Project Title Client Consultant Contractor G.B.BANG S.H.YOON 006 06.08.11 Wang, Zhongshun Issue for Information T.W.KIM S.H.YOON 004 17.09.10 Wang, Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON 005 16.11.10 Wang, Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON 002 30.06.10 Wang, Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON 003 18.08.10 Wang, Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON 000 19.02.10 Wang, Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON 001 08.04.10 Wang, Zhongshun Issue for Information T.W.KIM G.B.BANG REV DATE BY: DESCRIPTION CHKD. CERT. APPD. CONVERSION OF QURAYYAH OPEN CYCLE POWER PLANT TO COMBINED CYCLE POWER PLANT PROJECT C Document Title CREATED BY: CHECKED BY: DATE STARTED: DATE COMPLETED: OPR'G. DEPT.: ENG. DEPT.: DOC. NO. REV. NO. QURAYYAH SAUDI ARABIA DEVICE SUMMARY OF STG Wang, Zhongshun T.W.KIM THIS DOCUMENT IS NOT TO BE USED FOR CONSTRUCTION OR FOR ORDERING MATERIAL UNTIL CERTIFIED AND DATED APPROVAL/CERTIFICATION INFORMATION JOB ORDER NO. 30621127 000 3PS EE-01728 006 JOB NO. PROJECT SUBDIVISION DOCUMENT TYPE CODE DOCUMENT NUMBER REV. NO. 1-0923053.01

EE 01728 1_44 R006 Device Summary of STG

Embed Size (px)

DESCRIPTION

123

Citation preview

Page 1: EE 01728 1_44 R006 Device Summary of STG

Project Title

Client

Consultant

Contractor

G.B.BANG S.H.YOON006 06.08.11 Wang,Zhongshun Issue for Information T.W.KIM

S.H.YOON

004 17.09.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON

005 16.11.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG

S.H.YOON

002 30.06.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON

003 18.08.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG

S.H.YOON

000 19.02.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON

001 08.04.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG

REV DATE BY: DESCRIPTION CHKD. CERT. APPD.

CONVERSION OF QURAYYAH OPEN CYCLE POWERPLANT TO COMBINED CYCLE POWER PLANT

PROJECT C

Document Title

CREATED BY: CHECKED BY:

DATE STARTED: DATE COMPLETED:

OPR'G. DEPT.: ENG. DEPT.:

DOC. NO. REV. NO.

QURAYYAH SAUDI ARABIA

DEVICE SUMMARY OF STG

Wang, Zhongshun T.W.KIM

THIS DOCUMENT IS NOT TO BE USED FORCONSTRUCTION OR FOR ORDERING

MATERIAL UNTIL CERTIFIED AND DATED

APPROVAL/CERTIFICATION INFORMATION

JOB ORDER NO.

30621127 000 3PS EE-01728 006

JOB NO. PROJECT SUBDIVISION DOCUMENT TYPE CODE DOCUMENT NUMBER REV. NO.

1-0923053.01

Page 2: EE 01728 1_44 R006 Device Summary of STG

SIZE DWG NO SH REV

ATHIRD ANGLE PROJECTION REVISIONS

REV DESCRIPTIONSHT/ZONE

APPROVEDDATE(YYYY-MM-DD)

THIS DOCUMENT SHALL BEREVISED IN ITS ENTIRETY.ALL SHEETS OF THISDOCUMENT ARE THE SAMEREVISION LEVEL ASINDICATED

REVISION DESCRIPTION ISFULLY STATED ON FIRSTSHEET OF DOCUMENT.

UNLESS OTHERWISE SPECIFIED

DIMENSIONS ARE IN INCHES

TOLERANCES ON

2 PL DECIMALS +-

3 PL DECIMALS +-

ANGELS +-

FRACTIONS +-

SIGNATURES DATE(YYYY-MM-DD)

DRAWN

CHECKED

ENGRG

ISSUED

GENERAL ELECTRIC COMPANY

GE Energy

APPLIED PRACTICES

SIM TO:

SIZE CAGE CODE DWG NO

ASCALE SHEET

397A3135

397A3135

NONE NONE

1 F

DM:270T811 CC:VE14

Device Summary

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.The information contained herein is GE Energy STEAM Proprietary Technical Information thatbelongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, whichhas been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving thesame to have agreed to make no duplication, or other disclosure, or use whatsoever for any, orall such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.

GE CLASS II (INTERNAL NON-CRITICAL)

g2010-02-17NESHEWAIT, ADI

NESHEWAIT, ADI

NESHEWAUIT, ADI

BENES, LINDA

C UPDATED SYSTEM 6.5A PER DCI

10008335 - UPDATED DEVICE

MOV-VBV-1 SYSTEM 5.0A PER

DCI 10012309 - ADDED GXM-

1, GXM-2, PS-212C, SP-GXM-

1,SP-GXM-2, PS-213 AND PS-

214. DCI 10014837 - UPDATED

SYSTEM 4.0 ADDED PDS-221

MS# CE37383 AN# 10012736

2010-07-27 DRAWN

LB

D MODIFIED DEVICES INFO PER

DCI 10016613 TO ADD VOLTAGE

FREQ AND PHASE . MS# CE37901

2010-08-26 DRAWN

LB

E CHANGED VOLTAGE RATINGS OF

MOV-VBV PER DCI 10024804.

MSAN CE38430.

2010-12-16 DRAWN

LB

F SYSTEM 3.5 UPDATED PER

DCI11009288 , SYSTEM 3.1

UPDATED PER DCI11006301

AN#11017536 MS#CE39774

2011-07-13 DRAWN

BENES

LINDA

ENGINEER

EDARA SIRE

1 of 44

501340847
270T811
Page 3: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

2 F

System Title

1.1 STEAM/METAL THERMOCOUPLES

1.2 AXIAL POSITION

1.3 SHELL/ROTOR EXPANSION

1.4 ECCENTRICITY

1.5 BEARING VIBRATION

1.5B STC VIBRATION MONITORS

1.6A BEARING AND DRAIN THERMOCOUPLES

1.7 EXHAUST INSTRUMENTATION

2.0 TURNING GEAR

2.1 TURNING GEAR PANEL

3.1 OIL LUBE TANK

3.4 SEAL OIL

3.5 LUBE & HYDRAULIC SKID ENCLOSURE & VENTILATION DEVICES

4.0 HYDRAULIC POWER UNIT

5.0A GLAND CONDENSERS

5.0B STEAM SEAL SYSTEM

5.0C EXHAUST HOOD SPRAY SYSTEM

6.1 SPEED/LOAD

6.2 STEAM LINE PRESSURE TRANSMITTERS

6.3 EXTRACTION/ADMISSION

6.4C COMBINED STOP AND CONTROL VALVES

6.4D COMBINED REHEAT VALVES

6.4L ADMISSION CONTROL VALVES

6.4M ADMISSION STOP VALVES

6.4R EQUALIZING VALVES

6.4S REVERSE FLOW VALVES

6.4U REVERSE FLOW DISCHARGE VALVE

6.5 MOTOR OPERATED VALVES

6.5B AIR OPERATED VALVES

6.7B TRIP PUSHBUTTONS

7.0 GENERATOR

7.5 HYDROGEN GAS SYSTEM

7.5A G70 STEAM TURBINE ENCLOSURE & SKIRT LAGGING

2 of 44

Page 4: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

3 F

NOTES

Rev A - DCI 10004482 - Changed UNITS to BARS.

Added the following devices per revised instrumentation list

REDP-1A

REDX-1A

REDP-1B

REDX-1B

DEDX-1 (DEDP-1 is already on the Instrumentation List and VE14, but the prox was omitted)

DEDP-2

DEDX-2

EP-2

EX-2

EP-3

EX-3

Note: VE14 to be revised to change tag names for the existing eccentricity probe and prox from EP to EP-1 and EX to EX-1.

Rev B Updated system 7.5 devices to identify devices that will wired to TCP VIA MODBUS PROTOCOL

Rev C . Updated system 6.5A per DCI 10008335 - Updated Device MOV-VBV-1

System 5.0A per DCI 10012309 - Added GXM-1, GXM-2, PS-212C, SP-GXM-1,SP-GXM-2, PS-213 and PS-214. DCI 10014837 - Updated System 4.0 added PDS-221

Rev D - Modified devices info per DCI 10016613 to add missing Voltage Freq and Phase

3 of 44

Page 5: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

4 F

SWITCH SETTINGSContact Condition Additional Contacts

NO- Normally open CEC

-

Additional contact:

Normally closed

Electrically common

NC- Normally closed CES

-

Additional contact:

Normally closed

Electrically separate

()- Parenthesis indicates sets of

contacts

OEC

-

Additional contact:

Normally open

Electrically common

OES

-

Additional contact:

Normally open

Electrically separate

Example: NORM=(2) NO-CEC

4 of 44

Page 6: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

5 F

Device System Settings

23HG-1 7.0 SPACE HEATER-GENERATOR2.250 KW; 480 VAC; 3 PH; 60 HZ;

23HG-2 7.0 SPACE HEATER-GENERATOR2.250 KW; 480 VAC; 3 PH; 60 HZ;

23KE-1 7.0 HEATER-GENERATOR COLLECTOR ENCLOSURE472.0 W; 120 VAC; 1 PH; 50/60 HZ;

23QB-1 3.1 SPACE HEATER-LIFT OIL PUMP MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

23QB-2 3.1 SPACE HEATER-LIFT OIL PUMP MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

39VS-101 7.0 VIBRATION SENSOR (NON-CONT) GEN COLLECTOR ENDBENTLEY NEVADA, 3300 SERIES

PROXIMITY PROBE FOR GENERATOR SHAFT

RANGE:200 MV PER MILLIINCH

39VS-102 7.0 VIBRATION SENSOR (NON-CONT) GEN COLLECTOR ENDBENTLEY NEVADA, 3300 SERIES

PROXIMITY PROBE FOR GENERATOR SHAFT

RANGE:200 MV PER MILLIINCH

39VS-91 7.0 VIBRATION SENSOR (NON-CONT) GEN COUPLING ENDBENTLEY NEVADA, 3300 SERIES

PROXIMITY PROBE FOR GENERATOR SHAFT

RANGE:200 MV PER MILLIINCH

39VS-92 7.0 VIBRATION SENSOR (NON-CONT) GEN COUPLING ENDBENTLEY NEVADA, 3300 SERIES

PROXIMITY PROBE FOR GENERATOR SHAFT

RANGE:200 MV PER MILLIINCH

45FG-40A 7.0 FIRE DETECTOR-GENERATOR COMPARTMENT125VDC

45FG-40B 7.0 FIRE DETECTOR-GENERATOR COMPARTMENT125VDC

63QB-2 3.1 BEARING LIFT OIL SUPPLY PRESSURE DECREASING: 2740+-40.00 PSIG OR 189.0+-2.759 BARG(INCREASING: 2900+-40.00 PSIG OR 200.0+-2.759 BARG)NORM=(2) NO-CEC; TO TURNING GEAR MCC

63QB-3 3.1 BEARING LIFT OIL SUPPLY PRESSURE DECREASING: 2740+-40.00 PSIG OR 189.0+-2.759 BARG(INCREASING: 2900+-40.00 PSIG OR 200.0+-2.759 BARG)NORM=(2) NO-CEC; TO TURNING GEAR MCC

63QBF-1 3.1 LIFT OIL FILTER DIFFERENTIAL PRESSUREINCREASING: 100.0+-5.000 PSIG OR 6.897+-0.3449 BARG(DECREASING: 46.00+-5.000 PSIG OR 3.173+-0.3449 BARG)

74 2.1 RELAYNORM=NC;

74-1 2.1 DC TRIPPING BLOWN FUSE MONITOR RELAYNORM=NC;FUNCTION: PROVIDE THE CONTACT FOR K-PBM

5 of 44

Page 7: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

6 F

Device System Settings

88QB-1 3.1 BEARING LIFT OIL PUMP MOTOR75.00 HP; 55.93 KW; 1800 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072

88QB-2 3.1 BEARING LIFT OIL PUMP MOTOR75.00 HP; 55.93 KW; 1800 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072

95FP-1 7.0 GENERATOR AIR GAP FLUX PROBE

96VS-1 7.0 SHAFT VOLTAGE TRANSDUCER

AIT3350 7.5 GENERATOR CONDITION TRANSMITTER4.000 MA= 0.0 INH2O OR 0.0 MBAR20.00 MA= 100.0 INH2O OR 249.2 MBARUNITS ARE IN %.

HAZARDOUS ZONE 2

PROTECTION METHOD: ``D`` - EXPLOSION PROOF.

