Upload
mamat5255
View
165
Download
12
Embed Size (px)
Citation preview
EET 305
Mohd Rafi, Rev Mei 2011 1
The Load in Power System
EET 305
• The Load in Power System
Define and explain basic load forecasting and load characteristic.
Analyze and calculate power, power factor and power factor correction.
2
Load Characteristic
• Load Curve
• The load on a power station is not constant. It variesfrom time to time.
• The load curve is obtained by plotting the loads againstthe time on a graph paper.
• When it plotted from 24 hours of a day it is called dailyload curve and if the time considered is for one year(8760 hours) then it is called annual load curve.
• The yearly load curve is generally used to determine theload factor.
• The areas under the load curve represent the energygenerated in the period considered.
3Mohd Rafi, rev mei 2011
Load Characteristic
Load Curve
• The area under the curve divided by the total number of
hours gives the average load on the power station.
• The peak curve load indicated by the load curve
represents the maximum demand on the power station.
4Mohd Rafi, rev Mei 2011
Example of Typical
Commercial Load Curve
Load Characteristic
Load Curve
• The greatest problem for a power supply company is
varying load. The generation should be matched with the
load consistently.
5Mohd Rafi, rev Mei 2011
• The base load power is
supplied by power plants
running continuously.
• The Intermediated/Average
load prevails for some part of
the day.
• The peak load prevails only
a few hours of the day
Load Characteristic
• Terms and Definitions
a) Demand
The demand of the installation or system is the load
at the receiving terminals averaged over a specified
time.
b) Demand Interval (t)
The period over which the load is averaged.
Selected Δt period may be 15 min, 30 min, 1 hr, or
even longer.
6Mohd Rafi, rev Mei 2011
Load Characteristic
• Terms and Definitions
c) Maximum Demand
The maximum demand of an installation or system is
the greatest of all demands which have occurred
during the specified period of time.
d) Demand Factor (DF)
The ratio of the maximum demand of a system to a
total connected load of the system.
7Mohd Rafi, rev Mei 2011
DemandConnectedTotal
DemandMaximumDF
Load Characteristic
• Terms and Definitions
e) Diversified Demand / Coincident Demand
It is the demand of the composite group ( residential,
commercial, industrial, miscellaneous) , as a whole,
of somewhat unrelated loads ( loss in transmission &
distribution) over a specified period of time.
f) Utilization Factor (Fu)
It is the ratio of the maximum demand of a system to
the rated capacity of the system.
8Mohd Rafi rev Mei 2011
capacitysystemRated
demandMaximumFu
Load Characteristic
• Terms and Definitions
g) Load Factor (FLD)
The load factor is defined as the ratio of the average
load to the maximum load during a given period.
The load factor is always less than one, because the
average load is less than maximum load.
The greater the load factor, the less will be the cost
per unit.
where: T=time, in days, weeks, months or years.
9Mohd Rafi rev Mei 2011
Tx Load Max/Peak
Served Unit
Tx Load Max/Peak
xT LoadAverage FLD
Load Characteristic
• Terms and Definitions
h) Plant Capacity Factor
It is defined the ratio of the total actual energy produced
or served over a designated period of time to the energy
that would have been produced or served if the plant or
unit had operated continously at maximum rating.
where:
E=Energy produced, kWh
C=Plant capacity/rating, kW
t=Total number of hours
10Mohd Rafi, rev Mei 2011
txC
EfactorcapacityPlant
Load Characteristic
• Terms and Definitions
i) Plant Use Factor
It is defined as the ratio of the energy produced in giventime to the maximum possible energy that could havebeen produced during the actual numbers of hours thatwas in operation
where:
E=Energy produced, kWh
C=Plant capacity, kW
t1=The actual number of hours the plant was inoperation
11Mohd Rafi rev mei 2011
1txC
EfactorusePlant
Load Characteristic
• Terms and Definitions
j) Diversity Factor , FD
It is defined as the ratio of the sum of individual
maximum demands to maximum demand on power
station.
