52
SYNCHRONOUS GENERATOR TURBINE GOVERNOR EXCITATION TRANSFORMER 2 EXCITATION SYSTEM GENERATOR BREAKER 1 1 SYNCHRONIZING 2 PROTECTION STATIC STARTER CONTROL SYSTEMS AC & DC AUXILIARY SYSTEMS STEP UP TRANSFORMER HV- BREAKER HV SYSTEM CONTROL ROOM PT’s & CT’s AUX. TRANSF. STAR POINT CUBICLE LV SWITCHGEAR The power station

Electrical Sys -FGPS

Embed Size (px)

DESCRIPTION

it is usual for presentation for both electrical and electronics student who got training in NTPC faridabad

Citation preview

Page 1: Electrical Sys -FGPS

SYNCHRONOUSGENERATORTURBINE

GOVERNOR

EXCITATIONTRANSFORMER

2

EXCITATIONSYSTEM

GENERATORBREAKER1

1

SYNCHRONIZING

2

PROTECTION

STATIC STARTER

CONTROL SYSTEMS

AC & DCAUXILIARY SYSTEMS

STEP UP TRANSFORMER

HV- BREAKER

HV SYSTEM CONTROL ROOM

PT’s&CT’s

AUX.TRANSF.

STARPOINT

CUBICLE

LV SWITCHGEAR

The power station

Page 2: Electrical Sys -FGPS

• Generators• Excitation System• Transformers• MV Switchgear• EHV Switchgear• Generator

protections

Overview of Electrical Systems

•EHV protections

•Black Start DG set

•DC Systems

•415 V Systems

•Fire protection systems

•Switchyard Equipments

Page 3: Electrical Sys -FGPS

General Classification

ELECTRICAL SYSTEMS

AC 50 Hz SUPPLY SYSTEM D/C SYSTEM

220 KV 3 PHASE FOR BULK POWER TRANSMISSION

10.5 KV,15.75 KV 3 PHASE GENERATOR OUTPUT VOLTAGE

6.6 KV 3 PHASE FOR STATION AUXILLIARIES

415 V 3 PHASE FOR LOW VOLTAGE AUXILLIARIES

240 V SINGLE PHASE SUPPLY

220 V FOR UPS & EMERGENCY SYSTEMS

24 V FOR SOLENOIDS,

CONTROLLERS

48 V DC IN SWITCHYARD

Page 4: Electrical Sys -FGPS

GENERAL SINGLE LINE DIAGRAM

Page 5: Electrical Sys -FGPS

Turbo generator Excitation system Generator details

GAS TURBINE GENERATOR : 170.12 MVA,10.5kV,field voltage 410 V,stator current-9354 A- 2 NoSTEAM TURBINE GENERATOR : 188.23 MVA, 15.75kV,field voltage 432 V,stator current-6900 A- 1 NoAir cooled, 3000 RPM, 2 pole, double star.Four coolers in the generator for cooling the air.

–Providing variable DC current with short time overload capability

–Controlling terminal voltage,MVAR and PF with suitable accuracy

–Ensure stable operation with network and / or other machines

–Keep machine within permissible operating range

–Contribution to transient stability subsequent to a fault.

–Communicate with the power plant control system

Page 6: Electrical Sys -FGPS

• Apparent power• Active Power• Current• Voltage• Speed• Frequency• Power Factor• Stator Winding• Rated Field current• Rated Field Voltage

• 170.12MVA• 144.6MW• 9354A• 10.5KV+/-5%• 3000rpm• 50Hz• 0.85• YY• 833A• 410V

GT Generator

Page 7: Electrical Sys -FGPS

STG Generator

• Apparent power

• Active Power

• Current

• Voltage

• Speed

• Frequency

• Power Factor

• Stator Winding

• Rated Field current

• Rated Field Voltage

• 188.23MVA• 160MW• 6900A• 15.75KV+/-5%• 3000rpm• 50Hz• 0.85• YY• 798A• 432V

Page 8: Electrical Sys -FGPS

Steam Turbine Generator

Page 9: Electrical Sys -FGPS

The automatic voltage control system

SynchronousMachine

Excitation System

GridIf Ug

Controller

Page 10: Electrical Sys -FGPS

AVR

SM

High voltage line

Unit step up transformer

Excitation transformer

Sensing PT

Thyristor Converter

Synchronous machine

Static Excitation System

+ direct measuring of field -current, -voltage

+ superior dynamic performance (fast response)

+ field voltage reversing feature

+ very effective field discharge

+ Ceiling factor not limited

+ field ground dedection availabel

+ superior MTBF, MTTR

- Sliprings

Characteristic of Static Excitation System:

Page 11: Electrical Sys -FGPS

Brush less excitation system

• Just positive ceiling voltage capability

• Exciter response limited by the exciter machine time constant (>200ms)

• Field discharge with natural time constant

• Supply from PMG possible providing supporting of short circuit currents

• Relative large size of exciter machine for low speed generators

• No sliprings (less maintenance and dust)

Page 12: Electrical Sys -FGPS

Neutral terminal

• Grounding transformer used to reduce fault currents.