SIGNAL TO TCP VIA MODBUS PROTOCOL

AL-201 7.5A AC LIGHT - HPIP ENCLOSURE120 VAC60HZ, 1 PHASE

AL-202 7.5A AC LIGHT - HPIP ENCLOSURE120 VAC60HZ, 1 PHASE

AL-203 7.5A AC LIGHT - HPIP ENCLOSURE120 VAC60HZ, 1 PHASE

AL-204 7.5A AC LIGHT - HPIP ENCLOSURE120 VAC60HZ, 1 PHASE

AL-301 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE

AL-302 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE

AL-303 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE

AL-304 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE

AL-305 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE

AL-306 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE

AL-501 7.5A AC LIGHT - COUPLING COMPARTMENT120 VAC60HZ, 1 PHASE

AL-502 7.5A AC LIGHT-COUPLING COMPARTMENT120 VAC60HZ, 1 PHASE

AOV-SSDV 6.5B STEAM SEAL DUMP VALVEMKVI CONTROLLED VALVE 4-20 MA POSITIONER

4 MA = VALVE CLOSE

20 MA = VALVE OPEN

HAZARDOUS ZONE: NON RATED

AOV-SSFV 6.5B STEAM SEAL FEED VALVEMKVI CONTROLLED VALVE 4-20 MA POSITIONER

4 MA = VALVE OPEN

20 MA = VALVE CLOSE

HAZARDOUS ZONE: NON RATED

6 of 44

Page 8: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

7 F

Device System Settings

AOV-WSV 6.5B EXHAUST HOOD WATER SPRAY VALVEMKVI CONTROLLED VALVE 4-20 MA POSITIONER

4 MA = VALVE CLOSE

20 MA = VALVE OPEN

HAZARDOUS ZONE: NON RATED

AR-301 3.5 AC RECEPTACLE - LUBE AND HYDRAULIC ENCLOSURE

AR-302 3.5 AC RECEPTACLE - LUBE AND HYDRAULIC ENCLOSURE

ASW-201 7.5A AC 3 WAY SWITCH - HPIP ENCLOSURE120 VAC THREE WAY LIGHT SWITCH60HZ, 1 PHASE

ASW-202 7.5A AC 3 WAY SWITCH - HPIP ENCLOSURE120 VAC THREE WAY LIGHT SWITCH60HZ, 1 PHASE

ASW-211 7.5A AC 4 WAY SWITCH - HPIP ENCLOSURE

120 VACFOUR WAY LIGHT SWITCH60HZ, 1 PHASE

ASW-212 7.5A AC 4 WAY SWITCH - HPIP ENCLOSURE

120 VACFOUR WAY LIGHT SWITCH60HZ, 1 PHASE

ASW-301 3.5 AC 3-WAY LIGHT SWITCH - LUBE AND HYDRAULIC ENCLOSURE

ASW-302 3.5 AC 3-WAY LIGHT SWITCH - LUBE AND HYDRAULIC ENCLOSURE

ASW-501 7.5A AC 3 WAY LIGHT SWITCH - COUPLING COMPARTMENT120 VAC THREE WAY LIGHT SWITCH60HZ, 1 PHASE

ASW-502 7.5A AC 3 WAY LIGHT SWITCH - COUPLING COMPARTMENT120 VAC THREE WAY LIGHT SWITCH60HZ, 1 PHASE

BPM-1 3.1 LUBE OIL PUMP MOTOR NO.1125.0 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL PUMP NO. 1

IEC 60034 & IEC 60072

BPM-2 3.1 LUBE OIL PUMP MOTOR NO.2125.0 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL PUMP NO. 2

IEC 60034 & IEC 60072

BT-GJ1-1A 7.0 BEARING METAL TEMP-GENERATOR BEARING #1TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-1

BT-GJ1-1B 7.0 BEARING METAL TEMP-GENERATOR BEARING #1TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-1

BT-GJ1-2A 7.0 BEARING METAL TEMP-GENERATOR BEARING #1TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-2

7 of 44

Page 9: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

8 F

Device System Settings

BT-GJ1-2B 7.0 BEARING METAL TEMP-GENERATOR BEARING #1TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-2

BT-GJ2-1A 7.0 BEARING METAL TEMP-GENERATOR BEARING #2TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-1

BT-GJ2-1B 7.0 BEARING METAL TEMP-GENERATOR BEARING #2TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-1

BT-GJ2-2A 7.0 BEARING METAL TEMP-GENERATOR BEARING #2TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-2

BT-GJ2-2B 7.0 BEARING METAL TEMP-GENERATOR BEARING #2TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-2

CAFM-1 3.5 COOLING AIR FAN MOTOR #16.169 HP; 4.600 KW; 1166 RPM; 460 VAC; 3 PH; 60 HZ;

CAFM-2 3.5 COOLING AIR FAN MOTOR #26.169 HP; 4.600 KW; 1166 RPM; 460 VAC; 3 PH; 60 HZ;

CB-1 2.1 CIRCUIT BREAKER FOR TURNING GEAR CONTROL POWERFUNCTION: CIRCUIT PROTECTION FOR TURNING GEAR CONTROL CIRCUIT

CFM-1 7.5A COOLING AIR FAN #1 - HP/IP ENCLOSURE3.000 HP; 1180 RPM; 460 VAC; 3 PH; 60 HZ;

CFM-2 7.5A COOLING AIR FAN #2 HP/IP ENCLOSURE3.000 HP; 1180 RPM; 460 VAC; 3 PH; 60 HZ;

CFM-3 7.5A COOLING AIR FAN #1 COUPLING COMPARTMENT1.000 HP; 1180 RPM; 460 VAC; 3 PH; 60 HZ;

CFM-4 7.5A COOLING AIR FAN #2 COUPLING COMPARTMENT1.000 HP; 1180 RPM; 460 VAC; 3 PH; 60 HZ;

CONT 3.1 IMMERSION HEATER CONTACTORFUNCTION: CONTROLS POWER TO HTR-1/2/3.

CT-1 2.1 CURRENT TRANSFORMERFUNCTION: MEASURE TURNING GEAR MOTOR CURRENT FOR DISPLAY ON LOCAL AMP METER

DEDP-1 1.3 DIFF EXPANSION DETECTOR PROBE50MM PROBEFUNCTION: MONITOR, DISPLAY, ALARM, TRIP

DEDP-2 1.3 DIFF EXPANSION DETECTOR PROBE50MM PROBE

FUNCTION: MONITOR, DISPLAY, ALARM, TRIP

DEDX-1 1.3 PROXIMITOR-DIFF EXPANSION STC MONITORRANGE: 100 - 1100 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.1

DEDX-2 1.3 PROXIMITOR-DIFF EXPANSION STC MONITORRANGE: 100 - 1100 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.2

8 of 44

Page 10: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

9 F

Device System Settings

DHCP 7.5 HYDROGEN CONTROL PANEL POWER SUPPLYHYDROGEN CONTROL PANEL SUPPLY POWER 120 VAC 60 HZ AND 600 WATTS. EQUIPMENT POWERED BY UPS. REFER TO ML-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION.

DL-301 3.5 EMERGENCY DC LIGHT - LUBE AND HYDRAULIC ENCLOSURE

DL-302 3.5 EMERGENCY DC LIGHT - LUBE AND HYDRAULIC ENCLOSURE

DT-GAC-23 7.0 GENERATOR COLLECTOR-COLD AIR100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GAH-17 7.0 GENERATOR COLLECTOR-HOT AIR100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGC-10 7.0 GENERATOR TEMP-COLD GAS COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGC-11 7.0 GENERATOR TEMP-COLD GAS COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGC-12 7.0 GENERATOR TEMP-COLD GAS COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGC-13 7.0 GENERATOR TEMP-COLD GAS COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGH-15 7.0 GENERATOR TEMP-HOT GAS COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGH-16 7.0 GENERATOR TEMP-HOT GAS COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGH-18 7.0 GENERATOR TEMP-HOT GAS COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGH-19 7.0 GENERATOR TEMP-HOT GAS COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GGK-24 7.0 GENERATOR FRAME-COMMON COLD GAS100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS; ALSO IDENTIFIED AS GTG-2

DT-GSA-34 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSA-35 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSA-36 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSA-4 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

9 of 44

Page 11: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

10 F

Device System Settings

DT-GSA-5 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSA-6 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSC-20 7.0 GENERATOR TEMP-STATOR CENTER100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS; GROUNDED;

DT-GSC-21 7.0 GENERATOR TEMP-STATOR CENTER100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS; GROUNDED;

DT-GSC-22 7.0 GENERATOR TEMP-STATOR CENTER100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS; GROUNDED;

DT-GSF-1 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSF-2 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSF-3 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSF-31 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSF-32 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

DT-GSF-33 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;

EBPM 3.1 DC EMERGENCY BRG OIL PUMP MOTOR40.00 HP; 2500 RPM; 120 VDC;FUNCTION: DRIVE EMERGENCY LUBE OIL PUMP

IEC 60034 & IEC 60072

EP-1 1.4 ECCENTRICITY PROBE8 MM PROBEFUNCTION: MONITOR AND ALARM

HAZARDOUS ZONE: 2

PROTECTION METHOD: `N` NON-SPARKING

EP-2 1.4 ECCENTRICITY PROBE8 MM PROBEFUNCTION: MONITOR AND ALARM

HAZARDOUS ZONE: 2

PROTECTION METHOD: `N` NON-SPARKING

EP-3 1.4 ECCENTRICITY PROBE8 MM PROBEFUNCTION: MONITOR AND ALARM

HAZARDOUS ZONE: 2

PROTECTION METHOD: `N` NON-SPARKING

10 of 44

Page 12: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

11 F

Device System Settings

ESL-301 3.5 ENCLOSURE SELF CLN FILTER HOUSE UNDERVOLTAGE ALARMFUNCTION: ALARM ON LOW VOLTAGE SUPPLY TO SELF CLEANING FILTER HOUSE

ESPM 3.1 EMERGENCY SEAL OIL PUMP MOTOR30.00 HP; 2500 RPM; 120 VDC;FUNCTION: DRIVE EMERGENCY LUBE OIL PUMP

IEC 60034 & IEC 60072

EX-1 1.4 PROXIMITOR-ECCENTRICITY PROBE FOR STC MONITORRANGE: 10-90 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE

HAZARDOUS ZONE: NON-RATED

EX-2 1.4 PROXIMITOR-ECCENTRICITY PROBE FOR STC MONITORRANGE: 10-90 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE

HAZARDOUS ZONE: NON-RATED

EX-3 1.4 PROXIMITOR-ECCENTRICITY PROBE FOR STC MONITORRANGE: 10-90 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE

HAZARDOUS ZONE: NON-RATED

FHPS 3.5 ENCLOSURE SELF CLEANING FILTER HOUSE POWER SUPPLY120 VAC; 1 PH; 60 HZ; 240W

FM-2996A 7.5 GAS DRYER BLOWER MOTOR.0.5000 HP; 1800 RPM; 480 VAC; 3 PH; 60 HZ;DUAL TOWER GAS DRYER BLOWER MOTOR.

0.5 HP = 0.37 KW

FM-2996B 7.5 GAS DRYER BLOWER MOTOR.0.5000 HP; 1800 RPM; 480 VAC; 3 PH; 60 HZ;DUAL TOWER GAS DRYER BLOWER MOTOR.

0.5 HP = 0.37 KW

FQIC-2950 7.5 HYDROGEN GAS FLOW TOTALIZER4.00 MA = 65.00 OR .0020.00 MA = 3000 OR 3000FUNCTION: MONITOR HYDROGEN MAKE-UP GAS CONSUMPTION.

