Project Title
Client
Consultant
Contractor
G.B.BANG S.H.YOON006 06.08.11 Wang,Zhongshun Issue for Information T.W.KIM
S.H.YOON
004 17.09.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON
005 16.11.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG
S.H.YOON
002 30.06.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON
003 18.08.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG
S.H.YOON
000 19.02.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG S.H.YOON
001 08.04.10 Wang,Zhongshun Issue for Information T.W.KIM G.B.BANG
REV DATE BY: DESCRIPTION CHKD. CERT. APPD.
CONVERSION OF QURAYYAH OPEN CYCLE POWERPLANT TO COMBINED CYCLE POWER PLANT
PROJECT C
Document Title
CREATED BY: CHECKED BY:
DATE STARTED: DATE COMPLETED:
OPR'G. DEPT.: ENG. DEPT.:
DOC. NO. REV. NO.
QURAYYAH SAUDI ARABIA
DEVICE SUMMARY OF STG
Wang, Zhongshun T.W.KIM
THIS DOCUMENT IS NOT TO BE USED FORCONSTRUCTION OR FOR ORDERING
MATERIAL UNTIL CERTIFIED AND DATED
APPROVAL/CERTIFICATION INFORMATION
JOB ORDER NO.
30621127 000 3PS EE-01728 006
JOB NO. PROJECT SUBDIVISION DOCUMENT TYPE CODE DOCUMENT NUMBER REV. NO.
1-0923053.01
SIZE DWG NO SH REV
ATHIRD ANGLE PROJECTION REVISIONS
REV DESCRIPTIONSHT/ZONE
APPROVEDDATE(YYYY-MM-DD)
THIS DOCUMENT SHALL BEREVISED IN ITS ENTIRETY.ALL SHEETS OF THISDOCUMENT ARE THE SAMEREVISION LEVEL ASINDICATED
REVISION DESCRIPTION ISFULLY STATED ON FIRSTSHEET OF DOCUMENT.
UNLESS OTHERWISE SPECIFIED
DIMENSIONS ARE IN INCHES
TOLERANCES ON
2 PL DECIMALS +-
3 PL DECIMALS +-
ANGELS +-
FRACTIONS +-
SIGNATURES DATE(YYYY-MM-DD)
DRAWN
CHECKED
ENGRG
ISSUED
GENERAL ELECTRIC COMPANY
GE Energy
APPLIED PRACTICES
SIM TO:
SIZE CAGE CODE DWG NO
ASCALE SHEET
397A3135
397A3135
NONE NONE
1 F
DM:270T811 CC:VE14
Device Summary
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved.The information contained herein is GE Energy STEAM Proprietary Technical Information thatbelongs to the General Electric Company, GE Energy (USA), LLC and/or their affiliates, whichhas been provided solely for the express reason of restricted private use. All persons, firms, or corporations who receive such information shall be deemed by the act of their receiving thesame to have agreed to make no duplication, or other disclosure, or use whatsoever for any, orall such information except as expressly authorized in writing by the General Electric Company,GE Energy (USA), LLC and/or its affiliates.
GE CLASS II (INTERNAL NON-CRITICAL)
g2010-02-17NESHEWAIT, ADI
NESHEWAIT, ADI
NESHEWAUIT, ADI
BENES, LINDA
C UPDATED SYSTEM 6.5A PER DCI
10008335 - UPDATED DEVICE
MOV-VBV-1 SYSTEM 5.0A PER
DCI 10012309 - ADDED GXM-
1, GXM-2, PS-212C, SP-GXM-
1,SP-GXM-2, PS-213 AND PS-
214. DCI 10014837 - UPDATED
SYSTEM 4.0 ADDED PDS-221
MS# CE37383 AN# 10012736
2010-07-27 DRAWN
LB
D MODIFIED DEVICES INFO PER
DCI 10016613 TO ADD VOLTAGE
FREQ AND PHASE . MS# CE37901
2010-08-26 DRAWN
LB
E CHANGED VOLTAGE RATINGS OF
MOV-VBV PER DCI 10024804.
MSAN CE38430.
2010-12-16 DRAWN
LB
F SYSTEM 3.5 UPDATED PER
DCI11009288 , SYSTEM 3.1
UPDATED PER DCI11006301
AN#11017536 MS#CE39774
2011-07-13 DRAWN
BENES
LINDA
ENGINEER
EDARA SIRE
1 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
2 F
System Title
1.1 STEAM/METAL THERMOCOUPLES
1.2 AXIAL POSITION
1.3 SHELL/ROTOR EXPANSION
1.4 ECCENTRICITY
1.5 BEARING VIBRATION
1.5B STC VIBRATION MONITORS
1.6A BEARING AND DRAIN THERMOCOUPLES
1.7 EXHAUST INSTRUMENTATION
2.0 TURNING GEAR
2.1 TURNING GEAR PANEL
3.1 OIL LUBE TANK
3.4 SEAL OIL
3.5 LUBE & HYDRAULIC SKID ENCLOSURE & VENTILATION DEVICES
4.0 HYDRAULIC POWER UNIT
5.0A GLAND CONDENSERS
5.0B STEAM SEAL SYSTEM
5.0C EXHAUST HOOD SPRAY SYSTEM
6.1 SPEED/LOAD
6.2 STEAM LINE PRESSURE TRANSMITTERS
6.3 EXTRACTION/ADMISSION
6.4C COMBINED STOP AND CONTROL VALVES
6.4D COMBINED REHEAT VALVES
6.4L ADMISSION CONTROL VALVES
6.4M ADMISSION STOP VALVES
6.4R EQUALIZING VALVES
6.4S REVERSE FLOW VALVES
6.4U REVERSE FLOW DISCHARGE VALVE
6.5 MOTOR OPERATED VALVES
6.5B AIR OPERATED VALVES
6.7B TRIP PUSHBUTTONS
7.0 GENERATOR
7.5 HYDROGEN GAS SYSTEM
7.5A G70 STEAM TURBINE ENCLOSURE & SKIRT LAGGING
2 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
3 F
NOTES
Rev A - DCI 10004482 - Changed UNITS to BARS.
Added the following devices per revised instrumentation list
REDP-1A
REDX-1A
REDP-1B
REDX-1B
DEDX-1 (DEDP-1 is already on the Instrumentation List and VE14, but the prox was omitted)
DEDP-2
DEDX-2
EP-2
EX-2
EP-3
EX-3
Note: VE14 to be revised to change tag names for the existing eccentricity probe and prox from EP to EP-1 and EX to EX-1.
Rev B Updated system 7.5 devices to identify devices that will wired to TCP VIA MODBUS PROTOCOL
Rev C . Updated system 6.5A per DCI 10008335 - Updated Device MOV-VBV-1
System 5.0A per DCI 10012309 - Added GXM-1, GXM-2, PS-212C, SP-GXM-1,SP-GXM-2, PS-213 and PS-214. DCI 10014837 - Updated System 4.0 added PDS-221
Rev D - Modified devices info per DCI 10016613 to add missing Voltage Freq and Phase
3 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
4 F
SWITCH SETTINGSContact Condition Additional Contacts
NO- Normally open CEC
-
Additional contact:
Normally closed
Electrically common
NC- Normally closed CES
-
Additional contact:
Normally closed
Electrically separate
()- Parenthesis indicates sets of
contacts
OEC
-
Additional contact:
Normally open
Electrically common
OES
-
Additional contact:
Normally open
Electrically separate
Example: NORM=(2) NO-CEC
4 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
5 F
Device System Settings
23HG-1 7.0 SPACE HEATER-GENERATOR2.250 KW; 480 VAC; 3 PH; 60 HZ;
23HG-2 7.0 SPACE HEATER-GENERATOR2.250 KW; 480 VAC; 3 PH; 60 HZ;
23KE-1 7.0 HEATER-GENERATOR COLLECTOR ENCLOSURE472.0 W; 120 VAC; 1 PH; 50/60 HZ;
23QB-1 3.1 SPACE HEATER-LIFT OIL PUMP MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
23QB-2 3.1 SPACE HEATER-LIFT OIL PUMP MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
39VS-101 7.0 VIBRATION SENSOR (NON-CONT) GEN COLLECTOR ENDBENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH
39VS-102 7.0 VIBRATION SENSOR (NON-CONT) GEN COLLECTOR ENDBENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH
39VS-91 7.0 VIBRATION SENSOR (NON-CONT) GEN COUPLING ENDBENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH
39VS-92 7.0 VIBRATION SENSOR (NON-CONT) GEN COUPLING ENDBENTLEY NEVADA, 3300 SERIES
PROXIMITY PROBE FOR GENERATOR SHAFT
RANGE:200 MV PER MILLIINCH
45FG-40A 7.0 FIRE DETECTOR-GENERATOR COMPARTMENT125VDC
45FG-40B 7.0 FIRE DETECTOR-GENERATOR COMPARTMENT125VDC
63QB-2 3.1 BEARING LIFT OIL SUPPLY PRESSURE DECREASING: 2740+-40.00 PSIG OR 189.0+-2.759 BARG(INCREASING: 2900+-40.00 PSIG OR 200.0+-2.759 BARG)NORM=(2) NO-CEC; TO TURNING GEAR MCC
63QB-3 3.1 BEARING LIFT OIL SUPPLY PRESSURE DECREASING: 2740+-40.00 PSIG OR 189.0+-2.759 BARG(INCREASING: 2900+-40.00 PSIG OR 200.0+-2.759 BARG)NORM=(2) NO-CEC; TO TURNING GEAR MCC
63QBF-1 3.1 LIFT OIL FILTER DIFFERENTIAL PRESSUREINCREASING: 100.0+-5.000 PSIG OR 6.897+-0.3449 BARG(DECREASING: 46.00+-5.000 PSIG OR 3.173+-0.3449 BARG)
74 2.1 RELAYNORM=NC;
74-1 2.1 DC TRIPPING BLOWN FUSE MONITOR RELAYNORM=NC;FUNCTION: PROVIDE THE CONTACT FOR K-PBM
5 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
6 F
Device System Settings
88QB-1 3.1 BEARING LIFT OIL PUMP MOTOR75.00 HP; 55.93 KW; 1800 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072
88QB-2 3.1 BEARING LIFT OIL PUMP MOTOR75.00 HP; 55.93 KW; 1800 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072
95FP-1 7.0 GENERATOR AIR GAP FLUX PROBE
96VS-1 7.0 SHAFT VOLTAGE TRANSDUCER
AIT3350 7.5 GENERATOR CONDITION TRANSMITTER4.000 MA= 0.0 INH2O OR 0.0 MBAR20.00 MA= 100.0 INH2O OR 249.2 MBARUNITS ARE IN %.
HAZARDOUS ZONE 2
PROTECTION METHOD: ``D`` - EXPLOSION PROOF.
