48"
SINGLE RECEPTACLE
DUPLEX RECEPTACLE
2
SINGLE POLE (HORSE POWER RATED WHEN USED AS MOTOR DISCONNECT)
PC
DESCRIPTION
CEILING SURFACE MOUNTED LIGHT FIXTURE, CAPITAL LETTER IDICATESFIXTURE TYPE, SMALL LETTER INDICATES SWITCHING
RECESSED CEILING MOUNTED LIGHT FIXTURE
SUSPENDED LIGHT FIXTURE
TRACK AND TRACK LIGHT
SURFACE FLUORESCENT FIXTURE
EMERGENCY BATTERY LIGHT
PENDANT LIGHT FIXTURE
SYMBOL
A
7' - 6"
MOUNTINGHEIGHT
ELECTRICAL SYMBOL LEGEND
a
WALL MOUNTED LIGHT FIXTURE
CEILING EXIT SIGN, SHADED SIDE INDICATES LIGHTED FACE, ARROWSINSTALLED AS SHOWN
WALL EXIT SIGN
RECESSED FLUORESCENT
6" ABOVEDOORFRAME TOBOTTOM
WALL MOUNT OCCUPANCY SENSOR SWITCH
EMERGENCY REMOTE LAMP 7' - 6"
DOUBLE POLE 48"
33 - WAY 48"
44 - WAY 48"
LVLOW VOLTAGE 48"
M
DIMMER SWITCH 48"D
KEY OPERATED SWITCH 48"K
PILOT LIGHT (MAY BE USED WITH OTHER SWITCH TYPES) 48"P
MOMENTARY CONTACT 48"MC
PHOTOCELL 9' - 0"
POLE MOUNTED FIXTURE
CEILING MOUNT OCCUPANCY SENSOROS
TIME CONTROL SWITCH 48"T
M MOTION SENSOR SWITCH POWER PACKPP
C CONTACTOR (NUMBER INDICATES NUMBER OF POLES)2
DESCRIPTIONSYMBOL
18"
18"
DOUBLE DUPLEX RECEPTACLE 18"
TYPE L14-30 RECEPTACLE 18"A
TYPE L14-50 RECEPTACLE 6"B
SR
CIRCUIT BREAKER PANEL
WALL HEATER
HATCHED SYMBOL INDICATES REMOVED
DASHED SYMBOL INDICATES EXISTING
T
T1
BASEBOARD HEATER
LINE VOLTAGE THERMOSTAT
COMB. MOTOR STARTER
VARIABLE FREQUENCY DRIVE
DISCONNECT SWITCH.
CEILING MOUNTED VERTICAL MULTIPLE OUTLET ASSEMBLY
POWER OR DISTRIBUTION PANEL
MOTOR (SEE SCHEDULE)
TRANSFORMER
SPECIAL CABINET
CONDUIT TRANSITION DOWN
CONDUIT TRANSITION UP
BRANCH CIRCUIT HOME RUN
CONDUIT EXPOSED
SURFACE RACEWAY
CONDUIT STUBBED OUT
CONDUIT CONCEALED BELOW FLOOR
CONDUIT CONCEALED IN WALL OR OVERHEAD
SMOKE DETECTOR ('E' INDICATES DEVICE WITH ELEVATOR RECALL)
DUCT SMOKE DETECTOR
FLOORBOX COMMUNICATIONS OUTLET
1 KEYED NOTE
MULTIOUTLET ASSEMBLY , PROVIDE DEVICES AS SHOWN ON PLANS
GFCI RECEPTACLE 18"G
SPECIAL RECEPTACLE
FOURPLEX RECEPTACLE
SWITCHED DUPLEX RECEPTACLE
ISOLATED GROUND RECEPT (DUPLEX SHOWN)
FLOOR RECEPTACLE (DUPLEX SHOWN)
FOURPLEX RECEPTACLE WITH (1) DUPLEX SWITCHED AND (1)UNSWITCHED.
18"
18"
18"
18"
DUPLEX RECEPTACLE - HALF SWITCHED 18"
MOUNTINGHEIGHT
J
J CEILING MOUNTED JUNCTION BOX
WALL MOUNTED JUNCTION BOX
PUSH BUTTON, SEE DWG FOR TYPE 48"
48"
SF-1
DESCRIPTIONSYMBOLMOUNTING
HEIGHT
72"*
72"*
72"*
72"*
72"*
72"*
AUDIO/VISUAL INPUT JACK - 'V' INDICATES VIDEO/HDMI WALLPLATE
CEILING MOUNTED RECESSED SPEAKER
SURFACE MT SPEAKER
S
MICROPHONE OUTLET
CEILING MOUNTED HORN SPEAKER
VOLUME CONTROL
S
S
S
S
WALL MOUNTED SPEAKER
WALL MOUNTED HORN SPEAKER
WIRELESS CLOCK (120V POWERED)
90"
90"
* DISTANCE TO THE TOP OF THE EQUIPMENT OR DEVICE ** DISTANCE TO THE BOTTOM OF THE EQUIPMENT OR DEVICE
84"
V
M
48"
18"
A 18"
COMPUTER OUTLET (NUMBER INDICATES QUANTITY OF CABLES, NO NUMBERINDICATES ONE)
WALL TELEPHONE OUTLET
TELEPHONE OUTLET
W
TELEVISION/ FLAT PANEL MONITOR LOCATIONTV
2
WIRELESS ACCESS POINT OUTLET - QTY OF (2) CABLES AND JACKS AT EACH
18"
48"
18"
76"
CARD READER
KEYPAD
CR 48"
48"
BALANCED DOOR POSITION SWITCH
ELECTRIC STRIKEES
P
MAGNETIC LOCKML
12'AFF
IP CCTV CAMERA
DESCRIPTIONSYMBOLMOUNTING
HEIGHT
F MANUAL FIRE ALARM PULL STATION
H
FIXED TEMPERATURE DETECTOR
48"
S
FIRE ALARM HORN WITH STROBE
FIRE ALARM SPEAKER WITH STROBES 80"**
80"**
H
COMBINATION FIRE/SMOKE DAMPER OR SMOKE DAMPER BY DIVISION 23
DS
FIRE ALARM STROBE LIGHT 80"**
FIRE ALARM CHIME WITH STROBEC 80"**
FR FIRE ALARM MODULE/RELAY
MAGNETIC DOOR HOLD OPEN
SPRINKLER VALVE TAMPER SWITCH, NUMBER INDICATES QUANTITY
SPRINKLER FLOW SWITCH, NUMBER INDICATES QUANTITY
SPRINKLER PRESSURE SWITCH
FIRE ALARM REMOTE ANNUNCIATORFA ANNUN
72"*
FIRE ALARM CONTROL PANELFACP
72"*
CABLE TRAY
CONDUIT SLEEVE (SIZE DENOTED)
UE UNDERGROUND ELECTRICAL
ABBREVATIONS
A AMPERE
AC ABOVE COUNTER
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AL ALUMINUM
AMP AMPERE
ATS AUTOMATIC TRANSFER SWITCH
AV AUDIO VISUAL
BC BELOW COUNTER
C CONDUIT
CU COPPER
CUH CABINET UNIT HEATER
EF EXHAUST FAN
EWC ELECTRIC WATER COOLER
ANN ANNUNCIATOR
FA FIRE ALARM
FACP FIRE ALARM CONTROL PANEL
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GR GROUND
HP HORSEPOWER
JBOX JUNCTION BOX
KV KILOVOLT
KW KILOWATT
PH PHASE
TV TELEVISION
W WIRE
WP WEATHERPROOF
WH WATERHEATER
V VOLT
VFD VARIABLE FREQUENCY DRIVE
UE UNDERGROUND ELECTRICAL
RTU ROOF TOP UNIT
SWBD SWITCHBOARD
LIGHT FIXTURE WITH EMERGENCY BALLAST
1. NOT ALL SYMBOLS OR ABBREVATIONS ARE APPLICABLE TO THESE DRAWIANGS. 2. MOUNTING HEIGHT IS TO THE CENTER OF DEVICE UNLESS NOTED OTHERWISE. 3. FOR DEVICES SHOWN AS 48 INCHES MOUNTING HEIGHT, WHEN INSTALLED IN MASONRY BLOCK WALLS, MOUNTING AT 48 INCHES TO THE TOP OF THE OUTLET BOX IS ACCEPTABLE.
AREA OF RESCUE STATIONAR
L
P
PUSH BUTTONPB 48"
C
ELECTRIFIED LOCKEL
AP
DH
FS
TS
KP
ALARM SIRENA 12'AFF
TELEPHONE RINGER - EMERGENCY FIRE PHONETR
LUMINAIRE SCHEDULE
TYPE MANUFACTURERSCATALOG
INFORMATIONFIXTURE DESCRIPTION
LAMP DATA DRIVER DATA INPUT
WATTSVOLTAGE MOUNTING REMARKS
NO. TYPE NO. TYPE
A1
METALUX 2GR SERIES 2' X 4' RECESSED LED TROFFER, REGRESSED ALUMINUM DOOR FRAME HINGED AND LATCHED
WITH 0.125 INCH THICK PATTERN #12 DIFFUSER. 4900 LUMENS
LED 0-10V DIMMING DRIVER 38 277 RECESSEDOR EQUAL
A2
METALUX 2GR SERIES SAME AS TYPE 'A1', 2'X2' VERSION, 4300 LUMENS.
LED 0-10V DIMMING DRIVER 33 277 RECESSEDOR EQUAL
C1
HALO H4 LED 4 INCH LED RECESSED DOWNLIGHT. ALUMINUM CONSTRUCTION, 4000 DEGREE COLOR
TEMPERATURE,80 CRI, INITIAL LUMEN OUTPUT OF 600. WET LISTED. WHITE REFLECTOR WITH
WHITE TRIM RING. LED LED DRIVER 30 277 RECESSEDOR EQUAL SERIES
E1
LITHONIA LV SERIES SINGLE FACE LED EXIT LUMINAIRE, DIE CAST ALUMINUM HOUSING, WHITE BODY AND CANOPY,
POLYCARBONATE COVER, STENCIL FACE, RED LETTERS, AC ONLY.
LED LED DRIVER 1.5 277 UNIVERSALOR EQUAL
EM
LITHONIA INDX SERIES INDUSTRIAL BATTERY PACK LIGHT, 90 MIN ILLUMINATION, HIGH TEMPERATURE BATTERY,
POLYCARBONATE HOUSING AND LENS, GASKETED.
LED LED DRIVER 1.5 277 UNIVERSALOR EQUAL
F1
METALUX SN LED SERIES 4 FOOT LED STRIP LIGHT, WIDE COVERAGE SEMI FROST LENS, HIGH GLOSS BAKED ENAMEL
FINISH, 4000K, 5400 LUMENS, 80 CRI.
LED LED DRIVER 43 277 SURFACEOR EQUAL
F2
LITHONIA LBLED SERIES 4 FOOT LED CURVED BASKET WRAPAROUND LIGHT, #12 PRISMATIC DIFFUSER, NARROW HOUSING,
4000K, 4800 LUMENS.
LED LED DRIVER 32 277 SURFACEOR EQUAL
F3
METALUX SN LED SERIES 4 FOOT LED STRIP LIGHT, WIDE COVERAGE SEMI FROST LENS, HIGH GLOSS BAKED ENAMEL
FINISH, 4000K, 7400 LUMENS, 80 CRI.
LED LED DRIVER 64 277 SUSPENDED
PROVIDE WITH STEM MOUNT KIT
OR EQUAL
H1
HOLOPHANE PHUZION PHS LED, HIGH BAY LUMINAIRE, CAST ALUMINUM HOUSING, PRISMATIC GLASS LENS, PENDANT
MOUNTING, UPLIGHT, 4000K, 80 CRI, WIDE OPTIC, WHITE FINISH, 18000 LUMENS, HOOK
MOUNT WITH SAFETY CHAIN LED LED DRIVER 166 277 SUSPENDED
SUSPEND 24'AFF TYPICAL.