4 MA = 65 SCFD (1.84 SCMD)

20 MA = 3000 SCFD (85 SCMF)

FE-2950 IS THE FLOW ELEMENT

POWER REQUIREMENTS 1PH, 16W, 120VAC

SIGNAL TO TCP VIA MODBUS PROTOCOL

FY-1203 6.4D RIGHT INTERCEPT VALVE SOLENOID110 VAC; 60 HZ; FUNCTION: ACTIVATE DUMP VALVE ON IV TRIGGER AND ON TEST WHEN ENERGIZED

ACTIVATE FOR AIR BLEED

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

PHASE:SINGLE

11 of 44

Page 13: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

12 F

Device System Settings

FY-1204 6.4D LEFT INTERCEPT VALVE SOLENOID110 VAC; 60 HZ; FUNCTION: ACTIVATE DUMP VALVE ON IV TRIGGER AND ON TEST WHEN ENERGIZED

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

PHASE:SINGLE

FY-1212A 6.4D RIGHT REHEAT STOP VALVE TEST SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: MOVE VALVE TO TEST POSITION ON ENERGIZE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

PHASE:SINGLE

FY-1212B 6.4D RIGHT REHEAT STOP VALVE FAST CLOSING SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: FAST CLOSE VALVE ON ENERGIZE

ACTIVATE FOR AIR BLEED

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

PHASE:SINGLE

FY-1213A 6.4D LEFT REHEAT STOP VALVE TEST SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: MOVE VALVE TO TEST POSITION ON ENERGIZE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

PHASE:SINGLE

FY-1213B 6.4D LEFT REHEAT STOP VALVE FAST CLOSING SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: FAST CLOSE VALVE ON ENERGIZE

ACTIVATE FOR AIR BLEED

PHASE:SINGLE

FY-1214 6.4R EQUALIZER VALVE SOLENOID120 VAC; 60 HZ; FUNCTION: OPEN EV#2 ON ENERGIZE VIA AIR ACTUATOR

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

FY-1215 6.4R SOLENOID VALVE-LH EQUALIZER VLV AIR ACTUATOR120 VAC; 60 HZ; FUNCTION: OPEN EV#1 ON ENERGIZE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

FY-200 6.4C STOP VALVE TEST SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: MOVE SV #1 TO TEST POS ON ENERGIZE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

PHASE: SINGLE

12 of 44

Page 14: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

13 F

Device System Settings

FY-200B 6.4C STOP VLV #1 FAST CLOSING SOL. VLV.110 VAC; 60 HZ; FUNCTION : ACTIVATE DUMP VALVE (SV#1) FOR VALVE CLOSURE AND ON TEST WHEN ENERGIZED

ACTIVATE FOR AIR BLEED

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

PHASE:SINGLE

FY-201 6.4C STOP VALVE NO.2 TEST SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: MOVE SV #2 TO TEST POS ON ENERGIZE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

PHASE:SINGLE

FY-201B 6.4C STOP VLV. NO. 2 FAST CLOSING SOL. VLV.110 VAC; 60 HZ; FUNCTION : ACTIVATE DUMP VALVE (SV#2) FOR VALVE CLOSURE AND ON TEST WHEN ENERGIZED

ACTIVATE FOR AIR BLEED

PHASE:SINGLE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

FY-203 6.4M LP ADM STOP VALVE TEST SOLENOID VALVE120 VAC; 60 HZ; 7.700 W; FUNCTION: MOVE STOP VALVE TO TEST POSITION

HAZARDOUS ZONE: NON RATED

FY-211A 6.4C CONTROL VALVE FASV LEFT OR UPPER110 VAC; 60 HZ; FUNCTION: ACTIVATE DUMP VALVE (CV#1) ON CV TRIGGER

ACTIVATE FOR AIR BLEED

HAZARDOUS ZONE: NON-RATED

PHASE:SINGLE

PROTECTION METHOD: SIMPLE

FY-211B 6.4C CONTROL VALVE FASV RIGHT OR LOWER110 VAC; 60 HZ; FUNCTION: ACTIVATE DUMP VALVE (CV#2) ON CV TRIGGER

ACTIVATE FOR AIR BLEED

HAZARDOUS ZONE: NON-RATED

PHASE:SINGLE

PROTECTION METHOD: SIMPLE

FY-220 6.4S REVERSE FLOW VALVE SOLENOID120 VAC; 60 HZ; ENERGIZE TO OPEN

HAZARDOUS ZONE: NON RATED

FY-2445 6.4U REVERSE FLOW DISCHARGE VALVE SOLENOID VALVE120 VAC; 60 HZ; FUNCTION: OPEN RFDV ON ENERGIZE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

13 of 44

Page 15: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

14 F

Device System Settings

FY-265 3.1 BRG & SEAL OIL PUMP NO.1 & NO.2 TEST SOLENOID VALVE120 VAC; 60 HZ; 42.00 W; FUNCTION: DROPS PRESSURE TO START STANDBY OIL PUMP

FY-266 3.1 EMERGENCY BRG & SEAL OIL PUMP TEST SOLENOID VALVE120 VAC; 60 HZ; 42.00 W; FUNCTION: DROPS PRESSURE TO START STANDBY OIL PUMP

FY-281 4.0 HYD FLUID PUMP TEST SOLENOID VALVE120 VAC; 60 HZ; 30 W

FUNCTION: REMOTE OR LOCAL TEST OF PUMP START CIRCUITS

HAZARDOUS AREA : NON-RATED

FY-288A 2.0 TURNING GEAR ENGAGING SOLENOID VALVE A (AIR)120 VAC; 50/60 HZ; 6.100 W; CONTROLS PROVIDED STEP DOWN TRANSFORMER PROVIDES 120V, AC, 50/60HZ REGARDLESS OF CUSTOMER SUPPLIED VOLTAGE.

FUNCTION: CAUSES ENGAGEMENT OF TURNING GEAR

FY-288B 2.0 TURNING GEAR ENGAGING SOLENOID VALVE B (AIR)120 VAC; 50/60 HZ; 6.100 W; CONTROLS PROVIDED STEP DOWN TRANSFORMER PROVIDES 120V, AC, 50/60HZ REGARDLESS OF CUSTOMER SUPPLIED VOLTAGE.

FUNCTION: CAUSES ENGAGEMENT OF TURNING GEAR

FY-2955A 7.5 CORE MONITOR SOLENOID120 VAC; 60 HZ; 1 PHASETHIS SOLENOID IS POWERED BY THE GCM-X.

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `M` - ENCAPSULATION

FY-2955B 7.5 PYROLYSATE COLLECTOR SOLENOID120 VAC; 60 HZ; 1 PHASETHIS SOLENOID IS POWERED BY THE GCM-X.

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `M` - ENCAPSULATION

FY-2971 7.5 TURBINE END SCAVENGING SOLENOID1 PHASE120 VAC; 60 HZ; THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.

SIGNAL 20SCAV1 ENERGIZES SOLENOID VALVE FY-2971 ON THE H2 CTRL PANEL TO INCREASE SCAVENGING OF TE AT LOW PURITY

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `M` - ENCAPSULATION

SIGNAL TO TCP VIA MODBUS

FY-2972 7.5 COLLECTOR END GAS SOLENOID1 PHASE120 VAC; 60 HZ; THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.

SIGNAL 20CASE1 ENERGIZES SOLENOID VALVE FY-2972 ON THE H2 CTRL PANEL TO DIRECT GEN CASING GAS TO ANALYZER 1 (QT-290A) HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `M` - ENCAPSULATION

SIGNAL TO TCP VIA MODBUS

14 of 44

Page 16: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

15 F

Device System Settings

FY-2973 7.5 COLLECTOR END SCAVENGING SOLENOID1 PHASE120 VAC; 60 HZ; THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.

SIGNAL 20SCAV2 ENERGIZES SOLENOID VALVE FY-2973 ON THE H2 CTRL PANEL TO INCREASE SCAVENGING OF CE AT LOW PURITY;HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `M` - ENCAPSULATION

SIGNAL TO TCP VIA MODBUS PROT

FY-2974 7.5 COLLECTOR END GAS SOLENOID.1 PHASE120 VAC; 60 HZ; THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.

SIGNAL 20CASE2 ENERGIZES SOLENOID VALVE FY-2974 ON THE H2 CTRL PANEL TO DIRECT GEN CASING GAS TO ANALYZER 2 (QT-290B);HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `M` - ENCAPSULATION

SIGNAL TO TCP VIA MODBUS

FY-2981 7.5 CASE, PURGE, CALIBRATION SOLENOID.1 PHASE120 VAC; 60 HZ; DE-ENERGIZED STATE ALLOWS FLOW FROM GEN CASE TO FY-2972 AND FY-2974. REFER TO SYSTEM P&ID. THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `M` - ENCAPSULATION

SIGNAL TO TCP VIA MODBUS PROTOCOL

FY-2996A 7.5 DUAL GAS DRYER TOWER 1 SOLENOID1 PHASE120 VAC; 60 HZ; POWERED BY THE GAS DRYER AND CONTROLLED THE GAS DRYER`S PLC. NO MARK VI INTERFACE.

FY-2996B 7.5 DUAL GAS DRYER TOWER 2 SOLENOID1 PHASE120 VAC; 60 HZ; POWERED BY THE GAS DRYER AND CONTROLLED THE GAS DRYER`S PLC. NO MARK VI INTERFACE.

FY-CSBV 6.5B COOLING STEAM BLOCKING VALVE SOLENOIDDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED120 VAC; 60 HZ; 2.800 W; ENERGIZE TO CLOSE AOV-CSBV

HAZARDOUS ZONE: NON RATED

FY-LRSV 6.5B LEAKOFF RE-ENTRY STOP VALVE SOLENOIDDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED120 VAC; 60 HZ; 2.800 W; ENERGIZE TO CLOSE AOV-LRSV

HAZARDOUS ZONE: NON RATED

FY2253 6.5B 1ST STAGE REHEAT COOLING VALVE SOLENOID120 VAC; 60 HZ; 2.800 W; ENERGIZE TO OPEN

HAZARDOUS ZONE: NON RATED

15 of 44

Page 17: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

16 F

Device System Settings

FY5000 4.0 ELECTRICAL TRIP SOLENOID FOR ETD-1550 OHM COIL.30 W125 VDC; FUNCTION: IF DE-ENERGIZED DROPS HYD HEADER PRESS TO STOP VLV

HAZARDOUS AREA : NON-RATED

FY5002 4.0 ELECTRICAL TRIP SOLENOID FOR ETD-2550 OHM COIL.30 W125 VDC; FUNCTION: IF DE-ENERGIZED DROPS HYD HEADER PRESS TO STOP VLV

HAZARDOUS AREA : NON-RATED

FY5004 4.0 ELECTRICAL TRIP SOLENOID FOR ETD-3550 OHM COIL.30 W125 VDC; FUNCTION: IF DE-ENERGIZED DROPS HYD HEADER PRESS TO STOP VLV

HAZARDOUS AREA : NON-RATED

GASDRYER 7.5 GAS DRYER POWER SUPPLYTHE GAS DRYER REQUIRES 480 VAC 3 PHASE 60 HZ POWER WITH A 2500 WATT LOAD. PLEASE REFER TO MLI-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION.

GCMX 7.5 CORE MONITOR WITH PYROLYSATE COLLECTORTHE CORE MONITOR/PYROLYSATE COLLECTOR REQUIRES A 120 VAC 60 HZ POWER SUPPLY AND THE POWER DRAW IS 500 WATTS. PLEASE REFER TO ML-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION.

GXM-1 5.0A GLAND EXHAUSTER BLOWER MOTOR NO.120.11 HP; 3540 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: EXHAUSTS STEAM/AIR FROM CONDENSER/SPRAY CHAMBER

HAZARDOUS ZONE: NON RATED

GXM-2 5.0A GLAND EXHAUSTER BLOWER MOTOR NO.220.11 HP; 3540 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: EXHAUSTS STEAM/AIR FROM CONDENSER/SPRAY CHAMBER

HAZARDOUS ZONE: NON RATED

HCCM 4.0 HEATING / COOLING CIRCULATION PUMP MOTOR5.000 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072

FUNCTION: DRIVES FLUID HEATING/COOLING PUMP TO MAINTAIN HYDRAULIC FLUID TEMPERATURE

HAZARDOUS AREA : NON-RATED

HFPM-A 4.0 HYDRAULIC FLUID PUMP MOTOR A.25.00 HP; 1800 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072

FUNCTION: DRIVES FLUID PUMP NO. 1

HAZARDOUS AREA : NON-RATED

HFPM-B 4.0 HYDRAULIC FLUID PUMP MOTOR B.25.00 HP; 1800 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072

FUNCTION: DRIVES FLUID PUMP NO. 2

HAZARDOUS AREA : NON-RATED

HS-288 2.1 MANUAL TURNING GEAR RUN SWITCHFUNCTION: LOCAL CONTROL SWITCH TO START AND JOG TURNING GEAR

16 of 44

Page 18: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

17 F

Device System Settings

HTR-1 3.1 OIL TANK HEATER 110.00 KW; 460 VAC; 3 PH; 60 HZ;FUNCTION: KEEP RESERVIOR TEMP FROM FALLING BELOW MINIMUM REQUIRED.

HTR-2 3.1 OIL TANK HEATER 210.00 KW; 460 VAC; 3 PH; 60 HZ;FUNCTION: KEEP RESERVIOR TEMP FROM FALLING BELOW MINIMUM REQUIRED.

HTR-3 3.1 OIL TANK HEATER 310.00 KW; 460 VAC; 3 PH; 60 HZ;FUNCTION: KEEP RESERVIOR TEMP FROM FALLING BELOW MINIMUM REQUIRED.

