 43,2 136,9 47,5 129,9 51,3 126,3 53,3

165,9 36,0 158,1 39,5 149,9 43,5 141,3 47,8 134,1 51,6 130,4 53,6

171,2 36,3 163,1 39,9 154,6 43,8 145,7 48,1 138,2 51,9 134,4 53,8

176,5 36,7 168,1 40,2 159,3 44,2 150,1 48,4 142,4 52,1 138,5 54,1

181,7 37,0 173,1 40,6 164,0 44,5 154,5 48,7 146,6 52,4 - -

187,0 37,4 178,1 40,9 168,7 44,8 158,9 49,0 150,8 52,7 - -

182,0 41,0 173,3 45,2 164,1 49,8 154,5 54,9 146,5 59,3 142,4 61,6

187,5 41,4 178,5 45,5 169,0 50,1 159,2 55,2 150,9 59,6 146,7 61,9

193,1 41,8 183,8 45,9 174,1 50,5 163,9 55,5 155,5 59,9 151,2 62,2

198,9 42,2 189,3 46,3 179,3 50,9 168,9 55,9 160,2 60,2 155,8 62,5

204,8 42,6 195,0 46,7 184,7 51,3 173,9 56,3 165,0 60,5 160,5 62,8

210,9 43,0 200,8 47,2 190,1 51,7 179,1 56,6 170,0 60,9 165,3 63,1

kWf = Cooling capacity in kW kWe = Compressor power input in kW To = Internal exchanger water outlet temperature in° C

VERSION: EXCELLENCE

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)

Page 11: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

11

®

BT10E005GB-02

ELFOENERGY LARGE2

SIZE

702

802

To (ºC)

5

6

7

8

9

10

5

6

7

8

9

10

EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C

25 30 35 40 44 46

kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe

203,8 45,8 194,6 50,0 184,9 54,9 174,8 60,5 166,4 65,5 162,1 68,2

210,2 46,1 200,6 50,4 190,7 55,3 180,2 60,9 171,6 65,9 167,2 68,6

216,6 46,5 206,8 50,7 196,5 55,7 185,8 61,3 176,9 66,3 172,3 68,9

223,3 46,8 213,1 51,1 202,5 56,1 191,4 61,7 182,2 66,7 177,6 69,3

230,0 47,2 219,5 51,5 208,6 56,5 197,2 62,1 187,8 67,0 182,9 69,7

236,9 47,6 226,1 51,9 214,8 56,9 203,1 62,5 193,4 67,4 188,4 70,0

225,9 52,1 215,9 56,6 205,5 61,9 194,7 68,2 185,7 73,8 181,1 76,9

232,8 52,5 222,5 57,0 211,8 62,4 200,6 68,6 191,4 74,3 186,7 77,3

239,9 52,8 229,3 57,4 218,2 62,8 206,7 69,1 197,2 74,8 192,4 77,8

247,2 53,2 236,2 57,8 224,8 63,2 212,9 69,6 203,1 75,2 198,1 78,3

254,6 53,6 243,3 58,2 231,5 63,7 219,3 70,0 209,2 75,7 204,0 78,8

262,2 54,0 250,5 58,6 238,4 64,1 225,8 70,5 215,3 76,2

kWf = Cooling capacity in kW kWe = Compressor power input in kW To = Internal exchanger water outlet temperature in° C

2 3 4 5 6 7 8 9 2015

20

30

40

50

60

70

80

90

100

Q [l/s]

P [

kP

a]

3

52

4

02

4

32 4

52

5

02 5

52

6

02

7

02

8

02

COOLING PERFORMANCE

VERSION: EXCELLENCE

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)

INTERNAL EXCHANGER PRESSURE DROP

THE WATER FLOW RATE CAN BE CALCULATED WITH THE FOLLOWING FORMULA:

kWf = COOLING CAPACITY [kW] DT = TEMPERATURE DIFFERENCE BETWEEN

WATER INLET / OUTLET

Q [l/s] = kWf / (4,186 x DT)

THE AIR SIDE PRESSURE DROPS ARE RELATIVE TO THE MEDIUM AIR TEMPERATURE OF 7°C

Q = AIR FLOW [l/s] DP = PRESSURE DROP [kPa]

ADMISSIBLE WATER FLOW RATE

352 402 432 452 502 552 602 702 802

Qmin 3,2 3,6 3,9 3,9 4,4 4,4 4,9 5,5 6,1 [l/s]

Qmax 9,0 10,2 11,1 11,1 12,2 12,2 13,5 15,1 16,6 [l/s]

Min. (Qmin) and max. (Qmax) water flow-rates admissible for a correct unit operation.

To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the water input line. It is a device compulsory for the correct unit operation, and it is available as Clivet option (see the HYDRONIC GROUP ACCESSORIES). If the mechanical filter is selected and installed by the Customer, it is forbidden the use of filters with the mesh pitch higher than 1,6 mm, because they can cause a bad unit operation and also its serious damaging.

Page 12: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

12

®

BT10E005GB-02

ELFOENERGY LARGE2

COOLING

Cooling capacity 1 kW 91,7 104 116 125 135 146 167 185 209

Compressor power input kW 28,4 32,8 37 37,5 41,9 46 53,3 58,4 66,1

Total power input 2 kW 31,2 35,6 39,8 41,5 45,9 50 57,3 63,6 71,3

Heating capacity total recovery 3 kW 119 139 151 161 176 190 215 242 269

Heating capacity partial recovery 3 kW 30 34 38 41 44 48 55 61 69

EER 2,94 2,92 2,91 3,01 2,94 2,92 2,91 2,91 2,93

ESEER 4,27 4,4 4,32 4,31 4,31 4,29 4,26 4,35 4,17

COMPRESSOR

Type of compressors Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

N°. of Compressors Nr 2 2 2 2 2 2 2 2 2

Nominal capacity HP 35 40 43 45 50 55 60 70 80

Standard capacity steps Nr 3 3 3 3 3 3 2 3 2

Oil charge l 8 10 12 10 11 13 13 13 13

Refrigerant circuits Nr 1 1 1 1 1 1 1 1 1

INTERNAL EXCHANGER

Type of internal exchanger 4 PHE PHE PHE PHE PHE PHE PHE PHE PHE

Water flow rate (Internal Exchanger) 1 l/s 4,4 5 5,5 6 6,5 7 8 8,8 10

Internal exchanger pressure drop 1 kPa 27 27 28 32 31 35 37 37 38

Water content l 7 8 9 9 10 10 12 14 17

EXTERNAL SECTION FANS

Type of fans 5 AX AX AX AX AX AX AX AX AX

Number of fans Nr 2 2 2 3 3 3 3 4 4

Standard air flow l/s 9819 9722 9639 14583 14583 14431 14292 19167 18986

CONNECTION

Water fittings 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2

POWER SUPPLY

Standard power supply 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50

DIMENSIONS

Length mm 3075 3075 3075 4025 4025 4025 4025 5025 5025

Depth mm 1097 1097 1097 1097 1097 1097 1097 1097 1097

Height mm 1805 1805 1805 1805 1805 1805 1805 1805 1805

STANDARD UNIT WEIGHTS

Shipping weight kg 889 925 1015 1198 1224 1246 1290 1483 1527

Operating weight kg 896 933 1024 1207 1234 1256 1302 1497 1544

SIZE 352 402 432 452 502 552 602 702 802

SIZE 352 402 432 452 502 552 602 702 802

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS

F.L.A. - Total A 79,3 90,6 100 102,9 110,7 122 131,4 150 164,5

F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION

F.L.I. - Total kW 47,3 52,4 58,8 61 67,4 72,5 79 91,8 102,4

M.I.C. MAXIMUM INRUSH CURRENT

M.I.C. - Value A 264,6 311,6 317,2 378,4 387,8 399,1 405,7 470,2 484,7

Voltage unbalance: max 2 % Power supply: 400/3/50 Hz +/-6% Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.

VERSION: EXCELLENCE

ELFOEnergy LARGE2 GENERAL TECHNICAL SPECIFICATIONS (SERIES WSAT-XEE)

ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)

(1) data referred to the following conditions : - internal exchanger water = 12/7°C - external exchanger air intake 35°C (2) According to EUROVENT the Total Power Input does not consider the pump share, required to overcome the pressure drop for the solution circulation inside the exchangers.

(3) Option. recovery exchanger water = 40 / 45°C (4) PHE = plates (5) AX = axial-flow fan

ELECTRICAL DATA ELFOEnergy LARGE2 (SERIES WSAT-XEE)

Page 13: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

13

®

BT10E005GB-02

ELFOENERGY LARGE2

-10

-5

0

5

10

15

20

-12 -8 -4 0 4 8 12 16 20 24 28 32 36 40 44 48 52

To (°

C)

Ta (°C)

1 1

2 2

1

34

2

34

SIZE 352 402 432 452 502 552 602 702 802

EXTERNAL EXCHANGE

Max air intake temperature 1 °C 46 45 44 46 46 45 44 46 45

Max air intake temperature 2 °C 47 46 46 47 47 46 46 47 46

Max air intake temperature 3 °C 50 50 50 50 50 50 50 50 50

Min. air intake temperature 4 °C -10 -10 -10 -10 -10 -10 -10 -10 -10

Min. air intake temperature 5 °C -7 -7 -7 -7 -7 -7 -7 -7 -7

Min. air intake temperature 6 °C -2 -2 -2 -2 -2 -2 -2 -2 -2

Min. air intake temperature 7 °C 11 11 11 11 11 11 11 11 11

INTERNAL EXCHANGE

Max water inlet temperature °C 24 24 24 24 24 24 24 24 24

Min. water outlet temperature 8 °C 5 5 5 5 5 5 5 5 5

Min. water outlet temperature 9 °C -7 -7 -7 -7 -7 -7 -7 -7 -7

VERSION: EXCELLENCE

OPERATING LIMITS (COOLING)

ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)

SOUND LEVEL

The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field. Measures, according to ISO 3744 regulations, are carried out on a reflecting surface, with respect to the EUROVENT 8/1 certification. Data referred to the following conditions: - internal exchanger water = 12/7°C - outdoor air temperature 35°C

SIZ

E

Sound Power Level (dB) Sound pressure

level

Sound power level Sound pressure level

63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)

352 82 84 84 80 71 68 60 55 63 81

402 82 83 84 80 74 70 62 57 63 81

432 82 83 86 82 75 71 62 57 65 83

452 85 85 86 83 76 70 63 58 65 83

502 84 85 87 83 76 71 63 57 66 84

552 84 85 87 83 78 72 64 59 66 84

602 84 85 87 84 78 72 64 58 66 85

702 86 86 88 85 79 73 65 59 67 86

802 86 86 89 85 80 73 66 60 67 86

The sound levels indicated sideways are valid only for the operating range of the ‗Extremely low noise EN‘ configuration; with fresh air temperatures higher and in any case into the operating range of the ‗Compressor soundproofing SC‘ configuration, consider the sound levels of the ‗Compressor soundproofing‘ configuration .

Graph informed to size 352. The detail of each size is shown in tabular date. Ta = external exchanger air intake temperature (dry bulb) To (°C) = internal exchanger water outlet temperature 1. Standard unit: (not with ‗Low temperature liquid‘) 2. ‗Low temperature liquid‘ unit (with ethylene

glycol of 40%) 3. Partial-load unit (automatic capacity control) 4. Full-load unit (automatic air flow modulation)

Data referred to the following conditions : - internal exchanger water = 12/7°C - external exchanger air 35°C - still air Warning: the still air condition is meant as absence of air flow to the unit. Any wind condition can let air pass through the condenser coil thus worsening the operating limits of the unit. In case of predominant winds, windbreak barriers are necessary.

Note. For correct maintenance (not functioning) with external air temperatures at less than

-10°C, the Standard unit (not the FREE-COOLING configuration) must be equipped with the

"Electric panel anti-freeze protection" option and be continuously supplied with electricity.

The hydraulic circuit must be filled with an adequate percentage of anti-freeze. In this

condition, the minimum external air-temperature which is permitted depends on the chosen

model of "Electric panel anti-freeze protection" option, up to a limit value of -39°C.

The functioning mode can also be extended up to external air temperatures of less than -39°C, but only with a FREE-COOLING configuration which is complete with an adequately sized "Electric panel anti-frost protection" option.

In the Standard unit (not the FREE-COOLING configuration) with an empty hydraulic circuit, which has no electricity supply, correct maintenance (not functioning) is possible up to an external air temperature of -20°C.

