    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    HIGH-VOLTAGE CIRCUIT BREAKERS DYNAMIC

    CHARACTERISTICS TESTING INSTRUMENT

    User manual

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    2/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Catalog

    HIGH-VOLTAGE CIRCUIT BREAKERS DYNAMIC CHARACTERISTICS

    TESTING INSTRUMENT ......................................................................................................I

    CHAPTER 1.ABOUT THE PRODUCT.................................................................................1

    CHAPTER 2.THE FRONT-PANEL INTRO.........................................................................4

    CHAPTER 3.OPERATE INTRO............................................................................................8

    CHAPTER 4.PC SOFTWARE INTRO................................................................................17

    CHAPTER 5.EXAMPLE.......................................................................................................21

    CHAPTER 6.COMMON FAULT ANALYSIS.....................................................................25

    CHAPTER 7.BILL OF ASSEMBLY.....................................................................................26

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    3/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    CHAPTER 1. ABOUT THE PRODUCT

    1.1 Summarize

    The High-Voltage Circuit Breakers dynamic characteristics testing

    instrument is my company designed to meet the need of testing High-

    Voltage Circuit Breakers . It takes the ARM7 unit for core to sample,

    process and then output; the main characteristic is that its operated in

    alt. It has many advantages such as intelligence, multi-function, accurate

    data, strong anti-jamming, easy operation, small size, beautiful

    appearance, etc; It can test the Circuit Breakers as follows: indoors or

    outdoors Circuit Breakers with less oil or more oil, vacuum Circuit

    Breakers, SF6 Circuit Breakers and so on.

    1.2 Major testing items and functions

    1Twelve contacts closing time and opening time

    2Reclosing time

    3Opening or closings asynchronism

    4springing time or springing times

    5 clearance between open contacts/gaps, over-travel, over-shoot

    and springback

    6speed at instant of contacts touching (separating)7Opening (Closing) max speed

    8Opening (Closing) average speed

    9Operating current curve

    10Display and Print data and curve

    1.3 Major technique parameter

    1Time

    Simultaneity measure Contacts 12

    range06s

    resolution ratio0.01ms

    2Travel

    range250mm

    resolution ratio0.01mm

    3Error

    Time measure error0.1%

    Travel measure error1mm

    4Speed measure range020m/s

    5Internal Power

    Output Voltage20V265V error1%

    27 1

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    4/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    6Operating conditions

    operating voltageAC220V10 %

    frequency50Hz

    Power dissipation 60wambient temperature040C

    ambient humidity 90%RH

    bulk400350200 mm3 weight7kg

    1.4 Definition of Terms

    Touch speed Circuit Breakers is closing the speed at instant of

    contacts touching

    pswhen cant measureusing the average speed at 10ms as far

    as the Circuit Breakers touched to instead of

    Separate speedCircuit Breakers is openingthe speed at instant

    of contacts separating

    pswhen cant measure using the average speed at the Circuit

    Breakers separating as far as 10ms to instead of

    Average speed clearance between open contacts/gaps divide

    time

    Picture 1 Closing Curve Analyze

    2

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    5/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    2 Opening Curve Analyze

    3

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    6/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    CHAPTER 2. The front-panel Intro

    1.5 The front-panel disposal diagram

    Picture 3 Panel

    4

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    7/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    1.6 Test Contacts time

    Picture 4 Contacts

    Picture 5 Contacts connection

    The socket in right upper panelpicture 4is times contact.

    Using the time measure lines connector to insert the socket and the

    other connector, three clamps, to clamp the Circuit Breakers A, B and C.

    three phase.

    connect as picture 5

    Grounding port connects each moving contacts (each moving

    5

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    8/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    contact jumps out themselves).

    Ps : A1 contact is installed the senor

    1.7 Power Circuit Breakers

    Picture 6 Power Switch

    Please using the power wire by our company supply connects to the

    power socket in the flank of the instrument, turn on the power Circuit

    Breakers. If the instrument no work, check the fuse within the power

    socket

    Power requirementthe input AC Power must require

    220V10%,50Hz.Make sure earthing.

    1.8 Control Output

    When power on, user can choose internal power or external power

    in software. if choose internal power, the instrument supply power by

    closing socket or opening socket(DC +) and common socket(DC -)(as

    picture 7),if choose external power, the instrument dont supply power.

    When chosen, the corresponding led will light.

    6

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    9/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture 7 operating

    Picture 8 Power Led

    warning: 1. External power, common socket connect K+.

    2. Internal power, common socket connect K-.

    3. Internal power, system DC source turn off.

    1.9 Senor

    Picture 9 senor

    Using the senor data wire connects the senor and sample input

    socket.

    7

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    10/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    1.10 DC output Intro

    Picture 10 DC output

    User can choose internal power in software, set the DC output valueand turn on air Circuit Breakers. When into closing, opening or

    reclosing test interface, the +,-sockets output DC current. This is using

    stored energy to High-voltage Circuit Breakers Motor.