K-288 2.1 STOP VALVE CLOSED MULTIPLYING SIGNAL RELAYFUNCTION: PERMIT TURNING GEAR START, ENGAGE, AND OIL

K-289 2.1 MANUAL TURNING GEAR RUN SWITCH LOCKOUT CONTACTFUNCTION: ALARM IF TURNING GEAR NOT IN STANDBY

K-290 2.1 JOG MODE INDICATION ALARMFUNCTION: ALARM IF TURNING GEAR IN JOG

K-PBM 2.1 CONTACTOR MULTIPLIER FOR PBM MOTOR STARTER SIGNALFUNCTION: CONTROLS STARTING CONTACTOR FOR PIGGY BACK MOTOR

K-TGM 2.1 CONTACT MULTIPLIER FOR TGM MOTOR STARTER SIGNALFUNCTION: CONTROLS STARTING CONTACTOR FOR TURNING GEAR MOTOR

L-288 2.1 TURNING GEAR MOTOR NOT RUNNING INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION

L-289 2.1 TURNING GEAR RUNNING INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION

L-290 2.1 TURNING GEAR DISENGAGED INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION

L-291 2.1 TURNING GEAR ENGAGED INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION

L-292 2.1 TURNING GEAR REMOTE JOG ENABLED LIGHT120 VACFUNCTION: LOCAL INDICATION (ON PANEL)

L-ZSP 2.1 SAFE ENGAGE SPEED INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION

LS-232 5.0A GLAND EXHAUSTER CONDENSER CONDENSATE LEVEL HIGHSETTING: 3 INCHES (76.2 MM) ABOVE NORMAL OPERATING LEVEL

FUNCTION: MONITOR AND ALARM

HAZARDOUS ZONE: NON RATED

KKS DESIGNATION: MAW70 CL301

LS-260 3.1 LUBE OIL LEVEL IMMERSION HEATER PERMISSIVE SWITCHDECREASING: 8.0+-0.5 INCHES (203.2 MM) BELOW OPERATING OIL LEVEL

INCREASING: 7.0+-0.5 INCHES (177.8 MM) BELOW NORMAL

FUNCTION: PREVENTS HEATER OPERATION WHEN OIL LEVEL IS LOW

17 of 44

Page 19: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

18 F

Device System Settings

LSH-2990 7.5 LIQUID LEVEL DETECTOR HIGH LEVEL SWITCHNORM=(4) NO-CEC; DPDT SWITCH.

FUNCTION: ALARM WHEN FLUID ENTERS THE LIQUID LEVEL DETECTOR

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - EXPLOSION PROOF

SIGNAL TO TCP VIA MODBUS PROTOCOL

LSH-3401 7.5 SEAL OIL DRAIN HIGH LEVEL SWITCHNORM=(4) NO-CEC; DPDT SWITCH.

FUNCTION: ALARM WHEN FLUID ENTERS THE LIQUID LEVEL DETECTOR

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - EXPLOSION PROOF

SIGNAL TO TCP VIA MODBUS PROTOCOL

LSHH-2990 7.5 LIQUID LEVEL DETECTOR HIGH HIGH LEVEL SWITCHNORM=(4) NO-CEC; DPDT SWITCH.

FUNCTION: ALARM WHEN FLUID ENTERS THE LIQUID LEVEL DETECTOR

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - EXPLOSION PROOF

SIGNAL TO TCP VIA MODBUS PROTOCOL

LT-260 3.1 LUBE OIL TANK LEVEL4-20MA FOR 0-100% OF MEASURED LEVELHIGH LEVEL ALARM: 13.37 MA

NORMAL LEVEL: 12.00 MA

LOW LEVEL ALARM: 10.80 MA

LOW LOW LEVEL ALARM: 8.80 MA

BASED ON A 45`` PROBE LENGTH

LT-280 4.0 HYDRAULIC FLUID RESERVOIR LEVEL TRANSMITTER4.000 MA= 0.0 OR 0.0 20.00 MA= 100.0 OR 100.0 HIGH LEVEL ALARM: 13.37 MA

NORMAL LEVEL: 12.00 MA

LOW LEVEL ALARM: 10.80 MA

LOW LOW LEVEL ALARM: 8.80 MA

BASED ON A 45`` PROBE LENGTH

HAZARDOUS AREA : NON-RATED

LT-G1D-1A 7.0 LUBE SYSTEM TEMP-GENERATOR #1 BEARING DRAINTYPE K THERMOCOUPLE1 ELEMENT; GROUNDED; ONE HALF OF DUAL ELEMENT DEVICE - LT-G1D-1

LT-G1D-1B 7.0 LUBE SYSTEM TEMP-GENERATOR #1 BEARING DRAINTYPE K THERMOCOUPLE1 ELEMENT; GROUNDED; ONE HALF OF DUAL ELEMENT DEVICE - LT-G1D-1

LT-G2D-1A 7.0 LUBE SYSTEM TEMP-GENERATOR #2 BEARING DRAINTYPE K THERMOCOUPLE1 ELEMENT; GROUNDED; ONE HALF OF DUAL ELEMENT DEVICE - LT-G2D-1

18 of 44

Page 20: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

19 F

Device System Settings

LT-G2D-1B 7.0 LUBE SYSTEM TEMP-GENERATOR #2 BEARING DRAINTYPE K THERMOCOUPLE1 ELEMENT; GROUNDED; ONE HALF OF DUAL ELEMENT DEVICE - LT-G2D-1

ME-2996 7.5 GAS DRYER INLET HYGROMETER PROBE4.000 MA= 60.00 F OR 15.56 C20.00 MA= -60.00 F OR -51.11 CFUNCTION: PROBE FOR MEASURING INLET GAS DEW POINT ONLY. ALARM CONTACTS ARE LOCATED ON DEVICE MIC-2996

MIC-2951 7.5 DEW POINT SENSOR PROCESSOR4.0MA = -148 F OR -100C20.0MA = 68.0 F OR 20.000 CHIGH ALARM 32 F INC., HIGH-HIGH ALARM AT 68 F INC.

SIGNAL TO TCP VIA MODBUS PROTOCOL

MIC-2996 7.5 GAS DRYER DEW POINT SENSORNORM=(2) NC; CONTACT OPENS AT SET POINT; HIGH DEW POINT ALARM, SIGNAL NAME = 30DRYMH, SET AT +20 F INCREASING.

DEW POINT SENSOR FAULT, SIGNAL NAME = 30DRYFAULT

CONTACT OPENS OPEN ON GAS DRYER COMMON TROUBLE

MOV-B 6.5 STEAM SEAL DUMP BYPASS VALVE460 VAC; 3 PH; 60 HZ0.16 HP

0.8 FULL CURRENT AMPS

2.1 LOCKED ROTOR AMPS

FUNCTION: STEAM SEAL SYSTEM

HAZARDOUS ZONE: NON RATED

MOV-S1 6.5 STEAM SEAL FEED VALVE BLOCK460 VAC; 3 PH; 60 HZ0.16 HP

0.8 FULL CURRENT AMPS

2.1 LOCKED ROTOR AMPS

FUNCTION: FUNCTION: USED TO ISOLATE STEAM SEAL SYSTEM FROM MAIN STEAM

HAZARDOUS ZONE: NON RATED

MOV-S2 6.5 STEAM SEAL FEED SUPPLEMENTARY VALVE460 VAC; 3 PH; 60 HZ0.16 HP

0.8 FULL CURRENT AMPS

2.1 LOCKED ROTOR AMPS

FUNCTION: FUNCTION: AID SSFV IN MAINTAINING STEAM SEAL PRESSURE

HAZARDOUS ZONE: NON RATED

MOV-SAD-1 6.5 DRAIN VALVE-ADM CONTROL VALVE BEFORE SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP

0.8 FULL CURRENT AMPS

2.1 LOCKED ROTOR AMPS

FUNCTION: CONDENSATE DRAIN

HAZARDOUS ZONE: NON RATED

19 of 44

Page 21: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

20 F

Device System Settings

MOV-SAD-2 6.5 DRAIN VALVE-ADM CONTROL VALVE AFTER SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP

0.8 FULL CURRENT AMPS

2.1 LOCKED ROTOR AMPS

FUNCTION: CONDENSATE DRAIN

HAZARDOUS ZONE: NON RATED

MOV-SPD 6.5 DRAIN VALVE STEAM PACKING RE-ENTRY460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP

0.8 FULL CURRENT AMPS

2.1 LOCKED ROTOR AMPS

FUNCTION: CONDENSATE DRAIN

HAZARDOUS ZONE: NON RATED

MOV-SPDV-1 6.5 DRAIN VALVE MAIN STEAM LINE #1 LOW POINT460 VAC; 3 PH; 60 HZ; 1700 RPM0.37 HP1.5 FULL CURRENT AMPS

5.6 LOCKED ROTOR AMPS

FUNCTION: CONDENSATE DRAIN

MOV-SSV-1A 6.5 DRAIN VALVE MAIN STOP VALVE A BEFORE SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.37 HP

1.5 FULL CURRENT AMPS

5.6 LOCKED ROTOR AMPS

FUNCTION: CONDENSATE DRAIN

HAZARDOUS ZONE: NON RATED

MOV-SSV-1B 6.5 DRAIN VALVE MAIN STOP VALVE B BEFORE SEAT460 VAC; 3 PH; 60 HZ;1700 RPM0.37 HP1.5 FULL CURRENT AMPS

5.6 LOCKED ROTOR AMPS

FUNCTION: CONDENSATE DRAIN

HAZARDOUS ZONE: NON RATED

MOV-SSV-4A 6.5 DRAIN VALVE REHEAT STOP VALVE A AFTER SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP

0.8 FULL CURRENT AMPS

2.1 LOCKED ROTOR AMPS

FUNCTION: CONDENSATE DRAIN

HAZARDOUS ZONE: NON RATED

MOV-SSV-4B 6.5 DRAIN VALVE REHEAT STOP VALVE B AFTER SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP

0.8 FULL CURRENT AMPS

2.1 LOCKED ROTOR AMPS

FUNCTION: CONDENSATE DRAIN

HAZARDOUS ZONE: NON RATED

20 of 44

Page 22: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

21 F

Device System Settings

MOV-VBV-1 6.5 VACUUM BREAKER VALVE460 VAC, 3 PH, 60 HZ0.16 HP

0.5 FULL CURRENT AMPS

9.0 LOCKED ROTOR AMPS

FUNCTION: OPEN VLV TO BREAK CONDENSER VACUUM

HAZARDOUS ZONE: NON RATED

OCM 3.1 OIL CONDITIONER PUMP MOTOR5.000 HP; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL CONDITIONER PUMP

IEC 60034 & IEC 60072

PB-283A 6.7B CUSTOMER MOUNTED EMERGENCY TRIP PUSHBUTTONON TURBINE DECK

PB-283T 6.7B EMERGENCY TRIP PUSHBUTTON AT FRONT STANDARDFUNCTION: ALARM AND ELECTRICAL TRIP

PB-284A 6.7B EMERGENCY TRIP PUSHBUTTON AT STC/BU PANELFUNCTION: CAUSES TRIP THROUGH TRIP BUS

PB-285A 6.7B CUSTOMER TRIP BUTTON AT 2ND OIM LOCATIONFUNCTION: CAUSES TRIP THROUGH TRIP BUS

PB-286A 6.7B EMERGENCY TRIP PUSHBUTTON AT 2ND OIM LOCATIONFUNCTION: CAUSES TRIP THROUGH TRIP BUS

PB-289 2.1 LOCAL TURNING GEAR JOG PUSH BUTTONFUNCTION: PUSH TO JOG TURNING GEAR (WHEN PERMISSIVES SATISFIED)

PBM 2.0 TURNING GEAR MOTOR/PIGGY BACK MOTOR1.000 HP; 600 RPM; 460 VAC; 3 PH; 60 HZ;F.L.C. =3.9 AMP; L.R.C =10.2 AMP

FUCTION: TURN SHAFT/PRE-ENGAGEMENT OF TGM

PDS-221 4.0 PARTICULATE FILTER HIGH DIFF. PRESSUREINCREASING: 70.00+-5.000 PSIG OR 4.828+-0.3449 BARGHAZARDOUS AREA : NON-RATED

PDS-222 4.0 POLISHING FILTER HIGH DIFF PRESSUREINCREASING: 70.00+-5.000 PSIG OR 4.828+-0.3449 BARGHAZARDOUS AREA : NON-RATED

PDS-223 4.0 HEAT & COOLING PARTICULATE FILTER HIGH DIFF PRESSUREINCREASING: 70.00+-5.000 PSIG OR 4.828+-0.3449 BARGHAZARDOUS AREA : NON-RATED

PDS-287A 4.0 DUPLEX FILTER HIGH DIFF PRESSURE NO.1INCREASING: 100.0+-5.000 PSID OR 6.897+-0.3449 BARDNORM=(2) NO-OEC; FUNCTION: PROVIDES ALARM IF FILTER REQUIRES REPLACEMENT

HAZARDOUS AREA : NON-RATED

PDS-287B 4.0 DUPLEX FILTER HIGH DIFF PRESSURE NO.2INCREASING: 100.0+-5.000 PSIG OR 6.897+-0.3449 BARGNORM=(2) NO-OEC; FUNCTION: PROVIDES ALARM IF FILTER REQUIRES REPLACEMENT

HAZARDOUS AREA : NON-RATED

21 of 44

Page 23: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

22 F

Device System Settings

PDSL-3402 3.4 SEAL OIL DIFFERENTIAL PRESSURE LOW SWITCH DECREASING: 4.500 PSID OR 0.3104 BARDNORM=(2) NC-CEC; FUNCTION: ALARM

NOTE: SWITCH MUST BE COMPENSATED IN THE FIELD SINCE THE HGF AND HSF-2 SENSING LINES ARE AT DIFFERENT ELEVATIONS.