(1) Max inlet temperature - unit at full load (2) Max inlet air temperature - Unit at partial load (3) Min inlet air temperature - Unit at full load and still fresh air (4) Min inlet air temperature - Unit at partial load and still fresh air (5) Min inlet air temperature - unit at partial load and air speed of 0.5 m/s. (6) Min inlet air temperature - unit at partial load and air speed of 1 m/s. (7) Standard unit without low temperature liquid device and external exchanger air intake 35°C (8) Unit with low temperature liquid device and external exchanger air intake 35°C Fluid with ethylene glycol of 40%

Page 14: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

14

®

BT10E005GB-02

ELFOENERGY LARGE2

SIZE

352

402

432

452

502

552

602

To (ºC)

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C

25 30 35 40 42 44

kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe

96,6 23,3 91,6 25,5 86,3 27,9 80,9 30,5 78,6 31,6 76,3 32,7

99,6 23,5 94,4 25,8 89,0 28,2 83,4 30,8 81,1 31,8 78,8 32,9

102,6 23,7 97,2 26,0 91,7 28,4 86,0 31,0 83,7 32,1 81,3 33,2

105,6 24,0 100,1 26,2 94,5 28,7 88,6 31,3 86,3 32,3 83,8 33,4

108,6 24,2 103,0 26,5 97,2 28,9 91,3 31,5 88,8 32,6 86,4 33,7

111,7 24,4 105,9 26,7 100,0 29,2 93,9 31,8 91,4 32,9 88,9 34,0

109,5 26,9 103,9 29,5 98,0 32,3 91,8 35,2 89,2 36,4 86,6 37,6

113,1 27,2 107,3 29,8 101,1 32,5 94,8 35,4 92,1 36,6 89,5 37,8

116,6 27,5 110,5 30,1 104,2 32,8 97,6 35,7 94,9 36,8 92,1 38,0

119,8 27,8 113,7 30,3 107,2 33,1 100,3 36,0 97,4 37,2 94,5 38,4

122,9 28,2 116,9 30,6 110,2 33,3 102,9 36,3 99,8 37,5 96,6 38,9

125,9 28,6 119,9 30,9 113,1 33,6 105,3 36,6 102,0 38,0 98,5 39,4

122,1 30,3 115,6 33,2 109,0 36,3 102,0 39,8 99,2 41,2 96,3 42,7

125,8 30,7 119,4 33,5 112,4 36,7 104,9 40,3 101,8 41,8 98,5 43,4

129,5 31,1 123,0 33,8 115,9 37,0 108,3 40,5 105,0 42,1 101,7 43,7

133,2 31,5 126,5 34,2 119,4 37,3 112,0 40,6 108,9 42,1 105,8 43,5

137,0 31,8 129,8 34,7 122,9 37,6 116,1 40,5 113,5 41,7 110,9 42,9

140,7 32,1 133,0 35,2 126,3 37,9 120,7 40,2 118,7 41,0 116,9 41,8

130,7 30,6 124,3 33,6 117,5 37,0 110,5 40,5 107,5 42,0 104,6 43,6

135,0 30,9 128,3 33,9 121,3 37,3 114,0 40,8 111,0 42,3 107,9 43,9

139,2 31,2 132,3 34,2 125,1 37,6 117,5 41,1 114,4 42,6 111,2 44,2

143,4 31,5 136,3 34,5 128,8 37,9 121,1 41,4 117,8 42,9 114,6 44,4

147,6 31,8 140,2 34,8 132,6 38,2 124,6 41,7 121,3 43,1 118,0 44,6

151,7 32,1 144,2 35,2 136,3 38,5 128,1 41,9 124,8 43,4 121,4 44,9

140,9 34,1 133,9 37,5 126,6 41,3 119,0 45,4 115,9 47,1 112,7 49,0

145,5 34,5 138,2 37,9 130,6 41,6 122,8 45,7 119,6 47,4 116,4 49,2

150,0 34,8 142,5 38,2 134,7 42,0 126,6 46,0 123,3 47,8 120,0 49,6

154,5 35,2 146,7 38,6 138,7 42,3 130,4 46,4 127,0 48,1 123,6 49,9

159,0 35,5 151,0 38,9 142,8 42,7 134,2 46,8 130,7 48,5 127,2 50,3

163,5 35,9 155,3 39,3 146,8 43,0 138,0 47,1 134,4 48,9 130,7 50,7

152,0 37,4 144,6 41,2 136,8 45,2 128,7 49,7 125,3 51,6 121,9 53,5

156,9 37,8 149,2 41,5 141,1 45,6 132,7 50,1 129,2 51,9 125,7 53,9

161,8 38,2 153,8 41,9 145,4 46,0 136,7 50,4 133,1 52,3 129,5 54,2

166,7 38,6 158,4 42,3 149,8 46,3 140,8 50,7 137,1 52,6 133,3 54,5

171,5 39,0 163,0 42,7 154,1 46,7 144,9 51,0 141,1 52,8 137,2 54,7

176,3 39,4 167,5 43,1 158,4 47,1 149,0 51,3 145,1 53,1 141,1 54,9

175,2 43,3 166,4 47,7 157,2 52,4 147,6 57,7 143,7 59,9 139,7 62,2

180,3 43,7 171,3 48,1 161,8 52,9 152,0 58,0 147,9 60,2 143,8 62,5

185,6 44,2 176,3 48,5 166,6 53,3 156,5 58,4 152,3 60,6 148,1 62,8

191,1 44,6 181,5 49,0 171,5 53,7 161,1 58,8 156,9 60,9 152,6 63,2

196,7 45,1 186,8 49,4 176,5 54,1 165,9 59,2 161,5 61,3 157,1 63,5

202,5 45,6 192,3 49,9 181,7 54,6 170,7 59,6 166,3 61,7 161,8 63,8

kWf = Cooling capacity in kW kWe = Compressor power input in kW To = Internal exchanger water outlet temperature in° C

COOLING PERFORMANCE

VERSION: EXCELLENCE

ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)

Page 15: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

15

®

BT10E005GB-02

ELFOENERGY LARGE2

SIZE

702

802

To (ºC)

5

6

7

8

9

10

5

6

7

8

9

10

EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C

25 30 35 40 42 44

kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe

193,0 47,8 184,0 52,3 174,5 57,5 164,7 63,3 160,6 65,8 156,5 68,5

198,9 48,2 189,5 52,8 179,8 57,9 169,7 63,7 165,6 66,2 161,4 68,8

204,9 48,6 195,2 53,2 185,2 58,4 174,8 64,2 170,6 66,7 166,3 69,3

211,1 49,1 201,1 53,6 190,7 58,8 180,0 64,7 175,6 67,1 171,1 69,7

217,3 49,5 207,1 54,1 196,4 59,3 185,2 65,1 180,6 67,6 176,0 70,2

223,7 50,0 213,2 54,5 202,1 59,8 190,5 65,6 185,7 68,2 180,9 70,8

217,7 54,5 207,8 59,3 197,4 65,1 186,7 71,6 182,3 74,5 177,9 77,5

224,3 54,9 214,0 59,8 203,4 65,6 192,3 72,2 187,8 75,0 183,2 78,0

231,0 55,3 220,4 60,3 209,4 66,1 198,0 72,7 193,4 75,6 188,6 78,6

237,9 55,8 227,0 60,8 215,6 66,6 203,9 73,2 199,1 76,1 194,2 79,1

244,9 56,3 233,6 61,3 222,0 67,1 209,9 73,8 205,0 76,6 200,0 79,6

252,1 56,7 240,5 61,8 228,5 67,7 216,1 74,3 211,1 77,1 206,0 80,1

kWf = Cooling capacity in kW kWe = Compressor power input in kW To = Internal exchanger water outlet temperature in° C

COOLING PERFORMANCE

VERSION: EXCELLENCE

ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)

THE WATER FLOW-RATE CAN BE CALCULATED WITH THE FOLLOWING FORMULA

kWf = COOLING CAPACITY [kW] DT = TEMPERATURE DIFFERENCE BETWEEN

WATER INLET / OUTLET

Q [l/s] = kWf / (4,186 x DT)

THE AIR SIDE PRESSURE DROPS ARE RELATIVE TO THE MEDIUM AIR TEMPERATURE OF 7°C

Q = AIR FLOW [l/s] DP = PRESSURE DROP [kPa]

ADMISSIBLE WATER FLOW-RATE

352 402 432 452 502 552 602 702 802

Qmin 3,2 3,6 3,9 3,9 4,4 4,4 4,9 5,5 6,1 [l/s]

Qmax 9,0 10,2 11,1 11,1 12,2 12,2 13,5 15,1 16,6 [l/s]

Min. (Qmin) and max. (Qmax) water flow-rates admissible for a correct unit operation.

2 3 4 5 6 7 8 9 2015

20

30

40

50

60

70

80

90

100

Q [l/s]

P [

kP

a]

3

52

4

02

4

32 4

52

5

02 5

52

6

02

7

02

8

02

INTERNAL EXCHANGER PRESSURE DROP

To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the water input line. It is a device compulsory for the correct unit operation, and it is available as Clivet option (see the HYDRONIC GROUP ACCESSORIES). If the mechanical filter is selected and installed by the Customer, it is forbidden the use of filters with the mesh pitch higher than 1,6 mm, because they can cause a bad unit operation and also its serious damaging.

Page 16: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

16

®

BT10E005GB-02

ELFOENERGY LARGE2

COOLING

Cooling capacity 1 kW 91,5 102 113 122 131 143 162 183 204

Compressor power input kW 28,6 33,6 37,8 40 43,6 48,7 56,2 60,7 69,8

Total power input 2 kW 32,6 37,5 41,7 43,9 47,5 52,6 60,1 66,4 75,5

Heating capacity total recovery 3 kW 114 129 144 155 169 186 208 238 263

Heating capacity partial recovery 3 kW 30 33,9 37,7 40,5 43,6 47,9 54,5 60,9 68,4

EER 2,81 2,72 2,71 2,78 2,76 2,72 2,7 2,76 2,7

ESEER 4,07 4,11 4,06 4,22 4,21 4,18 4,09 4,18 3,98

COMPRESSOR

Type of compressors Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

N°. of Compressors Nr 2 2 2 2 2 2 2 2 2

Nominal capacity HP 35 40 43 45 50 55 60 70 80

Standard capacity steps Nr 3 3 3 3 3 3 2 3 2

Oil charge l 8 10 12 10 11 13 13 13 13

Refrigerant circuits Nr 1 1 1 1 1 1 1 1 1

INTERNAL EXCHANGER

Type of internal exchanger 4 PHE PHE PHE PHE PHE PHE PHE PHE PHE

Water flow rate (Internal Exchanger) 1 l/s 4,4 4,9 5,4 5,8 6,3 6,8 7,7 8,7 9,7

Internal exchanger pressure drop 1 kPa 47 47 48 45 41 41 43 45 44

Water content l 5 5 6 7 8 9 10 12 14

EXTERNAL SECTION FANS

Type of fans 5 AX AX AX AX AX AX AX AX AX

Number of fans Nr 2 2 2 2 2 2 2 3 3

Standard air flow l/s 12875 12875 12819 12569 12361 12361 12500 19167 19167

CONNECTION

Water fittings 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2

POWER SUPPLY

Standard power supply 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50

DIMENSION

Length mm 2710 2710 2710 2710 2710 2710 3075 4025 4025

Depth mm 1097 1097 1097 1097 1097 1097 1097 1097 1097

Height mm 1805 1805 1805 1805 1805 1805 1805 1805 1805

STANDARD UNIT WEIGHTS

Shipping weight kg 773 796 885 917 955 975 1077 1283 1310

Operating weight kg 778 802 892 924 963 984 1087 1295 1324

SIZE 352 402 432 452 502 552 602 702 802

SIZE 352 402 432 452 502 552 602 702 802

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS

F.L.A. - Total A 79,3 90,6 100 98,8 106,6 117,9 127,3 145,9 160,4

F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION

F.L.I. - Total kW 47,3 52,4 58,8 58,8 65,2 70,3 76,8 89,6 100,2

M.I.C. MAXIMUM INRUSH CURRENT

M.I.C. - Value A 264,6 311,6 317,2 374,3 383,7 395 401,6 466,1 480,6

Voltage unbalance: max 2 % Power supply: 400/3/50 Hz +/-6% Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.

VERSION: PREMIUM

ELFOEnergy LARGE2 GENERAL TECHNICAL SPECIFICATIONS (SERIES WSAT-XEE)

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)

((1) data referred to the following conditions : - internal exchanger water = 12/7°C - external exchanger air intake 35°C (2) According to EUROVENT the Total Power Input does not consider the pump share, required to overcome the pressure drop for the solution circulation inside the exchangers.

(3) Option. recovery exchanger water = 40 / 45°C (4) PHE = plates (5) AX = axial-flow fan

ELECTRICAL DATA ELFOEnergy LARGE2 (SERIES WSAT-XEE)

Page 17: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

17

®

BT10E005GB-02

ELFOENERGY LARGE2

-10

-5

0

5

10

15

20

-12 -8 -4 0 4 8 12 16 20 24 28 32 36 40 44 48 52

To (°

C)

Ta (°C)

11

2 2

1

34

2

34

SIZE 352 402 432 452 502 552 602 702 802

EXTERNAL EXCHANGER

Max air intake temperature 1 °C 45 44 43 44 44 43 42 44 43

Max air intake temperature 2 °C 50 50 50 50 50 50 50 50 50

Min. air intake temperature 3 °C -10 -10 -10 -10 -10 -10 -10 -10 -10

Min. air intake temperature 4 °C -7 -7 -7 -7 -7 -7 -7 -7 -7

Min. air intake temperature 5 °C -2 -2 -2 -2 -2 -2 -2 -2 -2

Min. air intake temperature 6 °C 11 11 11 11 11 11 11 11 11

INTERNAL EXCHANGER

Max water inlet temperature °C 24 24 24 24 24 24 24 24 24

Min. water outlet temperature 7 °C 5 5 5 5 5 5 5 5 5

Min. water outlet temperature 8 °C -7 -7 -7 -7 -7 -7 -7 -7 -7

VERSION: PREMIUM

OPERATING LIMITS (COOLING)

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)

The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field. Measures, according to ISO 3744 regulations, are carried out on a reflecting surface, with respect to the EUROVENT 8/1 certification. Data referred to the following conditions: - internal exchanger water = 12/7°C - outdoor air temperature 35°C

SOUND LEVEL

SIZ

E

Sound Power Level (dB) Sound pressure

level

Sound power level Sound pressure level

63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)

352 90 88 86 84 78 74 66 58 67 85

402 89 87 86 83 79 75 67 59 67 85

432 89 87 86 84 79 75 67 58 67 85

452 89 87 86 84 80 74 67 58 67 85

502 89 86 86 84 80 75 67 57 68 85

552 89 87 86 85 81 76 68 59 68 86

602 89 87 86 85 81 76 68 58 68 86

702 91 89 88 87 83 77 69 60 69 88

802 91 89 88 86 83 77 69 60 69 88

Graph informed to size 352. The detail of each size is shown in tabular date. Ta = external exchanger air intake temperature (dry bulb) To (°C) = internal exchanger water outlet temperature 1. Standard unit: (not with ‗Low temperature liquid‘) 2. ‗Low temperature liquid‘ unit (with ethylene

glycol of 40%) 3. Partial-load unit (automatic capacity control) 4. Full-load unit (automatic air flow modulation)

Data referred to the following conditions : - internal exchanger water = 12/7°C - external exchanger air 35°C - still air Warning: the still air condition is meant as absence of air flow to the unit. Any wind condition can let air pass through the condenser coil thus worsening the operating limits of the unit. In case of predominant winds, windbreak barriers are necessary.

Note. For correct maintenance (not functioning) with external air temperatures at less than

-10°C, the Standard unit (not the FREE-COOLING configuration) must be equipped with the

"Electric panel anti-freeze protection" option and be continuously supplied with electricity.

The hydraulic circuit must be filled with an adequate percentage of anti-freeze. In this

condition, the minimum external air-temperature which is permitted depends on the chosen

model of "Electric panel anti-freeze protection" option, up to a limit value of -39°C.

The functioning mode can also be extended up to external air temperatures of less than -39°C, but only with a FREE-COOLING configuration which is complete with an adequately sized "Electric panel anti-frost protection" option.