• The 100% stator earth fault detection is also done through this transformer

Page 13: Electrical Sys -FGPS

Starting system

• SFC manufacturer-AEG Germany

• Rating-2.9 MW

• Modes of operation:washing at 600 rpm

• Boiler purging at 900 rpm

• Unit black start at link circuit current 2.7 MW 1360 RPM

• Power operation at max dragging 2.9 Mw 2100 RPM

Page 14: Electrical Sys -FGPS

Transformers

• Generator transformer

• Unit auxiliary transformer

• Excitation Transformer

• MV/LV Transformers

• Lighting Transformers

Page 15: Electrical Sys -FGPS

• Three Phase, 153.5 MVA, BHEL make.

• Delta Star, neutral solidly grounded.

• 10.5/230 kV.• Cooling-ONAN/ONAF/

OFAF • Off circuit Tap changer at

five positions• Oil quantity:-39715 liters

Generator transformer UAT

• Rating 25 MVA 10.5/6.9 kV

• Cooling: ONAN/ONAF

• Quantity of oil-13095 liters

• On load tap changer at 12 positions

Page 16: Electrical Sys -FGPS

Busduct and UAT

Gen. Transformer

Page 17: Electrical Sys -FGPS

System

• There are two Unit Transformers connected thru GT, 10.5 KV Bus.

• These two Transformer make 2no. 6.6KV bus ( 11 &12 BBE) which in turn make another 2 bus thru Ties.(OCA- A&B)

• A total 4no 6.6KV bus exists which are interconnected thru Ties and Bus coupler.

• DG is also connected to OCA (A&B) bus thru 6.6KV Breakers.

Page 18: Electrical Sys -FGPS

6.6KV BUS SYSTEM

Page 19: Electrical Sys -FGPS

Changeover Schemes

Changeover Schemes are divided in Two Group: A. With Paralleling B. Without Paralleling Here there are Four Types of Schemes under these

Categories:• MANUAL Changeover • FAST Changeover• SLOW Changeover• BLACKOUT Condition

Page 20: Electrical Sys -FGPS

Manual Changeover Scheme

Features:

• It is a planned changeover.• Thru Operator Intervention.• No Interruption in Voltages.• Thru Synchronizing Relay

Page 21: Electrical Sys -FGPS

Manual Changeover Scheme

Scope:

1. Bus coupler at OCA

2. UAT Incomer ( BBE01&2)

3. DG Breaker 1&2

4.Tie Breaker at OCA( Tie1 &2)

Page 22: Electrical Sys -FGPS

Manual Changeover Scheme

Example :

U1-B/C-U2 Changeover:

--Proven scheme

--Either of Breaker can be closed thru ECB.

--Choice of Breaker tripping is done thru Trip selection switch.

Page 23: Electrical Sys -FGPS

Fast Changeover Scheme

Feature:• This is only for OCA Bus coupler.• This changeover occurs when Voltage sink is

likely to occur. • OCA Bus coupler will close in Auto without any

time delay. No manual Intervention possible.• This changeover will take place in less than

200millisecond, hence chances of supply interruption is very less.

Page 24: Electrical Sys -FGPS

Slow Changeover Scheme

Features:

• This is a backup of Fast changeover.

• Bus coupler will close in auto after certain Time delay and fulfillment of certain condition

• Chances of unit survival depends on situation

Page 25: Electrical Sys -FGPS

Black Out Condition

Normally blackout condition means:

• 1. All GCB and HVCB open.

• 2. Both Unit Incomer Breakers Open

• 3. No Auxiliary Power at station.

At this moment our attempt to restore the Auxiliary power as soon as possible.

Page 26: Electrical Sys -FGPS

Black Out Condition

Under this Condition:• DG set will take start in Auto• All Aux. Feeders at OCA Bus will Trip• Both DG Breakers will closed in Auto.• Priority Transformer feeders will close in Auto,

also their LT Incomers(except PCC) • Tie feeders at OCA and PCC will not Trip• This all will be done thru Logics As:

Page 27: Electrical Sys -FGPS

Black Out Condition Contd.

If due to any reason DG fail to start or DG Breaker does not close in Auto :

• Start DG Manually• Close the DG Breakers one by one• Close the Priority feeders one by one.

Page 28: Electrical Sys -FGPS

Black Out Condition --Normalisation

2. Thru GT1 and GT2 Transformer :• Back charge the transformer and close the U1 and

U2 breaker thru manual Changeover. D1 and D2 will trip respectively in auto.

3. Thru Unit Start Up.• Start Gas Turbine1/2 in Black Start mode. U1/U2

Breaker will close and D1/D2 will Trip in Auto.

Page 29: Electrical Sys -FGPS

Black Out Condition

Others:• During D1/D2 close condition—• Only Priority feeders can be closed- i.e ODA A

&B Breaker( Only emergency section, ODC I/c-A&B, and Common transformer breaker.)

