NIBE VVM 225 is a flexible electric boiler which meets the new energy requirements and which been adapted to facilitate the replacement of NIBE EVC 240. NIBE VVM 225 has a smart, user-friendly control system and can be easily docked with NIBE air/water heat pumps for further energy savings Thanks to smart technology, the product gives you control over your energy consumption and will be a key part of your connected home. The efficient con- trol system automatically adjusts the indoor climate for maximum comfort, and you do nature a favour at the same time. • For straightforward replacement of NIBE EVC 240. • Combine NIBE VVM 225 with an air/water heat pump for an energy-efficient climate system. • Energy-saving smart technology with user-friendly control. IT'S IN OUR NATURE NIBE.EU Electric boiler, indoor module NIBE VVM 225

Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

NIBE VVM 225 is a flexible electric boiler whichmeets the new energy requirements andwhich beenadapted to facilitate the replacement of NIBEEVC 240.

NIBE VVM 225 has a smart, user-friendly controlsystem and can be easily dockedwith NIBE air/waterheat pumps for further energy savings

Thanks to smart technology, the product gives youcontrol over your energy consumption and will be akey part of your connected home. The efficient con-trol system automatically adjusts the indoor climatefor maximum comfort, and you do nature a favourat the same time.

• For straightforward replacement of NIBE EVC 240.

• Combine NIBE VVM 225 with an air/water heatpump for an energy-efficient climate system.

• Energy-saving smart technology with user-friendlycontrol.

IT'S IN OUR NATURE NIBE.EU

Electric boiler, indoor moduleNIBE VVM 225

Page 2: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Installation method

VVM 225 consists of water heater with charge coil, ex-pansion vessel, safety valves, filler valve, immersionheater, circulation pump and control system.

VVM 225 is directly adapted for connection and commu-nication with NIBE SPLIT HBS 05 / F2040 / F2120, whichtogether constitute a complete heating installation.

NIBE SPLIT HBS 05 / F2040 / F2120 covers most of theheating and hot water requirement down to the heatpump’s stop temperature. If the outdoor temperaturedrops to a level below the heat pump’s stop temperat-ure, all heating is then provided using VVM 225.

The system requires the radiator circuit to be designedfor a low temperature heating medium. At the lowestdimensioned outdoor temperature (DOT), the highestrecommended temperatures are 55 °C on the supplyline and 45 °C on the return line, but VVM 225 canhandle up to 70 °C. For correct dimensioning of the heatpump, NIBE dimensioning programNIBE DIM is recom-mended.

A system with VVM 225 and NIBE compatible air/waterheat pumps means a complete, energy-saving installa-tion. VVM 225 can be supplemented with several differ-ent accessories.

OUTDOOR MODULES

Compatible Air/water heat pumpsNIBE SPLIT HBS 05

UNUN

LE

K

HBS 05-6

Part no. 067 578

AMS 10-6

Part no. 064 205

HBS 05-12

Part no. 067 480

AMS 10-8

Part no. 064 033

F2040

LEK

F2040-8

Part no. 064 109

F2040-6

Part no. 064 206

F2040-16

Part no. 064 108

F2120

LEK

F2120-8 3x400V

Part no. 064 135

F2120-8 1x230V

Part no. 064 134

F2120-12 3x400V

Part no. 064 137

F2120-12 1x230V

Part no. 064 136

Check the software version of compatible older NIBEair/water heat pumps, see page 7.

2 NIBE VVM 225

IT'S IN OUR NATURE

This is how NIBE VVM 225works

Page 3: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Principle of operationPrinciple of operation with hot water and a heating sys-tem. The heating medium side and the domestic hotwater side must be fitted with the necessary safetyequipment in accordancewith the applicable regulations.