TCD is Total Connected Demand, DF is Demand Factor
Dg = coincident max demand of group of n loads12
Mohd Rafi rev Mei 2011
g
n
i
ii
g
n
i
i
g
n
D
D
DFxTCD
D
D
D
D.......DD
demandmax Coincident
demandmaxividual Sum of indF
1121
Load Characteristic
• Terms and Definitions
k) Loss Factor , FLS
It is defined as the ratio of the average power loss to
the peak load power loss during a specified period of
time.
Coincidence factor, Fc =1/FD
l) Load Diversity, LD
It is the difference between the sum of the peaks of
two or more individual loads and the peak of the
combined load.
13Mohd Rafi rev Mei 2011
loadpeakatlossPower
losspowerAverageFLS
g
n
i
i DDLD
1
Load Characteristic
• Example 1
A generating station had a maximum load of 20,000 kW
and the units generated being 61,500,000 kWh for the
year.
Calculate load factor.
• Solution Example 1
14Mohd Rafi rev Mei 2011
%35
1002436520000
000,500,61
)()(
)(
xhoursxdaysx
kWh
hTxkWloadMax
kWhServedUnitFLD
Load Characteristic
• Example 2
A power station has two 60MW units each running for
7500 hours in a year and one 30MW unit running for
4500 hours in a year. The energy produced per year is
750x106 kWh.
Determine:
(a) Plant load factor
(b) Plant capacity factor
(c) Plant use factor.
Assume maximum demand to be 80% of the plant
capacity.
15Mohd Rafi rev Mei 2011
Load Characteristic
• Solution Example 2
a) Plant load factor
b) Plant capacity factor
16Mohd Rafi rev Mei 2011
71080101508760
10750
8760
10750
6
6
6
..xWxxh
kWhx
demandMaximum
loadAverageF
h
kWhxloadAverage
150MW30 2x60 plant powerthe ofCapacity
LD
570876010150
10750
8760 3
6
.xx
x
xplantofCapacity
generatedEnergyfactorcapacityPlant
Load Characteristic
• Solution Example 2
c) Plant use factor
Energy that can be generated by two 60MW units and
one 30MW unit
=2 units x 60MW x 7500h + 30MW x 4500h
=103.5x104MWh=1035x106kWh
17Mohd Rafi rev Mei 2011
720101035
107506
6
.kWhx
kWhxfactorusePlant
Load Characteristic
• Example 3
Assume the annual peak load of a primary feeder is
2000kW, at which the power loss i.e., total copper, or
I2R, loss is 80kW per three phase. Assuming an annual
loss factor of 0.15.
Determine:
(a) The average annual power loss
(b) The total annual energy loss due to the copper losses
of the feeder circuits.
18Mohd Rafi rev Mei 2011
Load Characteristic
• Solution Example 3
a) Average annual power loss
Average power loss = Power loss at peak load x FLS
= 80 kW x 0.15
=12 kW
b) Total annual energy loss
TAELCU = Average power loss x 8760 h
=12 kW x 8760 h
=105,120 kWh
19Mohd Rafi rev Mei 2011
Example of Transformer Sizing
• An application has been made to the utility to connect a commercial complex to the nearest distribution transformer. The distribution transformer is rated 310 kVA and the current maximum demand on this transformer is 250 kVA. The transformer is 20 years old and considering hot summer, it is suggested not to load it beyond 90% capacity. The load of the commercial complex are:
A gas station consisting of three unleaded petrol pumps, a diesel pump, and a LNG pump. Each pump is rated at 5 hp and has an efficiency of 0.9. A general purpose shop with installed load of 5 kW. A Fish and Chip shop with a connected load of 4 kW. Six street lights each rated at 100 W. The diversity factor of the pumps is 1.8. The demand factor of the general purpose shop is estimated to be 0.7. The Fish and Chip shop has a demand factor of 0.8. The diversity factor for the whole load is estimated to be 1.2. Calculate the the coincident maximum demand of the whole complex. Is it possible for this load to be connected to the existing distribution transformer?
