4
Electronic Energy Meter EMC For single-phase or three-phase networks Benefits that count 1 x 230 V or 3 x 57.7 / 100 V – 230 / 400 V Direct input connection up to 65 A 1 A and 5 A CT secondary currents in one instrument Certifiable Programmable pulse valency and duration Programmable transformer ratio Additional resettable register Measurement of instantaneous power and maximum demand Detection of faulty connections Backlit LC-Display Configuration and display of measured variables also possible with power off

Electronic Energy Meter EMC - شرکت فراکوه · 2020. 4. 23. · to IEC 61036 MDVH MDVH to IEC 61036" MDVH MDVHArticle no. 29-20065 29-20055 Certificate – certifiable Accuracy

  • Upload
    others

  • View
    2

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Electronic Energy Meter EMC - شرکت فراکوه · 2020. 4. 23. · to IEC 61036 MDVH MDVH to IEC 61036" MDVH MDVHArticle no. 29-20065 29-20055 Certificate – certifiable Accuracy

Electronic Energy Meter EMC For single-phase or three-phase networks

Benefits that count

■ 1 x 230 V or3 x 57.7 / 100 V – 230 / 400 V

■ Direct input connection up to 65 A■ 1 A and 5 A CT secondary currents in

one instrument■ Certifiable■ Programmable pulse valency and

duration■ Programmable transformer ratio

■ Additional resettable register■ Measurement of instantaneous power

and maximum demand■ Detection of faulty connections■ Backlit LC-Display■ Configuration and display of measured

variables also possible with power off

Page 2: Electronic Energy Meter EMC - شرکت فراکوه · 2020. 4. 23. · to IEC 61036 MDVH MDVH to IEC 61036" MDVH MDVHArticle no. 29-20065 29-20055 Certificate – certifiable Accuracy

Meters for active energy EMC 1203 EMC 1203to IEC 61036 MDVH MDVHto IEC 61036" MDVH MDVHArticle no. 29-20065 29-20055

Certificate – certifiable

Accuracy class 1 1

Type of connection 4-wire 4-wire

Current measurement Current transformer x /.. 1 A and 5 A 1 A and 5 ADirect input up to – –

Current transformer 1,10,20,30,40,50, –ratio adjustable 60,80,100,120,150, (Input disabled on

200, 250,300 .../1, certifiable meters)5,50,100,150,200,250,300,400,500,600,750,1000,1250,1500 .../5

Power draw ≤ 1.0 VA ≤ 1.0 VA

Input currents • •galvanically isolated

Voltage measurement Voltage circuit 3 x 230/400V 3 x 230/400V+/- 10% +/- 10%

Power draw ≤ 1.5 VA ≤ 1.5 VAFrequency 50 Hz 50 Hz

Auxiliary supply self-supplied from voltage input

Standard S0 pulse output Pulse frequency 5000 pulses/kWh 5000 pulses/kWh(volt-free contact)

Pulse duration min. 30 ms min. 30 ms

Max.voltage and current up to 230 VAC / up to 230 VAC / 100 mA 100 mA

LED frequency 10000 pulses/kWh 10000 pulses/kWh

7-digit display Backlit LCD – –

Detection of faulty connections • •

Ingress protection Enclosure IP51 IP51Terminal block with cover IP20 IP20

Input cable cross section Current transformer 10 mm2 10 mm2

Direct – –

Dimensions W x H x D (mm) 125 x 96 x 66 125 x 96 x 66

Mounting 35 mm DIN rail • •

Weight 0.5 kg 0.5 kg

Operating temperature -20 ... +55°C -20 ... +55°C

Special features

Front panel for EMC 1203 MDVH/DVH Article no. 29-20063 • •

Front panel for EMC 1203 / EMC 1203 I Article no. 29-20062 – –

Electronic Energy Meter EMC For single-phase or three-phase networks

Page 3: Electronic Energy Meter EMC - شرکت فراکوه · 2020. 4. 23. · to IEC 61036 MDVH MDVH to IEC 61036" MDVH MDVHArticle no. 29-20065 29-20055 Certificate – certifiable Accuracy

EMC 1203 EMC 1203 EMC 1203 I EMC 1201DVHDVH29-20057 29-20045 29-20046 29-20072

certifiable – – certifiable

2 1 1 1

4-wire 3- / 4-wire 3- / 4-wire 2-wire

– 1 A and 5 A 1 A and 5 A –65 A – – 65 A

– x / 1 or x /5 x / 1 or x /5 –1 to 999999 1 to 999999

≤ 1.0 VA < 0.03VA ../1A < 0.03VA ../1A ≤ 1.0 VA< 0.6VA ../5A < 0.6VA ../5A

– – • –

3 x 230/400V 3 x 57.7/100V 4 x 57.7/100V 1 x 230V+/- 10% to 230/400V to 230/400V +/- 10%

+/- 15% +/- 15%≤ 1.5 VA < 1 VA, 1W per phase < 1 VA, 1W per phase ≤ 1.5 VA50 Hz 45 to 65 Hz 45 to 65 Hz 50 Hz

self-supplied from voltage input

500 pulses/kWh 0.1 Wh to 0.1 Wh to 1000 pulses/kWh100 kWh 100 kWh

min. 30 ms 50 to 50 to min. 30 ms1500 ms 1500 ms

up to 230 VAC / 0...230 VAC - 325 0...230 VAC - 325 up to 230 VAC /100 mA VDC / 100 mA VDC / 100 mA 100 mA

1000 pulses/kWh 1 pulse/Wh 1 pulse/Wh 1000 pulses/kWh

– • • –

• • • –

IP51 IP51 IP51 IP51IP20 IP20 IP20 IP20

– 6 mm2 6 mm2 –25 mm2 – – 16 mm2

125 x 96 x 66 122.5 x 100 x 58.5 122.5 x 100 x 58.6 35.8 x 97.6 x 61.1

• • • •

0.5 kg 0.5 kg 0.5 kg 0.2 kg

-20 ... +55°C -20 ... +55°C -20 ... +55°C -20 ... +55°C

Class 1 accuracy on request Additional resettable register for periodic metering –Measurement of instantaneous power and maximum demandConfiguration and display also when disconnected from supply

• – – –

– • • –

Electronic Energy Meter EMC For single-phase or three-phase networks

Page 4: Electronic Energy Meter EMC - شرکت فراکوه · 2020. 4. 23. · to IEC 61036 MDVH MDVH to IEC 61036" MDVH MDVHArticle no. 29-20065 29-20055 Certificate – certifiable Accuracy

FRA

KO 9

5-00

191/

04/0

7/79

28

Subj

ect t

o te

chni

cal c

hang

es.

Electronic Energy Meter EMC For single-phase or three-phase networks

■ Front panel for EMC 1203 MDVH

■ Linking meters in theFRAKO Energy Management System

■ Visualization of meter data in theFRAKO Energy Management System

■ Front panel for EMC 1203 / EMC 1203 I