27
EKAS 2.19.28 Fault find- General Principles UEE31307 Certificate III in Refrigeration and Air Conditioning Stage 2A Units: UEENEEPOO1B Chris Hungerford 6/15/22

EKAS 2.19.28 Fault find- General Principles

  • Upload
    zayit

  • View
    28

  • Download
    1

Embed Size (px)

DESCRIPTION

EKAS 2.19.28 Fault find- General Principles. UEE31307 Certificate III in Refrigeration and Air Conditioning Stage 2A Units: UEENEEPOO1B Chris Hungerford Monday, August 25, 2014. The two golden rules. Test before you touch , this protects you physically, so you can have a good day! - PowerPoint PPT Presentation

Citation preview

Page 1: EKAS 2.19.28 Fault find- General Principles

EKAS 2.19.28

Fault find- General Principles

UEE31307 Certificate III in Refrigeration and Air Conditioning

Stage 2A Units: UEENEEPOO1B

Chris Hungerford4/21/23

Page 2: EKAS 2.19.28 Fault find- General Principles

The two golden rules• Test before you touch, this protects

you physically, so you can have a good day!

• Test your work is electrically safe when completed, tests include insulation resistance, earth continuity, polarity, and visual inspection, this protects you financially.

2.19.28.A

Page 3: EKAS 2.19.28 Fault find- General Principles

Safe Isolation of a Supply

• Test before you touch, this protects you physically, so you can have a good day!

Procedure to isolate a Supply1. Notify all persons likely to be affected by the isolation.2. Determine the method to isolating the supply.3. Test the supply availability.4. Isolate the supply.5. Danger tag the isolation device.6. Test that the supply is isolated.7. Test the testing device.

2.19.28.A

Page 4: EKAS 2.19.28 Fault find- General Principles

Are you working LIVE?Using a voltmeter to measure low voltage is working live!

Electrical Safety Regulation 200211 Requirements for electrical work(1) An employer or self-employed person must ensure that, unless the circumstances required under this division for the performance of live work apply, live work is not performed.Maximum penalty—40 penalty units.

WARNING

As per Regulation 12 “Requirement for performance of live work”, to perform live work you must satisfy the following seven (7) questions:

1. Have you prepared a risk assessment?2. Is your test equipment appropriate to perform live work? Minimum Cat III @ 500v ac.

3. Has your test equipment been maintained and confirmed that it is operating correctly? Regulation 18.2(b) “the instrument is tested at least every 6 mths to ensure it is in proper working order”, and Regulation 12.1(f) “the instrument is tested immediately prior to work to confirm that the instrument is operating correctly”

4. Have you the correct PPE, (Safety boots, long pants, long sleeved shirt, insulated gloves, safety glasses)? As per AS/NZS 4836 Safe working on low voltage electrical installations.

5. Is the isolation point clearly identified?6. Is the isolation point able to be reached without any obstructions?7. Is the area where the electrical live work is performed clear of any obstructions?Note: if you are not working within the requirements of the above laws then your inaction to comply threatens the following; 1. Your right to claim workcover in the event of an accident2. Your right to claim any insurance benefits in the event of an accident3. You will be fined the prescribed penalty units for those laws that you have breached.

2.19.28.A

Page 5: EKAS 2.19.28 Fault find- General Principles

What is a Fault?

• Any condition in an electrical system that is dangerous or unsafe is a fault.

• Any condition that will prevent the electrical system from operating correctly is a fault.

2.19.28.B

Page 6: EKAS 2.19.28 Fault find- General Principles

Overload An overload is a condition where the load on the circuit is too much, causing the current to exceed the current rating of the cables and supply. If the excessive current was allowed to continue, the cables would heat above their rating and may lead to a short circuit.

240vLoad48

I = V = 240 = 5A R 48

6A fuse

240v

48

I = V = 240 = 10A R 24

6A fuse

48

2.19.28.B

Page 7: EKAS 2.19.28 Fault find- General Principles

Short circuit, A very severe condition and will cause fire, burns, and equipment damage if not protected against. The only resistance to the current is that of the supply cables and the size of the electrical source.

240v, 500A supply

cables = 0.5

Load47.5

240v, 500A supply

cables = 0.5

Load48

I = V = 240 = 5A R (47.5+.5)

short circuit 0.5

I = V = 240 = 240A R (.5+.5)8A fuse

240v, 500A supply

short circuit 0.5

The fuse will open circuit whenthe current exceeds it’s rating.2.19.28.B

Page 8: EKAS 2.19.28 Fault find- General Principles

Partial open circuit, (hot joint) caused by loose or dirty connections that causes an increased circuit resistance. This increased resistance causes a heating effect at the joint and reduces the current at the load. Will cause fire and equipment damage. A fuse or circuit breaker will not protect against this type of fault. The only combat is by visual inspections or thermal imageries.