20
21
Load Forecasting
Introduction
• Load forecasting plays an important role in power system
planning, operation and control
• Forecasting means estimating active load at various load
buses ahead of actual load occurrence.
• Planning and operational applications of load forecasting
requires a certain ‘lead time’ also called forecasting
intervals.
• A good forecast reflecting current and future trends,
tempered with good judgment, is the key to all planning,
indeed to financial success.
22Mohd Rafi rev Mei 2011
Load Forecasting
• Factors Affecting Load Forecast
23Mohd Rafi rev Mei 2011
Load Forecasting
• Nature of Forecast
24Mohd Rafi rev Mei 2011
Nature of Forecast Lead time Application
Very Short Term A few seconds to
several minutes
Generation, distribution
schedules, contingency analysis
for system security
Short Term Half an hour to a
few hours
Allocation of spinning reserve;
operational planning and unit
commitment; maintenance
scheduling
Medium Term A few days to a few
weeks
Planning for seasonal peak-
winter, summer
Long Term A few months to a
few years
Planning generation growth
Load Forecasting
• Forecasting Methodology
• Forecasting techniques may be divided into three broad
classes. Techniques may be based on extrapolation or on
correlation or on a combination of both.
Extrapolation
– Extrapolation techniques involve fitting trend curves to
basic historical data adjusted to reflect the growth trend
itself.
Correlation
– Correlation techniques of forecasting relate system loads to
various demographic and economic factor.
25Mohd Rafi rev Mei 2011
Load Growth
Introduction
• In planning to accommodate future electric energy needs,
it is necessary that an estimate of the rate at which those
needs will grow.
26Mohd Rafi rev Mei 2011
• Examples of a typical
energy requirement
projection for a certain
country
Load Growth
Growth Rates
• Suppose a certain quantity M grows at a rate that is
proportional to the amount of M that is present.
• It gives
• Where a is the constant of proportionality, known as the
per-unit growth rate. The above equation may be written
as
• Where M0 is the value of M at t=0.
27Mohd Rafi rev Mei 2011
aMdt
dM
ateMM 0
Load Growth
Growth Rates
• At any two values of time, t1 and t2, the inverse ratio of
the corresponding quantities M1 and M2 is
• Based on above equation, the doubling time td may be
obtain such that M2 = 2M1 and t2 - t1= td
28Mohd Rafi rev Mei 2011
)tt(ae
M
M12
2
1
a
.
a
lntd
69302
Load Growth
Growth Rates
• Power system planners also need to know how much
power will be demanded.
29Mohd Rafi rev Mei 2011
• The approximation equation
in this curve
• Where P0 is the peak power at
t =0, b is the per unit growth
btePP 0
Examples of the peak power demand
for a certain country over several years.
Load Growth
Growth Rates
• The area under this curve over a given period is a
measure of the energy Q consumed during that period.
30Mohd Rafi rev Mei 2011
• If the per unit growth rate has not
changed, then the energy
consumed in one doubling period
equals the energy consumed for
the entire time prior to that
doubling.
Load Growth
• Growth Rates
• Evaluating the energy Q1 consumed up to t1 and the
energy Q2 consumed during the doubling time td = t2 - t1
• Td = (ln 2/b), therefore Q2 becomes
31Mohd Rafi rev Mei 2011
100
21112 Qe
b
Pe)(
b
PQ
btbt
1
2
1
1
1
1002
001
btbtbt
t
t
btbt
t
e)e(b
PdtePQ
eb
PdtePQ
d
Load Growth
• Example 1
• Suppose that the consumption of the energy in a certain
country has a growth rate of 4 percent per year.
In how many years will the energy consumption be
tripled?
• Solution Example 1
32Mohd Rafi rev Mei 2011
years..
lnt
t.lnorethenQ
Q t.
4727040
3
040333 040
1
2
Load Growth
• Example 2
• In certain country the energy consumption is expected to
be double in 10 years.
Calculate the growth rate in percent.