SIGNAL TO TCP VIA MODBUS PROTOCOL
AL-201 7.5A AC LIGHT - HPIP ENCLOSURE120 VAC60HZ, 1 PHASE
AL-202 7.5A AC LIGHT - HPIP ENCLOSURE120 VAC60HZ, 1 PHASE
AL-203 7.5A AC LIGHT - HPIP ENCLOSURE120 VAC60HZ, 1 PHASE
AL-204 7.5A AC LIGHT - HPIP ENCLOSURE120 VAC60HZ, 1 PHASE
AL-301 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE
AL-302 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE
AL-303 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE
AL-304 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE
AL-305 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE
AL-306 3.5 AC LIGHT - LUBE AND HYDRAULIC ENCLOSURE
AL-501 7.5A AC LIGHT - COUPLING COMPARTMENT120 VAC60HZ, 1 PHASE
AL-502 7.5A AC LIGHT-COUPLING COMPARTMENT120 VAC60HZ, 1 PHASE
AOV-SSDV 6.5B STEAM SEAL DUMP VALVEMKVI CONTROLLED VALVE 4-20 MA POSITIONER
4 MA = VALVE CLOSE
20 MA = VALVE OPEN
HAZARDOUS ZONE: NON RATED
AOV-SSFV 6.5B STEAM SEAL FEED VALVEMKVI CONTROLLED VALVE 4-20 MA POSITIONER
4 MA = VALVE OPEN
20 MA = VALVE CLOSE
HAZARDOUS ZONE: NON RATED
6 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
7 F
Device System Settings
AOV-WSV 6.5B EXHAUST HOOD WATER SPRAY VALVEMKVI CONTROLLED VALVE 4-20 MA POSITIONER
4 MA = VALVE CLOSE
20 MA = VALVE OPEN
HAZARDOUS ZONE: NON RATED
AR-301 3.5 AC RECEPTACLE - LUBE AND HYDRAULIC ENCLOSURE
AR-302 3.5 AC RECEPTACLE - LUBE AND HYDRAULIC ENCLOSURE
ASW-201 7.5A AC 3 WAY SWITCH - HPIP ENCLOSURE120 VAC THREE WAY LIGHT SWITCH60HZ, 1 PHASE
ASW-202 7.5A AC 3 WAY SWITCH - HPIP ENCLOSURE120 VAC THREE WAY LIGHT SWITCH60HZ, 1 PHASE
ASW-211 7.5A AC 4 WAY SWITCH - HPIP ENCLOSURE
120 VACFOUR WAY LIGHT SWITCH60HZ, 1 PHASE
ASW-212 7.5A AC 4 WAY SWITCH - HPIP ENCLOSURE
120 VACFOUR WAY LIGHT SWITCH60HZ, 1 PHASE
ASW-301 3.5 AC 3-WAY LIGHT SWITCH - LUBE AND HYDRAULIC ENCLOSURE
ASW-302 3.5 AC 3-WAY LIGHT SWITCH - LUBE AND HYDRAULIC ENCLOSURE
ASW-501 7.5A AC 3 WAY LIGHT SWITCH - COUPLING COMPARTMENT120 VAC THREE WAY LIGHT SWITCH60HZ, 1 PHASE
ASW-502 7.5A AC 3 WAY LIGHT SWITCH - COUPLING COMPARTMENT120 VAC THREE WAY LIGHT SWITCH60HZ, 1 PHASE
BPM-1 3.1 LUBE OIL PUMP MOTOR NO.1125.0 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL PUMP NO. 1
IEC 60034 & IEC 60072
BPM-2 3.1 LUBE OIL PUMP MOTOR NO.2125.0 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL PUMP NO. 2
IEC 60034 & IEC 60072
BT-GJ1-1A 7.0 BEARING METAL TEMP-GENERATOR BEARING #1TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-1
BT-GJ1-1B 7.0 BEARING METAL TEMP-GENERATOR BEARING #1TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-1
BT-GJ1-2A 7.0 BEARING METAL TEMP-GENERATOR BEARING #1TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-2
7 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
8 F
Device System Settings
BT-GJ1-2B 7.0 BEARING METAL TEMP-GENERATOR BEARING #1TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ1-2
BT-GJ2-1A 7.0 BEARING METAL TEMP-GENERATOR BEARING #2TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-1
BT-GJ2-1B 7.0 BEARING METAL TEMP-GENERATOR BEARING #2TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-1
BT-GJ2-2A 7.0 BEARING METAL TEMP-GENERATOR BEARING #2TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-2
BT-GJ2-2B 7.0 BEARING METAL TEMP-GENERATOR BEARING #2TYPE K THERMOCOUPLE1 ELEMENT; ONE HALF OF DUAL ELEMENT DEVICE - BT-GJ2-2
CAFM-1 3.5 COOLING AIR FAN MOTOR #16.169 HP; 4.600 KW; 1166 RPM; 460 VAC; 3 PH; 60 HZ;
CAFM-2 3.5 COOLING AIR FAN MOTOR #26.169 HP; 4.600 KW; 1166 RPM; 460 VAC; 3 PH; 60 HZ;
CB-1 2.1 CIRCUIT BREAKER FOR TURNING GEAR CONTROL POWERFUNCTION: CIRCUIT PROTECTION FOR TURNING GEAR CONTROL CIRCUIT
CFM-1 7.5A COOLING AIR FAN #1 - HP/IP ENCLOSURE3.000 HP; 1180 RPM; 460 VAC; 3 PH; 60 HZ;
CFM-2 7.5A COOLING AIR FAN #2 HP/IP ENCLOSURE3.000 HP; 1180 RPM; 460 VAC; 3 PH; 60 HZ;
CFM-3 7.5A COOLING AIR FAN #1 COUPLING COMPARTMENT1.000 HP; 1180 RPM; 460 VAC; 3 PH; 60 HZ;
CFM-4 7.5A COOLING AIR FAN #2 COUPLING COMPARTMENT1.000 HP; 1180 RPM; 460 VAC; 3 PH; 60 HZ;
CONT 3.1 IMMERSION HEATER CONTACTORFUNCTION: CONTROLS POWER TO HTR-1/2/3.
CT-1 2.1 CURRENT TRANSFORMERFUNCTION: MEASURE TURNING GEAR MOTOR CURRENT FOR DISPLAY ON LOCAL AMP METER
DEDP-1 1.3 DIFF EXPANSION DETECTOR PROBE50MM PROBEFUNCTION: MONITOR, DISPLAY, ALARM, TRIP
DEDP-2 1.3 DIFF EXPANSION DETECTOR PROBE50MM PROBE
FUNCTION: MONITOR, DISPLAY, ALARM, TRIP
DEDX-1 1.3 PROXIMITOR-DIFF EXPANSION STC MONITORRANGE: 100 - 1100 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.1
DEDX-2 1.3 PROXIMITOR-DIFF EXPANSION STC MONITORRANGE: 100 - 1100 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.2
8 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
9 F
Device System Settings
DHCP 7.5 HYDROGEN CONTROL PANEL POWER SUPPLYHYDROGEN CONTROL PANEL SUPPLY POWER 120 VAC 60 HZ AND 600 WATTS. EQUIPMENT POWERED BY UPS. REFER TO ML-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION.
DL-301 3.5 EMERGENCY DC LIGHT - LUBE AND HYDRAULIC ENCLOSURE
DL-302 3.5 EMERGENCY DC LIGHT - LUBE AND HYDRAULIC ENCLOSURE
DT-GAC-23 7.0 GENERATOR COLLECTOR-COLD AIR100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GAH-17 7.0 GENERATOR COLLECTOR-HOT AIR100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGC-10 7.0 GENERATOR TEMP-COLD GAS COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGC-11 7.0 GENERATOR TEMP-COLD GAS COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGC-12 7.0 GENERATOR TEMP-COLD GAS COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGC-13 7.0 GENERATOR TEMP-COLD GAS COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGH-15 7.0 GENERATOR TEMP-HOT GAS COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGH-16 7.0 GENERATOR TEMP-HOT GAS COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGH-18 7.0 GENERATOR TEMP-HOT GAS COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGH-19 7.0 GENERATOR TEMP-HOT GAS COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GGK-24 7.0 GENERATOR FRAME-COMMON COLD GAS100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS; ALSO IDENTIFIED AS GTG-2
DT-GSA-34 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSA-35 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSA-36 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSA-4 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
9 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
10 F
Device System Settings
DT-GSA-5 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSA-6 7.0 GENERATOR TEMP-STATOR COLLECTOR END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSC-20 7.0 GENERATOR TEMP-STATOR CENTER100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS; GROUNDED;
DT-GSC-21 7.0 GENERATOR TEMP-STATOR CENTER100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS; GROUNDED;
DT-GSC-22 7.0 GENERATOR TEMP-STATOR CENTER100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS; GROUNDED;
DT-GSF-1 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSF-2 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSF-3 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSF-31 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSF-32 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
DT-GSF-33 7.0 GENERATOR TEMP-STATOR COUPLING END100 OHM PLATINUM (DIN 43760) RTD2 ELEMENTS;
EBPM 3.1 DC EMERGENCY BRG OIL PUMP MOTOR40.00 HP; 2500 RPM; 120 VDC;FUNCTION: DRIVE EMERGENCY LUBE OIL PUMP
IEC 60034 & IEC 60072
EP-1 1.4 ECCENTRICITY PROBE8 MM PROBEFUNCTION: MONITOR AND ALARM
HAZARDOUS ZONE: 2
PROTECTION METHOD: `N` NON-SPARKING
EP-2 1.4 ECCENTRICITY PROBE8 MM PROBEFUNCTION: MONITOR AND ALARM
HAZARDOUS ZONE: 2
PROTECTION METHOD: `N` NON-SPARKING
EP-3 1.4 ECCENTRICITY PROBE8 MM PROBEFUNCTION: MONITOR AND ALARM
HAZARDOUS ZONE: 2
PROTECTION METHOD: `N` NON-SPARKING
10 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
11 F
Device System Settings
ESL-301 3.5 ENCLOSURE SELF CLN FILTER HOUSE UNDERVOLTAGE ALARMFUNCTION: ALARM ON LOW VOLTAGE SUPPLY TO SELF CLEANING FILTER HOUSE
ESPM 3.1 EMERGENCY SEAL OIL PUMP MOTOR30.00 HP; 2500 RPM; 120 VDC;FUNCTION: DRIVE EMERGENCY LUBE OIL PUMP
IEC 60034 & IEC 60072
EX-1 1.4 PROXIMITOR-ECCENTRICITY PROBE FOR STC MONITORRANGE: 10-90 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE
HAZARDOUS ZONE: NON-RATED
EX-2 1.4 PROXIMITOR-ECCENTRICITY PROBE FOR STC MONITORRANGE: 10-90 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE
HAZARDOUS ZONE: NON-RATED
EX-3 1.4 PROXIMITOR-ECCENTRICITY PROBE FOR STC MONITORRANGE: 10-90 MILSFUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE
HAZARDOUS ZONE: NON-RATED
FHPS 3.5 ENCLOSURE SELF CLEANING FILTER HOUSE POWER SUPPLY120 VAC; 1 PH; 60 HZ; 240W
FM-2996A 7.5 GAS DRYER BLOWER MOTOR.0.5000 HP; 1800 RPM; 480 VAC; 3 PH; 60 HZ;DUAL TOWER GAS DRYER BLOWER MOTOR.
0.5 HP = 0.37 KW
FM-2996B 7.5 GAS DRYER BLOWER MOTOR.0.5000 HP; 1800 RPM; 480 VAC; 3 PH; 60 HZ;DUAL TOWER GAS DRYER BLOWER MOTOR.
0.5 HP = 0.37 KW
FQIC-2950 7.5 HYDROGEN GAS FLOW TOTALIZER4.00 MA = 65.00 OR .0020.00 MA = 3000 OR 3000FUNCTION: MONITOR HYDROGEN MAKE-UP GAS CONSUMPTION.
4 MA = 65 SCFD (1.84 SCMD)
20 MA = 3000 SCFD (85 SCMF)
FE-2950 IS THE FLOW ELEMENT
POWER REQUIREMENTS 1PH, 16W, 120VAC
SIGNAL TO TCP VIA MODBUS PROTOCOL
FY-1203 6.4D RIGHT INTERCEPT VALVE SOLENOID110 VAC; 60 HZ; FUNCTION: ACTIVATE DUMP VALVE ON IV TRIGGER AND ON TEST WHEN ENERGIZED
ACTIVATE FOR AIR BLEED
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
PHASE:SINGLE
11 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
12 F
Device System Settings
FY-1204 6.4D LEFT INTERCEPT VALVE SOLENOID110 VAC; 60 HZ; FUNCTION: ACTIVATE DUMP VALVE ON IV TRIGGER AND ON TEST WHEN ENERGIZED
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
PHASE:SINGLE
FY-1212A 6.4D RIGHT REHEAT STOP VALVE TEST SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: MOVE VALVE TO TEST POSITION ON ENERGIZE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
PHASE:SINGLE
FY-1212B 6.4D RIGHT REHEAT STOP VALVE FAST CLOSING SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: FAST CLOSE VALVE ON ENERGIZE
ACTIVATE FOR AIR BLEED
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
PHASE:SINGLE
FY-1213A 6.4D LEFT REHEAT STOP VALVE TEST SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: MOVE VALVE TO TEST POSITION ON ENERGIZE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
PHASE:SINGLE
FY-1213B 6.4D LEFT REHEAT STOP VALVE FAST CLOSING SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: FAST CLOSE VALVE ON ENERGIZE
ACTIVATE FOR AIR BLEED
PHASE:SINGLE
FY-1214 6.4R EQUALIZER VALVE SOLENOID120 VAC; 60 HZ; FUNCTION: OPEN EV#2 ON ENERGIZE VIA AIR ACTUATOR
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
FY-1215 6.4R SOLENOID VALVE-LH EQUALIZER VLV AIR ACTUATOR120 VAC; 60 HZ; FUNCTION: OPEN EV#1 ON ENERGIZE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
FY-200 6.4C STOP VALVE TEST SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: MOVE SV #1 TO TEST POS ON ENERGIZE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
PHASE: SINGLE
12 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
13 F
Device System Settings
FY-200B 6.4C STOP VLV #1 FAST CLOSING SOL. VLV.110 VAC; 60 HZ; FUNCTION : ACTIVATE DUMP VALVE (SV#1) FOR VALVE CLOSURE AND ON TEST WHEN ENERGIZED
ACTIVATE FOR AIR BLEED
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
PHASE:SINGLE
FY-201 6.4C STOP VALVE NO.2 TEST SOLENOID VALVE110 VAC; 60 HZ; FUNCTION: MOVE SV #2 TO TEST POS ON ENERGIZE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
PHASE:SINGLE
FY-201B 6.4C STOP VLV. NO. 2 FAST CLOSING SOL. VLV.110 VAC; 60 HZ; FUNCTION : ACTIVATE DUMP VALVE (SV#2) FOR VALVE CLOSURE AND ON TEST WHEN ENERGIZED
ACTIVATE FOR AIR BLEED
PHASE:SINGLE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
FY-203 6.4M LP ADM STOP VALVE TEST SOLENOID VALVE120 VAC; 60 HZ; 7.700 W; FUNCTION: MOVE STOP VALVE TO TEST POSITION
HAZARDOUS ZONE: NON RATED
FY-211A 6.4C CONTROL VALVE FASV LEFT OR UPPER110 VAC; 60 HZ; FUNCTION: ACTIVATE DUMP VALVE (CV#1) ON CV TRIGGER
ACTIVATE FOR AIR BLEED
HAZARDOUS ZONE: NON-RATED
PHASE:SINGLE
PROTECTION METHOD: SIMPLE
FY-211B 6.4C CONTROL VALVE FASV RIGHT OR LOWER110 VAC; 60 HZ; FUNCTION: ACTIVATE DUMP VALVE (CV#2) ON CV TRIGGER
ACTIVATE FOR AIR BLEED
HAZARDOUS ZONE: NON-RATED
PHASE:SINGLE
PROTECTION METHOD: SIMPLE
FY-220 6.4S REVERSE FLOW VALVE SOLENOID120 VAC; 60 HZ; ENERGIZE TO OPEN
HAZARDOUS ZONE: NON RATED
FY-2445 6.4U REVERSE FLOW DISCHARGE VALVE SOLENOID VALVE120 VAC; 60 HZ; FUNCTION: OPEN RFDV ON ENERGIZE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
13 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
14 F
Device System Settings
FY-265 3.1 BRG & SEAL OIL PUMP NO.1 & NO.2 TEST SOLENOID VALVE120 VAC; 60 HZ; 42.00 W; FUNCTION: DROPS PRESSURE TO START STANDBY OIL PUMP
FY-266 3.1 EMERGENCY BRG & SEAL OIL PUMP TEST SOLENOID VALVE120 VAC; 60 HZ; 42.00 W; FUNCTION: DROPS PRESSURE TO START STANDBY OIL PUMP
FY-281 4.0 HYD FLUID PUMP TEST SOLENOID VALVE120 VAC; 60 HZ; 30 W
FUNCTION: REMOTE OR LOCAL TEST OF PUMP START CIRCUITS
HAZARDOUS AREA : NON-RATED
FY-288A 2.0 TURNING GEAR ENGAGING SOLENOID VALVE A (AIR)120 VAC; 50/60 HZ; 6.100 W; CONTROLS PROVIDED STEP DOWN TRANSFORMER PROVIDES 120V, AC, 50/60HZ REGARDLESS OF CUSTOMER SUPPLIED VOLTAGE.
