General Specifications <<Contents>> <<Index>> EJX910A Multivariable Transmitter Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-5690 Fax.: 81-422-52-2018 GS 01C25R01-01EN GS 01C25R01-01EN ©Copyright Mar. 2005 32nd Edition Nov. 2019 The high performance EJX910A multivariable transmitter features multi-sensing technology with a single-crystal silicon resonant sensor that outputs the measured differential pressure, static pressure and process temperature, which covers multiple protocols: HART, FOUNDATION fieldbus and RS485 Modbus. Additionally the HART protocol and FOUNDATION fieldbus protocol types are suitable to measure dynamically calculated and fully compensated mass flow for liquid, gas, or steam. 4 to 20 mA DC signal output is available in HART protocol type. FDT/DTM* standard conforming software is available for transmitter configuration. FSA120 (FlowNavigator ® ) is used for flow configuration of the HART protocol and FOUNDATION fieldbus protocol types. *: FDT (Field Device Tool): Defines the system environment in which the DTM runs. DTM (Device Type Manager): The application which defines the graphical user interface (GUI) specific to the device. Key features: [HART protocol type] • 1.0% mass flow rate accuracy over 1:10 flow range (In case of uncalibrated differential producer (Orifice)) • HART7: Orifice, Nozzle, Venturi, Multiport Averaging Pitot and Cone meters primary devices are supported • HART5: Orifice, Nozzle and Venturi primary devices are supported • Advanced diagnostic function (option) • Simultaneous dual output of 4 to 20mA and pulse signals. • HART protocol revision selectable from 5 (HART 5) or 7 (HART 7) • Long tag supporting up to 32 characters (HART 7) • Enhanced burst mode and event notification(HART 7) • SIL2 for safety requirement Note: HART 5 stands for HART protocol revision 5 HART 7 stands for HART protocol revision 7 [FOUNDATION Fieldbus protocol type] • 1.0% mass flow rate accuracy over 1:10 flow range (In case of uncalibrated differential producer (Orifice)) • Orifice, Nozzle and Venturi primary devices are supported • Advanced diagnostic function (option) • Various function blocks available; 5 AIs, AR, IT, SC, and IS as standard. PID as an optional feature. • Cyclically displays up to 10 variables • Software download function (option) [Modbus protocol type] • RS485 Modbus protocol type provides easy multi- sensing data transmission to the flow computers. • The process data status is provided for each measured differential pressure, static pressure and process temperature. It is easy to implement process data diagnosis. • Cyclically displays up to 16 variables including RTU management data. • Up to 32 transmitters can be connected by multi-drop communication. • 32 characters long tag and squawk are supported for easy identification of transmitters. STANDARD SPECIFICATIONS □ SPAN AND RANGE LIMITS Differential Pressure (DP) Measurement Span/Range kPa inH2O (/D1) mbar (/D3) mmH2O (/D4) L Span 0.1 to 10 0.4 to 40 1 to 100 10 to 1000 Range -10 to 10 -40 to 40 -100 to 100 -1000 to 1000 M Span 0.5 to 100 2 to 400 5 to 1000 50 to 10000 Range -100 to 100 -400 to 400 -1000 to 1000 -10000 to 10000 H Span 2.5 to 500 10 to 2000 25 to 5000 0.025 to 5 kgf/cm 2 Range -500 to 500 -2000 to 2000 -5000 to 5000 -5 to 5 kgf/cm 2 Static Pressure (SP) Absolute Pressure Measurement Span/Range MPa abs psia (/D1) bar abs (/D3) kgf/cm 2 abs (/D4) L Span 1 to 16 145 to 2300 10 to 160 10 to 160 Range 0 to 16 0 to 2300 0 to 160 0 to 160 M H Span 1 to 25 145 to 3600 10 to 250 10 to 250 Range 0 to 25 0 to 3600 0 to 250 0 to 250 [Style: S2]

EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

GeneralSpecifications

<<Contents>> <<Index>>

EJX910AMultivariable Transmitter

Yokogawa Electric Corporation2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 JapanTel.: 81-422-52-5690 Fax.: 81-422-52-2018

GS 01C25R01-01EN

GS 01C25R01-01EN©Copyright Mar. 2005

32nd Edition Nov. 2019

The high performance EJX910A multivariable transmitter features multi-sensing technology with a single-crystal silicon resonant sensor that outputs the measured differential pressure, static pressure and process temperature, which covers multiple protocols: HART, FOUNDATION fieldbus and RS485 Modbus.Additionally the HART protocol and FOUNDATION fieldbus protocol types are suitable to measure dynamically calculated and fully compensated mass flow for liquid, gas, or steam. 4 to 20 mA DC signal output is available in HART protocol type.FDT/DTM* standard conforming software is available for transmitter configuration. FSA120 (FlowNavigator®) is used for flow configuration of the HART protocol and FOUNDATION fieldbus protocol types.*: FDT (Field Device Tool): Defines the system environment

in which the DTM runs. DTM (Device Type Manager): The application which

defines the graphical user interface (GUI) specific to the device.

Key features:[HART protocol type]•1.0%massflowrateaccuracyover1:10flowrange (Incaseofuncalibrateddifferentialproducer(Orifice))•HART7:Orifice,Nozzle,Venturi,MultiportAveraging

Pitot and Cone meters primary devices are supported•HART5:Orifice,NozzleandVenturiprimarydevices

are supported•Advanceddiagnosticfunction(option)•Simultaneousdualoutputof4to20mAandpulse

signals.•HARTprotocolrevisionselectablefrom5(HART5)or7(HART7)

•Longtagsupportingupto32characters(HART7)•Enhancedburstmodeandeventnotification(HART7)•SIL2forsafetyrequirement

Note: HART5standsforHARTprotocolrevision5 HART7standsforHARTprotocolrevision7

[FOUNDATION Fieldbus protocol type]•1.0%massflowrateaccuracyover1:10flowrange (Incaseofuncalibrateddifferentialproducer(Orifice))•Orifice,NozzleandVenturiprimarydevicesare

supported•Advanceddiagnosticfunction(option)•Variousfunctionblocksavailable;5AIs,AR,IT,SC,

and IS as standard. PID as an optional feature.•Cyclicallydisplaysupto10variables•Softwaredownloadfunction(option)[Modbus protocol type]•RS485Modbusprotocoltypeprovideseasymulti-sensingdatatransmissiontotheflowcomputers.

•Theprocessdatastatusisprovidedforeachmeasured differential pressure, static pressure and process temperature. It is easy to implement process data diagnosis.

•Cyclicallydisplaysupto16variablesincludingRTUmanagement data.

•Upto32transmitterscanbeconnectedbymulti-dropcommunication.

•32characterslongtagandsquawkaresupportedforeasyidentificationoftransmitters.

STANDARD SPECIFICATIONS SPANANDRANGELIMITSDifferential Pressure (DP)MeasurementSpan/Range kPa inH2O

(/D1)mbar(/D3)

mmH2O(/D4)

LSpan 0.1 to 10 0.4 to 40 1 to 100 10 to 1000

Range -10 to 10 -40 to 40 -100 to 100

-1000 to 1000

MSpan 0.5 to 100 2 to 400 5 to 1000 50 to

10000

Range -100 to 100

-400 to 400

-1000 to 1000

-10000 to 10000

HSpan 2.5 to 500 10 to 2000 25 to 5000 0.025 to 5

kgf/cm2

Range -500 to 500

-2000 to 2000

-5000 to 5000

-5 to 5 kgf/cm2

Static Pressure (SP)Absolute Pressure

MeasurementSpan/Range MPa abs psia

(/D1)bar abs(/D3)

kgf/cm2 abs (/D4)

LSpan 1 to 16 145 to

2300 10 to 160 10 to 160

Range 0 to 16 0 to 2300 0 to 160 0 to 160

MH

Span 1 to 25 145 to 3600 10 to 250 10 to 250

Range 0 to 25 0 to 3600 0 to 250 0 to 250

[Style: S2]

Page 2: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

2

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

GaugePressure(Sealedgauge)MeasurementSpan/Range MPa psi

(/D1)bar(/D3)

kgf/cm2 (/D4)

LSpan 1 to 16 145 to

2300 10 to 160 10 to 160

Range -0.1 to 16 -14.5 to 2300 -1 to 160 -1 to 160

MH

Span 1 to 25 145 to 3600 10 to 250 10 to 250

Range -0.1 to 25 -14.5 to 3600 -1 to 250 -1 to 250

External Temperature (ET) (Pt100 ohm)Measurement External

Temperature Span/Range °C °F K

LMH

Span 10 to 1050 18 to 1890 10 to 1050

Range -200 to 850

-328 to 1562 73 to 1123

Fixed Temperature -273 to 1927

-459 to 3500 0 to 2200

PERFORMANCESPECIFICATIONSZero-based calibrated span output, and silicone oil, unless otherwise mentioned.For FOUNDATION Fieldbus and Modbus protocol types, use calibrated range instead of span in the following specifications.

SpecificationConformanceEJXseriesensuresspecificationconformancetoatleast±3σ.

Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types)

Mass Flow Reference Accuracy±1.0%ofMassFlowRateover10:1flowrange(100:1DPrange)forliquidsandgases.

Totalized Mass Flow Reference Accuracy1.0%ofTotalMassFlow.Note:Assume100:1DPrangeforliquidsandgases.

Conditionsformassflowaccuracy(1)Autocompensationmode.(2)MandHcapsule(3)Uncalibrateddifferentialproducer(Orifice)installed

based on the following standards. *1(4)Uncertaintiesfordischargecoefficient,primary

device bore, pipe diameter, and gas expansion factordefinedonfollowingstandards.*1

(5)Densityuncertaintylessthan0.1%.

