EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING DATA VRV Aurora Series RELQ-TATJA / TAYDA / TAYCA HEAT RECOVERY 60 Hz DESIGN MANUAL

EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

EDUS371705D-D202009

Engineering Data

Heat Recovery 60 Hz

Design ManualRELQ-TATJA, 208 / 230 VRELQ-TAYDA, 460 VRELQ-TAYCA, 575 V

EDU

S371705D-D

ENG

INEER

ING

DA

TA VR

V Aurora Series R

ELQ-TA

TJA / TA

YDA

/ TAYC

A H

EAT R

ECO

VERY 60 H

z DESIG

N M

AN

UA

L

Page 2: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING
Page 3: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

1

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Table of Contents

1. FeaturesandBenefits ................................................................................32. Compatibility ...............................................................................................43. Nomenclature .............................................................................................54. Model Names .............................................................................................9

4.1 Outdoor Units ....................................................................................94.2 Indoor Units .....................................................................................104.3 Branch Selector Unit ....................................................................... 114.4 Air Treatment Equipment ................................................................ 11

5. External Appearance ................................................................................125.1 Outdoor Units ..................................................................................125.2 Indoor Units .....................................................................................135.3 Branch Selector Unit .......................................................................145.4 Air Treatment Equipment ................................................................14

6. Outdoor Unit Combination ........................................................................157. Interchangeability .....................................................................................168. Capacity Range ........................................................................................17

8.1 Connection Ratio ............................................................................178.2 Capacity Range of Connectable Indoor Units .................................188.3 Limitation of Capacity Index for Heat Recovery ..............................19

9. Specifications ...........................................................................................209.1 RELQ-TATJA ...................................................................................209.2 RELQ-TAYDA ..................................................................................229.3 RELQ-TAYCA ..................................................................................24

10.Dimensions ...............................................................................................2611. Service Space ..........................................................................................2812. Center of Gravity ......................................................................................3013. Foundation Drawing .................................................................................3214. Piping Diagrams .......................................................................................3315. Wiring Diagrams .......................................................................................3516. Field Wiring ..............................................................................................4517. Electrical Characteristics ..........................................................................47

17.1 RELQ72-240TATJA .........................................................................4717.2 RELQ72-240TAYDA ........................................................................4817.3 RELQ72-240TAYCA ........................................................................49

18. Operation Limits .......................................................................................5019. Low Ambient Cooling Enhancement ........................................................5120. Sound Levels (Reference Data) ...............................................................52

Page 4: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

2

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

21. Accessories ..............................................................................................5521.1 Optional Accessories ......................................................................55

22. Selection Procedure .................................................................................5622.1 Selection Procedure ........................................................................56

23. Caution Label ...........................................................................................6223.1 RELQ72-240TATJA / TAYDA / TAYCA ............................................62

24. Caution for Refrigerant Leaks ..................................................................7124.1 Introduction .....................................................................................7124.2 Procedure for Checking Maximum Concentration ..........................72

25. Safety Devices Setting .............................................................................7425.1 FXFQ-T ...........................................................................................7425.2 FXZQ-TA .........................................................................................7425.3 FXUQ-P ...........................................................................................7425.4 FXEQ-P ...........................................................................................7425.5 FXDQ-M ..........................................................................................7525.6 FXSQ-TA .........................................................................................7525.7 FXMQ-PB ........................................................................................7525.8 FXMQ-M .........................................................................................7525.9 FXHQ-M ..........................................................................................7625.10 FXAQ-P .........................................................................................7625.11 FXLQ-M, FXNQ-M .........................................................................7625.12 FXTQ-TA .......................................................................................7625.13 CXTQ-TA .......................................................................................76

Appendix........................................................................................................771. Introduction ...............................................................................................78

1.1 ED Book List ...................................................................................781.2 Publication List of Engineering Data for VRV Products ..................79

Page 5: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

3

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1. Features and Benefits

The new VRV Aurora Series heat recovery unit demonstrates Daikin's technological leadership by offeringthefirstVRVaircooledsystemthatdeliverseffectiveandefficientheatingdownto−22°FWB(−30°CWB).• Available in 6, 8, 10 ton single modules and 12, 16, 20 ton multi-module systems• First Air Cooled VRVsystemtodeliverheatingdownto−22°F(−30°C)asstandard• Daikin’s patented inverted based vapor injection compressor delivers high heating capacity of up to100%at0°F(−18°C),upto85%at−13°F(−25°C)andupto60%at−22°F(−30°C)

•Refrigerantcooledefficientandstableinverterboardoperation,independentofambientconditions

• Hot gas base pan circuit allows installation without additional drain pan heater• Added peace of mind with ability of Auto changeover to back up (auxiliary) heat•YearroundcomfortandenergyefficiencydeliveredbycombingVRV and Variable Refrigerant

Temperature (VRT) technologies• Designed and optimized for Total Cost of Construction (TCC) and reduced Life Cycle Cost (LCC)•Corrosionresistant,1000hrsaltspraytestedDaikinPEbluefinheatexchanger• Ships factory standard with coil guards• Compatible with the full suite of VRV-IV T-series Branch Selector Boxes• Seamless connection to all VRV M, P and T series indoor units•Easecommissioningwithabilitytoprogramsettingsoffsiteusingnewconfiguratortool•3-digit7-segmentdigitaldisplayontheunitforimprovedandfasterconfiguration,commissioning,

and troubleshooting• Backed by 10 year parts limited warranty and 10 years replacement compressor limited warranty*

* Complete warranty details available from local distributor or manufacturer's representative

Page 6: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

4

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

2. Compatibility

208/230 V model 460 V model 575 V modelNew model Previous model New model Previous model New model Previous model

RELQ72TATJA RELQ72TATJU RELQ72TAYDA RELQ72TAYDU RELQ72TAYCA RELQ72TAYCURELQ96TATJA RELQ96TATJU RELQ96TAYDA RELQ96TAYDU RELQ96TAYCA RELQ96TAYCURELQ120TATJA RELQ120TATJU RELQ120TAYDA RELQ120TAYDU RELQ120TAYCA RELQ120TAYCURELQ144TATJA RELQ144TATJU RELQ144TAYDA RELQ144TAYDU RELQ144TAYCA RELQ144TAYCURELQ192TATJA RELQ192TATJU RELQ192TAYDA RELQ192TAYDU RELQ192TAYCA RELQ192TAYCURELQ240TATJA RELQ240TATJU RELQ240TAYDA RELQ240TAYDU RELQ240TAYCA RELQ240TAYCU

Page 7: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

5

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

3. Nomenclature

Outdoor Unit

Minor revision

Power supply symbolTJ: 3 phase, 208 / 230 V, 60 HzYD: 3 phase, 460 V, 60 HzYC: 3 phase, 575 V, 60 Hz

Indicates minor change category

Indicates major design categoryT: VRV IV

Capacity indication in cooling

RefrigerantQ: R410A

Indicates that this is aREL: Heat recovery air cooled (Cold Climate)

Q TJ AT A240REL

Page 8: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

6

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Indoor Unit

M 54 VJPB UX QF

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208/230 V, 60 HzSBL: 1 phase, 120 V, 60 Hz

Indicates major design category

Capacity indication in cooling05: 5,800 Btu/h 18: 18,000 Btu/h 48: 48,000 Btu/h07: 7,500 Btu/h 24: 24,000 Btu/h 54: 54,000 Btu/h09: 9,500 Btu/h 30: 30,000 Btu/h 60: 60,000 Btu/h12: 12,000 Btu/h 36: 36,000 Btu/h 72: 72,000 Btu/h15: 15,000 Btu/h 42: 42,000 Btu/h 96: 96,000 Btu/h

RefrigerantQ: R410A

ShapeF: Ceiling mounted cassette (Round flow with sensing)Z: VISTA™ 2 × 2 cassette unitU: 4-way blow ceiling-suspendedE: One way blow cassetteD: Slim ceiling mounted ductS: MSP concealed ducted unitM: Ceiling mounted ductH: Ceiling suspendedA: Wall mountedL: Floor standingN: Concealed floor standingT: Air handling unit (FXTQ) Upflow/Downflow (CXTQ)

Series categoryX: Inverter

Unit categoryF: Indoor unit for air cooled typeC: Cased coil unit

Page 9: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

7

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Branch Selector Unit

Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz

Indicates major design categoryT: VRV IV (Heat Recovery)

Capacity indication36: 36,000 Btu/h60: 60,000 Btu/h96: 96,000 Btu/h

Refrigerant: R410A

Unit categoryBS: Branch selector unit

BS T VJQ 36

Single Branch Selector Unit

Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz

Indicates major design categoryT: VRV IV (Heat Recovery)

Capacity indication of connectable indoor units per branch 54: 54,000Btu/h

Refrigerant: R410A

Number of branches4: 4 branches 6: 6 branches 8: 8 branches10: 10 branches12: 12 branches

Unit categoryBSF: Branch selector unit (Flex series)BS: Branch selector unit (Standard series)

BS T VJQ4 54

Multi Branch Selector Unit

Page 10: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

8

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Air Treatment Equipment

M 48 VJ UM FX QF

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz

Outdoor air processing unit

Indicates major design category

Capacity indication in cooling48: 48,000 Btu/h72: 72,000 Btu/h96: 96,000 Btu/h

RefrigerantQ: R410A

ShapeM: Ceiling mounted duct

Series categoryX: Inverter

Unit categoryF: Indoor unit for air cooled type

Outdoor Air Processing Unit

UG300V A M VJ

Standard symbolU: United States of America

Power supply symbolVJ: 1 phase, 208 / 230 V, 60 Hz

Indicates major design category

Airflow rate (H)300: 300 cfm 470: 470 cfm 600: 600 cfm1200: 1,200 cfm

Mounted type

Air

Ventilation

Energy Recovery Ventilator (VAM series)

Page 11: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

9

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

4. Model Names4.1 Outdoor Units

Capacity range 6 ton 8 ton 10 ton 12 ton 14 ton 16 ton 18 ton 20 ton Power supply, StandardCapacity index 72 96 120 144 168 192 216 240

Heat recovery 208 / 230 V RELQ 72TA 96TA 120TA 144TA 168TA 192TA 216TA 240TA TJAHeat recovery 460 V RELQ 72TA 96TA 120TA 144TA 168TA 192TA 216TA 240TA YDAHeat recovery 575 V RELQ 72TA 96TA 120TA 144TA 168TA 192TA 216TA 240TA YCA

TJ: 3 phase, 208 / 230 V, 60 HzYD: 3 phase, 460 V, 60 HzYC: 3 phase, 575 V, 60 HzA: Minor revision

Heat Recovery 208 / 230 V

Model name RELQ72TATJA RELQ96TATJA RELQ120TATJAOutdoor unit 1 RELQ72TATJA RELQ96TATJA RELQ120TATJA

Model name RELQ144TATJA RELQ192TATJA RELQ240TATJAOutdoor unit 1 RELQ72TATJA RELQ96TATJA RELQ120TATJAOutdoor unit 2 RELQ72TATJA RELQ96TATJA RELQ120TATJA

Heat Recovery 460 V

Model name RELQ72TAYDA RELQ96TAYDA RELQ120TAYDAOutdoor unit 1 RELQ72TAYDA RELQ96TAYDA RELQ120TAYDA

Model name RELQ144TAYDA RELQ192TAYDA RELQ240TAYDAOutdoor unit 1 RELQ72TAYDA RELQ96TAYDA RELQ120TAYDAOutdoor unit 2 RELQ72TAYDA RELQ96TAYDA RELQ120TAYDA

Heat Recovery 575 V

Model name RELQ72TAYCA RELQ96TAYCA RELQ120TAYCAOutdoor unit 1 RELQ72TAYCA RELQ96TAYCA RELQ120TAYCA

Model name RELQ144TAYCA RELQ192TAYCA RELQ240TAYCAOutdoor unit 1 RELQ72TAYCA RELQ96TAYCA RELQ120TAYCAOutdoor unit 2 RELQ72TAYCA RELQ96TAYCA RELQ120TAYCA

Page 12: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

10

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

4.2 Indoor Units

Capacity Range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power Supply, StandardCapacity Index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60 72 96

Ceiling mounted cassette (Roundflowwithsensing)type

FXFQ — 07T 09T 12T 15T 18T — 24T 30T 36T — 48T — — — —

VJU

VISTA™ 2 × 2 cassette unit FXZQ 05TA 07TA 09TA 12TA 15TA 18TA — — — — — — — — — —4-way blow ceiling-suspended type FXUQ — — — — — — 18P 24P 30P 36P — — — — — —

One way blow cassette type FXEQ — 07P 09P 12P 15P 18P — 24P — — — — — — — —Slim ceiling mounted duct type FXDQ — 07M 09M 12M — 18M — 24M — — — — — — — —

MSP concealed ducted unit FXSQ 05TA 07TA 09TA 12TA 15TA 18TA — 24TA 30TA 36TA — 48TA 54TA — — —Ceiling mounted duct type (Middle and high static pressure)

FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB — — —

Ceiling mounted duct type FXMQ — — — — — — — — — — — — — — 72M 96MCeiling suspended type FXHQ — — — 12M — — — 24M — 36M — — — — — —Wall mounted type FXAQ — 07P 09P 12P — 18P — 24P — — — — — — — —Floor standing type FXLQ — 07M 09M 12M — 18M — 24M — — — — — — — —Concealedfloorstandingtype FXNQ — 07M 09M 12M — 18M — 24M — — — — — — — —

Air handling unit FXTQ— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUA— — 09TA 12TA — 18TA — 24TA 30TA 36TA 42TA 48TA 54TA 60TA — — VJUD

Cased coil unit CXTQ — — — — — — — 24TA — 36TA — 48TA — 60TA — — SBLU

Page 13: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

11

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

4.3 Branch Selector Unit4.3.1 Single Branch Selector Unit

Series Model name Power supply, StandardHeat recovery BSQ 36T 60T 96T VJ

Note: No interchangeability between BSVQ-PVJU and BSQ-TVJ.

VJ: 1 phase, 208 / 230 V, 60 Hz

4.3.2 Multi Branch Selector UnitFlex Series

Series Model name Power supply, standardHeat recovery BSF 4Q54T 6Q54T 8Q54T VJ

Note:No interchangeability between BSV-Q36PVJU and BSF-Q54TVJ.