• Other than Priority 6.6 KV fdr , no 6.6 KV fdr can be closed

• 415V,ODA-B/C D&E , CW &Chlorination fdr., OSF MCC, Nox and Misc MCC can not be closed.

Page 30: Electrical Sys -FGPS

Supply to Switchyard

Switchyard

Page 31: Electrical Sys -FGPS

EHV Control and Switchgear

• Circuit Breaker

• Isolator

• Current Transformer

• Capacitive Voltage Transformer

• Lightning Arrestor

• PLCC equipment

• Bus Switching Schemes

• Disturbance recorder

• Event logger

• Remote telemetering units

Page 32: Electrical Sys -FGPS

Line diagram

Page 33: Electrical Sys -FGPS

Bus Switching Schemes

3 Generators

Bus Coupler

Transfer Bay

4 Transmission lines

Transfer Bus

Main Bus-1

Main Bus-2

Double main and Transfer bus scheme

Page 34: Electrical Sys -FGPS

PLCC System

Tx

Rx

Tx

Rx

CVT

Wave trapSubstation A Substation B

Page 35: Electrical Sys -FGPS

Electrical Protections

• Generator and transformer protections• 6.6 kV Protections

– Station transformer protections – Motor protections– Transformer protections

• 220 kV Protections– Line protections– Bus bar protection– Breaker failure protection

Page 36: Electrical Sys -FGPS

VT Panel Protection Panel Terminal Box

Page 37: Electrical Sys -FGPS

Protection Panel

Page 38: Electrical Sys -FGPS

Numerical Relays

Page 39: Electrical Sys -FGPS

Backside of relays

Page 40: Electrical Sys -FGPS

Tripping Matrix

Tripping Relay

Page 41: Electrical Sys -FGPS

Generator Protection:Protection Functions (1)

Generator differentialOver current protectionVoltage dependent backupStator earth faultNeutral displacementSensitive directional E/F100% Stator E/FUnder & over voltageUnder & over frequency

87G50/5151V/2150/51N59N67N27TN27 & 5981U/O

2759

81O81U

51V21

50N51N

5051

67N

59N 27TN

87G

Page 42: Electrical Sys -FGPS

Reverse powerLow forward powerOverload powerField failureNegative phase seq.OverfluxingDead Machine (GUESS)RTD Thermal protection

32R32L32O40462427/5038/26Interconnectiondf/dt rate of change of frequencydVø Voltage vector shift

RTD

32R32L320

24

40 46

Generator Protection:Protection Functions (2)

MiCOM-P340-42

Page 43: Electrical Sys -FGPS

Settings

• Reverse Power Frequency • Under frequency • Overfrequency

• Rotor earth fault• Stator earth fault• Over Voltage• Under Voltage• Over Current• Under Excitation• Overflux • Generator Differential• Overall Differential• REF• Stator earth fault(95%)• Unbalanced Load

• -3.3 %

• 47.5 & 47.0 Hz• 51.5 & 52 Hz

• 5Kohm and 40 Kohm• 14ohm• 127V/ 143V• 70V• 125%• 5.04V• 1.1-1.4• 25%• 33%• 33%• 5V• 51% , 1.5Sec

Page 44: Electrical Sys -FGPS

STG GRP

Page 45: Electrical Sys -FGPS

6.6 kV Protections• Station transformer protections

– Three phase Over current protection.– Earth fault protection.– Restricted earth fault protection.

• Motor protection– IDMT over current protection– Earth fault protection

• Transformer protection– IDMT over current protection– Earth fault protection

Page 46: Electrical Sys -FGPS

EHV Protections

• Line protections

• Transformer protections

• Generator Protections

• Bus bar protection

• Breaker failure protection

Page 47: Electrical Sys -FGPS

Line protections

• Main I Distance protection (21-1)

• Main II Distance protection (21-2)

• Breaker failure relay.

• Trip circuit supervision relay

• Trip coil supervision relay.

• Fault locator

• Disturbance recorder

Page 48: Electrical Sys -FGPS

Distance Protection

Zone 1: 80%, 0mS

Zone 2: 120%,300mS

Zone 3: 200%,1000mS

A B

Page 49: Electrical Sys -FGPS

220 kV Transformer protections

• Transformer Differential protection.(87)• Three phase over current protection. (51)• Earth fault relay (Phase current balance)• Breaker failure relay.• Bucholz relay• Winding temperature relay• Oil temperature relay• Pressure relief device

Page 50: Electrical Sys -FGPS

DC SYSTEM

Page 51: Electrical Sys -FGPS

DC Systems

• 220 Volts DC Gas Turbine batteries

• 220 and 24 Volts Station batteries

• 432 Volts UPS batteries

• 220 Volts Emergency Lighting batteries

• 48 V Switchyard Battery systems

Page 52: Electrical Sys -FGPS

415 Volts System

• GT MCCs– All the LT auxiliaries of Gas turbine including:

• Auxiliary lube oil pump

• Generator cooling water pump motors

• GT cooling water pump motors

• Ventilation fans

• Battery chargers

• Jacking oil pump motor