FUNCTION: CAUSES ENGAGEMENT OF TURNING GEAR
FY-288B 2.0 TURNING GEAR ENGAGING SOLENOID VALVE B (AIR)120 VAC; 50/60 HZ; 6.100 W; CONTROLS PROVIDED STEP DOWN TRANSFORMER PROVIDES 120V, AC, 50/60HZ REGARDLESS OF CUSTOMER SUPPLIED VOLTAGE.
FUNCTION: CAUSES ENGAGEMENT OF TURNING GEAR
FY-2955A 7.5 CORE MONITOR SOLENOID120 VAC; 60 HZ; 1 PHASETHIS SOLENOID IS POWERED BY THE GCM-X.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
FY-2955B 7.5 PYROLYSATE COLLECTOR SOLENOID120 VAC; 60 HZ; 1 PHASETHIS SOLENOID IS POWERED BY THE GCM-X.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
FY-2971 7.5 TURBINE END SCAVENGING SOLENOID1 PHASE120 VAC; 60 HZ; THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.
SIGNAL 20SCAV1 ENERGIZES SOLENOID VALVE FY-2971 ON THE H2 CTRL PANEL TO INCREASE SCAVENGING OF TE AT LOW PURITY
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
SIGNAL TO TCP VIA MODBUS
FY-2972 7.5 COLLECTOR END GAS SOLENOID1 PHASE120 VAC; 60 HZ; THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.
SIGNAL 20CASE1 ENERGIZES SOLENOID VALVE FY-2972 ON THE H2 CTRL PANEL TO DIRECT GEN CASING GAS TO ANALYZER 1 (QT-290A) HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
SIGNAL TO TCP VIA MODBUS
14 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
15 F
Device System Settings
FY-2973 7.5 COLLECTOR END SCAVENGING SOLENOID1 PHASE120 VAC; 60 HZ; THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.
SIGNAL 20SCAV2 ENERGIZES SOLENOID VALVE FY-2973 ON THE H2 CTRL PANEL TO INCREASE SCAVENGING OF CE AT LOW PURITY;HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
SIGNAL TO TCP VIA MODBUS PROT
FY-2974 7.5 COLLECTOR END GAS SOLENOID.1 PHASE120 VAC; 60 HZ; THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.
SIGNAL 20CASE2 ENERGIZES SOLENOID VALVE FY-2974 ON THE H2 CTRL PANEL TO DIRECT GEN CASING GAS TO ANALYZER 2 (QT-290B);HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
SIGNAL TO TCP VIA MODBUS
FY-2981 7.5 CASE, PURGE, CALIBRATION SOLENOID.1 PHASE120 VAC; 60 HZ; DE-ENERGIZED STATE ALLOWS FLOW FROM GEN CASE TO FY-2972 AND FY-2974. REFER TO SYSTEM P&ID. THIS SOLENOID IS POWERED BY THE H2 PANEL UPS.
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `M` - ENCAPSULATION
SIGNAL TO TCP VIA MODBUS PROTOCOL
FY-2996A 7.5 DUAL GAS DRYER TOWER 1 SOLENOID1 PHASE120 VAC; 60 HZ; POWERED BY THE GAS DRYER AND CONTROLLED THE GAS DRYER`S PLC. NO MARK VI INTERFACE.
FY-2996B 7.5 DUAL GAS DRYER TOWER 2 SOLENOID1 PHASE120 VAC; 60 HZ; POWERED BY THE GAS DRYER AND CONTROLLED THE GAS DRYER`S PLC. NO MARK VI INTERFACE.
FY-CSBV 6.5B COOLING STEAM BLOCKING VALVE SOLENOIDDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED120 VAC; 60 HZ; 2.800 W; ENERGIZE TO CLOSE AOV-CSBV
HAZARDOUS ZONE: NON RATED
FY-LRSV 6.5B LEAKOFF RE-ENTRY STOP VALVE SOLENOIDDE-ENERGIZED: 3 TO 1 OPEN; 2 PLUGGEDENERGIZED: 1 TO 2 OPEN; 3 PLUGGED120 VAC; 60 HZ; 2.800 W; ENERGIZE TO CLOSE AOV-LRSV
HAZARDOUS ZONE: NON RATED
FY2253 6.5B 1ST STAGE REHEAT COOLING VALVE SOLENOID120 VAC; 60 HZ; 2.800 W; ENERGIZE TO OPEN
HAZARDOUS ZONE: NON RATED
15 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
16 F
Device System Settings
FY5000 4.0 ELECTRICAL TRIP SOLENOID FOR ETD-1550 OHM COIL.30 W125 VDC; FUNCTION: IF DE-ENERGIZED DROPS HYD HEADER PRESS TO STOP VLV
HAZARDOUS AREA : NON-RATED
FY5002 4.0 ELECTRICAL TRIP SOLENOID FOR ETD-2550 OHM COIL.30 W125 VDC; FUNCTION: IF DE-ENERGIZED DROPS HYD HEADER PRESS TO STOP VLV
HAZARDOUS AREA : NON-RATED
FY5004 4.0 ELECTRICAL TRIP SOLENOID FOR ETD-3550 OHM COIL.30 W125 VDC; FUNCTION: IF DE-ENERGIZED DROPS HYD HEADER PRESS TO STOP VLV
HAZARDOUS AREA : NON-RATED
GASDRYER 7.5 GAS DRYER POWER SUPPLYTHE GAS DRYER REQUIRES 480 VAC 3 PHASE 60 HZ POWER WITH A 2500 WATT LOAD. PLEASE REFER TO MLI-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION.
GCMX 7.5 CORE MONITOR WITH PYROLYSATE COLLECTORTHE CORE MONITOR/PYROLYSATE COLLECTOR REQUIRES A 120 VAC 60 HZ POWER SUPPLY AND THE POWER DRAW IS 500 WATTS. PLEASE REFER TO ML-G2B0 FOR ADDITIONAL ELECTRICAL CONNECTION INFORMATION.
GXM-1 5.0A GLAND EXHAUSTER BLOWER MOTOR NO.120.11 HP; 3540 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: EXHAUSTS STEAM/AIR FROM CONDENSER/SPRAY CHAMBER
HAZARDOUS ZONE: NON RATED
GXM-2 5.0A GLAND EXHAUSTER BLOWER MOTOR NO.220.11 HP; 3540 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: EXHAUSTS STEAM/AIR FROM CONDENSER/SPRAY CHAMBER
HAZARDOUS ZONE: NON RATED
HCCM 4.0 HEATING / COOLING CIRCULATION PUMP MOTOR5.000 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072
FUNCTION: DRIVES FLUID HEATING/COOLING PUMP TO MAINTAIN HYDRAULIC FLUID TEMPERATURE
HAZARDOUS AREA : NON-RATED
HFPM-A 4.0 HYDRAULIC FLUID PUMP MOTOR A.25.00 HP; 1800 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072
FUNCTION: DRIVES FLUID PUMP NO. 1
HAZARDOUS AREA : NON-RATED
HFPM-B 4.0 HYDRAULIC FLUID PUMP MOTOR B.25.00 HP; 1800 RPM; 460 VAC; 3 PH; 60 HZ;IEC 60034 & IEC 60072
FUNCTION: DRIVES FLUID PUMP NO. 2
HAZARDOUS AREA : NON-RATED
HS-288 2.1 MANUAL TURNING GEAR RUN SWITCHFUNCTION: LOCAL CONTROL SWITCH TO START AND JOG TURNING GEAR
16 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
17 F
Device System Settings
HTR-1 3.1 OIL TANK HEATER 110.00 KW; 460 VAC; 3 PH; 60 HZ;FUNCTION: KEEP RESERVIOR TEMP FROM FALLING BELOW MINIMUM REQUIRED.
HTR-2 3.1 OIL TANK HEATER 210.00 KW; 460 VAC; 3 PH; 60 HZ;FUNCTION: KEEP RESERVIOR TEMP FROM FALLING BELOW MINIMUM REQUIRED.
HTR-3 3.1 OIL TANK HEATER 310.00 KW; 460 VAC; 3 PH; 60 HZ;FUNCTION: KEEP RESERVIOR TEMP FROM FALLING BELOW MINIMUM REQUIRED.
K-288 2.1 STOP VALVE CLOSED MULTIPLYING SIGNAL RELAYFUNCTION: PERMIT TURNING GEAR START, ENGAGE, AND OIL
K-289 2.1 MANUAL TURNING GEAR RUN SWITCH LOCKOUT CONTACTFUNCTION: ALARM IF TURNING GEAR NOT IN STANDBY
K-290 2.1 JOG MODE INDICATION ALARMFUNCTION: ALARM IF TURNING GEAR IN JOG
K-PBM 2.1 CONTACTOR MULTIPLIER FOR PBM MOTOR STARTER SIGNALFUNCTION: CONTROLS STARTING CONTACTOR FOR PIGGY BACK MOTOR
K-TGM 2.1 CONTACT MULTIPLIER FOR TGM MOTOR STARTER SIGNALFUNCTION: CONTROLS STARTING CONTACTOR FOR TURNING GEAR MOTOR
L-288 2.1 TURNING GEAR MOTOR NOT RUNNING INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION
L-289 2.1 TURNING GEAR RUNNING INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION
L-290 2.1 TURNING GEAR DISENGAGED INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION
L-291 2.1 TURNING GEAR ENGAGED INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION
L-292 2.1 TURNING GEAR REMOTE JOG ENABLED LIGHT120 VACFUNCTION: LOCAL INDICATION (ON PANEL)
L-ZSP 2.1 SAFE ENGAGE SPEED INDICATOR LIGHT120 VACFUNCTION: LOCAL INDICATION
LS-232 5.0A GLAND EXHAUSTER CONDENSER CONDENSATE LEVEL HIGHSETTING: 3 INCHES (76.2 MM) ABOVE NORMAL OPERATING LEVEL
FUNCTION: MONITOR AND ALARM
HAZARDOUS ZONE: NON RATED
KKS DESIGNATION: MAW70 CL301
LS-260 3.1 LUBE OIL LEVEL IMMERSION HEATER PERMISSIVE SWITCHDECREASING: 8.0+-0.5 INCHES (203.2 MM) BELOW OPERATING OIL LEVEL
INCREASING: 7.0+-0.5 INCHES (177.8 MM) BELOW NORMAL
FUNCTION: PREVENTS HEATER OPERATION WHEN OIL LEVEL IS LOW
17 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
18 F
Device System Settings
LSH-2990 7.5 LIQUID LEVEL DETECTOR HIGH LEVEL SWITCHNORM=(4) NO-CEC; DPDT SWITCH.
