EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
SECTION 133130
TEXTILE FACADE SYSTEM
PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Textile Facade System as shown on drawings and specified in this section.
2. Architect’s drawings indicate design intent with respect to sizes, shapes, and configurations
of the Textile Facade System. Textile Facade System manufacturer to provide all
components and accessories required for a complete Textile Facade System, whether or not
specifically shown or specified.
3. Textile Facade support frame will assume bolted/pinned connections for field assembly.
No field welding will be permitted.
B. Related Sections:
1. Related Documents: Drawings and general provisions of the Contract, including General
and Supplementary Conditions and Division 01 Specification Sections, apply to this
Section.
2. Division 03 Section “Cast-in-Place Concrete” for concrete caissons for posts of Textile
Facade System structural support.
3. Division 05 Sections "Structural Steel Framing" and “Architecturally Exposed Structural
Steel" for steel structure supporting the Textile Facade System.
4. Division 09 Sections “Finishes”.
5. Division 10 Sections “Specialties”.
C. The Textile Facade System Subcontractor shall be responsible for the structural design, detailing,
fabrication, supply, and installation of the Work specified herein. The intent of this specification
is to establish in the first instance an undivided, single-source responsibility of the Subcontractor
for all of the foregoing functions.
D. Subcontractor’s Work shall include the structural design, supply, fabrication, shipment, and
installation of the following items:
1. Architectural Textile Facade as indicated on the drawings and in these specifications.
2. Perimeter, catenary, and sectionalized aluminum tension frame system with tension clips.
3. Structural steel, struts, and beams as indicated on the drawings.
4. Finishes Covers and Fasteners.
E. This Project is a US Green Building Council LEEDTM
– CI project:
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
1. Select materials to maximize use of recycled steel and aluminum.
2. Select locally or regionally fabricated products when possible.
1.2 REFERENCES
A. Definitions:
1. Textile Facade System: Fabric Façade Panel supported by an extruded aluminum frame
and retained via EFS Clips ( PN EFS #14-000)
B. Reference Standards: Except as otherwise shown or noted, all work shall comply with the
requirements of the following codes and standards:
1. American Institute of Steel Construction (AISC)
a. Specifications for the Design, Fabrication, and Erection of Structural Steel for
Buildings.
b. Code of Standard Practices for Steel Buildings and Bridges.
c. Specifications for Structural Steel Buildings – Allowable Stress Design and Plastic
Design.
d. Specification for Allowable Stress Design of Single-angle Members.
e. Seismic Provisions for Structural Steel Buildings.
2. American Society of Civil Engineers
a. ASCE 19: Structural Applications of Steel Cables for Buildings.
3. American Society of Testing and Materials (ASTM)
a. ASTM A586: Standard Specifications for Zinc-Coated Parallel and Helical Steel
Wire Structural Strand.
b. ASTM D4851: Standard Test Methods for Coated Laminated and Woven Fabrics
for Architectural Use.
c. ASTM E84: Standard Test Method for Surface Burning Characteristics of
Building Materials.
d. ASTM C423: Standard Test Method for Sound Absorption and Sound Absorption
Coefficients by the Reverberation Room Method.
e. ASTM A36/A36M Specification for Carbon Structural Steel.
f. ASTM A500/A500M Specification for Cold-Formed Welded Seamless Carbon
Steel Structural Tubing in Rounds and Shapes.
4. American Welding Society (AWS)
a. AWS D1.1: Structural Welding Code (Steel).
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
b. AWS A2.4: Symbols for Welding, Brazing & Nondestructive Examination.
c. AWS D1.2 Structural Welding Code (Aluminum).
5. National Fire Protection Association (NFPA)
a. NFPA 701: Standard Methods of Fire Tests for Flame Propagation of Textiles and
Films.
6. The Society for Protective Coatings (SSPC)
a. Steel Structures Painting Manual, Volumes 1 and 2.
1.3 ACTION SUBMITTALS
A. Product Data: For each type of product
1. Include styles, material data, material descriptions, construction details, fabrication details,
dimensions of individual components and profiles, hardware, fittings, mounting
accessories, features, and finishes for Textile Facade Systems.
2. Include rated capacities, light transmissions, and operating characteristics of furnished
specialties and accessories.
B. LEED Submittals:
1. Product Data for Credit MR 4: For products having recycled content, documentation
indicating percentages by weight of postconsumer and preconsumer recycled content.