OR EQUAL SERIES
U1
FAIL SAFE UCL SERIES 2 FOOT LED UNDERCABINET FIXTURE, SOLID FACE, ACRYLIC LENS, WHITE FINISH, 3500K,
750 LUMENS/FT, INTEGRAL TOGGLE SWITCH.
LED LED DRIVER 9 120 SURFACEOR EQUAL
V1
TERON VICEROY SERIES 2 FOOT LED VANITY FIXTURE WITH (2) 6W LED STRIPS, SOLID FACE, ACRYLIC LENS,
UP/DOWNLIGHT HOUSING, STEEL TEXTURED WHITE HOUSING, 4000K
LED LED DRIVER 20 277 SURFACEOR EQUAL
W1
LITHONIA D SERIES SIZE 0 EXTERIOR WALL MOUNTED AREA FIXTURE, P1 VERSION, FORWARD THROW
DISTRIBUTION.SINGLE PIECE DIE-CAST ALUMINUM HOUSING,DARK BRONZE FINISH, 4000K,
BI-LEVEL 50% MOTION SENSOR, GLARE SHIELD. LED LED-DRIVER 50 277 WALL
SEE DRAWINGS FOR MOUNTING HEIGHT
OR EQUAL
W2
LITHONIA DSXW SERIES SIZE 1 EXTERIOR WALL PACK, 10 LED, TYPE II DISTRIBUTION SINGLE PIECE DIE-CAST
ALUMINUM HOUSING, SINGLE PIECE DIE CAST ALUMINUM HOUSING, DARK BRONZE FINISH,
4000K. LED LED-DRIVER 14 277 WALL
SEE DRAWINGS FOR MOUNTING HEIGHT
OR EQUAL
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:2
4 P
M
E1437-14-112
REPLACE BOILER PLANT 10.26.18ELECTRICAL SYMBOLS AND
ABBREVIATIONS
100% CONSTRUCTION DOCUMENT
5615-193 E1.DWG
AS NOTED
SEE DRAWINGS AND ONE-LINE
FOR EXACT QUANTITY AND
SIZE OF WIRING AND
CONDUITS
15-193 E2.DWG
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Ve
tera
ns A
ffa
irs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
10 - BOILER PLANT
CH MB CH
Project Phase
www.jlgarchitects.com
copyright © 2015
214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
KEY PLAN
437-14-112
REPLACE BOILER PLANT 10.26.18
100% CONSTRUCTION DOCUMENT
Dwg. of 69
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
DATE 10-26-18
ELECTRICAL SITE PLAN AND DETAILS
AS NOTED
0' 30'15' 60'
0' 30'15' 60'
57
E2
0' 4'2' 8'
0' 4'2' 8'
15-193 E3.DWG
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Ve
tera
ns A
ffa
irs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
10 - BOILER PLANT
CH MB CH
Project Phase
www.jlgarchitects.com
copyright © 2015
214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
KEY PLAN
437-14-112
REPLACE BOILER PLANT 10.26.18
100% CONSTRUCTION DOCUMENT
Dwg. of 69
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
DATE 10-26-18
ELECTRICAL DEMOLITION PLANS
AS NOTED
58
E3
3
4 3
4
3
3
3
3
43
3 3
4
BOILER ROOM
101
ELECTRICAL
102
VESTIBULE
100
SHOP
105
GENERATOR
ROOM
107
STORAGE
CLOSET
106
HOUSEKEEPING
CLOSET
104
OFFICE/CONTROL
103
LOCKER ROOM
108
LOWER LEVEL
001
SHOP ALCOVE
105A
F1 F1
F1 F1
F1 F1
F1 F1
F1 F1
F1
F1
F1 F1 F1 F1
F1F1F1F1
F1
F1
F1
F1
F1 F1
F1
F1
E1
A1
B1
A1
A2
EB101N1 EB101N2 EB101N3
TO MEZZANINELEVEL LIGHTS,SEE SHEET E5
E1
F1
E1
TO TUNNELLIGHTS
E1
E
M
M
V1
U1
C1B1
1
W1 W2
W2
W1
W1
W1
W1
E1
U1
U1
1
D
EB101N3-5
EB101N3-3
EB101N3-9
EB101N3-7
B1
B1B1
D
TO UPPER LEVEL LIGHTINGSEE SHEET E5
TO UPPER LEVEL LIGHTINGSEE SHEET E5
W1
W1
W1 W1 W2
W1
W15
4
4
44
5
6
W1
54444
4
4
4
EB101N1-28
F1 F1 F1 F1 F1 F1 F1 F1
EM
EM
EM EM
EM
F1 F1 F1 F1
F1 F1 F1 F1 F1 F1
7
2
EM
EM
EM
EM
EM
EB101N3-11
EB101N3-13
EB101N3-15
VIA PHOTOCELL
VIA PHOTOCELL
PC 9
3
EM
EM
EM
nl
F1
F1
10
TO UPPER LEVEL LIGHTINGSEE SHEET E5
7 7 7 77
8 8 8
2 HOUR RATED WALL
1 HOUR RATED WALL
C
EXTERIOR LIGHTING CONTACTOR
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:2
6 P
M
E4437-14-112
REPLACE BOILER PLANT 10.26.18MAIN LEVEL REMODELING
PLAN - LIGHTING
100% CONSTRUCTION DOCUMENT
59
1/4" = 1'-0"1MAIN LEVEL REMODELING PLAN - LIGHTING
1
PLAN NOTES:
TO NEAREST AVAILABLE 120V RECEPTACLECIRCUIT.
WALL MOUNT AT 7' AFF.
CONNECT VESTIBULE LIGHT TO OUTDOOR LIGHTINGFOR CONTROL VIA PHOTOCELL.
MOUNT CENTER OF FIXTURE AT 16'-4".
MOUNT CENTER OF FIXTURE AT 9'-0".
MOUNT CENTER OF FIXTURE AT 12'-0".
MOUNT FIXTURE BELOW PIPE RACKING, COORDINATEWITH MECHANICAL CONTRACTOR.
MOUNT FIXTURE TO BOTTOM OF CATWALK SYSTEM.
PROVIDE PHOTOCELL TO CONTROL OUTDOOR LIGHTINGAND OTHER FIXTURES AS NOTED.
COORDINATE EXACT PLACEMENT OF LIGHT FIXTURES WITHMECHANICAL SYSTEMS IN THIS ROOM.
2
3
15-193 E4.DWG
N
4
5
6
7
8
9
AS NOTED
10
OS
4
F2 V1
F3 F3
A1
A1
BOILER ROOM
101
BATHROOM
203
OFFICE
202
BOILER ROOM
101
H1 H1 H1 H1 H1
H1
H1 H1H1H1H1H1
H1 H1 H1H1 H1
H1
D
1
TO SWITCH BELOW,SEE SHEET E4
EB101N3-2
EB101N3-4
3
3
3
EM
EM
EM EM
EM
EM4
4 4
4
EM
3
F3 F3
UPPER LEVEL
201
F3 F3
F3 F3
16'AFF (TYP)
2 HOUR RATED WALLUPPER
MEZZANINE
301
F1F1
2
3
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:2
7 P
M
E5437-14-112
REPLACE BOILER PLANT 10.26.18UPPER LEVEL REMODELING
PLAN - LIGHTING
100% CONSTRUCTION DOCUMENT
60
1/4" = 1'-0"1UPPER LEVEL REMODELING PLAN - LIGHTING
1/4" = 1'-0"2UPPER MEZZANINE REMODELING PLAN - LIGHTING
1
PLAN NOTES:
TO UPPER MEZZANINE LIGHTING, SEE 2/E5 FOR CONTINUATION.
TO LIGHTING ON MEZZANINE BELOW, SEE 1/E5 FOR CONTINUATION.
TO SWITCH BELOW, SEE 1/E5 FOR CONTINUATION.
MOUNT TO CEILING STRUCTURE ABOVE CATWALK.
2
15-193 E5.DWG
N
3
4
AS NOTED
48"
J
J
GWP
48"
48"
32 33
31
30
EX
28
29
48"
1 2 3
EX
G
G G
48" 48"
GWP
ACG
J
ACG
G
6
GWP
GWP
GWP
GWP
GWP
GWP
GWP
GWP
EWCG
GWP
25
26
48" 48"
GWP
GWP
GWP
34
13
8
4
9
10
5
J
J
J
EX
20
22 23 24
GWP
GWP
27
48"
21
J
BOILER ROOM
101
ELECTRICAL
102
VESTIBULE
100
SHOP
105
GENERATOR
ROOM
107
STORAGE
CLOSET
106
HOUSEKEEPING
CLOSET
104
OFFICE/CONTROL
103
LOCKER ROOM
108
LOWER LEVEL
001
SHOP ALCOVE
105A
EB101N1EB101N2EB101N3
FACP
T10-LV1
EXISTING EMERGENCYDOMESTIC WATER PUMPS
EXISTINGFAN
CHEMICALPUMPS
EXISTINGTRANSFERPUMPS
BOILER B-1 BOILER B-2 BOILER B-3
ANN
EXISTING GENSETANNUNCIATORS
AC
MOA
AC
MOA
REF
MICRO
NEW DAYTANK ANDPUMPS
1
9
7
6
4
5
10-SWBD
ANN
NEW GENSETANNUNCIATOR
EB101N1-13,15
EB101N1-20,22
EB101N1-33
EB101N1-16,18
EB101N1-4
EB101N1-10,12,14
10
12
EB101N1-8
EB101N1-27
EB101N1-21,23,25
21 2123 2325 25 21
EB101N1-2
EB101N1-45
EB101N1-47
EB101N1-1,3
EB101N1-6
EB101N1-35,37
EB101N1-19
48" 48" 48"
48"48"
48" 48"
SALVAGEDFEEDWATERPUMPSP-1 AND P-2
EB101N1-49,51
48"
48"
48"
TK-01
8
SP-1
HTP-01
WH-2UNDER COUNTER
ST-1
IN PIT BELOW
WH-3
WH-4
DA-1
BATTERYCHARGER
EB101N2-11EB101N2-13,15,17
EB101N3-19,21,23 (3)#10,#10G IN 3/4"C.
ANNANNANN
EB101N1-7,9,11
7
9
EB101N1-43
11 2
20
20
20
20
20
22
22
22
22
20
10
4949 51
51
11
37 35
14
EXHAUST FAN VFDS
AC
AC
EB101N2-35
12
13
14
EXISTINGVFD
EXISTINGVFD
EF-1 EF-2 EF-3
EB101N1-5
3 1
1
3
1616 1818
EF-5
BOILER COMPRESSR BC-1 BOILER COMPRESSR BC-2 BOILER COMPRESSR BC-3
P1 P2
P1
P2
23
EB101N2-39
EB10N1-34
EB101N1-36
15
15
DP-01
16 16
16
P-3
P-4
P-6 P-7
17
EB101N1-38
3
GENERATORREMOTEE-STOP BUTTON
P-8
P-9
EF-6
BELOW LANDING
AC
18
18
SEE SHEET E2 FOR CONTINUATION
19
19
SEE SHEET E2 FOR CONTINUATION
20
400KW GENERATOR
2122
EXHAUST FAN EF-5ECM CONTROLLER
EB101N1-38
23
EB101N1-4024
25
EB101N1-48
26
26
27
1 HOUR RATED WALL
2 HOUR RATED WALL
28
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:2
8 P
M
E6437-14-112
REPLACE BOILER PLANT 10.26.18MAIN LEVEL REMODELING PLAN
- POWER
100% CONSTRUCTION DOCUMENT
61
1/4" = 1'-0"1MAIN LEVEL REMODELING PLAN - POWER
PROVIDE NEW MOA, SEE SECTION 26 27 26 WIRINGDEVICES.