VJ: 1 phase, 208/230 V, 60 Hz

Standard Series

Series Model name Power supply, standardHeat recovery BS 4Q54T 6Q54T 8Q54T 10Q54T 12Q54T VJ

Note:No interchangeability between BSV-Q36PVJU and BS-Q54TVJ.

VJ: 1 phase, 208/230 V, 60 Hz

4.4 Air Treatment EquipmentOutdoor Air Processing Unit

Series Model name Power supply, StandardFXMQ 48MF 72MF 96MF VJU

VJ: 1 phase, 208 / 230 V, 60 HzU(VJU): Standard symbol

Energy Recovery Ventilator (VAM series)

Series Model name Power supply, StandardVAM 300G 470G 600G 1200G VJU

VJ: 1 phase, 208 / 230 V, 60 HzU(VJU): Standard symbol

Page 14: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

12

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

5. External Appearance5.1 Outdoor UnitsSingle Outdoor Units

RELQ72TATJARELQ96TATJARELQ120TATJA

RELQ72TAYDARELQ96TAYDARELQ120TAYDA

RELQ72TAYCARELQ96TAYCARELQ120TAYCA

6, 8, 10 ton

Double Outdoor Units

RELQ144TATJARELQ192TATJARELQ240TATJA

RELQ144TAYCARELQ192TAYCARELQ240TAYCA

RELQ144TAYDARELQ192TAYDARELQ240TAYDA

12, 16, 20 ton

Page 15: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

13

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

5.2 Indoor Units

Ceilingmountedcassette(Roundflowwithsensing)type

FXFQ-T

Shown with BYCQ125B-W1

Ceiling mounted duct type

FXMQ-M

VISTA™ 2 × 2 cassette unit

FXZQ-TA

Shown with BYFQ60C3W1W Shown with BYFQ60C3W1S

Ceiling suspended type

FXHQ-M

4-way blow ceiling-suspended type

FXUQ-P

Wall mounted type

FXAQ-P

One way blow cassette type

FXEQ-P

Floor standing type

FXLQ-M

Slim ceiling mounted duct type

FXDQ-M

Concealedfloorstandingtype

FXNQ-M

MSP concealed ducted unit

FXSQ-TA

Air handling unit

FXTQ-TA

Ceiling mounted duct type (Middle and high static pressure)

FXMQ-PB

Cased coil unit

CXTQ-TA

Page 16: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

14

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

5.3 Branch Selector Unit5.3.1 Single Branch Selector Unit

Single port

BSQ36TVJBSQ60TVJBSQ96TVJ

5.3.2 Multi Branch Selector UnitFlex Series

BSF4Q54TVJ BSF6Q54TVJ BSF8Q54TVJ

Standard Series

BS4Q54TVJ BS6Q54TVJBS8Q54TVJ

BS10Q54TVJBS12Q54TVJ

5.4 Air Treatment Equipment

Outdoor air processing unit

FXMQ-MF

Energy recovery ventilator (VAM series)

VAM-G

Page 17: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

15

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

6. Outdoor Unit Combination

Model nameSystem capacity Number of

unitsModule Outdoor unit multi connection

piping kit *1Ton HP kW 72 96 120RELQ72TATJARELQ72TAYDARELQ72TAYCA

6 7.5 21.1 1 l

—RELQ96TATJARELQ96TAYDARELQ96TAYCA

8 10.0 28.1 1 l

RELQ120TATJARELQ120TAYDARELQ120TAYCA

10 12.5 35.2 1 l

RELQ144TATJARELQ144TAYDARELQ144TAYCA

12 15.0 42.2 2 ll

BHFP26P100UBHFP26P100UA

RELQ192TATJARELQ192TAYDARELQ192TAYCA

16 20.0 56.3 2 ll

RELQ240TATJARELQ240TAYDARELQ240TAYCA

20 25.0 70.3 2 ll

Note:*1. For multiple connection, the outdoor unit multi connection piping kit (separately sold) is required.

Page 18: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

16

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

7. Interchangeability

Branch selector unit

Outdoor unit

T-series branch selector unit (Reference)P-series branch selector unit

Single branch selector unit

Multi branch selector unit Single branch selector unit

Multi branch selector unitFlex series Standard series

BSQ36TVJBSQ60TVJBSQ96TVJ

BSF4Q54TVJBSF6Q54TVJBSF8Q54TVJ

BS4Q54TVJBS6Q54TVJBS8Q54TVJBS10Q54TVJBS12Q54TVJ

BSVQ36PVJUBSVQ60PVJUBSVQ96PVJU

BSV4Q36PVJUBSV6Q36PVJU

Heat recovery RELQ-TARELQ-TATJA Connectable Connectable Connectable Not connectable Not connectableRELQ-TAYDA Connectable Connectable Connectable Not connectable Not connectableRELQ-TAYCA Connectable Connectable Connectable Not connectable Not connectable

Note:*1. Combination of P-series and T-series of Branch selector units in a single system is not permitted.

Combining the two series may cause malfunction.

Page 19: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

17

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

8. Capacity Range8.1 Connection Ratio

Connection ratio =Total capacity index of the indoor units

Capacity index of the outdoor units

TypeMin.

connection ratio

Max. connection ratio

Types of connected indoor units Type of connected air treatment equipment

When using only FXDQ, FXMQ-PB,

FXAQ, FXSQ07-54TA

When using at least one FXZQ05TA, FXSQ05TA,

FXFQ07/09When using other indoor unit models

FXMQ-MF

When FXMQ-MF is only connected

When FXMQ-MF and indoor units are connected

Single outdoor units70% 200% *1

180% *1 200% *1100% 100% *2 *3

Double outdoor units 160% *1 160% *1

Note:*1.Iftheoperationalcapacityofindoorunitsismorethan130%,lowairflowoperationisenforcedinalltheindoorunits.Fieldsettingnowexiststo

configurethissituation.Forcoolingandheatingmode–seebelow.*2. When outdoor-air processing units (FXMQ-MF) and standard indoor units are connected, the total connection capacity of the outdoor-air

processing units (FXMQ-MF) must not exceed 30% of the capacity index of the outdoor units. And the connection ratio must not exceed 100%. *3.Itispermittedtouseamaximumconnectionratioof130%insomecircumstances–pleasecontactyourlocalDaikinrepresentativeforfurther

details.*4. For indoor units used for cooling only (do not connect to Branch Selector unit when using for heat recovery), total capacity index must be 70% or

less than the capacity index of the outdoor units.

Indoor unit fan tap settingIndoor units fan speed limitation related to connection capacity and outdoor air temperature for energy saving.Default value = 0

Value Indoor unit fan tap setting0 Fan speed is limited to L tap when indoor units capacity ≥ 130%.1 In heating mode, fan speed is limited to L tap when indoor units capacity ≥ 130%.2 Fan speed follows the setting of remote controllers (not limited by indoor units connection capacity).

3FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow85.1°F(29.5°C)andindoorairtemperatureisinconditionA(*).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover90.5°F(32.5°C)orindoorairtemperature is in condition B (**).

4FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow74.3°F(23.5°C)andindoorairtemperatureisinconditionA(*).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover79.7°F(26.5°C)orindoorairtemperature is in condition B (**).

5FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow66.7°F(19.3°C)andindoorairtemperatureisinconditionA(*).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover72.1°F(22.3°C)orindoorairtemperature is in condition B (**).

6 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow85.1°F(29.5°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover90.5°F(32.5°C).

7 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow74.3°F(23.5°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover79.7°F(26.5°C).

8 FanspeedislimitedtoLtapwhenoutdoorairtemperaturegoesdowntobelow66.7°F(19.3°C).Itreturnstoremotecontrollersettingwhenoutdoorairtemperaturegoesuptoover72.1°F(22.3°C).

*IndoorconditionA:Temperaturedifference(indoorairtemperature-settemperature)ismorethan−2.7°F(−1.5°C)andlessthan5.4°F(3°C).**IndoorconditionB:Temperaturedifference(indoorairtemperature-settemperature)is−2.7°F(−1.5°C)orless,or5.4°F(3°C)ormore.

Page 20: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

18

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

8.2 Capacity Range of Connectable Indoor Units

Type Ton Capacity index Model name Total capacity index of connectable indoor units *1

Maximum number of connectable indoor units

Single outdoor units

6 72RELQ72TATJA RELQ72TAYDA RELQ72TAYCA

51 to 93 (144) 12

8 96RELQ96TATJA RELQ96TAYDA RELQ96TAYCA

68 to 124 (192) 16

10 120RELQ120TATJA RELQ120TAYDA RELQ120TAYCA

84 to 156 (240) 20

Double outdoor units

12 144RELQ144TATJA RELQ144TAYDA RELQ144TAYCA

101 to 187 (230) 25

16 192RELQ192TATJA RELQ192TAYDA RELQ192TAYCA

135 to 249 (307) 33

20 240RELQ240TATJA RELQ240TAYDA RELQ240TAYCA

168 to 312 (384) 41

Note:*1. Values inside brackets are based on connection of indoor units rated at maximum capacity, 200% for single outdoor units, 160% for double

outdoor units, and 130% for triple outdoor units.

Page 21: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

19

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

8.3 Limitation of Capacity Index for Heat Recovery8.3.1 Single Branch Selector Unit

Model BSQ36TVJ BSQ60TVJ BSQ96TVJMaximum number of connectable indoor units 4 8 8Total capacity index of connectable indoor units unit ≤ 36 36 < unit ≤ 60 60 < unit ≤ 96

8.3.2 Multi Branch Selector UnitFlex series

Model BSF4Q54TVJ BSF6Q54TVJ BSF8Q54TVJMaximum number of connectable indoor units per branch 5 5 5

Number of branches 4 6 8Maximum capacity index of connectable indoor units per branch (H1) 54 or less 54 or less 54 or less

Series configuration

Maximum capacity index of connectable indoor units per branch selector unit

144 or less 162 or less 162 or less

Maximum capacity index of total connectable indoor units under branch selector units connected in series (H2)

230 or less 230 or less 230 or less

Parallel configuration

Maximum capacity index of connectable indoor units 144 or less 216 or less 290 or less

Standard series

Model BS4Q54TVJ BS6Q54TVJ BS8Q54TVJ BS10Q54TVJ BS12Q54TVJMaximum number of connectable indoor units per branch 5 5 5 5 5

Number of branches 4 6 8 10 12Maximum capacity index of connectable indoor units 144 or less 216 or less 290 or less 290 or less 290 or less

Maximum capacity index of connectable indoor units per branch (H1) 54 or less 54 or less 54 or less 54 or less 54 or less

Note:H1. When the total capacity index of indoor units to be connected downstream is larger than 54 (Max. 96), use a joint kit (KHRP26A250T, optional

parts) to join two branches downstream from the Branch Selector unit.H2. The total number of ports of Branch Selector units connected in series must be no more than 12 ports.

The total number of indoor units connected to Branch Selector units in series must be no more than 30 units. Thistotalincludestheports/indoorunitsofthefirstBranchSelectorintheseries.

High and low pressure gas pipingSuction gas pipingLiquid piping

Indoor unit(Heating)

Indoor unit(Cooling)

Indoor unit (Cooling only)

Heat recovery operation!

For indoor units used for cooling only (do not connect to Branch Selector unit when using for Heat recovery), total capacity index must be 50% or less than the capacity index of the outdoor units.

Branch Selector unit

Branch Selector unit

Heat recovery

Outdoor unit

Page 22: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

20

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

9. Specifications9.1 RELQ-TATJA

Outdoor Unit Model No. RELQ72TATJA RELQ96TATJA RELQ120TATJAPower supply 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz

H1 Cooling capacity

Nominal Btu/h (kW)

72,000 (21.1) 96,000 (28.1) 120,000 (35.2)Rated 69,000 (20.2) 92,000 (27.0) 114,000 (33.4)

H2 Heating capacity

Nominal Btu/h (kW)

81,000 (23.7) 108,000 (31.7) 135,000 (39.6)Rated 77,000 (22.6) 103,000 (30.2) 129,000 (37.8)

Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16(1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16(1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16(1,694 × 1,242 × 767)

Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil

Compressor

Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × number of units kW 3.9 × 1 5.0 × 1 6.6 × 1

Starting method Soft Start Soft Start Soft Start

Fan

Type Propeller Fan Propeller Fan Propeller FanMotor output kW 0.8 × 2 0.8 × 2 0.8 × 2

Airflowrate cfm(m³/min) 7,283 (206) 7,989 (226) 8,806 (249)

Drive Direct Drive Direct Drive Direct Drive

Connecting pipes

Liquid pipe in. (mm)

f3/8 (9.5) C1220T(Brazing Connection)

f3/8 (9.5) C1220T (Brazing connection)

f1/2 (12.7) C1220T (Brazing Connection)

Suction gas pipe in. (mm)

f3/4 (19.1) C1220T(Brazing Connection)

f7/8 (22.2) C1220T (Brazing connection)

f1-1/8 (28.6) C1220T(Brazing Connection)

High / Low pressure gas pipe

in. (mm)

f5/8 (15.9) C1220T(Brazing Connection)

f3/4 (19.1) C1220T (Brazing connection)

f3/4 (19.1) C1220T (Brazing Connection)

Weight lbs (kg) 727 (330) 793 (360) 793 (360)Sound pressure level (Reference data) dB (A) 60 (65 H3) 61 (67 H3) 63.5 (67 H3)

Sound power level (Reference data) dB 79 80.5 84.5

Safety devices

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 9.4-100 8.6-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve

Standard accessoriesInstallation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Note:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

C: 4D109459A, C: 4D109460B, C: 4D109461A

Page 23: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

21

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Outdoor unit model No. RELQ144TATJA RELQ192TATJA RELQ240TATJA

Unit combination RELQ72TATJARELQ72TATJA

RELQ96TATJARELQ96TATJA

RELQ120TATJARELQ120TATJA

Power supply 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz 3 phase, 208/230 V, 60 Hz

H1 Cooling capacity

Nominal Btu/h (kW)

144,000 (42.2) 192,000 (56.3) 240,000 (70.3)Rated 138,000 (40.4) 184,000 (53.9) 228,000 (66.8)

H2 Heating capacity

Nominal Btu/h (kW)

162,000 (47.5) 216,000 (63.3) 270,000 (79.1)Rated 154,000 (45.1) 206,000 (60.4) 256,000 (75.0)

Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil

Compressor

Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.9 + 12.9 17.5 + 17.5 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,294 + 3,294 4,230 + 4,230Motor output × number of units kW 4.0 × 1 + 4.0 × 1 5.0 × 1 + 5.0 × 1 6.5 × 1 + 6.5 × 1