Include statement indicating cost for each product having recycled content.
2. Product Certificates for Credit MR 5.1[and Credit MR 5.2]: For products and materials
required to comply with requirements for regionally manufactured materials. Include
statement indicating cost for each regionally manufactured material.
a. Include statement indicating location and distance of manufacturer to Project for
each regionally manufactured material.
C. Design Drawings:
1. Include plans, elevations, sections, mounting heights, and frame assembly details.
2. Preliminary support frame member sizes with wall thickness TBD.
3. Preliminary footing layout and foundation design with final size, shape and depth TBD.
4. Show fabric attachment hardware and details.
5. Show details of fabric panel anchorage and connection details, dimensions including length
of spans, seam locations and interferences with building construction.
D. Engineered Drawings (Submit after Design Drawings are approved):
1. Calculations with Wet Stamp seal of a Professional Engineer licensed in the same state as
the project location.
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
2. Include plans, elevations, sections, mounting heights, and frame assembly details.
3. Provide frame support member sizes and required wall thicknesses.
4. Identify all welding requirements.
5. Detail all bolted and/or pin connection points for frame assembly.
6. Identify required sizes of bolts, pins, plates and tubing.
7. Verify fabric selection meets minimum engineering requirements.
8. Detail fabric attachment methods, cable type (wire rope), cable end connections, clamps
and other attachment components.
9. Call out all cable sizes and pre-tensioning requirements.
10. Submit anchor-bolt plans and specifications before foundation work begins. Include
location, diameter, and projection of anchor bolts required to attach the Textile Facade
System to foundation. Indicate column reaction loads at each location.
E. Samples for Initial Selection: Electronic submittal of available frame finish colors.
F. Samples for Verification of the following:
1. Fabric: Qty (3) 8 ½” x 11” fabric samples selected by the architect.
2. Frame Finish: Qty (3) sample chips with a minimum size of 2” x 3”
G. Provide a Schedule of Values within (2) weeks of project award.
1.4 INFORMATIONAL SUBMITTALS
A. Qualification Data: For Installers, Fabricator and Professional Engineer.
B. Welding Certificates.
C. Fabric Manufacturer’s Warranty.
1.5 CLOSEOUT SUBMITTALS
A. Maintenance Data: Textile Facade System to include Maintenance Manuals.
1. Include the following information:
a. Methods for maintaining Textile Facade System.
b. Precautions on cleaning solutions, materials and methods that could be detrimental
to fabrics, finishes, and performance of the Textile Facade System
1.6 QUALITY ASSURANCE
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
A. Fabricator Qualifications: Shop that employs skilled workers who custom fabricate Textile
Facade Systems similar in size & complexity to those required for this Project with a successful
record in-service performance.
1. Fabricator's responsibilities include the fabrication of the Textile Façade System and
providing professional engineering services.
2. Engineering must utilize Finite Element Analysis software that performs fabric form
finding and includes fabric material properties and prestress characteristics.
3. Fabricator must have proven record of at least five (5) successful projects similar in size
and similar specified fabric material.
4. Fabricator must have been in continuous operation as a professional Textile Facade System
manufacturer for minimum of ten (10) years prior to this Project.
5. Fabricator must be a Made-in-America in-house manufacturing facility for both frame and
fabric components.
B. Installer Qualifications:
1. Must be a licensed contractor or have authority and required insurance to legally perform
work in the state where the Textile Façade System is being installed.
2. Must provide required insurance coverage required by the project.
C. Welding Qualifications: Qualify personnel procedures and personnel according to the following:
1. AWS D1.1/D1.1M Structural Welding Code - (Steel)
2. AWS D1.2 Structural Welding Code - (Aluminum)
1.7 FIELD CONDITIONS
A. Weather Limitations: Proceed with installation only when existing and forecasted weather
conditions permit installation of Textile Facade System in exterior locations performed
according to manufacturers' written instructions and warranty requirements.
B. Field Measurements: When Textile Facade System installation is indicated to fit to other work,
verify dimensions by Project Site field measurements before fabrication starts. Submit
measurements on Shop Drawings to Architect for approval. Allow clearances for fenestration
operation throughout the entire operating range. Notify Architect of discrepancies immediately.
Coordinate fabrication schedule with construction progress to avoid any delays to the Project.
1.8 WARRANTY
A. Special Warranty: Fabric Manufacturer and Textile Facade System fabricator agree to repair or
replace components of Textile Facade System that fail in material or workmanship within
specified Warranty period of one (1) year from the date of Substantial Completion.