PROVIDE 3/4" PLYWOOD BACKBOARD FROM FLOORTO 8'AFF, PAINT WITH TWO COATS FIRE RETARDANTPAINT. DO NOT PAINT OVER UL LABEL.
PROVIDE SEPARATE 120V CIRCUIT FOR AIRCOMPRESSOR CONTROL RELAYS AND ADJACENT AIRDRYER.
NEW UNDERGROUND FEEDER CONDUITS, SEE SHEETE2 AND DETAIL 2/E10 FOR REQUIREMENTS.
CUT AND PATCH EXISTING CONCRETE FLOOR ASREQUIRED FOR INSTALLATION OF NEW CONDUITS,ROUTE SHOWN IS APPROXIMATE, COORDINATE WITHHOLDOUTS ON ELECTRICAL EQUIPMENT.
NEW 400 KW GENERATOR, SEE ONE LINE DIAGRAMON E13 FOR WIRING REQUIREMENTS. MAXIMUMDIMENSIONS ON GENERATOR ARE 138 INCHES LONGBY 65 INCHES WIDE. BASIS OF DESIGN ISCATERPILLAR E13 SERIES.
CIRCUIT BREAKERS REQUIRED TO BE MOUNTED ONNORTH SIDE OF GENSET.
WATER JACKET HEATER, FIELD COORDINATE EXACTLOCATION ON GENSET.
PROVIDE 120V CONNECTION TO MASTER CONTROLPANEL, COORDINATE WITH MECHANICAL.
RECONNECT EXISTING COMPRESSOR THROUGH NEWDISCONNECT TO CIRCUIT INDICATED.
RECONNECT EXISTING AIR DRYER THROUGH NEWDISCONNECT TO CIRCUIT INDICATED.
PROVIDE 120V CONNECTION FOR REINSTALLATIONOF EXISTING UNDERGROUND TANK MONITORINGSYSTEM CONTROL PANEL, RECONNECT EXISTINGALARMS AND MONITORING DEVICES AND REINSTALLALL EQUIPMENT.
ALL ELECTRICAL CONDUIT TO BE CONCEALED IN THISROOM, CUT AND PATCH EXISTING WALLS ASREQUIRED FOR INSTALLATION OF NEW DEVICES.
PROVIDE EQUAL TO ASCO MTS SERIES MANUALTRANSFER SWITCH WITH TEMPORARY GENERATORCONNECTIONS, SWITCHED NEUTRAL, NEMA 3RENCLOSURE,INTEGRAL QUICK CONNECT CAMLOCKCONNECTIONS. SEE 2/E10 FOR WIRINGREQUIREMENTS.
13
14
15
15-193 E6.DWG
N
16
17
AS NOTED
18
19
20
21
22
PLAN NOTES:
1 PROVIDE 120V CONNECTION ON DEDICATED20A CIRCUIT TO ELECTRIC DOOR LOCKINGHARDWARE POWER SUPPLIES, COORDINATEWITH HARDWARE SUPPLIER FOR EXACTQUANTITY OF POWER SUPPLIES TO BE USED.
PROVIDE 120V CONNECTION ON DEDICATED20A CIRCUIT TO INTRUSION DETECTIONSYSTEM EQUIPMENT.
PROVIDE NEW STARTER/DISCONNECTS AND RECONNECTSALVAGED PUMPS, SEE MOTOR AND EQUIPMENT SCHEDULEFOR ADDITIONAL INFORMATION.
PROVIDE 120V CONNECTION WITHDISCONNECT TO ELECTRIC COOKTOP.
PROVIDE RECEPTACLE AT SHELF LOCATIONFOR MICROWAVE, COORDINATE EXACTMOUNTING HEIGHT WITH CASEWORKELEVATIONS.
PROVIDE 120V CONNECTION TO MEDGASALARM PANEL, COORDINATE WITH MECHANICALCONTRACTOR.
PROVIDE DEDICATED 20 CIRCUIT FOR FIRE ALARMCONTROL PANEL.
CONNECT EXISTING RELOCATED FUEL OIL PUMPS, PROVIDEWITH NEW STARTERS, SEE MOTOR AND EQUIPMENTSCHEDULE FOR ADDITIONAL INFORMATION.
PROVIDE 120V CONNECTION OF DEDICATED CIRCUITFOR CARD ACCESS SYSTEM CONTROL PANELS.
(3)#6,#10G IN 1" CONDUIT.
PROVIDE 120V CONNECTION TO DANGEROUSGAS DETECTION SYSTEM CONTROL PANEL, COORDINATEWITH MECHANICAL CONTRACTOR.
RECIRCUIT EXISTING PUMPS THROUGH EXISTING WALLMOUNTED DISCONNECTS TO NEW PANEL SHOWN.
PROVIDE SINGLE POINT 208V/1 PHASE CONNECTION TOSUMP CONTROL PANEL PER MOTOR AND EQUIPMENTSCHEDULE. PROVIDE SEPARATE 120V CIRCUUIT FORAUDIBLE ALARM AS NOTED ON THE PLANS.
RECIRCUIT EXISTING PUMPS THROUGH EXISTING FLOORMOUNTED VFDS TO NEW PANEL, SEE MOTOR ANDEQUIPMENT SCHEDULE FOR PANEL AND CIRCUIT NUMBER.
2
3
4
5
6
7
8
9
10
11
12
23
24
25
26
27
28
ACG
1617
18
11
19
12
J
15
14
7
BOILER ROOM
101
UPPER LEVEL
201
BATHROOM
203
OFFICE
202
EXISTINGDATARACK
EXISTINGVISNMETERS
EB101N1-27,29,31
PAGINGRACK
EB101N1-39,41
EB101N1-53
EB101N1-37
EF-1EF-2
EF-3
AH-1
EF-4
AH-2
48"
48"29
31
EB101N1-26
2
SS-21
2 HOUR RATED WALL
TO PLATFORM ABOVE
48"27
VIDEO SURVELLANCERACK
UPPER
MEZZANINE
301
SS-1
1
WH-1
TO OFFICE BELOW
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:2
9 P
M
E7437-14-112
REPLACE BOILER PLANT 10.26.18UPPER LEVEL PLAN - POWER
100% CONSTRUCTION DOCUMENT
62
1/4" = 1'-0"1UPPER LEVEL REMODELING PLAN - POWER
1/4" = 1'-0"2UPPPER MEZZANINE LEVEL REMODELING PLAN - POWER
PLAN NOTES:
1 WIRING BETWEEN CONDENSING UNIT AND EVAPORATORUNITS BY MECHANICAL CONTRACTOR.
PROVIDE (2) 20A/120V CIRCUITS FOR EXISTING VISN METERS,RECONNECT (7) EXISTING METER DISCONNECTS, ALTERNATE CIRCUITBETWEEN EACH DISCONNECT.
2
15-193 E7.DWG
N
AS NOTED
S
S
SF
S
CR
FS
CR
CRS
F
S
S
FA ANNUNS
S
SF
S
CR
H
A
A
A
A
F
S
GENERATOR
ROOM
107
SHOP
105
LOCKER ROOM
108
OFFICE/CONTROL
103
BOILER ROOM
101
LOWER LEVEL
001
ELECTRICAL
102
16' AFF
16' AFF
CARD ACCESS PANEL
INTRUSION DETECTION PANEL
8' AFF(LOWERLEVEL)
9' AFF
9' AFF
9' AFF
P P9' AFF
9' AFF
P
P
A
9' AFF
9' AFF
A
A
IC
M3
16' AFF
AC3
AC3
MS
W
A
A
A
A
IC
P
EXISTING TELEPHONEBLOCKS
A
6
6
A
9' AFF
3
1
66
66
P
3
7
7
6
5
2
7
7
36
3
7
16' AFFA
FIRE SPRINKLER TAMPERAND FLOW SWITCHES
MS
MS
MS
MS
MS
5
5
5
5
A
A
P
5
5
A
5
A
A6
EXISTING FIBER PULLBOX
AP
AP
AP
AP
5
6
TO MEZZANINE LEVEL
4
9' AFF
FS TS 5
8
8
8
8
8
10
WP
11
8
12' AFF
CLG
12
13
13
14
TS
6
6
W
16
15
16
S
16
S
16
S
S
16
S
16
17
FACP
13
12' AFF
12' AFF
12' AFF
12' AFF
12' AFF
12' AFF
12' AFF
12' AFF
12'
12'
W
W
K18
K
18
K
18
K
18
K
18
S
S
12' AFF 13
12' AFF
TR
TR
TR
TR16
TR
8'AFF
8'AFF
TR
TR
19
KP
19KP
19KP
19KP
9
WALLS IN GENERATOR ROOMHAVE A 1 HOUR RATING
1 HOUR RATED WALL
2 HOUR RATED WALL
9'AFF
A
6
CLG
A
6
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:3
0 P
M
E8437-14-112
REPLACE BOILER PLANT 10.26.18MAIN LEVEL REMODELING PLAN
- SYSTEMS
100% CONSTRUCTION DOCUMENT
63
1/4" = 1'-0"1MAIN LEVEL REMODELING PLAN - SYSTEMS
REINSTALL EXISTING ACCESS POINT IN NEW CEILING GRID.
PROVIDE NEW PAGING HORN, CONNECT TO EXISTING BOILERPAGING ZONE.
PROVIDE ADDRESSABLE FIRE ALARM MODULE ANDASSOCIATED CONNECTIONS TO EXTERIOR POST INDICATORVALVE TO MONITOR VALVE POSITION, PROGRAM TOGENERATE TROUBLE CONDITION ON FACP WHEN VALVE ISCLOSED.
INSTALL SALVAGED FIRE PHONE, AND CONNECT TO NEW FIREPHONE ALERT SPEAKER.
PROVIDE TELEPHONE AUDIOV/VISUAL SOUNDER EQUAL TOWHEELOCK UTA SERIES REMOTE RINGER, CONNECT TO FIREPHONE FOR REMOTE ANNUCIATION OF RINGER, PROVIDEREMOTE POWER SUPPLY AS REQUIRED.
PROVIDE NEW SIMPLEX FIRE ALARM PANEL PER SECTION 283100, CONNECT TO EXISTING VA CAMPUS SIMPLEX MAPNETNETWORK CONNECTION IN THIS BUILDING.
PROVIDE KEYED SWITCH WITH CYLINDER TO MATCH VAMASTER KEYING SYSTEM, CONNECT TO CARD ACCESSSYSTEM TO SHUNT DOOR POSITION SWITCH TO ALLOEXTENDED HOLD OPEN.
PROVIDE INTRUSION DETECTION SYSTEM KEYPAD, SEEDETAIL 10/E12 FOR ADDITIONAL INFORMATION.
15-193 E8.DWG
N
AS NOTED
12
13
14
15
16
17
GENERAL NOTES:
1. ALL PAGING SYSTEM WIRING, SECURITY SYSTEM WIRING, ANDCAMERA WIRING TO BE IN MINIMUM 3/4" CONDUIT, ORANGE INCOLOR.
2. ALL FIRE ALARM SYSTEM WIRING SHALL BE IN MINIMUM 3/4"CONDUIT, RED IN COLOR.
3. ALL DATA/TELEPHONE WIRING SHALL BE IN MINIMUM 3/4"CONDUIT, ORANGE IN COLOR, WHERE EXPOSED TO VIEW ORROUTED ACROSS OPEN SPACES.
18
19
PLAN NOTES:
1 PROVIDE EQUAL TO AIPHONE JP-DV SERIES SURFACEMOUNTED. VANDAL PROOF VIDEOINTERCOM SYSTEM.PROVIDE WITH EXTERNALSIGNALING RELAY TO ACTIVATEINTERNALDOORBELL SOUNDERS.