Starting method Soft Start Soft Start Soft Start

Fan

Type Propeller Fan Propeller Fan Propeller FanMotor output kW (0.8 × 2) × 2 (0.8 × 2) × 2 (0.8 × 2) × 2

Airflowrate cfm(m³/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)

Drive Direct Drive Direct Drive Direct Drive

Connecting pipes

Liquid pipe in. (mm)

f1/2 (12.7) C1220T (Brazing Connection)

f5/8 (15.9) C1220T (Brazing Connection)

f5/8 (15.9) C1220T (Brazing Connection)

Suction gas pipe in. (mm)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-3/8 (34.9) C1220T (Brazing Connection)

High / Low pressure gas pipe

in. (mm)

f7/8 (22.2) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360)Sound pressure level (Reference data) dB (A) 63 (68 H3) 64 (70 H3) 67 (70 H3)

Sound power level (Reference data) dB 82 83.5 87.5

Safety devices

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 4.7-100 4.3-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve

Standard accessoriesInstallation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Note:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

C: 4D109462B, C: 4D109463A, C: 4D109464A

Page 24: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

22

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

9.2 RELQ-TAYDA

Outdoor unit model No. RELQ72TAYDA RELQ96TAYDA RELQ120TAYDAPower supply 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz

H1 Cooling capacity

Nominal Btu/h (kW)

72,000 (21.1) 96,000 (28.1) 120,000 (35.2)Rated 69,000 (20.2) 92,000 (27.0) 114,000 (33.4)

H2 Heating capacity

Nominal Btu/h (kW)

81,000 (23.7) 108,000 (31.7) 135,000 (39.6)Rated 77,000 (22.6) 103,000 (30.2) 129,000 (37.8)

Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil

Compressor

Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × number of units kW 3.9 × 1 5.0 × 1 6.6 × 1

Starting method Soft Start Soft Start Soft Start

Fan

Type Propeller Fan Propeller Fan Propeller FanMotor output kW 0.6 × 2 0.6 × 2 0.6 × 2

Airflowrate cfm(m³/min) 7,283 (206) 7,989 (226) 8,806 (249)

Drive Direct Drive Direct Drive Direct Drive

Connecting pipes

Liquid pipe in. (mm)

f3/8 (9.5) C1220T (Brazing Connection)

f3/8 (9.5) C1220T (Brazing Connection)

f1/2 (12.7) C1220T (Brazing Connection)

Suction gas pipe in. (mm)

f3/4 (19.1) C1220T (Brazing Connection)

f7/8 (22.2) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

High / Low pressure gas pipe

in. (mm)

f5/8 (15.9) C1220T (Brazing Connection)

f3/4 (19.1) C1220T (Brazing Connection)

f3/4 (19.1) C1220T (Brazing Connection)

Weight lbs (kg) 727 (330) 793 (360) 793 (360)Sound pressure level (Reference data) dB (A) 60 (65 H3) 61 (67 H3) 63.5 (67 H3)

Sound power level (Reference data) dB 79 80.5 84.5

Safety devices

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 9.4-100 8.6-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve

Standard accessoriesInstallation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Note:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

C: 4D109465A, C: 4D109466B, C: 4D109467A

Page 25: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

23

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Outdoor unit model No. RELQ144TAYDA RELQ192TAYDA RELQ240TAYDA

Unit combination RELQ72TAYDARELQ72TAYDA

RELQ96TAYDARELQ96TAYDA

RELQ120TAYDARELQ120TAYDA

Power supply 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz 3 phase, 460 V, 60 Hz

H1 Cooling capacity

Nominal Btu/h (kW)

144,000 (42.2) 192,000 (56.3) 240,000 (70.3)Rated 138,000 (40.4) 184,000 (53.9) 228,000 (66.8)

H2 Heating capacity

Nominal Btu/h (kW)

162,000 (47.5) 216,000 (63.3) 270,000 (79.1)Rated 154,000 (45.1) 206,000 (60.4) 256,000 (75.0)

Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil

Compressor

Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.9 + 12.9 17.5 + 17.5 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,294 + 3,294 4,230 + 4,230Motor output × number of units kW 4.0 × 1 + 4.0 × 1 5.0 × 1 + 5.0 × 1 6.5 × 1 + 6.5 × 1

Starting method Soft Start Soft Start Soft Start

Fan

Type Propeller Fan Propeller Fan Propeller FanMotor output kW (0.6 × 2) × 2 (0.6 × 2) × 2 (0.6 × 2) × 2

Airflowrate cfm(m³/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)

Drive Direct Drive Direct Drive Direct Drive

Connecting pipes

Liquid pipe in. (mm)

f1/2 (12.7) C1220T (Brazing Connection)

f5/8 (15.9) C1220T (Brazing Connection)

f5/8 (15.9) C1220T (Brazing Connection)

Suction gas pipe in. (mm)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-3/8 (34.9) C1220T (Brazing Connection)

High / Low pressure gas pipe

in. (mm)

f7/8 (22.2) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360)Sound pressure level (Reference data) dB (A) 63 (68 H3) 64 (70 H3) 67 (70 H3)

Sound power level (Reference data) dB 82 83.5 87.5

Safety devices

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 4.7-100 4.3-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve

Standard accessoriesInstallation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Note:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

C: 4D109468B, C: 4D109469A, C: 4D109470A

Page 26: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

24

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

9.3 RELQ-TAYCA

Outdoor unit model No. RELQ72TAYCA RELQ96TAYCA RELQ120TAYCAPower supply 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz

H1 Cooling capacity

Nominal Btu/h (kW)

72,000 (21.1) 96,000 (28.1) 120,000 (35.2)Rated 69,000 (20.2) 92,000 (27.0) 114,000 (33.4)

H2 Heating capacity

Nominal Btu/h (kW)

81,000 (23.7) 108,000 (31.7) 135,000 (39.6)Rated 77,000 (22.6) 103,000 (30.2) 129,000 (37.8)

Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 (1,694 × 1,242 × 767)

Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil

Compressor

Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.7 17.5 23.1Number of revolutions r/min 3,738 3,294 4,350Motor output × number of units kW 3.9 × 1 5.0 × 1 6.6 × 1

Starting method Soft Start Soft Start Soft Start

Fan

Type Propeller Fan Propeller Fan Propeller FanMotor output kW 0.7 × 2 0.7 × 2 0.7 × 2

Airflowrate cfm(m³/min) 7,283 (206) 7,989 (226) 8,806 (249)

Drive Direct Drive Direct Drive Direct Drive

Connecting pipes

Liquid pipe in. (mm)

f3/8 (9.5) C1220T (Brazing Connection)

f3/8 (9.5) C1220T (Brazing Connection)

f1/2 (12.7) C1220T (Brazing Connection)

Suction gas pipe in. (mm)

f3/4 (19.1) C1220T (Brazing Connection)

f7/8 (22.2) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

High / Low pressure gas pipe

in. (mm)

f5/8 (15.9) C1220T (Brazing Connection)

f3/4 (19.1) C1220T (Brazing Connection)

f3/4 (19.1) C1220T (Brazing Connection)

Weight lbs (kg) 727 (330) 793 (360) 793 (360)Sound pressure level (Reference data) dB (A) 60 (65 H3) 61 (67 H3) 63.5 (67 H3)

Sound power level (Reference data) dB 79 80.5 84.5

Safety devices

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 10.7-100 9.4-100 8.6-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 (11.7) 25.8 (11.7) 25.8 (11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve

Standard accessoriesInstallation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Note:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

C: 4D107389C, C: 4D107390D, C: 4D107391C

Page 27: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

25

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Outdoor unit model No. RELQ144TAYCA RELQ192TAYCA RELQ240TAYCA

Unit combination RELQ72TAYCARELQ72TAYCA

RELQ96TAYCARELQ96TAYCA

RELQ120TAYCARELQ120TAYCA

Power supply 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz 3 phase, 575 V, 60 Hz

H1 Cooling capacity

Nominal Btu/h (kW)

144,000 (42.2) 192,000 (56.3) 240,000 (70.3)Rated 138,000 (40.4) 184,000 (53.9) 228,000 (66.8)

H2 Heating capacity

Nominal Btu/h (kW)

162,000 (47.5) 216,000 (63.3) 270,000 (79.1)Rated 154,000 (45.1) 206,000 (60.4) 256,000 (75.0)

Casing color Ivory White (5Y7.5/1) Ivory White (5Y7.5/1) Ivory White (5Y7.5/1)

Dimensions: (H × W × D) in. (mm)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

66-11/16 × 48-7/8 × 30-3/16 + 66-11/16 × 48-7/8 × 30-3/16

(1,694 × 1,242 × 767 + 1,694 × 1,242 × 767)

Heat exchanger Cross Fin Coil Cross Fin Coil Cross Fin Coil

Compressor

Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll Type Hermetically Sealed Scroll TypeVolume m³/h 12.9 + 12.9 17.5 + 17.5 22.4 + 22.4Number of revolutions r/min 3,804 + 3,804 3,294 + 3,294 4,230 + 4,230Motor output × number of units kW 4.0 × 1 + 4.0 × 1 5.0 × 1 + 5.0 × 1 6.5 × 1 + 6.5 × 1

Starting method Soft Start Soft Start Soft Start

Fan

Type Propeller Fan Propeller Fan Propeller FanMotor output kW (0.7 × 2) × 2 (0.7 × 2) × 2 (0.7 × 2) × 2

Airflowrate cfm(m³/min) 7,283 + 7,283 (206 + 206) 7,989 + 7,989 (226 + 226) 8,806 + 8,806 (249 + 249)

Drive Direct Drive Direct Drive Direct Drive

Connecting pipes

Liquid pipe in. (mm)

f1/2 (12.7) C1220T (Brazing Connection)

f5/8 (15.9) C1220T (Brazing Connection)

f5/8 (15.9) C1220T (Brazing Connection)

Suction gas pipe in. (mm)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-3/8 (34.9) C1220T (Brazing Connection)

High / Low pressure gas pipe

in. (mm)

f7/8 (22.2) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

f1-1/8 (28.6) C1220T (Brazing Connection)

Weight lbs (kg) 727 + 727 (330 + 330) 793 + 793 (360 + 360) 793 + 793 (360 + 360)Sound pressure level (Reference data) dB (A) 63 (68 H3) 64 (70 H3) 67 (70 H3)

Sound power level (Reference data) dB 82 83.5 87.5

Safety devices

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting Device

High Pressure Switch, Fan Driver Overload Protector,

Overcurrent Fuse, Inverter Overload Protector,

Leak Detecting DeviceDefrost method Deicer Deicer DeicerCapacity control % 5.4-100 4.7-100 4.3-100

RefrigerantRefrigerant name R410A R410A R410ACharge lbs (kg) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7) 25.8 + 25.8 (11.7 + 11.7)Control Electronic Expansion Valve Electronic Expansion Valve Electronic Expansion Valve

Standard accessoriesInstallation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Installation Manual,Operation Manual,

Connection Pipes, Clamps

Note:H1 Indoortemp.:80°FDB(26.7°CDB),67°FWB(19.4°CWB)/Outdoortemp.:95°FDB(35.0°CDB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H2 Indoortemp.:70°FDB(21.1°CDB)/Outdoortemp.:47°FDB(8.3°CDB),43°FWB(6.1°CWB)/Equivalentpipinglength:25ft.(7.6m),level

difference:0ft.(0m).H3 Soundpressurelevelmayincreaseduringheatingoperationatambienttempsbelow41°F(5°C)valueinparenthesisisthemaxsound

pressure at those conditions.

C: 4D107392D, C: 4D107393C, C: 4D107394D

Page 28: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

26

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

10. Dimensions

RELQ72-120TATJA / TAYDA / TAYCA

C: 3

D10

7340

A

A

AA

A

AA

A

AA

A

AA

Page 29: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

27

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ144-240TATJA / TAYDA / TAYCA

C: 3

D10

7341

C

Not

es :

1. H

eigh

ts o

f wal

ls o

f thi

s ex

ampl

e;Fr

ont :

59

in. (

1500

mm

)S

uctio

n si

de :

19-5

/8 in

. (50

0 m

m)

Sid

e : H

eigh

t unr

estri

cted

The

inst

alla

tion

spac

e sh

own

in th

is fi

gure

is b

ased

on

the

cond

ition

of c

oolin

g op

erat

ion

at th

e ou

tdoo

r air

tem

pera

ture

of 9

5°FD

B (3

5°C

DB

).Th

e in

stal

latio

n sp

ace

of s

uctio

n si

de s

how

n ab

ove

mus

t be

expa

nded

in th

e fo

llow

ing

case

.· D

esig

n ou

tdoo

r tem

pera

ture

bec

omes

ove

r 95°

FDB

(35°

CD

B).

· Ope

ratin

g ov

er m

ax. o

pera

ting

load

(In

case

of c

ausi

ng a

hea

vy h

eatin

g lo

ad a

t ind

oor u

nit s

ide)

2. If

the

abov

e w

all h

eigh

ts a

re e

xcee

ded

then

h2/

2 an

d h1

/2 s

houl

d be

add

ed to

the

front

and

suc

tion

side

ser

vice

spac

es re

spec

tivel

y as

sho

wn

in th

e fo

llow

ing

figur

e.3.

Whe

n in

stal

ling

the

units

the

mos

t app

ropr

iate

pat

tern

sho

uld

be s

elec

ted

from

“Ins

talla

tion

and

repa

ir sp

ace

draw

ing”

in o

rder

to o

btai

n th

e be

st fi

t in

the

spac

e av

aila

ble

alw

ays

bear

ing

in m

ind

the

need

to le

ave

enou

gh ro

omfo

r a p

erso

n to

pas

s be

twee

n un

its a

nd w

all a

nd fo

r the

air

to c

ircul

ate

freel

y.(If

mor

e un

its a

re to

be

inst

alle

d th

an a

re s

how

n in

“Ins

talla

tion

and

repa

ir sp

ace

draw

ing”

, you

r lay

out s

houl

d ta

keac

coun

t of t

he p

ossi

bilit

y of

sho

rt ci

rcui

ting.

)4.

The

uni

ts s

houl

d be

inst

alle

d to

leav

e su

ffici

ent s

pace

at t

he fr

ont f

or th

e on

site

refri

gera

nt p

ipin

g w

ork

to b

e ca

rrie

dou

t com

forta

bly.