FUNCTION: ALARM WHEN FLUID ENTERS THE LIQUID LEVEL DETECTOR
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - EXPLOSION PROOF
SIGNAL TO TCP VIA MODBUS PROTOCOL
LSH-3401 7.5 SEAL OIL DRAIN HIGH LEVEL SWITCHNORM=(4) NO-CEC; DPDT SWITCH.
FUNCTION: ALARM WHEN FLUID ENTERS THE LIQUID LEVEL DETECTOR
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - EXPLOSION PROOF
SIGNAL TO TCP VIA MODBUS PROTOCOL
LSHH-2990 7.5 LIQUID LEVEL DETECTOR HIGH HIGH LEVEL SWITCHNORM=(4) NO-CEC; DPDT SWITCH.
FUNCTION: ALARM WHEN FLUID ENTERS THE LIQUID LEVEL DETECTOR
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - EXPLOSION PROOF
SIGNAL TO TCP VIA MODBUS PROTOCOL
LT-260 3.1 LUBE OIL TANK LEVEL4-20MA FOR 0-100% OF MEASURED LEVELHIGH LEVEL ALARM: 13.37 MA
NORMAL LEVEL: 12.00 MA
LOW LEVEL ALARM: 10.80 MA
LOW LOW LEVEL ALARM: 8.80 MA
BASED ON A 45`` PROBE LENGTH
LT-280 4.0 HYDRAULIC FLUID RESERVOIR LEVEL TRANSMITTER4.000 MA= 0.0 OR 0.0 20.00 MA= 100.0 OR 100.0 HIGH LEVEL ALARM: 13.37 MA
NORMAL LEVEL: 12.00 MA
LOW LEVEL ALARM: 10.80 MA
LOW LOW LEVEL ALARM: 8.80 MA
BASED ON A 45`` PROBE LENGTH
HAZARDOUS AREA : NON-RATED
LT-G1D-1A 7.0 LUBE SYSTEM TEMP-GENERATOR #1 BEARING DRAINTYPE K THERMOCOUPLE1 ELEMENT; GROUNDED; ONE HALF OF DUAL ELEMENT DEVICE - LT-G1D-1
LT-G1D-1B 7.0 LUBE SYSTEM TEMP-GENERATOR #1 BEARING DRAINTYPE K THERMOCOUPLE1 ELEMENT; GROUNDED; ONE HALF OF DUAL ELEMENT DEVICE - LT-G1D-1
LT-G2D-1A 7.0 LUBE SYSTEM TEMP-GENERATOR #2 BEARING DRAINTYPE K THERMOCOUPLE1 ELEMENT; GROUNDED; ONE HALF OF DUAL ELEMENT DEVICE - LT-G2D-1
18 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
19 F
Device System Settings
LT-G2D-1B 7.0 LUBE SYSTEM TEMP-GENERATOR #2 BEARING DRAINTYPE K THERMOCOUPLE1 ELEMENT; GROUNDED; ONE HALF OF DUAL ELEMENT DEVICE - LT-G2D-1
ME-2996 7.5 GAS DRYER INLET HYGROMETER PROBE4.000 MA= 60.00 F OR 15.56 C20.00 MA= -60.00 F OR -51.11 CFUNCTION: PROBE FOR MEASURING INLET GAS DEW POINT ONLY. ALARM CONTACTS ARE LOCATED ON DEVICE MIC-2996
MIC-2951 7.5 DEW POINT SENSOR PROCESSOR4.0MA = -148 F OR -100C20.0MA = 68.0 F OR 20.000 CHIGH ALARM 32 F INC., HIGH-HIGH ALARM AT 68 F INC.
SIGNAL TO TCP VIA MODBUS PROTOCOL
MIC-2996 7.5 GAS DRYER DEW POINT SENSORNORM=(2) NC; CONTACT OPENS AT SET POINT; HIGH DEW POINT ALARM, SIGNAL NAME = 30DRYMH, SET AT +20 F INCREASING.
DEW POINT SENSOR FAULT, SIGNAL NAME = 30DRYFAULT
CONTACT OPENS OPEN ON GAS DRYER COMMON TROUBLE
MOV-B 6.5 STEAM SEAL DUMP BYPASS VALVE460 VAC; 3 PH; 60 HZ0.16 HP
0.8 FULL CURRENT AMPS
2.1 LOCKED ROTOR AMPS
FUNCTION: STEAM SEAL SYSTEM
HAZARDOUS ZONE: NON RATED
MOV-S1 6.5 STEAM SEAL FEED VALVE BLOCK460 VAC; 3 PH; 60 HZ0.16 HP
0.8 FULL CURRENT AMPS
2.1 LOCKED ROTOR AMPS
FUNCTION: FUNCTION: USED TO ISOLATE STEAM SEAL SYSTEM FROM MAIN STEAM
HAZARDOUS ZONE: NON RATED
MOV-S2 6.5 STEAM SEAL FEED SUPPLEMENTARY VALVE460 VAC; 3 PH; 60 HZ0.16 HP
0.8 FULL CURRENT AMPS
2.1 LOCKED ROTOR AMPS
FUNCTION: FUNCTION: AID SSFV IN MAINTAINING STEAM SEAL PRESSURE
HAZARDOUS ZONE: NON RATED
MOV-SAD-1 6.5 DRAIN VALVE-ADM CONTROL VALVE BEFORE SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP
0.8 FULL CURRENT AMPS
2.1 LOCKED ROTOR AMPS
FUNCTION: CONDENSATE DRAIN
HAZARDOUS ZONE: NON RATED
19 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
20 F
Device System Settings
MOV-SAD-2 6.5 DRAIN VALVE-ADM CONTROL VALVE AFTER SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP
0.8 FULL CURRENT AMPS
2.1 LOCKED ROTOR AMPS
FUNCTION: CONDENSATE DRAIN
HAZARDOUS ZONE: NON RATED
MOV-SPD 6.5 DRAIN VALVE STEAM PACKING RE-ENTRY460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP
0.8 FULL CURRENT AMPS
2.1 LOCKED ROTOR AMPS
FUNCTION: CONDENSATE DRAIN
HAZARDOUS ZONE: NON RATED
MOV-SPDV-1 6.5 DRAIN VALVE MAIN STEAM LINE #1 LOW POINT460 VAC; 3 PH; 60 HZ; 1700 RPM0.37 HP1.5 FULL CURRENT AMPS
5.6 LOCKED ROTOR AMPS
FUNCTION: CONDENSATE DRAIN
MOV-SSV-1A 6.5 DRAIN VALVE MAIN STOP VALVE A BEFORE SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.37 HP
1.5 FULL CURRENT AMPS
5.6 LOCKED ROTOR AMPS
FUNCTION: CONDENSATE DRAIN
HAZARDOUS ZONE: NON RATED
MOV-SSV-1B 6.5 DRAIN VALVE MAIN STOP VALVE B BEFORE SEAT460 VAC; 3 PH; 60 HZ;1700 RPM0.37 HP1.5 FULL CURRENT AMPS
5.6 LOCKED ROTOR AMPS
FUNCTION: CONDENSATE DRAIN
HAZARDOUS ZONE: NON RATED
MOV-SSV-4A 6.5 DRAIN VALVE REHEAT STOP VALVE A AFTER SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP
0.8 FULL CURRENT AMPS
2.1 LOCKED ROTOR AMPS
FUNCTION: CONDENSATE DRAIN
HAZARDOUS ZONE: NON RATED
MOV-SSV-4B 6.5 DRAIN VALVE REHEAT STOP VALVE B AFTER SEAT460 VAC; 3 PH; 60 HZ; 1700 RPM0.16 HP
0.8 FULL CURRENT AMPS
2.1 LOCKED ROTOR AMPS
FUNCTION: CONDENSATE DRAIN
HAZARDOUS ZONE: NON RATED
20 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
21 F
Device System Settings
MOV-VBV-1 6.5 VACUUM BREAKER VALVE460 VAC, 3 PH, 60 HZ0.16 HP
0.5 FULL CURRENT AMPS
9.0 LOCKED ROTOR AMPS
FUNCTION: OPEN VLV TO BREAK CONDENSER VACUUM
HAZARDOUS ZONE: NON RATED
OCM 3.1 OIL CONDITIONER PUMP MOTOR5.000 HP; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL CONDITIONER PUMP
IEC 60034 & IEC 60072
PB-283A 6.7B CUSTOMER MOUNTED EMERGENCY TRIP PUSHBUTTONON TURBINE DECK
PB-283T 6.7B EMERGENCY TRIP PUSHBUTTON AT FRONT STANDARDFUNCTION: ALARM AND ELECTRICAL TRIP
PB-284A 6.7B EMERGENCY TRIP PUSHBUTTON AT STC/BU PANELFUNCTION: CAUSES TRIP THROUGH TRIP BUS
PB-285A 6.7B CUSTOMER TRIP BUTTON AT 2ND OIM LOCATIONFUNCTION: CAUSES TRIP THROUGH TRIP BUS
PB-286A 6.7B EMERGENCY TRIP PUSHBUTTON AT 2ND OIM LOCATIONFUNCTION: CAUSES TRIP THROUGH TRIP BUS
PB-289 2.1 LOCAL TURNING GEAR JOG PUSH BUTTONFUNCTION: PUSH TO JOG TURNING GEAR (WHEN PERMISSIVES SATISFIED)
PBM 2.0 TURNING GEAR MOTOR/PIGGY BACK MOTOR1.000 HP; 600 RPM; 460 VAC; 3 PH; 60 HZ;F.L.C. =3.9 AMP; L.R.C =10.2 AMP
FUCTION: TURN SHAFT/PRE-ENGAGEMENT OF TGM
PDS-221 4.0 PARTICULATE FILTER HIGH DIFF. PRESSUREINCREASING: 70.00+-5.000 PSIG OR 4.828+-0.3449 BARGHAZARDOUS AREA : NON-RATED
PDS-222 4.0 POLISHING FILTER HIGH DIFF PRESSUREINCREASING: 70.00+-5.000 PSIG OR 4.828+-0.3449 BARGHAZARDOUS AREA : NON-RATED
PDS-223 4.0 HEAT & COOLING PARTICULATE FILTER HIGH DIFF PRESSUREINCREASING: 70.00+-5.000 PSIG OR 4.828+-0.3449 BARGHAZARDOUS AREA : NON-RATED
PDS-287A 4.0 DUPLEX FILTER HIGH DIFF PRESSURE NO.1INCREASING: 100.0+-5.000 PSID OR 6.897+-0.3449 BARDNORM=(2) NO-OEC; FUNCTION: PROVIDES ALARM IF FILTER REQUIRES REPLACEMENT
HAZARDOUS AREA : NON-RATED
PDS-287B 4.0 DUPLEX FILTER HIGH DIFF PRESSURE NO.2INCREASING: 100.0+-5.000 PSIG OR 6.897+-0.3449 BARGNORM=(2) NO-OEC; FUNCTION: PROVIDES ALARM IF FILTER REQUIRES REPLACEMENT
HAZARDOUS AREA : NON-RATED
21 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
22 F
Device System Settings
PDSL-3402 3.4 SEAL OIL DIFFERENTIAL PRESSURE LOW SWITCH DECREASING: 4.500 PSID OR 0.3104 BARDNORM=(2) NC-CEC; FUNCTION: ALARM
NOTE: SWITCH MUST BE COMPENSATED IN THE FIELD SINCE THE HGF AND HSF-2 SENSING LINES ARE AT DIFFERENT ELEVATIONS.
DEAD BAND = .35 PSID
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
PDSL-3406 3.4 SEAL OIL DIFF PRESSURE LOW-LOW, START DC PUMP DECREASING: 3.500 PSID OR 0.2414 BARDFUNCTION: START DC PUMP
NOTE: SWITCH MUST BE COMPENSATED IN THE FIELD SINCE THE HGF & HSF-2 SENSING LINES ARE AT DIFFERENT ELEVATIONS.