PROVIDE EQUAL TO AIPHONE JPS SERIES 7 INCH VIDEOINTERCOM MASTER STATION, DESKTOP MOUNTING, CONNECTTO EXTERIORDOOR INTERCOM STATION, SEE PLAN NOTE #1.PROVIDE CONNECTION FROM MASTERSTATION TO RELEASEELECTRIC DOORHARDWARE ON EXTERIOR DOOR ADJACENTTO THE EXTERIOR INTERCOM.
PROVIDE CARD ACCESS AND DOOR MONITORING EQUIPMENT,SEE DETAIL 9/E12 FOR TYPICAL ROUGH IN AND WIRINGREQUIREMENTS.
PROVIDE DOOR POSITION MONITORING AT THIS DOOR,CONNECT TO ALARM ANNUNCIATOR PANEL IN CONTROLROOM 103.
INTRUSION DETECTION ALARM .DOOR ALARM TO SOUND UPONDOOR FORCE OR DOOR PROP ALARM, VALID CARD SWIPE ORKEYPAD CODE ENTRY SHALL DEACTIVATE ALARM.
PROVIDE 3/4” CONDUIT FROM CAMERA TO VIDEOSURVEILLANCE SYSTEM RACK ON MEZZANINE LEVEL FORVIDEO SURVEILLANCE CAMERA. MOUNT CAMERA AT HEIGHTINDICATED OR TO CEILING STRUCTURE BOTTOM WHERENOTED.
REINSTALL AND RECONNECT SALVAGED SPEAKER TOEXISTING SPEAKER WIRING.
PROVIDE CEILING MOUNTED MOTION SENSOR,CONNECT TO INTRUSION DETECTION SYSTEM PANEL IN 3/4"CONDUIT.
PROVIDE DATA JACK AT BOILER PLANT MASTER CONTROLPANEL, COORDINATE WITH MECHANICAL CONTRACTOR.PROVIDE CABLING IN 3/4" CONDUIT TO MEZZANINE DATARACK.
INSTALL DEVICE IN LOWER LEVEL UNDERNEATH STAIRSTRUCTURE NEAR STEAM TUNNEL ENTRANCE.
PROVIDE WEATHERPROOF FIRE ALARM HORN/STROBE ABOVEFIRE DEPARTMENT CONNECTION. PROGRAM TO ACTIVATEUPON SPRINKLER SYSTEM FLOW.
2
3
4
5
6
7
8
9
10
11
S S S
S
F
BATHROOM
203
OFFICE
202
UPPER LEVEL
201
IC
M
9' AFF
EXISTINGDATA RACK
2 2
1
AP
A
3
4
5
TO LOWER LEVEL
J
A
CLG CLG
CLG
6
CLG
CLG
DS
DS
DS
DS
S
S S S
S
7
7J
J
S
8
9
9
2 HOUR RATED WALL
9
9
PAGING RACK
VIDEO SURV. RACK
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:3
1 P
M
E9437-14-112
REPLACE BOILER PLANT 10.26.18UPPER LEVEL REMODELING
PLAN - SYSTEMS
100% CONSTRUCTION DOCUMENT
64
1/4" = 1'-0"1UPPER LEVEL REMODELING PLAN - SYSTEMS
PLAN NOTES:
1 PROVIDE EQUAL TO AIPHONE JPS SERIES 7 INCH VIDEO INTERCOMSTATION, DESKTOP MOUNTING, CONNECT TO EXTERIOR DOORSTATION. PROVIDE CONNECTION TO RELEASE ELECTRIC DOORLOCK FROM MASTER STATION.
REINSTALL SALVAGED PUBLIC ADDRESS SYSTEM SPEAKER.
INSTRUSION DETECTION SYSTEM AUDIBLE ALARM. DOOR ALARM TOSOUND UPON DOOR FORCE OR DOOR PROP ALARM, VALID CARDSWIPE OR KEYPAD CODE SHALL DEACTIVATE ALARM.
PROVIDE (2) 2" CONDUITS FOR NEW COMMUNICATIONS CABLING,ROUTE ADJACENT TO MECHANICAL PIPING.
ROUTE COMMUNICATIONS CONDUITS DOWN WALL INTO EXISTINGDATA CABINET.
ROUTE COMMUNICATIONS CONDUIT DOWN WALL AND STUB INTOACCESSIBLE CEILING SPACE IN CONTROL OFFICE BELOW.
MOUNT REMOTE TEST SWITCH FOR DUCT DETECTORS INACCESSIBLE SPACE ABOVE CATWALK, FIELD COORDINATE EXACTLOCATION.
PROVIDE TELEPHONE AUDIOV/VISUAL SOUNDER EQUAL TOWHEELOCK UTA SERIES REMOTE RINGER, CONNECT TO FIREPHONE FOR REMOTE ANNUCIATION OF RINGER, PROVIDE REMOTEPOWER SUPPLY AS REQUIRED.
PROVIDE DUCT SMOKE DETECTOR IN SUPPLY AND RETURN WITHCONNECTION TO FAN SHUTDOWN RELAY.
2
3
4
5
6
15-193 E9.DWG
N
AS NOTED
7
8
GENERAL NOTES:
1. ALL PAGING SYSTEM WIRING, SECURITY SYSTEM WIRING,AND CAMERA WIRING TO BE IN MINIMUM 3/4" CONDUIT,ORANGE IN COLOR.
2. ALL FIRE ALARM SYSTEM WIRING SHALL BE IN MINIMUM 3/4"CONDUIT, RED IN COLOR.
3. ALL DATA/TELEPHONE WIRING SHALL BE IN MINIMUM 3/4"CONDUIT, ORANGE IN COLOR, WHERE EXPOSED TO VIEW ORROUTED ACROSS OPEN SPACES.
9
J
800
A-3
P
EXISTING BUILDING 10SWITCHGEAR MAIN SWITCH480V
BUILDING 10GENERATOR300 kVA
BUILDING 10SWITCHBOARD480V, 800A
BUILDING
10 ATS
XFMR101C2,45.0 kVA
PANEL
101C2
WELDINGXFMR,15.0 kVA
WELDINGPANEL240V
PANEL
101W2
G
500A-3P
100
A-3
P
60
A-3
P
PANEL101W1480V
MCC10480V
600
A-3
P
XFMR
T-101C1
30 kVA
100
A-3
P
100
A-3
P
60
A-3
P
BLDG
50
PANEL
AIR COOLED CHILLER ACCH-4
SWITCH
SECTIONALIZINGSECTIONALIZING
SWITCH
EXISTING
SAC-2SAC-1
23.9KV
XCEL SOURCE #3
800
150E 150E
23.9KV
XCEL SOURCE #4
M
- EPDM STRESSCONE TERMINATIONS
- ELBOW TERMINATIONS
- FUSE
- SWITCH
- TRANSFORMER
- METER
- CURRENT TRANSFORMER
- POTENTIAL TRANSFORMER
EXISTING
25KV SERVICEDISCONNECTSWITCHGEARWITH METERINGSS-SOUTH
25E
SWITCH
SECTIONALIZING
S56-1
50E50E
PULL BOX
CHILLER PLANT FEED#1 CHILLER PLANT FEED#2
ADD FUSE
EXISTING VAULT
EXISTING
50E
T10-1
BOILER PLANT FEED #1 -SEE 2/E10
T10-2
BOILER PLANT FEED #2 -SEE 2/E10
50E
SWITCH
SECTIONALIZING
S10-1
NEW
TO SPARE OUTPUT
800A-3P
KIRK KEYINTERLOCK
SEE
1/E12
K K KDRAW OUT800A-3PLSIG
DRAW OUT800A-3PLSIG
T10-LV1150 KVA-480VKV-PRI 120/208-SEC
50A
-3P
PANEL
EB101N3
(4)3
/0+
#6G
ND
IN
2"C
.
SPD
50A
-3P
KIRK KEYINTERLOCK
LSIG 200
A-3
P
50A
-3P
100
A-3
P
90A
-3P
15A
-3P
225
A-3
P
PANELEB101N1
PANEL
EB101N2
SPD
BOILER
90A
-3P
BOILER
INTEGRAL ATS -OPEN TRANSITION
(4) 3/0+#6 GNDIN 2"C.
BLDG
50
PANEL
(4)#
3+
#8
GN
D IN
2"
C.
800
A-3
P
800
A-3
P
INTEGRAL ATS -OPEN TRANSITION
G
DETAIL NOTES:
(4) 3/0+#6 GNDIN EACH OF (2)2"C.
DETAIL NOTES:
(4) 300MCM IN EACH OF (3) 3 "C.
(4) 300MCM +1/0G
IN EACHOF(3) 2 1/2"C.
(4)#
8+
#1
0 G
ND
IN
1"
C.
T10-LV2
30 KVA-480V
KV-PRI120/208-SEC
BOILER
90A
-3P
ST-1
70A
-3P
15A
-3P
100
A-3
P
40A
-3P
30A
-3P
30A
-3P
AH-1
30A
-3P
AH-2
15A
-3P
15A
-3P
200
A-3
P
EF-1EF-2
15A
-3P
EF-3
30A
-3P
- DASHED INDICATES EXISTING EQUIPMENT OR WIRING
- SOLID LINE INDICATES NEW EQUIPMENT OR WIRING
#1 #3 #2WH-3
225
A-3
P
WH-4DA-1
HPT-01
SP
AR
E
BOILER PLANTFEED #1SEE 3/E10 FORCONTINUATION
SP
AR
E
SEE1/E12
SWBD-10
KIRK KEYINTERLOCK
800 AMPERES, 480/277V, 3 PH, 4 WIRE, 65,000 AIC
SP
AR
E
BOILER PLANTFEED #2SEE 3/E10 FORCONTINUATION
SP
AR
E
SWITCH
SECTIONALIZING
S56-2
EXISTING
60A
-3P
SP
AR
E
60A
-3P
SP
AR
E
40A
-3P
SP
AR
E
30A
-3P
SP
AR
E
PROVIDE TEMPORARY POWER TO BUILDING 50 PANEL
VIA EXISTING BURIED CONDUIT DURING CONSTRUCTION
OF NEW BUILDING 10 SERVICE. RETAIN EXISTING
TRANSFORMER T-101C1 AND PANEL 101C1 DURING
CONSTRUCTION FOR TEMPORARY CONNECTION OFF OF
EXISTING BUILDING #10 SWITCHGEAR. REMOVE WHEN
NEW SYSTEM IS OPERATIONAL.
DISCONNECT THE EXISTING 25KV FEEDER THAT IS
CURRENTLY CONNECTED TO S56-2, PULL BACK INTO
THE ADJACENT VAULT, AND RECONNECT INTO NEW
SWITCH S10-1.
PROVIDE NEW 25KV FEED INTO S56-2 FROM NEW
SWITCHGEAR S10-1, QUANTITY (3) 4/0 CU 25KV ,
4/0 CU 600V NEUTRAL IN 4" CONDUIT.
QTY (3) 4/0 CU 25 KV, 4/0 CU 600V NEUTRAL IN
EXISTING 4" CONDUIT
480V/277
3-PHASE
T10-1
750 KVA
23.9 KV-PRI
277/480-SEC
(3)#
8+
#10
GN
D
IN 3
/4"
C.
SEE MOTOR AND EQUIPMENT SCHEDULE FOR WIRING AND
CONDUIT REQUIREMENTS.
DETAIL NOTES:
T10-2
750 KVA
23.9 KV-PRI
277/480-SEC
(4) 300MCM IN EACH
OF (3) 3 " C.
(3)#
8+
#10
GN
D
IN 3
/4"
C.
(4)#
3+
#8 G
ND
IN2
" C
.
(4)
3/0
+#
6
GN
D IN
2"C
.
EXISTING 25KV SERVICE
DISCONNECT SWITCHGEAR
WITH METERING
SS-NORTH
1. PROVIDE CONTINUOUS RUNS OF 25 KV WIRING,
SPLICING IN VAULTS IS NOT ALLOWED.
