Technology and Solutions Protection and Substation Automation © ABB Switzerland Ltd. - 1 EFP_basics / 2003-04-01 / RW Topic: END FAULT PROTECTION APPLICATION BASICS BASICS

EFP

Embed Size (px)

DESCRIPTION

End fault protection-basics

Citation preview

Page 1: EFP

Technology and SolutionsProtection and Substation Automation

© A

BB

Sw

itzer

land

Ltd.

-1E

FP_b

asic

s / 2

003-

04-0

1 / R

W

Topic:

END FAULTPROTECTIONAPPLICATION

BASICS BASICS

Page 2: EFP

© A

BB

Sw

itzer

land

Ltd.

-2E

FP_b

asic

s / 2

003-

04-0

1 / R

WTopic Objectives

r Definition Protection Zone - Physical Zone

r Definition End- Fault Conditionr Fault clearance without EFP

r Fault evaluation

r EFP applicationr Fault clearance with EFP

r End- Fault Condition in a bus- coupler

r CB auxiliary circuitsr Modern protection systems

r BBP - additional CB functionality on feedersr Future standards

Objectives

Page 3: EFP

© A

BB

Sw

itzer

land

Ltd.

-3E

FP_b

asic

s / 2

003-

04-0

1 / R

W

1 CT

Definition Protection Zone - Physical Zone

2 CTs (overlapped protection zones)

busbar zone

(physical)

line zone

(physical)

protection zone

protection zone

protection zone

protection zone

Page 4: EFP

© A

BB

Sw

itzer

land

Ltd.

-4E

FP_b

asic

s / 2

003-

04-0

1 / R

WDefinition End- Fault Condition

1 CT

2 CTs (overlapped protection zones)

End - Zone

End - Zone

End - Fault

Page 5: EFP

© A

BB

Sw

itzer

land

Ltd.

-5E

FP_b

asic

s / 2

003-

04-0

1 / R

WBusbar Configurations

CT line side

CT bus side

CT overlapped

Selectivity

Speed

Selectivity

Speed

single or multiple busbar

1 1/2 breaker busbar

How will an End- Fault condition be cleared in different busbar

configurations (without any End-Fault Protection) ???

Page 6: EFP

© A

BB

Sw

itzer

land

Ltd.

-6E

FP_b

asic

s / 2

003-

04-0

1 / R

W

Bus

bar

Fault clearance (without EFP)

I. Multiple BB, CT line side

G

Page 7: EFP

© A

BB

Sw

itzer

land

Ltd.

-7E

FP_b

asic

s / 2

003-

04-0

1 / R

W

Line

G

Fault clearance (without EFP)

I. Multiple BB, CT line side

Page 8: EFP

© A

BB

Sw

itzer

land

Ltd.

-8E

FP_b

asic

s / 2

003-

04-0

1 / R

W

Bus

bar

Line

G

Fault clearance (without EFP)

II. Multiple BB, CT bus side

Page 9: EFP

© A

BB

Sw

itzer

land

Ltd.

-9E

FP_b

asic

s / 2

003-

04-0

1 / R

W

OC Back- up

Line

Dis

tanc

e

G

Fault clearance (without EFP)

II. Multiple BB, CT bus side

Page 10: EFP

© A

BB

Sw

itzer

land

Ltd.

-10

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Bus

bar

Line

G

Fault clearance (without EFP)

III. Multiple BB, CT overlapped

Page 11: EFP

© A

BB

Sw

itzer

land

Ltd.

-11

EFP

_bas

ics

/ 200

3-04

-01

/ RW

G

Fault clearance (without EFP)

III. Multiple BB, CT overlapped

Page 12: EFP

© A

BB

Sw

itzer

land

Ltd.

-12

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Line Distance

OC Back- up

OC Back- up

Fault clearance (without EFP)

IV. 1 1/2 CB BB, CT line side

Page 13: EFP

© A

BB

Sw

itzer

land

Ltd.

-13

EFP

_bas

ics

/ 200

3-04

-01

/ RW

OC Back- up

OC Back- up

Fault clearance (without EFP)

V. 1 1/2 CB BB, CT bus side

Page 14: EFP

© A

BB

Sw

itzer

land

Ltd.

-14

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Fault clearance (without EFP)

VI. 1 1/2 CB BB, CT overlapped

Page 15: EFP

© A

BB

Sw

itzer

land

Ltd.

-15

EFP

_bas

ics

/ 200

3-04

-01

/ RW

CT line side

CT bus side

CT overlapped

single or multiple busbar

1 1/2 breaker busbar

Fault Evaluation

++ very good

+ acceptable

- critical

Selectivity

Selectivity

Speed

Speed

++

++++

++

++

+ -

---

-

-

Page 16: EFP

© A

BB

Sw

itzer

land

Ltd.

-16

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Fault Evaluation

Conclusion:

An additional protection function is required in CT bus side and 1 1/2 circuit

breaker configuration without overlapped CTs

!!!

ð End- Fault Protection Function

Page 17: EFP

© A

BB

Sw

itzer

land

Ltd.

-17

EFP

_bas

ics

/ 200

3-04

-01

/ RW

logic depending on the switchgear configuration (CT bus side, Line side;

1 1/2 CB)

feeder current

End- Fault Protection Function

EFP

&

I >

remote tripping

intertripping

t = EFP pick up time (higher than the highest possible arc extinguish time + safety time

CB opent

~120 ms

Page 18: EFP

© A

BB

Sw

itzer

land

Ltd.