    1.11 Button intro

    Picture 11 Button

    Reset Buttonreset machine

    Optical Encoder: make the cursor move and change the value.

    Turn leftCursor moves to left or upper.

    Turn rightCursor moves to right or bottom.

    Push downchoosing

    Ps: On normal Optical Encoder turn once, cursor move once. But at

    curve analyze Encoder turn once, cursor moving until Encoder turn

    back.

    CHAPTER 3. Operate intro

    1.12 Closing Test

    8

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    11/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    When power on, display as picture 12

    Picture 12 the main interface

    First choose the kinds of Circuit Breakers, oil, vacuum,SF6 Circuit

    Breakers. appear the next menuas picture 14user can set the

    instrument configure, average speed and instant speed(vacuum no)

    the instrument configure,

    first choose internal or external powerif choose internal

    powermust set the output DC value between 0V~220V

    secondchoose internal trigger or external trigger

    thirdif sample input connect the linear Sensor, choose linear and

    set the total length(25 or 250 mm). if sample input connect the Angle

    Sensor, choose Angle and set mm/.

    This setting can auto save.

    9

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    12/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture 13 Next menu

    After, user can choose the Close to run closing test.

    Set time. For example, if the Circuit Breakers need 200ms to run, we

    can set time 0.3s.

    Click runinto the interface as Picture 14.

    Picture 14 closing test running

    If no error tip, turn to the result interface. But if Relays inside the

    machine no work, will turn to the error interface as Picture 15,16

    10

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    13/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture 15 relays error Picture 16 Circuit Breakers error

    1.13 Opening test

    When power on, display as picture 12

    First choose the kinds of Circuit Breakerses, oil, vacuum,SF6 Circuit

    Breakers. appear the next menuas picture 14user can set the

    instrument configure, average speed and instant speed(vacuum no)

    the instrument configure,

    first choose internal or external powerif choose internal

    powermust set the output DC value between 0V~220V

    secondchoose internal trigger or external trigger

    thirdif sample input connect the linear Sensor, choose linear and

    set the total length(25 or 250 mm). if sample input connect the Angle

    Sensor, choose Angle and set mm/.

    This setting can auto save.

    After, user can choose the Open to run opening test.

    Set time. For example, if the Circuit Breakers need 200ms to run, we

    can set time 0.3s.

    If no error tip, turn to the result interface. But if the relays inside the

    machine dont work, will turn to the error interface as Picture 15, 16.

    1.14 Reclosing Test

    When power on, display as picture 12

    First choose the kinds of Circuit Breakers, oil, vacuum, SF6 Circuit

    Breakers. appear the next menuas picture 14user can set the

    instrument configure, average speed and instant speed(vacuum no)

    the instrument configure,

    first choose internal or external powerif choose internal

    powermust set the output DC value between 0V~220V

    secondchoose internal trigger or external trigger

    thirdif sample input connect the linear Sensor, choose linear and

    11

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    14/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    set the total length(25 or 250 mm). if sample input connect the Angle

    Sensor, choose Angle and set mm/.

    This setting can auto save.

    After, user can choose the Reclose to run Reclosing test. as picture2122the option of time is like the closing test and the opening test.

    Choosing the next option ,rotate the Optical Encoder, choose you want

    testing fromO-C(opening-closing),C-O(closing-opening),O-C-O(closing-

    opening-closing),C-O-C(closing-opening-closing).Push down, will appear

    one time to set(O-C-O,C-O-C will appear two),this time is a delay time

    between the Circuit Breakers open and close(0.0s~9.9s).

    Picture 17 C-OO-C Picture 18 C-O-C,O-C-O

    If no error tip, turn to the result interface. But if Relays inside the

    machine no work, will turn to the error interface as Picture 17,18.

    1.15 Separate test

    When power on, display as picture 12

    First choose the kinds of Circuit Breakers, oil, vacuum,SF6 Circuit

    Breakers. appear the next menuas picture 14user can set the

    instrument configure, average speed and instant speed(vacuum no)

    the instrument configure,

    first choose internal or external powerif choose internalpowermust set the output DC value between 0V~220V

    secondchoose internal trigger or external trigger

    thirdif sample input connect the linear Sensor, choose linear and

    set the total length(25 or 250 mm). if sample input connect the Angle

    Sensor, choose Angle and set mm/.

    This setting can auto save.

    After, user can choose the Low Voltage to run Separating test. At first

    will into choosing power interface, confirm the choosing, into the set

    interface of the separating test. As picture 14.

    12

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    15/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture 19 Separating Test

    Confirm the power choosinginto the interface as picture 19.