DEAD BAND = .35 PSID

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

PDSL-3406 3.4 SEAL OIL DIFF PRESSURE LOW-LOW, START DC PUMP DECREASING: 3.500 PSID OR 0.2414 BARDFUNCTION: START DC PUMP

NOTE: SWITCH MUST BE COMPENSATED IN THE FIELD SINCE THE HGF & HSF-2 SENSING LINES ARE AT DIFFERENT ELEVATIONS.

DEAD BAND = 0.35 PSID

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

PDT-216 6.3 LP ADMISSION STRAINER DIFFERENTIAL PRESSURE4.0 MA = 0.0 PSID20.0 MA = 100.0 PSID

PDT-251 5.0B STEAM SEAL DUMP VALVE DIFFERENTIAL PRESSURE TRANSMITTER4.000 MA= 0.0 PSID OR 0.0 BARD20.00 MA= 20.00 PSID OR 1.379 BARDMONITOR STEAM SEAL CONDITIONS

HAZARDOUS ZONE: NON RATED

PDT-292 7.5 GENERATOR ROTOR FAN PRESSURE DIFFERENTIAL4.000 MA= 0.0 INH2O OR 0.0 MBAR20.00 MA= 30.00 INH2O OR 74.75 MBARFUNCTION: ALARM AT 12 IN H2O (304.8 MM H2O)

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

SIGNAL TO TCP VIA MODBUS PROTOCOL

PDT-2955 7.5 CORE MONITOR FLOW TRANSMITTER4.0 MA = 0.0 INH20 OR 0.000 MBAR20.0 MA = 3.0 INH20 OR 7.4752 MBARLOW FLOW LIMIT=1.1 INH20 (27.9 MMH2O), HIGH FLOW LIMIT=1.9 INH20 (48.3 MMH2O)

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

SIGNAL TO TCP VIA MODBUS PROTOCOL

PDT-303 3.5 ENCLOSURE SELF CLN FILTER HOUSE DIFF PRESSURE4.000 MA= 0.0 INH2O OR 0.0 MBAR20.00 MA= 4.000 INH2O OR 9.967 MBARFUNCTION: MONITOR AIR FILTER DP, ALARM ON 2.1 IN H2O

PDT-3402 3.4 SEAL OIL DIFFERENTIAL PRESSURE, SEAL OIL VS GAS PRESSURE4.000 MA= 0.0 PSID OR 0.0 BARD20.00 MA= 15.00 PSID OR 1.035 BARDFUNCTION: FOR MONITORING DP THRU TURBINE CONTROLLER, DP SET TO 5.5 PSID (37.92 KPAD)

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

22 of 44

Page 24: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

23 F

Device System Settings

PS-212C 5.0A GLAND SEAL EXHAUSTER BLOWER MOTOR RUNNING DECREASING: 5.000 INH2O OR 12.46 MBARNORM=(2) NC-CES; FUNCTION: ALARM NOT RUNNING

HAZARDOUS ZONE: NON RATED

PS-213 5.0A GSC EXHAUSTER AMBIENT AIR BLEED FILTER HIGH DIFF PRES DECREASING: 13.60 INH2O OR 33.89 MBARNORM=(2) NC-CES; FUNCTION: MONITOR AND ALARM

HAZARDOUS ZONE: NON RATED

PS-214 5.0A GSC EXHAUSTER AMBIENT AIR BLEED FILTER HIGH DIFF PRES DECREASING: 13.60 INH2O OR 33.89 MBARNORM=(2) NC-CES; FUNCTION: MONITOR AND ALARM

HAZARDOUS ZONE: NON RATED

PS-263 3.1 EMERGENCY SEAL OIL PUMP RUNNING SWITCHINCREASING: 40.00+-2.000 PSIG OR 2.759+-0.1379 BARG(DECREASING: 35.00+-2.000 PSIG OR 2.414+-0.1379 BARG)NORM=(2) NO-CES; FUNCTION: SENSES EMERGENCY DC PUMP OUTPUT PRESSURE

PS-265A 3.1 LUBE OIL PUMP NO 1. AND NO 2. START DECREASING: 111.0+-4.000 PSIG OR 7.656+-0.2759 BARG(INCREASING: 123.0+-4.500 PSIG OR 8.483+-0.3104 BARG)NORM=(2) NC-CEC;

PS-266A 3.1 FUNCTION: STARTS EBOP AND ESOP DECREASING: 95.00+-4.000 PSIG OR 6.552+-0.2759 BARG(INCREASING: 107.0+-4.500 PSIG OR 7.380+-0.3104 BARG)NORM=(2) NC-CEC; FUNCTION: STARTS EMERGENCY DC LUBE OIL PUMP

PS-267A 3.1 LUBE OIL PUMP NO.1 RUNNING PRESSURE SWITCHINCREASING: 40.00+-2.000 PSIG OR 2.759+-0.1379 BARG(DECREASING: 35.00+-2.000 PSIG OR 2.414+-0.1379 BARG)NORM=(2) NO-CES; FUNCTION: SENSES PUMP NO.1 OUTPUT PRESSURE

PS-267B 3.1 LUBE OIL PUMP NO.2 RUNNING PRESSURE SWITCHINCREASING: 40.00+-2.000 PSIG OR 2.759+-0.1379 BARG(DECREASING: 35.00+-2.000 PSIG OR 2.414+-0.1379 BARG)NORM=(2) NO-CES; FUNCTION: SENSES PUMP NO.2 OUTPUT PRESSURE

PS-268 3.1 EMERGENCY LUBE OIL PUMP RUNNING PRESSURE SWITCHINCREASING: 40.00+-2.000 PSIG OR 2.759+-0.1379 BARG(DECREASING: 35.00+-2.000 PSIG OR 2.414+-0.1379 BARG)NORM=(2) NO-CES; FUNCTION: SENSES EMERGENCY DC PUMP OUTPUT PRESSURE

PS-270A 3.1 LUBE OIL LOW PRESSURE ALARM SWITCH DECREASING: 10.00+-1.000 PSIG OR 0.6897+-0.0690 BARG(INCREASING: 12.00+-1.000 PSIG OR 0.8276+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: ALARM LOW LUBE OIL PRESSURE

(10PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 25PSIG)

23 of 44

Page 25: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

24 F

Device System Settings

PS-270B 3.1 LOW LUBE OIL HEADER PRESSURE TRIP & ALARM DECREASING: 6.000+-1.000 PSIG OR 0.4138+-0.0690 BARG(INCREASING: 8.000+-1.000 PSIG OR 0.5518+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TRUB ON LOW LUBE OIL PRESSURE AND ALARMS

(6PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 21PSIG)

PS-270C 3.1 LOW LUBE OIL HEADER PRESSURE TRIP & ALARM DECREASING: 6.000+-1.000 PSIG OR 0.4138+-0.0690 BARG(INCREASING: 8.000+-1.000 PSIG OR 0.5518+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB AND ALARMS ON LOW LUBE OIL PRESSURE

(6PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 21PSIG)

PS-270D 3.1 LOW LUBE OIL HEADER PRESSURE TRIP & ALARM DECREASING: 6.000+-1.000 PSIG OR 0.4138+-0.0690 BARG(INCREASING: 8.000+-1.000 PSIG OR 0.5518+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB AND ALARMS ON LOW LUBE OIL PRESSURE

(6PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 21PSIG)

PS-270E 3.1 LIFT OIL PRESSURE PERMISSIVEINCREASING: 6.000+-1.000 PSIG OR 0.4138+-0.0690 BARG(DECREASING: 8.000+-1.000 PSIG OR 0.5518+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: PRESSURE PERMISSIVE FOR LIFT OIL PUMP

(6PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 21PSIG)

PS-271A 3.1 LUBE OIL FILTER HIGH DIFF PRESSURE ALARMINCREASING: 15.00+-0.3000 PSID OR 1.035+-0.0207 BARD(DECREASING: 11.00+-3.000 PSID OR 0.7587+-0.2069 BARD)NORM=(1) NO-CEC; FUNCTION: PROVIDES ALARM IF FILTER REQUIRES REPLACEMENT

PS-271B 3.1 LUBE OIL FILTER HIGH DIFF PRESSURE ALARMINCREASING: 15.00+-0.3000 PSID OR 1.035+-0.0207 BARD(DECREASING: 11.00+-0.3000 PSID OR 0.7587+-0.0207 BARD)NORM=(1) NO-CEC; FUNCTION: PROVIDES ALARM IF FILTER REQUIRES REPLACEMENT

PS-271G 3.1 LUBE OIL TANK LOW VACUUM SWITCH DECREASING: 4.000+-0.1000 INH2O OR 9.967+-0.2492 MBAR(INCREASING: 3.600+-0.1000 INH2O OR 8.970+-0.2492 MBAR)NORM=(1) NO-CEC;

PS-273A 3.1 DIRTY ELEMENTS ALARMSINCREASING: 25.00+-2.000 PSID OR 1.724+-0.1379 BARDFUNCTION: SIGNALS NEED FOR FILTER CHANGE ACTIVATES WHEN DIFF. PRESS. ACROSS ELEMENTS REACHES SETPOINT

PS-280A 4.0 HYD FLUID PUMP A DISCHARGE PRESSUREINCREASING: 2300 PSIG OR 158.6 BARG(DECREASING: 2200 PSIG OR 151.7 BARG)NORM=(2) NO-OES; FUNCTION: SENSES HYD PUMP A OUTPUT PRESSURE

HAZARDOUS AREA : NON-RATED

24 of 44

Page 26: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

25 F

Device System Settings

PS-280B 4.0 HYD FLUID PUMP B DISCHARGE PRESSUREINCREASING: 2300 PSIG OR 158.6 BARG(DECREASING: 2200 PSIG OR 151.7 BARG)NORM=(2) NO-OES; FUNCTION: SENSES HYD PUMP B OUTPUT PRESSURE

HAZARDOUS AREA : NON-RATED

PS-281A 4.0 LOW HYD FLUID PRESSURE ALARM DECREASING: 1950 PSIG OR 134.5 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: ALARM ON LOW HYD PRESSURE

HAZARDOUS AREA : NON-RATED

PS-281B 4.0 HYD FLUID PRESSURE LOW PUMP A START DECREASING: 1950 PSIG OR 134.5 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: STARTS STANDBY PUMP ON LOW HYD PRESSURE.

HAZARDOUS AREA : NON-RATED

PS-281C 4.0 HYD FLUID PRESSURE LOW PUMP B START DECREASING: 1950 PSIG OR 134.5 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: STARTS STANDBY PUMP ON LOW HYD PRESSURE.

HAZARDOUS AREA : NON-RATED

PS-281D 4.0 LOW HYD PRESSURE TRIP & ALARM DECREASING: 1650 PSIG OR 113.8 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB ON LOW HYD PRESSURE

HAZARDOUS AREA : NON-RATED

PS-281E 4.0 LOW HYD PRESSURE TRIP & ALARM DECREASING: 1650 PSIG OR 113.8 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB AND ALARMS ON LOW HYD PRESSURE

HAZARDOUS AREA : NON-RATED

PS-281F 4.0 LOW HYD PRESSURE TRIP & ALARM DECREASING: 1650 PSIG OR 113.8 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB AND ALARMS ON LOW HYD PRESSURE

HAZARDOUS AREA : NON-RATED

PS-282 4.0 EMERGENCY TRIP HEADER TRIPPED DECREASING: 200.0 PSIG OR 13.79 BARG(INCREASING: 300.0 PSIG OR 20.69 BARG)NORM=(2) NC-CES; FUNCTION: SENSES LOW PRESSURE IN HYD LINE TO STOP VLV

HAZARDOUS AREA : NON-RATED

PS-301 3.5 ENCLOSURE SELF CLN FILTER HOUSE LOW PRESSURE ALARM DECREASING: 60.00 PSIG OR 4.138 BARGNORM=NO;FUNCTION: ALARM ON LOW COMPRESSED AIR SUPPLY TO SELF CLEANING FILTER HOUSE

25 of 44

Page 27: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

26 F

Device System Settings

PS-302A 3.5 COOLING AIR FAN #1 RUNNING PRESSURE SWITCHINCREASING: 0.4000 INH2O OR 0.9967 MBARNORM=NO-CEC;

PS-302B 3.5 COOLING AIR FAN #2 RUNNING PRESSURE SWITCHINCREASING: 0.4000 INH2O OR 0.9967 MBARNORM=NO-CEC;

PS-303 3.5 LUBE AND HYDRAULIC ENCLOSURE LOW PRESSURE ALARM DECREASING: 0.2000 INH2O OR 0.4983 MBARNORM=NC-CEC;

PS-3404 3.4 SEAL OIL INLET PRESS LOW, START DC PUMP DECREASING: 96.00 PSIG OR 6.621 BARGFUNCTION: START DC PUMP

DEAD BAND = 0.1 TO 2.5 PSIG (5.86 TO 19.99 KPAG)

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

PSL-2930 7.5 H2 SUPPLY PRESSURE LOW DECREASING: 110.0 PSIG OR 7.587 BARG(INCREASING: 125.0 PSIG OR 8.621 BARG)NORM=NO;H2 SUPPLY PRESSURE LOW ALARM.