DETAIL GENERAL NOTES:
(4) 300MCM IN EACH
OF (3) 3 " C.
(4) 300MCM IN EACH
OF (3) 3 " C.
EXISTING
PULLBOX
TO 5 KV
SERVICE
T10
BOILER
PLANT
500 KVA
PANEL
101C1
400KW GENERATOR
EXISTING BUILDING #10 TRANSFORMER TO REMAIN
OPERATIONAL DURING CONSTRUCTION TO PROVIDE
POWER TO TEMPORARY BOILERS, PUMPS, BUILDING
#50, AND OTHER TEMPORARY CONSTRUCTION
POWER REQUIREMENTS. REMOVE TRANSFORMER AND
PAD AFTER INSTALLATION AND TESTING OF
PERMANENT SYSTEMS. SEE DETAIL 4/E2.
(4) 300MCM +1/0G
IN EACH OF (3) 2 1/2"C.
TEMPGENSETINLET
TEMPGENSETMANUALSWITCH
SP
AR
E
(4) 300MCM +1/0G
IN EACHOF(3) 2 1/2"C.
PROVIDE EQUAL TO ASCO MTS SERIES MANUAL TRANSFER
SWITCH FOR TEMPORARY GENERATOR CONNECTIONS,
SWITCHED NEUTRAL, NEMA 3R ENCLOSURE,INTEGRAL QUICK
CONNECT CAMLOCK CONNECTIONS. MOUNT ON EXTERIOR
WALL PER FLOORPLANS.
LS
I
LS
I
THE EXISTING GENERATOR AND ATS MAY STAY IN PLACE
TO PROVIDE EMERGENCY POWER TO THE TEMPORARY
BOILER DURING CONSTRUCTION. CONTRACTOR SHALL
PROVIDE A TEMPORARY OUTDOOR GENERATOR WHEN THE
EXISTING GENSET IS REMOVED UNTIL THE NEW BOILER
SYSTEM IS OPERATIONAL.
1
1
1 3 2
BUILDING 10 ELECTRICAL ONE-LINE DIAGRAM- DEMOLITIONNO SCALE
1E1025 KV ONE LINE DIAGRAM - REVISED
NO SCALE
3E10
BUILDING 10 ELECTRICAL ONE-LINE DIAGRAMNO SCALE
2E10
1
1
2
2
2
2
411 1226179 18
3
33
105 13
1
11111 1 1 1 1 1 1 1 1
3
3
2
2
T56-1
M
25E 25E 25E
M
25E
T56-2 T56-3
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:3
1 P
M
E10437-14-112
REPLACE BOILER PLANT 10.26.18ELECTRICAL ONE-LINE
DIAGRAMS
100% CONSTRUCTION DOCUMENT
6515-193 E10.DWG
AS NOTED
EB101N1 MCB 400A NEMA 1 107
208Y/120, 3 PH., 4W.
400 AMP 10,000 SURFACE SWBD
CKT
#
TRIP
AMPSPOLE
LOAD IN VOLT-AMPERES LOAD
DESCRIPTIONPH LOAD DESCRIPTION
LOAD IN VOLT-AMPERES TRIP
AMPSPOLE
CKT
#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING
1 20 1 1000 EXT.REC A LOCKER ROOM 400 20 1 2
3 20 1 600 EXT.REC B 103 1000 20 1 4
5 20 1 800 102 REC C 103 1200 20 1 6
7 20 1 1600 CARD ACCESS A MICROWAVE 1600 *20 1 8
9 20 1 1600 PWR SUPPLY B REF 1200 *20 1 10
11 20 1 1600 IDS SYSTEM C COOKTOP 1600 20 1 12
13 20 1 400 SHOP REC A 103 200 20 1 14
15 20 1 400 SHOP REC B WEST EXT.REC 400 20 1 16
17 20 1 400 SHOP REC C WEST EXT.REC 400 20 1 18
19 20 1 400 SHOP REC A 001 REC 600 20 1 20
21 20 1 400 SHOP REC B 101 REC 800 20 1 22
23 20 1 400 SHOP REC C DAY TANK PUMPS 1600 20 1 24
25 20 1 400 SHOP REC A CATWALK REC 800 20 1 26
27 20 1 800 OFFICE 202 B TUNNEL LIGHTS 1400 20 1 28
29 20 1 1200 IT RACK C SUMP PUMP 1664 15 30
31 20 1 1200 PAGING RACK A 2 32
33 20 1 1000 101 REC B SUMP ALARM 600 20 1 34
35 20 1 1000 MEDGAS C EXT. RECEPT 600 20 1 36
37 20 1 1000 GAS DET. A MASTER CONTROL 1200 20 1 38
39 20 1 400 VISN METERS B TANK MONITORING 1200 20 1 40
41 20 1 400 VISN METERS A SPARE 15 42
43 20 1 1600 FACP B 44
45 20 1 1200 106,107 C 3 46
47 20 1 1200 001 REC A AIR DRYER 20 1 48
49 20 1 400 CHEM.PUMPS B PANEL 101N2 16525 200 50
51 30 SPARE C 19885 52
53 2 A 18505 3 54
55 20 1 SPARE B SPARE 20 50
57 20 1 SPARE C 52
59 20 1 SPARE A 3 54
61 20 1 SPARE B SPARE 20 1 50
63 20 1 SPARE C SPARE 20 1 52
65 20 1 SPARE A SPARE 20 1 54
LOAD TYPEVA / PHASE TOTAL
VA
DEMAND
FACTOR
DIVERSIFIED
LOAD
NOTES:
A B C 1. BREAKERS NOTED WITH * TO BE GFCI
LIGHTING 0 1400 0 1400 1.00 1400
RECEPTACLES 10200 9400 8200 27800 0.50 13900
MOTORS & EQUIP 19125 22085 24369 65579 0.90 59021
KITCHEN EQUIP. 0 0 0 0 0.65 0
HEAT / AC 0 0 0 0 0.90 0
LARGEST MOTOR 0.25 0
TOTAL AMPS: 206 TOTAL VA: 74,321
PANELBOARD LOAD SCHEDULE
PANEL: MAIN: ENCLOSURE: LOCATION:
VOLTS:
RATING: AIC RATING: MOUNTING: FED FROM:
LOAD CALCULATIONS
EB101N2 MLO NEMA 1 107
208Y/120, 3 PH., 4W.
225 AMP 10,000 SURFACE 101N1
CKT
#
TRIP
AMPSPOLE
LOAD IN VOLT-AMPERES LOAD
DESCRIPTIONPH LOAD DESCRIPTION
LOAD IN VOLT-AMPERES TRIP
AMPSPOLE
CKT
#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING
1 20 1 400 EF-4 A SS-1 2080 30 2
3 40 3000 WH-1 B 2080 2 4
5 2 3000 C SS-2 2080 30 6
7 40 3000 WH-2 A 2080 2 8
9 2 3000 B SUMP PUMP 1300 30 10
11 20 1 1500 BATT.CHARGER C 1300 2 12
13 60 4800 JACKET HTR A HTP-01 2105 15 14
15 4800 B 2105 16
17 3 4800 C 2105 3 18
19 15 830 EX.PUMP P-1 A SPARE 40 20
21 830 B 22
23 3 830 C 3 24
25 15 830 EX.PUMP P-2 A SPARE 15 26
27 830 B 28
29 3 830 C 3 30
31 20 1 720 EF-5 A SPARE 15 32
33 20 1 600 DP-01 B 34
35 20 1 1600 EX. AIR DRYER C 3 36
37 20 1 REC -101 A SPARE 15 38
39 20 1 1600 EX. EXHAUST B 40
41 20 1 720 EF-6 A 3 42
43 20 1 SPARE B SPARE 20 44
45 20 1 SPARE C 2 46
47 20 1 SPARE A SPARE 20 48
49 20 1 SPARE B 2 50
51 20 1 SPARE C SPARE *20 1 52
53 20 1 SPARE C SPARE *20 1 54
LOAD TYPEVA / PHASE TOTAL
VA
DEMAND
FACTOR
DIVERSIFIED
LOAD
NOTES:
A B C 1. BREAKERS NOTED WITH * TO BE GFCI
LIGHTING 0 0 0 0 1.00 0
RECEPTACLES 0 0 0 0 0.50 0
MOTORS & EQUIP 16845 20145 18765 55755 0.90 50180
KITCHEN EQUIP. 0 0 0 0 0.65 0
HEAT / AC 0 0 0 0 0.90 0
LARGEST MOTOR 0.25 0
TOTAL AMPS: 139 TOTAL VA: 50,180
PANELBOARD LOAD SCHEDULE
PANEL: MAIN: ENCLOSURE: LOCATION:
VOLTS:
RATING: AIC RATING: MOUNTING: FED FROM:
LOAD CALCULATIONS
EB101N3 MLO NEMA 1 107
480Y/277, 3 PH., 4W.
225 AMP 25,000 SURFACE SWBD-10
CKT
#
TRIP
AMPSPOLE
LOAD IN VOLT-AMPERESLOAD DESCRIPTION PH LOAD DESCRIPTION
LOAD IN VOLT-AMPERES TRIP
AMPSPOLE
CKT
#LIGHTING RECPT MTRS&EQUIP KITCHEN HEAT/AC HEAT/AC KITCHEN MTRS&EQUIP RECPT LIGHTING
1 20 1 1992 MAIN LVL LTG A 101 LTG -HIGH BAY 2988 20 1 2
3 20 1 539 001 LTG B MEZZ LEVEL LTG 1240 20 1 4
5 20 1 294 102 LTG C SPARE 20 1 6
7 20 1 735 LTG -S. INT A EXISTING WTR.PUMP 3047 15 8
9 20 1 392 EXT. LTG B 3047 10
11 20 1 882 101 LTG C 3047 3 12
13 20 1 343 EXT. LTG A SPARE 20 1 14
15 20 1 LTG - OFFICE/LOCK. B SPARE 20 1 16
17 20 1 SPARE C SPARE 20 1 18
19 30 3878 EX.AIR COMP A EXISTING TRAN.PUMP 2100 15 20
21 3878 B 2100 22
23 3 3878 C 2100 3 24
25 15 830 EX.FUEL PUMP P-6 A EXISTING TRAN.PUMP 15 26
27 830 B 28
29 3 830 C 3 30
31 15 EX.FUEL PUMP P-7 A EX.DOMES.WTR PUMP 2100 15 32
33 B 2100 34
35 3 C 2100 3 36
37 15 1216 BOILER COMPRESSOR A EX.DOMES.WTR PUMP 15 38
39 1216 B 40
41 3 1216 C 3 42
43 15 1216 BOILER COMPRESSOR A SPARE 30 44
45 1216 B 46
47 3 1216 C 3 48
49 15 1216 BOILER COMPRESSOR A SPARE 25 50
51 1216 B 52
53 3 1216 C 3 54
LOAD TYPEVA / PHASE TOTAL
VADEMAND FACTORDIVERSIFIED LOAD
NOTES:
A B C 1. BREAKERS NOTED WITH * TO BE GFCI
LIGHTING 6058 2171 1176 9405 1.00 9405
RECEPTACLES 0 0 0 0 0.50 0
MOTORS & EQUIP 15603 15603 15603 46809 0.90 42128
KITCHEN EQUIP. 0 0 0 0 0.65 0
HEAT / AC 0 0 0 0 0.90 0
LARGEST MOTOR 0.25 0
TOTAL AMPS: 62 TOTAL VA: 51,533
PANELBOARD LOAD SCHEDULE
PANEL: MAIN: ENCLOSURE: LOCATION:
VOLTS:
RATING: AIC RATING: MOUNTING: FED FROM:
LOAD CALCULATIONS
MOTOR NO
LOCATION (ROOM NO)
LOAD IN HORSEPOWER (HP) OR FULL
LOAD AMPS (FLA)
VOLTAGE, PHASE
PANEL AND CIRCUIT NUMBER OR MCC
NUMBER
CONDUCTOR SIZE AND QUANTITY
GROUND CONDUCTOR SIZE
CONDUIT SIZE
CONTROLLER DISCONNECT CONTROL OR AUXILIARY DEVICE (SEE
NOTES)
MAGNETIC STARTER/DISCONNECT
STARTER SIZE
VARIABLE FREQUENCY DRIVE
MANUAL MOTOR CONTROLLER
LOW VOLTAGE SWITCH
OCC SENSOR
CONTROLLER BY (DIV. NO.)