AA A A A A A A A A

A A A A A A A A A

A A A A A A A A

Page 30: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

28

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

11. Service Space

RELQ72-240TATJA / TAYDA / TAYCA

C: 3

D08

5503

H

Uni

t : in

. (m

m)

Not

es:

1. H

eigh

ts o

f wal

ls in

cas

e of

Pat

tern

s 1

and

2;Fr

ont :

59

in. (

1500

mm

)Su

ctio

n si

de :

19-5

/8 in

. (50

0 m

m)

Side

: H

eigh

t unr

estri

cted

The

inst

alla

tion

spac

e sh

own

in th

is fi

gure

is b

ased

on

the

cond

ition

of c

oolin

g op

erat

ion

at th

e ou

tdoo

r air

tem

pera

ture

of 9

5 °FD

B (3

5°C

DB)

. Th

e in

stal

latio

n sp

ace

of s

uctio

n si

de s

how

n ab

ove

mus

t be

expa

nded

in th

e fo

llow

ing

case

.∙D

esig

n ou

tdoo

r tem

pera

ture

bec

omes

ove

r 95°

FDB

(35°

CD

B).

∙Ope

ratin

g ov

er m

ax. o

pera

ting

load

(In

case

of c

ausi

ng a

hea

vy h

eatin

g lo

ad a

t ind

oor u

nit s

ide)

2. If

the

abov

e w

all h

eigh

ts a

re e

xcee

ded

then

h2/

2 an

d h1

/2 s

houl

d be

add

ed to

the

front

and

suc

tion

side

ser

vice

spa

ces

resp

ectiv

ely

as s

how

n in

the

follo

win

g fig

ure.

3. W

hen

inst

allin

g th

e un

its th

e m

ost a

ppro

pria

te p

atte

rn s

houl

d be

sel

ecte

d fro

m "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g" in

ord

er to

obt

ain

the

best

fit i

n th

e sp

ace

avai

labl

e al

way

s be

arin

g in

min

d th

e ne

ed to

leav

e en

ough

room

for a

per

son

to p

ass

betw

een

units

and

wal

l and

for t

he a

ir to

circ

ulat

e fre

ely.

(If m

ore

units

are

to b

e in

stal

led

than

are

sho

wn

in "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g", y

our l

ayou

t sho

uld

take

acc

ount

of t

he p

ossi

bilit

y of

sho

rt ci

rcui

ting.

)4.

The

uni

ts s

houl

d be

inst

alle

d to

leav

e su

ffici

ent s

pace

at t

he fr

ont f

or th

e on

site

refri

gera

nt p

ipin

g w

ork

to b

e ca

rried

out

com

forta

bly.

Page 31: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

29

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ72-240TATJA / TAYDA / TAYCA

Not

es:

1. H

eigh

ts o

f wal

ls in

cas

e of

Pat

tern

s 1

and

2;Fr

ont :

59

in. (

1500

mm

)Su

ctio

n si

de :

19-5

/8 in

. (50

0 m

m)

Side

: H

eigh

t unr

estri

cted

The

inst

alla

tion

spac

e sh

own

in th

is fi

gure

is b

ased

on

the

cond

ition

of c

oolin

g op

erat

ion

at th

e ou

tdoo

r air

tem

pera

ture

of 9

5 °FD

B (3

5°C

DB)

. Th

e in

stal

latio

n sp

ace

of s

uctio

n si

de s

how

n ab

ove

mus

t be

expa

nded

in th

e fo

llow

ing

case

.∙D

esig

n ou

tdoo

r tem

pera

ture

bec

omes

ove

r 95°

FDB

(35°

CD

B).

∙Ope

ratin

g ov

er m

ax. o

pera

ting

load

(In

case

of c

ausi

ng a

hea

vy h

eatin

g lo

ad a

t ind

oor u

nit s

ide)

2. If

the

abov

e w

all h

eigh

ts a

re e

xcee

ded

then

h2/

2 an

d h1

/2 s

houl

d be

add

ed to

the

front

and

suc

tion

side

ser

vice

spa

ces

resp

ectiv

ely

as s

how

n in

the

follo

win

g fig

ure.

3. W

hen

inst

allin

g th

e un

its th

e m

ost a

ppro

pria

te p

atte

rn s

houl

d be

sel

ecte

d fro

m "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g" in

ord

er to

obt

ain

the

best

fit i

n th

e sp

ace

avai

labl

e al

way

s be

arin

g in

min

d th

e ne

ed to

leav

e en

ough

room

for a

per

son

to p

ass

betw

een

units

and

wal

l and

for t

he a

ir to

circ

ulat

e fre

ely.

(If m

ore

units

are

to b

e in

stal

led

than

are

sho

wn

in "I

nsta

llatio

n an

d re

pair

spac

e dr

awin

g", y

our l

ayou

t sho

uld

take

acc

ount

of t

he p

ossi

bilit

y of

sho

rt ci

rcui

ting.

)4.

The

uni

ts s

houl

d be

inst

alle

d to

leav

e su

ffici

ent s

pace

at t

he fr

ont f

or th

e on

site

refri

gera

nt p

ipin

g w

ork

to b

e ca

rried

out

com

forta

bly.

C: 3

D08

5503

H

Uni

t : in

. (m

m)

Page 32: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

30

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

12. Center of Gravity

RELQ72TATJA / TAYDA / TAYCA

4D107384

Page 33: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

31

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ96-120TATJA / TAYDA / TAYCA

4D107385

Page 34: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

32

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

13. Foundation Drawing

RELQ72-120TATJA / TAYDA / TAYCA

C: 3

D08

5480

F

A A A AA A

A A A

A A AA

AAA

A

A A

Page 35: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

33

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

14. Piping Diagrams

RELQ72TATJA / TAYDA / TAYCA

3D10

7166

Page 36: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

34

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ96-120TATJA / TAYDA / TAYCA

3D10

7167

Page 37: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

35

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

15. Wiring Diagrams

RELQ72TATJA

C: 2

D11

2580

C

1. T

HIS

WIR

ING

DIA

GR

AM

AP

PLI

ES

ON

LY T

O T

HE

OU

TDO

OR

UN

IT.

2.

: F

IELD

WIR

ING

,

: TE

RM

INA

L B

LOC

K,

: C

ON

NE

CTO

R,

: T

ER

MIN

AL,

: PR

OTE

CTI

VE

GR

OU

ND

(SC

RE

W),

:

NO

ISE

LES

S G

RO

UN

D.

3. W

HE

N U

SIN

G T

HE

OP

TIO

NA

L A

DA

PTE

R, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L O

F TH

E O

PTI

ON

AL

AD

AP

TER

.4.

FO

R C

ON

NE

CTI

ON

WIR

ING

TO

IND

OO

R-O

UTD

OO

R T

RA

NS

MIS

SIO

N F

1·F2

, OU

TDO

OR

-OU

TDO

OR

TR

AN

SM

ISS

ION

F1·

F2,

OU

TDO

OR

-MU

LTI T

RA

NS

MIS

SIO

N Q

1·Q

2, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L. 5

. HO

W T

O U

SE

BS

1~3

SW

ITC

H, R

EFE

R T

O “S

ER

VIC

E P

RE

CA

UTI

ON

S” L

AB

EL

ON

C

ON

TRO

L B

OX

CO

VE

R.

6. W

HE

N O

PE

RAT

ING

, DO

N'T

SH

OR

TCIR

CU

IT T

HE

PR

OTE

CTI

ON

DE

VIC

E (S

1PH

). 7

. CO

LOR

S B

LK :

BLA

CK

; R

ED

: R

ED

; B

LU :

BLU

E ;

WH

T : W

HIT

E ;

GR

N :

GR

EE

N ;

GR

Y : G

RAY

; Y

LW :

YE

LLO

W.

8. C

LAS

S 2

WIR

E

NO

TES

)

Page 38: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

36

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ72TATJA

A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMP. SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (L1R)C1 CAPACITOR (A3P) R72T THERMISTOR (L2R)DS1, DS2 DIP SWITCH (A1P) S1NPH PRESSURE SENSOR (HIGH)E1HC, E2HC CRANKCASE HEATER S1NPL PRESSURE SENSOR (LOW)F1U FUSE (A1P, A6P) S1PH PRESSURE SWITCH (HIGH)F2U FUSE (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F101U FUSE (A4P, A5P) SHT1 CURRENT SENSOR (A3P) F4U, F5U FUSE (A2P) T1A CURRENT SENSORHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V1D DIODE (A3P)K3R MAGNETIC RELAY (A3P) V1R POWER MODULE (A3P)K1M MAGNETIC CONTACTOR (A3P) V3R POWER MODULE (A4P, A5P)K3R MAGNETIC RELAY (Y1S) (A1P) X1A, X2A CONNECTOR (M1F)K4R MAGNETIC RELAY (Y2S) (A1P) X3A, X4A CONNECTOR (M2F)K6R MAGNETIC RELAY (OPTION) (A1P) X6A CONNECTOR (CHECK THE RESIDUAL CHARGE)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K9R MAGNETIC RELAY (Y4S) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K11R MAGNETIC RELAY (Y3S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K12R MAGNETIC RELAY (Y5S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K13R MAGNETIC RELAY (Y6S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K84R MAGNETIC RELAY (A3P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)L1R, L2R REACTOR Y4E ELECTRIC EXPANSION VALVE (INJECTION)M1C MOTOR (COMPRESSOR) Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)M1F, M2F MOTOR (FAN) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1RP REVERSE PHASE PROTECTOR CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R1 RESISTOR (CURRENT LIMITING) (A3P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y4S 4 WAY VALVE (HP/LP GAS)R1T THERMISTOR (AIR) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R3T THERMISTOR (RECEIVER INLET) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1C~Z6C NOISE FILTER (FERRITE CORE)R6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)

C: 2D112580C

Page 39: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

37

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ96-120TATJA

C: 2

D11

2581

C

1. T

HIS

WIR

ING

DIA

GR

AM

AP

PLI

ES

ON

LY T

O T

HE

OU

TDO

OR

UN

IT.

2.

: F

IELD

WIR

ING

,

: TE

RM

INA

L B

LOC

K,

: C

ON

NE

CTO

R,

: T

ER

MIN

AL,

: PR

OTE

CTI

VE

GR

OU

ND

(SC

RE

W),

:

NO

ISE

LES

S G

RO

UN

D.

3. W

HE

N U

SIN

G T

HE

OP

TIO

NA

L A

DA

PTE

R, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L O

F TH

E O

PTI

ON

AL

AD

AP

TER

.4.

FO

R C

ON

NE

CTI

ON

WIR

ING

TO

IND

OO

R-O

UTD

OO

R T

RA

NS

MIS

SIO

N F

1·F2

, OU

TDO

OR

-OU

TDO

OR

TR

AN

SM

ISS

ION

F1·

F2,

OU

TDO

OR

-MU

LTI T

RA

NS

MIS

SIO

N Q

1·Q

2, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L. 5

. HO

W T

O U

SE

BS

1~3

SW

ITC

H, R

EFE

R T

O “S

ER

VIC

E P

RE

CA

UTI

ON

S” L

AB

EL

ON

C

ON

TRO

L B

OX

CO

VE

R.

6. W

HE

N O

PE

RAT

ING

, DO

N'T

SH

OR

TCIR

CU

IT T

HE

PR

OTE

CTI

ON

DE

VIC

E (S

1PH

). 7

. CO

LOR

S B

LK :

BLA

CK

; R

ED

: R

ED

; B

LU :

BLU

E ;

WH

T : W

HIT

E ;

GR

N :

GR

EE

N ;

GR

Y : G

RAY

; Y

LW :

YE

LLO

W.

8. C

LAS

S 2

WIR

E

NO

TES

)

Page 40: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

38

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ96-120TATJA

A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMP. SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (POWER MODULE) (A3P) C1 CAPACITOR (A3P) R72T THERMISTOR (DIODE) (A3P) C2 CAPACITOR (A2P) S1NPH PRESSURE SENSOR (HIGH)DS1, DS2 DIP SWITCH (A1P) S1NPL PRESSURE SENSOR (LOW)E1HC, E2HC CRANKCASE HEATER S1PH PRESSURE SWITCH (HIGH)F1U FUSE (A1P, A2P, A6P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F2U FUSE (A1P, A2P) T1A CURRENT SENSORF3U FUSE (A2P) T2A, T3A CURRENT SENSOR (A3P) F4U, F5U FUSE (X2M) V1D DIODE (A3P)F101U FUSE (A4P, A5P) V1R DIODE BRIDGEHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V2R POWER MODULE (A3P)K1M MAGNETIC CONTACTOR (A4P) V3R POWER MODULE (A4P, A5P)K3R MAGNETIC RELAY (Y1S) (A1P) X1A, X2A CONNECTOR (M1F)K4R MAGNETIC RELAY (Y2S) (A1P) X3A, X4A CONNECTOR (M2F)K5R MAGNETIC RELAY (A3P) X13A, X14A CONNECTOR (E1HC, E2HC)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K9R MAGNETIC RELAY (Y4S) (A1P) X2M TERMINAL BLOCK (FUSE)K11R MAGNETIC RELAY (Y3S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K12R MAGNETIC RELAY (Y5S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K13R MAGNETIC RELAY (Y6S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K84R MAGNETIC RELAY (A3P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)L1R REACTOR Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)M1C MOTOR (COMPRESSOR) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1F, M2F MOTOR (FAN) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)Q1RP REVERSE PHASE PROTECTOR CIRCUIT (A1P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R1 RESISTOR (CURRENT LIMITING) (A3P) Y4S 4 WAY VALVE (HP/LP GAS)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R1T THERMISTOR (AIR) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R3T THERMISTOR (RECEIVER INLET) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Z1C~Z8C NOISE FILTER (FERRITE CORE)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1F NOISE FILTERR6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)

C: 2D112581C

Page 41: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

39

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ72TAYDA

C: 2

D11

2582

D

1. T

HIS

WIR

ING

DIA

GR

AM

AP

PLI

ES

ON

LY T

O T

HE

OU

TDO

OR

UN

IT.

2.

: F

IELD

WIR

ING

,

: TE

RM

INA

L B

LOC

K,

: C

ON

NE

CTO

R,

: T

ER

MIN

AL,

: PR

OTE

CTI

VE

GR

OU

ND

(SC

RE

W),

:

NO

ISE

LES

S G

RO

UN

D.