240v48

I = V = 240 = 5A R 48

P=V*I =240 *5 = 1200W

240v48

I = V = 240 = 4A R (12+48)

P=I *R =4 *48=768W

12P=I R = 4 *12 = 192W2 2

2 2

2.19.28.B

Page 9: EKAS 2.19.28 Fault find- General Principles

Partial short circuit Like a short circuit with a higher resistance. Normally earth faults. Fuses and circuit breakers may not open circuit if the fault current does not exceed their rating. Earth leakages are good examples.

240vLoad48

I = V = 240 = 5A R 48

6A fuse

240v 48

I = V = 240 = 7A R 34.2

6A fuse

120

5A2A

2.19.28.B

Page 10: EKAS 2.19.28 Fault find- General Principles

Procedures for fault findingVoltage

Present Not present

Measurecurrent

No current High current Low current

Measureresistance

Measureresistance

Opencircuit

Shortcircuit

Partialshort circuit or

overload

Partialopen circuit

Very low resistance

Low resistance

Partialshort circuit or

overload2.19.28.B

Page 11: EKAS 2.19.28 Fault find- General Principles

Flowchart For Problem Resolution

Don’t Stuff With It!

YES NO

YES

YOU IDIOT!

NO

Will it Blow UpIn Your Hands?

NO

Look The Other Way

Anyone ElseKnow? You’re SCREWED!

YESYES

NO

Hide ItCan You Blame Someone Else?

NO

NO PROBLEM!

Yes

Is It Working?

Did You Stuff With It?

Page 12: EKAS 2.19.28 Fault find- General Principles

Common sense ways to think of categories

Overvoltage category

• The higher the short circuit fault current available, the higher the category

– High energy transients are much more dangerous, because they can trigger an arc blast

• The greater the source impedance, the lower the category

2.19.28.B

Page 13: EKAS 2.19.28 Fault find- General Principles

2.19.28.B

Page 14: EKAS 2.19.28 Fault find- General Principles

CAT IV-600 V CAT III-1000 V

What’s the bottom line?• If you work on power circuits, you

need a CAT III-600 V or CAT IV-600 V/ CAT III 1000 V meter.

• Look for the CAT rating and voltage rating marked near the input jacks.– CAT or voltage rating alone can be

misleading

• Look for independent certification.

2.19.28.B

Page 15: EKAS 2.19.28 Fault find- General Principles

Fault finding: Continuity technique• Warning: Disconnect the supply.

• All healthy component’s circuit have a value of resistance.

• Placing an ohmmeter across the component should indicate the components condition.– Values of 0 are considered as short circuited.

– Values of infinite ohms are considered as open circuited.

2.19.28.B

Page 16: EKAS 2.19.28 Fault find- General Principles

Fault finding: Supply available technique• Low voltage is present therefore Regulation 12 ESR2002

must be satisfied before working live.• Voltmeter set to highest scale• Place voltmeter across the circuit with supply available:

– the voltmeter should indicate the supply if healthy.– If the voltmeter does not indicate the supply then search across

the circuit devices for the voltage.

A1 A2 NA 240V

HP/LPT/OT=25deg C contactor

Voltmeter should indicate 240v if healthy

2.19.28.B

Page 17: EKAS 2.19.28 Fault find- General Principles

A1 A2 NA 240V

HP/LPT/OT=25deg C contactor

Voltmeter = 0v

NO supply indicated by the voltmeter, be careful, •just because the voltmeter does not indicate any voltage does not mean there is no voltage present, the voltage difference across the across the HP/LP is zero. It could be 240v each side of the HP/LP therefore the difference is zero.

2.19.28.B

Page 18: EKAS 2.19.28 Fault find- General Principles

A1 A2 NA 240V

HP/LPT/OT=25deg C contactor

Voltmeter = 0v

Voltmeter=0v, the fault has not shown itself.

2.19.28.B

Page 19: EKAS 2.19.28 Fault find- General Principles

A1 A2 NA 240V

HP/LPT/OT=25deg C contactor

Voltmeter = 240v

Voltmeter=240v, the fault has shown itself.

A healthy circuit the voltage should be 0v across a closed switch. This voltmeter indicates a difference therefore the T/O is defective.