-18

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Fault clearance (with EFP)

How will an End- Fault condition be cleared in

different busbar configurations (with End- Fault Protection)

???

Page 19: EFP

© A

BB

Sw

itzer

land

Ltd.

-19

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Bus

bar

Line

G

Fault clearance (with EFP)

II. Multiple BB, CT bus side

Page 20: EFP

© A

BB

Sw

itzer

land

Ltd.

-20

EFP

_bas

ics

/ 200

3-04

-01

/ RW

G

Fault clearance (with EFP)

II. Multiple BB, CT bus side

EFP

Intertripping

ð Fault cleared selectively !!!(~250ms)

Page 21: EFP

© A

BB

Sw

itzer

land

Ltd.

-21

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Fault clearance (with EFP)

IV. 1 1/2 CB BB, CT line side

EFPIntertripping

Remote trip

ð Fault cleared selectively !!!(~250ms)

Page 22: EFP

© A

BB

Sw

itzer

land

Ltd.

-22

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Fault clearance (with EFP)

V. 1 1/2 CB BB, CT bus side

EFP

ð Fault cleared selectively !!!(~250ms)

Intertripping

Page 23: EFP

© A

BB

Sw

itzer

land

Ltd.

-23

EFP

_bas

ics

/ 200

3-04

-01

/ RW

How will an End- Fault condition be cleared in a bus- coupler (without any

EFP)

???

End- Fault Condition in a Bus- Coupler

Page 24: EFP

© A

BB

Sw

itzer

land

Ltd.

-24

EFP

_bas

ics

/ 200

3-04

-01

/ RW

BB1

BB2

End- Fault Condition in a Bus- Coupler

~ ~

Page 25: EFP

© A

BB

Sw

itzer

land

Ltd.

-25

EFP

_bas

ics

/ 200

3-04

-01

/ RW

End- Fault Condition in a Bus- Coupler

Page 26: EFP

© A

BB

Sw

itzer

land

Ltd.

-26

EFP

_bas

ics

/ 200

3-04

-01

/ RW

⇒ by the coupler function of the

BUSBAR protection

End- Fault Condition in a Bus- Coupler

Page 27: EFP

© A

BB

Sw

itzer

land

Ltd.

-27

EFP

_bas

ics

/ 200

3-04

-01

/ RW

r a bus- coupler

End Fault Protection application

r multiple BB configuration with CT bus sider 1 1/2 circuit breaker configuration without

overlapped CTs

Summery:An EFP function in strictly required in:

It is not required in:r configuration with overlapped CTs

It will reduce the tripping time in:r multiple BB configuration with CT line side

Page 28: EFP

© A

BB

Sw

itzer

land

Ltd.

-28

EFP

_bas

ics

/ 200

3-04

-01

/ RW

CB auxiliary circuits

What “problem” will occur in case on a “switch

onto fault” situation???

Page 29: EFP

© A

BB

Sw

itzer

land

Ltd.

-29

EFP

_bas

ics

/ 200

3-04

-01

/ RW

CB auxiliary circuits

CB open !!!

CB closing command

flash over before CB indicates closed

⇒ EFP will trip the BB wrongly

EFP enabled

I>

CT bus side

Page 30: EFP

© A

BB

Sw

itzer

land

Ltd.

-30

EFP

_bas

ics

/ 200

3-04

-01

/ RW

CB auxiliary circuits

CB open !!!

CB closing command

flash over before CB indicates closed

⇒ EFP will trip the line remote end wrongly

EFP enabled

I>

CT line side

Page 31: EFP

© A

BB

Sw

itzer

land

Ltd.

-31

EFP

_bas

ics

/ 200

3-04

-01

/ RW

⇒ in case on a “switch onto fault situation” the EFP will generate a tripping signal before the closed indication appears

(flash- over in the circuit breaker)

CB auxiliary circuits

Page 32: EFP

© A

BB

Sw

itzer

land

Ltd.

-32

EFP

_bas

ics

/ 200

3-04

-01

/ RW

CB auxiliary circuits

How can this be avoided???

Page 33: EFP

© A

BB

Sw

itzer

land

Ltd.

-33

EFP

_bas

ics

/ 200

3-04

-01

/ RW

⇒ the protection system must be informed in advance that the CB is going to be closed

⇒ by the (manual) close command of the CB

CB auxiliary circuits

Page 34: EFP

© A

BB

Sw

itzer

land

Ltd.

-34

EFP

_bas

ics

/ 200

3-04

-01

/ RW

logic depending on the switchgear configuration (CT bus side, Line side;

1 1/2 CB)

feeder current

End- Fault Protection Function

EFP

&I >

remote tripping

intertripping

t = EFP pick up time (higher than the highest possible arc extinguish time + safety time

CB opent

~120 ms

CB (manual)

close command

Page 35: EFP

© A

BB

Sw

itzer

land

Ltd.

-35

EFP

_bas

ics

/ 200

3-04

-01

/ RW

Phase

R S T

CB / isolator auxiliary circuits

CB open

CB closed

++

protection

system

NC aux.

contacts

Phase

R

S

T

NC aux.

contacts

+

CB closing

coil

CB (manual)

close commandCB close

order

Page 36: EFP

© A

BB

Sw

itzer

land

Ltd.

-36

EFP

_bas

ics

/ 200

3-04

-01

/ RW