DEAD BAND = 0.2 TO 1 PSIG (0.0141 TO 0.070 KG/CM2G)

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

SIGNAL TO TCP VIA MODBUS PROTOCOL

PSL-2950 7.5 GENERATOR GAS PRESSURE LOW DECREASING: 58.00+-0.6000 PSIG OR 4.000+-0.0414 BARGGENERATOR CASING GAS PRESSURE LOW ALARM.

DEAD BAND = 0.2 TO 0.6 PSIG (0.0141 TO 0.0422 KG/CM2G)

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

SIGNAL TO TCP VIA MODBUS PROTOCOL

PT-071-1 6.2 1ST STAGE SHELL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: MONITOR, THRUST PROTECTION

PT-071-2 6.2 1ST STAGE SHELL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: MONITOR,THRUST PROTECTION

PT-071-3 6.2 1ST STAGE SHELL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: MONITOR, THRUST PROTECTION

PT-203-1 6.2 INLET STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: INLET STEAM PRESSURE SIGNAL FOR CONTROL AND LIMITING

PT-203-2 6.2 INLET STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: INLET STEAM PRESSURE SIGNAL FOR CONTROL AND LIMITING

26 of 44

Page 28: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

27 F

Device System Settings

PT-203-3 6.2 INLET STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: INLET STEAM PRESSURE SIGNAL FOR CONTROL AND LIMITING

PT-206-1 6.2 HOT REHEAT PRESSURE4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL

PT-206-2 6.2 HOT REHEAT PRESSURE4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL

PT-206-3 6.2 HOT REHEAT PRESSURE4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL

PT-210A 1.7 EXHAUST VACUUM TRANSMITTER NO.14.000 MA= 0.0 INHG OR 0.0 BAR20.00 MA= 30.00 INHG OR 1.003 BARFUNCTION: MONITOR, ALARM AND TRIP ON LOW EXHAUST VACUUM

PT-210B 1.7 EXHAUST VACUUM TRANSMITTER NO.24.000 MA= 0.0 INHG OR 0.0 BAR20.00 MA= 30.00 INHG OR 1.003 BARFUNCTION: MONITOR, ALARM AND TRIP ON LOW EXHAUST VACUUM

PT-210C 1.7 EXHAUST VACUUM TRANSMITTER NO.34.000 MA= 0.0 INHG OR 0.0 BAR20.00 MA= 30.00 INHG OR 1.003 BARFUNCTION: MONITOR, ALARM AND TRIP ON LOW EXHAUST VACUUM

PT-210E 5.0C EXHAUST HOOD WATER SPRAY SUPPLY AVAILABLE4.000 MA= 0.0 PSIA OR 0.0 BARA20.00 MA= 100.0 PSIA OR 6.897 BARAHAZARDOUS ZONE: NON RATED

PT-211-1 6.2 COLD REHEAT PRESSURE (HP TURB EXHAUST) #14.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL

PT-211-2 6.2 COLD REHEAT PRESSURE (HP TURB EXHAUST) #24.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL

PT-212 5.0B STEAM SEAL MANIFOLD PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 125.0 PSIG OR 8.621 BARGFUNCTION: PRESSURE SIGNAL FOR SSFV/SSDV CONTROL

HAZARDOUS ZONE: NON RATED

PT-213A 1.7 LP INLET PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARG

PT-213B 1.7 LP INLET PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARG

PT-213C 1.7 LP INLET PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARG

27 of 44

Page 29: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

28 F

Device System Settings

PT-218-1 6.3 LP ADM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARGFUNCTION: LP ADM PRESSURE CONTROL

PT-218-2 6.3 LP ADM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARGFUNCTION: LP ADM PRESSURE CONTROL

PT-218-3 6.3 LP ADM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARGFUNCTION: LP ADM PRESSURE CONTROL

PT-225-1 6.2 CROSSOVER STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARGFUNCTION: MONITOR CROSSOVER STEAM PRESSURE

PT-232 5.0A PACKING GLAND EXHAUST PRESSURE TRANSMITTER4.000 MA= 0.0 INH2O OR 0.0 MBAR20.00 MA= 50.00 INH2O OR 124.6 MBARFUNCTION: MONITOR

HAZARDOUS ZONE: NON RATED

PT-245A 6.2 REHEAT BOWL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: MONITOR, THRUST PROTECTION

PT-245B 6.2 REHEAT BOWL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: MONITOR, THRUST PROTECTION

PT-245C 6.2 REHEAT BOWL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: MONITOR, THRUST PROTECTION

PT-250 5.0B AUX STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 500.0 PSIG OR 34.49 BARGMAX EXPECTED STM SEAL SOURCE PRESSURE = 290 PSIA (20.0 BARA)

HAZARDOUS ZONE: NON RATED

PT-252 6.2 RH COOLING STEAM LINE PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: MONITOR

PT-270 3.1 BRG HEADER PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 90.00 PSIG OR 6.207 BARGFUNCTION: MONITOR

PT-281 4.0 HYD FLUID PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 3000 PSIG OR 206.9 BARGFUNCTION: MONITOR HYDRAULIC HEADER PRESSURE.

HAZARDOUS AREA : NON-RATED

28 of 44

Page 30: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

29 F

Device System Settings

PT-2950 7.5 GENERATOR GAS PRESSURE4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 100.0 PSIG OR 6.897 BARGLOW PRESSURE ALARM AT 58 PSIG (4.08 KG/CM2G).

HIGH PRESSURE ALARM AT 64 PSIG (4.50 KG/CM2G).

HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: `D` - FLAME PROOF

SIGNAL TO TCP VIA MODBUS PROTOCOL

QT-290A 7.5 CELL #1 TRANSMITTER SIGNAL4.000 MA= 70.00 OR 70.00 20.00 MA= 100.0 OR 100.0 HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: ``D`` AND ``IA``

SIGNAL TO TCP VIA MODBUS PROTOCOL

QT-290B 7.5 CELL #2 TRANSMITTER SIGNAL4.000 MA= 70.00 OR 70.00 20.00 MA= 100.0 OR 100.0 HAZARDOUS ZONE: ZONE 2

PROTECTION METHOD: ``D`` AND ``IA``

SIGNAL TO TCP VIA MODBUS PROTOCOL

REDP-1A 1.3 ROTOR EXPANSION DETECTOR PROBE50MM PROBEFUNCTION: MONITOR, DISPLAY, ALARM, AND HP DIFF EXPANSION CALCULATION

REDP-1B 1.3 ROTOR EXPANSION DETECTOR PROBE50MM PROBEFUNCTION: MONITOR, DISPLAY, ALARM, AND HP DIFF EXPANSION CALCULATION

REDX-1A 1.3 PROXIMITOR-ROTOR EXPANSIONRANGE: 100 - 1100 MILS (2.54 - 27.9 MM)FUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO. 1A

REDX-1B 1.3 PROXIMITOR-ROTOR EXPANSIONRANGE: 100 - 1100 MILS (2.54 - 27.9 MM)FUNCTION: PROVIDE HIGH FREQUENCY EXCITATION TO PROBE NO. 1B

RP-1 1.5 REFERENCE PROBEFUNCTION: PROVIDES ONCE PER REV SIGNAL

RX-1 1.5B PROXIMITOR-REFERENCE PROBE FOR VIB PHASEFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

S1 2.1 SHORTING TYPE SWITCHFUNCTION: PROVIDE THE DIRECT CONTACT FOR TGM

SEDP-1 1.3 CASE EXPANSION DETECTOR TO STC MONITORRANGE: 0-2 INCHESFUNCTION: MONITOR, DISPLAY, AND ALARM HIGH

SP-BPM-1 3.1 SPACE HEATER, LUBE OIL PUMP MOTOR #1350.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072

350W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

SP-BPM-2 3.1 SPACE HEATER, LUBE OIL PUMP MOTOR #2350.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072

350W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

29 of 44

Page 31: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

30 F

Device System Settings

SP-CAFM-1 3.5 SPACE HEATER, COOLING AIR FAN MOTOR #160.00 W; 120 VAC; 1 PH; 60 HZ;IEC MOTOR

SP-CAFM-2 3.5 SPACE HEATER, COOLING AIR FAN MOTOR #260.00 W; 120 VAC; 1 PH; 60 HZ;IEC MOTOR

SP-CFM-1 7.5A SPACE HEATER FOR MOTOR CFM-1

120 VAC; 1 PH; 60 HZ;

SP-CFM-2 7.5A SPACE HEATER FOR MOTOR CFM-2120 VAC; 1 PH; 60 HZ;

SP-CFM-3 7.5A SPACE HEATER FOR MOTOR CFM-3120 VAC; 1 PH; 60 HZ;

SP-CFM-4 7.5A SPACE HEATER FOR MOTOR CFM-4120 VAC; 1 PH; 60 HZ;

SP-EBPM 3.1 SPACE HEATER, EMRG. DC LUBE PUMP MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072

200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

SP-ESPM 3.1 SPACE HEATER, EMERG. DC SEAL PUMP MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072

200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

SP-GXM-1 5.0A SPACE HEATER, GLAND EXHAUSTER MOTOR #1180.0 W; 120 VAC; 1 PH; 60 HZ;HAZARDOUS ZONE: NON RATED

SP-GXM-2 5.0A SPACE HEATER, GLAND EXHAUSTER MOTOR #2180.0 W; 120 VAC; 1 PH; 60 HZ;HAZARDOUS ZONE: NON RATED

SP-HCCM 4.0 SPACE HEATER FOR HEATING & COOLING CIRC PUMP MOTOR.200.0 W; 120 VAC; 1 PH; 60 HZ;SPACE HEATER WATTAGE <= 200 WATTS

HAZARDOUS AREA : NON-RATED

SP-HFPM-A 4.0 SPACE HEATER FOR HYD FLUID PUMP MOTOR A.200.0 W; 120 VAC; 1 PH; 60 HZ;SPACE HEATER RATING <= 200 WATTS

HAZARDOUS AREA : NON-RATED

SP-HFPM-B 4.0 SPACE HEATER FOR HYD FLUID PUMP MOTOR B.200.0 W; 120 VAC; 1 PH; 60 HZ;SPACE HEATER RATING <= 200 WATTS

HAZARDOUS AREA : NON-RATED

SP-OCM 3.1 SPACE HEATER, OIL CONDITIONER MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072

200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

SP-PBM 2.0 SPACE HEATER, PIGGY BACK MOTOR65.00 W; 120 VAC; 1 PH; 60 HZ;

SP-TGM 2.0 SPACE HEATER, TURNING GEAR MOTOR65.00 W; 120 VAC; 1 PH; 60 HZ;

30 of 44

Page 32: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

31 F

Device System Settings

SP-VXM-1 3.1 SPACE HEATER, VAPOR EXTRACTOR #1200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072

200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

SP-VXM-2 3.1 SPACE HEATER, VAPOR EXTRACTOR #2200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072

200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.

ST-201A 6.1 PRIMARY SPEED PROBE NO.1FUNCTION: PROVIDES SPEED SIGNAL TO STC CABINET ELECTRONICS

ST-201B 6.1 PRIMARY SPEED PROBE NO.2FUNCTION: PROVIDES SPEED SIGNAL TO STC CABINET ELECTRONICS

ST-201C 6.1 PRIMARY SPEED PROBE NO.3FUNCTION: PROVIDES SPEED SIGNAL TO STC CABINET ELECTRONICS

ST-202A 6.1 EMERGENCY OVERSPEED PROBE NO.1FUNCTION: PROVIDES OVERSPEED SIGNAL TO STC CABINET ELECTRONICS

ST-202B 6.1 EMERGENCY OVERSPEED PROBE NO.2FUNCTION: PROVIDES OVERSPEED SIGNAL TO STC CABINET ELECTRONICS

ST-202C 6.1 EMERGENCY OVERSPEED PROBE NO.3FUNCTION: PROVIDES OVERSPEED SIGNAL TO STC CABINET ELECTRONICS

SV-1203A 6.4D SERVO FOR RIGHT INTERCEPT VALVE POS CONTROLRATED FLOW: 24.00 GPM AT 1000 PSID 4-WAY, 3-COIL (33 MA PER COIL)

FUNCTION: ACTUATOR FLOW CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

SV-1204A 6.4D SERVO FOR LEFT INTERCEPT VALVE POS CONTROLRATED FLOW: 24.00 GPM AT 1000 PSID 4-WAY, 3-COIL (33 MA PER COIL)

FUNCTION: ACTUATOR FLOW CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

SV-211A 6.4C INLET CONTROL VALVE SERVO VALVERATED FLOW: 24.00 GPM AT 1000 PSID 4-WAY, 3-COIL, (33 MA PER COIL)

FUNCTON: CV #1 ACTUATOR FLOW CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

SV-211B 6.4C INLET CONTROL VALVE SERVO VALVERATED FLOW: 24.00 GPM AT 1000 PSID 4-WAY, 3-COIL, (33 MA PER COIL)

FUNCTON: CV #2 ACTUATOR FLOW CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

SV-216 6.4L LP ADM VALVE (OFF TURB) SERVO VALVERATED FLOW: 25.00 GPM AT 1000 PSID (95 LPM @ 68.97 BARD)

FUNCTION: CONTROLS POS OF OFF TURB LP CONTROL VLV

HAZARDOUS ZONE: NON RATED

31 of 44

Page 33: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

32 F

Device System Settings

T1 2.1 TRANSFORMERFUNCTION: PROVIDE THE VOLTAGE FOR TURNING GEAR CIRCUIT

TAFM 4.0 TRANSFER & AUX FILTER UNIT MOTOR0.5000 HP; 1800 RPM; 120 VAC; 1 PH; 60 HZ;FUNCTION: POWERS PUMP ON HYD FLUID FILTERING SYSTEM

IEC 60034 7 IEC 60072

HAZARDOUS AREA : NON-RATED

TAFMS 4.0 TRANSFER & AUX FILTER PUMP MOTOR SWITCHFUNCTION: CONTROLS PUMP ON HYD FLUID FILTERING SYSTEM

HAZARDOUS AREA : NON-RATED

TC-2996A 7.5 DESICCANT BED #1 TEMPERATURE SWITCHINCREASING: 400.0 F OR 204.4 CNORMAL READING = 325 F +/- 25 F AT END OF HEATING CYCLE.