1. Failures include, but are not limited to:
a. Structural or framework failures.
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
b. Fabric deterioration including any seam failure.
c. Metals, metal finishes, and any other materials beyond normal weathering.
2. Fabric Warranty: Fabric manufacturer’s limited Warranty.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Approved Manufacturer: Eide Industries, Inc., 16215 Piuma Avenue, Cerritos, CA 90703, Toll-
Free: (800) 422-6827, Phone: (562) 402-8335, Fax: (562) 924-2233, Contact: Bryan Presby
Email: [email protected], Website: www.eidestructures.com
B. Single Source Responsibility: Provide components and materials specified in this section from a
single manufacturer.
C. Substitutions: [Section 01 25 00 - Substitution Procedures] No substitutions permitted.
2.2 DESCRIPTION
A. General: Provide a Textile Facade System that complies with requirements specified herein by
testing the Subcontractor’s corresponding membrane system in accordance with the indicated
test methods.
B. Regulatory Requirements: Provide Textile Facade System in compliance with requirements and
limitations of Jurisdictional Authorities that are within Subcontractor's control.
1. Building Code Criteria: The Textile Facade System shall comply with the International
Building Code, 2009 Edition.
2. Comply with Local Building Codes and respective loading criteria for Snow Loads, Live
Loads, Dead Loads, Wind Speed, and Seismic Loads.
3. Life Safety: Textile Facade System shall be detailed so that no life safety issue is created
in the event of the loss of fabric membrane or associated parts. The Textile Facade
System does not rely on any membrane for structural stability.
2.3 PERFORMANCE / DESIGN CRITERIA
A. Delegated Design: Retain a qualified Professional Engineer to design Textile Facade System.
Design Engineering requirements to include, but are not limited to, the following:
1. Prepare structural design drawings defining the precise interface geometry determination,
reaction loads imposed on structural steel framing, anchoring loads, connection details,
interfaces and seam layouts.
B. In engineering the Textile Facade System, fittings and accessories to withstand structural loads
indicated, determine allowable design working stresses of railing materials based on the
following:
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
1. Steel: 72 percent of minimum yield strength.
2. Stainless Steel: 60 percent of minimum yield strength.
3. Aluminum: The lesser of minimum yield strength divided by 1.65 or minimum ultimate
tensile strength divided by 1.95.
C. Structural Performance: Textile Facade System shall withstand the effects of gravity loads and
the following loads and stresses within limits and under conditions indicated according to
ASCE/SEI 7:
1. Wind Loads: To be determined by Subcontractor’s Engineer of Record.
2. Live Loads: To be determined by Subcontractor’s Engineer of Record.
3. Seismic Loads: To be determined by Subcontractor’s Engineer of Record.
D. Thermal Movements: Allowance for thermal movements from ambient and surface temperature
changes.
1. Material Surface Temperature Change: 22 degrees F to 158 degrees F
E. Control of Corrosion: Prevent galvanic action and other forms of corrosion by insulating metals
and other materials from direct contact with incompatible materials.
2.4 TEXTILE FACADE MATERIALS
A. Product: Subject to compliance with requirements, provide fabric as called out and specified by
the Architect in the bid set drawings and specifications.
B. Fire-Test-Response Characteristics: Provide Textile Facade System fabric with the Fire-Test-
Response characteristics indicated, determined by testing identical products according to the test
method indicated below by a recognized testing and inspection agencies acceptable to authorities
having jurisdiction on the Project:
1. Flame-Resistance Ratings: Passes NFPA 701
2. California State Fire Marshal Tittle 19
C. Textile Manufacturer: The following is a list of approved fabrics for the Textile Facade System,
reference drawings for fabric call out.
1. Serge Ferrari Textiles
a. Soltis product line
1) Serge Ferrari Soltis 86
2) Serge Ferrari Soltis 92
3) Serge Ferrari Soltis 381
b. Color: To be selected from the manufacturer’s range of available colors
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
2.5 TEXTILE FACADE SYSTEM FRAME, FITTINGS AND ACCESSORIES
A. General: Provide standard accessories with Textile Facade System fabricator as specified.
Fabricate and finish accessories in the factory to greatest extent possible, by manufacturer's
standard procedures and processes. Comply with indicated profiles as well as dimensional and
structural requirements.
