3 ELECTRICAL CONDUCTORS

Electric Conductors

Embed Size (px)

DESCRIPTION

abcdef

Citation preview

Page 1: Electric Conductors

3

ELECTRICALCONDUCTORS

Page 2: Electric Conductors

3.1 ELECTRICAL CONDUCTORS

METALS USED

The metals that are most commonly used as conductors in electric cables are

COPPER and ALUMINIUM.

COPPER is obtained impurely by scorching sulphurous minerals that contain it

and at high levels of purity by electrolytic procedures – REQUIRES RE-WORDING.

Making use of its high flexibility, it can be manufactured into very fine wires. This

process hardens the copper and limits its flexibility, which is then recovered by

subjecting the copper conductor to an annealing process.

The conductor stretching operation is called wire drawing, and a number of wires

or bunches of wires are wound around a central one to form a conductor referred

to as a cord. The flexibility of the cord will depend on the fineness of the wires.

The total cross-section is the sum of the areas of each one of the individual wires.

In spite of its numerous qualities, copper

does have a number of drawbacks,

such as its high density and cost,

which from time to time requires

its substitution by another metal

of lower density and cost in order

to reduce the cable material and

ultimately, the manufacturing

costs.

3.1.1 COPPER

• 20 •

Page 3: Electric Conductors

3.1.2 ALUMINIUM

When coming into contact with air, ALUMINIUM is covered with a layer of oxide

called alumina, which protects it from subsequent oxidation. Nevertheless, this

has the drawback of being an insulator, and hinders their connection with

terminations. When in contact with harder metals, such as iron, copper or alloys,

and when in the presence of moisture, aluminium produces a galvanic reaction

which over a period of time, slowly corrodes resulting in total degeneration. In

spite of these drawbacks, which can also be avoided, the fact is that aluminium

has qualities that often make it irreplaceable for overhead power line cabling,

large sectioned cable for high or low voltage circuits, etc. Given its low density (a

third that of copper) and by establishing a relation between their corresponding

resistivities, one half of the weight in copper can be replaced by aluminium

without adversely altering the electrical resistance.

The mechanical properties of aluminium are substantially inferior to those of

copper, and as its resistance to traction is low, hence it is used in alloy or with steel

wires with the aim of endowing it with high tensile strength for overhead lines.

The standard resistivity of aluminium is:

Internationally, the manufacturing of conductors for insulated electric cables is in

keeping with the requirements of the Standards IEC 60228 and EN 60228, which

are in compliance with UNE-EN 60228.

The configuration of a conductor is defined by the

number of wires that make it up, and their nominal

diameter. The degree of rigidity or flexibility is

defined by the different classes that are indicated in

the aforementioned Standards, with Class 1 “Solid”

corresponding to those conductors comprising only

• 21 •

3.2 CONDUCTOR CHARACTERISTICS

1

35,38= 0,028264 ohm • mm2/m a 20ºC

Page 4: Electric Conductors

one wire. Class 2 “Stranded” corresponds to conductors comprising several wires

laid up together, where the minimum number that each individual cross sectional

area should have is specif ied. Classes 5 and 6 “Flexible and Extra

Flexible”correspond to flexible conductors, where the Standard makes special

mention of the maximum diameter of wires, but not to the number of them, which

is left to the judgment of each manufacturer. The difference between Class 5 and

Class 6 lies in the fact that in the latter the wires are smaller for greater flexibility.

Regardless of the other requirements expressed in the Standard, “the

determining factor that must be fulfilled is the maximum electrical resistance of

each conductor", as is indicated in the Standard UNE–EN 60228 (coinciding with

IEC 60228).

WHAT IS THE GEOMETRIC SECTION?

The geometric section of a conductor is the cross section

of a wire or the sum of the cross sections of each of the

wires, in the case of cords, expressed in mm2.

WHAT IS THE NOMINAL SECTION?

The rounded-off value that is close to the geometric section, and which is used for

the cable name, expressed in mm2.

WHAT IS THE ELECTRIC SECTION?

This is the maximum resistance value set by the Standard, in Ohm/km at 20ºC, and

is thus the only one that guarantees the appropriate behaviour of the conductor

with regard to energy transmission.

WHAT IS ELECTRICAL RESISTANCE?

Electrical resistance is the greater or lesser difficulty with which an electric current

runs through a conductor. In accordance with the theory of electrons, an electrical

current is no more than the movement of electrons from one body to another. In

their movement, electrons have to overcome the nuclei of the atoms making up the

conductive material, colliding with them, which results in a certain degree of

difficulty.

This reasoning explains why bodies have different electrical resistances; this is

logical, considering that their atomic makeup is different.

• 22 •

Page 5: Electric Conductors

3.2.1 STANDARD FOR MEASURING RESISTIVITY

Only electrolytically refined copper is used for electrical uses, as the slightest

impurity is sufficient to increase resistivity considerably.

The resistivity of 100% pure copper is:

1/58 = 0, 017241 Ohm. mm2 / m a 20º C

This value is taken as the international standard for

measuring resistivity. For electric cables the minimum

value of resistivity is 98%.

3.2.2 TYPES OF COPPER FOR ELECTRIC CONDUCTORS

Hard copper: used for over-head lines, or in those cases where greater mechanical

resistance is required. It has a breaking load of between 35 and 50 kg/ mm2 and a

stretch at break of between 0.5 and 3%. A minimum electric conductivity of 97%

with regard to the international standard is required.

Annealed copper: always used in insulated conductors. It has a breaking load of

between 20 and 30 kg/ mm2 and a stretch at break of between 25 and 30%. A

minimum electric conductivity of 98% with regard to the international standard is

required.

• 23 •

ELECTRICAL EQUIVALENCE BETWEEN CU AND AL

Resistivity of Cu 0,017241 Ohm•mm2/m a 20ºC

Resistivity of Al 0,028264 Ohm•mm2/m a 20ºC= 0,61

E.g. Section of Al 95mm2 x 0,61 = 57,95mm2 => cable 70mm2 Cu

E.g. Section of Cu 95mm2 : 0,61 = 155,74mm2 => cable 185mm2 Al

Page 6: Electric Conductors

3.2.4 HOW IS THE ELECTRICAL RESISTANCEVALUE OF A CONDUCTOR DETERMINED?

In order to determine the electrical resistance value for a conductor, the cable has

to be kept at an ambient temperature of between 10 and 30º'baC for a minimum

of 12 hours. A Wheatstone bridge or a Thomson bridge is used, depending of the

length and section of the conductor.

The value, in Ohms, of the reading from the bridge divided by the length of the

cable in km will give the resistance of the conductor in Ohms/km. If the measurement

has been carried out at a temperature T other than 20º'baC, it will have been

corrected by means of the following formula:

EXAMPLE: Cable ENERGY–FOC, RV-K 0.6 /1 kV 2 X 1.5 mm2, length: 2,350 m

Black conductor reading (Wheatstone bridge): 32.17 Ohm

Temperature of the cable: 30º C

[ 1 + α20 (T−20)]

32,17

R30 = -------------- = 13,69 Ω / Km a 30º C

2,35

RT 13,69

R20 =------------------------------------ = -------------= 13,17Ω / Km a 20º C

[ 1 + α20 (T-20)] 1,0393

Maximum value of UNE-EN 60228 = 13,3 Ω / Km a 20º C

(*) RT =

R20 =

α20 =

Resistance at temperature

Resistance at 20º C

Coefficient of resistivity variation at 20º C

αCu = 0,00393

Al = 0,00403• 24 •

(*) RT = R20