    Picture 20 Separating Test setting

    Set the percent of the voltage value, then choose the Close(closing

    test run) or the Open(opening test run) push downafter , choose print or

    back. On the basic of the Standard for hand-over test of electric

    equipment, the Circuit Breakers should be false-action reliability on lower

    than 30% of rated voltage, the Circuit Breakers should action reliability on

    higher than 65%.

    After push down run, will appear the interface as picture 21.if the

    instrument dont check out the opening or closing sign at A1,the interface

    will display false action, if check out, display action.

    13

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    16/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture 21 Separating test

    Push down the option Print, will print out the result of this test.

    1.16 Result of test

    The interface of Result of test have, DataDisplay,

    TimeCurve SpeedTravelCurve TravelTimeCurve, four interface

    options.

    1.16.1DataDisplay

    DataDisplay, displays the time of opening or closing, closing springing. clearance

    between open contacts overtravel Contact bouncing duration overshoot average

    speedmax speedtouching (separating) speed. as picture 23,24

    Picture 23 when oil switch Picture 24 when vacuum switch

    The option of the interface as picture 23,24

    14

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    17/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    1Printprint out the result of this test, the opening(closing) time,

    Bounce time or times, clearance between open contacts, overtravel,

    Contact bouncing duration, overshoot, Avg.speed, max speed, Inst.Speed

    (separating) speed.2SaveSave the data of this test, no current data. If you have saved,

    this button will change to delete.

    3PageIf the test is reclosing test, this button can display the other

    result. For example, test is closing opening test, first display the result of

    the closing, push down Page, display the result of the opening.

    1.16.2Timing Curve

    Display the Breaks curve of twelve contacts and the current-timing

    curve within 200ms of the operate current. As picture 25

    Picture 25 breaks curve

    The option of the interface:

    1Datago to the DataDisplay interface.

    2Analysewhen push down, will have a line which can get the data

    of the curve and the data will be displayed at right of the interface.

    When push down again, this line is sure and have the other line until

    user push down this button.

    3Next

    display the others data of the reclosing test.

    4Printpint out the timing curve.

    5Returnback to The interface of Result of test

    1.16.3Travel-Timing Curve

    Display the Distance-Time curve of the moving contact. as picture

    26.

    15

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    18/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture 26 Distance-Time curve

    The option of the interface:

    1Datago to the DataDisplay interface.

    2Analysewhen push down, will have a line which can get the data

    of the curve and the data will be displayed at right of the interface. When

    push down again, this line is sure and have the other line until user push

    down this button.

    3Nextdisplay the others data of the reclosing test.

    4Print

    pint out the timing curve.

    5Returnback to The interface of Result of test.

    1.16.4 Speed-Travel Curve

    Display the Speed-Distance curve of the moving contact. as picture 27

    Picture 27 Speed-Distance Curve

    16

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    19/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    The option of the interface:

    1Datago to the DataDisplay interface.

    2Analysewhen push down, will have a line which can get the data

    of the curve and the data will be displayed at right of the interface. Whenpush down again, this line is sure and have the other line until user push

    down this button.

    3Nextdisplay the others data of the reclosing test.

    4Printpint out the timing curve.

    5Returnback to The interface of Result of test

    1.17 State of Contacts

    User can see the real-time state of the twelve contacts .push down

    the back option, back to main interface.

    1.18 History Data

    Display the history data. the instrument can save 24 group of opening

    test or closing test data and save 8 group of reclosing test. if save more

    data, will cover the oldest data.

    The option of the interface:

    1Loadwhen push down first, user can choose which group to read.

    Push down again, will read the cursor point data.

    2Nexthistory data of the opening test or closing test change to

    history data of the reclosing test.3Deleteclear the history data of the opening test or closing test or

    the history data of the reclosing test. if user wish delete the specifically

    data, can first get in the data which want to delete, and then push down

    the delete in the DisplayData interface.

    4Returnback to the main interface.

    1.19 PC communication

    Use the USB cable connects the compute and the instrument. Push

    down the PC-Com option in the main interface. This function can make PC

    to control the instrument testing and receive the history data.

    1.20 Date

    Change Date & Time.

    CHAPTER 4. PC software intro

    1.21 Installation

    This software is Installationfree version, user can unzip to hard disk as

    17

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    20/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    picture 29 30.

    picture 29 Software package picture 30 software main program

    runGKStudio.exeto use.

    1.22 Operation

    1.22.1 Communication

    First, Use the USB cable connects the compute and the instrument.

    Push down the PC-Com option in the main interface.

    Second,user can check the state of communication by push theConnect button. if the PC connected the instrument, user can use all

    function. If no, will give a tip as picture 31

    Picture 31 USB connect failure

    1.22.2 Read the history data in the instrument

    Push down Upload,PC will receive all data which saved in the

    instrument. User can choose one group data to check by choosing in drop

    down listResult of test at left interface. The oscilloscope will display

    curve, then pushing down view data will see all detailed data of this

    group data. User can save this group data by pushing save, the data will

    be saved by .GK at hard disk.