*1: Standards: ISO5167-1 1991, ISO5167-2 2003, ASME, MFC-3M 1989, AGA No.3 1992

Differential Pressure (DP) Reference Accuracy of Calibrated Span

(Includes terminal-based linearity, hysteresis, and repeatability)

Measurement span HReferenceaccuracy

X≤span ±0.04%ofSpanX > span ±(0.005+0.0049URL/span)%ofSpan

X 70kPa(280inH2O)URL

(upperrangelimit) 500kPa(2000inH2O)

Measurement span MReferenceaccuracy

X≤span ±0.04%ofSpanX > span ±(0.005+0.0035URL/span)%ofSpan

X 10kPa(40inH2O)URL

(upperrangelimit) 100kPa(400inH2O)

Measurement span LReferenceaccuracy

X≤span ±0.04%ofSpanX > span ±(0.015+0.005URL/span)%ofSpan

X 2kPa(8inH2O)URL

(upperrangelimit) 10kPa(40inH2O)

Ambient Temperature Effects per 28°C (50°F) Change

Capsule EffectHML

±(0.04%Span+0.0125%URL)±(0.04%Span+0.009%URL)±(0.055%Span+0.09%URL)

Static Pressure Effects per 6.9 MPa (1000 psi) Change

Span EffectsL,MandHcapsules±0.075%ofspan

Effect on ZeroCapsule EffectHML

±0.028%URL±0.02%URL±0.05%URL

Overpressure EffectsOverpressure condition: up to maximum working pressureMandHcapsules±0.03%ofURL

Stability (All normal operating condition, including overpressure effects)MandHcapsules±0.1%ofURLper15years

Static Pressure (SP) Reference Accuracy of Calibrated Span for

Absolute pressure (Includes terminal-based linearity, hysteresis,

and repeatability)Capsule Reference accuracyL,M,H ±0.1%ofspan

Note: Gauge pressure reference is 1013.25 hPa (1 atm)Thegaugepressurevariableisbasedontheabove reference accuracy and can be affected by changes in the atmospheric pressure.

Ambient Temperature Effects per 28°C (50°F) Change

Capsule EffectM,HL

±0.08%Span±0.018%URL±0.08%Span±0.028%URL

Aug. 15, 2016-00

Page 3: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

3<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

External temperature (ET) Accuracy (Includes terminal-based linearity,

hysteresis, and repeatability)

Capsule AccuracyL,M,H ±0.5°C(±0.9°F)

SpecificationforExternaltemperatureisthetransmitter portion only.Sensor errors caused by the RTD are not included.The transmitter is compatible with any Pt100 RTD conforming to IEC 751.Input/output signal is non-isolated.

Ambient Temperature Effects per 28°C (50°F ) Change

Capsule EffectL,M,H ±0.5°C(±0.9°F)

Power Supply Effects (HART protocol type)±0.005%perVolt(from21.6to32VDC,350Ω)

Vibration EffectsSignal Effect

Differential Pressure ±0.1%ofURLStatic Pressure ±0.1%ofURLExternal Temperature ±0.5°C(±0.9°F)

Amplifierhousingcode1:WhentestedpertherequirementsofIEC60770-1fieldorpipelinewithhighvibrationlevel(10-60Hz,0.21mmdisplacement/60-2000Hz3g)Amplifierhousingcode2:WhentestedpertherequirementsofIEC60770-1fieldwithgeneralapplicationorpipelinewithlowvibrationlevel(10-60Hz0.15mmdisplacement/60-500Hz2g)

Mounting Position EffectsRotation in diaphragm plane has no effect.Tiltingupto90degreewillcausezeroshiftupto0.4kPa(1.6inH2O)whichcanbecorrectedbythezeroadjustment.

Response TimeSignal Capsule HART Fieldbus*1 Modbus

Differential Pressure

L 230 ms 300 ms 230 msM,H 200 ms 300 ms 200 ms

Static Pressure L,M,H 200 ms 300 ms 200 ms

Whenamplifierdampingissettozeroandincludingdead time.

*1: Output from transducer block.

FUNCTIONALSPECIFICATIONSOutputspecificationsforHARTProtocolType

Output Dual output (Both analog and pulse/contact outputs can be obtained simultaneously. See “Wiring Example for Analog Output and Status/Pulse Output”).

HART Protocol RevisionHARTprotocolrevisioncanbeselectedfrom5or7when ordering.The protocol revision can be changed by user configuration.TheHARTprotocolrevisionatthetimeofshipmentis shown by the last number at the serial number column of the name plate.Analog OutputTwo wire 4 to 20 mA DC output, user-selectable for Differential Pressure, Static Pressure, External Temperature or Flow Rate signal.Output range: 3.8 mA to 21.6 mA.DigitalHARTFSKprotocolaresuperimposedonthe4 to 20 mA signal.Failure Alarm AnalogoutputstatusatCPUfailureandhardwareerror;Up-scale:110%,21.6mADCormore(standard)Down-scale:−2.5%,3.6mADCorless

Analog output status at process abnormality (Option code/DG6);

The result of process abnormality detected by the advanceddiagnosticfunctioncanbereflectedtoan analog alert status. The following three setting modes are available.

ModeBurnout Fall back Off

Standard 110%,21.6mA or more Holdstoa

specifiedvaluewithin the

output range from 3.8mA to

21.6mA

Normal output Option Code

/C1 -1.25%, 3.8mA or less

/C2 -1.25%, 3.8mA or less

/C3 103.1%,20.5mA or more

Pulse/Contact OutputPulse or status output is selected by parameter setting.Transistorcontactoutput(sinktype).Contactrating:10.5to30VDC,120mADCmax.Lowlevel:0to2VDC.(Seefigurebelowforhighandlowlevels(pulseoutput).)

High level

Low level0 to 2 V

0VF01E.ai

Pulse OutputScaledpulseorfrequencypulseoutputisselectableby parameter setting.•Scaled Pulse Output FunctionPulseisoutputbytheunitofthescaledflowrate.Scaledpulsecanbetotalized.

•FrequencyOutputFunctionNumberofpulsesoutputpersecondat100%ofoutput.Pulsefrequency:Max.10kHzDutycycles:Approx.50%(1:2to2:1)

Contact Output FunctionHighorlowalarmStatus signal output mode can be reversed (ON/OFF).

Sep. 30, 2013-00

Page 4: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

4

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

Signal Output

Output Flow rate*1

Differential pressure

Static pressure

External temperature

Total flow*1

4-20mA *3 *2 Pulse output

High/Lowalarm

*1: WhenMeasurementfunctioncodeBisspecified.*2: Squarerootoutputisnotavailable.Lowcutlinear

mode is not supported.*3: Reversed output is not available.

OutputspecificationsforFOUNDATION Fieldbus Protocol Type

OutputDigital communication signal based on the FOUNDATIONfieldbusspecification.

FunctionalSpecificationsFunctionalspecificationsforFieldbuscommunicationconformtothestandardspecification(H1)ofFOUNDATIONfieldbus.

Function Block

Block name Number Execution

time Note

AI 5 30 ms Forflow,differentialpressure,static pressure, external temperature and capsule or amplifiertemperature.

SC 1 30 ms An output of Signal characterizerblockisanonlinear function of the respective input. The function is determined by a table.

IT 1 30 ms Integrator block intergrates a variable as a function of the time of accumulates the counts.

IS 1 30 ms Input Selector block provides selection of up to eight inputs and generate an output basedontheconfiguredaction.

AR 1 30 ms Arithmetic block allows simple use of popular measurement math functions.

PID 1 45 ms Applicablewhen/LC1optionisspecified.

LMFunctionLMfunctionissupported.

OutputspecificationsforModbusProtocolType

Item DescriptionCommunication protocol

2-wire half duplex RS-485 Modbus

Flow control NoneBaud rate 1200, 4800, 9600*, 19200Start bit 1bit(Fixed)Stop bit 1 bit*, 2 bitsParity bit Odd, Even, None*Transfer mode RTU(RemoteTerminalUnit)

Data length: 8 bitsLSB(Leastsignificantbitsentfirst)

Slave address 1* to 247

Item DescriptionSupport function 1: Read Coils

2: Read Discrete Inputs3:ReadHoldingRegisters4: Read Input Register5: Write Single Coil8:Diagnostic(00:ReturnQueryData)16: Write Multiple registers43:ReaddeviceIdentification

Bus termination Standard RS-485 bus terminationON(busend),OFF*(notbusend)

*: Factory default setting

Advanced Diagnostics (option for HART and FOUNDATION Fieldbus protocol types)

•ImpulselineblockagedetectionThe impulse line condition can be calculated and detectedbyextractingthefluctuationcomponentfrom the differential pressure and static pressure signals. Also EJX910A detects the impulse line abnormality particularly which side of impulse line is plugged.

•HeattracemonitoringThechangeoftheflangetemperaturecalculatedby using the two temperature sensors built in the EJX910A enables to detect the heat trace breakage or the abnormal temperature due to the failure.

Damping Time Constant (1st order)Amplifierdampingtimeconstantisadjustablefrom0.00 to 100.00 seconds and added to response time, applicableindependentlyfor“DP,SP,ET,andflow”forHART,FOUNDATIONfieldbusand“DP,SP,andET”for Modbus.

Update Period

Signal HART Fieldbus ModbusFlow rate 100 ms 200 ms Differential pressure 100 ms 200 ms 100 msStatic pressure 100 ms 200 ms 100 msExternal temperature 400 ms 800 ms 400 msTotalflow 1000 ms *

*: Output from IT function block.ZeroAdjustmentLimits

Zero can be fully elevated or suppressed, within the lower and upper range limits of the capsule, applicable for DP, SP, and ET independently.

External Zero AdjustmentExternalzeroforDPiscontinuouslyadjustablewith0.01%incrementalresolutionofspan.

IntegralIndicator(LCD)5-digit(Flow,DP,SP,andET)or6-digit(Totalflow)numerical display, 6-digit unit display and bar graph.Theindicatorisconfigurabletodisplayoneoruptofour variables periodically.For FOUNDATION Fieldbus, the indicator is configurabletodisplayupto10functionblockoutputvalues.ForModbus,theindicatorisconfigurabletodisplayupto16outputvaluesincludingRTUoutput.

BurstPressureLimits69MPa(10000psi)

Feb. 28, 2014-00

Page 5: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

5<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

Self DiagnosticsCPUfailure,hardwarefailure,configurationerror,process alarm for differential pressure, static pressure and external temperature.

SILCertificationEJX series transmitters except FOUNDATION Fieldbus andModbusprotocoltypesarecertifiedbyTÜVincompliancewiththefollowingstandards;IEC61508:2010;Part1toPart7Functional Safety of electrical/electronic/programmableelectronicsafety-relatedsystems;SIL2capabilityforsingletransmitteruse,SIL3capabilityfor dual transmitter use.

Functions Applicable for HART Protocol Revision 7•Longtagsupportingupto32charactersLongtagsecuresabetterassetmanagementwithabundant digits in its software.

•EnhancedburstmodeandeventnotificationAdvanced burst mode includes the variety of transmission setting by specifying burst variables, update period, and message trigger mode, and eventnotificationfunctiongivesyoualertsignalbased on the status change in preset values and self-diagnosis.

•SquawkIdentifying the transmitter by displaying the particularpatternonLCD

•MultidropcommunicationUpto63transmitterscanbeconnected.Ananalogsignal output available for one device in a loop.