3. W

HE

N U

SIN

G T

HE

OP

TIO

NA

L A

DA

PTE

R, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L O

F TH

E O

PTI

ON

AL

AD

AP

TER

.4.

FO

R C

ON

NE

CTI

ON

WIR

ING

TO

IND

OO

R-O

UTD

OO

R T

RA

NS

MIS

SIO

N F

1·F2

, OU

TDO

OR

-OU

TDO

OR

TR

AN

SM

ISS

ION

F1·

F2,

OU

TDO

OR

-MU

LTI T

RA

NS

MIS

SIO

N Q

1·Q

2, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L. 5

. HO

W T

O U

SE

BS

1~3

SW

ITC

H, R

EFE

R T

O “S

ER

VIC

E P

RE

CA

UTI

ON

S” L

AB

EL

ON

C

ON

TRO

L B

OX

CO

VE

R.

6. W

HE

N O

PE

RAT

ING

, DO

N'T

SH

OR

TCIR

CU

IT T

HE

PR

OTE

CTI

ON

DE

VIC

E (S

1PH

). 7

. CO

LOR

S B

LK :

BLA

CK

; R

ED

: R

ED

; B

LU :

BLU

E ;

WH

T : W

HIT

E ;

GR

N :

GR

EE

N ;

GR

Y : G

RAY

; Y

LW :

YE

LLO

W.

8. C

LAS

S 2

WIR

E

NO

TES

)

Page 42: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

40

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ72TAYDA

A1P PRINTED CIRCUIT BOARD (MAIN) R10T THERMISTOR (SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R11T THERMISTOR (DEICER)A3P PRINTED CIRCUIT BOARD (INV) R12T THERMISTOR (COMP. SUCTION)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R13T THERMISTOR (RECEIVER GAS PURGE)A6P PRINTED CIRCUIT BOARD (SUB) R14T THERMISTOR (M1C BODY)A7P PRINTED CIRCUIT BOARD (ABC I/P) R15T THERMISTOR (LEAK DETECTION)A8P PRINTED CIRCUIT BOARD (CURRENT LIMITING) R16T THERMISTOR (EVT)A9P PRINTED CIRCUIT BOARD (NOISE FILTER) R21T THERMISTOR (M1C DISCHARGE)A10P PRINTED CIRCUIT BOARD (OPEN PHASE PROTECTION) S1NPH PRESSURE SENSOR (HIGH)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) S1NPL PRESSURE SENSOR (LOW)C47, C48 CAPACITOR (A3P) S1PH PRESSURE SWITCH (HIGH)DS1, DS2 DIP SWITCH (A1P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)E1HC, E2HC CRANKCASE HEATER T1A CURRENT SENSORF1U FUSE (A1P, A6P) T1R TRANSFORMER (460 V / 230 V)F2U FUSE (A1P) V1R DIODE BRIDGE (A3P)F101U FUSE (A4P, A5P) V1R POWER MODULE (A4P, A5P)F401U, F403U FUSE (A2P) V2R POWER MODULE (A3P)F601U FUSE (A3P) X1A, X2A CONNECTOR (M1F)HAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) X3A, X4A CONNECTOR (M2F)K1M MAGNETIC CONTACTOR (A3P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K1M MAGNETIC CONTACTOR (A8P) X7A, X8A CONNECTOR (T1R)K3R MAGNETIC RELAY (A3P) X9A, X11A CONNECTOR K3R MAGNETIC RELAY (Y1S) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K4R MAGNETIC RELAY (Y2S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K8R MAGNETIC RELAY (Y7S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K9R MAGNETIC RELAY (Y4S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K11R MAGNETIC RELAY (Y3S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K12R MAGNETIC RELAY (Y5S) (A1P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)K13R MAGNETIC RELAY (Y6S) (A1P) Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)L1R REACTOR Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1C MOTOR (COMPRESSOR) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)M1F, M2F MOTOR (FAN) Y1S SOLENOID VALVE (OS OIL RETURN 1)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y2S SOLENOID VALVE (HOT GAS BYPASS)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R1 RESISTOR (CURRENT LIMITING) (A8P) Y4S 4 WAY VALVE (HP/LP GAS)R24 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R313 RESISTOR (CURRENT SENSOR) (A3P) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R865, R867 RESISTOR (A3P) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R1T THERMISTOR (AIR) Z1C, Z2C NOISE FILTER (FERRITE CORE)R3T THERMISTOR (RECEIVER INLET) ZF NOISE FILTER (A2P, A9P) (WITH SURGE ABSORBER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) CONNECTOR FOR OPTIONAL ACCESSORIESR5T THERMISTOR (HEAT EXC. LIQUID LOWER) X37A CONNECTOR (POWER ADAPTER) (A1P)R6T THERMISTOR (SUBCOOL GAS) COOL/HEAT SELECTORR7T THERMISTOR (SUBCOOL LIQUID) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R8T THERMISTOR (HEAT EXC. GAS UPPER) S2S SELECTOR SWITCH (COOL/HEAT)R9T THERMISTOR (HEAT EXC. GAS LOWER)

C: 2D112582D

Page 43: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

41

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ96-120TAYDA

C: 2

D11

2583

D

1. T

HIS

WIR

ING

DIA

GR

AM

AP

PLI

ES

ON

LY T

O T

HE

OU

TDO

OR

UN

IT.

2.

: F

IELD

WIR

ING

,

: TE

RM

INA

L B

LOC

K,

: C

ON

NE

CTO

R,

: T

ER

MIN

AL,

: PR

OTE

CTI

VE

GR

OU

ND

(SC

RE

W),

:

NO

ISE

LES

S G

RO

UN

D.

3. W

HE

N U

SIN

G T

HE

OP

TIO

NA

L A

DA

PTE

R, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L O

F TH

E O

PTI

ON

AL

AD

AP

TER

.4.

FO

R C

ON

NE

CTI

ON

WIR

ING

TO

IND

OO

R-O

UTD

OO

R T

RA

NS

MIS

SIO

N F

1·F2

, OU

TDO

OR

-OU

TDO

OR

TR

AN

SM

ISS

ION

F1·

F2,

OU

TDO

OR

-MU

LTI T

RA

NS

MIS

SIO

N Q

1·Q

2, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L. 5

. HO

W T

O U

SE

BS

1~3

SW

ITC

H, R

EFE

R T

O “S

ER

VIC

E P

RE

CA

UTI

ON

S” L

AB

EL

ON

C

ON

TRO

L B

OX

CO

VE

R.

6. W

HE

N O

PE

RAT

ING

, DO

N'T

SH

OR

TCIR

CU

IT T

HE

PR

OTE

CTI

ON

DE

VIC

E (S

1PH

). 7

. CO

LOR

S B

LK :

BLA

CK

; R

ED

: R

ED

; B

LU :

BLU

E ;

WH

T : W

HIT

E ;

GR

N :

GR

EE

N ;

GR

Y : G

RAY

; Y

LW :

YE

LLO

W.

8. C

LAS

S 2

WIR

E

NO

TES

)

Page 44: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

42

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ96-120TAYDA

A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMP. SUCTION)A2P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A3P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A4P, A5P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A6P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A7P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) R71T THERMISTOR (POWER MODULE) (A3P) C48, C51 CAPACITOR (A3P) R72T THERMISTOR (DIODE) (A3P) C404 CAPACITOR (A2P) S1NPH PRESSURE SENSOR (HIGH)DS1, DS2 DIP SWITCH (A1P) S1NPL PRESSURE SENSOR (LOW)E1HC, E2HC CRANKCASE HEATER S1PH PRESSURE SWITCH (HIGH)F1U FUSE (A1P, A3P, A6P) SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F2U FUSE (A1P) T1A CURRENT SENSORF101U FUSE (A4P, A5P) T1R TRANSFORMER (460 V / 230 V)F404U FUSE (A2P) V1D DIODE (CURRENT LIMITING) (A3P)F410U, F412U FUSE (A2P) V1R DIODE BRIDGEHAP PILOTLAMP (A1P, A3P~A6P) (SERVICE MONITOR-GREEN) V1R POWER MODULE (A4P, A5P)K1M MAGNETIC CONTACTOR V2R POWER MODULE (A3P)K3R MAGNETIC RELAY (A3P) X1A, X2A CONNECTOR (M1F)K3R MAGNETIC RELAY (Y1S) (A1P) X3A, X4A CONNECTOR (M2F)K4R MAGNETIC RELAY (Y2S) (A1P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K6R MAGNETIC RELAY (OPTION) (A1P) X6A, X7A CONNECTOR (T1R)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K9R MAGNETIC RELAY (Y4S) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K11R MAGNETIC RELAY (Y3S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A7P)K12R MAGNETIC RELAY (Y5S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K13R MAGNETIC RELAY (Y6S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K84R MAGNETIC RELAY (A3P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)L1R REACTOR Y4E ELECTRIC EXPANSION VALVE (INJECTION)M1C MOTOR (COMPRESSOR) Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)M1F, M2F MOTOR (FAN) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)PS SWITCHING POWER SUPPLY (A1P, A3P, A6P) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y1S SOLENOID VALVE (OS OIL RETURN 1)R1 RESISTOR (CURRENT LIMITING) (A3P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R24 RESISTOR (CURRENT SENSOR) (A4P, A5P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R131, R133 RESISTOR (A3P) Y4S 4 WAY VALVE (HP/LP GAS)R401 RESISTOR (CURRENT SENSOR) (A3P) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R1T THERMISTOR (AIR) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R3T THERMISTOR (RECEIVER INLET) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Z1C~Z3C NOISE FILTER (FERRITE CORE)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) ZF NOISE FILTER (A2P) (WITH SURGE ABSORBER)R6T THERMISTOR (SUBCOOL GAS) CONNECTOR FOR OPTIONAL ACCESSORIESR7T THERMISTOR (SUBCOOL LIQUID) X37A CONNECTOR (POWER ADAPTER) (A1P)R8T THERMISTOR (HEAT EXC. GAS UPPER) COOL/HEAT SELECTORR9T THERMISTOR (HEAT EXC. GAS LOWER) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R10T THERMISTOR (SUCTION) S2S SELECTOR SWITCH (COOL/HEAT)R11T THERMISTOR (DEICER)

C: 2D112583D

Page 45: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

43

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ72-120TAYCA

C: 2

D11

2579

C

1. T

HIS

WIR

ING

DIA

GR

AM

AP

PLI

ES

ON

LY T

O T

HE

OU

TDO

OR

UN

IT.

2.

: F

IELD

WIR

ING

,

: TE

RM

INA

L B

LOC

K,

: C

ON

NE

CTO

R,

: T

ER

MIN

AL,

: PR

OTE

CTI

VE

GR

OU

ND

(SC

RE

W),

:

NO

ISE

LES

S G

RO

UN

D.

3. W

HE

N U

SIN

G T

HE

OP

TIO

NA

L A

DA

PTE

R, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L O

F TH

E O

PTI

ON

AL

AD

AP

TER

.4.

FO

R C

ON

NE

CTI

ON

WIR

ING

TO

IND

OO

R-O

UTD

OO

R T

RA

NS

MIS

SIO

N F

1·F2

, OU

TDO

OR

-OU

TDO

OR

TR

AN

SM

ISS

ION

F1·

F2,

OU

TDO

OR

-MU

LTI T

RA

NS

MIS

SIO

N Q

1·Q

2, R

EFE

R T

O T

HE

INS

TALL

ATIO

N M

AN

UA

L. 5

. HO

W T

O U

SE

BS

1~3

SW

ITC

H, R

EFE

R T

O “S

ER

VIC

E P

RE

CA

UTI

ON

S” L

AB

EL

ON

C

ON

TRO

L B

OX

CO

VE

R.

6. W

HE

N O

PE

RAT

ING

, DO

N'T

SH

OR

TCIR

CU

IT T

HE

PR

OTE

CTI

ON

DE

VIC

E (S

1PH

). 7

. CO

LOR

S B

LK :

BLA

CK

; R

ED

: R

ED

; B

LU :

BLU

E ;

WH

T : W

HIT

E ;

GR

N :

GR

EE

N ;

GR

Y : G

RAY

; Y

LW :

YE

LLO

W.

8. C

LAS

S 2

WIR

E

NO

TES

)

Page 46: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

44

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ72-120TAYCA

A1P PRINTED CIRCUIT BOARD (MAIN) R12T THERMISTOR (COMP. SUCTION)A2P, A3P PRINTED CIRCUIT BOARD (NOISE FILTER) R13T THERMISTOR (RECEIVER GAS PURGE)A4P PRINTED CIRCUIT BOARD (INV) R14T THERMISTOR (M1C BODY)A5P, A6P PRINTED CIRCUIT BOARD (FAN) R15T THERMISTOR (LEAK DETECTION)A7P PRINTED CIRCUIT BOARD (SUB) R16T THERMISTOR (EVT)A8P PRINTED CIRCUIT BOARD (ABC I/P) R21T THERMISTOR (M1C DISCHARGE)BS1~BS3 PUSH BUTTON SWITCH (A1P) (MODE, SET, RETURN) S1NPH PRESSURE SENSOR (HIGH)C1 CAPACITOR (A4P) S1NPL PRESSURE SENSOR (LOW)DS1, DS2 DIP SWITCH (A1P) S1PH PRESSURE SWITCH (HIGH)E1HC, E2HC CRANKCASE HEATER SEG1~SEG3 7-SEGMENT DISPLAY (A1P)F1U FUSE (A1P, A4P, A7P) T1A CURRENT SENSORF2U FUSE (A1P) T1R TRANSFORMER (575 V / 220 V)F101U FUSE (A2P, A5P, A6P) V1D DIODE (A4P)

F100U, F104U, F105U FUSE (A2P)

V1R POWER MODULE (A4P)V1R POWER MODULE (A5P, A6P)