EXPLANATION

Indoor module (VVM 225)EB15

Heat pumpEB101Safety valve, heat pumpFL10Tapping valveQM1FilterballQZ2Shut-off valveQM40

-EB15

-XL4 -XL3-XL1-XL2

P

-EB101 -XL1

-XL2

-XL9

-XL8

-FL10

-QM1

-QZ2

-QM40

NIBE VVM 225 3

IT'S IN OUR NATURE

Page 4: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Transport and storageVVM 225 should be transported and stored vertically ina dry place. However, the VVM 225 may be carefullylaid on its back when being moved into a building.

R

0

R0

Installation andpositioning• Position VVM 225 on a firm base that can take theweight. Use the product's adjustable feet to obtain ahorizontal and stable set-up.

• Because water can emerge from the safety valve forhot water in VVM 225, the area where VVM 225 islocated must be provided with floor drainage.

INSTALLATION AREALeave a free space of 800 mm in front of the product.All service on VVM 225 can be carried out from the front.

800

10-25

Leave 10 – 25 mm free space between the indoormodule and the wall behind for routing of cables andpipes.

4 NIBE VVM 225

IT'S IN OUR NATURE

Good to know about VVM 225

Page 5: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Simple installationVVM 225 is easy to install. All pipe connections areeasily accessible. This is especially useful for the replace-ment market.

Supplied components

Room sensorOutside sensor

LE

K

LE

K

LE

K

Current sensor

LOCATIONThe kit of supplied items is placed on top of the product.

EquipmentVVM 225 is equipped with filler and drain valves. In ad-dition, VVM 225 is equipped with expansion vessel aswell as required safety valves.

Ensure that incoming water is clean. When using aprivate well, it may be necessary to supplement withan extra water filter.

DesignVVM 225 is fitted with intelligent control. This makesfor easy operation while always enabling the indoormodule to be used as efficiently as possible. The circu-lation pump is controlled for optimum operation Currenttemperatures and set values can easily be shown onthe display.

The insulation is made of moulded Neopor, whichprovides excellent heat insulation.

The outer casing is made of white, powder-coated, steelplate.

NIBE VVM 225 5

IT'S IN OUR NATURE

Installation

Page 6: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Dimensions and pipe connectionsSETTING OUT DIMENSIONS

YXHConnection

VVM 225

H

440

420

402

351

162

350 428

188

338

402

479

512

25-50

View from underneath

Y

X

428512200mmXL1 Heating medium supply line Ø350479200mmXL2 Heating medium return line Ø440402250mmXL3 Cold water Ø402338260mmXL4 Hot water Ø42018885mmXL8 Connection, docking from heat

pump Ø35118885mmXL9 Connection, docking to heat

pump Ø162460145mmWM1 Drip tray

Pipe connections

UN

XL3

XL2

XL1XL4XL9XL8

Pipe dimensionsConnection

VVM 225

H

440

420

402

351

162

350 428

188

338

402

479

512

25-50

22mmHeating medium supply line ØXL122mmHeating medium return line ØXL222mmCold water ØXL322mmHot water ØXL422mmConnection, docking from heat pump ØXL822mmConnection, docking to heat pump ØXL9

440

420

402

351

162

350 428

1475

25-50

188

338

596

402

479

512

596

599

VVM 225

560 440

6 NIBE VVM 225

IT'S IN OUR NATURE

Page 7: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

DockingVVM 225 can be connected in several ways. The neces-sary safety equipment must be installed in accordancewith current regulations for all docking options.

See nibe.se/dockning for more detailed docking options.

Compatible NIBEair/water heat pumps

VVM 225Air/water heat pumpall versionsF2040-6all versionsF2040-8all versionsF2120-8all versionsF2120-12all versionsNIBE AMS10-6 + HBS05-6all versionsNIBE AMS10-8 + HBS05-12

Pump capacitydiagramAvailable pressure, circulation pump, QN4 in closed position(electric boiler)

00 200 400 600 800 1000 1200 1400 1600

10

20

30

40

50

60

70

80

90

Tillgängligt tryck(kPa)

Flöde(l/h)

20% 40% 60%80% 100%

Available pressure(kPa)