Functions Applicable for Modbus Protocol•Processdatadiagnosis

The process data status is provided for each measured differential pressure, static pressure and process temperature. Also device status parameter is available for detail diagnosis.

•Longtagsupportingupto32charactersLongtagsecuresabetterassetmanagementwithabundant digits.

•SquawkIdentifying the transmitter by displaying the particularpatternonLCD.

•Multi-dropcommunicationUpto32transmitterscanbeconnected.

Mass Flow Calculation(ForMeasurementfunctioncodeBofHARTandFOUNDATIONFieldbusprotocoltypes)

AutoCompensationMode(FSA120FlowNavigatorisrequiredforconfiguration)Configurationofthefluidphysicalpropertiesandprimary element for the EJX900 series can be performed using a dialog window of FSA120.Allflowfactorsformassflowcalculationaredynamically compensated to an optimum value.InAutomode,massflowcanbemeasuredwithhighaccuracy.Theflowfactorsthatareautomaticallycompensatedaredischargecoefficient,diameterofprimarydevice,upstream internal pipe diameter, gas expansion factor, density, and viscosity.

Dec. 27, 2017-00

Supported primary devices are different by output signal type. HART7protocoltype:Orifice,Nozzle,Venturi,Multiport Averaging Pitot and Cone metersHART5andFOUNDATION Fieldbus protocol types: Orifice,Nozzle,Venturi

FlowNavigator:FSA120FlowConfigurationSoftware(refertoGS01C25R51-01EN).ThesoftwarepackageisusedtoperformmassflowconfigurationfortheEJX910A.Thesesoftwarecan also read and write the general parameters of HARTcommunicationsorFOUNDATION Fieldbus communication.Configurationofthefluidphysicalproperties and the primary element of the EJX900 series can be done by means of a dialog menu.

BasicFlowCalculationModeFlow operation and density compensation are performedconventionally,withtheflowfactorsbeinginput manually.Theoperationalexpressionisswitchedbythefluidtype and the unit setting.Density compensation by phase:

Gas: Compensation as ideal gas by temperature and pressure.

Liquid:Compensationbytemperature.Flow unit categories: See Table 1.

Table 1. Flow Operational Expression

T01E.ai

Flow unit Category

Qm, Qv or Qv_norm *1

= Kfactor

Flow equationFluid type

Mass FlowNormal·StandardVolume Flow

LiquidNormal·StandardVolume FlowVolume Flow

Mass Flow

Qm or Qv_norm *1

= Kfactor

Qv = Kfactor *1Volume Flow

Gas

*1: : User setting parameter

× ∆P×Tb/T×SP/SPb

× ∆P×(1+Temp K1×(T–Tb))

× ∆P×T/Tb×SPb/SP

Table 2. Symbol

Symbol DescriptionQm Mass FlowQv VolumeFlowQv_norm Normal·StandardVolumeFlowKfactor BasicflowCalculationfactor∆P DifferentialPressure(TransmitterSettingunit)Tb Reference temperature unit: KT Temperature unit: KSPb Reference static pressure unit: kPa absSP Static Pressure unit: kPa absTemp K1 The density rate of change per temperature

1degC of a density base value (value which set100%to1)ForVolumeFlow:Set0

Page 6: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

6

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

NORMALOPERATINGCONDITION(Optional features or approval codes may affect limits.)

AmbientTemperatureLimits–40to85°C(–40to185°F)–30to80°C(–22to176°F)withLCDdisplay

ProcessTemperatureLimits–40to120°C(–40to248°F)

AmbientHumidityLimits0to100%RH

WorkingPressureLimits(Siliconeoil)MaximumPressureLimits

LCapsule 16MPa(2300psi)MandHCapsule 25MPa(3600psi)

MinimumPressureLimitSeefigurebelow.

Atmosphericpressure

-40(-40)

0(32)

40(104)

80(176)

120(248)

1(0.14)

2.7(0.38)

10(1.4)

(psi abs)

100(14.5)

Process temperature °C (°F)

WorkingpressurekPa abs

Applicable range

F02E.ai

Figure 1. Working Pressure and Process Temperature

Supply&LoadRequirements(forHARTprotocoltype)(Optional features or safety approvals may affect electricalrequirements.)With24VDCsupply,uptoa570Ωloadcanbeused.Seefigurebelow.

E-10.5 0.0244

(Ω)

Power supply voltage E (V DC)

600

250

R

10.5 16.6 25.2 42

Externalloadresistance

DigitalCommunication

range(HART)

R=

F03E.ai

Figure 2. Relationship Between Power Supply VoltageandExternalLoadResistance

Mar. 11, 2019-00

Supply Voltage [forHART]10.5to42VDCforgeneraluseandflameprooftype.10.5to32VDCforlightningprotector(Optioncode

/A).10.5to30VDCforintrinsicallysafe,typenor

nonincendive.Minimumvoltagelimitedat16.6VDCforHART

communication.[for FOUNDATIONfieldbus]9to32VDCforgeneraluse,flameprooftype,Typen

or nonincendive.[for Modbus]9to30VDC250mWforgeneraluseandflameproof

type,quiescentsupplycurrent10mAtypicalLoad(forHARTprotocoltype)0to1335Ωforoperation250to600Ωfordigitalcommunication

FOUNDATION FieldbusCommunicationRequirementsSupplyVoltage:9to32VDCCurrent draw :Steadystate15mA(max)Softwaredownloadstate24mA(max)

EMC Conformity StandardsEN61326-1 Class A, Table2EN61326-2-3EN61326-2-5(forfieldbus)

EuropeanPressureEquipmentDirective 2014/68/EUSoundEngineeringPractice(forallcapsules)

Withoptioncode/PE3(forMandHcapsules)

CategoryIII,ModuleH,TypeofEquipment:PressureAccessory-Vessel,typeofFluid:LiquidandGas,Groupoffluid:1and2

EU RoHS DirectiveEN 50581

SafetyRequirementStandardsEN61010-1, EN61010-2-030C22.2 No.61010-1, C22.2 No.61010-2-030• Installationcategory:I

(Anticipatedtransientovervoltage330V)• Pollutiondegree:2• Indoor/Outdooruse

Page 7: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

7<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

PHYSICALSPECIFICATIONSWetted Parts Materials Diaphragm,coverflange,processconnector,

capsule gasket, and vent/drain plugSee“MODELANDSUFFIXCODES.”

Process connector gasketPTFETeflonFluorinated rubber for option code N2 and N3

Non-wetted Parts Materials BoltsB7carbonsteel,316LSSTor660SST

Housing • Lowcoppercastaluminumalloy• ASTMCF-8MStainlesssteel(optional)

Coating of housing[for aluminum housing]Polyester resin powder coating Mint-green paint (Munsell 5.6BG 3.3/2.9 or its equivalent)[foroptioncode/Por/X2]Epoxy and polyurethane resin solvent coating

Degrees of protectionIP66/IP67, Type 4X

Cover O-ringsBuna-N,fluoro-rubber(optional)

Name plate and tag316 SST

FillfluidSiliconeoil,fluorinatedoil(optional)

Cable for RTDExternal Temperature Input Code -1, -2, -3, -4

Oil-proof and a heat-resistant cable with a shieldOutsidediameter:8.5mm(0.335inch),Voltagerating:300VTemperaturerating:–40to105°C(–40to221°F)Frameresistance:UL(CSA)VW-1Adaptationstandard:UL(CSA)AWMSTYLE2517

External Temperature Input Code -B,-C,-DA heat-resistant FEP cable with a shieldOutsidediameter:4.3mm(0.168inch)Voltagerating:300VTemperaturerating:–80to200°C(–112to392°F)Flame resistance: NEC Article 800-CMPAdaptationstandard:NECArticle725-PLTC

Note for using an extension cable: When extending a temperature cable with using an extension cable and a junction box, total cable length including the original external temperature cablemustbelessthan25m.UsePEorXLPEinsulated cable for extension.

Cable gland:Nickel plating brass

Weight2.8kg(6.2lb)withoutintegralindicator,mountingbracket, process connector and RTD cable.Add1.5kg(3.3lb)forAmplifierhousingcode2.

ConnectionsSee“MODELANDSUFFIXCODES.”Processconnectionofcoverflange:IEC61518

Mar. 11, 2019-00

Page 8: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

8

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

MODELANDSUFFIXCODESModel SuffixCodes Description

EJX910A . . . . . . . . . . . . . . . . . . . . . . . . . . Multivariable transmitterOutput signal

-E . . . . . . . . . . . . . . . . . . . . . . . .-J . . . . . . . . . . . . . . . . . . . . . . . .-F . . . . . . . . . . . . . . . . . . . . . . . .-M . . . . . . . . . . . . . . . . . . . . . . . .

4to20mADCwithdigitalcommunication(HARTprotocol)*84to20mADCwithdigitalcommunication(HART5/HART7protocol)*9Digital communication (FOUNDATIONfieldbusprotocol)Digitalcommunication(RS485Modbusprotocol)When Output signal code -M is selected, option code A must also be selected.

Measurementspan(capsule)

L . . . . . . . . . . . . . . . . . . . . . . .M . . . . . . . . . . . . . . . . . . . . . .H. . . . . . . . . . . . . . . . . . . . . . .

0.1to10kPa(0.4to40inH2O)0.5to100kPa(2to400inH2O)2.5to500kPa(10to2000inH2O)

Wetted partsmaterial *1

S. . . . . . . . . . . . . . . . . . . . . See Table 5.

Process connections

0 . . . . . . . . . . . . . . . . . . .1 . . . . . . . . . . . . . . . . . . .2 . . . . . . . . . . . . . . . . . . .3 . . . . . . . . . . . . . . . . . . .4 . . . . . . . . . . . . . . . . . . .5 . . . . . . . . . . . . . . . . . . .

withoutprocessconnector(Rc1/4femaleonthecoverflanges)with Rc1/4 female process connectorwith Rc1/2 female process connectorwith 1/4 NPT female process connectorwith 1/2 NPT female process connectorwithoutprocessconnector(1/4NPTfemaleonthecoverflanges)

Bolts and nuts materia J . . . . . . . . . . . . . . . . .G. . . . . . . . . . . . . . . . .C. . . . . . . . . . . . . . . . .

B7 carbon steel316LSST660 SST

Installation

-7 . . . . . . . . . . . . . .-8 . . . . . . . . . . . . . .-9 . . . . . . . . . . . . . .-B . . . . . . . . . . . . . .