F1UT THERMAL FUSE (A4P) V1T TRANSISTOR (A4P)HAP PILOTLAMP (A1P, A4P~A7P) (SERVICE MONITOR-GREEN) X1A, X2A CONNECTOR (M1F, M2F)K1M MAGNETIC CONTACTOR (A4P) X5A CONNECTOR (CHECK THE RESIDUAL CHARGE)K3R MAGNETIC RELAY (Y1S) (A1P) X3A, X4A CONNECTOR (T1R)K4R MAGNETIC RELAY (Y2S) (A1P) X13A, X14A CONNECTOR (E1HC, E2HC)K6R MAGNETIC RELAY (OPTION) (A1P) X1M TERMINAL BLOCK (POWER SUPPLY)K7R MAGNETIC RELAY (E1HC, E2HC) (A1P) X1M TERMINAL BLOCK (CONTROL) (A1P)K8R MAGNETIC RELAY (Y7S) (A1P) X1M TERMINAL BLOCK (ABC I/P) (A8P)K9R MAGNETIC RELAY (Y4S) (A1P) Y1E ELECTRIC EXPANSION VALVE (HEAT EXC. UPPER)K11R MAGNETIC RELAY (Y3S) (A1P) Y2E ELECTRIC EXPANSION VALVE (SUBCOOL HEAT EXC.)K12R MAGNETIC RELAY (Y5S) (A1P) Y3E ELECTRIC EXPANSION VALVE (HEAT EXC. LOWER)K13R MAGNETIC RELAY (Y6S) (A1P) Y4E ELECTRIC EXPANSION VALVE (INJECTION)L1R REACTOR Y5E ELECTRIC EXPANSION VALVE (REFRIGERANT COOLING)M1C MOTOR (COMPRESSOR) Y6E ELECTRIC EXPANSION VALVE (LEAK DETECTION)M1F, M2F MOTOR (FAN) Y7E ELECTRIC EXPANSION VALVE (RECEIVER GAS PURGE)PS SWITCHING POWER SUPPLY (A1P, A4P, A7P) Y1S SOLENOID VALVE (OS OIL RETURN 1)Q1LD LEAKAGE DETECTION CIRCUIT (A1P) Y2S SOLENOID VALVE (HOT GAS BYPASS)R1 RESISTOR (CURRENT LIMITING) (A4P) Y3S SOLENOID VALVE (LIQUID SHUT OFF)R2 RESISTOR (CURRENT SENSOR) (A4P, A5P, A6P) Y4S 4 WAY VALVE (HP/LP GAS)R1T THERMISTOR (AIR) Y5S 4 WAY VALVE (HEAT EXC. LOWER)R3T THERMISTOR (RECEIVER INLET) Y6S 4 WAY VALVE (HEAT EXC. UPPER)R4T THERMISTOR (HEAT EXC. LIQUID UPPER) Y7S SOLENOID VALVE (ACCUMU OIL RETURN)R5T THERMISTOR (HEAT EXC. LIQUID LOWER) Z1C~Z3C NOISE FILTER (FERRITE CORE)R6T THERMISTOR (SUBCOOL GAS) ZF NOISE FILTER (A2P, A3P) (WITH SURGE ABSORBER)R7T THERMISTOR (SUBCOOL LIQUID) CONNECTOR FOR OPTIONAL ACCESSORIESR8T THERMISTOR (HEAT EXC. GAS UPPER) X37A CONNECTOR (POWER ADAPTER) (A1P)R9T THERMISTOR (HEAT EXC. GAS LOWER) COOL/HEAT SELECTORR10T THERMISTOR (SUCTION) S1S SELECTOR SWITCH (FAN/COOL·HEAT)R11T THERMISTOR (DEICER) S2S SELECTOR SWITCH (COOL/HEAT)

C: 2D112579D

Page 47: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

45

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

16. Field Wiring

RELQ72-120TATJA / TAYDA / TAYCA

C: 3

D10

7344

A

Not

es 1

) All

wiri

ng, c

ompo

nent

s an

d m

ater

ials

to b

e pr

ocur

edon

the

site

mus

t com

ply

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.2)

Use

cop

per c

ondu

ctor

s on

ly.3)

As

for d

etai

ls, s

ee w

iring

dia

gram

.4)

Fie

ld w

iring

dia

gram

is to

be

used

as

a gu

idel

ine

only.

Wiri

ng s

houl

d co

mpl

y w

ith a

pplic

able

loca

l and

nat

iona

l cod

es.

5) U

nit s

hall

be g

roun

ded

in c

ompl

ianc

e w

ith th

e ap

plic

able

loca

l and

nat

iona

l cod

es.

6) W

iring

sho

wn

are

gene

ral p

oint

s-of

-con

nect

ion

guid

es o

nly

and

are

not i

nten

ded

for o

r to

incl

ude

all d

etai

ls fo

r a s

peci

fic in

stal

latio

n.7)

Be

sure

to in

stal

l the

sw

itch

and

the

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8) In

stal

l the

mai

n sw

itch

that

can

inte

rrup

t all

the

pow

er s

ourc

es in

an

inte

grat

ed

man

ner b

ecau

se th

is s

yste

m c

onsi

sts

of th

e eq

uipm

ent u

tiliz

ing

the

mul

tiple

po

wer

sou

rces

.9)

If th

ere

exis

ts th

e po

ssib

ility

of r

ever

sed

phas

e, lo

st p

hase

, mom

enta

ry b

lack

out

or th

e po

wer

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed

phas

e pr

otec

tion

circ

uit l

ocal

ly.R

unni

ng th

e pr

oduc

t in

reve

rsed

pha

se m

ay b

reak

the

com

pres

sor a

nd o

ther

pa

rts.

Page 48: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

46

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ144-240TATJA / TAYDA / TAYCA

C: 3

D10

7345

A

Not

es 1

) All

wiri

ng, c

ompo

nent

s an

d m

ater

ials

to b

e pr

ocur

edon

the

site

mus

t com

ply

with

the

appl

icab

le lo

cal a

nd n

atio

nal c

odes

.2)

Use

cop

per c

ondu

ctor

s on

ly.3)

As

for d

etai

ls, s

ee w

iring

dia

gram

.4)

Fie

ld w

iring

dia

gram

is to

be

used

as

a gu

idel

ine

only.

Wiri

ng s

houl

d co

mpl

y w

ith a

pplic

able

loca

l and

nat

iona

l cod

es.

5) U

nit s

hall

be g

roun

ded

in c

ompl

ianc

e w

ith th

e ap

plic

able

loca

l and

nat

iona

l cod

es.

6) W

iring

sho

wn

are

gene

ral p

oint

s-of

-con

nect

ion

guid

es o

nly

and

are

not i

nten

ded

for o

r to

incl

ude

all d

etai

ls fo

r a s

peci

fic in

stal

latio

n.7)

Be

sure

to in

stal

l the

sw

itch

and

the

fuse

/bre

aker

to th

e po

wer

line

of e

ach

piec

e of

equ

ipm

ent.

8) In

stal

l the

mai

n sw

itch

that

can

inte

rrup

t all

the

pow

er s

ourc

es in

an

inte

grat

ed

man

ner b

ecau

se th

is s

yste

m c

onsi

sts

of th

e eq

uipm

ent u

tiliz

ing

the

mul

tiple

po

wer

sou

rces

.9)

If th

ere

exis

ts th

e po

ssib

ility

of r

ever

sed

phas

e, lo

st p

hase

, mom

enta

ry b

lack

out

or th

e po

wer

goe

s on

and

off

whi

le th

e pr

oduc

t is

oper

atin

g, a

ttach

a re

vers

ed

phas

e pr

otec

tion

circ

uit l

ocal

ly.R

unni

ng th

e pr

oduc

t in

reve

rsed

pha

se m

ay b

reak

the

com

pres

sor a

nd o

ther

pa

rts.

Page 49: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

47

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

17. Electrical Characteristics17.1 RELQ72-240TATJA

Model nameUnits Power supply Comp. OFM

SCCRHz Volts Min. Max. MCA MOP RLA kW FLA

RELQ72TATJA 60 208/230 187 253 60.8 70 20.7 0.8 × 2 2.9 × 2

SCCR kA rms, Symmetrical

@600 V MAX: 5

RELQ96TATJA 60 208/230 187 253 76.5 80 36.8 0.8 × 2 2.9 × 2RELQ120TATJA 60 208/230 187 253 83.4 90 39.3 0.8 × 2 2.9 × 2

RELQ144TATJARELQ72TATJA

60 208/230 187 253 60.8 + 60.8 70 + 70 21.6 +

21.6 (0.8 × 2) × 2 (2.9 × 2) × 2RELQ72TATJA

RELQ192TATJARELQ96TATJA

60 208/230 187 253 76.5 + 76.5 80 + 80 38.1 +

38.1 (0.8 × 2) × 2 (2.9 × 2) × 2RELQ96TATJA

RELQ240TATJARELQ120TATJA

60 208/230 187 253 83.4 + 83.4 90 + 90 40.4 +

40.4 (0.8 × 2) × 2 (2.9 × 2) × 2RELQ120TATJA

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)SCCR: Short-Circuit Current Rating

Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

C: 4D109454CC: 4D109455B

Page 50: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

48

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

17.2 RELQ72-240TAYDA

Model nameUnits Power supply Comp. OFM

SCCRHz Volts Min. Max. MCA MOP RLA kW FLA

RELQ72TAYDA 60 460 416 508 28.1 35 9.4 0.6 × 2 1.0 × 2

SCCR kA rms, Symmetrical

@600 V MAX: 5

RELQ96TAYDA 60 460 416 508 39.8 45 16.6 0.6 × 2 1.0 × 2RELQ120TAYDA 60 460 416 508 43.4 50 17.8 0.6 × 2 1.0 × 2

RELQ144TAYDARELQ72TAYDA

60 460 416 508 28.1 + 28.1 35 + 35 9.8 +

9.8 (0.6 × 2) × 2 (1.0 × 2) × 2RELQ72TAYDA

RELQ192TAYDARELQ96TAYDA

60 460 416 508 39.8 + 39.8 45 + 45 17.3 +

17.3 (0.6 × 2) × 2 (1.0 × 2) × 2RELQ96TAYDA

RELQ240TAYDARELQ120TAYDA

60 460 416 508 43.4 + 43.4 50 + 50 18.3 +

18.3 (0.6 × 2) × 2 (1.0 × 2) × 2RELQ120TAYDA

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)SCCR: Short-Circuit Current Rating

Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

C: 4D109456AC: 4D109457A

Page 51: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

49

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

17.3 RELQ72-240TAYCA

Model nameUnits Power supply Comp. OFM

SCCRHz Volts Min. Max. MCA MOP RLA kW FLA

RELQ72TAYCA 60 575 518 632 21.6 25 7.5 0.7 × 2 1.0 × 2

SCCR kA rms, Symmetrical

@600 V MAX: 5

RELQ96TAYCA 60 575 518 632 28.5 35 13.3 0.7 × 2 1.0 × 2RELQ120TAYCA 60 575 518 632 31.2 40 14.2 0.7 × 2 1.0 × 2

RELQ144TAYCARELQ72TAYCA

60 575 518 632 21.6 + 21.6 25 + 25 7.8 +

7.8 (0.7 × 2) × 2 (1.0 × 2) × 2RELQ72TAYCA

RELQ192TAYCARELQ96TAYCA

60 575 518 632 28.5 + 28.5 35 + 35 13.8 +

13.8 (0.7 × 2) × 2 (1.0 × 2) × 2RELQ96TAYCA

RELQ240TAYCARELQ120TAYCA

60 575 518 632 31.2 + 31.2 40 + 40 14.6 +

14.6 (0.7 × 2) × 2 (1.0 × 2) × 2RELQ120TAYCA

Symbols:MCA: Min. Circuit Amps. (A)MOP: Max. Overcurrent Protector (A)RLA: Rated Load Amps. (A)OFM: Outdoor Fan MotorkW: Rated Motor Output (kW)FLA: Full Load Amps. (A)SCCR: Short-Circuit Current Rating

Notes:1. RLA is based on the following conditions. Indoortemp.80°FDB(26.7°CDB)/67°FWB(19.4°CWB) Outdoortemp.95°FDB(35.0°CDB)

2. Voltage range Units are designed to operate only at the rated voltage provided in the table above.

3. The maximum percent unbalance of phase voltage shall be 2%.4. Select wire size based on the value of MCA.5. MOP is used to select the circuit breaker.

C: 3D107367AC: 3D107368A

Page 52: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

50

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

18. Operation Limits

RELQ72-240TATJA / TAYDA / TAYCA

3D107374

Page 53: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

51

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

19. Low Ambient Cooling Enhancement

RELQ72-240TATJA / TAYDA / TAYCA

�� RELQ-T series include a feature for Low Ambient Cooling.�� The function enhances RELQ-T series as follows:

• Allowsoperationto−4°FDB(−20°CDB)ambienttemperatureincoolingmode.(Normallimitis23°FDB(−5°CDB).) • Operationbelow23°FDB(−5°CDB)requirestheadditionofwindcoversontotheoutdoorunit.*

Application Rules: • Totalconnectionindexofeachsystemislimitedto50-130%whenheightdifferenceis0-194ft.(0-50m),80-130%when194-

295 ft. (50-90 m).• All units on the system must be connected to a Branch Selector Box. Low Ambient Cooling is available on indoor units connected

to either single-port (BSQ_TVJ) or Flex Series (BSF_Q54TVJ) multi-port branch selector boxes *1. Both single port and multi port boxes can be used in the same system, however indoor units connected to Standard Series (BS_Q54TVJ) multi port branch selector boxes will operate as standard without Low Ambient Cooling functionality.

• FunctionisengagedbyafieldsettingontheoutdoorunittoenableLowambientcooling.*1AdipswitchsettingisnecessaryontheSingle Branch Selector Boxes BSQ-T series serving the indoor units NOT subject to Low Ambient Cooling requirements. For Flex series (BSF-Q54TVJ) Multi-port Branch Selector Boxes, all indoor units connected to each port are subject to Low Ambient Cooling modeifthefieldsettingontheoutdoorunitiseffective.

• Duringoperationbelow23°FDB(−5°CDB),theavailablecoolingcapacitydecreasesasfollows: 14°FDB(−10°CDB)-Reducesto80%ofnominal. 5°FDB(−15°CDB)-Reducesto65%ofnominal. −4°FDB(−20°CDB)-Reducesto60%ofnominal.*1

• While system is operating in low ambient cooling mode, Branch selector boxes supporting low ambient cooling could experience operation sound levels of up to 3 dB(A) higher than maximum. It is recommended to locate units away from zones sensitive to sound levels. *1

• Allowableheightdifferencebetweenoutdoorandindoorunits(whenoutdoorunitisbelow)islimitedto130ft.(40m).(Normallimitis 195 ft. (60 m).)

Note:*1. Not applicable for Standard Series multi-port Branch selector box. *2.ContactyourlocalDaikinrepresentativeforwindcoverspecificationrequirementsandpartnumbers.

