Upload
fatih-tokgoez
View
214
Download
0
Embed Size (px)
DESCRIPTION
ch5
Citation preview
7/15/2014
1
Chapter 5: Line Model and Performance
1
2
This chapter deals with the representation and performance of
transmission lines under normal operating conditions.
Transmission lines can be represented by an equivalent circuit with
appropriate circuit parameters on a «per-phase» basis.
The terminal voltages are represented as «line-to-neutral»
The currents are represented as «phase current»
The three-phase system is reduced to an equivalent single-phase
system
The aim of transmission line is to transmit power from one end
to another over a distance with high efficiency and low voltage
regulation
7/15/2014
2
3
The transmission lines are categorized into three types
1) Short transmission line– the line length is up to 80 km.
2) Medium transmission line– the line length is between 80km to 160 km.
3) Long transmission line – the line length is more than 160 km.
4
Short Line Model
The short line model is suitable for the lines up to 80 km.
The short line model is suitable for the voltage level up to 69 kV.
The line is modeled using resistance R and inductive reactance X.
Due to smaller length and lower voltage the capacitance of the line
can be ignored.
7/15/2014
3
5
Short Line Model
Z: per-phase impedance of the short line
r: per-phase resistance per unit length
L: per-phase inductance per unit length
l: length of the line
R: per-phase resistance of the line
X: per-phase inductive reactance of the line
Receiving-end current
Sending-end voltage
Sending-end current
6
Two-port network model of short transmission line
The ABCD parameters are given as in matrix form:
7/15/2014
4
7
Voltage Regulation:
Voltage regulation of the line may be defined as the percentage change in
voltage at the receiving-end of the line (expresed as percent of full-load
voltage) in going from no-load to full-load.
Voltage regulation is a measure of voltage drop of the line and depends on the power factor of
the load.
8
Total Line Loss and Efficiency:
The total line loss is
total line losssending-end
side complex
power
receiving-end side
complex power
Transmission line
efficiency
Total real power at the
receiving-end
Total real power at the
sending-end
7/15/2014
5
9
f=60 Hz
10
Medium Line Model
The medium line model is suitable for the lines between 80-250 km.
The transmission voltage level is generally bigger than 69 kV.
Since the distance and voltage are increased, shunt capacitance
should be taken into account.
Series resistance R and inductive reactance X of the line are still
used.
7/15/2014
6
11
Nominal π-Model:
Half of the shunt capacitance may be considered to be lumped at each end of the line.
g represents the leakage current over the insulators and corona effects
Y: total shunt admittance of the line
g: shunt conductance per-unit length, generally
taken as zero under normal operating conditions
C: Line-to-neutral capacitance per unit length
l: length of the line
Z: Total series impedance of the line Nominal π-model for medium length line
12
Derivations of equations to obtain ABCD parameters:
7/15/2014
7
13
Derivations of equations to obtain ABCD parameters:
Receiving-end side voltage and current can be found
in terms of sending-end side voltage and current:
Since
14
7/15/2014
8
15
Long Line Model
For short and medium length lines, the models are obtained using lumped
parameters.
For lines longer than 250 km, the distributed parameters should be
considered for accurate solutions.
Expressions for voltage and current at any point on the line are derived.
Based on these equations an equivalent π-model is obtained.
16
Long line with distributed parameters
z: series impedance per phase per unit length
y: shunt admittance per phase per unit length
z = r + jwL
y = g + jwC
Δx = small segment
7/15/2014
9
17
Derivations of equations to obtain ABCD parameters:
KVL
KCL
1
2
Combining 1 and 2 with differentiating
Let
2nd order DE is obtained
18
Derivations of equations to obtain ABCD parameters:
The solution of the differential equation is
Propagation constant
(complex number)
Real Part
(attenuation constant)
Imaginary Part
(phase constant)
From (1)
or
Characteristic impedance
of the line
3
4
7/15/2014
10
19
Derivations of equations to obtain ABCD parameters:
To find constant A1 and A2 we need boundary conditions
V(x) = VR and I(x) = IR at x=0
From (3) and (4)
The general expressions for voltage and
current along a long transmission line
By rearranging (3) and (4)
5
20
By rearranging (5)
Derivations of equations to obtain ABCD parameters:
By recognizing the hyperbolic functions
sinh and cosh
At x = l we reach sending-end side:
V(x=l) = VS and I(x=l) = IS
Rewriting the equations in ABCD form
7/15/2014
11
21
Equivalent π model for long line
The parameters of the equivalent π model
Note that:
22
7/15/2014
12
23
When line losses are neglected (g=r=0), the characteristic impedance becomes purely resistive:
Also known as «surge impedance»
For a lossles line the following equations can be derived:
Velocity of propagation
Wavelength
When the internal flux
of the conductor is neglected
sm /7.637,795,299
Speed of light (3x108 m/s)
km5000
24
Surge Impedance Loading
Surge Impedance Loading (SIL) is the case when the line is terminated with an
impedance equal to the characteristic impedance at the receiving-end side.
For a lossless line ZC is a real number so there is no reactive power in the line.
The reactive power consumption in the line by series inductive reactance (reactive
losses) are exactly offset by reactive power supplied by shunt capacitance.