Verticalpiping,leftsidehighpressure,andprocessconnectiondownsideHorizontalpipingandrightsidehighpressureHorizontalpipingandleftsidehighpressureBottom Process Connection, left side high pressure

Amplifierhousing 1 . . . . . . . . . . . . .2 . . . . . . . . . . . . .

Cast aluminum alloyASTM CF-8M stainless steel

Electrical connection F . . . . . . . . . . .2 . . . . . . . . . . .4 . . . . . . . . . . .5 . . . . . . . . . . .7 . . . . . . . . . . .9 . . . . . . . . . . .A. . . . . . . . . . .C. . . . . . . . . . .D. . . . . . . . . . .

G1/2female,twoelectricalconnections(OneconnectionforRTD)1/2NPTfemale,twoelectricalconnections(OneconnectionforRTD)M20female,twoelectricalconnections(OneconnectionforRTD)G 1/2 female, two electrical connections and blind plug *2*6*7

1/2NPT female, two electrical connections and a blind plug *2*6*7

M20 female, two electrical connections and a blind plug *2*6*7

G 1/2 female, two electrical connections and a 316 SST blind plug *21/2 NPT female, two electrical connections and a 316 SST blind plug *2

M20 female, two electrical connections and a 316 SST blind plug *2

Integral indicator

D. . . . . . . . .N. . . . . . . . .

Digital indicatorNone

Mounting bracket

B. . . . . . .D. . . . . . .J . . . . . . .K. . . . . . .M . . . . . .N. . . . . . .

304SST2-inchpipemounting,flattype(forhorizontalpiping)304SSTorSCS13A2-inchpipemounting,Ltype(forverticalpiping)316SST2-inchpipemounting,flattype(forhorizontalpiping)316SSTorSCS14A2-inchpipemounting,Ltype(forverticalpiping)316SSTorSCS14A2-inchpipemounting(forbottomprocessconnectiontype)None

External temperature input -0 . . . .-1 . . . .-2 . . . .-3 . . . .-4 . . . .-B . . . .-C . . . .-D . . . .

Fixedtemperature(withoutcable)*5RTDinputwith0.5m(1.64ft)ofshieldedcableandtwocableglands*3 *7 *10

RTDinputwith4m(13.1ft)ofshieldedcableandtwocableglands*3 *7 *10

RTDinputwith7.5m(24.6ft)ofshieldedcableandtwocableglands*3 *7 *10

RTDinputwith25m(81ft)ofshieldedcableandtwocableglands*3 *7 *10

RTDinputwith4m(13.1ft)ofshieldedcablewithoutcablegland*3 *4

RTDinputwith7.5m(24.6ft)ofshieldedcablewithoutcablegland*3 *4

RTDinputwith25m(81ft)ofshieldedcablewithoutcablegland *3 *4

Measurement function

A. . .B. . .

MultiSensing(DP,PandT)MassFlowMeasurement(Flow,DP,PandT)(ApplicableforOutputsignalcodes-E,-J,and-F).

Option codes /Optionalspecification

The“”marksindicatethemosttypicalselectionforeachspecification.*1: Usersmustconsiderthecharacteristicsofselectedwettedpartsmaterialandtheinfluenceofprocessfluids.Theuseof

inappropriatematerialscanresultintheleakageofcorrosiveprocessfluidsandcauseinjurytopersonneland/ordamageto plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm andthefillfluidcancontaminatetheuser’sprocessfluids.

Beverycarefulwithhighlycorrosiveprocessfluidssuchashydrochloricacid,sulfuricacid,hydrogensulfide,sodiumhypochlorite,andhigh-temperaturesteam(150°C[302°F]orabove).ContactYokogawafordetailedinformationofthewetted parts material.

*2: ForExternaltemperatureinputcode0(Fixedtemperature).*3: Recommended External Temperature Input Cable is as shown in Table 4. RTD is not provided.*4: Specify when using conduit for RTD connection.*5: Preset external temperature value is used for density compensation.*6: Material of a blind plug is aluminum alloy or 304 SST.

Nov. 20, 2019-00

Page 9: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

9<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

*7: NotapplicableforAmplifierhousingcode2.*8: OutputsignalcodeE:HART5.*9: OutputsignalcodeJ:HART5orHART7selectable.SpecifyHART5orHART7whenordering.(OutputsignalcodeJis

recommendedforHARTcommunication.)*10: Refer to table 6 whether the cable glands are attached or not.

Selection guide for HART 5 and HART 7SelectHART5orHART7asfollow.

Output signal code

Specifieditemwhenordering"HART protocol revision"

HART protocol revision

Selection guideNoteRequirementforHART7

function Other conditions

-E Not Available

HART5 NO

Not available to switch toHART7protocolafterdelivery.

*

-J

Specify '5' AvailabletoswitchtoHART7 protocol after delivery by user-configuration.

**

Specify '7' HART7

YESInthiscase,besuretoconfirmthatHARTconfigurationtoolsupportsHART7byTable3.

AvailabletoswitchtoHART5 protocol after delivery by user-configuration.

*: Thiscodewillbeunifiedtothenewcode“-J”.Thereforethecode“-J”isrecommendedforHARTcommunicationtype.**: IndicatethemosttypicalselectionforHARTcommunication.SelectthiswhenHART7functionalityisnotrequired.Incase

ofselectingHART7withoutconformingtoTable3,communicationwillnotbeavailable.

HART protocol revision and communicationProtocolrevisionsupportedbyHARTconfigurationtoolmustbethesameorhigherthanthatoftheEJXmultivariable transmitter. HART7communicationissupportedbyFieldMateR2.02orlater.

Table 3. HART protocol revision and communication

Protocol revision supportedbyHARTconfigurationtool

HART 5 HART 7

ProtocolrevisionofEJXmultivariable transmitter

HART 5 CommunicationAvailable

CommunicationAvailable

HART 7 CommunicationNot Available

CommunicationAvailable

Applicable External Temperature CableTable 4.

External Temperature Input Code -1, -2, -3, -4 -B, -C, -DGeneral Application

FactoryMutual(FM)Explosionproof Approval

Intrinsically Safe Approval Nonincendive

ATEXFlameproof Approval

Intrinsically Safe Approval

CanadianStandardsAssociation(CSA) Explosionproof Approval

IECEx Scheme Flameproof Approval

Wetted Parts MaterialsTable 5.

Wetted parts material code

Coverflangeandprocess connector Capsule Capsule

gasket Vent/Drain plug

S # ASTM CF-8M *1 HastelloyC-276*2(Diaphragm)F316LSST,316LSST(Others)

Teflon-coated316LSST 316 SST

*1: Castversionof316SST.EquivalenttoSCS14A.*2: HastelloyC-276orASTMN10276.The‘#’marksindicatetheconstructionmaterialsconformtoNACEmaterialrecommendationsperMR0175/ISO15156.Please refer to the latest standards for details. Selected materials also conform to NACE MR0103.

Nov. 20, 2019-00

Page 10: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

10

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

AttachedCableglandsforEJX910AandEJX930ATable 6.

Flameproof approval Intrinsically safe approvalGeneral

ApplicationFMCSA ATEX IECEx

SchemeNEPSI

KOSHAINMETRO

FM ATEXNEPSI

KOSHAINMETRO

External Temperature

Input

-0 No No No No No NoN/A

No-1, -2, -3, -4 N/A Yes Yes No N/A Yes Yes-B, -C, -D No N/A No No No N/A No

Yes: Attached No: Not attached N/A: Not applicable

OPTIONALSPECIFICATIONS(ForExplosionProtected)Item Description Code

Factory Mutual(FM)

FM Explosionproof Approval *4Applicable Standard: FM3600:2018, FM3615:2018, FM3810:2018, NEMA 250:2003,

ANSI/UL61010-1:2012,ANSI/UL61010-2-30:2012Explosionproof for Class I, Division 1, Groups B, C and D, Dust-ignitionproof for Class II/III, Division 1,GroupsE,FandG,inHazardouslocations,indoorsandoutdoors(Enclosure:Type4X)“FACTORYSEALED,CONDUITSEALNOTREQUIRED.”Temperatureclass:T6,Amb.Temp.:–40to60°C(–40to140°F)

FF1

FM Intrinsically Safe and Nonincendive Approval *1 *3 *4

Applicable Standard: FM 3600:2011, FM 3610:2010, FM 3611:2004, FM 3810:2005, ANSI/ISA-60079-0-2009, ANSI/ISA-60079-11-2009, ANSI/ISA-60079-27-2006, ANSI/ISA-61010-1-2004, NEMA 250:1991

Intrinsically Safe for Class I,II, & III, Division 1, Groups A,B,C,D,F & G, Entity, FISCO.Class I, Zone 0, AEx ia IIC,Enclosure:Type4X,Temp.Class:T4,Amb.Temp.:–40to60°C(–40to140°F).Intrinsically Apparatus Parameters:[FISCO(IIC)]Ui=17.5V,Ii=380mA,Pi=5.32W,Ci=3.52nF,Li=0μH[FISCO(IIB)]Ui=17.5V,Ii=460mA,Pi=5.32W,Ci=3.52nF,Li=0μH[Entity]Ui=24V,Ii=250mA,Pi=1.2W,Ci=3.52nF,Li=0μHSensorCircuit:Uo=6.51V,Io=4mA,Po=6mW,Co=34μF,Lo=500mHNonincendive for Class I, Division 2, Groups A, B, C and D, NIFW, FNICOClass I, Zone 2, Group IIC, NIFW, FNICOClass II, Division 2, Groups F&G, and Class III, Division 1Enclosure:Type4X,Temp.Class:T4,Amb.Temp.:–40to60°C(–40to140°F)NonincendiveApparatusParameters:Vmax.=32V,Ci=1.76nF,Li=0μH

FS15

ATEX ATEX Flameproof Approval *4Applicable Standard: EN 60079-0:2012+A11:2013, EN 60079-1:2014, EN 60079-31:2014Certificate:KEMA07ATEX0109XII2G,2DExdIICT6...T4Gb(“ExdbIICT6...T4Gb”fromAugust1,2017),ExtbIIICT85°CDbDegree of protection: IP66/IP67Amb.Temp.(Tamb)forgas-proof:T4;–50to75°C(–58to167°F),T5;–50to80°C(–58to176°F),T6;–50to75°C(–58to167°F)ProcessTemp.forgas-proof(Tp):T4;–50to120°C(–58to248°F),T5;–50to100°C(–58to212°F),T6;–50to85°C(–58to185°F)Max.surfaceTemp.fordust-proof:T85°C(Tamb:–30to75°C,Tp:–30to85°C)*5