In the Standard unit (not the FREE-COOLING configuration) with an empty hydraulic circuit, which has no electricity supply, correct maintenance (not functioning) is possible up to an external air temperature of -20°C.

(1) Max inlet temperature - unit at full load (2) Max inlet air temperature - Unit at partial load (3) Min inlet air temperature - Unit at full load and still fresh air (4) Min inlet air temperature - Unit at partial load and still fresh air (5) Min inlet air temperature - unit at partial load and air speed of 0.5 m/s. (6) Min inlet air temperature - unit at partial load and air speed of 1 m/s. (7) Standard unit without low temperature liquid device and external exchanger air intake 35°C (8) Unit with low temperature liquid device and external exchanger air intake 35°C Fluid with ethylene glycol of 40%

Page 18: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

18

®

BT10E005GB-02

ELFOENERGY LARGE2

SIZE

352

402

432

452

502

552

602

To (ºC)

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C

25 30 35 38 40 42

kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe

96,2 23,4 91,2 25,7 86,0 28,2 82,7 29,7 80,5 30,8 78,2 31,9

99,3 23,6 94,1 25,9 88,7 28,4 85,3 30,0 83,0 31,1 80,7 32,2

102,3 23,9 97,0 26,2 91,5 28,7 88,0 30,2 85,6 31,3 83,2 32,4

105,4 24,1 99,9 26,4 94,2 28,9 90,7 30,5 88,3 31,6 85,8 32,7

108,4 24,3 102,8 26,7 97,0 29,2 93,4 30,7 91,0 31,8 88,5 32,9

111,4 24,6 105,7 26,9 99,8 29,4 96,1 31,0 93,7 32,0 91,2 33,1

107,8 27,6 102,2 30,2 96,1 33,1 92,4 34,9 89,8 36,1 87,1 37,4

110,8 27,8 105,0 30,5 98,8 33,3 94,9 35,1 92,3 36,3 89,6 37,6

113,9 28,1 107,9 30,8 101,6 33,6 97,6 35,3 94,9 36,6 92,2 37,8

117,1 28,4 111,0 31,1 104,5 33,9 100,4 35,6 97,7 36,8 94,9 38,0

120,6 28,7 114,2 31,3 107,5 34,1 103,4 35,9 100,6 37,0 97,7 38,2

124,1 29,0 117,5 31,6 110,7 34,4 106,4 36,1 103,6 37,3 100,6 38,5

119,6 30,8 113,2 33,8 106,5 37,1 102,3 39,2 99,5 40,7 96,7 42,2

123,2 31,1 116,5 34,2 109,6 37,4 105,5 39,5 102,6 40,9 99,8 42,4

126,8 31,5 119,9 34,5 112,9 37,8 108,6 39,8 105,6 41,3 102,7 42,7

130,3 31,9 123,5 34,8 116,3 38,1 111,7 40,2 108,6 41,7 105,4 43,2

133,8 32,3 127,2 35,1 119,7 38,4 114,9 40,6 111,5 42,1 108,0 43,7

137,3 32,8 130,9 35,5 123,3 38,7 118,0 41,0 114,3 42,6 110,4 44,4

128,3 32,7 121,7 35,9 114,7 39,3 110,3 41,5 107,4 43,1 104,3 44,6

132,2 33,0 125,4 36,2 118,2 39,7 113,8 41,8 110,7 43,3 107,7 44,9

136,2 33,3 129,2 36,6 121,8 40,0 117,2 42,2 114,1 43,6 111,0 45,2

140,3 33,7 133,0 36,9 125,4 40,3 120,7 42,5 117,5 43,9 114,3 45,4

144,3 34,0 136,8 37,3 129,0 40,7 124,2 42,8 120,9 44,2 117,6 45,7

148,4 34,4 140,6 37,6 132,6 41,0 127,6 43,1 124,3 44,5 120,9 46,0

138,1 35,5 131,5 39,0 124,1 42,9 119,2 45,4 115,8 47,2 112,2 49,0

142,0 35,8 134,8 39,3 127,6 43,2 123,3 45,7 120,4 47,4 117,5 49,1

146,2 36,1 138,5 39,7 131,4 43,6 127,3 46,0 124,7 47,7 122,1 49,4

150,7 36,5 142,7 40,1 135,4 44,0 131,2 46,4 128,6 48,0 126,1 49,7

155,5 36,9 147,3 40,5 139,6 44,4 135,1 46,8 132,2 48,5 129,3 50,3

160,5 37,3 152,4 40,9 144,0 44,8 138,9 47,3 135,4 49,1 131,8 50,9

151,0 39,7 143,0 43,7 134,7 47,9 129,6 50,7 126,1 52,5 122,6 54,5

155,5 40,3 147,7 44,0 139,1 48,3 133,5 51,1 129,6 53,1 125,6 55,2

160,1 40,8 152,2 44,5 143,3 48,7 137,4 51,6 133,3 53,6 129,1 55,7

164,6 41,3 156,4 45,0 147,3 49,2 141,4 52,0 137,4 53,9 133,2 55,9

169,2 41,8 160,3 45,7 151,1 49,8 145,5 52,4 141,7 54,1 137,9 56,0

173,9 42,2 164,0 46,4 154,8 50,4 149,6 52,7 146,3 54,2 143,1 55,7

171,1 45,5 162,2 50,1 153,1 55,1 147,5 58,2 143,7 60,4 139,8 62,7

176,2 46,1 167,1 50,8 158,1 55,5 152,8 58,3 149,3 60,2 145,9 62,1

181,4 46,7 171,9 51,4 162,9 56,0 157,7 58,7 154,3 60,4 151,0 62,2

186,7 47,3 176,8 52,0 167,4 56,6 162,0 59,3 158,5 61,1 155,2 62,9

192,2 47,9 181,6 52,5 171,6 57,3 165,8 60,2 162,1 62,2 158,4 64,3

197,7 48,5 186,5 53,0 175,6 58,1 169,2 61,4 164,9 63,8 160,7 66,2

kWf = Cooling capacity in kW kWe = Compressor power input in kW To = Internal exchanger water outlet temperature in° C

COOLING PERFORMANCE

VERSION: PREMIUM

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)

Page 19: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

19

®

BT10E005GB-02

ELFOENERGY LARGE2

SIZE

702

802

To (ºC)

5

6

7

8

9

10

5

6

7

8

9

10

EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C

25 30 35 38 40 42

kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe

193,8 49,6 184,2 54,4 174,3 59,7 168,2 63,3 164,0 65,7 159,8 68,3

199,3 50,1 189,5 54,8 179,3 60,2 172,9 63,7 168,5 66,2 164,1 68,8

205,0 50,5 195,0 55,3 184,4 60,7 177,8 64,2 173,4 66,7 168,8 69,3

211,0 51,0 200,6 55,8 189,7 61,2 183,0 64,7 178,5 67,2 173,8 69,7

217,0 51,5 206,3 56,3 195,2 61,7 188,4 65,2 183,8 67,6 179,2 70,2

223,3 52,0 212,2 56,8 201,0 62,2 194,1 65,7 189,5 68,1 184,9 70,6

213,8 57,2 203,5 62,5 192,9 68,6 186,3 72,6 181,9 75,4 177,4 78,4

220,4 57,6 209,7 63,0 198,6 69,2 191,7 73,3 187,1 76,2 182,4 79,2

226,8 58,2 215,7 63,6 204,4 69,8 197,5 73,8 192,8 76,7 188,1 79,6

233,0 58,8 221,8 64,3 210,4 70,4 203,5 74,3 198,9 77,0 194,3 79,8

239,1 59,6 227,7 65,1 216,5 71,0 209,9 74,6 205,4 77,1 201,0 79,7

244,9 60,4 233,6 66,0 222,8 71,5 216,5 74,8 212,4 77,1 208,4 79,3

kWf = Cooling capacity in kW kWe = Compressor power input in kW To = Internal exchanger water outlet temperature in° C

COOLING PERFORMANCE

VERSION: PREMIUM

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC)

INTERNAL EXCHANGER PRESSURE DROP

THE WATER FLOW RATE CAN BE CALCULATED WITH THE FOLLOWING FORMULA:

kWf = COOLING CAPACITY [kW] DT = TEMPERATURE DIFFERENCE BETWEEN

WATER INLET / OUTLET

Q [l/s] = kWf / (4,186 x DT)

THE AIR SIDE PRESSURE DROPS ARE RELATIVE TO THE MEDIUM AIR TEMPERATURE OF 7°C

Q = AIR FLOW [l/s] DP = PRESSURE DROP [kPa]

ADMISSIBLE WATER FLOW RATE

352 402 432 452 502 552 602 702 802

Qmin 2,3 2,6 2,9 3,2 3,6 3,9 4,4 4,9 5,5 [l/s]

Qmax 6,6 7,4 8,1 9,0 10,2 11,1 12,2 13,5 15,1 [l/s]

Min. (Qmin) and max. (Qmax) water flow-rates admissible for a correct unit operation.

2 3 4 5 6 7 8 9 2015

20

30

40

50

60

70

80

90

100

Q [l/s]

P [

kP

a]

35

2

402

43

2

452

50

2

552

60

2

702

80

2

To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the water input line. It is a device compulsory for the correct unit operation, and it is available as Clivet option (see the HYDRONIC GROUP ACCESSORIES). If the mechanical filter is selected and installed by the Customer, it is forbidden the use of filters with the mesh pitch higher than 1,6 mm, because they can cause a bad unit operation and also its serious damaging.

Page 20: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

20

®

BT10E005GB-02

ELFOENERGY LARGE2

COOLING

Cooling capacity 1 kW 84,3 95,6 108 116 125 139 158 172 199

Compressor power input kW 30 35,4 40,1 42,6 46,2 52,3 60,3 64,7 75,3

Total power input 2 kW 32,8 38,2 42,9 45,4 49 55,1 63,1 68,7 79,3

Heating capacity total recovery 3 kW 114 129 144 155 169 186 208 238 263

Heating capacity partial recovery 3 kW 29 33 37 40 43 48 55 59 69

EER 2,57 2,5 2,52 2,56 2,55 2,52 2,5 2,5 2,51

ESEER 3,75 3,91 3,9 4,1 4,08 4,05 3,95 3,98 3,84

COMPRESSOR

Type of compressors Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll Scroll

N°. of Compressors Nr 2 2 2 2 2 2 2 2 2

Nominal capacity HP 35 40 43 45 50 55 60 70 80

Standard capacity steps Nr 3 3 3 3 3 3 2 3 2

Oil charge l 8 10 12 10 11 13 13 13 13

Refrigerant circuits Nr 1 1 1 1 1 1 1 1 1

INTERNAL EXCHANGER

Type of internal exchanger 4 PHE PHE PHE PHE PHE PHE PHE PHE PHE

Water flow rate (Internal Exchanger) 1 l/s 4 4,6 5,2 5,5 6 6,6 7,5 8,2 9,5

Internal exchanger pressure drop kPa 41 42 44 41 37 38 41 39 42

Water content l 5 5 6 7 8 9 10 12 14

EXTERNAL SECTION FANS

Type of fans 5 AX AX AX AX AX AX AX AX AX

Number of fans Nr 2 2 2 2 2 2 2 3 3

Standard air flow l/s 9833 9833 9764 9514 9319 9319 9653 14583 14583

CONNECTION

Water fittings 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2 2" 1/2

POWER SUPPLY

Standard power supply 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50 400/3~/50

DIMENSION

Length mm 2710 2710 2710 2710 2710 2710 3075 4025 4025

Depth mm 1097 1097 1097 1097 1097 1097 1097 1097 1097

Height mm 1805 1805 1805 1805 1805 1805 1805 1805 1805

STANDARD UNIT WEIGHTS

Shipping weight kg 773 796 885 917 955 975 1077 1283 1310

Operating weight kg 778 802 892 924 963 984 1087 1295 1324

SIZE 352 402 432 452 502 552 602 702 802

SIZE 352 402 432 452 502 552 602 702 802

F.L.A. - FULL LOAD CURRENT AT MAX ADMISSIBLE CONDITIONS

F.L.A. - Total A 79,3 90,6 100 98,8 106,6 117,9 127,3 145,9 160,4

F.L.I. FULL LOAD POWER INPUT AT MAX ADMISSIBLE CONDITION

F.L.I. - Total kW 47,3 52,4 58,8 58,8 65,2 70,3 76,8 89,6 100,2

M.I.C. MAXIMUM INRUSH CURRENT

M.I.C. - Value A 264,6 311,6 317,2 374,3 383,7 395 401,6 466,1 480,6

Voltage unbalance: max 2 % Power supply: 400/3/50 Hz +/-6% Electrical data refer to standard units; according to the installed accessories, the data can suffer light variations.

VERSION: PREMIUM

ELFOEnergy LARGE2 GENERAL TECHNICAL SPECIFICATIONS (SERIES WSAT-XEE)

ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)

(1) data referred to the following conditions : - internal exchanger water = 12/7°C - external exchanger air intake 35°C (2) According to EUROVENT the Total Power Input does not consider the pump share, required to overcome the pressure drop for the solution circulation inside the exchangers.