SIL for typical transmission lines varies from approximately 150 MW for 230-kV lines
to about 2000 MW for 765-kV lines.
Shunt capacitive compensation may be required to increase voltage at certain
buses for the cases where line loading is bigger than SIL.
Shunt inductive compensation may be required to decrease voltgae at certain buses
for the cases where line loading is smaller than SIL.
= since
7/15/2014
13
25
26
Thermal Limit of Transmission Lines
Thermal limit of a transmission line is defined in terms of the maximum current carrying
capacity (ampacity).
The excess amount of current flowing on the line produces heat leading to undesirable
results such as
annealing loss
gradual loss of mechanical strength of the conductor caused by temperature extremes
increase sag and decreased clearance to ground due to conductor expansion at higher
temperatures
So the transmission line can be utilized best only if it is loaded up to its thermal limit
which cannot be done normally without line compensation.
Thermal loading limit
of a line
Obtained from manufacturer’s data
7/15/2014
14
27
Maximum Power Transfer and Angle Stability
Power-angle curve of a transmission line
Stable region unstable regionFor a lossless line three-phase real power transfer
from sending-end to receiving-end side
practice
SILpu pu
28
Voltage Stability
Voltage stability is defined as “the ability of a power system to maintain steady acceptable
voltages at all buses in the system under normal operating conditions and after being subjected
to a disturbance” (Kundur, 1994).
A typical voltage-power characteristics (Kundur, 1994)
7/15/2014
15
29
A typical reactive power – voltage curves (Kundur, 1994)
30
Transmission Line Loadability Curve (Kundur, 1994)
Transmission Line Loadability Curve
7/15/2014
16
31
Transmission Line Loadability Characteristics
Loadability characteristics of transmission lines (Zhang et al., 2006)
32
SILpu pu
7/15/2014
17
33
Transmission Line Compensation
Normally transmission lines are not loaded at their surge impedance, the ideal
case in which neither reactive power is produced nor consumed in the line.
On long transmission lines, light loads less than SIL result in a voltage rise at
the receiving-end.
On long transmission lines, heavy loads greater than SIL result in a voltage dip
at the receiving-end.
Shunt reactors are widely used to reduce high voltages under light load or
open line conditions.
Shunt capacitors, static var compensators, and synchronous condensers
(very old technique) are used to boost voltage, increase power transfer and
improve system stability.
Today transmission line compensation is done using modern power electronic
based high power converters called «Flexible AC Transmission Systems»
34
Shunt Reactors
Shunt reactors are conventional solutions to compensate for the undesirable voltage
effects associated with line capacitance.
Shunt reactors are used to control voltage during low-load period.
Shunt reactors are usually unswitched.
Photo: http://kiran111.hubpages.com/hub/electrical-substation
Shunt reactor banks
7/15/2014
18
35
The amount of shunt reactive power required on a transmission line to maintain the receiving-end
voltage at a specified value can be obtained as follow:
Reactance of shunt reactor
connected at the receiving-end
Since
Solving for XLsh
If VS=VR is required
The amount of shunt reactive power
36
7/15/2014
19
37
Shunt Capacitive Compensation
Photo: http://kiran111.hubpages.com/hub/electrical-substation
Shunt capacitor banks
Shunt capacitors are used for
compensating reactive power of lagging power factor load
improving power factor
voltage control during heavy lagging power factor loads
38
Single-Line Diagram of the Thyristor controlled SVC (Static Var Compensator)
Figure: http://www.mathworks.com/help/releases/R2013b/physmod/sps/powersys/ug/pe_applications6a.gif
Operate
as a variable
shunt reactor
Operate
as a variable
shunt capacitor
7/15/2014
20
39
Single-Line Diagram of the STATCOM (Static Synchronous Compensator)
STATCOM configuration:(a) single-line diagram (b) operating modes
40
Series Capacitive Compensation
Series capacitors are connected in series with the line (at sending/receiving-end or mid-point)
To reduce the series reactance between the load and the supply point
To increase power transfer
To improve transient and steady-state stability of the power system
Series capacitors are provided with bypass circuit breaker and protective spark–gaps
Studies show that the addition of series capacitors on EHV lines can more than double
the transient stability load limit of long lines at a fraction of the cost of a new transmission line
7/15/2014
21
41
Series Capacitors
Photo:http://1.bp.blogspot.com/-VuW2DoFs420/Tg3ocZTd0yI/AAAAAAAAAMY/pZyF63u7JJY/s1600/Series-Capacitors.jpg
42
With the series capacitor switched, the power transfer over the line for a lossless line becomes:
Series and shunt compensation
XCser Series capacitor reactance
XCser / X’ Percentage compensation (25-70 % in practice)
7/15/2014
22
43
There are two drawbacks of series capactive compensation:
Protection devices are required to protect capacitors and bypass the high current produced
when a short circuits occurs in the power system.
Series capacitors can lead to subsynchronous resonance due to the resonant circuit that
can oscillate at a frequency below the normal synchronous frequency (50/60 Hz) when stilmulated
by a disturbance. Subsynchronous resonance can damage turbine-generator.
44