KF22

ATEX Intrinsically Safe Approval *1 *3 *4

Applicable Standards: EN 60079-0:2012+A11:2013, EN 60079-11:2012Certificate:KEMA06ATEX0278XII 1G, 2D Ex ia IIC/IIB T4 Ga Ex ia IIIC T85°C T100°C T120°C Db Type of protection: IP66/IP67Amb.Temp.forEPLGa:–40to60°C(–40to140°F)Amb.Temp.forEPLDb:–30to60°C*5Max.ProcessTemp.(Tp):120°C(248°F)Max.SurfaceTemp.forEPLDb.T85°C(Tp:80°C),T100°C(Tp:100°C),T120°C(Tp:120°C)AmbientHumidity:0to100%(Nocondensation)Electrical data:Supply/Outputcircuit(terminals+and–)[FISCO(IIC)]Ui=17.5V,Ii=380mA,Pi=5.32W,Ci=3.52nF,Li=0μH[FISCO(IIB)]Ui=17.5V,Ii=460mA,Pi=5.32W,Ci=3.52nF,Li=0μH[Entity]Ui=24V,Ii=250mA,Pi=1.2W,Ci=3.52nF,Li=0μHExternalTemperatureInputcircuit(connector)Uo=7.63V,Io=3.85mA,Po=0.008W,Co=4.8μF,Lo=100mH

KS26

Nov. 20, 2019-00

Page 11: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

11<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

Item Description CodeCanadianStandardsAssociation(CSA)

CSA Explosionproof Approval *4Certificate:2014354Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30,C22.2 No.94, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1, C22.2 No.61010-2-030Explosion-proof for Class I, Groups B, C and D.Dustignition-proof for Class II/III, Groups E, F and G.WheninstalledinDivision2,“SEALNOTREQUIRED”Enclosure:Type4X,Temp. Code: T6...T4Ex d IIC T6...T4 Enclosure: IP66 and IP67Max.ProcessTemp.:T4;120°C(248°F),T5;100°C(212°F),T6;85°C(185°F)Amb.Temp.:–50to75°C(–58to167°F)forT4,–50to80°C(–58to176°F)forT5,–50to75°C(–58to167°F)forT6*5

ProcessSealingCertificationDualSealCertifiedbyCSAtotherequirementofANSI/ISA12.27.01NoadditionalsealingrequiredPrimarysealfailureannunciation:atthezeroadjustmentscrew

CF1

IECExScheme

IECEx Flameproof Approval *4Applicable Standard: IEC 60079-0:2011, IEC60079-1:2007-4Certificate:IECExCSA07.0008Flameproof for Zone 1, Ex d IIC T6...T4 Gb Enclosure: IP66 and IP67Max.ProcessTemp.:T4;120°C(248°F),T5;100°C(212°F),T6;85°C(185°F)Amb.Temp.:–50to75°C(–58to167°F)forT4,–50to80°C(–58to176°F)forT5,–50to75°C(–58to167°F)forT6

SF2

ContactYokogawarepresentativeforthecodesindicatedas‘—’*1: Not Applicable for Output signal codes -E and -J.*2: Not Applicable for Output signal code -F.*3: Not Applicable for Output signal code -M.*4: Applicable for Electrical connection codes 2, 4, 7, 9, C, and D.*5: Lowerlimitofambienttemperatureis–15°C(5°F)whenoptioncodeHEisspecified.

OPTIONALSPECIFICATIONSItem Description Code

Painting Color change Amplifiercoveronly*20 PAmplifiercoverandterminalcover,Munsell7.5R4/14 PR

Coating change Anti-corrosion coating*1*20 X2316 SST exterior parts 316SSTzero-adjustmentscrewandsetscrews*15 HCFluoro-rubber O-ring AllO-ringsofamplifierhousing.Lowerlimitofambienttemperature:–15°C(5°F) HELightningprotector HARTprotocoltype:

Transmitterpowersupplyvoltage:10.5to32VDCAllowablecurrent:Max.6000A(1×40μs),Repeating1000A(1×40μs)100timesApplicable Standards: IEC 61000-4-4, IEC 61000-4-5

FOUNDATIONfieldbusprotocoltype:Allowablecurrent:Max.6000A(1×40μs),Repeating1000A(1×40μs)100timesApplicable Standards: IEC 61000-4-4, IEC 61000-4-5

Modbus protocol type:Applicable Standards: IEC 61000-4-5Thisoption(optioncodeA)mustbeselectedwhenModbusprotocoltype(Outputsignalcode-M)isselected.

A

Oil-prohibited use*2 Degrease cleansing treatment K1Degreasecleansingtreatmentwithfluorinatedoilfilledcapsule.Operatingtemperature−20to80°C(−4to176°F) K2

Oil-prohibited use with dehydrating treatment*2

Degrease cleansing and dehydrating treatment K5Degreasecleansinganddehydratingtreatmentwithfluorinatedoilfilledcapsule.Operatingtemperature−20to80°C(−4to176°F) K6

Capsulefillfluid FluorinatedoilfilledincapsuleOperatingtemperature−20to80°C(−4to176°F) K3

Calibration units*3 Pcalibration(psiunit)(SeeTableforSpanandRangeLimits.)

D1barcalibration(barunit) D3M calibration (kgf/cm2unit) D4

Plug option*22 Longvent*4Totallength:119mm(standard:34mm);Totallengthwhencombiningwithoption code K1,K2, K5, and K6: 130 mm. Material: 316 SST U1

Without vent and drain plugs UNGold-plated *2 Surface of isolating diaphragms are gold plated, effective for hydrogen permeation.

OverpressureeffectsforMandHcapsules:±0.06%ofURL A1

Nov. 20, 2019-00

Page 12: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

12

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

Item Description CodeOutput limits and failure operation*5

(forHARTprotocoltype)

Failurealarmdown-scale:OutputstatusatCPUfailureandhardwareerroris−2.5%,3.6mADC or less. C1

NAMURNE43CompliantOutput signal limits: 3.8 mA to 20.5 mA

Failurealarmdown-scale:OutputstatusatCPUfailureandhardwareerroris−2.5%,3.6mADCorless. C2

Failurealarmup-scale:OutputstatusatCPUfailureandhardwareerroris110%,21.6mAormore. C3

Body option*6

HL

TerminalSide

F04E.ai

Right side high pressure, without drain and vent plugs N1

N1 and Process connection, based on IEC61518 with female thread on both sides of cover flange,withblindkidneyflangesonback. N2

N2,andMaterialcertificateforcoverflange,diaphragm,capsulebody,andblindkidneyflange N3

Wired tag plate 316SSTtagplatewiredontotransmitter(TagNo.:Maximum.16characters.) N4Dataconfigurationatfactory*7

DataconfigurationforHARTcommunicationtype Software damping, Descriptor, Message CA

DataconfigurationforFieldbuscommunicationtype Software damping CC

DataconfigurationforModbuscommunicationtype Software damping, Descriptor, Message CE

PID function *13 (For FOUNDATIONFieldbusprotocoltype)PID control function LC1

Software downloadingfunction *13

(For FOUNDATIONFieldbusprotocoltype)Based on FOUNDATIONFieldbusSpecification(FF-883)Downloadclass:Class1 EE

Advanced diagnostics(ForHARTorFOUNDATION Fieldbusprotocoltype)

Multi-sensing process monitoring•Impulselineblockagedetection*16

•Heattracemonitoring

HARTprotocoltype DG6

FOUNDATION Fieldbus protocol type *17 DG1European Pressure EquipmentDirective*14

PED2014/68/EUCategoryIII,ModuleH,typeofequipment:Pressureaccessory-vessel,Tupeoffluid:LiquidandGas,Groupoffluid:1and2Lowerlimitofambientandprocesstemperature:−29°C

PE3

Materialcertificate*8 Coverflange*9 M01Coverflange,Processconnector*10 M11Coverflange,Diaphragm,Capsulebody*9*23 MA1Coverflange,Processconnector,Diaphragm,Capsulebody*10*23 MC1Coverflange,BoltandNutforcoverflange,Diaphragm,Capsulebody,VentandDrainplug, Ventscrew,Capsulegasket*9*21*22 MG1

Coverflange,Processconnector,Boltandnutforcoverflange,Boltforprocessconnector,Diaphragm,Capsulebody,VentandDrainplug,Ventscrew,Capsulegasket*10*21*22 MH1

Pressure test/Leaktestcertificate*11

TestPressure:16MPa(2300psi)*18 Nitrogen(N2)Gas*12

Retention time: one minuteT12

TestPressure:25MPa(3600psi)*19 T13*1: Not applicable with color or coating change option.*2: Applicable for Wetted parts material code S.*3: TheunitofMWP(Max.workingpressure)onthenameplateofahousingisthesameunitasspecifiedbyoptioncodesD1,

D3, and D4.*4: Applicableforverticalimpulsepipingtype(Installationcode7)andWettedpartsmaterialcodeS.*5: ApplicableforOutputsignalcodes-Eand-J.Thehardwareerrorindicatesfaultyamplifierorcapsule.*6: ApplicableforWettedpartsmaterialcodeS;Processconnectioncodes3,4,and5;Installationcode9;andMounting

bracketcodeN.Processconnectionfacesontheothersideofzeroadjustmentscrew.*7: Alsosee‘OrderingInformation’.*8: Materialtraceabilitycertification,perEN102043.1B.*9: Applicable for Process connections codes 0 and 5.*10: Applicable for Process connections codes 1, 2, 3, and 4.*11: TheunitonthecertificateisalwaysPaunitregardlessofselectionofoptioncodeD1,D3orD4.*12: Drynitrogengasisusedforoil-prohibiteduse(optioncodesK1,K2,K5,andK6).*13: Applicable for Output signal code -F.*14: ApplicableforMeasurementspancodesMandH.IfcompliancewithcategoryIIIisneeded,specifythiscode.*15: 316or316LSST.ThespecificationisincludedinAmplifiercode2.*16: Thechangeofpressurefluctuationismonitoredandthendetectstheimpulselineblockage.RefertoTI01C25A31-01Efor

detailedtechnicalinformationrequiredforusingthisfunction.*17: ThisoptioncodemustbespecifiedwithoptioncodeEE.*18: ApplicableforCapsulecodeL.*19: ApplicableforCapsulecodesMandH.*20: Notapplicablewithamplifierhousingcode2.*21: NotapplicablewithplugoptioncodeUN.*22: Not applicable with option code N1, N2 and N3. *23: ApplicableforoptioncodeUNandN1.