DEAD BAND = 0.35 PSID
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
PDT-216 6.3 LP ADMISSION STRAINER DIFFERENTIAL PRESSURE4.0 MA = 0.0 PSID20.0 MA = 100.0 PSID
PDT-251 5.0B STEAM SEAL DUMP VALVE DIFFERENTIAL PRESSURE TRANSMITTER4.000 MA= 0.0 PSID OR 0.0 BARD20.00 MA= 20.00 PSID OR 1.379 BARDMONITOR STEAM SEAL CONDITIONS
HAZARDOUS ZONE: NON RATED
PDT-292 7.5 GENERATOR ROTOR FAN PRESSURE DIFFERENTIAL4.000 MA= 0.0 INH2O OR 0.0 MBAR20.00 MA= 30.00 INH2O OR 74.75 MBARFUNCTION: ALARM AT 12 IN H2O (304.8 MM H2O)
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
SIGNAL TO TCP VIA MODBUS PROTOCOL
PDT-2955 7.5 CORE MONITOR FLOW TRANSMITTER4.0 MA = 0.0 INH20 OR 0.000 MBAR20.0 MA = 3.0 INH20 OR 7.4752 MBARLOW FLOW LIMIT=1.1 INH20 (27.9 MMH2O), HIGH FLOW LIMIT=1.9 INH20 (48.3 MMH2O)
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
SIGNAL TO TCP VIA MODBUS PROTOCOL
PDT-303 3.5 ENCLOSURE SELF CLN FILTER HOUSE DIFF PRESSURE4.000 MA= 0.0 INH2O OR 0.0 MBAR20.00 MA= 4.000 INH2O OR 9.967 MBARFUNCTION: MONITOR AIR FILTER DP, ALARM ON 2.1 IN H2O
PDT-3402 3.4 SEAL OIL DIFFERENTIAL PRESSURE, SEAL OIL VS GAS PRESSURE4.000 MA= 0.0 PSID OR 0.0 BARD20.00 MA= 15.00 PSID OR 1.035 BARDFUNCTION: FOR MONITORING DP THRU TURBINE CONTROLLER, DP SET TO 5.5 PSID (37.92 KPAD)
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
22 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
23 F
Device System Settings
PS-212C 5.0A GLAND SEAL EXHAUSTER BLOWER MOTOR RUNNING DECREASING: 5.000 INH2O OR 12.46 MBARNORM=(2) NC-CES; FUNCTION: ALARM NOT RUNNING
HAZARDOUS ZONE: NON RATED
PS-213 5.0A GSC EXHAUSTER AMBIENT AIR BLEED FILTER HIGH DIFF PRES DECREASING: 13.60 INH2O OR 33.89 MBARNORM=(2) NC-CES; FUNCTION: MONITOR AND ALARM
HAZARDOUS ZONE: NON RATED
PS-214 5.0A GSC EXHAUSTER AMBIENT AIR BLEED FILTER HIGH DIFF PRES DECREASING: 13.60 INH2O OR 33.89 MBARNORM=(2) NC-CES; FUNCTION: MONITOR AND ALARM
HAZARDOUS ZONE: NON RATED
PS-263 3.1 EMERGENCY SEAL OIL PUMP RUNNING SWITCHINCREASING: 40.00+-2.000 PSIG OR 2.759+-0.1379 BARG(DECREASING: 35.00+-2.000 PSIG OR 2.414+-0.1379 BARG)NORM=(2) NO-CES; FUNCTION: SENSES EMERGENCY DC PUMP OUTPUT PRESSURE
PS-265A 3.1 LUBE OIL PUMP NO 1. AND NO 2. START DECREASING: 111.0+-4.000 PSIG OR 7.656+-0.2759 BARG(INCREASING: 123.0+-4.500 PSIG OR 8.483+-0.3104 BARG)NORM=(2) NC-CEC;
PS-266A 3.1 FUNCTION: STARTS EBOP AND ESOP DECREASING: 95.00+-4.000 PSIG OR 6.552+-0.2759 BARG(INCREASING: 107.0+-4.500 PSIG OR 7.380+-0.3104 BARG)NORM=(2) NC-CEC; FUNCTION: STARTS EMERGENCY DC LUBE OIL PUMP
PS-267A 3.1 LUBE OIL PUMP NO.1 RUNNING PRESSURE SWITCHINCREASING: 40.00+-2.000 PSIG OR 2.759+-0.1379 BARG(DECREASING: 35.00+-2.000 PSIG OR 2.414+-0.1379 BARG)NORM=(2) NO-CES; FUNCTION: SENSES PUMP NO.1 OUTPUT PRESSURE
PS-267B 3.1 LUBE OIL PUMP NO.2 RUNNING PRESSURE SWITCHINCREASING: 40.00+-2.000 PSIG OR 2.759+-0.1379 BARG(DECREASING: 35.00+-2.000 PSIG OR 2.414+-0.1379 BARG)NORM=(2) NO-CES; FUNCTION: SENSES PUMP NO.2 OUTPUT PRESSURE
PS-268 3.1 EMERGENCY LUBE OIL PUMP RUNNING PRESSURE SWITCHINCREASING: 40.00+-2.000 PSIG OR 2.759+-0.1379 BARG(DECREASING: 35.00+-2.000 PSIG OR 2.414+-0.1379 BARG)NORM=(2) NO-CES; FUNCTION: SENSES EMERGENCY DC PUMP OUTPUT PRESSURE
PS-270A 3.1 LUBE OIL LOW PRESSURE ALARM SWITCH DECREASING: 10.00+-1.000 PSIG OR 0.6897+-0.0690 BARG(INCREASING: 12.00+-1.000 PSIG OR 0.8276+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: ALARM LOW LUBE OIL PRESSURE
(10PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 25PSIG)
23 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
24 F
Device System Settings
PS-270B 3.1 LOW LUBE OIL HEADER PRESSURE TRIP & ALARM DECREASING: 6.000+-1.000 PSIG OR 0.4138+-0.0690 BARG(INCREASING: 8.000+-1.000 PSIG OR 0.5518+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TRUB ON LOW LUBE OIL PRESSURE AND ALARMS
(6PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 21PSIG)
PS-270C 3.1 LOW LUBE OIL HEADER PRESSURE TRIP & ALARM DECREASING: 6.000+-1.000 PSIG OR 0.4138+-0.0690 BARG(INCREASING: 8.000+-1.000 PSIG OR 0.5518+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB AND ALARMS ON LOW LUBE OIL PRESSURE
(6PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 21PSIG)
PS-270D 3.1 LOW LUBE OIL HEADER PRESSURE TRIP & ALARM DECREASING: 6.000+-1.000 PSIG OR 0.4138+-0.0690 BARG(INCREASING: 8.000+-1.000 PSIG OR 0.5518+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB AND ALARMS ON LOW LUBE OIL PRESSURE
(6PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 21PSIG)
PS-270E 3.1 LIFT OIL PRESSURE PERMISSIVEINCREASING: 6.000+-1.000 PSIG OR 0.4138+-0.0690 BARG(DECREASING: 8.000+-1.000 PSIG OR 0.5518+-0.0690 BARG)NORM=(2) NC-CES; FUNCTION: PRESSURE PERMISSIVE FOR LIFT OIL PUMP
(6PSIG BASED ON TURBINE CENTERLINE PRESSURE, SKID MANUFACTURER SHOULD PRE-SET SWITCH TO 21PSIG)
PS-271A 3.1 LUBE OIL FILTER HIGH DIFF PRESSURE ALARMINCREASING: 15.00+-0.3000 PSID OR 1.035+-0.0207 BARD(DECREASING: 11.00+-3.000 PSID OR 0.7587+-0.2069 BARD)NORM=(1) NO-CEC; FUNCTION: PROVIDES ALARM IF FILTER REQUIRES REPLACEMENT
PS-271B 3.1 LUBE OIL FILTER HIGH DIFF PRESSURE ALARMINCREASING: 15.00+-0.3000 PSID OR 1.035+-0.0207 BARD(DECREASING: 11.00+-0.3000 PSID OR 0.7587+-0.0207 BARD)NORM=(1) NO-CEC; FUNCTION: PROVIDES ALARM IF FILTER REQUIRES REPLACEMENT
PS-271G 3.1 LUBE OIL TANK LOW VACUUM SWITCH DECREASING: 4.000+-0.1000 INH2O OR 9.967+-0.2492 MBAR(INCREASING: 3.600+-0.1000 INH2O OR 8.970+-0.2492 MBAR)NORM=(1) NO-CEC;
PS-273A 3.1 DIRTY ELEMENTS ALARMSINCREASING: 25.00+-2.000 PSID OR 1.724+-0.1379 BARDFUNCTION: SIGNALS NEED FOR FILTER CHANGE ACTIVATES WHEN DIFF. PRESS. ACROSS ELEMENTS REACHES SETPOINT
PS-280A 4.0 HYD FLUID PUMP A DISCHARGE PRESSUREINCREASING: 2300 PSIG OR 158.6 BARG(DECREASING: 2200 PSIG OR 151.7 BARG)NORM=(2) NO-OES; FUNCTION: SENSES HYD PUMP A OUTPUT PRESSURE
HAZARDOUS AREA : NON-RATED
24 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
25 F
Device System Settings
PS-280B 4.0 HYD FLUID PUMP B DISCHARGE PRESSUREINCREASING: 2300 PSIG OR 158.6 BARG(DECREASING: 2200 PSIG OR 151.7 BARG)NORM=(2) NO-OES; FUNCTION: SENSES HYD PUMP B OUTPUT PRESSURE
HAZARDOUS AREA : NON-RATED
PS-281A 4.0 LOW HYD FLUID PRESSURE ALARM DECREASING: 1950 PSIG OR 134.5 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: ALARM ON LOW HYD PRESSURE
HAZARDOUS AREA : NON-RATED
PS-281B 4.0 HYD FLUID PRESSURE LOW PUMP A START DECREASING: 1950 PSIG OR 134.5 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: STARTS STANDBY PUMP ON LOW HYD PRESSURE.
HAZARDOUS AREA : NON-RATED
PS-281C 4.0 HYD FLUID PRESSURE LOW PUMP B START DECREASING: 1950 PSIG OR 134.5 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: STARTS STANDBY PUMP ON LOW HYD PRESSURE.
HAZARDOUS AREA : NON-RATED
PS-281D 4.0 LOW HYD PRESSURE TRIP & ALARM DECREASING: 1650 PSIG OR 113.8 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB ON LOW HYD PRESSURE
HAZARDOUS AREA : NON-RATED
PS-281E 4.0 LOW HYD PRESSURE TRIP & ALARM DECREASING: 1650 PSIG OR 113.8 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB AND ALARMS ON LOW HYD PRESSURE
HAZARDOUS AREA : NON-RATED
PS-281F 4.0 LOW HYD PRESSURE TRIP & ALARM DECREASING: 1650 PSIG OR 113.8 BARG(INCREASING: 2150 PSIG OR 148.3 BARG)NORM=(2) NC-CES; FUNCTION: TRIPS TURB AND ALARMS ON LOW HYD PRESSURE
HAZARDOUS AREA : NON-RATED
PS-282 4.0 EMERGENCY TRIP HEADER TRIPPED DECREASING: 200.0 PSIG OR 13.79 BARG(INCREASING: 300.0 PSIG OR 20.69 BARG)NORM=(2) NC-CES; FUNCTION: SENSES LOW PRESSURE IN HYD LINE TO STOP VLV
HAZARDOUS AREA : NON-RATED
PS-301 3.5 ENCLOSURE SELF CLN FILTER HOUSE LOW PRESSURE ALARM DECREASING: 60.00 PSIG OR 4.138 BARGNORM=NO;FUNCTION: ALARM ON LOW COMPRESSED AIR SUPPLY TO SELF CLEANING FILTER HOUSE
25 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
26 F
Device System Settings
PS-302A 3.5 COOLING AIR FAN #1 RUNNING PRESSURE SWITCHINCREASING: 0.4000 INH2O OR 0.9967 MBARNORM=NO-CEC;
PS-302B 3.5 COOLING AIR FAN #2 RUNNING PRESSURE SWITCHINCREASING: 0.4000 INH2O OR 0.9967 MBARNORM=NO-CEC;
PS-303 3.5 LUBE AND HYDRAULIC ENCLOSURE LOW PRESSURE ALARM DECREASING: 0.2000 INH2O OR 0.4983 MBARNORM=NC-CEC;
PS-3404 3.4 SEAL OIL INLET PRESS LOW, START DC PUMP DECREASING: 96.00 PSIG OR 6.621 BARGFUNCTION: START DC PUMP
DEAD BAND = 0.1 TO 2.5 PSIG (5.86 TO 19.99 KPAG)
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
PSL-2930 7.5 H2 SUPPLY PRESSURE LOW DECREASING: 110.0 PSIG OR 7.587 BARG(INCREASING: 125.0 PSIG OR 8.621 BARG)NORM=NO;H2 SUPPLY PRESSURE LOW ALARM.
DEAD BAND = 0.2 TO 1 PSIG (0.0141 TO 0.070 KG/CM2G)
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
SIGNAL TO TCP VIA MODBUS PROTOCOL
PSL-2950 7.5 GENERATOR GAS PRESSURE LOW DECREASING: 58.00+-0.6000 PSIG OR 4.000+-0.0414 BARGGENERATOR CASING GAS PRESSURE LOW ALARM.