• Solution Example 2
33Mohd Rafi rev Mei 2011
%.x.
a
t
lna
d
93610010
6930
2
Load Growth
• Example 3
• Assume that one of the distribution transformer of the
Riverside substation supplies three primary feeders. The
30-min annual max demands per feeder as listed as
following table, together with the power factor (PF) at the
time of annual peak load. Assume a diversity factor of
1.15 among the three feeder for both real power (P) and
reactive power (Q).
34Mohd Rafi rev Mei 2011
Feeder Demand (kW) PF
1 1800 0.95
2 2000 0.85
3 2200 0.90
Load Growth
• Example 3
a) Calculate the 30-min annual max demand on the substation
transformer in kW and in kVar
b) Find the load diversity in KW
c) Select a suitable substation transformer size if zero load growth is
expected and if the company policy permits as much as 25 % short
time overload on the distribution substation transformer. Use the
suitable standard 3-phase as follow
2500/3125 KVA self-cooled/forced air cooled
3750/4687 KVA self-cooled/forced air cooled
5000/6250 KVA self-cooled/forced air cooled
7500/9375 KVA self-cooled/forced air cooled
35EET 305 Power System Fundamental - Mohd Rafi (SoESE)
Load Growth
• Example 3
d) Now assume that the substation load will increase at aconstant percentage rate per year and will double in 10years. If the 7500/9375 KVA rated transformer isinstalled, in how many years will be loaded to its fans-on rating. Assume the load growth equation is
Pn=P0(1+g)n
where: Pn=Load at the end of the nth year
P0=Initial Load
g=Annual growth rate
n=Numbers of years
36EET 305 Power System Fundamental - Mohd Rafi (SoESE)
Load Growth
• Solution Example 3
a) Given the diversity factor FD = 1.15
Therefore, Annual maximum demand Dg,kW
37Mohd Rafi rev Mei 2011
15122002000180021 .
D
kWkWkW
D
D.......DD demandmax Coincident
demandmaxividual Sum of indF
gg
n
D
kW..
kW
.
)kWkWkW(D kW,g 395217
151
6000
151
220020001800
Load Growth
• Solution Example 3
a) Dg =5217.39kW ( in KW), in KVA, then find the power
factor angle
The total Reactive Power (Q)
38
kVar.).)(tan(
).)(tan().)(tan(tanxPQ i
i
i
79289684252200
7931200021818003
1
PF Angle
0.95 18.2
0.85 31.79
0.90 25.84
kVar..
kVar.D kVar,g 952518
151
792896
Load Growth
• Solution Example 3
a) Therefore Dg
Dg =(P2+Q2)1/2=S
= ( 52172+2518.822)1/2 = 5793.60 KVA
b) The load diversity (LD) is
39
kWkWkWDDLD g
n
i
i 783521760001
Load Growth
• Solution Example 3
c) The transformer size capacity if permits of 25% short
time overload
The maximum demand is 5793.60 KVA
The most suitable distribution transformer is 3750/4687
KVA self-cooled/ forced air cooled
40
Tx Size 25% overload Remarks
2500/3125 KVA 3125x1.25=3906.25 Under size
3750/4687 KVA 4687x1.25=5858.75 Nearest
5000/6250 KVA 6250x1.25=7812.5 Over size
7500/9375 KVA 9375x1.25=11718.75 Over size
Load Growth
• Solution Example 3
d) The term fans-on means the forced air cooled rating.
The increase annual growth rate (g) per year,
given Pn=P0(1+g)n
hence (1+g)10=2 , 1+ g =1.07177
g = 0.07177%/year
Therefore, (1.07177)n x 5793.60 KVA = 9375 KVA
Or
If the 7500/9375 KVA rated transformer is installed, it
will be loaded to its fan-on rating in about 7 years.41
Yearsor..ln
.lnn 79446
071771
61821
Costumer Billing
• Introduction
• Customer billing is done by taking the difference in
readings of the meter at two successive times, usually at
an interval of 1 month.