(3) Option. recovery exchanger water = 40 / 45°C (4) PHE = plates (5) AX = axial-flow fan

ELECTRICAL DATA ELFOEnergy LARGE2 (SERIES WSAT-XEE)

Page 21: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

21

®

BT10E005GB-02

ELFOENERGY LARGE2

-10

-5

0

5

10

15

20

-12 -8 -4 0 4 8 12 16 20 24 28 32 36 40 44 48 52

To (°

C)

Ta (°C)

1 1

2 2

1

34

2

34

SIZE 352 402 432 452 502 552 602 702 802

EXTERNAL EXCHANGER

Max air intake temperature 1 °C 43 41 40 41 41 40 40 41 40

Max air intake temperature 2 °C 45 44 43 44 44 43 42 44 43

Max air intake temperature 3 °C 50 50 50 50 50 50 50 50 50

Min. air intake temperature 4 °C -10 -10 -10 -10 -10 -10 -10 -10 -10

Min. air intake temperature 5 °C -7 -7 -7 -7 -7 -7 -7 -7 -7

Min. air intake temperature 6 °C -2 -2 -2 -2 -2 -2 -2 -2 -2

Min. air intake temperature 7 °C 11 11 11 11 11 11 11 11 11

INTERNAL EXCHANGER

Max water inlet temperature °C 24 24 24 24 24 24 24 24 24

Min. water outlet temperature 8 °C 5 5 5 5 5 5 5 5 5

Min. water outlet temperature 9 °C -7 -7 -7 -7 -7 -7 -7 -7 -7

VERSION: PREMIUM

OPERATING LIMITS (COOLING)

ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)

SOUND LEVEL

SIZ

E

Sound Power Level (dB) Sound pressure

level

Sound power level Sound pressure level

63 125 250 500 1000 2000 4000 8000 dB(A) dB(A)

352 83 84 85 80 72 69 60 55 63 81

402 82 83 84 80 74 70 62 57 63 81

432 82 83 86 81 75 71 62 56 65 82

452 83 83 85 82 76 70 63 57 65 83

502 81 83 86 82 75 70 62 55 65 83

552 82 83 87 83 77 72 64 58 66 84

602 82 83 86 83 78 71 64 57 66 84

702 85 85 88 85 79 73 65 59 67 86

802 84 85 88 85 79 73 65 59 67 86

The sound levels refer to the unit at full load, in the rated test conditions. The sound pressure level refers to a distance of 1m from the external surface of the units operating in an open field. Measures, according to ISO 3744 regulations, are carried out on a reflecting surface, with respect to the EUROVENT 8/1 certification. Data referred to the following conditions: - internal exchanger water = 12/7°C - outdoor air temperature 35°C

The sound levels indicated sideways are valid only for the operating range of the ‗Extremely low noise EN‘ configuration; with fresh air temperatures higher and in any case into the operating range of the ‗Compressor soundproofing SC‘ configuration, consider the sound levels of the ‗Compressor soundproofing‘ configuration .

Graph informed to size 352. The detail of each size is shown in tabular date. Ta = external exchanger air intake temperature (dry bulb) To (°C) = internal exchanger water outlet temperature 1. Standard unit: (not with ‗Low temperature liquid‘) 2. ‗Low temperature liquid‘ unit (with ethylene

glycol of 40%) 3. Partial-load unit (automatic capacity control) 4. Full-load unit (automatic air flow modulation)

Data referred to the following conditions : - internal exchanger water = 12/7°C - external exchanger air 35°C - still air Warning: the still air condition is meant as absence of air flow to the unit. Any wind condition can let air pass through the condenser coil thus worsening the operating limits of the unit. In case of predominant winds, windbreak barriers are necessary.

Note. For correct maintenance (not functioning) with external air temperatures at less than

-10°C, the Standard unit (not the FREE-COOLING configuration) must be equipped with the

"Electric panel anti-freeze protection" option and be continuously supplied with electricity.

The hydraulic circuit must be filled with an adequate percentage of anti-freeze. In this

condition, the minimum external air-temperature which is permitted depends on the chosen

model of "Electric panel anti-freeze protection" option, up to a limit value of -39°C.

The functioning mode can also be extended up to external air temperatures of less than -39°C, but only with a FREE-COOLING configuration which is complete with an adequately sized "Electric panel anti-frost protection" option.

In the Standard unit (not the FREE-COOLING configuration) with an empty hydraulic circuit, which has no electricity supply, correct maintenance (not functioning) is possible up to an external air temperature of -20°C.

(1) Max inlet temperature - unit at full load (2) Max inlet air temperature - Unit at partial load (3) Min inlet air temperature - Unit at full load and still fresh air (4) Min inlet air temperature - Unit at partial load and still fresh air (5) Min inlet air temperature - unit at partial load and air speed of 0.5 m/s. (6) Min inlet air temperature - unit at partial load and air speed of 1 m/s. (7) Standard unit without low temperature liquid device and external exchanger air intake 35°C (8) Unit with low temperature liquid device and external exchanger air intake 35°C Fluid with ethylene glycol of 40%

Page 22: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

22

®

BT10E005GB-02

ELFOENERGY LARGE2

SIZE

352

402

432

452

502

552

602

To (ºC)

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

5

6

7

8

9

10

EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C

25 30 32 35 38 40

kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe

89,1 24,6 84,3 26,9 82,3 27,9 79,3 29,4 76,1 31,0 74,0 32,1

91,9 24,8 87,0 27,2 84,9 28,2 81,7 29,7 78,5 31,3 76,3 32,4

94,7 25,1 89,6 27,5 87,5 28,5 84,3 30,0 81,0 31,5 78,8 32,6

97,4 25,4 92,1 27,8 90,0 28,8 86,8 30,2 83,6 31,7 81,5 32,7

100,1 25,7 94,5 28,2 92,4 29,1 89,3 30,5 86,4 31,9 84,5 32,8

102,7 26,0 96,9 28,6 94,8 29,5 91,9 30,8 89,3 32,0 87,7 32,7

102,2 29,3 96,5 32,0 94,2 33,1 90,6 34,8 87,0 36,6 84,5 37,8

104,9 29,6 98,9 32,3 96,6 33,4 93,0 35,1 89,5 36,9 87,2 38,1

107,7 30,0 101,6 32,6 99,2 33,7 95,5 35,4 91,9 37,2 89,6 38,4

110,7 30,3 104,5 33,0 101,9 34,1 98,1 35,7 94,3 37,4 91,7 38,6

113,7 30,6 107,5 33,3 104,9 34,4 100,8 36,0 96,6 37,7 93,6 38,8

116,7 31,0 110,8 33,7 108,1 34,8 103,6 36,4 98,7 37,9 95,3 38,9

115,3 32,9 108,6 36,0 105,9 37,3 102,0 39,4 98,1 41,5 95,6 42,9

118,1 33,4 111,9 36,4 109,2 37,7 104,8 39,7 100,1 42,0 96,8 43,5

121,3 33,8 115,1 36,8 112,4 38,1 107,9 40,1 102,9 42,3 99,5 43,9

124,8 34,2 118,1 37,3 115,4 38,5 111,1 40,5 106,6 42,5 103,5 44,0

128,6 34,5 121,0 37,8 118,2 39,1 114,4 40,9 111,0 42,6 109,0 43,7

132,9 34,8 123,7 38,4 121,0 39,7 118,0 41,3 116,3 42,6 115,8 43,2

123,3 35,0 116,7 38,3 114,0 39,7 109,8 41,8 105,5 44,0 102,6 45,5

127,4 35,3 120,1 38,7 117,3 40,1 113,0 42,2 108,8 44,4 106,1 45,8

131,1 35,7 123,5 39,1 120,5 40,5 116,2 42,6 112,1 44,7 109,4 46,1

134,6 36,2 126,8 39,6 123,8 41,0 119,5 42,9 115,3 44,9 112,6 46,1

137,7 36,8 130,1 40,3 127,1 41,5 122,8 43,3 118,5 45,0 115,8 46,0

140,5 37,6 133,3 41,0 130,4 42,1 126,1 43,7 121,7 45,0 118,8 45,8

131,8 37,9 124,7 41,9 121,9 43,4 117,9 45,5 114,0 47,6 111,5 49,0

135,8 38,4 128,4 42,1 125,4 43,7 120,6 46,2 115,7 48,9 112,3 50,7

139,8 38,9 132,3 42,5 129,0 44,1 123,9 46,8 118,5 49,6 114,7 51,6

143,8 39,4 136,2 43,0 132,9 44,6 127,8 47,2 122,3 49,9 118,5 51,8

147,8 39,8 140,2 43,7 137,1 45,2 132,2 47,4 127,2 49,6 123,7 51,1

151,9 40,2 144,4 44,4 141,5 45,8 137,2 47,5 133,1 48,9 130,5 49,7

147,2 43,1 139,1 47,1 135,7 48,8 130,3 51,5 124,6 54,4 120,7 56,3

151,0 43,8 143,1 47,8 139,7 49,5 134,3 51,9 128,6 54,5 124,6 56,1

155,1 44,4 147,0 48,5 143,5 50,1 138,2 52,4 132,6 54,8 128,7 56,4

159,6 44,9 150,8 49,0 147,3 50,6 141,9 53,0 136,5 55,4 132,9 57,0

164,4 45,3 154,7 49,5 151,0 51,1 145,6 53,7 140,5 56,2 137,2 57,9

169,6 45,6 158,4 49,8 154,5 51,6 149,2 54,4 144,5 57,3 141,7 59,2

165,7 49,8 157,4 54,2 153,9 56,2 148,4 59,3 142,5 62,8 138,5 65,2

171,1 50,3 161,5 55,1 158,0 57,0 152,9 59,8 148,3 62,6 145,4 64,5

176,3 50,9 165,9 55,9 162,3 57,7 157,7 60,3 153,8 62,6 151,6 64,0

181,3 51,5 170,6 56,5 167,1 58,3 162,6 60,6 159,0 62,6 157,2 63,8

186,1 52,2 175,6 57,0 172,1 58,7 167,6 60,9 164,0 62,7 162,0 63,8

190,7 52,9 181,0 57,4 177,5 58,9 172,8 61,0 168,7 62,9 166,3 64,0

kWf = Cooling capacity in kW kWe = Compressor power input in kW To = Internal exchanger water outlet temperature in° C

COOLING PERFORMANCE

VERSION: PREMIUM

ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)

Page 23: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

23

®

BT10E005GB-02

ELFOENERGY LARGE2

SIZE

702

802

To (ºC)

5

6

7

8

9

10

5

6

7

8

9

10

EXTERNAL EXCHANGER AIR INTAKE TEMPERATURE (ºC) HEAT DROP 5°C

25 30 32 35 38 40

kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe kWf kWe

181,6 52,8 172,2 57,9 168,4 60,1 162,7 63,5 156,9 67,1 153,0 69,6

186,9 53,4 176,8 58,6 172,9 60,8 167,2 64,1 161,7 67,6 158,1 70,0

192,1 54,0 181,7 59,2 177,6 61,4 171,7 64,7 166,0 68,3 162,3 70,7

197,0 54,7 186,9 59,8 182,7 61,9 176,4 65,4 169,9 69,0 165,6 71,5

201,8 55,5 192,5 60,3 188,2 62,5 181,1 66,0 173,4 69,9 167,9 72,6

206,4 56,4 198,4 60,8 193,9 63,0 186,0 66,7 176,5 70,9 169,3 74,0

209,5 61,4 199,6 67,0 195,2 69,5 188,1 73,5 180,4 77,9 175,0 81,0

215,7 62,0 204,4 68,0 200,1 70,4 194,0 74,2 188,2 78,0 184,5 80,5

222,2 62,6 209,9 68,8 205,5 71,3 199,5 75,0 194,3 78,6 191,2 81,0

228,7 63,3 215,9 69,6 211,2 72,1 204,6 75,9 198,5 79,8 194,8 82,5

235,4 64,0 222,5 70,1 217,2 72,8 209,2 77,1 201,0 81,7 195,5 84,9

242,2 64,8 229,6 70,5 223,5 73,4 213,3 78,4 201,7 84,1 193,2 88,3

kWf = Cooling capacity in kW kWe = Compressor power input in kW To = Internal exchanger water outlet temperature in° C

COOLING PERFORMANCE

VERSION: PREMIUM

ACOUSTIC CONFIGURATION : EXTREMELY LOW NOISE (EN)

INTERNAL EXCHANGER PRESSURE DROP

THE WATER FLOW RATE CAN BE CALCULATED WITH THE FOLLOWING FORMULA:

kWf = COOLING CAPACITY [kW] DT = TEMPERATURE DIFFERENCE BETWEEN

WATER INLET / OUTLET

Q [l/s] = kWf / (4,186 x DT)

THE AIR SIDE PRESSURE DROPS ARE RELATIVE TO THE MEDIUM AIR TEMPERATURE OF 7°C

Q = AIR FLOW [l/s] DP = PRESSURE DROP [kPa]

ADMISSIBLE WATER FLOW RATE

352 402 432 452 502 552 602 702 802

Qmin 2,3 2,6 2,9 3,2 3,6 3,9 4,4 4,9 5,5 [l/s]

Qmax 6,6 7,4 8,1 9,0 10,2 11,1 12,2 13,5 15,1 [l/s]

Min. (Qmin) and max. (Qmax) water flow-rates admissible for a correct unit operation.

2 3 4 5 6 7 8 9 2015

20

30

40

50

60

70

80

90

100

Q [l/s]

P [

kP

a]

35

2

402

43

2

452

50

2

552

60

2

702

80

2

To the internal exchanger pressure drops must be added the pressure drops of the steel mesh mechanical filter that must be placed on the water input line. It is a device compulsory for the correct unit operation, and it is available as Clivet option (see the HYDRONIC GROUP ACCESSORIES). If the mechanical filter is selected and installed by the Customer, it is forbidden the use of filters with the mesh pitch higher than 1,6 mm, because they can cause a bad unit operation and also its serious damaging.

Page 24: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

24

®

BT10E005GB-02

ELFOENERGY LARGE2

Configuration which allows hot water production

free-of-charge during the cooling function, thanks to the

recovery of part of the condensation heat which would

otherwise be disposed of into the external heat source.

This configuration is also known as "desuperheating coil". It is

made up of brazed-plate exchanger in AISI 316 stainless steel

which is ideal for recovering around a quarter of the heating capacity of the unit (equal to the sum of the cooling capacity and the absorbed power input of the compressors).

The partial recovery device is considered to be working when it is supplied by the flow of water to be heated. This condition improves the unit performance, since it reduces the condensation temperature: in nominal conditions, the cooling capacity increases indicatively by 3,2% and the absorbed power input from the compressors is reduced by 3,6%.

When the temperature of the water to be heated is particularly

low, it is opportune to insert a flow regulation valve in the

hydraulic circuit, to maintain the recovery output temperature

at higher than 35°C and thus avoid refrigerant condensation in

the partial energy recovery device.

INTERNAL EXCHANGER PRESSURE DROP - PARTIAL ENERGY RECOVERY

5

10

15

20

25

30

35

40

45

0,5 1 1,5 2 2,5 3 3,5 4 4,5 5 5,5 6

Q [l/s]

432-452352 402 552-602 702-802502

ΔP

[kP

a]

Q WATER FLOW RATE [l/s] DP PRESSURE DROP [kPa]

CONFIGURATIONS

D - PARTIAL ENERGY RECOVERY

D - Partial recovery device 1. Internal exchanger 2. Compressors 3. Recovery exchanger 4. External exchanger 5. Electronic expansion valve

TW in Chilled water Inlet TW out Chilled water Outlet RW in Recovery water inlet RW out Recovery water outlet AE Outdoor air

B - WATER LOW TEMPERATURE

Configuration also known as "Brine". Enables a non-freezable solution to be cooled (for instance, water and ethylene glycol in appropriate quantities) up to a temperature of between +4°C and –7°C.