Flow(l/h)

Available pressure, circulation pump, QN4 in open position(heat pump)

00 200 400 600 800 1000 1200 1400 1600 1800 2000

10

20

30

40

50

60

70

80

90

Tillgängligt tryck(kPa)

Flöde(l/h)

20% 40%

60%80%

100%

Available pressure(kPa)

Flow(l/h)

NIBE VVM 225 7

IT'S IN OUR NATURE

Page 8: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Electrical installationELECTRICAL CONNECTIONS

GeneralAll electrical equipment, except the outdoor sensors,room sensors and the current sensors are ready connec-ted at the factory.

• Disconnect the electric boiler/indoor module beforeinsulation testing the property.

• If the building is equipped with an earth-fault breaker,VVM 225 should be equipped with a separate one.

• The electrical wiring diagram for the indoor modulecan be found in the Installer manual.

• A screened three-core cable is used as the communic-ation cable.

• Communication and sensor cables to external connec-tions must not be laid close to high current cables.

• The minimum area of communication and sensorcables to external connections must be 0.5 mm² upto 50, for example EKKX or LiYY or equivalent.

• When cable routing in VVM 225, cable grommets UB1and UB2 must be used. In UB1 and UB2, the cablesare inserted through the indoor module from the backto the front. (See the Installer Manual.)

Electrical installation and service must be carried outunder the supervision of a qualified electrician. Cut thecurrent with the circuit breaker before carrying out anyservicing. Electrical installation and wiring must be car-ried out in accordance with the stipulations in force.

Miniature circuit-breakerThe indoor module and a large proportion of its internalcomponents are internally fused by a miniature circuitbreaker.

Temperature limiterThe temperature limiter (FQ1) cuts the power supply tothe electric additional heat, if the temperature rises tobetween 90 and 100 °C and it is reset manually.

SETTINGS

Electric additional heat – maximum outputThe immersion heater can be set up to a maximum of9 kW.

The immersion heater output is divided into seven steps,according to the table in the Installer Manual.

Setting maximum output in the electric additional heatis done in menu 5.1.12.

Emergency modeWhen the indoor module’s switch (SF1) is set to emer-gency mode, only the most essential functions are ac-tivated.

• Hot water production stops.

• The load monitor is not connected.

• Fixed temperature in the supply line.

8 NIBE VVM 225

IT'S IN OUR NATURE

Page 9: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Regular checksYour electric boiler/indoor module is, in principle, main-tenance free and therefore requires the minimal careafter commissioning. However, it is recommended thatyou check your installation regularly.

Aminimum level of maintenance is required. Only safetyvalves require checking. All essential components canbe accessed from the front. This facilitates service andmaintenance.

If something unusual occurs, messages about the mal-function appear in the display in the form of differentalarm texts.

NIBE VVM 225 9

IT'S IN OUR NATURE

Maintenance of VVM 225

Page 10: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Control, generalThe indoor temperature depends on several differentfactors. Sunlight and heat emissions from people andhousehold machines are normally sufficient to keep thehouse warm during the warmer parts of the year. Whenit gets colder outside, the climate system must bestarted. The colder it is outside, the warmer radiatorsand under floor heating system must be.

Control of the heat production is performed based onthe "floating condensing" principle, which means thatthe temperature level needed for heating at a specificoutdoor temperature is produced based on collectedvalues from the outdoor and supply temperaturesensors. The room sensor can also be used to com-pensate the deviation in room temperature.

Heat productionThe supply of heat to the house is regulated inaccordance with the heating curve setting se-lected. After adjustment, the correct amount

of heat for the current outdoor temperature is supplied.The supply temperature of the heat pump will oscillatearound the theoretically required value.

OWN CURVEVVM225 has pre-programmed non-linear heating curves.It is also possible to create your own defined curve. Thisis an individual linear curve with a number of breakpoints. You select break points and the associatedtemperatures.