CONTROLLER LOCATION (ROOM
NO.OR AS NOTED)
DISCONNECT SIZE
FUSIBLE / NON FUSIBLE
NEMA RATING
DISCONNECT BY (DIV. NO.)
VFD
DEFINITE PURPOSE RELAY
TIME SWITCH
THERMOSTAT
LOW VOLTAGE SWITCH
OCC SENSOR
FIRE ALARM CONTROL RELAY
FIRE ALARM DUCT DETECTORS
(SUPPLY AND RETURN)
INTERLOCK WITH
1 BOILER B-1 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26
2 BOILER B-2 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26
3 BOILER B-3 101 40 HP 480, 3 SWBD-10 3 #4 #8 1-1/4" 23 BAS 100A NF 1 26
4 ST-1 101 3 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 ON UNIT ON UNIT
5 DA-1 101 10 HP 480, 3 SWBD-10 3 #10 #10 3/4" 23 ON UNIT ON UNIT
6 DAY TANK KIT TK-01 107 .5 HP 120, 1 EB101N1-24 2 #12 #12 3/4" 20A NF 1 26
7 WH-1 MEZZ 301 6 KW 208, 1 EB101N2-3,5 2 #8 #10 3/4" 23 BAS 60A NF 1 26
8 WH-2 105 6 KW 208, 1 EB101N2-7,9 2 #8 #10 3/4" 23 BAS 60A NF 1 26
9 WH-3 101 144 KW 480, 3 SWBD-10 3 #3/0 #6 2" 23 BAS ON UNIT
10 WH-4 105 144 KW 480, 3 SWBD-10 3 #3/0 #6 2" 23 BAS ON UNIT
11 AH-1 101 15 MCA 480, 3 SWBD-10 3 #10 #10 3/4" 23 BAS 30A F 30 1 26 3 1
12 AH-2 101 15 MCA 480, 3 SWBD-10 3 #10 #10 3/4" 23 BAS 30A F 30 1 26 3 1
13 HPT-01 101 5 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 BAS 30A NF 1 26
14 SPLIT SYSTEM SS-1 (CONDENSING UNIT) MEZZ 301 20 MCA 208, 1 EB101N2-2,4 2 #10 #10 3/4" ON UNIT
15 SPLIT SYSTEM SS-2 (CONDENSING UNIT) 101-UPPER LVL 20 MCA 208, 1 EB101N2-6,8 2 #10 #10 3/4" ON UNIT
16 M-EF-1 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 30A NF 1 26 3
17 M-EF-2 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 30A NF 1 26 3
18 M-EF-3 101-ROOF 2 HP 480, 3 SWBD-10 3 #12 #12 3/4" 23 102 ON UNIT 3
19 M-EF-4 108- ROOF FRAC 120, 1 EB101N2-1 3 #12 #12 3/4" 23 BAS 20A NF 1 26
20 M-EF-5 102 -ROOF 1/2 HP 120, 1 EB101N2-31 3 #12 #12 3/4" 23 BAS ON UNIT
21 M-EF-6 107 1/4 HP 120, 1 EB10N2-41 2 #12 #12 3/4" 23 BAS 20A NF 1 26
22 BOILER COMPRESSOR BC-1 101 5 HP 480, 3 EB101N3-37,39,41 3 #12 #12 3/4" 23 ON UNIT ON UNIT
23 BOILER COMPRESSOR BC-2 101 5 HP 480, 3 EB101N3-43,45,47 3 #12 #12 3/4" 23 ON UNIT ON UNIT
24 BOILER COMPRESSOR BC-3 101 5 HP 480, 3 EB101N3-49,51,53 3 #12 #12 3/4" 23 ON UNIT ON UNIT
25 EXISTING FEEDWATER PUMP P-1 101 1.5 HP 208, 3 EB101N2-19,21,23 3 #12 #12 3/4" 1 26 101 ON STRT
26 EXISTING FEEDWATER PUMP P-2 101 1.5 HP 208, 3 EB101N2-25,27,29 3 #12 #12 3/4" 1 26 101 ON STRT
27 DIESEL PUMP DP-1 EXTERIOR. 4.9 AMP 120, 1 EB101N2-33 2 #12 #12 3/4" 26 101 20A NF 3R 26
28 EXISTING TRANSFER PUMP P-3 RM 001 3 HP 480, 3 EB101N3-20,22.24 3 #12 #12 3/4" EXISTING
29 EXISTING TRANSFER PUMP P-4 RM 001 3 HP 480, 3 EB101N3-26,28,30 3 #12 #12 3/4" EXISTING
30 EXISTING DOMESTIC WATER PUMP P-8 RM 001 7.5 HP 480, 3 EB101N3-32,34,36 3 #12 #12 3/4" EXISTING
31 EXISTING DOMESTIC WATER PUMP P-9 RM 001 7.5 HP 480, 3 EB101N3-38,40,42 3 #12 #12 3/4" EXISTING
32 EXISTING FUEL PUMP P-6 101 1.5 HP 480, 3 EB101N3-25,27,29 3 #12 #12 3/4" 1 26 101 ON STRT
33 EXISTING FUEL PUMP P-7 101 1.5 HP 480, 3 EB101N3-31,33,35 3 #12 #12 3/4" 1 26 101 ON STRT
34 SUMP PUMP SP-1 001-PIT 2 HP 208, 1 EB101N2-10,12 2 #10 #10 3/4" 23 ON UNIT 30A F 30 1 26
1. ELECTRICAL CONTRACTOR TO FURNISH, SET, AND WIRE AUXILIARY CONTROL DEVICE
2. ELECTRICAL CONTRACTOR TO SET, AND WIRE AUXILIARY CONTROL DEVICE FURNISHED BY OTHERS
3. ELECTRICAL CONTRACTOR TO WIRE AUXILIARY CONTROL DEVICE FURNISHED AND SET BY OTHERS
4. PROVIDE DUCT DETECTOR IN SUPPLY AND RETURN DUCTS AND CONNECT TO FA SYSTEM
MOTOR AND EQUIPMENT SCHEDULE
X
X
X
X
X
X
X
X
X
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:3
2 P
M
E11437-14-112
REPLACE BOILER PLANT 10.26.18ELECTRICAL SCHEDULES
100% CONSTRUCTION DOCUMENT
6615-193 E11.DWG
AS NOTED
SPD
NOTE:
#6
48"
91.5"
36" 42" 36"42" 42"
1
2
1
2
2
1
DATA PHONE
DATA DATA
DATA-CLOSET#-ROOM#-PLATE#
NOTES:
PHONE-CLOSET#-PLATE#
1 2
3 4
3/4" CONDUIT
48"
CARDREADER
48"
NOTES:
TYPICAL SINGLEDOOR
TYPICAL DOUBLEDOOR
3/4" CONDUIT
SEE NOTE#3
LAN
200W/CH-70V
DATAPORT
200W/CH-70V
DATAPORT
SPEAKER
SPEAKER
DATAPORT
SPEAKER #18/2
GPIODOOR INTERCOM CONTACT
SPEAKER
SEE NOTE #2
SEE NOTE#1
1. ALL EQUIPMENT SHOWN AS DASHED IS EXISTING.
1.
2.
3.
4.
"DATA CLOSET#-ROOM#-PLATE#-JACK#"
4-POLE
TRANSFER
SWITCH
480V/277, 3 PH, 4 WIRE
LOAD
EGC
N G
SERVICE
EQUIPMENT
BONDING
JUMPER
CONDUCTOR
ELECTRODE NEARBY,
PREFERABLY THE
STRUCTURAL STEEL
N
GROUNDING
GROUNDING ELECTRODE
SEPARATELY
DERIVED SYSTEMGEN.
NOTE:
KP
MS
A
NOTES:
120V
PROVIDE OTHER GROUND CONNECTIONS AS
SPECIFIED IN N.E.C. ARTICLE 250-64
TO MOUNTING
STEEL
NEUTRAL BUS IN
DISCONNECT
GROUND BUS
TO DISCONNECT
FRAME GROUNDING ROD
(LOCATED NEAR
DISCONNECT
MOUNTING BASE)
PROVIDE A GROUNDING CONDUCTOR
IN ALL BRANCH CIRCUIT AND
FEEDER CONDUITS, SEE
SPECIFICATION SECTION 26 05 26
GANG
OPERATED
SWITCH
GANG
OPERATED
SWITCH
BUSSING
(TYPICAL)
FUSIBLE
SWITCH
FUSIBLE
SWITCH
GANG
OPERATED
SWITCH
COMPARTMENT
GANG
OPERATED
SWITCH
COMPARTMENT
FUSIBLE
INDIVIDUALLY
OPERATED
SWITCH
COMPARTMENT
FUSIBLE
INDIVIDUALLY
OPERATED
SWITCH
COMPARTMENT
GANG
OPERATED
SWITCH
OPERATING
HANDLE
BEHIND
PADLOCKED
COVER
GANG
OPERATED
SWITCH
OPERATING
HANDLE
BEHIND
PADLOCKED
COVERDOOR
HANDLE
W/PADLOCK
DATA JACK#
ROOM#-PLATE#
D2
101-1
2. SEE SECTION 27 10 05 FOR PLATE AND JACK REQUIREMENTS.
5. LABEL ALL VOICE AND DATA CABLES AT BOTH ENDS WITH
7. DATA JACKS ARE NUMBERED LEFT TO RIGHT, TOP TO BOTTOM.
6. ALL (4) JACKS TO BE CATEGORY 6e CABLES.
4. PLATES ARE LABELED AS SHOWN, NUMBER PLATES ARE CLOCKWISE FROM THE DOOR.
3. DATA JACKS TO BE ORANGE COLOR, PHONE JACKS TO BE IVORY.
1. = (3) DATA, (1) PHONE JACK.
GENERAL NOTES
DETAIL NOTES:
1. CONFIGURE DOOR INTERCOM TO TRIGGER DRY CONTACT
INPUTS ON EXISTING QSC Q-SYS DSP GPIO INPUT. PROGRAM
TO INITIATE DOOR CHIME OVER PA SPEAKERS IN BOILER
PLANT ZONE
2. BOILER PLANT SPEAKERS CURRENTLY CONNECTED TO ZONE
#13, DISCONNECT SPEAKER LINES AND RECONNECT TO SPARE
OUTPUT ON EXISTING QSC DAB-801 SPEAKER MODULE.
REPROGRAM BOILER PLANT AS A SEPARATE PUBLIC ADDRESS
ZONE
SOUND EQUIPMENT
CABINET 10
BOILER PLANT
MEZZANINE
DATAPORT
EXISTING REDUNDANT
AMPLIFIER
EXISTING AUDIO
NETWORK SIGNAL
EXISTING QSC CORE 110F
SERIES DSP/ IO FRAME EXISTING
AMPLIFIERQSC DAB-801
ZONE #13 BLDG 11/12/13
ZONE #14 BLDG 51
ZONE #15 BLDG 10 (BOILER PLANT)
CONFIGURE CARD ACCESS SYSTEM TO DISABLE AUDIBLE
ALARM SIGNAL UPON VALID CARD SWIPE OR FROM IDS
KEYPAD NUMERIC CODE ENTRY.