Includes:

- Appropriate exchangers, complete with thick closed-cell insulation;

- Electronic-type expansion valve, functional calibration and safety devices adapted to the particulars of use.

In the selection phase, it is necessary to indicate the type of function required, and the unit will be optimised with:

- Unit with single working set-point (only at low temperature)

- Unit with double working set-point.

The unit in this configuration have a different operation field, indicated on the previous pages.

In the low temperature operation, some partialisation degrees could be not available. For more information, contact our Sales Department.

Consult the appropriate table, shown in the final section, to verify the compatibility between the different options.

D

AE

35°C

45°C

RW out

40°C

RW in

7°C

TW out

12°C

TW in

T

TEEV

1

4

3

2

5

Page 25: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

25

®

BT10E005GB-02

ELFOENERGY LARGE2

Configuration which allows hot water production free-of-charge during the cooling function, thanks to the total recovery of the

condensation heat which would otherwise be discharge into the external heat source. This solution increases the overall

efficiency of the system in all cases in which a high-level of hot water production is requested.

It is made up of 316 Stainless steel brazed plate heat exchanger, which is ideal for recovering the entire unit heating capacity

(equal to the sum of the cooling capacity and the absorbed power input of the compressors), from the on-of type solenoid

valves, the temperature sensors for the hot water circuit supply and return and the relative integrated logic controller with two

partialisation steps.

La disponibilità di acqua calda è sempre subordinata alla produzione di acqua refrigerata. Si veda il seguente esempio:

1. Cooling capacity request = 100% / Heat capacity request = 0%→ Cooling capacity production only.

2. Cooling capacity request = 100% / Heat capacity request = 100%→ Cooling capacity production and heat capacity

production by recovery.

3. Cooling capacity request = 50% / Heat capacity request = 100%→ Cooling capacity production and heat capacity

production by recovery, equals 50% of the requested heat capacity.

R - TOTAL ENERGY RECOVERY

INTERNAL EXCHANGER PRESSURE DROP - TOTAL RECOVERY ENERGY

To avoid constant switching in the cooling circuit should be added to a adequate capacity storage tank in the hot water circuit of the system.

TOTAL ENERGY RECOVERY NOT OPERATING

When the set-point recovery is fulfilled, the coil is reactivated. In this condition the total recovery circuit operates as a partial recovery (desuperheater).

TOTAL ENERGY RECOVERY OPERATING

When hot water is required, the condensing coil is turned off. The condensation takes place entirely in the recovery circuit.

R - Total recovery device

1 Internal exchanger 2 Compressors 3 Recovery exchanger 4 Total recovery enabling valve 5 External exchanger enabling valve

6 External exchanger 7 Electronic expansion valve T Temperature probe

TW in Chilled water inlet TW out Chilled water outlet RW Recovery water inlet RW out Recovery water outlet

AE Outdoor air

Q WATER FLOW RATE [l/s] DP PRESSURE DROP [kPa]

AE

35°C

45°C

RW out

40°C

RW in

7°C

TW out

12°C

TW in

T

TEEV

1

6

4

5

3

2

7

R

20

30

40

50

60

70

80

90

100

3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18Q [l/s]

ΔP

[kP

a]

If the hot water circulation is not present on the heat recovery exchanger, the maximum inlet air temperature decreases of about 2 °C compared to units without 'Total Energy Recovery'.

AE

35°C

45°C

RW out

44°C

RW in

7°C

TW out

12°C

TW in

T

TEEV

1

6

4

5

3

2

7

R

Page 26: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

26

®

BT10E005GB-02

ELFOENERGY LARGE2

AE

35°C

7°C

TW out

12°C

TW in

EEV

1

5

3

2

6

4T

AE

0°C

10°C

TW out

15°C

TW in

1

5

6

3

2

EEV

4 T

AE

11°C

10°C

TW out

15°C

TW in

EEV

1

5

6

3

2

4T

FCD - DIRECT FREE-COOLING

Configuration which enables great savings on the management costs of the system in applications which require chilled water even during cold seasons like, for instance, industrial processes, data centres, telecommunications, technological applications and trade centres.

When the external air temperature is less than the temperature of the return water in the system, the FREE-COOLING system recovers coolness from outdoor and reduces the compressor working up to their being withdrawn completely.

The higher the temperature of the chilled water in the system (e.g. 10-15°C instead of 7-12°C), the greater the field of application of the FREE-COOLING system and, therefore, the energy saving.

USING UNFREEZABLE SOLUTIONS

The FREE-COOLING configuration is particularly indicated in buildings where, at least at certain times of the year, the external air

temperature also reaches very low values. For this reason, the liquid must be protected from the risk of freezing, typically by adding

an appropriate anti-freeze substance such as ethylene glycol. The percentage of glycol in the solution depends on the minimum

temperature value foreseen in the installation area, and in any case, remains within the main parameters of the system design.

TECHNICAL DESCRIPTION

In comparison with standard units, Clivet units in the direct FREE-COOLING configuration also include:

three-way switching valve with on/off regulation Finned water-air COIL exchanger (FREE-COOLING coil) additional outdoor air temperature sensor and control logic dedicated flush hydraulic connections.

(A) SUMMER SEASON

In the summer, with external air temperatures greater than the return temperature of the system liquid, the three-way valve is switched in such a way as to exclude the FREE-COOLING coils.

The cooling of the liquid is referred to the direct expansion circuit, via the workings of the compressors as in a traditional chiller.

(B) INTERMEDIATE SEASON During the intermediate season, or rather when the external air temperature is a little less than the temperature of the return water in the system, when the system senses that the external air temperature conditions are favourable:

it switches the position of the three-way valve forcing the solution to transit through the FREE-COOLING coils before reaching the evaporator;

it puts the fans to their maximum speed to exploit as much as possible the solution cooling using the outdoor air ; it undertakes the initial cooling of the solution in a "natural and free" way; it supplies any missing capacity through the chiller cycle, using the compressors functioning partially (the absorbed power input is proportional to the level of partialisation).

In case of an increase in the external air temperature, the microprocessor automatically converts the unit functioning to the summer setting, guaranteeing the conditions requested by the user at all times.

(C) WINTER SEASON During the winter season, with the temperature of the external air lower than the temperature of the return water in the system, the system senses that conditions are favourable for the FREE-COOLING function:

the three-way valve is switched as in the previous case, forcing the solution to transit through the FREE-COOLING coils before reaching the evaporator; the external air temperature brings the solution to the FREE-COOLING coil output already at the temperature requested by the user; the microprocessor management totally deactivates all the compressors supplying all the requested cooling capacity AT NO COST, in contrast to traditional chillers.

The difference between the outdoor air temperature and that requested by the user can also be such as to lower the solution temperature at the FREE-COOLING coil output to below the set-point requested for this use. This is a condition which does not compromise unit safety thanks to the presence of anti-freeze in the solution. The microprocessor modulates the fan speed until their withdrawal. If, with all the fans switched off, the temperature continues to go down, the three-way valve automatically positions itself in the summer setting, thus enabling the set-point to be maintained.

D - Partial recovery device

1. Internal exchanger 2. Compressors

3. Recovery exchanger 4. External exchanger 5. Electronic expansion valve TW in Chilled water Inlet

TW out Chilled water Outlet

RW in Recovery water inlet RW out Recovery water outlet AE Outdoor air

A

MANAGEMENT LOGIC

There are three main function modes, which can be differentiated in essence by the position of the three-way switching valve and by the number of active compressors.

B

C

Page 27: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

27

®

BT10E005GB-02

ELFOENERGY LARGE2

UNIT PERFORMANCES IN THE DIRECT FREE-COOLING CONFIGURATION

The unit performance in the direct FREE-COOLING configuration also depends on the antifreeze percentage used in the circuit and are shown below in two main operating modes.

(1) Data referred to the following conditions: - water temperature: 15°C inlet / 10°C outlet - glycol percentage 30%

2

4

6

8

10

12

14

16

18

20% 30% 40% 50% 60% 70% 80% 90% 100%

DT

[°C

]

% FC

352-452-702

402-502-552

432

602-802

OPERATING MODE: DEACTIVATED DIRECT FREE-COOLING

To consider the standard unit performance at the requested conditions and apply the following correction factors.

EXAMPLE Determine the performance of the following units : WSAT-XEE FCD 702 SC EXC (EXCELLENCE version, direct FREE-COOLING configuration), with water = 15/10 °C / 30% glycol / Outdoor air 35°C Reference:

WSAT-XEE S 702 SC EXC Cooling capacity = 214,8 kW / Electric compressor capacity = 56,9 kW

Calculation:

WSAT-XEE FCD 702 SC EXC (Direct FREE-COOLING) Cooling capacity = 214,8 x 0,95 = 204,1 kW / Electric compressor capacity = 56,9 x 1,03 = 58,6 kW

OPERATING MODE: ACTIVATED DIRECT FREE-COOLING

When the outside air temperature increases, the cooling capacity of FREE-COOLING decreases (at the same temperature of water on returning from). If you know the cooling capacity required by the system, you can calculate the maximum outside air temperature from which the cooling capacity is available through FREE-COOLING. Below this temperature, the required power is supplied only by modulation of the air flow fans.

EXAMPLE Determine the performances with outdoor air = +1°C for the following unit: WSAT-XEE FCD 702 SC EXC, EXCELLENCE version, Direct FREE-COOLING configuration), with water at 15/10 °C / 30% glycol. Reference:

WSAT-XEE FCD 702 SC EXC FREE-COOLING nominal capacity = 204 kW (from table - Water 15/10 ° C / 30% glycol / outdoor air temperature 0 ° C) Calculation: Approach between the system outlet water temperature and the outdoor air = 15°C - 1°C = 14°C

From the graph: FREE-COOLING percentage = 93% FREE-COOLING capacity at +1°C of outdoor temperature = 204 x 93% = 189,7 kW

KEY DT Approach between the system outlet water temperature and the outdoor air %FC FREE-COOLING percentage (compared with the FREE-COOLING nominal capacity)

Size (SC / EN Version) 352 402 432 452 502 552 602 702 802

Free-cooling nominal capacity (1) kW 101 113 126 136 148 160 181 204 227

°C 0,5 -0,5 -2,0 0,0 -0,5 -1,0 -2,5 0,0 -2,5 Temperature wih Free-cooling at 100% (1)

Percentage weight of ethylene glycol 10% 20% 30% 40%

Cooling power factor 0,97 0,96 0,95 0,94

Compressor input factor 1,040 1,034 1,030 1,027

Page 28: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

28

®

BT10E005GB-02

ELFOENERGY LARGE2

HYDRONIC GROUP ACCESSORIES

1PUS - STANDARD PUMP

Option supplied built-in. Centrifugal electro-pump, with AISI type 304 stainless steel body and rotor. Mechanical seal using ceramic, carbon and EPDM elastomer components. Three-phase electric motor with an IP55 protection. Complete with thermoforming insulating shell, rapid attachments with insulating shells, non-return valve, safety valve, manometers, system load safety pressure switch, stainless steel anti-freeze immersion heaters set on inlet and supply. The different available models can be set apart by the useful prevalence of the system.

1PU1SB - STANDARD PUMP WITH EMERGENCY PUMP

Option supplied built-in. Two centrifugal electro-pumps one of which is in stand-by, with AISI type 304 stainless steel body and impeller. Mechanical seal using ceramic, carbon and EPDM elastomer components. Three-phase electric motor with an IP55 protection. Complete with thermoforming insulating shell, rapid attachments with insulating shells, non-return valve, safety valve, manometers, system load safety pressure switch, stainless steel anti-freeze immersion heaters set on inlet and supply. The built-in microprocessor controller balances the working hours and in case of any breakdown signals the fault and automatically activates the reserve pump. The different available models can be set apart by the useful prevalence of the system

The 1PUS and 1PU1SB options are supplied as standard with a hydraulic connection kit on the system return (to be installed externally to the unit, by the Customer). The kit is made up of:

no. 1 cast-iron butterfly shut-off valve, complete with activating handle and mechanical calibration lock no. 1 rapid connection

A300 / A500 - 300 / 500 LITRES STORAGE TANK

Option supplied built-in. Stainless steel storage tank complete with double-sheeted coating with closed-cell insulation, stainless steel anti-freeze immersion heater, bleed valve, discharge cock, cast-iron butterfly shut-off valve with rapid attachments and activating handle with mechanical calibration lock at the evaporator output, rapid attachments with insulation shells. The available models have different static pressure.

The A300 and A500 options are supplied as standard with the hydraulic connection kit on the system return (to be installed externally to the unit, by the Customer). The kit is made up of:

no. 1 cast-iron butterfly intercept valve, complete with activating handles and mechanical calibration lock no. 1 rapid connection

1 Internal exchanger 2 Shut-off valve 3 Bleed valve 4 Storage tank with antifreeze heater 5 Drain valve 6 Shut-off valve with rapid connection 7 Steel mesh filter water side

8 Manometer 9 Safety valve (6 Bar) 10 Closed couple pumps with high efficiency

impellers 11 Non-return valve

12 Safety pressure switch system load (Prevents the operation of the pumps in case of lack of

water)

TW in Cooling water inlet

TW out Cooling water outlet

- - - Standard Hydraulic connection Kit

The gray area indicates additional optional

components.