    18

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    21/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture 32 history data display

    19

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    22/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    33 history data display by word

    Pushing read will see the last uploading history data.

    1.22.3 PC control of the instrument to test

    When PC connected the instrument, check the set of speed, trigger

    and power, choose type of test, type of switch, type of senor and so on.

    Click Start, please make sure all right, click OK. The instrument will

    run the test and upload the result of test.

    1.22.4 Save the data on PC

    All the result of test and uploading history data can be save as 1.as

    word,2.as excel,3 print the report.

    1. Click the export, as picture 35, choose save as word. if

    users PC installed the Microsoft office 2003,will save data

    report as word.

    2. Click the export, as picture 35, choose save as excel.

    3. Click the print, will get into print preview, user can set page

    header and footer at the Preferences windows. Click the print.

    20

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    23/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture .35 export report

    CHAPTER 5. Example

    1.23 How to connection

    Require: fix the senor to the A1.

    1when using the internal power supply, closing control connects to

    picture 36 using our lines; opening control connects to in picture

    36; Common connects to -KM in picture 36; the fuse in picture 36

    must be removed.

    2when using the external power supply, closing control connects to

    in picture 36 using our lines; opening control connects to in picture

    36; Common connects to +KM in picture 36

    21

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    24/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    +KM -KM

    closing control

    HC

    5 8

    LD DL1

    11 10

    HD

    16 13

    6 7

    + DL2

    TQ

    +HM opening control -HM

    Hc HQ Hc

    Picture 36 console panel connection

    1.24 Fit sensor in oil Circuit Breakers

    open the cover of the explosion chamber, insert the transmission pole into

    the explosion chamber, and screw the inside end of the transmission pole

    tightly to the screw of the moving contact, the other end of the pole connects to

    the sample ruler.

    The ruler should glide in the runner easily, and the base of the ruler must be fixed

    to the explosion chamber.

    Requirements: connect the contact to the A1 on the front-panel, the signal

    lines plug of the sampler connects to the Sample Input interface, when fix the

    sample pole ,the sample ruler should be kept clean and straight. when theres

    pollute like oil or dust in the sample ruler, the ruler should be cleaned by gasoline

    or alcohol., or the measured results may be discrete.

    How to connect: all the moving contacts of the switches connects to the

    ground hole in the front-panel of the tester, the ground hole then connects to the

    earth ground reliably; the static contacts to the A,B,C hole correspondingly.(see

    Picture 38)

    22

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    25/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    1 2

    3

    Picture 37 explosion chamber

    Picture 37it shows a sample ruler for 110KV-220KV switches; if 1,2,3 parts

    are removed, the sample ruler is applied to the 10KV switches.

    Picture 38 Fit sensor in oil Circuit Breakers

    1.25 Fit sensor in vacuum Circuit Breakers

    Let the switch be at a open state, fix the senor to fixed shelf in the bottom

    of the switchs, make the probe just touch the moving contact by adjusting the

    23

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    26/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    spring, use the line to connect the probe and the External Trigger hole in the

    front-panel, how to connect the remainder lines is just like the method for oil

    switch.(see picture 39)

    Picture 39 Fit sensor in vacuum Circuit Breakers

    1.26 Fit sensor in SF6 Circuit Breakers

    Remove the glass window of the lift-pole room, fix the fixing board with the

    infrared-induction head into the screw hole in the room, fix the sample ruler to

    the corresponding position , adjust the fixing parts to make the ruler to slide in the

    runner up and down, how to connect the lines is just like the methods for other

    switches.(as picture 40)

    24

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    27/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    Picture 40 Fit sensor in sf6 Circuit Breakers

    CHAPTER 6. Common Fault Analysis

    1.27 Display too bright or too dark

    if the LCD display too bright or too dark,please adjust the potentiometer by a

    screw until the display show comfort you.

    1.28 System halted

    press the Reset key when the tester is halted.

    25

  • 7/28/2019 Electric Circuit Breaker Test Instrument HYGK-306

    28/28

    High-Voltage Switch Dynamic Characteristics Testing Instrument User manual

    1.29 Print abnormality

    Power down the instrument when the printer operates abnormally, and wait

    for about half a minute.

    CHAPTER 7. bill of assembly

    list 7.1 bill of assembly

    instrument 1 unit

    Seniors 1 set

    User manual 1 copy

    Mini printer User manual 1 copyTest cables 1 set

    We are responsible for the customer who use

    our products, guarantee to keep the products in

    good repair in one year after we sell them to you.

    Welcome to feedback the invaluable advice and

    information of the products to us .Thanks for

    your cooperation.

    Forgive us not to inform you the possible

    changes.

    26