CONFIGURE CARD ACCESS SYSTEM TO ACTIVATE IDS
SYSTEM AUDIBLE ALARMS UPON DOOR PROP SIGNAL,
PROVIDE 30 SECOND TIMER FUNCTION.
EACH DEVICE SHALL BE GIVEN AN INDEPENDENT ADDRESS
ON THE IDS SYSTEM, AND ASSIGNED TO PARTITION NOTED.
IDS
POWER
SUPPLY
IDS
CONTROL
PANEL
ELECTRIC LATCH
RETRACTION OR
VERTICAL ROD DEVICE
BY DIVISION 08
ELECTRIC HINGE
OR POWER TRANSFER
BY DIVISION 08
BALANCED
DOOR
POSITION
SWITCH
BALANCED
DOOR
POSITION
SWITCH
REQUEST TO
EXIT SENSOR
3/4"
CONDUIT
3/4"
CONDUIT
TO ACCESS CONTROL
SYSTEM PANELS IN
ELECTRICAL ROOM 102
3/4" CONDUIT
TYPICAL
JUNCTION BOX
ELECTRIC STRIKE
BY DIVISION 08
CARD
READER
ELECTRIC HINGE
OR POWER TRANSFER
BY DIVISION 08
DOOR
POSITION
SWITCH
REQUEST TO
EXIT SENSOR
3/4"
CONDUIT
TO ACCESS CONTROL SYSTEM
PANELS IN ELECTRICAL ROOM 102
3/4" CONDUIT
PROVIDE MINIMUM 4" CONCRETE HOUSEKEEPING PAD
REINFORCE WITH #3 BARS AT 12 INCHES ON CENTER
PROVIDE WITH 3/4" CHAMFER EDGE
03
04
02
01
I1
I202
01
I2
I1
I3
I4
01
02
03
04
I2
I1
01
02
03
SEE NOTE #1
SEE NOTE #2 DOOR PROP SIGNAL
I/0 MODULE
THIS DETAIL IS A TYPICAL INSTALLATION, COORDINATE EXACT WIRING AND DOOR
HARDWARE REQUIREMENTS WITH DIVISION 08 AND ACCESS CONTROL SYSTEM SUPPLIER.
DOOR HARDWARE POWER SUPPLIES SHALL BE CENTRALLY LOCATED IN THE MAIN
ELECTRICAL ROOM, SEE POWER DRAWINGS FOR CIRCUIT REQUIREMENTS.
SURFACE MOUNTED CONDUIT IS ALLOWED WITHIN BOILER PLANT, ROUTE CONDUIT DOWN
SECURED SIDE OF DOOR AND STUB CONDUIT THROUGH TO EXTERIOR CARD READER.
DISARM SIGNAL
MS
MS
MS
KP
ALL WIRING IN EMT CONDUIT, 3/4" MINIMUM.
KP
KEYED
BYPASS
SWITCH
KP
4.
SEE NOTE #5 SEE NOTE #5
SEE NOTE #5
IDS MASTER KEYPADOFFICE 103
SEE DWG
IDS MOTION SENSORS
PARTITION #1
BOILER PLANT
PARTITION #2
GENERATOR ROOM 107
PARTITION #3
ELECTRICAL ROOM 102
PARTITION #4
STEAM TUNNEL ENTRY
IDS AUDIBLE ALARM
SEE DWG FOR LOCATION
SEE NOTE#6
SEE NOTE #3
1.
2.
3.
4.
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPEAKER
SPD
TRANSFER SWITCH TRANSFER SWITCH
- KEY INTERLOCK
K
AP
PR
OX
IMA
TE
LY
45
IN
CH
ES
APPROXIMATELY 60 INCHES
OPERATOR
K
K
K
OPERATOR
K
K
K
3
SYSTEM GROUNDING DETAILNO SCALE
1E12
DISCONNECT GROUNDING DETAILSNO SCALE
2E12
SWITCHBOARD SWBD-10 ELEVATIONNO SCALE
3E12
S10-1 CIRCUIT DIAGRAMNO SCALE
4E12
S10-1 ENCLOSURE TOP VIEWNO SCALE
5E12
S10-1 SIDE VIEWNO SCALE
6E12
PATCH PANEL SAMPLE LABELSNO SCALE
7E12
TYPICAL COMMUNICATIONS PLATE DETAILNO SCALE
8E12
TYPICAL CARD ACCESS WIRING DETAILNO SCALE
9E12
PAGING AND DOORBELL SYSTEM ONE-LINE DIAGRAMNO SCALE
11E12
TYPICAL INTRUSION DETECTION SYSTEM WIRING DETAILNO SCALE
10E12
AUDIBLE ALARM SHALL SOUND IF DOOR HAS BEEN PROPPED
FOR MORE THAN 30 SECONDS UNLESS BYPASSED WITH
KEYED SWITCH ADJACENT TO DOOR.
AUDIBLE ALARM SHALL SOUND IF DOOR HAS BEEN PROPPED
FOR MORE THAN 30 SECONDS UNLESS BYPASSED WITH
KEYED SWITCH ADJACENT TO DOOR.
5. BALANCED MAGNETIC SWITCH FURNISHED
UNDER SECTION 28 16 00.
6. KEYED SWITCH PROVIDED IN SECTION 28 13 16.
PROVIDE WITH RED/GREEN LIGHTS TO INDICATED
DOOR BYPASS STATUS, MATCH VA KEY TYPE.
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:3
2 P
M
E12437-14-112
REPLACE BOILER PLANT 10.26.18ELECTRICAL DETAILS
100% CONSTRUCTION DOCUMENT
6715-193 E12.DWG
AS NOTED
(10
") M
IN(1
0")
MIN
CONDUIT ROOF PENETRATION DETAILNO SCALE
1E13
ROOF
EMERGENCY GENERATOR EXHAUSTNO SCALE
2E13
4"
4"
PROVIDE EXOTHERMICWELDING FOR ALLCONNECTIONS (TYPICAL)GROUND
ROD(TYPICAL)
2"
TRANSFORMER PAD AND GROUNDING DETAILNO SCALE
3E13
EMERGENCY GENERATOR WITH INTEGRAL RADIATORNO SCALE
4E13
VIBRATION ISOLATORSTO STRUCTURE ( TYP)
CONDUIT, TYP.
BATT INSULATION
PREFABRICATED FORMED 0.06"
THICK ALUMINUM FLASHING ROUND COLLAR
WITH MIN. 3" WIDE FLANGE. ATTACH TO ROOF
PER MANUFACTURER'S INSTRUCTIONS
MULTIPLE MEMBRANE STRIPPING PLIES FEATHERED
AT FIELD OF ROOF BY ROOFING CONTRACTOR.
PRIME FLANGE BEFORE STRIPPING.
SEAL-OFF FITTING, TYP.
STAINLESS CLAMP, TYP.
PREFABRICATED RUBBER BOOT CAP
WITH GRADUATED STEPS &
WEATHER-PROOF PRESSURE SEAL
TO COLLAR
SEALANT AT PENETRATION
TO MEMBRANE JUNCTURE
BY ROOFING CONTRACTOR
ROOF MEMBRANE
METAL ROOF
WATER CUT-OFF MASTIC
COMPATIBLE WITH ROOF
MEMBRANE
CONDUIT CLAMP,
SIZE AS REQUIRED
INTEGRAL GALVANIZED
LIPPED STEEL MOUNTING
CHANNEL, ATTACH TO
STRUCTURE BELOW
DECK
GENERAL NOTES:
1. MAINTAIN A MINIMUM CLEARANCE OF 12 INCHES ON ALL SIDES OF ROOF PENETRATION FROM WALLS,
CURBS, AND OTHER PROJECTIONS TO FACILITATE PROPER FLASHING.
2. FLANGES OF ADJACENT FLASHINGS SHALL NOT BE CUT OR OVERLAPPED.
3. VERIFY ROOF & STRUCTURAL SYSTEM WITH ARCHITECT.
4. COORDINATE FLASHING INSTALLATION WITH ROOFING CONTRACTOR TO ENSURE PROPER METHODS
& MATERIALS ARE USED TO MAINTAIN ROOF WARRANTY.
ENGINE EXHAUST PIPE SIZE
AS RECOMMENDED BY
MANUFACTURER
MUFFLER, SIZE AS
RECOMMENDED BY
MANUFACTURER,
PROVIDE VIBRATION ISOLATORS
12" LONG DRIP LEG WITH DRAIN VALVE
EXHAUST PIPE, SIZE AS RECOMMENDED BY
MANUFACTURER.
THIMBLE OUTER SLEEVE
CLEARANCE AS REQUIRED BY THIMBLE
MANUFACTURER
FLASHING & ROOF OPENING BY GENERAL
CONTRACTOR
THIMBLE INNER SLEEVE
RAIN SHIELD
RAIN CAP
CONDUIT OPENING,
VERIFY SIZE AND
LOCATION WITH
TRANSFORMER
MANUFACTURER
PRIMARY SERVICE
CONDUITS
TO TRANSFORMER
NEUTRAL, #4/0.
SECONDARY
SERVICE CONDUITS
#4 REBAR WITH TIES
12 INCHES ON CENTER
EACH WAY
TRANSFORMER PAD,
VERIFY SIZE WITH
MANUFACTURER. PAD
SHALL EXTEND A MINIMUM
OF 8 INCHES BEYOND
TRANSFORMER
CONCRETE, SEE
SECTION 03 30 00.
FINISHED
GRADE
COMPACTED
GRAVEL BASE
SECONDARY
CONDUIT
PRIMARY
CONDUIT
GROUND
ROD
GROUND
ROD
HOT AIR
EXHAUST PIPING, ROOF THIMBLE AND
INSTALLATION PROVIDED BY DIVISION 26
INSTALL MUFFLER AND
FLEXIBLE CONNECTION.
INSULATE MUFFLER
INTEGRAL
RADIATOR
THERMOSTATIC AIR
RECIRCULATING
DAMPER PROVIDED BY
DIVISION 23
FLEXIBLE DUCT CONNECTOR
AND DUCTWORK PROVIDED BY
DIVISION 23
PROVIDE
VIBRATION
ISOLATORSPROVIDE FLEXIBLE FUEL
LINES FOR INSTALLATION
BY DIVISION 23
BLOCK
HEATER
EXTEND EXISTING
CONCRETE PAD
NOTE:
1.
CONDUIT
FLOOR
FIRESTOP MATERIAL
FLOOR OR DECK PENETRATION
PARTITION OR CHASE PENETRATION
[150mm] [150mm]
MASONRYPARTITION
PARTITION SUPPORT
FIRESTOP MATERIAL
[150mm] [150mm]
DRYWALL PARTITION
6" 6"
6" 6"
FLOOR PENETRATION
CONDUIT
[15
0m
m]
[15
0m
m]
6"
6"
CONDUIT PENETRATION OF SMOKE/FIRE BARRIERSNO SCALE
5E13
3/4" APPROVED
FIRESTOP INSULATION
WITH VAPOR BARRIER
APPLICABLE TO PENETRATIONS OF ALL FIRE
RATED MEMBRANES, IN ACCORDANCE WITH
NFPA 101. REFER TO SPECIFICATIONS SECTION
07 84 00, FIRE STOPPING SYSTEMS.