STANDARD PUMP / STANDARD PUMP WITH EMERGENCY PUMP

STORAGE TANK

7°C

TW out

12°C

TW in

A

1

12

98

11 11

10 10

98

2

IFWX

6

7

2

7°C

TW out

12°C

TW in

A

1

12

98

11 11

10 10

98

4

5

3

2

IFWX

6

7

2

7°C

TW out

12°C

TW in

1

4

5

3

IFWX

6

7

2

STANDARD PUMP / WITH EMERGENCY PUMP AND STORAGE TANK

Page 29: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

29

®

BT10E005GB-02

ELFOENERGY LARGE2

VERSION: EXCELLENCE

0

20

40

60

80

100

120

140

160

180

200

220

240

260

2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5 9 9,5 10 10,5 11

ΔP

[K

Pa

]

Q [l/s]

PU1

60

2

80

2

55

2

40

2

43

2

35

2

50

2

70

2

45

2

PU2

PU3

PU4

PU6

PU5

VERSION: PREMIUM

0

20

40

60

80

100

120

140

160

180

200

220

240

260

2 2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5 9 9,5 10 10,5 11

ΔP

[K

Pa

]

Q [l/s]

PU1

60

2

80

2

55

2

40

2

43

2

35

2

50

2

70

2

45

2

PU2

PU3

PU4

PU6

PU5

Attention: to obtain the values of available head, the heads represented on these charts must be decreased by: Evaporator pressure drop IFVX Accessory - Steel mesh filter water side (if supplied)

SINGLE PUMP TECHNICAL FEATURES

PUMP NOMINAL CAPACITY [kW] NOMINAL CURRENT [A]

PU1 1,4 2,6

PU2 1,4 2,6

PU3 1,8 3,2

PU4 1,8 3,4

PU5 2,9 4,8

PU6 3,3 5,6

1PUS / 1PU1SB PERFORMANCE OPTIONS

Page 30: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

30

®

BT10E005GB-02

ELFOENERGY LARGE2

A300RPS / A500RPS - 300 / 500 LITRES STORAGE TANK WITH PRIMARY CIRCUIT BUILT-IN

Option supplied built-in. Simplifies system design and manufacture. Available only with ‗1PUS option - Standard pump or‘ ‗1PU1SB - Standard pump with emergency pump‘. This accessory includes components designed for the A300 / A500 option and:

Primary circuit, already built and tested on the unit cast-iron butterfly shut-off valve, with rapid connection and activating handle and mechanical calibration lock in evaporator outlet and on the pump suction

A300RPS / A500RPS options are available only with ―Low head pump‖ option.

0

5

10

15

20

25

30

2 4 6 8 10 12 14

P [k

Pa

]

Q [l/s]

IFWX - STEEL MESH FILTER WATER SIDE

The device prevents fouling of the exchanger by any impurities in the hydraulic circuit. The mechanical filter mesh stainless steel should be placed on the water inlet. It is easily removed for periodic maintenance and cleaning. Also includes:

cast-iron butterfly shut-off valve, with rapid connection and activating handle and mechanical calibration lock; rapid connections with insulating protection.

Accessories supplied separately

Installation by the User, outside the unit

352÷802

Diameter 2 1/2’’

Filtering degree 1,6 mm

SIZE

Q = WATER FLOW [l/s] DP = PRESSURE DROP WATER SIDE[kPa]

STEEL MESH FILTER PRESSURE DROP STEEL MESH FILTER CHARACTERISTICS

Pressure drop with clean filter

Check the presence of the necessary hydraulic shut off valve on the system, to the periodic maintenance

1 Internal exchanger 2 Shut-off valve 3 Bleed valve 4 Storage tank with antifreeze heater 5 Drain valve 6 Shut-off valve with rapid connection 7 Steel mesh filter water side 8 Manometer 9 Safety valve (6 Bar) 10 Closed couple pumps with high efficiency impellers 11 Non-return valve

12 Safety pressure switch system load (Prevents the operation of the pumps in case of lack of water)

TW in Cooling water inlet

TW out Cooling water outlet

The gray area indicates additional optional components.

7°C

TW out

12°C

TW in

IFWX

A

1

12

98

11 11

10 10

9824

5

3

6

7

2

Page 31: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

31

®

BT10E005GB-02

ELFOENERGY LARGE2

ABU - FLUSH HYDRAULIC CONNECTIONS

Option which simplifies the hydraulic connections which otherwise occur within the unit (by the Customer).

Includes from internal piping to the external unit panel, two rapid flush connections, two "welding" pipes for connecting to the

system by the Customer.

IMPORTANT! The flush hydraulic connections are supplied as a standard in the unit complete with the following options:

Direct FREE-COOLING configuration Standard pump / Standard emergency pump Storage tank Storage tank with a primary circuit built-in HYDROPACK

GENERAL NOTE

It is also opportune to provide for the following system components, which are not included in the Clivet supply.

Shut-off valve, where it is not already provided for in the Clivet supply.

Support devices for the piping and anti-vibration flexible joints.

Expansion vessel (example for closed-circuit system)

Supply control thermometer Additional vent and discharge valves where necessary

A - STANDARD UNIT

B - UNIT WITH ABU OPTION

The accessory is supplied built-in.

Scheme, not in scale

Page 32: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

32

®

BT10E005GB-02

ELFOENERGY LARGE2

2PM - HYDROPACK WITH TWO PUMPS

Option supplied built-in. Pumping station made up of two parallel electro-pumps, with modular self-adapting activation logic.

Enables an automatic reduction in liquid flow in critical conditions, avoiding blocks due to overloading and consequential interventions by specialised technical personnel.

Centrifugal electro-pump, with AISI type 304 stainless steel body and impeller.

Mechanical seal using ceramic, carbon and EPDM elastomer components. Three-phase electric motor with an IP55 protection. Three-phase electric motor with an IP55 protection grade. Complete with thermoforming insulating shell, rapid connections with insulating shells, non-return valve, safety valve, manometers, system load safety pressure switch, stainless steel anti-freeze immersion inlet and supply resistances.

The different available models can be set apart by the useful prevalence of the system.

HYDROPACK

The 2PM option is supplied as standard with the hydraulic connection kit on the system return (to be installed externally to the unit, by

the Customer). The kit is made up of:

no. 1 cast-iron butterfly intercept valve, complete with activating handles and mechanical calibration lock no. 1 rapid connection

The 2PM option is:

compatible with the A300 / A500 option - 300 / 500 litre storage tank not compatible with the A300RPS / A500RPS option - 300 / 500 litres storage tank with a primary circuit built-in.

11 Internal exchanger 2 Compressors 3 Recovery exchanger 4 Total recovery enabling valve 5 External exchanger enabling valve 6 External exchanger 7 Electronic expansion valve

T Temperature probe

TW in Chilled water inlet TW out Chilled water outlet RW Recovery water inlet RW out Recovery water out

- - - Standard Hydraulic connection Kit

The gray area indicates additional optional

components.

HYDROPACK HYDROPACK WITH STORAGE TANK

The 2PM option is supplied with a kit made up of 2 blind rapid connections, for the removal of a pump in case of maintenance.

7°C

TW out

12°C

TW in

1

12

98

11 11

10 10

98

2

IFWX

6

7

2

7°C

TW out

12°C

TW in

1

12

98

11 11

10 10

93

84

5

2

IFWX

6

7

2

Page 33: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

33

®

BT10E005GB-02

ELFOENERGY LARGE2

0

20

40

60

80

100

120

140

160

180

200

220

240

260

2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5 9 9,5 10 10,5 11 11,5 12 12,5 13

ΔP

[K

Pa

]

Q [l/s]

2 x PU1

60

2

80

2

55

2

40

2

43

2

35

2

50

2

70

2

45

2

2 x PU2

2 x PU3

2 x PU5

2 x PU6

0

20

40

60

80

100

120

140

160

180

200

220

240

260

2,5 3 3,5 4 4,5 5 5,5 6 6,5 7 7,5 8 8,5 9 9,5 10 10,5 11 11,5 12 12,5 13

ΔP

[K

Pa

]

Q [l/s]

2 x PU1

60

2

80

2

55

2

40

2

43

2

35

2

50

2

70

2

45

2

2 x PU2

2 x PU3

2 x PU5

2 x PU6

SINGLE PUMP TECHNICAL CHARACTERISTICS

PUMP NOMINAL CAPACITY [kW] NOMINAL CURRENT [A]

2PU1 2 x 1,4 2 x 2,6

2PU2 2 x 1,4 2 x 2,6

2PU3 2 x 1,8 2 x 3,2

2PU5 2 x 2,9 2 x 4,8

2PU6 2 x 3,3 2 x 5,6

VERSION: EXCELLENCE

VERSION: PREMIUM

Attention: to obtain the values of available head, the heads represented on these charts must be decreased by: Evaporator pressure drop IFVX Accessory - Steel mesh filter water side (if supplied)

PERFORMANCES OF THE 2PM OPTION (HYDROPACK)

Page 34: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

34

®

BT10E005GB-02

ELFOENERGY LARGE2

ACCESSORIES

PGFC - FINNED COIL PROTECTION GRILL

This accessory is used to protect the external coil from the accidental contact with external things or people. Ideal for installation in places where is possible the passage of people such as parking, terraces, etc.

The accessory is supplied built-in.

PGCCH - ANTI-HAIL PROTECTION GRILLES

This accessory is used to protect the external coil from hail. The hail can deform the fins of the Exchange worsting heat exchange with air.

The accessory is supplied built-in.

CCCA - COPPER / ALUMINIUM CONDENSER COIL WITH ACRYLIC LINING

Batteries with copper tubes and aluminium fins with acrylic paint. They can be used in the presence of saline concentrations in the air and other weathering agents moderately aggressive.

Option is not suitable for application in sulphureous ambient.

CCCC - COPPER / COPPER CONDENSER COIL

Exchange with copper tubes, copper fins and brass shell. They can be used in the presence of saline concentrations in the air and other weathering agents moderately aggressive.

Option is not suitable for application in sulphureous ambient.

CCCA1 - COPPER / ALUMINIUM CONDENSER COIL WITH FIN GUARD (SILVER) TREATMENT

Treatment that offers an optimum heat exchange and guaranteed over time and protects against corrosion finned heat exchangers. They can be used in the presence of saline concentrations in the air and other aggressive chemical agents, keeping the performance of the exchanger constant over time.

AMMX - SPRING ANTIVIBRATION MOUNTS

The spring anti-vibration devices are fastened in housings on the longitudinal members.  They reduce the vibrations caused by the machine, reducing the noises transmitted by the support structures.

Accessory is supplied separately

Page 35: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

35

®

BT10E005GB-02

ELFOENERGY LARGE2

FANQE - ELECTRICAL PANEL VENTILATION

The device is installed and tested built-in.

This option is necessary for very hot climates, where the external temperature can be between +40°C and +50°C. It is made up of a forced ventilation system, activated by a thermostat, which provides for the correct usage temperature to be maintained by the components inside the electrical panel. The option includes a thermostat which activates forced ventilation when necessary.

In order to guarantee that the correct unit operation, the temperature inside the unit must not exceed 50°C. Therefore, during storage or when the unit is already installed but not powered, it is necessary to avoid exceeding the above-indicated temperature. When the unit has been installed, the protection and safety devices are only active with the power supply switched on and the unit not isolated.

This accessory functions at all times even when the unit is switched off as long as the electricity supply is maintained and the unit is not isolated.

RE-20 / RE-25 / RE-30 / RE-35 / RE-39 - PROTEZIONE ANTIGELO QUADRO ELETTRICO

This option is necessary for very cold climates, where the external temperature can be between -10°C and -39°C. It includes thermostat self-regulating heaters which are able to protect the electric panel from condensation and frost, guaranteeing its correct operation. The selection of devices is carried out based on the minimum temperatures reached at the unit installation site.

This addiction element stay always switch on also when the unit is switch off as long as to keep the supply power on.

The device is installed and tested built-in.

This accessory does not lead to substantial variations in the electrical data of the unit declared in the section Electrical Data.

This accessory is necessary for the correct unit operation in the FCD (FREE-COOLING) configuration with external temperatures below –10°C. Furthermore, it is necessary for the units to be maintained correctly in all the remaining configurations (not functioning).

The device is installed and tested built-in.

PM - PHASE MONITOR

The phase monitor makes it possible to check the correct connection of the phases and their imbalance in units powered with a tri-phase system. If the connection of the phases is not correct, or the threshold of phase imbalance is exceeded, or the voltage is too high or too low for a certain amount of time, the monitor acts on the control circuit and orders the unit to be shut down. As soon as nominal line conditions are restored, the unit is automatically reset. As soon as nominal line conditions are restored, the unit reset is manual.

PFCP - POWER FACTOR CORRECTION CAPACITORS

The component is necessary to lower the phase difference between current and voltage in the electromagnetic components of the machine, such as asynchronous motors. By re-phasing it is possible to reduce the intensity of the line current by reducing a part of the power of the mains (reactive power). This often leads to an economic benefit which the energy provider grants to the final user. The component makes it possible to bring the cosfi power factor to values which on average are greater than 0.9.

The device is installed and tested built-in.

Option also known as 'Soft starter'. Electronic device that automatically and gradually starts the compressors reducing the start-up current of about 40% in comparison with the nominal value. It follows that the electrical power and its protective devices can be sized with lower parameters , so with a lower cost of initial investment.

SFSTR - BREAKAWAY CURRENT REDUCING DEVICE

The device is installed and tested built-in. RPM

I

- - - CURRENT ABSORBED WITHOUT SFSTR OPTION

— CURRENT ABSORBED WITH SFSTR OPTION

Nominal operating point

ELFOEnergy LARGE2 ELECTRICAL DATA (SERIES WSAT-XEE) WITH SFSTR OPTION

SIZE 352 402 432 452 502 552 602 702 802

M.I.C. MAXIMUM INRUSH CURRENT

M.I.C. - Value (EXCELLENCE VERSION) A 167 179 189 216 222 230 244 298 313 M.I.C. - Value (PREMIUM VERSION) A 167 179 184 212 217 226 240 294 309

Page 36: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

36

®

BT10E005GB-02

ELFOENERGY LARGE2

CREFP - DEVICE FOR FAN CONSUMPTION REDUCTION OF THE EXTERNAL SECTION WITH VARIABLE SPEED (PHASE-CUTTING) (ONLY EXCELLENCE VERSION)

External axial fan option. This device is installed as an alternative to the ECOBREEZE that is standard on the EXCELLENCE version. It provides the three-phase electric motor with external rotor and built-in thermal protection, running IP54. It is equipped with variable speed control.

The device is installed and tested built-in.

MHP - HIGH AND LOW PRESSURE GAUGESMANOMETRI

Although the standard unit permit already to show the digital parameters of pressure of the refrigeration circuit, this option allow the analogic measures of the refrigerant pressures on suction and compression, giving a most easy way to check the work parameters from specialists in the field. The two liquid pressure gauges and corresponding pressure sockets are installed on the machine in an easily accessible location.