• The difference in readings indicates the amount of
electricity, in kilowatt hours, consumed by the customer
in that period.
• The amount is multiplied by the appropriate rate or the
series of rates and the adjustment factor, and the bill is
sent to the customer.
42
Costumer Billing
43
• Sample of
Electricity Bill
Costumer Billing
• Tariff
• ‘Electricity Tariff’ can be define as a list of fixed rateelectricity prices which has been approved by a government.
• In Malaysia the tariff for electricity are divided into 7categories as follow:
1) Domestic
2) Commercial
3) Industrial
4) Mining
5) Street Lighting
6) Specific Agriculture
7) Top up & Stand By
44
Costumer Billing
• Tariff
• Examples of Electricity Tariff in Malaysia
45
Costumer Billing
• Example 1
• Assume that the customer A, use the following and
typical , domestic tariff rate schedule.
46
Costumer Billing
• Example 1(cont)
a) Assume that an average month is 730h and find the
monthly load factor
b) Find the reasonable size of continuous KVA rating of the
distribution transformer
c) Calculate the monthly bill
d) What size of capacitor (in kVar) would rise the PF of the
customer to 0.9
47
Costumer Billing
• Solution Example 1
a) Customer A , FLD
b) Continuous KVA rating
The continuous suitable rating for the distribution
transformer is 10 KVA
48
20507308
1200.
hxkW
kWh
TxloadPeak
servedUnitFLD
kVA..
kW
Cos
PS A
A 419850
8
Costumer Billing
• Solution Example 1
c) The monthly bill
First 200kWh = 200kWh x 21.8 sen/kWh = RM43.6
Next800kWh = 800 kWh x 28.9 sen/kWh =RM 231.2
Over 1000kWh = 200 kWh x 31.2 sen/kWh = RM 62.4
The total monthly Bill= RM 337.20
d) Size of capacitor
Current PF=0.85, the kVarh value is
49
kVarh.).Cos(xSin.
kWh69743850
850
1200 1
Costumer Billing
• Solution Example 1
d) Size of capacitor (cont.)
At PF=0.9, the kVarh value is
Therefore, the capacitor size required is
50
kVarh.).Cos(xSin.
kWh1958190
90
1200 1
kVar.h
kVarh)..(220
730
1958169743
Power Factor Surcharge
Percent of
surcharge from
the current bill
Condition
1.5%For every 0.01 less than
0.85 power factor
3%For every 0.01 less than
0.75 power factor
51
52
Power Factor
• Definition of Power Factor
• Power factor is the ratio between actual (true) load power
(kW) and the apparent load power (kVA)
• It is a measure of how effectively the current is being
converted into useful work output and more particularly
is a good indicator of the effect of the load current on
the efficiency of the supply.
53
)KVA(powerloadApparent
)kW(powerloadActualpf
Power Factor
• Fundamental of Basic Electricity - The Power Triangle
54
P - kW
Q - kVar
S - kVA
KVA
kWFactorPower
QPS
22
Power Factor
• Equipment Causing Poor Power Factor
• Lightly loaded induction motor. Examples of this type of
equipment and their approximate power factor are:
70% power factor or better: Air conditioners, pumps,
center less grinders, cold header, up setter, fans or
blower
60% to 70% power factor: Induction furnaces,
standard stamping machines and weaving machines
60% power factor and below: Single-stroke presses,
automated machine tools, finish grinders, welders
55
Power Factor
• Reactive Power Problem (Motor)
• Example that a motor is rated at 10,000W at 0.8 power
factor. The resistance is 5ohm. At 415V, the motor will
require the following amount of current:
I=10000/(√3x0.8x415)=17.39A
Losses when pf =0.8 : I2R=(17.39)2(5)=1,512W
The same motor rated at 0.65 power factor will require:
I=10000/(√3x0.65x415)=21.403A
Losses when pf=0.65 : I2R=(21.403)2(5)=2290.4W
56
Power Factor
• Reactive Power Problem (Transformer)
• Example that 11/0.433 kV 1000kVA transformer has
maximum loading of 800KW and power factor of 0.45
What is the % loading of the transformer?
