Electrical-Engineering-portal.com-Learn How to Specify Current Transformers_2

Embed Size (px)

Citation preview

  • 8/16/2019 Electrical-Engineering-portal.com-Learn How to Specify Current Transformers_2

    1/6

    electrical-engineering-portal.com

    http://electrical-engineering-portal.com/learn-how-to-specify-current-transformers?

    utm_source=EEP+Monthly+Download+Updates&utm_campaign=77e9126042-

    Complete_Power_Engineering_Guide12 _5_2015&utm_medium=email&utm_term=0_91c70c6fa4-77e9126042-

    320879933&mc_cid=77e9126042&mc_eid=5681cd642a

    Google+

    Learn How To Specify Current Transformers

    Learn How To Specify Current Transformers (photo credit: naswgr.net)

    Instrument and protection CTs

    Curr ent transformers are used to supply information to the protective relays and/or current, power and energy meterin

    “instruments”. For this purpose they must supply a secondary current proportional to the primary current flowing

    through them and must be adapted to network characteristics: voltage, frequency and current.

    They are defined by their ratio, power and accuracy class. Their class (accuracy as a function of CT 

    load and of overcurrent) is chosen according to the application.

    A “protection” current transformer (CT)  must saturate sufficiently high to allow a relatively accurate measurement

    the fault current by the protection whose operating threshold can be very high. Current transformers are thus expecte

    to have an Accuracy Limit Factor (ALF) that is usually fairly high. Note that the associated “relay” must be able to

    withstand high overcurrents.

    http://electrical-engineering-portal.com/download-center/books-and-guides/schneider-electric/current-transformers-how-to-specifyhttp://electrical-engineering-portal.com/learn-how-to-specify-current-transformers?utm_source=EEP+Monthly+Download+Updates&utm_campaign=77e9126042-Complete_Power_Engineering_Guide12_5_2015&utm_medium=email&utm_term=0_91c70c6fa4-77e9126042-320879933&mc_cid=77e9126042&mc_eid=5681cd642ahttp://electrical-engineering-portal.com/http://electrical-engineering-portal.com/download-center/books-and-guides/schneider-electric/current-transformers-how-to-specifyhttp://electrical-engineering-portal.com/learn-how-to-specify-current-transformers?utm_source=EEP+Monthly+Download+Updates&utm_campaign=77e9126042-Complete_Power_Engineering_Guide12_5_2015&utm_medium=email&utm_term=0_91c70c6fa4-77e9126042-320879933&mc_cid=77e9126042&mc_eid=5681cd642ahttp://electrical-engineering-portal.com/

  • 8/16/2019 Electrical-Engineering-portal.com-Learn How to Specify Current Transformers_2

    2/6

     An example of a protection CT

    An “instrument”current transformer (CT) requires good accuracy around the nominal current value. The metering

    instruments do not need to withstand currents as high as the protection relays. This is why the “instrument” CTs, unlik

    the “protection” CTs, have the lowest possible Safety Factor (SF) in order to protect these instruments through earlier

    saturation.

    Some current transformers have secondary windings dedicated to protection and metering. These “instrument” and

    “protection” CTs are governed by standard IEC 60044-1 (in France NF C 42-502).

    The matching of CTs with protection relays calls for a thorough knowledge of current transformers. The following

    section gives a few reminders of CTs corresponding to this use.

    Characterisation of CTs

    An example of a protection CT //

    Rated primary current: 200 A,

    Rated secondary current: 5 A.

    Its accuracy load: Pn = 15 VA

    Its accuracy limit factor is ALF = 10

    For I = ALF. In, its accuracy is 5% (5P), (see figure 1)

    To simplify, for the protection CT given in example, the ratio

    error is less than 5% at 10 In , if the real load consumes 15

    VA at In. However these data are not sufficient. Also, it is

    useful to know the standard values.

  • 8/16/2019 Electrical-Engineering-portal.com-Learn How to Specify Current Transformers_2

    3/6

    Figure 1 – Example of the nameplate of a current transformer with two secondaries

    12 definitions related to current transformers //

    Rated (nominal) primary current I1

    Rated (nominal) secondary current I2

    Ratio (I1 / I2)

     Accuracy load

    Rated (nominal) accuracy power Pn

    Real power Pr 

     Accuracy class

    Special accuracy class

    Real accuracy factor (Fp or Kr)

     Accuracy limit factor (ALF or Kn)

    Short time withstand current

    CT rated voltage

    ≡ Rated (nominal) primary current I1

  • 8/16/2019 Electrical-Engineering-portal.com-Learn How to Specify Current Transformers_2

    4/6

    Defined by standards, it is chosen from the discrete values: 10 – 12.5 – 15 – 20 – 25 – 30 – 40 – 50 – 60 – 75 A and

    their decimal multiples.