This option integrates the shut-off valve, supplied as standard. The presence of the shut-off valve

also on the inlet enables the compressors to be isolated and substituted without discharging the

refrigerant from the entire chiller circuit. Extraordinary maintenance activities are thus eased.

SDV - SHUT-OFF VALVE ON COMPRESSOR SUCTION AND DISCHARGE

The device is installed and tested built-in.

1 Compressors 2 Shut-off valve 3 Safety valve 4 SDV option

KRIX - KIT FOR REMOTE MICROPROCESSOR REMOTE CONTROL INTERFACE

2 x 0.25 mm2 MAX 1000 m

230/1/50Power input

Unit connection. Shielded cable .

This accessory permits to be install keyboard in a remote position . It includes the compartment and the power transformer. To be connected during commissioning of the unit at a maximum distance of 1000 m.

Separately provided accessory

The compartment must be installed on a wall using appropriate anchors. It can also be mounted on wall box universal 503 (installation by the costumer)

The transformer is designed for DIN rail. It must be powered at 230/1/50 and electrically connected to the multifunction keypad compartment (installation by the costumer)

The device is installed and tested built-in.

2

1

34

Page 37: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

37

®

BT10E005GB-02

ELFOENERGY LARGE2

UNIT STATUS

0 OFF

1 LOCAL ON

2 FROM SERIAL

SELECTOR POSITION

Option to display the compressor operating status from the remote location . The contacts are available in a special terminal block.

CFSC - FREE CONTACTS FOR COMPRESSOR STATE

The three-position selector allows the following actions:

Sequential unit switching off that allows its next correct restarting Enabling to the unit starting from the built-in multifunction keypad. Enabling to the unit starting via serial port from remote supervisor.

Option to display the compressor operating status from the remote location . The contacts are available in a special terminal block.

210

The device allows variation of the set-point pre-set by an external signal of type 4÷20 mA.

The device allows the automatic adjustment of the set-point pre-set depending on outside air temperature. It provides the sliding temperature of the liquid, that is variable depending on external conditions, for the benefit of saving energy of the system.

The device allows variation of the set-point pre-set by an external signal of type 0÷10 V.

5

6

7

8

9

10

11

12

13

14

0 1 2 3 4 5 6 7 8 9 10

Se

t-P

oin

t [°

C]

Input [V]

4

5

6

7

8

9

10

11

12

13

14

4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

Se

t-P

oin

t [°

C]

Input [mA]

6

7

8

9

10

11

12

13

12 14 16 18 20 22 24 26 28 30 32 34 36

Se

t-P

oin

t [°

C]

Air Temperature (dry bulb) [°C]

SPC4 - SPC4 - SET POINT COMPENSATION WITH 0-10 V SIGNAL

SPC2 - SET POINT COMPENSATION WITH OUTSIDE TEMPERATURE PROBE

SPC1 - SET POINT COMPENSATION WITH 4-20 mA

The device is installed and tested built-in.

MAX 24V 1A

-+

MAX 24V 1A

-+

CLSCLR - FREE CONTACTS FOR COMPRESSOR STATE AND FOR OPERATION IN LOCAL/REMOTE MODE

Page 38: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

38

®

BT10E005GB-02

ELFOENERGY LARGE2

The device is installed and tested built-in.

CMSC10 - LonWorks SERIAL CONVERTER KIT

It allows serial connection of supervision systems, using LonWorks as the communication protocol. It allows access to a list of operating variables, control and alarms compliant with the Echelon® standard.

The device is installed and tested built-in.

CMSC8 - BACnet SERIAL CONVERTER KIT

It allows serial connection of supervision systems, using BACnet or SNMPv3.0 as the communication protocol. It allows access to the complete list of operating variables, controls and alarms. The device has the following communication ports:

2 serial ports configurable as RS232 or RS485 protocols available for MODBUS and BACnet MSTP; 1 RJ45 Ethernet port for BACnet IP, SNMPv3, TCP / IP.

The device configuration is done through the integrated Web Server Linux can be done from a PC connected to the network.

The configuration and management of the BACnet network are by the Customer

The configuration and management of the LonWorks network are by the Customer

The LonWorks technology uses LonTalk® protocol for the communication between network nodes. Contact your service provider for more information

ETHERNET

SPC3 - SET POINT COMPENSATION ACCORDING TO THE OUTSIDE ENTHALPY

The device allows the automatic adjustment of the unit set-point according to the external enthalpy. It provides the sliding temperature of the liquid, that is variable depending on external conditions, for the benefit of saving energy of the system.

The device is installed and tested built-in.

Page 39: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

39

®

BT10E005GB-02

ELFOENERGY LARGE2

FOULING CORRECTION FACTOR

INTERNAL EXCHANGER

m² °C/W F1 FK1

0.44 x 10^(-4) 1,00 1,00

0.88 x 10^(-4) 0,97 0,99

1.76 x 10^(-4) 0,94 0,98

F1 = Cooling capacity correction factors FK1 = Compressor power input correction factor

CORRECTION FACTOR FOR ANTIFREEZE SOLUTIONS

5% 10% 15% 20% 25% 30% 35% 40% % ethylene glycol by weight

Freezing temperature °C -2,0 -3,9 -6,5 -8,9 -11,8 -15,6 -19,0 -23,4

Safety temperature °C 3,0 1,0 -1,0 -4,0 -6,0 -10,0 -14,0 -19,0

Cooling capacity factor Nr 0,995 0,990 0,985 0,981 0,977 0,974 0,971 0,968

Compressor input factor Nr 0,997 0,993 0,990 0,988 0,986 0,984 0,982 0,981

Internal exchanger glicol solution flow factor Nr 1,003 1,010 1,020 1,033 1,050 1,072 1,095 1,124

Pressure drop factor Nr 1,029 1,060 1,090 1,118 1,149 1,182 1,211 1,243

The correction factors shown refer to water and glycol ethylene mixes used to prevent the formation of frost on the exchangers in the water circuit during inactivity in winter.

PLATE EXCHANGER OPERATING LIMITS

INTERNAL EXCHANGER

DPr DPw

kPa kPa

CLIVET (C) 4500 1000

PED (CE) 4500 1000

DPr = Maximum operating pressure on refrigerant side DPw = Maximum operating pressure on water side

OVERLOAD AND CONTROL DEVICE CALIBRATION

OPEN CLOSED VALUE

High pressure switch kPa 4050 3300 -

Low pressure switch kPa 450 600 -

Low pressure switch (Brine) kPa 200 350 -

Antifreeze protection °C 3,0 5,5 -

High pressure safety valve kPa - - 4500

Low pressure safety valve kPa - - 3000

Max n° avviamenti del compressore per ora Nr - - 10

High compressor discharge temperature safety thermostat

°C - - 120

Page 40: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

40

®

BT10E005GB-02

ELFOENERGY LARGE2

OPTION COMPATIBILITY - WSAT-XEE SERIE / EXCELLENCE VERSION

Standard

o Option

X Not available

REF. DESCRIPTION 352 402 432 452 502 552 602 702 802

CONFIGURATION AND MAIN OPTIONS

B Water low temperature o o o o o o o o o

D Partial energy recovery o o o o o o o o o

R Total energy recovery o o o o o o o o o

FCD Direct FREE-COOLING o o o o o o o o o

B + D Water low temperature + Partial energy recovery o o o o o o o o o

B + R Water low temperature + Total energy recovery o o o o o o o o o

B + FCD Water low temperature + Direct FREE-COOLING x x x x x x x x x

D + FCD Partial energy recovery + Direct FREE-COOLING o o o o o o o o o

R + FCD Total energy recovery + Direct FREE-COOLING x x x x x x x x x

A300 300 l. storage tank o o o o o o o x x

A500 500 l. storage tank x x x x x x x o o

1PUS - Standard pump

(PU1) Pump type 1 o o o x x x x x x

(PU2) / (PU3) Pump type 2 / Pump type 3 o o o o o x x x x

(PU4) / (PU5) / (PU6) Pump type 4 / Pump type 5 / Pump type 6 o o o o o o o o o

+ D + Partial energy recovery o o o o o o o o o

+ D + A300 + Partial energy recovery + 300 l. storage tank o o o o o o o x x

+ D + A500 + Partial energy recovery + 500 l. storage tank x x x x x x x o o

+ A300RPS (PU1) + 300 l. storage tank with primary circuit onboard o o o x x x x x x

+ A300RPS (PU4) + 300 l. storage tank with primary circuit onboard x x x o o o o x x

+ A500RPS (PU4) + 500 l. storage tank with primary circuit onboard x x x x x x x o o

1PU1SB - Standard pump with standby pump

(PU1) Pump type 1 o o o x x x x x x

(PU2) / (PU3) Pump type 2 / Pump type 3 o o o o o x x x x

(PU4) / (PU5) / (PU6) Pump type 4 / Pump type 5 / Pump type 6 o o o o o o o o o

+ D + Partial energy recovery o o o o o o o o o

+ D + A300 + Partial energy recovery + 300 l. storage tank o o o o o o o x x

+ D + A500 + Partial energy recovery + 500 l. storage tank x x x x x x x o o

+ A300RPS (PU1) + 300 l. storage tank with primary circuit onboard o o o x x x x x x

+ A300RPS (PU4) + 300 l. storage tank with primary circuit onboard x x x o o o o x x

+ A500RPS (PU4) + 500 l. storage tank with primary circuit onboard x x x x x x x o o

2PM - Hydropack with 2 pumps

(PU1) Pump type 1 o o o o o o o o x

(PU2) / (PU3) Pump type 2 / Pump type 3 o o o o o o o o o

(PU4) Pump type 4 x x x x x x x x x

(PU5) / (PU6) Pump type 5 / Pump type 6 x x x x x x o o o

+ A300RPS + 300 l. storage tank with primary circuit onboard x x x x x x x x x

+ A500RPS + 500 l. storage tank with primary circuit onboard x x x x x x x x x

ACCESSORIES

CREFB Device for reducing consumption ECOBREEZE of the outdoor

section variable speed fans • • • • • • • • • CREFP

Device for reducing consumption of the outdoor section variable

speed fans (phase-cut) o o o o o o o o o

FCD + CCCA Direct FREE-COOLING + Copper / aluminium condenser co il with

acrylic liningo o o o o o o o o

FCD + CCCA1 Direct FREE-COOLING + Copper / aluminium condenser co il with Fin-

guard treatmentx x x x x x x x x

FCD + CCCC Direct FREE-COOLING + Copper /copper condenser co il x x x x x x x x x

Page 41: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

41

®

BT10E005GB-02

ELFOENERGY LARGE2

OPTION COMPATIBILITY - WSAT-XEE SERIE / PREMIUM VERSION

Standard

o Option

X Not available

REF. DESCRIPTION 352 402 432 452 502 552 602 702 802

CONFIGURATION AND MAIN OPTIONS

B Water low temperature o o o o o o o o o

D Partial energy recovery o o o o o o o o o

R Total energy recovery o o o o o o o o o

FCD Direct FREE-COOLING o o o o o o o o o

B + D Water low temperature + Partial energy recovery o o o o o o o o o

B + R Water low temperature + Total energy recovery o o o o o o o o o

B + FCD Water low temperature + Direct FREE-COOLING x x x x x x x x x

D + FCD Partial energy recovery + Direct FREE-COOLING o o o o o o o o o

R + FCD Total energy recovery + Direct FREE-COOLING x x x x x x x x x

A300 300 l. storage tank o o o o o o o x x

A500 500 l. storage tank x x x x x x x o o

1PUS - Standard pump

(PU1) Pump type 1 o o o x x x x x x

(PU2) / (PU3) Pump type 2 / Pump type 3 o o o o o x x x x

(PU4) / (PU5) / (PU6) Pump type 4 / Pump type 5 / Pump type 6 o o o o o o o o o

+ D + Partial energy recovery o o o o o o o o o

+ D + A300 + Partial energy recovery + 300 l. storage tank o o o o o o o x x

+ D + A500 + Partial energy recovery + 500 l. storage tank x x x x x x x o o

+ A300RPS (PU1) + 300 l. storage tank with primary circuit onboard o o o x x x x x x

+ A300RPS (PU4) + 300 l. storage tank with primary circuit onboard x x x o o o o x x

+ A500RPS (PU4) + 500 l. storage tank with primary circuit onboard x x x x x x x o o

1PU1SB - Standard pump with standby pump

(PU1) Pump type 1 o o o x x x x x x

(PU2) / (PU3) Pump type 2 / Pump type 3 o o o o o x x x x

(PU4) / (PU5) / (PU6) Pump type 4 / Pump type 5 / Pump type 6 o o o o o o o o o

+ D + Partial energy recovery o o o o o o o o o

+ D + A300 + Partial energy recovery + 300 l. storage tank o o o o o o o x x

+ D + A500 + Partial energy recovery + 500 l. storage tank x x x x x x x o o

+ A300RPS (PU1) + 300 l. storage tank with primary circuit onboard o o o x x x x x x

+ A300RPS (PU4) + 300 l. storage tank with primary circuit onboard x x x o o o o x x

+ A500RPS (PU4) + 500 l. storage tank with primary circuit onboard x x x x x x x o o

2PM - Hydropack with 2 pumps

(PU1) Pump type 1 o o o o o o o o x

(PU2) / (PU3) Pump type 2 / Pump type 3 o o o o o o o o o

(PU4) Pump type 4 x x x x x x x x x

(PU5) / (PU6) Pump type 5 / Pump type 6 x x x x x x o o o

+ A300RPS + 300 l. storage tank with primary circuit onboard x x x x x x x x x

+ A500RPS + 500 l. storage tank with primary circuit onboard x x x x x x x x x

ACCESSORIES

CREFB Device for reducing consumption ECOBREEZE of the outdoor

section variable speed fansx x x x x x x x x

CREFP Device for reducing consumption of the outdoor section variable

speed fans (phase-cut) • • • • • • • • •

X X X X X X X X X

Page 42: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

42

®

BT10E005GB-02

ELFOENERGY LARGE2

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)

W1 W2

W3 W4

G

5

7

40 1097 40

18

05

(Eco

bre

eze

+ 3

0m

m)

8

9

548 549

321

369

.5

250 2575 250

30

10

37

30

3075

329

16

0

33

44

6

M N

OP

13

50

13

50

700

2

1

OD

(10)

(12)

(11

)

(11

)