Nov. 20, 2019-00

Page 13: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

13<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

DIMENSIONSUnit:mm(approx.inch)

95(3

.74)

*4

242(9.53)175(6.89)129(5.08)97

(3.82)

223(

8.78

)

52(2

.05)

97(3

.82)

41 (1.6

1)

67(2

.64)

(for RTD)Conduit connectionIntegral indicator

(optional)

Zero adjustmentGround terminal(optional)

Mounting bracket(L-type,optional)

Process connector Conduit connection

110(4.33)

ø78(

3.07

)

ø70(

2.76

)

39(1.54)

12(0.47)

138(

5.43

)*2

54(2.13)

2-inch pipe(O.D. 60.5 mm)

Vent/Drain*5plugs

175(

6.89

)

145(

5.71

)12

4(4.

88)

47(1

.85)

95(3.74)*4

89(3.50)

115(4.53)

41(1.61)

110(4.33)12

(0.47)39

(1.54)

ø70

(2.7

6)12

9(5.

08)

ø78(

3.07

)

130(5.12)*3

67(2.64)

Drain plug*5

2-inch pipe(O.D. 60.5 mm)

Vent plug*5

Zeroadjustment

Ground terminal

Drain plug*5

Vent plug*5

Mounting bracket(Flat-type,optional)

Conduitconnection

(for RTD)Conduit connection

Integral indicator (optional)

(optional)

Processconnector

54(2.13)

Horizontal Impulse Piping Type (Installation code 9)

Vertical Impulse Piping Type (Installation code 7)

Highpressure side

Lowpressure side

Lowpressure side

Highpressure side

*1: When Installation code 8 is selected, high and low pressure side on above figure are reversed. (i.e. High pressure side is on the right side.)*2: When Option code K1, K2, K5, or K6 is selected, add 15 mm(0.59 inch) to the value in the figure.*3: When Option code K1, K2, K5, or K6 is selected, add 30 mm(1.18 inch) to the value in the figure.*4: When electrical connection code 7 or C is selected, a blind plug is protruded upto 8 mm(0.31 inch) from the conduit connection.*5: When option code /UN is specified, Vent/drain holes and plugs are not applicable.

Electrical connection code 2External temp. input code 1, 2, 3, and 4

Electrical connection code 4External temp. input code 1, 2, 3, and 4

Electrical connection code 9External temp. input code 0

Electrical connection code 2 and 4External temp. input code B, C, and D

Electrical connection code 2External temp. input code 1, 2, 3, and 4

Electrical connection code 9External temp. input code 0

Electrical connection code 4External temp. input code 1, 2, 3, and 4

Electrical connection code 2 and 4External temp. input code B, C, and D

6 (0.2

4)

105(

4.13

)

58(2

.28)

54(2

.13)

69(2

.72)

116(

4.57

)

48(1

.89)

54(2.13)6

(0.24)

105(4.13)58(2.28)

48(1.89)

Cable Gland

Cable Gland

Cable Gland

69(2.72)116(4.57)

Cable Gland

F05E.ai

41.3

(1.6

3)

Nov. 20, 2019-00

Page 14: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

14

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

Unit:mm(approx.inch)

12 (0.47)

39(1.54)

129 (5.08)

Groundterminal

ø78(

3.07

)

ø70

(2.7

6)

130*2

(5.12)

54 (2.13)

188(7.40)

109

(4.2

9)

Lowpressure side

Highpressure side

110 (4.33)

Vent plug*4

Process connector(optional)

Conduitconnection

Mountingbracket*1

(optional)

95(3.74)*3

159(

6.26

)

73(2.87)

Conduitconnection(for RTD)

2-inch pipe (O.D. 60.5 mm)

Integral indicator(optional)

60(2

.36)

Bottom Process Connection Type (Installation code B)

Electrical connection code 2External temp. input code 1, 2, 3, and 4

Electrical connection code 9External temp. input code 0

Electrical connection code 4External temp. input code 1, 2, 3, and 4

Electrical connection code 2 and 4External temp. input code B, C, and D

54(2.13)6

(0.24)

48(1.89)

105(4.13)58(2.28)

Cable Gland

69(2.72)116(4.57)

Cable Gland

Zeroadjustment

*1: AtransmitterwithSSThousingisnotapplicableformountingtohorizontal2-inchpipe.*2: WhenOptioncodeK1,K2,K5,orK6isselected,add30mm(1.18inch)tothevalueinthefigure.*3: Whenelectricalconnectioncode7orCisselected,ablindplugisprotrudedupto8mm(0.31inch)fromtheconduit

connection.*4: Whenoptioncode/UNisspecified,ventholesandplugsarenotapplicable.

F06.ai

AB

SUPPLY

CHECK

PULSE

+– Power supply and output terminals

External indicator (ammeter) terminals *1*2

Pulse or status contact output terminals *2

*1: When using an external indicator or check meter, the internal resistance must be 10Ω or less.*2: Not available for FOUNDATION Fieldbus communication type.

+–+–

Terminal Wiring (HART and FOUNDATION Fieldbus protocol types)

RTD cable connection

Ground terminal

12

23

24

SUPPLY

MODBUS

+– Power supply terminals

Modbus communication (RS-485) terminals

Terminal Wiring (Modbus protocol type)

Ground terminal

12

43

Terminal Configuration

1Terminal 2Terminal

3Terminal

4Terminal

Nov. 20, 2019-00

Page 15: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

15<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

WiringExampleforAnalogOutputandStatus/PulseOutput(forHARTProtocoltype)

250Ω

R +

–BPULSE

SUPPLY

EJX910A Electrical Terminal

Recorder or other instrument

This supply voltage requires a power sourse with a maximum output current of no less than E/R+25mA.

Electric counter

E(16.4 to 30V DC)

Counting input

Common

+

B

EJX910A Electrical Terminal

250Ω

24V DC

PULSE

SUPPLY+

Distributor

+–

BPULSE

SUPPLY

R

E

EJX910A Electrical Terminal Use the Three-wire shielded cable.

Use the Three-wire shielded cable.

Electric counter*1

*1

*1

*1

*2

*2

*2

*2

*1: To avoid the influence of external noise, use an electric counter which fits to the pulse frequency.*2: Resistor is not necessary in case of an electric counter which can receive contact pulse signal directly.*3: When using analog and pulse output simultaneously, the HART communication may be influenced by noise comparing analog output only. Take countermeasure for noise shown above, e.g. use shield cable etc.

Shielded Cable

Shielded Cable

PULSE

SUPPLY +–

BMognetic

valve

AC power supply

External Power supply 30V DC, 120mA max(Contact Rating)

EJX910A Electrical Terminal

E

250Ω

R+

–BPULSE

SUPPLY

Counting inputCommon

For the shielded cables in this example of flowmeter installation, use two-wire separately shielded cables.This supply voltage requires a power sourse with a maximum output current of no less than E/R+25mA.

Recorder or other instrument

Electric counter

E(16.4 to 30V DC)

Shielded Cable

The supply voltage requires output impedance no more than 1/1000 of R (load resistance).EJX910A Electrical Terminal

250ΩRE(10.5 to 30V DC) Counting inputCommon

24V DC

PULSE

SUPPLY

For the shielded cables in this example of flowmeter installation, use two-wire separately shielded cables.

This supply voltage requires a power sourse with a maximum output current of no less than E/R.

Distributor (or communication medium : ex. EP card)

(or communication medium : ex. EP card)Electric counter

+–

B

Shielded Cable

EJX910A Electrical Terminal

When analog and pulse output are used, the length of communication line is subjected to wiring conditions. Refer to example 1 to 3.

Relay

*1: Either B or +*1

*1: Either B or +

*1

*1: Either B or +

*1: Either B or +

*1: Either B or +

*1: Either B or +

*1

*1

*1

*1

Analog Output

Pulse Output

Status Output

Simultaneous Analog

-Pulse Output *3

DescriptionConnection

F07E.ai

0.1 C ( µF ) × f ( kHz )

≤ R (kΩ) ≤120

E (V)

The load resistance of pulse output should be used to 1kΩ, 2W.If no translation of the pulse output possible by the cable length or the frequency of the pluse output,the load resistance should be selected by calculation as shown below.

Example of CEV cable capacitance 0.1µF/km

WhereE = Supply voltage (V) f = Frequency of pulse output (kHz)R = Value of load resistance (kΩ)

C = Cable capacitance (µF) P = Power ratio of the load resistance (mW)

P (mW) =R (kΩ)E2 (V)

Example 3In this case, No communi-cation is possible (when shielded cable is not used).

The range of load resistance R for the pulse output.

Example 1In this case, Communica-tion is possible(up to adistance of 2km when aCEV cable is used).

Example 2In this case, Communica-tion is possible (up to adistance of 200m when a CEV cable is used) and R = 1kΩ).

In this case, Communication is possible (up to a distance of 2km when a CEV cable is used.)

In this case, No communication is possible.

In this case, No communication is possible.

Feb. 28, 2014-00

Page 16: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

16

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

< Ordering Information for HART protocol type >Specify the following when ordering.1. Model,suffixcodes,andoptioncodes2. Calibration range and units

1)Calibrationrangecanbespecifiedwithrangevaluespecificationsupto5digits(excludinganydecimalpoint)for low or high range limits within the range of –32000 to 32000.

Whenreverserangeisdesignated,specifyLowerRangeValue(LRV)asgreaterthanUpperRangeValue(URV).

2)Specifyunitfromthetables“CalibrationUnitsforHARTprotocoltype”3. Static pressure is selected from gauge pressure or absolute pressure.4. TAGNO(ifrequired) Specifiedcharacters(upto22characters,or16characterswhen/N4isspecified)areengravedonthestainless

steeltagplatefixedontheterminalbox.5. SOFTWARETAG(ifrequired) Specifiedcharacters*1aresetas“Tag”(thefirst8characters)and“Longtag”*2(32characters)intheamplifier

memory. Whenthe“SOFTWARETAG”isnotspecified,specified“TAGNO”issetas“Tag”(thefirst8characters)and“Long

tag”*2(22characters)intheamplifiermemory.*1: Outputsignalcode“E”(HART5):upto8charactersarespecified Outputsignalcode“J”(HART5/HART7):upto32charactersarespecified*2: ApplicableonlyforHART7

6. Otherfactoryconfigurations(ifrequired) SpecifyingoptioncodeCAwillallowfurtherconfigurationatfactory. Followingareconfigurableitemsandsettingrange.

1)Descriptor(upto16characters)2)Message(upto30characters)3)Softwaredampinginsecond(0.00to100.00)

7. Whentheoutputsignalcodeis“J”,specifytheHARTprotocolrevision“5”or“7”.

Table 11. Factory Setting for HART protocol type

Parameter Default value DescriptionTag number AsspecifiedinorderFlow unit kg/h ValidwhenMeasurementFunctionCodeBisspecified.