    ≡ Rated (nominal) secondary current I2

    Equals 1A or 5 A.

    ≡ Ratio (I1 / I

    2)

    The primary and secondary currents are standard, thus these values are discrete. (Learn more about ratios of 

    magnetic HV instrument current transformers – Here)

    ≡ Accuracy load

    Load value on which the accuracy conditions are based.

    ≡ Rated (nominal) accuracy power Pn

    Expressed in VA, it is the apparent power supplied to the secondary circuit for the nominal (rated) secondary current

    and the accuracy load. The standard values are: 1 – 2.5 – 5 – 10 – 15 – 30 VA .

    ≡ Real power Pr 

    In this technical article, it is the power corresponding to the real load consumption of the CT at In.

    ≡ Accuracy class

    This class defines the error limits guaranteed on the ratio and on the phase shift in specified power and current

    conditions. For the nominal 5P and 10P classes, the table in figure 6 defines these limits.

    Figure 2 // Errors on the module and the phase at nominal current

    (according to standard IEC 60044-1)

     Accuracyclass

    Current error for the nominalcurrent as a %

    Phase shift for the nominalcurrent

    Composite errors for the accuracy limitcurrent as a %

    Minutes Centiradians

    5P ± 1 ± 60 ± 1.8 5

    10P ± 3 – – 10

    ≡ Special accuracy class

    Class X is a class defined by British standard BS 3938. It must also be defined in the future standard IEC 60044-1

    under the name of class PX. This class specifies the minimum value of the knee point voltage Vk of the CT.

    It also imposes a maximum value of Rct (CT secondary winding resistance). Sometimes, it 

    http://electrical-engineering-portal.com/understanding-the-ratios-of-magnetic-hv-instrument-current-transformers

  • 8/16/2019 Electrical-Engineering-portal.com-Learn How to Specify Current Transformers_2

    5/6

    Figure 3 – Voltages corresponding to different CT classes

    specifies the maximum value of the magnetising current Io at knee point voltage.

    If we consider the magnetising curve V(Io) of the CT, the knee point voltage Vk is defined as the point on this curv

    from which a 10% increase in voltage causes a 50% increase in the magnetising current Io. Class X corresponds to a

    better metering accuracy than classes 5P and even more so 10P (see figure 3).

    It is always possible to find an equivalence betweena CT defined in class X and a 5P CT or in some

    cases even a 10P CT.

    ≡ Real accuracy factor (Fp or Kr )

    This is the ratio between the overcurrent

    corresponding to the nominal error and the rated

    current of the CT when the real load is different from

    the nominal load.

    ≡ Accuracy limit factor (ALF or Kn)

    This is the ratio between the nominal overcurrent

    (e.g. 10 In) and the rated current (In).

    ≡ Short time withstand current

    Expressed in kA, this is the maximum current Ith that can be withstood for one second (when the secondary is short-

    circuited). It represents the thermal withstand of the CT to overcurrents (the standard values are given by the

    standards mentioned in the appendix).

    ≡ CT rated voltage

    This is the rated voltage to which the CT primary is subjected. It is important to remember that the primary is at HV

    potential and that one of the terminals of the secondary (which must never be opened) is normally earthed.

    Just as for any devices, a maximum withstand voltage for one minute at power frequency and a maximum impulse

    voltage withstand are also defined. Their values are defined by the standards.

    For example: for a rated voltage of 24 kV, the CT must withstand 50 kV for 1 minute at 50 Hz and 125 

    kV at the impulse voltage.

    CT with several secondaries

    Some current transformers may have several secondaries dedicated to protection or to metering. The most typical

    cases are CTs with 2 secondaries, more rarely with 3 secondaries. Physically, these CTs group in the same mould the

    equivalent of 2 or 3 separate CTs that can have different classes and ratios (see figure 4 below).

    http://electrical-engineering-portal.com/instrument-transformers-cts-vts-in-the-system

  • 8/16/2019 Electrical-Engineering-portal.com-Learn How to Specify Current Transformers_2

    6/6

    Figure 4 – Manufacturing principle of a CT with 3 secondaries (with 3 windings in

    the same mould)

    Current transformers – VIDEO sessions

    What are CTs and why use them?

    CT Polarity

    CTR

    Wye connected CTs

    Delta connected CTs

    Current transformer model

    Reference //  Cahier Technique Schneider Electric no. 194 – Current transformers: how to specify them by Schneider

    Electric