1000

EXC - SC EXC - EN

SIZE 352 402 432 352 402 432

M mm 1933 1946 2011 1933 1946 2011

N mm 1142 1129 1064 1142 1129 1064

O mm 579 581 590 579 581 590

P mm 518 516 507 518 516 507

OD mm 76,1 76,1 76,1 76,1 76,1 76,1

Length mm 3075 3075 3075 3075 3075 3075

Depth mm 1097 1097 1097 1097 1097 1097

Height mm 1805 1805 1805 1805 1805 1805

W1 kg 149 153 156 149 153 156

W2 kg 325 342 396 325 342 396

W3 kg 161 165 168 161 165 168

W4 kg 261 272 304 261 272 304

Operating weight kg 896 933 1024 896 933 1024

Shipping weight kg 889 925 1015 889 925 1015

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

DIMENSIONAL: WSAT-XEE 352-402-432 - EXCELLENCE VERSION

(1) INTERNAL EXCHANGER (EVAPORATOR) (2) EXTERNAL EXCHANGER (CONDENSER) (3) HOLE TO HANG UNIT (4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT) (5) ELECTRICAL PANEL (6) POWER INPUT (7) SOUNDPROOFED CABIN (8) INTERNAL EXCHANGER WATER OUTLET (9) INTERNAL EXCHANGER WATER INLET (10) MINIMUM DIMENSION FOR A SAFE PASSAGE. (11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL. (12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE. (G) BARYCENTRE

Page 43: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

43

®

BT10E005GB-02

ELFOENERGY LARGE2

ACOUSTIC CONFIGURATION: SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)

25

6

7

7 8

9

40 1097 40 4025

3 3 3

4 4 44

548 549

32

13

69.5329.5

16

0

18

05

(Eco

bre

eze

+ 3

0m

m)

1762.5 1762.5

PO

M N1

350

13

50

W1 W2 W3

W4

G

W5 W6

250 250

1000

700

30

10

37

30

1

OD

(10)

(12)

(11

)

(11

)

EXC - SC EXC - EN

SIZE 452 502 552 602 452 502 552 602

M mm 2553 2576 2574 2590 2553 2576 2574 2590

N mm 1472 1449 1451 1435 1472 1449 1451 1435

O mm 564 565 565 566 564 565 565 566

P mm 533 532 532 531 533 532 532 531

OD mm 76,1 76,1 76,1 76,1 76,1 76,1 76,1 76,1

Length mm 4025 4025 4025 4025 4025 4025 4025 4025

Depth mm 1097 1097 1097 1097 1097 1097 1097 1097

Height mm 1805 1805 1805 1805 1805 1805 1805 1805

W1 kg 80 80 82 84 80 80 82 84

W2 kg 254 257 261 267 254 257 261 267

W3 kg 287 301 306 323 287 301 306 323

W4 kg 85 85 87 89 85 85 87 89

W5 kg 253 255 259 265 253 255 259 265

W6 kg 247 258 262 275 247 258 262 275

Operating weight kg 1207 1234 1256 1302 1207 1234 1256 1302

Shipping weight kg 1198 1224 1246 1290 1198 1224 1246 1290

DIMENSIONAL: WSAT-XEE 452-502-552-602 - EXCELLENCE VERSION

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

(1) INTERNAL EXCHANGER (EVAPORATOR) (2) EXTERNAL EXCHANGER (CONDENSER) (3) HOLE TO HANG UNIT (4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT) (5) ELECTRICAL PANEL (6) POWER INPUT (7) SOUNDPROOFED CABIN (8) INTERNAL EXCHANGER WATER OUTLET (9) INTERNAL EXCHANGER WATER INLET (10) MINIMUM DIMENSION FOR A SAFE PASSAGE. (11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL. (12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE. (G) BARYCENTRE

Page 44: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

44

®

BT10E005GB-02

ELFOENERGY LARGE2

ACOUSTIC CONFIGURATION : SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)

1

2

3 3

4

6

7

8

9

548 5475025

W1 W2 W3

W4

G

W5 W6

44

4 3

250 2262.5 2262.5 250

13

50

135

0

700

329

159

32

036

9.5

5

7

40 1097 40

18

05

(Eco

bre

eze

+ 3

0m

m)

PO

M N

30

10

37

30

OD

(11

)

(10)

(11

)

(12)

1000

SIZE 702 802 702 802

M mm 3216 3227 3216 3227

N mm 1809 1798 1809 1798

O mm 564 565 564 565

P mm 533 532 533 532

OD mm 76,1 76,1 76,1 76,1

Length mm 5025 5025 5025 5025

Depth mm 1097 1097 1097 1097

Height mm 1805 1805 1805 1805

W1 kg 114 115 114 115

W2 kg 284 292 284 292

W3 kg 374 389 374 389

W4 kg 108 109 108 109

W5 kg 306 315 306 315

W6 kg 312 323 312 323

Operating weight kg 1497 1544 1497 1544

Shipping weight kg 1483 1527 1483 1527

DIMENSIONAL: WSAT-XEE 702-802 - EXCELLENCE VERSION

EXC - SC EXC - EN

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

(1) INTERNAL EXCHANGER (EVAPORATOR) (2) EXTERNAL EXCHANGER (CONDENSER) (3) HOLE TO HANG UNIT (4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT) (5) ELECTRICAL PANEL (6) POWER INPUT (7) SOUNDPROOFED CABIN (8) INTERNAL EXCHANGER WATER OUTLET (9) INTERNAL EXCHANGER WATER INLET (10) MINIMUM DIMENSION FOR A SAFE PASSAGE. (11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL. (12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE. (G) BARYCENTRE

Page 45: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

45

®

BT10E005GB-02

ELFOENERGY LARGE2

ACOUSTIC CONFIGURATION : SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)

W1 W2

W3 W4

G

7 8

9

250 2210 250

30

10

37

30

334

6

M N

OP

13

50

135

0

700

2

1OD

(10)

(12)

(11

)

(11)

1000

5

180

5(E

cob

ree

ze +

30

mm

)

40109740

16

0

329

2710 548 549

3

21

36

9.5

4

PRM - SC PRM - EN

SIZE 352 402 432 452 502 552 352 402 432 452 502 552

M mm 1637 1658 1724 1699 1704 1714 1637 1658 1724 1699 1704 1714

N mm 1073 1052 986 1011 1006 996 1073 1052 986 1011 1006 996

O mm 584 587 596 594 596 596 584 587 596 594 596 596

P mm 513 510 501 503 501 501 513 510 501 503 501 501

OD mm 76,1 76,1 76,1 76,1 76,1 76,1 76,1 76,1 76,1 76,1 76,1 76,1

Length mm 2710 2710 2710 2710 2710 2710 2710 2710 2710 2710 2710 2710

Depth mm 1097 1097 1097 1097 1097 1097 1097 1097 1097 1097 1097 1097

Height mm 1805 1805 1805 1805 1805 1805 1805 1805 1805 1805 1805 1805

W1 kg 138 138 141 152 158 159 138 138 141 152 158 159

W2 kg 277 291 344 350 367 377 277 291 344 350 367 377

W3 kg 152 153 155 166 172 173 152 153 155 166 172 173

W4 kg 211 219 250 256 267 274 211 219 250 256 267 274

Operating weight kg 778 802 892 924 963 984 778 802 892 924 963 984

Shipping weight kg 773 796 885 917 955 975 773 796 885 917 955 975

DIMENSIONAL: WSAT-XEE 352-402-432-452-502-552 - PREMIUM VERSION

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

(1) INTERNAL EXCHANGER (EVAPORATOR) (2) EXTERNAL EXCHANGER (CONDENSER) (3) HOLE TO HANG UNIT (4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT) (5) ELECTRICAL PANEL (6) POWER INPUT (7) SOUNDPROOFED CABIN (8) INTERNAL EXCHANGER WATER OUTLET (9) INTERNAL EXCHANGER WATER INLET (10) MINIMUM DIMENSION FOR A SAFE PASSAGE. (11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL. (12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE. (G) BARYCENTRE

Page 46: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

46

®

BT10E005GB-02

ELFOENERGY LARGE2

ACOUSTIC CONFIGURATION : SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)

W1 W2

W3 W4

G

5

7

40 1097 40

18

05

(Eco

bre

eze

+ 3

0m

m)

8

9

548 549

321

369

.5

250 2575 250

30

10

37

30

3075

329

16

0

33

44

6

M N

OP

13

50

13

50

700

2

1

OD

(10)

(12)

(11

)

(11

)

1000

PRM - SC PRM - EN

SIZE 602 602

M mm 2052 2052

N mm 1023 1023

O mm 595 595

P mm 502 502

OD mm 76,1 76,1

Length mm 3075 3075

Depth mm 1097 1097

Height mm 1805 1805

W1 kg 157 157

W2 kg 434 434

W3 kg 169 169

W4 kg 326 326

W5 kg 0 0

W6 kg 0 0

Operating weight kg 1087 1087

Shipping weight kg 1077 1077

DIMENSIONAL: WSAT-XEE 602 - PREMIUM VERSION

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

(1) INTERNAL EXCHANGER (EVAPORATOR) (2) EXTERNAL EXCHANGER (CONDENSER) (3) HOLE TO HANG UNIT (4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT) (5) ELECTRICAL PANEL (6) POWER INPUT (7) SOUNDPROOFED CABIN (8) INTERNAL EXCHANGER WATER OUTLET (9) INTERNAL EXCHANGER WATER INLET (10) MINIMUM DIMENSION FOR A SAFE PASSAGE. (11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL. (12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE. (G) BARYCENTRE

Page 47: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

47

®

BT10E005GB-02

ELFOENERGY LARGE2

ACOUSTIC CONFIGURATION : SOUNDPROOFING COMPRESSOR (SC) / EXTREMELY LOW NOISE (EN)

25

6

7

7 8

9

40 1097 40 4025

3 3 3

4 4 44

548 549

32

13

69.5329.5

16

0

18

05

(Eco

bre

eze

+ 3

0m

m)

1762.5 1762.5

PO

M N1

350

13

50

W1 W2 W3

W4

G

W5 W6

250 250

1000

700

30

10

37

30

1

OD

(10)

(12)

(11

)

(11

)

PRM - SC PRM - EN

SIZE 702 802 702 802

M mm 2626 2643 2626 2643

N mm 1399 1382 1399 1382

O mm 567 567 567 567

P mm 530 530 530 530

OD mm 76,1 76,1 76,1 76,1

Length mm 4025 4025 4025 4025

Depth mm 1097 1097 1097 1097

Height mm 1805 1805 1805 1805

W1 kg 79 79 79 79

W2 kg 260 264 260 264

W3 kg 332 344 332 344

W4 kg 84 84 84 84

W5 kg 258 262 258 262

W6 kg 282 292 282 292

Operating weight kg 1295 1324 1295 1324

Shipping weight kg 1283 1310 1283 1310

DIMENSIONAL: WSAT-XEE 702-802 - PREMIUM VERSION

The presence of optional accessories may result in a substantial variation of the weights shown in the table.

(1) INTERNAL EXCHANGER (EVAPORATOR) (2) EXTERNAL EXCHANGER (CONDENSER) (3) HOLE TO HANG UNIT (4) LIFTING BRACKETS (REMOVABLE, IF REQUIRED, AFTER POSITIONING THE UNIT) (5) ELECTRICAL PANEL (6) POWER INPUT (7) SOUNDPROOFED CABIN (8) INTERNAL EXCHANGER WATER OUTLET (9) INTERNAL EXCHANGER WATER INLET (10) MINIMUM DIMENSION FOR A SAFE PASSAGE. (11) MINIMUM DIMENSION FOR A PROPER AIR FLOW TO THE CONDENSER COIL. (12) MINIMUM DIMENSION ON THE ELECTRICAL SWITCHBOARD SIDE. (G) BARYCENTRE

Page 48: ELFOENERGY LARGE - HVACR.pl€¦ · FREE HOT WATER Condensation heat recovery: Partial: recovers around 20% of the available heat (desuperheater); Total: recovers 100% of available

The d

ata

co

nta

ined

in t

his

bulle

tin is n

ot bin

din

g a

nd m

ay b

e c

han

ge

d b

y t

he m

anu

factu

rer

with

out

pri

or

notice.

All

rep

roduction

, even p

art

ial, is p

rohib

ited. ©

Co

pyri

ght

- C

LIV

ET

S.p

.A.

- F

eltre

(B

L)

- Italy

CLIVET SPA Via Camp Lonc 25, Z.I. Villapaiera - 32032 Feltre (BL) - Italy Tel. + 39 0439 3131 - Fax + 39 0439 313300 - [email protected] CLIVET UK LTD 4 Kingdom Close, Segensworth East - Fareham, Hampshire - PO15 5TJ - United Kingdom Tel. + 44 (0) 1489 572238 - Fax + 44 (0) 1489 573033 - [email protected] CLIVET SAS ZAC des Godets 1, Impasse de la Noisette, Hall A6 - 91370 Verrières le Buisson - France Tel. + 33 (0)1 69202575 - Fax + 33 (0)1 69206076 [email protected] CLIVET ESPAÑA S.A. Parque Empresarial Villapark, Avda. Quitapesares 50 - 28670, Villaviciosa de Odón, Madrid - España Tel. + 34 91 6658280 - Fax + 34 91 6657806 - [email protected] CLIVET GmbH Hummelsbütteler Steindamm 84, 22851 Norderstedt - Germany Tel. + 49 (0) 40 32 59 57-0 - Fax + 49 (0) 40 32 59 57-194 - [email protected] CLIVET NEDERLAND B.V. Siliciumweg 20a, 3812 SX Amersfoort - Netherlands Tel. + 31 (0) 33 7503420 - Fax + 31 (0) 33 7503424 - [email protected] CLIVET RUSSIA Elektrozavodskaya st. 24, office 509 - 107023, Moscow, Russia Tel. + 74956462009 - Fax + 74956462009 - [email protected] CLIVET MIDEAST FZC Rep Office: PO Box 28178 - Light industrial unit #10 -Dubai Silicon Oasis - Dubai,UAE Tel. + 97 14 3208499 - Fax + 97 14 3208216 - [email protected] CLIVET AIRCONDITIONING SYSTEMS (P) LTD 3C3, Gundecha Onclave, Kherani Road, Saki Naka, Andheri (East), Mumbai 400 072 (INDIA) Tel. + 91 - 22 - 6193 7000 - Fax + 91 - 22 - 6193 7001 - [email protected]