PF=KW/KVA=0.45
KVA(Load) = kW/PF=800/0.45=1777
%Tx Load = kVA (Load) / Tx Capacity
= (1777 / 1000 ) x 100 = 177%
57
Power Factor
• Reactive Power Problem (Transformer)
• Example that 11/0.433 kV 1000kVA transformer has
maximum loading of 800KW and power factor of 0.9
What is the % loading of the transformer?
PF=KW/KVA=0.9
KVA(Load) = kW/PF=800/0.9=888.88
%Tx Load = kVA (Load) / Tx Capacity
= (888.88 / 1000 ) x 100 = 88.88%
58
Power Factor
• Reactive Power Problem (Transformer)
• Condition 1
PF=0.45
TX Size=1000kVA
Load KVA=1777 KVA
%TX Load=177%
• Condition 2
PF=0.9
TX Size=1000kVA
Load KVA=888 KVA
%TX Load=88%
59
Power Factor
• Minimum Power Factor
• Customers are advise to maintain power factor at
minimum of 0.85
60
Power Factor
• Power Factor Improvement
61
Example Of Power Flow Diagram Of Industrial Plant
Power Factor
• Power Factor Improvement
62
Power Triangle To Illustrate Power Factor Correction
Power Factor
• Power Factor Improvement
• The amount of reactive compensation supplied by the
capacitor bank is
• Apparent power consumed by the load before adding
capacitors
• Apparent power supplied by the source after adding
capacitors
63
11
1Cos
P
PF
PS LOADLOAD
22
2Cos
P
PF
PS LOADLOAD
21 QQQCAP
Power Factor
• Power Factor Improvement
• Where PF1, and PF2 are the actual load power factor and
desired system power factors, respectively.
64
2
2
1
22
11 LOADLOAD
LOAD PPF
PPSQ
2
2
2
22
22 LOADLOAD
LOAD PPF
PPSQ
1
11
12
2
2
1 PFPFxPQ LOADCAP
Power Factor
• Example 1
• An industrial plant has an active power demand of
500kW at a power factor of 0.76 lagging. Determine the
reactive power rating of the capacitor bank required to
improve the power factor to the following:
a) 0.8 lagging
b) 0.9 lagging
c) Unity
Assume the capacitor steps are available in 50 kVar
increments
65
Power Factor
• Solution Example 1
66
1
11
12
2
2
1 PFPFxPQ LOADCAP
kVarkVar...
xkWQ)a CAP 506521800
11
760
1500
22
kVarkVar...
xkWQ)b CAP 20041851900
11
760
1500
22
kVarkVar..
xkWQ)c CAP 400642711
11
760
1500
22
Power Factor
• Example 2
Assume that a 700 kVA load has a 65% power factor. It is
desired to improve the power factor to 92%.Using the
power factor correction table (Table 1).
Determine the following:
a) The correction factor required
b) The capacitor size required
c) What would be the resulting power factor if the next
higher standard capacitor size is used. Assume the
capacitor steps are available in 50 kVar increments
67
Power Factor
• Solution Example 2
a) From correction factor table (Table 1), the correctionfactor required can be found as 0.743
b) The 700 KVA load at 65% power factor is
PL=SL x cos W
=700k x 0.65 W
=455 kW
The capacitor size necessary to improve the power factorfrom 65 to 92% can be found as
Capacitor size = PL x (Correction Factor)
=(455)(0.743)
=338.065 kVar
68
Power Factor
• Solution Example 2
c) Assume that the next higher standard capacitor size (or
rating) is selected to be 350 kVar. Therefore the resulting
new correction factor can be found from
From the table by using interpolation method, based on
original power factor (65%) and new correction factor
(0.769), refer to Table 1.
The new corrected % PF = (92)(0.1613)+(93)(0.8387)
= 92.8387 % =0.92869
7690455
350.
kW
kVar
P
RatingCapacitorStandardFactorCorrectionNew
L
70