Page 54: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

52

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

20. Sound Levels (Reference Data)

RELQ72TATJA / TAYDA / TAYCA

4D107376A

Page 55: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

53

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ96TATJA / TAYDA / TAYCA

4D107377A

Page 56: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

54

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

RELQ120TATJA / TAYDA / TAYCA

4D107378A

Page 57: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

55

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

21. Accessories21.1 Optional AccessoriesRELQ72-240TATJA / TAYDA / TAYCA

Optional accessories

RELQ72TATJARELQ96TATJARELQ72TAYDARELQ96TAYDARELQ72TAYCARELQ96TAYCA

RELQ120TATJARELQ120TAYDARELQ120TAYCA

RELQ144TATJARELQ192TATJARELQ240TATJARELQ144TAYDARELQ192TAYDARELQ240TAYDARELQ144TAYCARELQ192TAYCARELQ240TAYCA

Distributive piping

REFNET header

KHRP25M33H9, KHRP25M33HA (Max.8 branch)

KHRP25M33H9, KHRP25M33HA (Max.8 branch)

KHRP25M72H9, KHRP25M72HA (Max.8 branch)

KHRP25M33H9, KHRP25M33HA (Max.8 branch)

KHRP25M72H9, KHRP25M72HA (Max.8 branch)

KHRP25M73HU9, KHRP25M73HUA (Max.8 branch)

REFNET joint

KHRP25A22T9, KHRP25A22TA KHRP25A33T9, KHRP25A33TA

KHRP25A22T9, KHRP25A22TA KHRP25A33T9, KHRP25A33TA

KHRP25M72TU9, KHRP25M72TUA

KHRP25A22T9, KHRP25A22TA KHRP25A33T9, KHRP25A33TA

KHRP25M72TU9, KHRP25M72TUA KHRP25M73TU9, KHRP25M73TUA

Outdoor unit multi connection piping kit — — BHFP26P100U, BHFP26P100UA

C: 3D091328H

Page 58: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

56

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

22. Selection Procedure22.1 Selection Procedure22.1.1 Flowchart

Provisionally select outdoor unit type and size based on limitation of connection ratio

Correct for cooling & heating capacity of the outdoor unit by the following items

VRV system selection is complete.

Confirm that the number of indoor units connected to the outdoor unit is within limitation.

Corrected capacity of the outdoor unit ≥ Required total heat load to the outdoor unit

2) Use the system peak load1) Use the sum of the peak load of each room

Define required total heat load to outdoor unit

Indoor unit capacity corrected for indoor air temperature (WB) ≥ Required heat load × Safety factor for the indoor units

Yes

No

-Piping length, level difference-Piping heat loss-Safety factor for the outdoor unit-Defrost (only for heating capacity)

-Outdoor air temperature-Indoor air temperature-Connection ratio

Given conditions:· Design temperature and humidity (indoor & outdoor)· Required heat load of each room· System peak load (if necessary)· Piping length, level difference· Specifications of indoor units (type and number)

Define safety factor for the indoor units and outdoor unit

[1] Given conditions

[2] Selection of indoor units

[3] Selection of outdoor unit

Page 59: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

57

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

22.1.2 Selection Example

The following is a selection example based on total heat load for cooling.

Room ARoom H Room G

Room F

Room B Room ERoom C Room D

Floor plan

[1] Given conditions-Design conditionsIndoorairtemperature:67°FWB/80°FDB,Outdoorairtemperature:93°FDB

-Determine peak load of each room (and system peak load if necessary)

-Required heat load of each roomTime Room A Room B Room C Room D Room E Room F Room G Room H Total9:00 16.4 16.5 10.4 10.4 30.9 30.8 10.0 10.0 135.4

12:00 22.4 24.4 17.3 17.3 25.1 23.2 13.7 13.7 157.114:00 30.7 32.2 16.8 16.8 24.9 23.4 14.1 14.1 173.016:00 36.1 36.4 13.3 13.3 21.5 21.2 13.0 13.0 167.8

Total heat load (MBH)

From the above heat load calculation, the maximum heat load for the system (system peak load) is 173.0 MBH.

Level difference120 ft.

Select VRV indoor units FXMQ-PB series for each room.

Equivalent pipe length 200 ft.

-Safety factorIn this example, safety factor is not used. (i. e., safety factor = 1.0)

[2] Selection of indoor unitsCalculate total heat capacity of indoor units corrected for indoor air temperature.In case design temperature of the indoor air falls between temperatures listed in the table, calculate the capacity by interpolation.The corrected total heat capacity of indoor units shall satisfy the maximum heat load of each room.

Page 60: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

58

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Capacity table of indoor unitCooling Capacity

Model Capacity indication

Indoorairtemp.°FWB(Te:43°F(6°C))61 64 67 70 72 75

TC SHC TC SHC TC SHC TC SHC TC SHC TC SHCMBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH MBH

FXMQ07PBVJU 07 5.7 5.5 6.4 5.9 7.2 6.1 7.3 6.5 7.4 5.8 7.6 5.8 FXMQ09PBVJU 09 7.5 6.9 8.5 7.3 9.5 7.8 9.7 8.1 9.8 7.1 10.0 7.2FXMQ12PBVJU 12 9.5 8.5 10.7 9.1 12.0 9.7 12.2 10.0 12.4 9.2 12.6 9.2FXMQ15PBVJU 15 11.2 10.2 12.7 10.7 14.2 11.4 14.5 11.6 14.7 11.5 14.9 9.6 FXMQ18PBVJU 18 14.2 13.9 16.1 14.7 18.0 15.6 18.4 16.1 18.6 14.6 18.9 12.1FXMQ24PBVJU 24 19.0 16.5 21.5 17.7 24.0 18.8 24.5 19.2 24.8 17.9 25.3 20.1FXMQ30PBVJU 30 23.7 20.8 26.8 22.3 30.0 23.8 30.6 24.4 31.0 22.5 31.6 22.5FXMQ36PBVJU 36 28.4 25.0 32.2 26.9 36.0 28.8 36.7 30.0 37.2 27.7 37.9 27.7FXMQ48PBVJU 48 37.9 31.3 43.0 33.6 48.0 35.8 49.0 36.9 49.6 34.7 50.5 33.2FXMQ54PBVJU 54 42.6 35.2 48.3 37.8 54.0 40.3 55.1 41.5 55.8 39.0 56.8 37.4

TC: Total capacity: MBHSHC: Sensible heat capacity: MBH

Selection results of indoor units

Room A Room B Room C Room D Room E Room F Room G Room HMax. heat load (MBH) 36.1 36.4 17.3 17.3 30.9 30.8 14.1 14.1

Selected IDU FXMQ48PBVJU FXMQ48PBVJU FXMQ18PBVJU FXMQ18PBVJU FXMQ36PBVJU FXMQ36PBVJU FXMQ15PBVJU FXMQ15PBVJUCorrected TC (MBH) 48.0 48.0 18.0 18.0 36.0 36.0 14.2 14.2

* In case of selection based on Total Heat Load and Sensible Heat Load, select indoor units which satisfy not only the Total Heat Load but also the Sensible Heat Load of each room. The sensible heat capacity of indoor units is to be corrected for indoor air temperature. If the design temperature of indoor air falls between temperatures listed in table, calculate sensible heat capacity by using the bypass factor calculated by interpolation for each indoor air temperature.

[3] Selection of outdoor unit[3] –1 Define the required total heat load from the indoor units to the outdoor unitDefinetherequiredtotalheatload(A)basedon(1)thesumofthepeakloadofeachroomor(2)thesystempeakload.In this example, select an outdoor unit by (2).Therefore, (A) = 173.0 MBH

Page 61: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

59

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

[3] –2 Provisionally select outdoor unit(1) Calculate CI (Capacity Index) of the selected indoor units.

CI of VRV indoor units CI of FXMQ15PBVJU = 15 CI of FXMQ18PBVJU = 18 CI of FXMQ36PBVJU = 36 CI of FXMQ48PBVJU = 48

Capacity Range 0.5 ton 0.6 ton 0.8 ton 1 ton 1.25 ton 1.5 ton 2 ton 2.5 ton 3 ton 3.5 ton 4 ton 4.5 ton 5 ton 6 ton 8 ton Power Supply, StandardCapacity Index 5.8 7.5 9.5 12 15 18 20 24 30 36 42 48 54 60 72 96

Ceiling Mounted Duct Type (Middle and High Static Pressure)

FXMQ — 07PB 09PB 12PB 15PB 18PB — 24PB 30PB 36PB — 48PB 54PB — — — VJU

Calculate the total CI of the indoor units.Total CI = 15 × 2 + 18 × 2 + 36 × 2 + 48 × 2 = 234

(2) Provisionally select an outdoor unit based on the total CI of the indoor units

The connection ratio of RELQ-TA shall be between 70% and 130%.As the total CI of the indoor units is 234, outdoor units from 16 ton to 20 ton are connectable.Start from 16 ton which is the smallest outdoor unit.

(3) Confirm that the number of the connected indoor units is within the limitation.

The number of the connected indoor units = 8

The max. number of connectable indoor units of 16 ton outdoor unit = 33

Page 62: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

60

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

[3] –3 Calculate the corrected capacity of the outdoor unit.-Calculate the connection ratio of the system.Total CI = 234, CI of RELQ192TAYDA = 192Connection ratio = 234 / 192 = 122%

- Using the capacity table of the outdoor unit, calculate the capacity (B) corrected for outdoor air temperature, indoor air temperature, and connection ratio.

* In case the outdoor air temperature, the indoor air temperature, or the connection ratio falls between temperatures listed in the table, calculate the capacity by interpolation.

RELQ192TATJA / TAYDA / TAYCA Cooling Capacity for Standard Condition (Te: 43°F)

120% 122% 130%

201 (B) 205

Connection ratio

Cooling capacity

(B)=201+(205–201)×(122–120)/(130–120)=201.8

Page 63: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

61

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

-Confirmcapacitycorrectionfactorbypipinglengthandleveldifference(K1)

(K1) = 0.924

0.924

-Calculate capacity correction factor by piping heat loss (K2)(K2)=1+(heatlossfactorperfeetofpiping×(equivalentpipinglength–25ft.))/100

Incoolingmode,heatlossfactorperfeetat93°Fiscalculatedasbelow.(R) Heat loss factor per feet = 0.072*2 + (0.098*1–0.072*2) × (93*3–86*4) / (95*5–86*4) = 0.0922

Using “Equivalent piping length = 200 ft” and “Heat loss factor per feet = 0.0922”, (K2)=1+(0.0922×(200–25))/100=1.161

Cooling Ambient temperature

Heat loss factor per feet of piping (%)

Heating Ambient temperature

Heat loss factor per feet of piping (%)

5°F 14°F 23°F 32°F 41°F 50°F 59°F 68°F0.328 0.305 0.282 0.256 0.233 0.210 0.187 0.161

41°F

0.000

50°F

0.000

59°F

0.013

68°F

0.030

77°F

0.046

86°F*4

0.072*2

93°F*3

(R)

95°F*5

0.098*1

104°F

0.125

-Calculate the corrected capacity of RELQ192TAYCA (C) by using (K1) and (K2).Corrected capacity of RELQ192TAYCA (C) = (B) × (K1) / (K2) (add defrost correction factor for heating capacity)Therefore (C) = 201.8 × 0.924 / 1.161 = 160.6 MBH

If the corrected capacity (C) is the same or greater than the required total heat load (A), selection is complete.If(C)<(A),returntoProcedure[3]–2andprovisionallyselectalargeroutdoorunit.In this example, 160.6 MBH (C) < 173.0 MBH (A), so need to select a larger outdoor unit.

The capacity of RELQ240TAYCA at the same condition is 186.3 MBH, which is more than the heat load (A): 173.0 MBH.So the selection is complete.

Page 64: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

62

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

23. Caution Label23.1 RELQ72-240TATJA / TAYDA / TAYCA

3P558142-1B

Page 65: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

63

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1P385984-1A

Page 66: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

64

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1P385984-1A

Page 67: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

65

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1P385984-1A

Page 68: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

66

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1P385984-1A

Page 69: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

67

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1P385984-1A

Page 70: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

68

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1P385984-1A

Page 71: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

69

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

3P385987-1A

Page 72: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

70

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

3P385987-1A

Page 73: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

71

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

24. Caution for Refrigerant Leaks24.1 Introduction

The installer and system specialist shall secure safety against leakage according to local regulations or standards. The following standards may be applicable if local regulations are not available.

The VRV System, like other air conditioning systems, uses R410A as refrigerant. R410A itself is an entirely safe non-toxic, non-combustible refrigerant.Neverthelesscaremustbetakentoensurethatairconditioningfacilitiesareinstalledinaroomwhichissufficientlylarge.Thisassuresthat the maximum concentration level of refrigerant gas is not exceeded, in the unlikely event of major leak in the system and this in accordance to the local applicable regulations and standards.

Maximum concentration levelThe maximum charge of refrigerant and the calculation of the maximum concentration of refrigerant is directly related to the humanly occupied space in to which it could leak.The unit of measurement of the concentration is lbs./ft.³ (kg/m³) (the weight in Ibs. (kg) of the refrigerant gas in 1 ft.³ (1 m³) volume of the occupied space).Compliance to the local applicable regulations and standards for the maximum allowable concentration level is required.

Direction of therefrigerant flow

Room where refrigerant leak has occurred(outflow of all the refrigerant from the system)

Pay special attention to places, such as basements, etc. where refrigerant could stay, since refrigerant is heavier than air.

Page 74: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

72

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

24.2 Procedure for Checking Maximum Concentration

Check the maximum concentration level in accordance with steps 1 to 4 below and take whatever action is necessary to comply.Step1: Calculate the amount of refrigerant (lbs. (kg)) charged to each system separately.

Amount of refrigerant in a single unitsystem (amount of refrigerant withwhich the system is charged beforeleaving the factory)

+

Additional charging amount (amountof refrigerant added locally inaccordance with the length or diameterof the refrigerant piping)

= Total amount of refrigerant (lbs. (kg))in the system

Note:Where a single refrigerant facility is divided into 2 entirely independent refrigerant systems then use the amount of refrigerant with which each separate system is charged.

Step 2: Calculate the smallest room volume (ft.³(m³)) In case like the following, calculate the volume of (a), (b) as a single room or as the smallest room. (a) Where there are no smaller room divisions.

(b)Wherethereisaroomdivisionbutthereisanopeningbetweentheroomssufficientlylargetopermitafreeflowofairbackandforth.