FUNCTION: HEATER PROTECTION

TC-2996B 7.5 DESICCANT BED #2 TEMPERATURE SWITCHINCREASING: 400.0 F OR 204.4 CNORMAL READING = 325 F +/- 25 F AT END OF HEATING CYCLE.

FUNCTION: HEATER PROTECTION

TCV-260 6.5B VALVE POSITIONER4 MA = OPEN

20 MA = CLOSED

FUNCTION: REGULATE COOLING WATER FLOW TO MAINTAIN CONSTANT LUBE OIL TEMPERATURE

HAZARDOUS ZONE: NON RATED

TDR-1 2.1 TIME DELAY ACFUNCTION: PROVIDE THE TIME DELAY FOR TG CIRCUIT

TE-200-1 1.1 INLET STEAM LINE TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START

TE-200-2 1.1 INLET STEAM LINE TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START

TE-200-3 1.1 INLET STEAM LINE TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START

TE-203A 1.1 1ST STAGE BOWL UPPER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START, WATER DETECTION

TE-203B 1.1 1ST STAGE BOWL UPPER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START, WATER DETECTION

TE-203C 1.1 1ST STAGE BOWL LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION

32 of 44

Page 34: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

33 F

Device System Settings

TE-205A 1.1 REHEAT BOWL UPPER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION

TE-205C 1.1 REHEAT BOWL LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START WATER DETECTION

TE-205D 1.1 REHEAT BOWL LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START, WATER DETECTION

TE-206-1 1.1 HOT REHEAT LINE STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START

TE-206-2 1.1 HOT REHEAT LINE STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START

TE-206-3 1.1 HOT REHEAT LINE STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START

TE-209E 1.1 CROSSOVER PIPING STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-209F 1.1 CROSSOVER PIPING STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-210A 1.7 EXHAUST STEAM THERMOCOUPLE NO.1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM AND TRIP ON HIGH TEMP

TE-210B 1.7 EXHAUST STEAM THERMOCOUPLE NO.2TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM AND TRIP ON HIGH TEMP

TE-210C 1.7 EXHAUST STEAM THERMOCOUPLE NO.3TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM AND TRIP ON HIGH TEMP

TE-211A 1.1 HP EXHAUST UPPER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION

TE-211C 1.1 HP EXHAUST LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION

33 of 44

Page 35: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

34 F

Device System Settings

TE-211D 1.1 HP EXHAUST LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION

TE-211G 1.1 HP EXHAUST STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, TRIP ON HIGH TEMP

TE-211H 1.1 HP EXHAUST STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM , TRIP ON HIGH TEMP

TE-211J 1.1 HP EXHAUST STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, TRIP ON HIGH TEMP

TE-212A-1 5.0B STEAM SEAL HEADER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

ALARM PER GEK110856

HAZARDOUS ZONE: NON RATED

TE-212A-2 5.0B STEAM SEAL HEADER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

ALARM PER GEK110856

HAZARDOUS ZONE: NON RATED

TE-212A-3 5.0B STEAM SEAL HEADER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

ALARM PER GEK110856

HAZARDOUS ZONE: NON RATED

TE-212B 5.0A GLAND SEAL EXHAUST AIR/STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

HAZARDOUS ZONE: NON RATED

TE-213G 1.7 L-1 STAGE LOWER STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, AND TRIP ON HIGH TEMP

TE-213H 1.7 L-1 STAGE LOWER STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, TRIP ON HIGH TEMP

TE-213J 1.7 L-1 STAGE LOWER STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, TRIP ON HIGH TEMP

34 of 44

Page 36: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

35 F

Device System Settings

TE-215-A 1.1 REVERSE FLOW DISCHARGE VALVE LINE TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-227-1 1.1 LP ADM STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR FOR SUPERHEAT CHECK

TE-227-2 1.1 LP ADM STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR FOR SUPERHEAT CHECK

TE-240A 1.1 IP LAST STAGE BOWL UPPER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: WATER DETECTION

TE-240B 1.1 IP LAST STAGE BOWL LOWER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: WATER DETECTION

TE-250-B 5.0B STEAM SEAL FEED TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

MAX EXPECTED TEMP FROM STM SEAL SOURCE = 554 DEG. F (290 DEG. C)

HAZARDOUS ZONE: NON RATED

TE-251E 5.0B LEAKOFF RE-ENTRY LINE TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; LOCATED DOWNSTREAM OF AOV-LRSV

FUNCTION: MONITOR

HAZARDOUS ZONE: NON RATED

TE-252 1.1 RH COOLING STEAM INLET TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-260B 3.1 LUBE OIL COOLER OUTLET TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;

TE-260H 3.1 LUBE OIL RESERVOIR TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;

TE-260J 3.1 LUBE OIL COOLER OUTLET TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;

TE-260K 3.1 LUBE OIL COOLER OUTLET TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;

TE-261A 1.6A ACTIVE THRUST BRG OIL DRAIN TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

35 of 44

Page 37: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

36 F

Device System Settings

TE-261B 1.6A INACTIVE THRUST BRG OIL DRAIN TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-262 1.6A TURBINE/GENERATOR BEARING OIL DRAIN TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-263 1.6A TURBINE/GENERATOR BEARING OIL DRAIN TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-264 1.6A TURBINE/GENERATOR BEARING OIL DRAIN TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-265 1.6A TURBINE/GENERATOR BEARING OIL DRAIN TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-271A 1.6A THRUST BRG FACE UPPER INACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

TE-271B 1.6A THRUST BRG FACE LOWER INACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

TE-271C 1.6A THRUST BRG FACE UPPER ACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

TE-271D 1.6A THRUST BRG FACE LOWER ACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

TE-271I 1.6A THRUST BRG FACE RIGHT INACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-271J 1.6A THRUST BRG FACE LEFT INACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-271K 1.6A THRUST BRG FACE RIGHT ACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

TE-271L 1.6A THRUST BRG FACE LEFT ACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR

36 of 44

Page 38: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

37 F

Device System Settings

TE-272A 1.6A TURB/GEN BRG NO.1 METAL TEMP #1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

TE-273A 1.6A TURB/GEN BRG NO.2 METAL TEMP #1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

TE-274A 1.6A TURB/GEN BRG NO.3 METAL TEMP #1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

TE-275A 1.6A TURB/GEN BRG NO.4 METAL TEMP #1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM

TE-280 4.0 HYD FLUID RESERVOIR TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR BULF RESERVOIR FLUID TEMPERATURE

ALARM AT 135F INCREASING

HAZARDOUS AREA : NON-RATED

TE-304 3.5 LUBE AND HYDRAULIC ENCLOSURE AIR TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; ALARM AT 140F

TE-HTR1 3.1 IMMERSION HEATER SHEATH TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;

TE-HTR2 3.1 IMMERSION HEATER SHEATH TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;

TE-HTR3 3.1 IMMERSION HEATER SHEATH TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;

TG-AMM 2.1 AMMETERFUNCTION: DISPLAY THE TURNING GEAR MOTOR CURRENT

TGM 2.0 TURNING GEAR MOTOR10.00 HP; 1800 RPM; 460 VAC; 3 PH; 60 HZ;F.L.C.=13.3 A; L.R.C.=81 A

FUCTION: ROTATE TURBINE ROTOR AT LOW SPEED

TR-1 3.1 TRANSFORMER FOR HEATER POWERFUNCTION: 460 VAC TO HEATER THERMOSTAT VOLTAGE

TS-260 3.1 LUBE OIL RESERVOIR IMMERSION HEATER THERMOSTAT DECREASING: 75.00+-3.000 OR 75.00+-3.000 (INCREASING: 85.00+-3.000 OR 85.00+-3.000 )FUNCTION: TURN ON HTR-1/2/3 WHEN TEMP FALLS BELOW SET POINT.

TS-280B 4.0 HYDRAULIC FLUID COOLING CONTROL SWITCHINCREASING: 120.0 F OR 48.89 C(DECREASING: 110.0 F OR 43.33 C)NORM=(2) NO-OEC; FUNCTION: STARTS FLUID COOLING; HCCM.

HAZARDOUS AREA : NON-RATED

37 of 44

Page 39: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

38 F

Device System Settings

TS-HCCM 4.0 THERMOSTAT FOR HEATING & COOLING CIRCULATION PUMP MOTOR.HAZARDOUS AREA : NON-RATED

TS-HFPM-A 4.0 THERMOSTAT FOR HYDRAULIC FLUID PUMP MOTOR A.INCREASING: 104.0+-5.000 F OR 40.00+-2.778 CHAZARDOUS AREA : NON-RATED

TS-HFPM-B 4.0 THERMOSTAT FOR HYDRAULIC FLUID PUMP MOTOR B.INCREASING: 104.0+-5.000 F OR 40.00+-2.778 CHAZARDOUS AREA : NON-RATED

VP-1X 1.5 DISPLACEMENT VIB PROBE BRG NO.1 X-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB

VP-1Y 1.5 DISPLACEMENT VIB PROBE BRG NO.1 Y-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB

VP-2X 1.5 DISPLACEMENT VIB PROBE BRG NO.2 X-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB

VP-2Y 1.5 DISPLACEMENT VIB PROBE BRG NO.2 Y-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB

VP-3X 1.5 DISPLACEMENT VIB PROBE BRG NO.3 X-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB

VP-3Y 1.5 DISPLACEMENT VIB PROBE BRG NO.3 Y-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB

VP-4X 1.5 DISPLACEMENT VIB PROBE BRG NO.4 X-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB

VP-4Y 1.5 DISPLACEMENT VIB PROBE BRG NO.4 Y-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB

VX-1X 1.5B PROXIMITOR-VIB PROBE BRG NO.1 X-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

VX-1Y 1.5B PROXIMITOR-VIB PROBE BRG NO.1 Y-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

VX-2X 1.5B PROXIMITOR-VIB PROBE BRG NO.2 X-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

VX-2Y 1.5B PROXIMITOR-VIB PROBE BRG NO.2 Y-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

VX-3X 1.5B PROXIMITOR-VIB PROBE BRG NO.3 X-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

VX-3Y 1.5B PROXIMITOR-VIB PROBE BRG NO.3 Y-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

VX-4X 1.5B PROXIMITOR-VIB PROBE BRG NO.4 X-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

VX-4Y 1.5B PROXIMITOR-VIB PROBE BRG NO.4 Y-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE

VXM-1 3.1 VAPOR EXTRACTOR MOTOR NO. 13.000 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL TANK VENT FAN

IEC 60034 & IEC 60072

VXM-2 3.1 VAPOR EXTRACTOR MOTOR NO.23.000 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL TANK VENT FAN

IEC 60034 & IEC 60072

ZE-5000A 4.0 PROXIMITY SWITCH ETD #1 - RESET20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED

38 of 44

Page 40: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

39 F

Device System Settings

ZE-5000B 4.0 PROXIMITY SWITCH ETD #1 - TRIPPED20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED

ZE-5002A 4.0 PROXIMITY SWITCH ETD #2 - RESET20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED

ZE-5002B 4.0 PROXIMITY SWITCH ETD #2 - TRIPPED20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED

ZE-5004A 4.0 PROXIMITY SWITCH ETD #3 - RESET20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED

ZE-5004B 4.0 PROXIMITY SWITCH ETD #3 - TRIPPED20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED

ZP-201A 1.2 AXIAL POS PROBE NO.1 FOR STC OR B/N MONITORINGFUNCTION: MONITOR, ALARM, AND TRIP ON THRUST BRG WEAR

ZP-201B 1.2 AXIAL POS PROBE NO.2 FOR STC OR B/N MONITORINGFUNCTION: MONITOR, ALARM, AND TRIP ON THRUST BRG WEAR

ZP-201C 1.2 AXIAL POS PROBE NO.3 FOR STC OR B/N MONITORINGFUNCTION: MONITOR, ALARM, AND TRIP ON THRUST BRG WEAR

ZPX-201A 1.2 PROXIMITOR - AXIAL POSITION PROBE NO.1FUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.1

ZPX-201B 1.2 PROXIMITOR - AXIAL POSITION PROBE NO.2FUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.2

ZPX-201C 1.2 PROXIMITOR - AXIAL POSITION PROBE NO.3FUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.3

ZS-1203C 6.4D RIGHT INTERCEPT VALVE CLOSED LIMIT SWITCHFUNCTION: CONTACTS CLOSE ON RIGHT CRV RIV CLOSE FOR CIRCUIT BREAKER

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-1204C 6.4D LEFT INTERCEPT VALVE CLOSED LIMIT SWITCHFUNCTION: CONTACTS CLOSE ON RIGHT CRV RIV CLOSE FOR CIRCUIT BREAKER

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-1212C 6.4D RIGHT RSV CLOSED LIMIT SWITCH FOR CIRCUIT BREAKERFUNCTION: CONTACTS CLOSE ON RIGHT CRV RIV CLOSE FOR CIRCUIT BREAKER

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-1213C 6.4D LEFT RSV CLOSED LIMIT SWITCH FOR CIRCUIT BREAKERFUNCTION: CONTACTS CLOSE ON RIGHT CRV RIV CLOSE FOR CIRCUIT BREAKER

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

39 of 44

Page 41: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

40 F

Device System Settings

ZS-1214A 6.4R EQUALIZER VALVE CLOSED LIMIT SWITCH (RH CRV)DPDT-DOUBLE BREAK; NORM=(2) NO-CES

FUCTON: (2) NO CONTACTS CLOSE ON EV#2 CLOSE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-1214B 6.4R EQUALIZER VLV OPEN LIMIT SWITCH (RH CRV)DPDT-DOUBLE BREAK; NORM=(2) NO-CES

FUNCTON: (2) NO CONTACTS CLOSE ON EV#2 OPEN

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-1215A 6.4R POSITION SWITCH - LH EQUALIZER VALVE CLOSED ENDDPDT-DOUBLE BREAK; NORM=(2) NO-CES

FUNCTON: (2) NO CONTACTS CLOSE ON EV#1 CLOSE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-1215B 6.4R POSITION SWITCH - LH EQUALIZER VALVE OPEN ENDDPDT-DOUBLE BREAK; NORM=(2) NO-CES

FUNCTON: (2) NO CONTACTS CLOSE ON EV#1 OPEN

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-200C 6.4C STOP VALVE NO.1 CLOSED POS SWITCH FOR CIRCUIT BREAKERFUNCTION: CONTACTS CLOSE ON SV #1 CLOSE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-201C 6.4C STOP VALVE NO.2 CLOSED POS SWITCH FOR CIRCUIT BREAKERFUNCTION: CONTACTS CLOSE ON SV #2 CLOSE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-203A 6.4M LP ADM STOP VALVE NO.1 CLOSED POS LIMIT SWITCHFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS CLOSED

HAZARDOUS ZONE: NON RATED

ZS-203B 6.4M LP ADM STOP VALVE NO.1 OPEN POS LIMIT SWITCHFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS OPEN

HAZARDOUS ZONE: NON RATED

ZS-203C 6.4M LP ADM STOP VALVE NO.1 CLOSED POS SWITCH FOR BREAKERFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS CLOSED

HAZARDOUS ZONE: NON RATED

ZS-203D 6.4M LP ADM STOP VALVE NO.1 TEST POS LIMIT SWITCHFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS IN TEST POS

HAZARDOUS ZONE: NON RATED

ZS-203E 6.4M LP ADM STOP VALVE NO.1 CLOSED POS FOR BREAKERFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS CLOSED

HAZARDOUS ZONE: NON RATED

ZS-211AC 6.4C CONTROL VALVE NO.1 CLOSED POSITION SWITCHFUNCTION : CONTACTS CLOSE ON CV#1 CLOSE FOR CIRCUIT BREAKER

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

40 of 44

Page 42: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

41 F

Device System Settings

ZS-211BC 6.4C CONTROL VALVE NO.2 CLOSED POSITION SWITCHFUNCTION : CONTACTS CLOSE ON CV#2 CLOSE FOR CIRCUIT BREAKER

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-216 6.4L FUNCTION``LP ADM VALVE CLOSED POS SWITCHFUNCTION: PROVIDES SIGNAL WHEN CONTROL VLV IS CLOSED

HAZARDOUS ZONE: NON RATED

ZS-220A 6.4S REVERSE FLOW VALVE CLOSED LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE CLOSED

HAZARDOUS ZONE: NON RATED

ZS-220B 6.4S REVERSE FLOW VALVE OPEN LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE OPEN

HAZARDOUS ZONE: NON RATED

ZS-2445A 6.4U REVERSE FLOW DISCHARGE VALVE CLOSED LIMIT SWITCHDPDT-DOUBLE BREAK; NORM=(2) NO-CES

FUNCTION: (2) NO CONTACTS CLOSE ON RFDV CLOSE

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-2445B 6.4U REVERSE FLOW DISCHARGE VALVE OPEN LIMIT SWITCHDPDT-DOUBLE BREAK; NORM=(2) NO-CES

FUNCTION: (2) NO CONTACTS CLOSE ON RFDV OPEN

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZS-260C 3.1 LIFT OIL LIMIT SWITCH- PERMISSIVE TO STARTFUNCTION: INDICATES PUMP SUCTION SIDE ISOLATION VALVE IS OPEN.

ZS-260D 3.1 LIFT OIL LIMIT SWITCH- PERMISSIVE TO STARTFUNCTION: INDICATES PUMP SUCTION SIDE ISOLATION VALVE IS OPEN.

ZS-280A 4.0 INDICATES VALVE POSITIONPOSITION SWITCHFUNCTION: INDICATES SUCTION SHUT OFF VALVE A IS FULLY OPEN

HAZARDOUS AREA : NON-RATED

ZS-280B 4.0 INDICATES VALVE POSITIONPOSITION SWITCHFUNCTION: INDICATES SUCTION SHUT OFF VALVE B IS FULLY OPEN

HAZARDOUS AREA : NON-RATED

ZS-288 2.0 TURNING GEAR ENGAGED POSITION SWITCH3 N.C. & 3 N.O. CONTACTS; 20 A

FUCTION: INDICATES TURNING GEAR ENGAGED

(NOTE: ALWAYS 120VAC, 50/60HZ RATED)

CONTROLS PROVIDED STEP DOWN TRANSFORMER PROVIDES 120V,AC, 50/60HZ REGARDLESS OF CUSTOMER SUPPLIED VOLTAGE

ZS-289 2.0 TURNING GEAR DISENGAGED POSITION SWITCH2 N.C. & 2 N.O. CONTACTS; 120 VAC; 20 A

FUCTION: INDICATES TURNING GEAR DISENGAGED

(NOTE: ALWAYS 120VAC, 50/60HZ RATED)

CONTROLS PROVIDED STEP DOWN TRANSFORMER PROVIDES 120V,AC, 50/60HZ REGARDLESS OF CUSTOMER SUPPLIED VOLTAGE

41 of 44

Page 43: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

42 F

Device System Settings

ZS-2996 7.5 DUAL GAS DRYER PLC`S LIMIT SWITCHTHIS LIMIT SWITCH IS POWERED BY THE GAS DRYER AND FOR THE GAS DRYER`S ON BASE PLC. THE PLC AND LIMIT SWITCH DO NOT TALK WITH THE MARK VI, INTERNALLY CONTROLLED.

ZS-CSBV-C 6.5B COOLING STEAM BLOCKING VALVE CLOSED POSITION SWITCHNORM=(1) NO; DPDT; CONTACT CLOSED WHEN VALVE CLOSED

HAZARDOUS ZONE: NON RATED

ZS-CSBV-O 6.5B COOLING STEAM BLOCKING VALVE OPEN POSITION SWITCHNORM=(1) NO; DPDT; CONTACT CLOSED WHEN VALVE OPEN

HAZARDOUS ZONE: NON RATED

ZS-LRSV-C 6.5B LEAKOFF RE-ENTRY STOP VALVE CLOSED POSITION LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE CLOSED

HAZARDOUS ZONE: NON RATED

ZS-LRSV-O 6.5B LEAKOFF RE-ENTRY STOP VALVE OPEN POSITION LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE OPEN

HAZARDOUS ZONE: NON RATED

ZSC2253 6.5B 1ST STG REHEAT COOLING VLV CLOSED POSITION LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE CLOSED

HAZARDOUS ZONE: NON RATED

ZSO2253 6.5B 1ST STG REHEAT COOLING VLV OPEN POSITION LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE OPEN

HAZARDOUS ZONE: NON RATED

ZT-1203-1 6.4D RIGHT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ

FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-1203-2 6.4D RIGHT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ

FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-1203-3 6.4D RIGHT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ

FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-1204-1 6.4D LEFT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ

FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

42 of 44

Page 44: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

43 F

Device System Settings

ZT-1204-2 6.4D LEFT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ

FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-1204-3 6.4D LEFT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ

FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-1212 6.4D RIGHT REHEAT STOP VALVE POS DETECTORONE(1) MAGNETO RESTRICTIVE DEVICE, POWER SUPPLY 24 VDC/150 MA

OUTPUT: 4-20MA (INCREASING CURRENT TO OPEN)

FUNCTION : POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-1213 6.4D LEFT REHEAT STOP VALVE POS DETECTORONE(1) MAGNETO RESTRICTIVE DEVICE, POWER SUPPLY 24 VDC/150 MA

OUTPUT: 4-20MA (INCREASING CURRENT TO OPEN)

FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-200-1 6.4C STOP VALVE POSITION DETECTORONE(1) MAGNETO RESTRICTIVE DEVICE, POWER SUPPLY 24 VDC/150 MA

OUTPUT: 4-20MA (INCREASING CURRENT TO OPEN).

FUNCTION : POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-201-1 6.4C STOP VALVE POSITION DETECTORONE(1) MAGNETO RESTRICTIVE DEVICE, POWER SUPPLY 24 VDC/150 MA

OUTPUT: 4-20MA (INCREASING CURRENT TO OPEN).

FUNCTION : POSITION SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-211A-1 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ

FUNCTION: POS SIGNAL FOR CV #1 MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-211A-2 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ

FUNCTION: POS SIGNAL FOR CV #1 MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

43 of 44

Page 45: EE 01728 1_44 R006 Device Summary of STG

© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information

GE CLASS II (INTERNAL NON-CRITICAL)

SIZE DWG NO SH REV

A

GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO

AGE EnergygDRAWN

ISSUED SCALE SHEET

397A3135

397A3135

NESHEWAIT, ADI 2010-02-17

BENES, LINDA NONE

44 F

Device System Settings

ZT-211A-3 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ

FUNCTION: POS SIGNAL FOR CV #1 MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-211B-1 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ

FUNCTION: POS SIGNAL FOR CV #2 MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-211B-2 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ

FUNCTION: POS SIGNAL FOR CV #2 MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-211B-3 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ

FUNCTION: POS SIGNAL FOR CV #2 MONITORING AND CONTROL

HAZARDOUS ZONE: NON-RATED

PROTECTION METHOD: SIMPLE

ZT-216-1 6.4L LP ADM VALVE (OFF TURB) POS DETECTORFUNCTION: POS SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON RATED

ZT-216-2 6.4L LP ADM VALVE (OFF TURB) POS DETECTORFUNCTION: POS SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON RATED

ZT-216-3 6.4L LP ADM VALVE (OFF TURB) POS DETECTORFUNCTION: POS SIGNAL FOR MONITORING AND CONTROL

HAZARDOUS ZONE: NON RATED

ZT-SSDV 6.5B AOV-SSDV POSITION TRANSMITTER4 MA = 0% STROKE

20 MA = 100% STROKE

4-20 MA POSITION FEEDBACK

``2-WIRE`` TYPE

HAZARDOUS ZONE: NON RATED

ZT-SSFV 6.5B AOV-SSFV POSITION TRANSMITTER4 MA = 0% STROKE

20 MA = 100% STROKE

4-20 MA POSITION FEEDBACK

``2-WIRE`` TYPE

HAZARDOUS ZONE: NON RATED

ZT-WSV 6.5B AOV-WSV POSITION TRANSMITTER4 MA = 0% STROKE

20 MA = 100% STROKE

4-20 MA POSITION FEEDBACK

``2-WIRE`` TYPE

HAZARDOUS ZONE: NON RATED

44 of 44