2.19.28.B

Page 20: EKAS 2.19.28 Fault find- General Principles

A1 A2 NA 240V

HP/LPT/OT=25deg C contactor

Voltmeter = 180v

2.19.28.B

Page 21: EKAS 2.19.28 Fault find- General Principles

A1 A2 NA 240V

HP/LPT/OT=25deg C contactor

Voltmeter = 180v

Voltmeter = 180v, therefore the circuit between HP/LP to A1 is OK.

2.19.28.B

Page 22: EKAS 2.19.28 Fault find- General Principles

A1 A2 NA 240V

HP/LPT/OT=25deg C contactor

Voltmeter = 240v

Voltmeter = 240v, and 180v as before, therefore, the problem must be across the HP/LP.

2.19.28.B

Page 23: EKAS 2.19.28 Fault find- General Principles

A1 A2 NA 240V

HP/LPT/OT=25deg C contactor

Voltmeter = 60v

Voltmeter = 180v

The Voltmeter across the HP/LP should be equal to 0v as the resistance of a closed switch should be as close to zero ohms.

The voltmeter indicates an elevated voltage (60v) therefore there must be an elevated resistance, i.e. high resistance.

2.19.28.B

Page 24: EKAS 2.19.28 Fault find- General Principles

Work Record required by Regulations

Electrical Safety Regulation 2002Part 2 Electrical work

14 Testing of electrical equipment after electrical work

(1) This section applies if electrical work is performed on electrical equipment.

(2) A person who performs part or all of the electrical work, and is responsible for bringing the electrical equipment to a state of readiness for connection to a source of electricity for use for its intended purpose, must ensure the electrical equipment is tested, as required under subsections (5) and (6).

Maximum penalty—40 penalty units.

.

2.19.28.B

Date of inspection

Appliance Visual inspection

Earth continuity

Insulation resistance

M

Polarity = Correct

RCD test current

30 MA trip timeMilliseconds

0 180 Test butt

2/7/09 Refrigerator ( LG model R100020 Serial 1004039832)

O.K 0.3 75M N/A N/A N/A N/A

2/7/09 Safetypac (Clipsal mod 56B, serial 9987987)

o.K. 0.8 187M 22 18

Page 25: EKAS 2.19.28 Fault find- General Principles

Electrical Safety Regulation 2002 Part 2 Electrical work15 Certificate of testing and safetyThis section applies if a licensed electrical contractor performs electrical work that must be tested

under this division.(2) The contractor must, as soon as practicable after the testing, ensure that the person for whom the

electrical work was performed is given a certificate complying with this section.(5) A licensed electrical contractor must keep a copy of a certificate given under this section for at least

5 years after the certificate is given.Maximum penalty for subsection (5)—20 penalty units

Work Record required by Regulations

Certificate of Testing and SafetyAs per Electricity Safety Regulation 2002,Part 8”Electricity Supply”, Division 3 “Testing”, Regulation 159,”Certificate of Testing & Work”

Electrical worker who tested the electrical work.

Phone Licence No: Contractors Licence Details of work

Details of Electrical Contractor Inspection Certificate No:

Acts, Regulations,Codes of Practices & Standards.

Electricity Act 1994 & Electricity Regulation 2006Electrical Safety Act 2002 & Electrical Safety Regulation 2002AS/NZS 3000:2000. Incorporating Amendment No. 1 (September 2001), Amendment No. 2 (April 2002), & Amendment No. 3 (July 2003). The Wiring Rules.

AS/NZS 3008.1.1:1998, Electrical installations— Selection of cables Part 1.1: Cables for alternating voltages up to and including 0.6/1 kV—Typical Australian installation conditions

I certify that the electrical installation work listed above has been tested in accordance with the prescribed procedures and that such work is electrically safe and complies in every respect with the requirement of the Electricity Safety Regulation 2002, regulation 159.Signature of Electrical worker:

Date of Certification:

2.19.28.B

Page 26: EKAS 2.19.28 Fault find- General Principles

Manufacturer Specifications of disconnected & replacement equipment.

When replacing any load you should be sure that the new item is suitable with regards to: Speed, Rotation, Power rating, Voltage, Current, Physical size, Environmental conditions & design of replacement, Dust & waterproof, temperature, UV rating, touch proof, life span.

2.19.28.C

Page 27: EKAS 2.19.28 Fault find- General Principles

Energising supply• Only after the visual inspections and safety testing as per

AS/NZS 3000:2007 has proven that the circuit is fit for purpose are you to energise the circuit.

• Remove only your Danger tag. If another worker has their danger tag on the isolated point then you can not energise.

• If clear: Energise the circuit.• Test for the correct and safe operation of the circuit, i.e.

rotation, system performance, current draw, voltage, etc.• Prepare all your safety and performance documentation.

2.19.28.C