Hot water productionHot water charging starts when the temperat-ure has fallen to the set start temperature. Hotwater charging stops when the hot water

temperature at the hot water sensor has been reached.

For occasional higher hot water demand, there is afunction called "temporary lux" that allows the temperat-ure to be raised via one time increase or up to 12 hours(selected in the menu system).

With the Smart Control function activated, VVM 225learns how much hot water is used and when. TheSmart Control function memorises the previous week’shot water consumption and adapts the hot water tem-perature for the comingweek to ensureminimal energyconsumption.

It is also possible to set VVM 225 in holiday mode, whichmeans that the lowest possible temperature is achievedwithout the risk of freezing.

Docking, heat pumpVVM 225 can be dockedwith NIBE air/water heat pump.

See table on page 7.

Alarm indicationsThe status lamp lights red in the event of an alarm andthe display shows detailed information depending onthe fault. An alarm log is created with each alarm con-taining a number of temperatures, times and operatingstatus.

10 NIBE VVM 225

IT'S IN OUR NATURE

Functions

Page 11: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

The displayVVM 225 is controlled using a clear and easy to usedisplay.

Instructions, settings and operational information areshown on the display. You can easily navigate betweenthe different menus and options to set the comfort orobtain the information you require.

The display unit is equipped with a USB socket that canbe used to update the software and save logged inform-ation in VVM 225.

Visit nibeuplink.com and click the "Software" tab todownload the latest software for your installation.

NIBE UplinkUsing the Internet and NIBE Uplink, you canobtain a quick overview and the present statusof the installation and the heating in your home.

You can obtain a good overall view, allowing you tomonitor and control the heating and hot water comforteffectively. If the system is affected by a malfunction,you receive an alert via e-mail that allows you to reactquickly.

NIBE Uplink also gives you the opportunity to controlthe comfort in your home easily, no matter where youare.

RANGE OF SERVICESYou have access to different levels of service via NIBEUplink. A basic level that is free and a premium levelwhere you can select different extended service func-tions for a fixed annual subscription fee (the subscriptionfee varies depending on the selected functions).

NIBE Uplink also available as an app from App Store andGoogle Play.

INSTALLATION AND ASSOCIATEDEQUIPMENT REQUIREMENTSThe following is required in order for NIBE Uplink tofunction with the installation:

• Network cable (straight, at least Cat 5E UTP).

• Internet connection.

• Web browser that supports JavaScript.

If it is not possible to connect to NIBE Uplink, VVM 225can be controlled remotely via text message. For this,the SMS 40 accessory is required.

For further presentation, visit nibeuplink.com.

NIBE SMART PRICE ADAPTION™Smart Price Adaption is not available in allcountries. Contact your NIBE dealer for moreinformation.

Smart Price Adaption adjusts the heat pump's consump-tion according to the time of day that electricity pricesare lowest. This allows for savings, provided that thehourly rate subscription has been signed with the elec-tricity supplier.

The function is based on hourly rates for the coming daybeing downloaded via NIBE Uplink. To use the function,an Internet connection and account on NIBE Uplink arenecessary.

SMART HOMEWhen you have a smart home system that can commu-nicate with NIBE Uplink, you can control the installationvia an app by activating the “smart home” function.

By allowing connected units to communicate with NIBEUplink, your heating system becomes a natural part ofyour homesmart home and gives you the opportunityto optimise the operation.

Remember that the “smart home” function requiresNIBE Uplink in order to work.

NIBE SMART ENERGY SOURCE™Smart Energy Source™ prioritises how / towhat extent each docked energy source willbe used. Here you can choose if the system is

to use the energy source that is cheapest at the time.You can also choose if the system is to use the energysource that is most carbon neutral at the time.