StandardflowconfigurationFluid: N2Primaryelementtype:ISO5167-11991OrificeCornerTapsUpstreaminternalpipediameter=0.0527m(CarbonSteel)Diameterofprimarydevice=0.03162m(SUS304)OperatingPressurerange=0.1to1MPaabsOperatingTemperaturerange=0to50°C

FlowLRV 0

FlowURV 1000

Flow Damping *1 0.00 s

DP unit kPa SelectablefromTable13.PressureUnitDPLRV 0 AsspecifiedinorderDPURV Max.spanDP Damping *1 2.00 s AsspecifiedinorderSP A/G Selection Absolute AsspecifiedinorderSP unit MPa SelectablefromTable14.StaticPressureUnitSPLRV 0 AsspecifiedinorderSPURV 16SP Damping *1 1.00 s AsspecifiedinorderET unit °C SelectablefromTable15.TemperatureUnitETLRV –200 AsspecifiedinorderETURV 850ET Damping *1 1.00 s AsspecifiedinorderFixed Temperature 20°C(68°F) WhenExternalTemperatureInputCode0isspecified.Output signal DP WhenMeasurementFunctionCodeAisspecified.

Flow WhenMeasurementFunctionCodeBisspecified.Display setting DP and unit WhenMeasurementFunctionCodeAisspecified.

Flow and unit WhenMeasurementFunctionCodeBisspecified.

*1: Tospecifytheseitemsatfactory,optioncodeCAisrequired.

Mar. 11, 2019-00

Page 17: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

17<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

Calibration Units fot HART protocol typeTable 12-1. Mass Flow Unit

Unit LCD Communicationgrams per second g/s ←grams per minute g/m g/mingrams per hour g/h ←kilograms per second kg/s ←kilograms per minute kg/m kg/minkilograms per hour kg/h ←kilograms per day kg/d ←metric tons per minute t/m t/minmetric tons per hour t/h ←metric tons per day t/d ←pounds per second lb/s ←pounds per minute lb/m lb/minpounds per hour lb/h ←pounds per day lb/d ←short tons per minute STon/m STon/minshort tons per hour STon/h ←short tons per day STon/d ←long tons per hour LTon/h ←long tons per day LTon/d ←

Table12-2. Normal•StandardVolumeFlowUnit

Unit LCD Communicationnormal cubic meter per hour Nm3/h ←normal liter per hour NL/h ←standard cubic feet per minute SCFM ←standard liter per hour SL/h ←standard liter per minute SL/m SL/minstandard liter per second SL/s ←normal cubic meter per day Nm3/d ←standard cubic feet per day SCFD ←standard cubic feet per hour SCFH ←standard cubic feet per second SCFS ←standard cubic meter per day Sm3/d ←standard cubic meter per hour Sm3/h ←thousand standard cubic feet per day

MSCFD ←

million standard cubic feet per day

MMSCFD ←

Table 12-3. Volume Flow Unit

Unit LCD Communicationcubic feet per minute CFM ←gallons per minute GPM ←liters per minute L/m L/minimperial gallons per minute IGal/m Impgal/mincubic meter per hour M3/h ←gallons per second gal/s ←million gallons per day Mgal/d ←liters per second L/s ←million liters per day ML/d ←cubic feet per second CFS ←cubic feet per day ft3/d ←cubic meters per second M3/s ←cubic meters per day M3/d ←imperial gallons per hour IGal/h Impgal/himperial gallons per day IGal/d Impgal/dcubic feet per hour CFH ←cubic meters per minute m3/m m3/minbarrels per second bbl/s ←barrels per minute bbl/m bbl/minbarrels per hour bbl/h ←barrels per day bbl/d ←gallons per hour gal/h ←imperial gallons per second IGal/s Impgal/sliters per hour L/h ←gallons per day gal/d ←

Sep. 30, 2013-00

Page 18: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

18

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

Table 13. Pressure Unit

Unit LCD CommunicationmmH2O@4C mmH2O ←mmH2O@68F mmH2O ←mmHg mmHg ←Torr Torr ←MPa MPa ←kPa kPa ←Pa Pa ←mbar mbar ←bar bar ←gf/cm2 gf/cm2 ←kgf/cm2 kgf/cm2 ←inH2O@4C inH2O ←inH2O@68F inH2O ←inHg inHg ←ftH2O@4C ftH2O ←psi psi ←atm atm ←ftH2O@68F ftH2O ←hPa hPa ←

Table 14. Static Pressure Unit

Unit LCD/Communication

When abs is selectedLCD Communication

mmH2O@4C mmH2O mmH2OA mmH2OmmH2O@68F mmH2O mmH2OA mmH2OmmHg@0C mmHg mmHgA mmHgTorr Torr TorrA TorrMPa MPa MPaA MPakPa kPa kPaA kPaPa Pa PaA Pambar mbar mbarA mbarbar bar barA bargf/cm2 gf/cm2 g/cm2A g/cm2kgf/cm2 kgf/cm2 kg/cm2A kg/cm2inH2O@4C inH2O inH2OA inH2OinH2O@68F inH2O inH2OA inH2OinHg@0C inHg inHgA inHgftH2O@4C ftH2O ftH2OA ftH2Opsi psi psiA psiatm atm atmA atmftH2O@68F ftH2O ftH2OA ftH2OhPa hPa hPaA hPa

Table 15. Temperature Unit

Unit LCD/Communication°C deg C°F deg FKelvin K

Table 16. Total Flow Unit

Unit LCD/Communicationgrams gkilograms kgmetric tons tpounds lbshort tons STonlong tons LTonounce ozgallons galliters Limperial gallons Impgalcubic meters m3barrels bblcubic yards yd3cubic feet ft3cubic inches in3normal cubic meter Nm3normal liter NLstandard cubic feet SCF

Sep. 30, 2013-00

Page 19: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

19<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN

< Ordering Information for FOUNDATION Fieldbus protocol type >Specify the following when ordering.1. Model,suffixcodes,andoptioncodes2. Calibration range and units for Differential pressure, Static pressure and external temperature

1)Calibrationrangecanbespecifiedwithrangevaluespecificationsupto5digits(excludinganydecimalpoint)for low or high range limits within the range of –32000 to 32000. When reverse range is designated, specify LowerRangeValue(LRV)asgreaterthanUpperRangeValue(URV).

2)Specifyunit.SeeTable17forsettableunitatfactory.3. Static pressure is selected from gauge pressure or absolute pressure.4. TagNumber(ifrequired) Specifysoftwaretag(PD_TAG)upto32characterstobewrittenontheamplifiermemoryandTagnumberupto

22characters(or16characterswhen/N4isspecified)tobeengravedonthetagplateseparately.5. Outputmode(AI1L_TYPE); Selectonefrom‘Direct’,‘indirectLinear’or‘indirectSQRT’foroutputmodeofAI1(Differentialpressure).6. Outputscaleandunit(AI1OUT_SCALE); ThissettingisusedforIndicatorandoutputofAI1blockforDifferentialpressure.Thescalerangecanbespecified

withrangelimitspecificationsupto5digit(excludinganydecimalpoint)forlowandhighrangelimitswithintherangeof–32000to32000.WhenAI1L_TYPEisDirect,thesesettingdoesnotaffecttheoutputofAI1block.

7. Specify Node address in hexadecimal.8. Select‘BASIC’or‘LINKMASTER’forOperationFunctionalClass.9. Otherfactoryconfigurations(ifrequired) SpecifyingoptioncodeCCwillallowfurtherconfigurationatfactory. Followingisconfigurableitemandsettingrange: Softwaredampinginsecond(0.00to100.00)

Table 17. Factory Setting for FOUNDATION Fieldbus protocol type

Parameter Default value DescriptionTag number AsspecifiedinorderSoftwareTag(PD_TAG) FT1001 AsspecifiedinorderFlowunit(XD_SCALEofAI4) kg/h ValidwhenMeasurementFunctionCodeBisspecified.

StandardflowconfigurationFluid: N2Primaryelementtype:ISO5167-11991OrificeCornerTapsUpstreaminternalpipediameter=0.0527m(CarbonSteel)Diameterofprimarydevice=0.03162m(SUS304)OperatingPressurerange=0.1to1MPaabsOperatingTemperaturerange=0to50°C

FlowLRV(XD_SCALEofAI4) 0

FlowURV(XD_SCALEofAI4) 1000

Flow Damping *1 0.00 s

DPunit(XD_SCALEofAI1) kPa Selectable from kPa, MPa, Pa, hPa, mbar, bar, gf/cm2, kgf/cm2, mmH2O,mmH2O(68°F),inH2O,inH2O(68°F),ftH2O, ftH2O(68°F),mmAq,mmWG,mmHgorpsi.

DPLRV(XD_SCALEofAI1) 0 AsspecifiedinorderDPURV(XD_SCALEofAI1) Max.spanDP Damping *1 2.00 s AsspecifiedinorderSP A/G selection Absolute Absoluteorgauge,asspecifiedinorderSPunit(XD_SCALEofAI2) MPa SeeDescriptionfor‘DPunit(XD_SCALEofAI1).’SPLRV(XD_SCALEofAI2) 0 AsspecifiedinorderSPURV(XD_SCALEofAI2) 16SP Damping *1 1.00 s AsspecifiedinorderETunit(XD_SCALEofAI3) °C Selectable from °C,°F or Kelvin.ETLRV(XD_SCALEofAI3) –200 AsspecifiedinorderETURV(XD_SCALEofAI3) 850ET Damping *1 1.00 s AsspecifiedinorderFixed Temperature 20°C(68°F) WhenExternalTemperatureInputCode0isspecified.Output signal DP, SP, ET WhenMeasurementFunctionCodeAisspecified.

Flow, DP, SP, ET WhenMeasurementFunctionCodeBisspecified.Display setting DP and unit WhenMeasurementFunctionCodeAisspecified.

Flow and unit WhenMeasurementFunctionCodeBisspecified.Node Address ‘0xF5’ AsspecifiedinorderOperation Functional Class ‘BASIC’ Asspecifiedinorder

*1: Tospecifytheseitemsatfactory,optioncodeCCisrequired.

