EHV & HV Shunt Reactor Protection

Meliha B. Selak, P. Eng

BC Hydro, Protection & Control Planning

IEEE Croatia Section, PES Chapter, Zagreb October 12, 2012

Page 2: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

The shunt reactor as a component of the power system is used to compensate for the effects of high charging currents of long transmission lines and cables.

Shunt Reactor

Page 3: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Shunt Reactor

Page 4: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Most shunt reactors are permanently connected through a switching device (disconnect switch or circuit breaker) at the ends of EHV/HV kV transmission lines to limit fundamental-frequency temporary overvoltages and energization overvoltages (switching transients).

Shunt Reactor Connections to EHV/HV kV

Page 5: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Line Connected Shunt Reactor

21L

52

52

21L

52

52

Transmission Line

PN

PN PN

PN

CircuitBreaker

Reactor

Page 6: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

The principal hazards to a reactor are similar to that for a transformer: • bushing and isolation failures (resulting in large changes in the magnitude

of phase current) • turn-to turn faults within winding, (resulting in small changes in the magnitude

of phase current), • Miscellaneous failures (such as low oil, loss of cooling, pole

disagreement, …)

Hazards to a Reactor

Page 7: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Protection of reactors are basically the same as for transformers with the size and importance to the system including:

– Reactor Electrical Protection – Reactor non-electrical protection

Reactor Protection

Page 8: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

• BC Hydro system is to provide reliable protection for all possible faults using both electrical and non-electrical devices.

• Reliable protection system is both

dependable and secure

BC Hydro Protection Philosophy

Page 9: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Reliability

• Dependability A dependable protection system operates when required. • Security A secure protection system does not operate for normal system operation or when not required to operate to clear a fault.

Page 10: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Reliability

Page 11: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Additional Power system protection Philosophy

• Sensitivity Protection shall have adequate sensitivity to detect faults, considering a single system contingency or fault resistance which results in reduced operating quantities to the protection. • Selectivity Protection systems should remove from service the minimum number of system elements necessary to clear a fault.

Page 12: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Continue • Speed Protection systems should provide fault clearing in a minimum time, considering time delays required to achieve security and selectivity. • Loadability Protection should not limit the load carrying capability of major equipment such as transmission lines, transformers, circuit breakers, disconnect switches.

Page 13: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Continue

• Isolation Isolation of a system component is intended to prevent its re-energization until an inspection has been completed. Isolation is accomplished by opening the circuit breakers and/or disconnect switches closest to the system component, with lockout block closing of those devices

Page 14: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Shunt Reactor Current is mainly inductive and it is small (10%-15% of nominal currents)

Shunt Reactors are frequently switched and during the periods of the system operations with low loads it is energized; and with the rise of load it is de-energized

Switching operations result in EMT and some mechanical effects.

Shunt Reactor Operation Characteristics

Page 15: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Inductive – Shunt Reactor De-energisation

Ls Lb

Lp CpCs CL L

CB

Interactive process characterised by: •Current chopping (interaction of arc with capacitance in parallel with the CB) •Relatively high frequency recovery voltage on load side •Reignitions (can normally not be avoided)

Page 16: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Shunt Reactor De-energisation - Voltages

Page 17: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Shunt Reactor De-energisation - Reignitions

Page 18: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Reactor Primary Protection

• Primary protection includes differential and overcurrent protection. – Differential protection scheme is high-impedance

differential protection and is connected to dedicated current transformers.

– Applied as a primary protection for faults • between windings of different phase • winding-to-core • Winding-to-winding faults

– Does not detect interturn faults.

Page 19: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

• Backup protection for reactor faults is provided also by an inverse time neutral overcurrent protection to detect high-magnitude winding-to-ground (winding-to-tank) faults.

• It does not have to be directional but should override maximum contribution to external faults (HV bus and lines) and unequal current transformer saturation.

Page 20: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Reactor Standby Protection

• Standby protection includes overcurrent protection and non-electrical protective devices. – Non-electrical devices will be connected for alarm

and trip

Page 21: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Major concern

• Sensitivity and Security Reactor protection must detect minimum interturn faults, winding to ground faults and core faults and must be selective to prevent unnecessary trips and reactor isolation for external faults or transients on energizing and de-energizing the reactor.

Page 22: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Interturn faults

Interturn faults are extremely difficult to detect • Detection of those faults depends on the

grounding of reactor. – If reactor is supplied from a grounded

system, and its neutral is solidly grounded, this reduction in impedance causes an increase in current magnitude in the particular phase, resulting in a zero sequence current flowing through the neutral to ground.

Page 23: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Interturn Faults Detection

• Used the neutral ground overcurrent elements, connected to separate neutral CTs, supervised by the zero-sequence voltage polarized directional element.

• Directional neutral ground protection scheme includes an “Inrush Tripping Suppressor” (ITS) scheme that – disables tripping on de-energization, – disable several seconds following energization.

Page 24: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Inrush Tripping Suppression Logic

Inrush Tripping Suppression (ITS) feature is implemented using phase overcurrent elements to avoid false tripping by sensitive protection elements on energizing the reactor. (ITS blocks the ground overcurrent tripping on deenergization of the reactor and retains the blocking function for a few seconds after energization).

Page 25: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Directionalized to see zero sequence current flow

into the reactor. (This device should not operate for external faults) The setting is about 5-10 % of reactor rating

(This setting could be slightly desensitized because of the directional element’s sensitivity).

Inrush Tripping Suppression (ITS) (to avoid false tripping by sensitive protection elements on

energizing the reactor) Tripping is time delayed by 15 cycles

(Time delay is necessary to avoid race between reset of ITS logic and transient pick up of the 67N element).

Turn-to-Turn Protection Scheme

Page 26: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Present BCH 500 kV Shunt Reactor One Line Diagram

87R

51R51RS

21L21LS

CB2

RCB

CB1

DCS

500 kV Line

500 kV Reactor

63G 63Q

71G 71Q

CTsCTs

CTs

CTs

Neutral CTs

PT

Page 27: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Protection tripping for reactor faults is similar to that for transformers.

– In new installations, tripping from the sudden pressure relay should be supervised by the sensitive ground directional relay, as recommended in BC Hydro internal report "The Model 11 Gas Relay - Performance Analysis and Recommendations"

Reactor Protection Tripping

Page 28: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

BC Hydro Reactor Protection Scheme

“52a”Reactor CB Status

ITStimer

67NTDirectional

15cyc

050N

50P/51P

50G/51G

S

R

Trip

Trip

Reset PB

Q

Latch Maintain TT to Remote End

240cyc

0

Isolalation Timer

Open Reactor CB

Trip Output TRIP Line CBs

OR

OR

AND

AND

AND

AND

Non-Electrical Protection

87R

Initiate TT

Send TT to Remote End

63G 63Q

71Q71G

Numerical multifunctional protective device

OR

AND

50A50B50C 240

cyc

0

AND

Inrush Tripping Suppression by O/C

AND

ANDLoc End OpenRem End Open

Note: 50 elements measure reactor current

Page 29: EHV & HV Shunt Reactor  · PDF fileEHV & HV Shunt Reactor Protection . Meliha B. Selak, ... (interaction of arc with ... reactor isolation for external faults or transients on

Finally - Why do we have protection?