3/4" [19mm] APPROVED
FIRESTOP INSULATION WITH
VAPOR BARRIER
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:3
3 P
M
E13437-14-112
REPLACE BOILER PLANT 10.26.18ELECTRICAL DETAILS
100% CONSTRUCTION DOCUMENT
6815-193 E13.DWG
AS NOTED
GENERAL NOTES:
NO. 29 X 29 X 17 GAUGECOPPER CONDUCTOR
NO. 231 GROUND ROD CLAMPFOR 5/8 INCH ROD
NO. TL5810 5/8 INCH X 10 FOOTCOPPER CLAD GROUND ROD
NO. 55 1/2 INCH x 12 INCHSOLID COPPER POINT
NO. 29 X 29 X 17 GAUGECOPPER CONDUCTOR
NO. 685 CONCEALED BASE ASSEMBLY
NO. 166 LOOP CABLE HOLDERAT 3'-0" ON CENTER
LIGHTING PROTECTION GROUNDING DETAILNO SCALE
4E14
LIGHTING PROTECTION CONNECTION DETAILNO SCALE
5E14
8" RADIUS
NPL CAT. #10A ALUMINUMLIGHTNING PROTECTIONCONDUCTOR
NLP CAT. #1007AEALUMINUMPARALLEL CABLESPLICER
NPL CAT. #1308A ADHESIVE ALUMINUMCABLE HOLDER (FASTEN CABLE EVERY 36"WITH PROPER COMPATIBLE ADHESIVE,SEE GENERAL NOTE 21)
NLP CAT. #202A 1/2"X12" SOLIDALUMINUM AIR TERMINAL
NLP CAT. #804AE ALUMINUM FLATMOUNT AIR TERMINAL BASE (FASTENWITH NLP CAT. #TEKSS3 3/4" LONGSTAINLESS STEEL SELF TAPPING SCREWS)
NLP CAT. #1308A ADHESIVEALUMINUM CABLE HOLDER (FASTENCABLE EVERY 36" WITH PROPERCOMPATIBLE ADHESIVE, SEE GENERAL NOTE 21)
NLP CAT. #1007AEALUMINUM PARALLEL CABLESPLICER
NLP CAT. #10A ALUMINUMLIGHTNING PROTECTIONCONDUCTOR
NLP CAT. #1019AE ALUMINUM 3SQUARE INCH BONDING PLATE(FASTEN WITH NLP CAT. #TEKSS33/4" LONG STAINLESS STEEL SELFTAPPING SCREWS)
NLP CAT. #202A 1/2"X12" SOLIDALUMINUM AIR TERMINAL
NLP CAT. #801AE ALUMINUM SIDE MOUNT AIRTERMINAL BASE (FASTEN WITH NLP CAT.#TEKSS3 3/4" LONG STAINLESS STEEL SELFTAPPING SCREWS
NLP CAT. #10A ALUMINUM LIGHTNINGPROTECTION CONDUCTOR
NLP CAT. #1302A ALUMINUM CABLE LOOP(FASTEN CABLE EVERY 36 INCHES USINGNLP CAT. #TEKSS3 3/4" LONG STAINLESSSTEEL SELF TAPPING SCREWS)
EQUIPMENT AIR TERMINAL DETAILNO SCALE
2E14
PARAPET AIR TERMINAL DETAILNO SCALE
6E14
CABLE SPLICE DETAILNO SCALE
8E14DOWNLEAD TO GROUND DETAIL
NO SCALE
7E14
TYPICAL BONDING DETAILNO SCALE
3E14
NLP CAT. #27 COPPER LIGHTNINGPROTECTION CONDUCTOR TO GROUND ROD
1" SCH 40 PVC CONDUIT(SEE GENERAL NOTE 19)
SEE GENERAL NOTE 20
NLP CAT. #1150BE BIMETALLIC CABLECONNECTOR CAP FOR 1" SCH 40 PVC CONDUIT
NLP CAT. #10A ALUMINUM LIGHTNINGPROTECTION CONDUCTOR
10" MIN.
90°2'-0"
MAX.
24"
1. THE FINAL INSTALLATION SHALL MEET THE UL96A
REQUIREMENTS FOR LIGHTNING PROTECTION
SYSTEMS.
2. IT IS THE INSTALLING CONTRACTOR'S
RESPONSIBILITY TO PROVIDE A FULLY COMPLIANT
SYSTEM.
3. FIELD VERIFY PROTECTION REQUIREMENTS AND
COMMUNICATE ANY DISCREPANCIES AND/OR
DEFICIENCIES WITH THE SYSTEM DESIGNER PRIOR
TO INSTALLATION.
4. ACTUAL JOB SITE CONDITIONS MAY NECESSITATE
SLIGHT ALTERNATIONS OF AIR TERMINAL AND
GROUND LOCATIONS. ANY ALTERATIONS SHALL BE
APPROVED BY THE SYSTEM DESIGNER PRIOR TO
THEIR EXECUTION AND SHALL BE AT NO
ADDITIONAL COST TO THE GOVERNMENT.
5. AIR TERMINALS SHALL BE PLACED AROUND THE
ROOF PERIMETER OR RIDGE AT 20'-0" MAXIMUM
INTERVALS FOR 10" TO 23" AIR TERMINALS AND
AT 25'-0" MAXIMUM INTERVALS FOR 24" AIR
TERMINALS.
6. AIR TERMINALS SHALL BE PLACED WITHIN 24"
FROM THE OUTSIDE EDGES OF THE OBJECT TO BE
PROTECTED.
7. MID-ROOF AIR TERMINALS ON FLAT OR GENTLY
SLOPING ROOFS SHALL BE INSTALLED AT MAXIMUM
50'-0" INTERVALS.
8. ALL ROOF PROJECTIONS AND/OR OBJECTS THAT
ARE SUBJECT TO A DIRECT LIGHTNING STRIKE
SHALL BE PROVIDED WITH AIR TERMINALS UNLESS
THEY ARE LOCATED WITHIN A ZONE OF
PROTECTION.
9. FIELD VERIFY ALL ZONES OF PROTECTION.
10. METAL BODIES SITUATED WITHIN 6'-0" OF A
LIGHTNING PROTECTION CONDUCTOR SHALL BE
BONDED TO THE LIGHTNING PROTECTION SYSTEM.
11. NO BEND OF CONDUCTOR SHALL FORM A FINAL
INCLUDED ANGLE OF LESS THAN 90 DEGREES NOR
SHALL HAVE A RADIUS OF BEND LESS THAN 8".
CONDUIT SHALL ROUTE THE LIGHTNING
PROTECTION CONDUCTOR IN A MANNER CONSISTENT
WITH THESE BEND REQUIREMENTS.
12. CONDUCTORS SHALL INTERCONNECT ALL AIR
TERMINALS TO FORM A TWO WAY HORIZONTAL OR
DOWNWARD PATH TO THE GROUND SYSTEM.
13. ALL LIGHTNING PROTECTION CONDUCTORS SHALL
BE FASTENED AT MAXIMUM INTERVALS OF 3'-0"
ON CENTER.
14. CONNECTIONS TO GROUND RODS OR GROUND LOOP
CABLE SHALL BE MADE AT A POINT NOT LESS
THAN 12" BELOW GRADE AND 24" AWAY FROM
FOUNDATION WALL.
15. ALL POTENTIAL GROUND SOURCES THAT ENTER A
STRUCTURE FROM BELOW GRADE (EARTH) MUST BE
INTERCONNECTED TO THE LIGHTNING PROTECTION
SYSTEM.
16. ALL ADHESIVE TYPE FITTINGS SHALL BE SET IN
PLACE WITH COMPATIBLE ROOF CEMENT.
17. BARE COPPER LIGHTNING PROTECTION MATERIAL
SHALL NOT BE INSTALLED ON ALUMINUM AND
ALUMINUM LIGHTNING PROTECTION MATERIALS
SHALL NOT BE INSTALLED ON COPPER.
18. ALL INCOMING ELECTRICAL, TELEPHONE, DATA,
RADIO, AND TELEVISION SERVICES SHALL BE
EQUIPPED WITH SURGE SUPPRESSION DEVICE.
UNLESS SPECIFIED OTHERWISE THE REQUIRED
SURGE SUPPRESSION DEVICES SHALL BE
FURNISHED AND INSTALLED BY THE ELECTRICAL
CONTRACTOR.
19. ALL REQUIRED 1" SCHEDULE 40 PVC CONDUIT
SHALL FURNISHED AND INSTALLED BY THE
ELECTRICAL CONTRACTOR AT LOCATIONS
DESIGNATED BY THE DESIGNER. CONDUIT SHALL
MAINTAIN A CONTINUOUS AND DIRECT ROUTE TO
GROUND WITH NO MORE THAN 360 DEGREES OF
CUMULATIVE BEND IN ANY SINGLE RUN.
20. ALL REQUIRED SEALING AND/OR FLASHING OR
ROOF PENETRATION SHALL BE FURNISHED AND
INSTALLED BY THE CONTRACTOR.
21. ANY ROOF PADS, PAVERS, SLIP SHEETS, BATTEN
STRIPS, OR SPECIAL REQUIREMENTS OF THE ROOF
SYSTEMS MANUFACTURER FOR ROOF MOUNTED
LIGHTNING PROTECTION EQUIPMENT SHALL BE
FURNISHED AND INSTALLED BY THE CONTRACTOR.
22. THE LAYOUT SHOWN ON THIS DRAWING IS
DIAGRAMMATIC, CONTRACTOR TO FIELD
COORDINATE ALL ROOF PENETRATIONS AND EXACT
MOUNTING LOCATIONS OF ALL AIR TERMINALS.
23. CONTRACTOR TO PROVIDE SHOP DRAWINGS ON THIS
SYSTEM SHOWING MOUNTING DETAILS, AIR
TERMINAL LAYOUTS, ETC.
VENT
EXHAUST FAN
EXHAUST FANEXHAUST FAN
BOILER STACK BOILER STACK BOILER STACK
ROOF HATCH
EXHAUST FAN
ACCU UNIT
TYPICAL PARAPET MOUNTED AIR TERMINAL
CONCEAL DOWN
PROVIDE AIR TERMINAL AND BOND TO EACH
GENSETEXHAUST
EACH METALLIC ROOF PENETRATION
INTAKE HOOD
EXHAUST FAN
TYPICAL PARAPET MOUNTED AIR TERMINALMUFFLER VENT
RELIEF VENT
RELIEF VENT
VENT
INTAKE LOUVER
INTAKE LOUVER
GROUND ROD
STEAM VENT
PLUMBING VENT
BOILER VENTS BOILER VENTS BOILER VENTS
VENT
SCUPPERSCUPPER
SCUPPERSCUPPER
SCUPPER
SCUPPER
GAS VENTS
PLUMBING VENT
INTERIOR WALLSEE 7/E14
CONCEAL DOWNINTERIOR WALLSEE 7/E14
GROUND ROD
KEY PLAN
Fargo, ND 58102
2101 Elm Street
Medical Center
Dept. of Veterans Affairs
Building No.
VA Project No.
Drawing Title
Contract No.
Vete
rans A
ffairs
Location
Drawn ByChecked ByDesigned By
Project Title
Drawing No.
Date
Scale:
Depart
ment of
Dwg. of 6910 - BOILER PLANTFARGO VA HEALTH CARE SYSTEM
FARGO, NORTH DAKOTA
VA263-P-1218CH MB CHVA263
Project Phase
www.jlgarchitects.com
copyright © 2017
Fargo214 Broadway
Fargo, ND 58102
phone 7 0 1.3 6 4.0 2 3 7
facsimile 7 0 1.3 6 4.0 2 2 8
Elec. dwg name:
Submittal Date
S.D. 1 SUBMITTAL 12/30/2015
D.D. 1 SUBMITTAL (PRELIM.) 02/16/2016
D.D. 1 (35%) SUBMITTAL 09/30/2016
D.D. 2 (50%) SUBMITTAL 03/03/2017
D.D. 3 (99%) SUBMITTAL 10/20/2017
C.D. 4 (100%) SUBMITTAL 06/01/2018
10/2
9/2
018 1
:38:3
3 P
M
E14437-14-112
REPLACE BOILER PLANT 10.26.18LIGHTNING DETAIL SHEET
100% CONSTRUCTION DOCUMENT
6915-193 E14.DWG
N 1/8" = 1'-0"1LIGHTING PROTECTION PLAN
AS NOTED