Mar. 11, 2019-00

Page 20: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

20

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

Calibration Units for FOUNDATION Fieldbus protocol type

Table 18. Temperature Unit

INDEX UNIT LCD1000 K Kelvin1001 °C deg C1002 °F deg F

Table 19-1. Pressure unit (1)

INDEX UNIT LCD1130 Pa Pa1131 GPa GPa1132 MPa MPa1133 kPa kPa1134 mPa mPa1135 μPa uPa1136 hPa hPa1137 bar bar1138 mbar mbar1139 torr torr1140 atm atm1141 psi psi1142 psia psia1143 psig psig1144 g/cm2 g/cm21145 kg/cm2 kg/cm21146 inH2O inH2O1147 inH2O(4°C) inH2O1148 inH2O(68°F) inH2O1149 mmH2O mmH2O1150 mmH2O(4°C) mmH2O1151 mmH2O(68°F) mmH2O1152 ftH2O ftH2O1153 ftH2O(4°C) ftH2O1154 ftH2O(68°F) ftH2O1155 inHg inHg1156 inHg(0°C) inHg1157 mmHg mmHg1158 mmHg(0°C) mmHg

Table 19-2. Pressure unit (2)

INDEX UNIT LCD1541 Paa Paa1542 Pag Pag1543 GPaa GPaa1544 GPag GPag1545 MPaa MPaa1546 MPag MPag1547 kPaa kPaa1548 kPag kPag1549 mPaa mPaa1550 mPag mPag1551 μPaa uPaa1552 μPag uPag1553 hPaa hPaa1554 hPag hPag1555 g/cm2a g/cm2a1556 g/cm2g g/cm2g1557 kg/cm2a kg/cm2a1558 kg/cm2g kg/cm2g1559 inH2Oa inH2Oa1560 inH2Og inH2Og1561 inH2Oa(4°C) inH2Oa1562 inH2Og(4°C) inH2Og1563 inH2Oa(68°F) inH2Oa1564 inH2Og(68°F) inH2Og1565 mmH2Oa mmH2Oa1566 mmH2Og mmH2Og1567 mmH2Oa(4°C) mmH2Oa1568 mmH2Og(4°C) mmH2Og1569 mmH2Oa(68°F) mmH2Oa1570 mmH2Og(68°F) mmH2Og1571 ftH2Oa ftH2Oa1572 ftH2Og ftH2Og1573 ftH2Oa(4°C) ftH2Oa1574 ftH2Og(4°C) ftH2Og1575 ftH2Oa(68°F) ftH2Oa1576 ftH2Og(68°F) ftH2Og1577 inHga inHga1578 inHgg inHgg1579 inHga(0°C) inHga1580 inHgg(0°C) inHgg1581 mmHga mmHga1582 mmHgg mmHgg1583 mmHga(0°C) mmHga1584 mmHgg(0°C) mmHgg1590 Barg Barg1591 mBarg mBarg1597 Bara Bara

Sep. 30, 2013-00

Page 21: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

21<<Contents>> <<Index>>

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation GS 01C25R01-01EN Sep. 30, 2013-00

Table 20-1. Mass Flow Unit

INDEX UNIT LCD1318 g/s g/s1319 g/min g/m1320 g/h g/h1322 kg/s kg/s1323 kg/min kg/m1324 kg/h kg/h1325 kg/d kg/d1327 t/min t/m1328 t/h t/h1329 t/d t/d1330 lb/s lb/s1331 lb/min lb/m1332 lb/h lb/h1333 lb/d lb/d1335 STon/min STon/m1336 STon/h STon/h1337 STon/d STon/d1340 LTon/h LTon/h1341 LTon/d LTon/d

Table20-2. Normal•StandardVolumeFlowUnit

INDEX UNIT LCD1360 SCFM SCFM1361 SCFH SCFH1524 Nm3/h Nm3/h1525 Nm3/d Nm3/d1529 Sm3h Sm3/h1530 Sm3/d Sm3/d1534 NL/h NL/h1537 SL/s SL/s1538 SL/h SL/h1539 SL/m SL/m1598 MSCFD MSCFD1599 MMSCFD MMSCFD65520 SCFS SCFS65521 SCFD SCFD

Table 20-3. Volume Flow Unit

INDEX UNIT LCD1347 m3/s m3/s1348 m3/min m3/m1349 m3/h m3/h1350 m3/d m3/d1351 L/s L/s1352 L/min L/m1353 L/h L/h1355 ML/d ML/d1356 CFS CFS1357 CFM CFM1358 CFH CFH1359 ft3/d ft3/d1362 gal/s gal/s1363 GPM GPM1364 gal/h gal/h1365 gal/d gal/d1366 Mgal/d Mgal/d1367 ImpGal/s IGal/s1368 ImpGal/min IGal/m1369 ImpGal/h IGal/h1370 ImpGal/d IGal/d1371 bbl/s bbl/s1372 bbl/min bbl/m1373 bbl/h bbl/h1374 bbl/d bbl/d

Page 22: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

22

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01EN

< Ordering Information for Modbus protocol type >Specify the following when ordering.1. Model,suffixcodes,andoptioncodes2. Calibration range and units

1)Calibrationrangecanbespecifiedwithrangevaluespecificationsupto5digits(excludinganydecimalpoint)for low or high range limits within the range of –32000 to 32000.

Whenreverserangeisdesignated,specifyLowerRangeValue(LRV)asgreaterthanUpperRangeValue(URV).

2)Specifyunitfromthetables“CalibrationUnitsforModbusprotocoltype”3. Static pressure is selected from gauge pressure or absolute pressure.4. TAGNO(ifrequired) Specifiedcharacters(upto22characters,or16characterswhen/N4isspecified)areengravedonthestainless

steeltagplatefixedontheterminalbox.5. SOFTWARETAG(ifrequired) Specifiedcharacters(upto32characters)aresetas“Tag”(thefirst8characters)and“Longtag”(32characters)in

theamplifiermemory. Whenthe“SOFTWARETAG”isnotspecified,specified“TAGNO”issetas“Tag”(thefirst8characters)and“Long

tag”(22characters)intheamplifiermemory.6. Otherfactoryconfigurations(ifrequired) SpecifyingoptioncodeCEwillallowfurtherconfigurationatfactory. Followingareconfigurableitemsandsettingrange.

1)Descriptor(upto16characters)2)Message(upto30characters)3)Softwaredampinginsecond(0.00to100.00)

Table 21. Factory Setting for Modbus protocol type

Parameter Default value DescriptionTag number AsspecifiedinorderDP unit kPa SelectablefromTable22.PressureUnitDPLRV 0 AsspecifiedinorderDPURV Max.spanDP Damping *1 2.00 s AsspecifiedinorderSP A/G Selection Absolute AsspecifiedinorderSP unit MPa SelectablefromTable23.StaticPressureUnitSPLRV 0 AsspecifiedinorderSPURV 16SP Damping *1 1.00 s AsspecifiedinorderET unit °C SelectablefromTable24.TemperatureUnitETLRV –200 AsspecifiedinorderETURV 850ET Damping *1 1.00 s AsspecifiedinorderFixed Temperature 20°C(68°F) WhenExternalTemperatureInputCode0isspecified.Display setting DP and unit

*1: Tospecifytheseitemsatfactory,optioncodeCEisrequired.

Mar. 11, 2019-00

Page 23: EJX910A Multivariable Transmitter - Yokogawa …Mass Flow (For Measurement Function Code B of HART and FOUNDATION Fieldbus protocol types) Mass Flow Reference Accuracy ±1.0% of Mass

23

All Rights Reserved. Copyright © 2005, Yokogawa Electric Corporation

<<Contents>> <<Index>>

GS 01C25R01-01ENSubject to change without notice.

Calibration Units for Modbus protocol typeTable 22. Pressure Unit

Unit LCD CommunicationmmH2O@4C mmH2O ←mmH2O@68F mmH2O ←mmHg mmHg ←Torr Torr ←MPa MPa ←kPa kPa ←Pa Pa ←mbar mbar ←bar bar ←gf/cm2 gf/cm2 ←kgf/cm2 kgf/cm2 ←inH2O@4C inH2O ←inH2O@68F inH2O ←inHg inHg ←ftH2O@4C ftH2O ←psi psi ←atm atm ←ftH2O@68F ftH2O ←hPa hPa ←

Table 23. Static Pressure Unit

Unit LCD/Communication

When abs is selectedLCD Communication

mmH2O@4C mmH2O mmH2OA mmH2OmmH2O@68F mmH2O mmH2OA mmH2OmmHg@0C mmHg mmHgA mmHgTorr Torr TorrA TorrMPa MPa MPaA MPakPa kPa kPaA kPaPa Pa PaA Pambar mbar mbarA mbarbar bar barA bargf/cm2 gf/cm2 g/cm2A g/cm2kgf/cm2 kgf/cm2 kg/cm2A kg/cm2inH2O@4C inH2O inH2OA inH2OinH2O@68F inH2O inH2OA inH2OinHg@0C inHg inHgA inHgftH2O@4C ftH2O ftH2OA ftH2Opsi psi psiA psiatm atm atmA atmftH2O@68F ftH2O ftH2OA ftH2OhPa hPa hPaA hPa

Table 24. Temperature Unit

Unit LCD/Communication°C deg C°F deg FKelvin K

< Material Cross Reference >

ASTM JIS316 SUS316F316 SUSF316316L SUS316LF316L SUSF316L304 SUS304F304 SUSF304660 SUH660B7 SNB7CF-8M SCS14A

< Related Instruments>FSA120FlowConfigurationSoftware(FlowNavigator):RefertoGS01C25R51-01ENPower Distributor: Refer to GS 01B04T01-02E or

GS 01B04T02-02E

< Trademarks >1. , FieldMate and FlowNavigator are

registered trademarks of Yokogawa Electric Corporation.

2. Teflon;TrademarkofE.I.DuPontdeNemours&Co.

3.Hastelloy;TrademarkofHaynesInternationalInc.4.HART®: Registered trademark of the FieldComm

Group.5. AIChE, DIPPR (Design Institute for Physical

Properties);TrademarksofAmericanInstituteofChemical Engineers.

6.AGA;TrademarkofAmericanGasAssociation.7. FOUNDATIONFieldbus;Trademarkofthe

FieldComm Group.8. Modbus is a registered trademark of AEG

Schneider.Othercompany/organizationand/orproductnamesare registered trade marks of their respective holders.

< Information on EU WEEE Directive >EUWEEE(WasteElectricalandElectronicEquipment)DirectiveisonlyvalidintheEU.This instrument is intended to be sold and used only asapartofequipmentwhichisexcludedfromWEEEDirective, such as large-scale stationary industrial tools,alarge-scalefixedinstallationandsoon,and,therefore, subjected to the exclusion from the scope of the WEEE Directive. The instrument should be disposed of in accordance with local and national legislation/regulations.

Mar. 11, 2019-00