DEAD BAND = 0.2 TO 0.6 PSIG (0.0141 TO 0.0422 KG/CM2G)
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
SIGNAL TO TCP VIA MODBUS PROTOCOL
PT-071-1 6.2 1ST STAGE SHELL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: MONITOR, THRUST PROTECTION
PT-071-2 6.2 1ST STAGE SHELL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: MONITOR,THRUST PROTECTION
PT-071-3 6.2 1ST STAGE SHELL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: MONITOR, THRUST PROTECTION
PT-203-1 6.2 INLET STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: INLET STEAM PRESSURE SIGNAL FOR CONTROL AND LIMITING
PT-203-2 6.2 INLET STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: INLET STEAM PRESSURE SIGNAL FOR CONTROL AND LIMITING
26 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
27 F
Device System Settings
PT-203-3 6.2 INLET STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 2500 PSIG OR 172.4 BARGFUNCTION: INLET STEAM PRESSURE SIGNAL FOR CONTROL AND LIMITING
PT-206-1 6.2 HOT REHEAT PRESSURE4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL
PT-206-2 6.2 HOT REHEAT PRESSURE4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL
PT-206-3 6.2 HOT REHEAT PRESSURE4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL
PT-210A 1.7 EXHAUST VACUUM TRANSMITTER NO.14.000 MA= 0.0 INHG OR 0.0 BAR20.00 MA= 30.00 INHG OR 1.003 BARFUNCTION: MONITOR, ALARM AND TRIP ON LOW EXHAUST VACUUM
PT-210B 1.7 EXHAUST VACUUM TRANSMITTER NO.24.000 MA= 0.0 INHG OR 0.0 BAR20.00 MA= 30.00 INHG OR 1.003 BARFUNCTION: MONITOR, ALARM AND TRIP ON LOW EXHAUST VACUUM
PT-210C 1.7 EXHAUST VACUUM TRANSMITTER NO.34.000 MA= 0.0 INHG OR 0.0 BAR20.00 MA= 30.00 INHG OR 1.003 BARFUNCTION: MONITOR, ALARM AND TRIP ON LOW EXHAUST VACUUM
PT-210E 5.0C EXHAUST HOOD WATER SPRAY SUPPLY AVAILABLE4.000 MA= 0.0 PSIA OR 0.0 BARA20.00 MA= 100.0 PSIA OR 6.897 BARAHAZARDOUS ZONE: NON RATED
PT-211-1 6.2 COLD REHEAT PRESSURE (HP TURB EXHAUST) #14.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL
PT-211-2 6.2 COLD REHEAT PRESSURE (HP TURB EXHAUST) #24.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: PRESSURE SIGNAL FOR IV CONTROL
PT-212 5.0B STEAM SEAL MANIFOLD PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 125.0 PSIG OR 8.621 BARGFUNCTION: PRESSURE SIGNAL FOR SSFV/SSDV CONTROL
HAZARDOUS ZONE: NON RATED
PT-213A 1.7 LP INLET PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARG
PT-213B 1.7 LP INLET PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARG
PT-213C 1.7 LP INLET PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARG
27 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
28 F
Device System Settings
PT-218-1 6.3 LP ADM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARGFUNCTION: LP ADM PRESSURE CONTROL
PT-218-2 6.3 LP ADM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARGFUNCTION: LP ADM PRESSURE CONTROL
PT-218-3 6.3 LP ADM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARGFUNCTION: LP ADM PRESSURE CONTROL
PT-225-1 6.2 CROSSOVER STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 200.0 PSIG OR 13.79 BARGFUNCTION: MONITOR CROSSOVER STEAM PRESSURE
PT-232 5.0A PACKING GLAND EXHAUST PRESSURE TRANSMITTER4.000 MA= 0.0 INH2O OR 0.0 MBAR20.00 MA= 50.00 INH2O OR 124.6 MBARFUNCTION: MONITOR
HAZARDOUS ZONE: NON RATED
PT-245A 6.2 REHEAT BOWL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: MONITOR, THRUST PROTECTION
PT-245B 6.2 REHEAT BOWL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: MONITOR, THRUST PROTECTION
PT-245C 6.2 REHEAT BOWL PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: MONITOR, THRUST PROTECTION
PT-250 5.0B AUX STEAM PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 500.0 PSIG OR 34.49 BARGMAX EXPECTED STM SEAL SOURCE PRESSURE = 290 PSIA (20.0 BARA)
HAZARDOUS ZONE: NON RATED
PT-252 6.2 RH COOLING STEAM LINE PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 1000 PSIG OR 68.97 BARGFUNCTION: MONITOR
PT-270 3.1 BRG HEADER PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 90.00 PSIG OR 6.207 BARGFUNCTION: MONITOR
PT-281 4.0 HYD FLUID PRESSURE TRANSMITTER4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 3000 PSIG OR 206.9 BARGFUNCTION: MONITOR HYDRAULIC HEADER PRESSURE.
HAZARDOUS AREA : NON-RATED
28 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
29 F
Device System Settings
PT-2950 7.5 GENERATOR GAS PRESSURE4.000 MA= 0.0 PSIG OR 0.0 BARG20.00 MA= 100.0 PSIG OR 6.897 BARGLOW PRESSURE ALARM AT 58 PSIG (4.08 KG/CM2G).
HIGH PRESSURE ALARM AT 64 PSIG (4.50 KG/CM2G).
HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: `D` - FLAME PROOF
SIGNAL TO TCP VIA MODBUS PROTOCOL
QT-290A 7.5 CELL #1 TRANSMITTER SIGNAL4.000 MA= 70.00 OR 70.00 20.00 MA= 100.0 OR 100.0 HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: ``D`` AND ``IA``
SIGNAL TO TCP VIA MODBUS PROTOCOL
QT-290B 7.5 CELL #2 TRANSMITTER SIGNAL4.000 MA= 70.00 OR 70.00 20.00 MA= 100.0 OR 100.0 HAZARDOUS ZONE: ZONE 2
PROTECTION METHOD: ``D`` AND ``IA``
SIGNAL TO TCP VIA MODBUS PROTOCOL
REDP-1A 1.3 ROTOR EXPANSION DETECTOR PROBE50MM PROBEFUNCTION: MONITOR, DISPLAY, ALARM, AND HP DIFF EXPANSION CALCULATION
REDP-1B 1.3 ROTOR EXPANSION DETECTOR PROBE50MM PROBEFUNCTION: MONITOR, DISPLAY, ALARM, AND HP DIFF EXPANSION CALCULATION
REDX-1A 1.3 PROXIMITOR-ROTOR EXPANSIONRANGE: 100 - 1100 MILS (2.54 - 27.9 MM)FUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO. 1A
REDX-1B 1.3 PROXIMITOR-ROTOR EXPANSIONRANGE: 100 - 1100 MILS (2.54 - 27.9 MM)FUNCTION: PROVIDE HIGH FREQUENCY EXCITATION TO PROBE NO. 1B
RP-1 1.5 REFERENCE PROBEFUNCTION: PROVIDES ONCE PER REV SIGNAL
RX-1 1.5B PROXIMITOR-REFERENCE PROBE FOR VIB PHASEFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
S1 2.1 SHORTING TYPE SWITCHFUNCTION: PROVIDE THE DIRECT CONTACT FOR TGM
SEDP-1 1.3 CASE EXPANSION DETECTOR TO STC MONITORRANGE: 0-2 INCHESFUNCTION: MONITOR, DISPLAY, AND ALARM HIGH
SP-BPM-1 3.1 SPACE HEATER, LUBE OIL PUMP MOTOR #1350.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072
350W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
SP-BPM-2 3.1 SPACE HEATER, LUBE OIL PUMP MOTOR #2350.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072
350W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
29 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
30 F
Device System Settings
SP-CAFM-1 3.5 SPACE HEATER, COOLING AIR FAN MOTOR #160.00 W; 120 VAC; 1 PH; 60 HZ;IEC MOTOR
SP-CAFM-2 3.5 SPACE HEATER, COOLING AIR FAN MOTOR #260.00 W; 120 VAC; 1 PH; 60 HZ;IEC MOTOR
SP-CFM-1 7.5A SPACE HEATER FOR MOTOR CFM-1
120 VAC; 1 PH; 60 HZ;
SP-CFM-2 7.5A SPACE HEATER FOR MOTOR CFM-2120 VAC; 1 PH; 60 HZ;
SP-CFM-3 7.5A SPACE HEATER FOR MOTOR CFM-3120 VAC; 1 PH; 60 HZ;
SP-CFM-4 7.5A SPACE HEATER FOR MOTOR CFM-4120 VAC; 1 PH; 60 HZ;
SP-EBPM 3.1 SPACE HEATER, EMRG. DC LUBE PUMP MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072
200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
SP-ESPM 3.1 SPACE HEATER, EMERG. DC SEAL PUMP MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072
200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
SP-GXM-1 5.0A SPACE HEATER, GLAND EXHAUSTER MOTOR #1180.0 W; 120 VAC; 1 PH; 60 HZ;HAZARDOUS ZONE: NON RATED
SP-GXM-2 5.0A SPACE HEATER, GLAND EXHAUSTER MOTOR #2180.0 W; 120 VAC; 1 PH; 60 HZ;HAZARDOUS ZONE: NON RATED
SP-HCCM 4.0 SPACE HEATER FOR HEATING & COOLING CIRC PUMP MOTOR.200.0 W; 120 VAC; 1 PH; 60 HZ;SPACE HEATER WATTAGE <= 200 WATTS
HAZARDOUS AREA : NON-RATED
SP-HFPM-A 4.0 SPACE HEATER FOR HYD FLUID PUMP MOTOR A.200.0 W; 120 VAC; 1 PH; 60 HZ;SPACE HEATER RATING <= 200 WATTS
HAZARDOUS AREA : NON-RATED
SP-HFPM-B 4.0 SPACE HEATER FOR HYD FLUID PUMP MOTOR B.200.0 W; 120 VAC; 1 PH; 60 HZ;SPACE HEATER RATING <= 200 WATTS
HAZARDOUS AREA : NON-RATED
SP-OCM 3.1 SPACE HEATER, OIL CONDITIONER MOTOR200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072
200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
SP-PBM 2.0 SPACE HEATER, PIGGY BACK MOTOR65.00 W; 120 VAC; 1 PH; 60 HZ;
SP-TGM 2.0 SPACE HEATER, TURNING GEAR MOTOR65.00 W; 120 VAC; 1 PH; 60 HZ;
30 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
31 F
Device System Settings
SP-VXM-1 3.1 SPACE HEATER, VAPOR EXTRACTOR #1200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072
200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
SP-VXM-2 3.1 SPACE HEATER, VAPOR EXTRACTOR #2200.0 W; 120 VAC; 1 PH; 60 HZ;IEC 60034 & IEC 60072
200W IS MAXIMUM, ACTUAL RATING MAY BE LESS.
ST-201A 6.1 PRIMARY SPEED PROBE NO.1FUNCTION: PROVIDES SPEED SIGNAL TO STC CABINET ELECTRONICS
ST-201B 6.1 PRIMARY SPEED PROBE NO.2FUNCTION: PROVIDES SPEED SIGNAL TO STC CABINET ELECTRONICS
ST-201C 6.1 PRIMARY SPEED PROBE NO.3FUNCTION: PROVIDES SPEED SIGNAL TO STC CABINET ELECTRONICS
ST-202A 6.1 EMERGENCY OVERSPEED PROBE NO.1FUNCTION: PROVIDES OVERSPEED SIGNAL TO STC CABINET ELECTRONICS
ST-202B 6.1 EMERGENCY OVERSPEED PROBE NO.2FUNCTION: PROVIDES OVERSPEED SIGNAL TO STC CABINET ELECTRONICS
ST-202C 6.1 EMERGENCY OVERSPEED PROBE NO.3FUNCTION: PROVIDES OVERSPEED SIGNAL TO STC CABINET ELECTRONICS
SV-1203A 6.4D SERVO FOR RIGHT INTERCEPT VALVE POS CONTROLRATED FLOW: 24.00 GPM AT 1000 PSID 4-WAY, 3-COIL (33 MA PER COIL)
FUNCTION: ACTUATOR FLOW CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
SV-1204A 6.4D SERVO FOR LEFT INTERCEPT VALVE POS CONTROLRATED FLOW: 24.00 GPM AT 1000 PSID 4-WAY, 3-COIL (33 MA PER COIL)
FUNCTION: ACTUATOR FLOW CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
SV-211A 6.4C INLET CONTROL VALVE SERVO VALVERATED FLOW: 24.00 GPM AT 1000 PSID 4-WAY, 3-COIL, (33 MA PER COIL)
FUNCTON: CV #1 ACTUATOR FLOW CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
SV-211B 6.4C INLET CONTROL VALVE SERVO VALVERATED FLOW: 24.00 GPM AT 1000 PSID 4-WAY, 3-COIL, (33 MA PER COIL)
FUNCTON: CV #2 ACTUATOR FLOW CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
SV-216 6.4L LP ADM VALVE (OFF TURB) SERVO VALVERATED FLOW: 25.00 GPM AT 1000 PSID (95 LPM @ 68.97 BARD)
FUNCTION: CONTROLS POS OF OFF TURB LP CONTROL VLV
HAZARDOUS ZONE: NON RATED
31 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
32 F
Device System Settings
T1 2.1 TRANSFORMERFUNCTION: PROVIDE THE VOLTAGE FOR TURNING GEAR CIRCUIT
TAFM 4.0 TRANSFER & AUX FILTER UNIT MOTOR0.5000 HP; 1800 RPM; 120 VAC; 1 PH; 60 HZ;FUNCTION: POWERS PUMP ON HYD FLUID FILTERING SYSTEM
IEC 60034 7 IEC 60072
HAZARDOUS AREA : NON-RATED
TAFMS 4.0 TRANSFER & AUX FILTER PUMP MOTOR SWITCHFUNCTION: CONTROLS PUMP ON HYD FLUID FILTERING SYSTEM
HAZARDOUS AREA : NON-RATED
TC-2996A 7.5 DESICCANT BED #1 TEMPERATURE SWITCHINCREASING: 400.0 F OR 204.4 CNORMAL READING = 325 F +/- 25 F AT END OF HEATING CYCLE.