NIBE VVM 225 11

IT'S IN OUR NATURE

Page 12: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Dimensions and setting-out coordinates

440

420

402

351

162

350 428

1475

25-50

188

338

596

402

479

512

596599

VVM 225

560 440

12 NIBE VVM 225

IT'S IN OUR NATURE

Technical data

Page 13: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

Technical data3X400V3x400V

F2040-6 / F2040-8 / F2120-8 / F2120-12Compatible outdoor modules

NIBE AMS10-6 + HBS05-6

NIBE AMS10-8 + HBS05-12

9kWAdditional power

Energy labelling

XLDeclared load profile for water heating

DThe product’s room heating efficiency class1

CThe product’s hot water heating efficiency class2

Electrical data

400V 3N~50HzRated voltage

16AMax operating current

16ARecommended fuse rating

4 – 75WOutput, GP1

IP21Enclosure class

Heating medium circuit

low energyEnergy class, GP1

0.3 (3 bar)MPaMax system pressure heating medium

400litres/hMin flow

70°CMax HM temp

Pipe connections

Ø22mmHeating medium

Ø22mmHot water connection

Ø22mmCold water connection

Ø22mmHeat pump connections

1Scale for the product’s room heating efficiency class: A++ to G.2Scale for the product’s hot water heating efficiency class: A to G.

NIBE VVM 225 13

IT'S IN OUR NATURE

Page 14: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

MiscellaneousIndoor module

180lVolume, hot water heater

1.0 (10 bar)MPa (bar)Max. permitted pressure, water heater

0.9 (9 bar)MPa (bar)Cut-off pressure, hot water heater

0.3 (3 bar)MPa (bar)Max permitted pressure in indoor module

Capacity hot water heating According to EN 16147

187lTap volume 40°C at Economy comfort

212lTap volume 40 °C during Normal comfort

231lTap volume 40 °C during Lux comfort

Dimensions and weight

596mmWidth

599mmDepth

1,475mmHeight (without base)

1,500 – 1,525mmHeight (with base)

1,550mmRequired ceiling height

130kgWeight (excl. packaging and without water)

069 207Part no.

14 NIBE VVM 225

IT'S IN OUR NATURE

Page 15: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ

AccessoriesDetailed information about the accessories and completeaccessories list available at nibe.se.

Not all accessories are available on all markets.

Active cooling. ACS 310*

LEK

LEK

LEK

ACS 310 is an accessory that enablesVVM 225 to control the production ofcooling.

*The accessory requires that NIBE air/wa-ter heat pump is installed.

Base extension EF 45

LEK

This accessory is used to create a largerconnection area under VVM 225.

Buffer vessel UKV

Communications module SMS 40

LEK

When there is no internet connection, you canuse the accessory SMS 40 to control VVM 225via SMS.

Exhaust air heat pump F135*

LEK

F135 is an exhaust air heap pump spe-cially designed to combine the recoveryof mechanical exhaust air with air/waterheat pump. Indoor module/control mod-ule controls F135.

*The accessory requires that NIBE air/water heat pump is installed.

Extra shunt group ECS 40/ECS 41

LEK

LEK

LEK

This accessory is used whenVVM 225 is installed in houses withtwo or more different heating sys-tems that require different supplytemperatures.

Solar package NIBE PV

Solar panel package with extremely longservice-life to produce your own electri-city.

9 kW30 Solarpanels

6 kW20 Solarpanels

3 kW10 Solarpanels

24 kW80 Solarpanels

15 kW50 Solarpanels

12 kW40 Solarpanels

Top cabinet

LEK

Top cabinet that conceals any pipes.

Ventilation heat exchanger ERS

LEK

This accessory is used to supply the accom-modationwith energy that has been recoveredfrom the ventilation air. The unit ventilates thehouse and heats the supply air as necessary.

NIBE VVM 225 15

IT'S IN OUR NATURE

Page 16: Electricboiler,indoormodule NIBEVVM225 · VVM 225 H 440 420 402 351 162 350 428 188 338 402 479 512 25-50 Uhdveqnltmcdqmdsg X W XL1Heatingmediumsupplyline Ø mm 200 512 428 XL2HeatingmediumreturnlineØ