B. Metal Surfaces: Provide materials with smooth seamless surfaces, without seam marks, roller
marks, rolled trade names, stains, discolorations, or blemishes.
C. Fabric Retention Frame shall be constructed of Extruded ASTM alloy 6061 and then heat-treated
to T6.
D. Support frame material shall be constructed of cold rolled carbon steel unless otherwise specified
by the Architect in the bid drawings.
E. Steel and Iron:
1. Tubing: ASTM A500/A500M Cold-Formed Welded and Seamless Carbon Steel Structural
Tubing in Rounds and Shapes –A513/A513M Electric-Resistance–Welded Carbon and
Alloy Steel Mechanical Tubing
2. Bars: ASTM A29/A29M Steel Bars, Carbon and Alloy, Hot-Wrought, Grade 1010
3. Plates, Shapes, and Bars: ASTM A36 Carbon Structural Steel or ASTM A572 High-
Strength Low-Alloy Columbium-Vanadium Structural Steel per engineer requirements.
F. Aluminum Support Extrusions
1. EIDE Facade System per parts list attached. Job Specific.
2. Provide alloy and temper recommended by aluminum producer and finisher for type of use
and finish indicated, and with strength and durability properties for each aluminum form
required not less than that of alloy and temper designated below.
3. Extruded Bars and Shapes: ASTM B221Aluminum & Aluminum – Alloy Extruded Bars,
Rods, Wire, Profiles and Tubes, Alloy 6063-T5/T52.
2.6 TEXTILE FACADE FRAME FINISH
A. Frame Finish shall be Polyester Powder Coat unless otherwise specified by the Architect on the
bid set drawings.
1. Polyester Powder Coat Finish:
a. Commercial blast clean surface in accordance to SSPC-SP 10.
b. Apply Polyester Powder Coat to a minimum of 3 mils thick.
c. Color: As selected from manufacturer’s available stock colors.
2. Three Part Paint Finish for Corrosive Environments:
a. Commercial blast clean surface in accordance to SSPC-SP 10.
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
b. Primer Material properties – (1) coat of PPG/Ameron’s Dimecoat 9 at 2.5-4.0 mils
MDFT.
c. Paint Material properties – (1) coat of PPG/Ameron’s Amerlock 2 at 3.0-7.0 mil
MDFT per coat.
d. Paint Material properties – (1) coat of PPG/Ameron’s PSX 700 at 3.0-7.0 mil
MDFT per coat.
e. Minimum thickness – 8.5-18 mils TDFT.
f. Color: As selected from manufacturer’s available stock colors
PART 3 - EXECUTION
3.1 EXAMINATION
A. Examine structural steel framing and other substrates, with Authorized Installation Technician
present, for compliance with requirements for installation tolerances and other conditions
affecting performance of the Work.
B. Prepare written report, endorsed by Authorized Installation Technician, listing conditions
detrimental to performance.
C. Proceed with installation only after unsatisfactory conditions have been corrected.
3.2 JOB SITE SAFETY
A. Supervisor required to have completed 30-hour Occupational Safety and Health Training Course
in Construction Safety and Health and all installers to be certified First Aid trained.
3.3 ERECTION
A. Proceed with installation of Textile Facade System only when weather conditions permit work to
be performed in accordance with manufacturer’s recommendations.
B. Erect frame and fabric in accordance with the procedures of the approved manufacturer.
C. Adequate pre-stress what shall be applied to eliminate fabric wrinkles.
3.4 FIELD QUALITY CONTROL
A. Manufacturer's Field Service: A factory-authorized service Authorized Installation Technician
must be present during all tests and inspections of components, assemblies, and equipment
installations, including connections.
B. Prepare tests and inspection reports.
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
PROFILE Eide PN Length
EFS #14-200 20
EFS #14-240 20
EFS #14-260 20
EFS #14-300 20
EFS #14-320 20
EFS #14-360 20
EFS #14-380 20
EFS #14-800 20
EFS #14-820 20
EFS #14-880 20
EFS#14-860 20
EIDE INDUSTRIES INC. – TEXTILE FACADE SYSTEM GUIDE SPECIFICATION
29 APRIL 2016
TEXTILE FACADE SYSTEM 133130
PROFILE Eide PN Length
EFS#14-864 20
EFS#15-000 20
EFS #15-020 20
EFS #14-420 20
EFS #14-000 500
EFS #15-180 100
EFS #15-190 100
END OF SECTION 133130