FUNCTION: HEATER PROTECTION
TC-2996B 7.5 DESICCANT BED #2 TEMPERATURE SWITCHINCREASING: 400.0 F OR 204.4 CNORMAL READING = 325 F +/- 25 F AT END OF HEATING CYCLE.
FUNCTION: HEATER PROTECTION
TCV-260 6.5B VALVE POSITIONER4 MA = OPEN
20 MA = CLOSED
FUNCTION: REGULATE COOLING WATER FLOW TO MAINTAIN CONSTANT LUBE OIL TEMPERATURE
HAZARDOUS ZONE: NON RATED
TDR-1 2.1 TIME DELAY ACFUNCTION: PROVIDE THE TIME DELAY FOR TG CIRCUIT
TE-200-1 1.1 INLET STEAM LINE TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START
TE-200-2 1.1 INLET STEAM LINE TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START
TE-200-3 1.1 INLET STEAM LINE TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START
TE-203A 1.1 1ST STAGE BOWL UPPER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START, WATER DETECTION
TE-203B 1.1 1ST STAGE BOWL UPPER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START, WATER DETECTION
TE-203C 1.1 1ST STAGE BOWL LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION
32 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
33 F
Device System Settings
TE-205A 1.1 REHEAT BOWL UPPER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION
TE-205C 1.1 REHEAT BOWL LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START WATER DETECTION
TE-205D 1.1 REHEAT BOWL LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START, WATER DETECTION
TE-206-1 1.1 HOT REHEAT LINE STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START
TE-206-2 1.1 HOT REHEAT LINE STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START
TE-206-3 1.1 HOT REHEAT LINE STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, CONTROL START
TE-209E 1.1 CROSSOVER PIPING STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-209F 1.1 CROSSOVER PIPING STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-210A 1.7 EXHAUST STEAM THERMOCOUPLE NO.1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM AND TRIP ON HIGH TEMP
TE-210B 1.7 EXHAUST STEAM THERMOCOUPLE NO.2TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM AND TRIP ON HIGH TEMP
TE-210C 1.7 EXHAUST STEAM THERMOCOUPLE NO.3TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM AND TRIP ON HIGH TEMP
TE-211A 1.1 HP EXHAUST UPPER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION
TE-211C 1.1 HP EXHAUST LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION
33 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
34 F
Device System Settings
TE-211D 1.1 HP EXHAUST LOWER INNER METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, WATER DETECTION
TE-211G 1.1 HP EXHAUST STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, TRIP ON HIGH TEMP
TE-211H 1.1 HP EXHAUST STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM , TRIP ON HIGH TEMP
TE-211J 1.1 HP EXHAUST STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, TRIP ON HIGH TEMP
TE-212A-1 5.0B STEAM SEAL HEADER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
ALARM PER GEK110856
HAZARDOUS ZONE: NON RATED
TE-212A-2 5.0B STEAM SEAL HEADER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
ALARM PER GEK110856
HAZARDOUS ZONE: NON RATED
TE-212A-3 5.0B STEAM SEAL HEADER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
ALARM PER GEK110856
HAZARDOUS ZONE: NON RATED
TE-212B 5.0A GLAND SEAL EXHAUST AIR/STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
HAZARDOUS ZONE: NON RATED
TE-213G 1.7 L-1 STAGE LOWER STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, AND TRIP ON HIGH TEMP
TE-213H 1.7 L-1 STAGE LOWER STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, TRIP ON HIGH TEMP
TE-213J 1.7 L-1 STAGE LOWER STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM, TRIP ON HIGH TEMP
34 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
35 F
Device System Settings
TE-215-A 1.1 REVERSE FLOW DISCHARGE VALVE LINE TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-227-1 1.1 LP ADM STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR FOR SUPERHEAT CHECK
TE-227-2 1.1 LP ADM STEAM TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR FOR SUPERHEAT CHECK
TE-240A 1.1 IP LAST STAGE BOWL UPPER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: WATER DETECTION
TE-240B 1.1 IP LAST STAGE BOWL LOWER TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: WATER DETECTION
TE-250-B 5.0B STEAM SEAL FEED TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
MAX EXPECTED TEMP FROM STM SEAL SOURCE = 554 DEG. F (290 DEG. C)
HAZARDOUS ZONE: NON RATED
TE-251E 5.0B LEAKOFF RE-ENTRY LINE TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; LOCATED DOWNSTREAM OF AOV-LRSV
FUNCTION: MONITOR
HAZARDOUS ZONE: NON RATED
TE-252 1.1 RH COOLING STEAM INLET TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-260B 3.1 LUBE OIL COOLER OUTLET TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;
TE-260H 3.1 LUBE OIL RESERVOIR TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;
TE-260J 3.1 LUBE OIL COOLER OUTLET TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;
TE-260K 3.1 LUBE OIL COOLER OUTLET TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;
TE-261A 1.6A ACTIVE THRUST BRG OIL DRAIN TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
35 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
36 F
Device System Settings
TE-261B 1.6A INACTIVE THRUST BRG OIL DRAIN TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-262 1.6A TURBINE/GENERATOR BEARING OIL DRAIN TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-263 1.6A TURBINE/GENERATOR BEARING OIL DRAIN TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-264 1.6A TURBINE/GENERATOR BEARING OIL DRAIN TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-265 1.6A TURBINE/GENERATOR BEARING OIL DRAIN TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-271A 1.6A THRUST BRG FACE UPPER INACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
TE-271B 1.6A THRUST BRG FACE LOWER INACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
TE-271C 1.6A THRUST BRG FACE UPPER ACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
TE-271D 1.6A THRUST BRG FACE LOWER ACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
TE-271I 1.6A THRUST BRG FACE RIGHT INACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-271J 1.6A THRUST BRG FACE LEFT INACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-271K 1.6A THRUST BRG FACE RIGHT ACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
TE-271L 1.6A THRUST BRG FACE LEFT ACTIVE METAL TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR
36 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
37 F
Device System Settings
TE-272A 1.6A TURB/GEN BRG NO.1 METAL TEMP #1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
TE-273A 1.6A TURB/GEN BRG NO.2 METAL TEMP #1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
TE-274A 1.6A TURB/GEN BRG NO.3 METAL TEMP #1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
TE-275A 1.6A TURB/GEN BRG NO.4 METAL TEMP #1TYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR, ALARM
TE-280 4.0 HYD FLUID RESERVOIR TEMPTYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; FUNCTION: MONITOR BULF RESERVOIR FLUID TEMPERATURE
ALARM AT 135F INCREASING
HAZARDOUS AREA : NON-RATED
TE-304 3.5 LUBE AND HYDRAULIC ENCLOSURE AIR TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED; ALARM AT 140F
TE-HTR1 3.1 IMMERSION HEATER SHEATH TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;
TE-HTR2 3.1 IMMERSION HEATER SHEATH TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;
TE-HTR3 3.1 IMMERSION HEATER SHEATH TEMPERATURETYPE K THERMOCOUPLE2 ELEMENTS; UNGROUNDED;
TG-AMM 2.1 AMMETERFUNCTION: DISPLAY THE TURNING GEAR MOTOR CURRENT
TGM 2.0 TURNING GEAR MOTOR10.00 HP; 1800 RPM; 460 VAC; 3 PH; 60 HZ;F.L.C.=13.3 A; L.R.C.=81 A
FUCTION: ROTATE TURBINE ROTOR AT LOW SPEED
TR-1 3.1 TRANSFORMER FOR HEATER POWERFUNCTION: 460 VAC TO HEATER THERMOSTAT VOLTAGE
TS-260 3.1 LUBE OIL RESERVOIR IMMERSION HEATER THERMOSTAT DECREASING: 75.00+-3.000 OR 75.00+-3.000 (INCREASING: 85.00+-3.000 OR 85.00+-3.000 )FUNCTION: TURN ON HTR-1/2/3 WHEN TEMP FALLS BELOW SET POINT.
TS-280B 4.0 HYDRAULIC FLUID COOLING CONTROL SWITCHINCREASING: 120.0 F OR 48.89 C(DECREASING: 110.0 F OR 43.33 C)NORM=(2) NO-OEC; FUNCTION: STARTS FLUID COOLING; HCCM.
HAZARDOUS AREA : NON-RATED
37 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
38 F
Device System Settings
TS-HCCM 4.0 THERMOSTAT FOR HEATING & COOLING CIRCULATION PUMP MOTOR.HAZARDOUS AREA : NON-RATED
TS-HFPM-A 4.0 THERMOSTAT FOR HYDRAULIC FLUID PUMP MOTOR A.INCREASING: 104.0+-5.000 F OR 40.00+-2.778 CHAZARDOUS AREA : NON-RATED
TS-HFPM-B 4.0 THERMOSTAT FOR HYDRAULIC FLUID PUMP MOTOR B.INCREASING: 104.0+-5.000 F OR 40.00+-2.778 CHAZARDOUS AREA : NON-RATED
VP-1X 1.5 DISPLACEMENT VIB PROBE BRG NO.1 X-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB
VP-1Y 1.5 DISPLACEMENT VIB PROBE BRG NO.1 Y-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB
VP-2X 1.5 DISPLACEMENT VIB PROBE BRG NO.2 X-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB
VP-2Y 1.5 DISPLACEMENT VIB PROBE BRG NO.2 Y-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB
VP-3X 1.5 DISPLACEMENT VIB PROBE BRG NO.3 X-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB
VP-3Y 1.5 DISPLACEMENT VIB PROBE BRG NO.3 Y-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB
VP-4X 1.5 DISPLACEMENT VIB PROBE BRG NO.4 X-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB
VP-4Y 1.5 DISPLACEMENT VIB PROBE BRG NO.4 Y-AXISFUNCTION: MONITOR, ALARM, AND TRIP ON VIB
VX-1X 1.5B PROXIMITOR-VIB PROBE BRG NO.1 X-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
VX-1Y 1.5B PROXIMITOR-VIB PROBE BRG NO.1 Y-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
VX-2X 1.5B PROXIMITOR-VIB PROBE BRG NO.2 X-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
VX-2Y 1.5B PROXIMITOR-VIB PROBE BRG NO.2 Y-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
VX-3X 1.5B PROXIMITOR-VIB PROBE BRG NO.3 X-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
VX-3Y 1.5B PROXIMITOR-VIB PROBE BRG NO.3 Y-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
VX-4X 1.5B PROXIMITOR-VIB PROBE BRG NO.4 X-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
VX-4Y 1.5B PROXIMITOR-VIB PROBE BRG NO.4 Y-AXISFUNCTION: PROVIDE HIGH FREQUENCY EXCITATION FOR PROBE
VXM-1 3.1 VAPOR EXTRACTOR MOTOR NO. 13.000 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL TANK VENT FAN
IEC 60034 & IEC 60072
VXM-2 3.1 VAPOR EXTRACTOR MOTOR NO.23.000 HP; 3600 RPM; 460 VAC; 3 PH; 60 HZ;FUNCTION: DRIVE LUBE OIL TANK VENT FAN
IEC 60034 & IEC 60072
ZE-5000A 4.0 PROXIMITY SWITCH ETD #1 - RESET20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED
38 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
39 F
Device System Settings
ZE-5000B 4.0 PROXIMITY SWITCH ETD #1 - TRIPPED20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED
ZE-5002A 4.0 PROXIMITY SWITCH ETD #2 - RESET20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED
ZE-5002B 4.0 PROXIMITY SWITCH ETD #2 - TRIPPED20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED
ZE-5004A 4.0 PROXIMITY SWITCH ETD #3 - RESET20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED
ZE-5004B 4.0 PROXIMITY SWITCH ETD #3 - TRIPPED20 - 250 VAC, 20-320 VDC, 50/60 HZHAZARDOUS AREA : NON-RATED
ZP-201A 1.2 AXIAL POS PROBE NO.1 FOR STC OR B/N MONITORINGFUNCTION: MONITOR, ALARM, AND TRIP ON THRUST BRG WEAR
ZP-201B 1.2 AXIAL POS PROBE NO.2 FOR STC OR B/N MONITORINGFUNCTION: MONITOR, ALARM, AND TRIP ON THRUST BRG WEAR
ZP-201C 1.2 AXIAL POS PROBE NO.3 FOR STC OR B/N MONITORINGFUNCTION: MONITOR, ALARM, AND TRIP ON THRUST BRG WEAR
ZPX-201A 1.2 PROXIMITOR - AXIAL POSITION PROBE NO.1FUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.1
ZPX-201B 1.2 PROXIMITOR - AXIAL POSITION PROBE NO.2FUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.2
ZPX-201C 1.2 PROXIMITOR - AXIAL POSITION PROBE NO.3FUNCTION: PROVIDES HIGH FREQUENCY EXCITATION TO PROBE NO.3
ZS-1203C 6.4D RIGHT INTERCEPT VALVE CLOSED LIMIT SWITCHFUNCTION: CONTACTS CLOSE ON RIGHT CRV RIV CLOSE FOR CIRCUIT BREAKER
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-1204C 6.4D LEFT INTERCEPT VALVE CLOSED LIMIT SWITCHFUNCTION: CONTACTS CLOSE ON RIGHT CRV RIV CLOSE FOR CIRCUIT BREAKER
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-1212C 6.4D RIGHT RSV CLOSED LIMIT SWITCH FOR CIRCUIT BREAKERFUNCTION: CONTACTS CLOSE ON RIGHT CRV RIV CLOSE FOR CIRCUIT BREAKER
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-1213C 6.4D LEFT RSV CLOSED LIMIT SWITCH FOR CIRCUIT BREAKERFUNCTION: CONTACTS CLOSE ON RIGHT CRV RIV CLOSE FOR CIRCUIT BREAKER
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
39 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
40 F
Device System Settings
ZS-1214A 6.4R EQUALIZER VALVE CLOSED LIMIT SWITCH (RH CRV)DPDT-DOUBLE BREAK; NORM=(2) NO-CES
FUCTON: (2) NO CONTACTS CLOSE ON EV#2 CLOSE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-1214B 6.4R EQUALIZER VLV OPEN LIMIT SWITCH (RH CRV)DPDT-DOUBLE BREAK; NORM=(2) NO-CES
FUNCTON: (2) NO CONTACTS CLOSE ON EV#2 OPEN
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-1215A 6.4R POSITION SWITCH - LH EQUALIZER VALVE CLOSED ENDDPDT-DOUBLE BREAK; NORM=(2) NO-CES
FUNCTON: (2) NO CONTACTS CLOSE ON EV#1 CLOSE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-1215B 6.4R POSITION SWITCH - LH EQUALIZER VALVE OPEN ENDDPDT-DOUBLE BREAK; NORM=(2) NO-CES
FUNCTON: (2) NO CONTACTS CLOSE ON EV#1 OPEN
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-200C 6.4C STOP VALVE NO.1 CLOSED POS SWITCH FOR CIRCUIT BREAKERFUNCTION: CONTACTS CLOSE ON SV #1 CLOSE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-201C 6.4C STOP VALVE NO.2 CLOSED POS SWITCH FOR CIRCUIT BREAKERFUNCTION: CONTACTS CLOSE ON SV #2 CLOSE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-203A 6.4M LP ADM STOP VALVE NO.1 CLOSED POS LIMIT SWITCHFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS CLOSED
HAZARDOUS ZONE: NON RATED
ZS-203B 6.4M LP ADM STOP VALVE NO.1 OPEN POS LIMIT SWITCHFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS OPEN
HAZARDOUS ZONE: NON RATED
ZS-203C 6.4M LP ADM STOP VALVE NO.1 CLOSED POS SWITCH FOR BREAKERFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS CLOSED
HAZARDOUS ZONE: NON RATED
ZS-203D 6.4M LP ADM STOP VALVE NO.1 TEST POS LIMIT SWITCHFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS IN TEST POS
HAZARDOUS ZONE: NON RATED
ZS-203E 6.4M LP ADM STOP VALVE NO.1 CLOSED POS FOR BREAKERFUNCTION: PROVIDES SIGNAL WHEN STOP VLV IS CLOSED
HAZARDOUS ZONE: NON RATED
ZS-211AC 6.4C CONTROL VALVE NO.1 CLOSED POSITION SWITCHFUNCTION : CONTACTS CLOSE ON CV#1 CLOSE FOR CIRCUIT BREAKER
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
40 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
41 F
Device System Settings
ZS-211BC 6.4C CONTROL VALVE NO.2 CLOSED POSITION SWITCHFUNCTION : CONTACTS CLOSE ON CV#2 CLOSE FOR CIRCUIT BREAKER
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-216 6.4L FUNCTION``LP ADM VALVE CLOSED POS SWITCHFUNCTION: PROVIDES SIGNAL WHEN CONTROL VLV IS CLOSED
HAZARDOUS ZONE: NON RATED
ZS-220A 6.4S REVERSE FLOW VALVE CLOSED LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE CLOSED
HAZARDOUS ZONE: NON RATED
ZS-220B 6.4S REVERSE FLOW VALVE OPEN LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE OPEN
HAZARDOUS ZONE: NON RATED
ZS-2445A 6.4U REVERSE FLOW DISCHARGE VALVE CLOSED LIMIT SWITCHDPDT-DOUBLE BREAK; NORM=(2) NO-CES
FUNCTION: (2) NO CONTACTS CLOSE ON RFDV CLOSE
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-2445B 6.4U REVERSE FLOW DISCHARGE VALVE OPEN LIMIT SWITCHDPDT-DOUBLE BREAK; NORM=(2) NO-CES
FUNCTION: (2) NO CONTACTS CLOSE ON RFDV OPEN
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZS-260C 3.1 LIFT OIL LIMIT SWITCH- PERMISSIVE TO STARTFUNCTION: INDICATES PUMP SUCTION SIDE ISOLATION VALVE IS OPEN.
ZS-260D 3.1 LIFT OIL LIMIT SWITCH- PERMISSIVE TO STARTFUNCTION: INDICATES PUMP SUCTION SIDE ISOLATION VALVE IS OPEN.
ZS-280A 4.0 INDICATES VALVE POSITIONPOSITION SWITCHFUNCTION: INDICATES SUCTION SHUT OFF VALVE A IS FULLY OPEN
HAZARDOUS AREA : NON-RATED
ZS-280B 4.0 INDICATES VALVE POSITIONPOSITION SWITCHFUNCTION: INDICATES SUCTION SHUT OFF VALVE B IS FULLY OPEN
HAZARDOUS AREA : NON-RATED
ZS-288 2.0 TURNING GEAR ENGAGED POSITION SWITCH3 N.C. & 3 N.O. CONTACTS; 20 A
FUCTION: INDICATES TURNING GEAR ENGAGED
(NOTE: ALWAYS 120VAC, 50/60HZ RATED)
CONTROLS PROVIDED STEP DOWN TRANSFORMER PROVIDES 120V,AC, 50/60HZ REGARDLESS OF CUSTOMER SUPPLIED VOLTAGE
ZS-289 2.0 TURNING GEAR DISENGAGED POSITION SWITCH2 N.C. & 2 N.O. CONTACTS; 120 VAC; 20 A
FUCTION: INDICATES TURNING GEAR DISENGAGED
(NOTE: ALWAYS 120VAC, 50/60HZ RATED)
CONTROLS PROVIDED STEP DOWN TRANSFORMER PROVIDES 120V,AC, 50/60HZ REGARDLESS OF CUSTOMER SUPPLIED VOLTAGE
41 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
42 F
Device System Settings
ZS-2996 7.5 DUAL GAS DRYER PLC`S LIMIT SWITCHTHIS LIMIT SWITCH IS POWERED BY THE GAS DRYER AND FOR THE GAS DRYER`S ON BASE PLC. THE PLC AND LIMIT SWITCH DO NOT TALK WITH THE MARK VI, INTERNALLY CONTROLLED.
ZS-CSBV-C 6.5B COOLING STEAM BLOCKING VALVE CLOSED POSITION SWITCHNORM=(1) NO; DPDT; CONTACT CLOSED WHEN VALVE CLOSED
HAZARDOUS ZONE: NON RATED
ZS-CSBV-O 6.5B COOLING STEAM BLOCKING VALVE OPEN POSITION SWITCHNORM=(1) NO; DPDT; CONTACT CLOSED WHEN VALVE OPEN
HAZARDOUS ZONE: NON RATED
ZS-LRSV-C 6.5B LEAKOFF RE-ENTRY STOP VALVE CLOSED POSITION LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE CLOSED
HAZARDOUS ZONE: NON RATED
ZS-LRSV-O 6.5B LEAKOFF RE-ENTRY STOP VALVE OPEN POSITION LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE OPEN
HAZARDOUS ZONE: NON RATED
ZSC2253 6.5B 1ST STG REHEAT COOLING VLV CLOSED POSITION LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE CLOSED
HAZARDOUS ZONE: NON RATED
ZSO2253 6.5B 1ST STG REHEAT COOLING VLV OPEN POSITION LIMIT SWITCHNORM=(1) NO; CONTACT CLOSED WHEN VALVE OPEN
HAZARDOUS ZONE: NON RATED
ZT-1203-1 6.4D RIGHT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ
FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-1203-2 6.4D RIGHT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ
FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-1203-3 6.4D RIGHT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ
FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-1204-1 6.4D LEFT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ
FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
42 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
43 F
Device System Settings
ZT-1204-2 6.4D LEFT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ
FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-1204-3 6.4D LEFT INTERCEPT VALVE POS DETECTOR+/- 4.0 INCH (100 MM), 20V, 3000HZ
FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-1212 6.4D RIGHT REHEAT STOP VALVE POS DETECTORONE(1) MAGNETO RESTRICTIVE DEVICE, POWER SUPPLY 24 VDC/150 MA
OUTPUT: 4-20MA (INCREASING CURRENT TO OPEN)
FUNCTION : POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-1213 6.4D LEFT REHEAT STOP VALVE POS DETECTORONE(1) MAGNETO RESTRICTIVE DEVICE, POWER SUPPLY 24 VDC/150 MA
OUTPUT: 4-20MA (INCREASING CURRENT TO OPEN)
FUNCTION: POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-200-1 6.4C STOP VALVE POSITION DETECTORONE(1) MAGNETO RESTRICTIVE DEVICE, POWER SUPPLY 24 VDC/150 MA
OUTPUT: 4-20MA (INCREASING CURRENT TO OPEN).
FUNCTION : POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-201-1 6.4C STOP VALVE POSITION DETECTORONE(1) MAGNETO RESTRICTIVE DEVICE, POWER SUPPLY 24 VDC/150 MA
OUTPUT: 4-20MA (INCREASING CURRENT TO OPEN).
FUNCTION : POSITION SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-211A-1 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ
FUNCTION: POS SIGNAL FOR CV #1 MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-211A-2 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ
FUNCTION: POS SIGNAL FOR CV #1 MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
43 of 44
© COPYRIGHT 2010-2011 GE ENERGY (USA), LLC AND/OR ITS AFFILIATES. All rights reserved. GE Energy STEAM Proprietary Technical Information
GE CLASS II (INTERNAL NON-CRITICAL)
SIZE DWG NO SH REV
A
GENERAL ELECTRIC COMPANY SIZE CAGE CODE DWG NO
AGE EnergygDRAWN
ISSUED SCALE SHEET
397A3135
397A3135
NESHEWAIT, ADI 2010-02-17
BENES, LINDA NONE
44 F
Device System Settings
ZT-211A-3 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ
FUNCTION: POS SIGNAL FOR CV #1 MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-211B-1 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ
FUNCTION: POS SIGNAL FOR CV #2 MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-211B-2 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ
FUNCTION: POS SIGNAL FOR CV #2 MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-211B-3 6.4C INLET VALVE POSITION FEEDBACK TRANSDUCER+/- 2.0 INCH (+/-50MM), 20V, 3000HZ
FUNCTION: POS SIGNAL FOR CV #2 MONITORING AND CONTROL
HAZARDOUS ZONE: NON-RATED
PROTECTION METHOD: SIMPLE
ZT-216-1 6.4L LP ADM VALVE (OFF TURB) POS DETECTORFUNCTION: POS SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON RATED
ZT-216-2 6.4L LP ADM VALVE (OFF TURB) POS DETECTORFUNCTION: POS SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON RATED
ZT-216-3 6.4L LP ADM VALVE (OFF TURB) POS DETECTORFUNCTION: POS SIGNAL FOR MONITORING AND CONTROL
HAZARDOUS ZONE: NON RATED
ZT-SSDV 6.5B AOV-SSDV POSITION TRANSMITTER4 MA = 0% STROKE
20 MA = 100% STROKE
4-20 MA POSITION FEEDBACK
``2-WIRE`` TYPE
HAZARDOUS ZONE: NON RATED
ZT-SSFV 6.5B AOV-SSFV POSITION TRANSMITTER4 MA = 0% STROKE
20 MA = 100% STROKE
4-20 MA POSITION FEEDBACK
``2-WIRE`` TYPE
HAZARDOUS ZONE: NON RATED
ZT-WSV 6.5B AOV-WSV POSITION TRANSMITTER4 MA = 0% STROKE
20 MA = 100% STROKE
4-20 MA POSITION FEEDBACK
``2-WIRE`` TYPE
HAZARDOUS ZONE: NON RATED