Opening betweenrooms

Partition

(Where there is an opening without a door or where there are openings above and below the door which are each equivalent in size to 0.15%ormoreofthefloorarea.)

(c) Where there is a gas leak detection alarm device linked to a mechanical ventilator in the smallest room then the next smallest room will become the measurement target.

Page 75: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

73

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Step 3: Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above.

Total volume of refrigerant in therefrigerant system

≤ Maximum concentration level (lbs./ft.3(kg/m3))Size (ft.3(m3)) of the smallest room in whichthere is an indoor unit installed

If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result falls short of the maximum concentration.

Step 4: Dealing with the situations where the result exceeds the maximum concentration level. Where the installation of a facility results in a concentration in excess of the maximum concentration level then it will be necessary to

revise the system. Please consult your Daikin supplier.

Page 76: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

74

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

25. Safety Devices Setting25.1 FXFQ-T

Model FXFQ07TVJU FXFQ09TVJU FXFQ12TVJU FXFQ15TVJU FXFQ18TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – – –Fan motor thermal protector °F(°C) – – – – –Fan motor thermal fuse °F(°C) – – – – –

Model FXFQ24TVJU FXFQ30TVJU FXFQ36TVJU FXFQ48TVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – –Fan motor thermal protector °F(°C) – – – –Fan motor thermal fuse °F(°C) – – – –

C: 3D086932C

25.2 FXZQ-TA

Model FXZQ05TAVJU FXZQ07TAVJU FXZQ09TAVJU FXZQ12TAVJU FXZQ15TAVJU FXZQ18TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F(°C) – – – – – –Fan motor thermal protector °F(°C) – – – – – –Drain pump fuse °F(°C) – – – – – –

C: 4D110603

25.3 FXUQ-P

Model FXUQ18PVJU FXUQ24PVJU FXUQ30PVJU FXUQ36PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 ADrain pump thermal fuse °F(°C) – – – –Fan motor thermal protector °F(°C) – – – –Fan motor thermal fuse °F(°C) – – – –

C: 3D090213

25.4 FXEQ-P

Model FXEQ07PVJU FXEQ09PVJU FXEQ12PVJU FXEQ15PVJU FXEQ18PVJU FXEQ24PVJUPrinted circuit board fuse A1P 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A

Fan motor thermal protector °F(°C)OFF: 223±9

(106±5)ON: 205±27

(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

OFF: 223±9 (106±5)

ON: 205±27(96±15)

OFF: 223±9(106±5)

ON: 205±27(96±15)

C: 4D098709

Page 77: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

75

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

25.5 FXDQ-M

Model FXDQ07MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJUPrinted circuit board fuse A1P 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A

Fan motor thermal protector °F OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

OFF: 266±9ON: 181±27

C: 3D051758

25.6 FXSQ-TA

Model FXSQ05TAVJU FXSQ07TAVJU FXSQ09TAVJU FXSQ12TAVJU FXSQ15TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) — — — — —

Model FXSQ18TAVJU FXSQ24TAVJU FXSQ30TAVJU FXSQ36TAVJU FXSQ48TAVJU FXSQ54TAVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) — — — — — —

3D112398

25.7 FXMQ-PB

Model FXMQ07PBVJU FXMQ09PBVJU FXMQ12PBVJU FXMQ15PBVJU FXMQ18PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)

Model FXMQ24PBVJU FXMQ30PBVJU FXMQ36PBVJU FXMQ48PBVJU FXMQ54PBVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 APrinted circuit board fuse (Fan driver) 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 A 250 V, 6.3 ADrain pump thermal fuse °F(°C) 293 (145) 293 (145) 293 (145) 293 (145) 293 (145)

C: 3D086916B

25.8 FXMQ-M

Model FXMQ72MVJU FXMQ96MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – –

Fan motor thermal protector °F OFF: 275±14(ON: 189±27)

OFF: 275±14(ON: 189±27)

Page 78: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

76

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

25.9 FXHQ-M

Model FXHQ12MVJU FXHQ24MVJU FXHQ36MVJUPrinted circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 AFan motor thermal fuse °F – – –

Fan motor thermal protector °F OFF: 266±9ON: 176±36

OFF: 266±9ON: 176±36

OFF: 266±9ON: 176±36

C: 3D049334A

25.10 FXAQ-P

Model FXAQ07PVJU FXAQ09PVJU FXAQ12PVJU FXAQ18PVJU FXAQ24PVJUPrinted circuit board fuse 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AFan motor thermal fuse °F – – – – –Fan motor thermal protector °F – – – – –

C: 4D047085D

25.11 FXLQ-M, FXNQ-M

Model FXLQ07MVJUFXNQ07MVJU

FXLQ09MVJUFXNQ09MVJU

FXLQ12MVJUFXNQ12MVJU

FXLQ18MVJUFXNQ18MVJU

FXLQ24MVJUFXNQ24MVJU

Printed circuit board fuse 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A 250 V, 5 A

Fan motor thermal protector °F(°C)OFF: 275±18

(135±10)ON: 248 (120)

or less

OFF: 275±18(135±10)

ON: 248 (120)or less

OFF: 275±18(135±10)

ON: 248 (120)or less

OFF: 275±18(135±10)

ON: 248 (120)or less

OFF: 275±18(135±10)

ON: 248 (120)or less

C: 3D045646B

25.12 FXTQ-TA

Model FXTQ09TAVJUA FXTQ12TAVJUA FXTQ18TAVJUA FXTQ24TAVJUA FXTQ30TAVJUAModel (with factory disconnect) FXTQ09TAVJUD FXTQ12TAVJUD FXTQ18TAVJUD FXTQ24TAVJUD FXTQ30TAVJUDPrinted circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector

Model FXTQ36TAVJUA FXTQ42TAVJUA FXTQ48TAVJUA FXTQ54TAVJUA FXTQ60TAVJUAModel (with factory disconnect) FXTQ36TAVJUD FXTQ42TAVJUD FXTQ48TAVJUD FXTQ54TAVJUD FXTQ60TAVJUDPrinted circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 AOthers Blower motor, Fan driver overload protector

25.13 CXTQ-TA

Model CXTQ24TASBLU CXTQ36TASBLU CXTQ48TASBLU CXTQ60TASBLUPrinted circuit board fuse (F1U) 32 V, 3 A 32 V, 3 A 32 V, 3 A 32 V, 3 APrinted circuit board fuse (F2U) 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A 250 V, 3.15 A

Page 79: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

77

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Appendix

1. Introduction ...............................................................................................781.1 ED Book List ...................................................................................781.2 Publication List of Engineering Data for VRV Products ..................79

Page 80: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

78

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1. Introduction1.1 ED Book List

Design Manual ..................................................... RELQ-TA ......EDUS371705D-D (This booklet)

Capacity Table Book

Heat Recovery .................................................... RELQ-TA ..........EDUS371705C-C

Installation

Heat Pump, Heat Recovery .....................................................................EDUS371848-N

Indoor Units

Ceiling Mounted Cassette Type (Round Flow with Sensing) ....... FXFQ-T ..... EDUS391400A-F14

VISTA™ 2 × 2 Cassette Unit .................................. FXZQ-TA ........ EDUS391776A-F9

4-Way Blow Ceiling-Suspended Type ....................... FXUQ-P ........ EDUS391437-F15

One Way Blow Cassette Type ................................ FXEQ-P ........ EDUS391533-F16

Slim Ceiling Mounted Duct Type ............................. FXDQ-M ........... EDUS39-600-F2

MSP Concealed Duct Unit ..................................... FXSQ-TA ...... EDUS391777A-F17

Ceiling Mounted Duct Type .................................... FXMQ-PB ........ EDUS391503A-F4

Ceiling Mounted Duct Type .................................... FXMQ-M ....... EDUS39-900A-F11

Ceiling Suspended Type ........................................ FXHQ-M ........... EDUS39-600-F5

Wall Mounted Type ............................................... FXAQ-P .......... EDUS391100-F6

Floor Standing Type / Concealed Floor Standing Type ........ FXLQ-MFXNQ-M .......... EDUS391502-F7

Air Handling Unit .................................................. FXTQ-TA .... Engineering Data FXTQ-TA

Cased Coil Unit ................................................... CXTQ-TA .... Engineering Data CXTQ-TA

Branch Selector Unit ............................................. BSQ-TBSF-Q54TBS-Q54T

..........EDUS391434A-B

Air Treatment Equipment

Outdoor Air Processing Unit ................................... FXMQ-MF ....... EDUS39-900A-F10

Energy Recovery Ventilator .................................... VAM-G ............. EDUS711116A

Controls ............................................................................................ EDUS721909A-T

Remote Controller

Navigation Remote Controller ................................. BRC1E73 ............... EDUS721438

Page 81: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

79

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

1.2 Publication List of Engineering Data for VRV Products

Shaded sections indicate Engineering Data Book/s published for this series.Timing of publication is subject to change without notice.

Outdoor Unit

Refrigerant Category Product series Type Volts Model name Area Book category Book No. Published in

R410A

Air cooled

VRV IV-X

H/R208/230 V460 V575 V

REYQ-XATJA, XAYDA, XAYCA USA Canada

Design manual EDUS371848B-D Sep.2020

Capacity table EDUS371848A-C Jan.2020

H/P

208/230 V460 V RXYQ-XATJA, XAYDA USA

CanadaDesign manual EDUS341923A-D Oct.2020Capacity table EDUS341923-C Nov.2019

575 V RXYQ-XAYCA CanadaDesign manual EDUS341928A-D Oct.2020Capacity table EDUS341928-C Nov.2019

VRV IV

H/R

208/230 V460 V REYQ-TATJA, TAYDA USA

CanadaDesign manual EDUS371704C-D

Feb.2020Capacity table EDUS371704C-C

575 V REYQ-TAYCA CanadaDesign manual EDUS371706C-DCapacity table EDUS371706C-C

H/P

208/230 V 460 V RXYQ-TATJA, TAYDA USA

CanadaDesign manual EDUS341703B-D

Jan.2020Capacity table EDUS341703B-C

575 V RXYQ-TAYCA CanadaDesign manual EDUS341824A-DCapacity table EDUS341824A-C

VRV Aurora

H/R208/230 V460 V575 V

RELQ-TATJA, TAYDA, TAYCA USACanada

Design manual EDUS371705D-D Sep.2020

Capacity table EDUS371705C-C Feb.2020

H/P208/230 V460 V575 V

RXLQ-TATJA, TAYDA, TAYCA USACanada

Design manual EDUS341819A-DJan.2020

Capacity table EDUS341819A-C

VRV IV-S H/P 208/230 V RXTQ36TAVJ9ARXTQ48/60TAVJUA

USA Canada

Design manual EDUS331608C-DFeb.2020

Capacity table EDUS331608C-C

VRV LIFE H/P 208/230 V RXSQ-TAVJUA USA Canada

Design manual EDUS331721A-DFeb.2020

Capacity table EDUS331721A-CInstallation for all VRV air cooled type Installation EDUS371848-N Aug.2019

Water cooled

VRV-W H/P H/R

208/230 V460 V575 V

RWEQ-TATJU, TAYDU, TAYCU RWEQ-TATJA, TAYDA

USA Canada

Design manual EDUS301864B-D Sep.2020

Capacity table EDUS301864A-C Jan.2020

Installation for all VRV water cooled type Installation EDUS301864-N Aug.2019

Note:C/O: Cooling only, H/P: Heat pump, H/R: Heat recovery

Page 82: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

80

RELQ-TATJA / TAYDA / TAYCA EDUS371705D-D

Indoor Unit and Other Products

Refrigerant Product category Product type Model name Area Book No. Published in

R410A

VRV Indoor units

Ceiling Mounted Cassette Type (Round Flow with Sensing) FXFQ07-48TVJU USA EDUS391400B-F14 Jun.2020

VISTA™ 2 x 2 Cassette Unit FXZQ05-18TAVJU USA EDUS391776A-F9 Sep.2020

4-Way Blow Ceiling- Suspended Type FXUQ18-36PVJU USA EDUS391437-F15 May 2015

One Way Blow Cassette Type FXEQ07-24PVJU USA EDUS391533-F16 Oct.2015Slim Ceiling Mounted Duct Type FXDQ07-24MVJU USA EDUS39-600-F2 Sep.2006MSP Concealed Ducted Unit FXSQ05-54TAVJU USA EDUS391777A-F17 Sep.2020

Ceiling Mounted Duct Type (Middle and High Static Pressure) FXMQ07-54PBVJU USA EDUS391503B-F4 Jun.2020

Ceiling Mounted Duct Type FXMQ72/96MVJU USA EDUS39-900A-F11 May 2010Ceiling Suspended Type FXHQ12-36MVJU USA EDUS39-600-F5 Sep.2006Wall Mounted Type FXAQ07-24PVJU USA EDUS391100-F6 Jan.2012Floor Standing Type Concealed Floor Standing Type

FXLQ07-24MVJU FXNQ07-24MVJU USA EDUS391502-F7 Jul.2015

Low-temperature hydrobox HXY48TAVJU USA EDUS392021-F18 Sep.2020

Cased Coil Unit CXTQ24-60TASBLU USA Engineering Data CXTQ-TA —

Air Handling Unit FXTQ09-60TAVJUA FXTQ09-60TAVJUD USA Engineering Data

FXTQ-TA Sep.2016

Outdoor Air Processing Unit FXMQ48-96MFVJU USA EDUS39-900A-F10 May 2010

Branch Selector UnitBSQ-TVJBSF-Q54TVJBS-Q54TVJ

USA EDUS391434A-B Aug.2020

Controls and

networks

Control systems Control devices Adaptors

Please refer to ED Book with No. on the right for applicable models. USA EDUS721909A-T Oct.2020

Navigation remote controller BRC1E73 USA EDUS721438 Apr.2015intelligent Touch Manager DCM601A71, DCM601A72 USA EDUS721212 Oct.2012intelligent Touch Controller DCS601C71 USA EDUS72-608 Dec.2006Interface for use in BACnet® DMS502B71 USA EDUS72-749 Oct.2007

Option for all type Please refer to ED Book with No. on the right for applicable models. USA OHUS07-1 Nov.2007

Energy Recovery Ventilator (VAM) VAM300-1200GVJU USA EDUS711116A Jun.2017

Page 83: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING
Page 84: EDUS371705D-D Engineering Data...EDUS371705D-D 202009 Engineering Data Heat Recovery 60 Hz Design Manual RELQ-TATJA, 208 / 230 V RELQ-TAYDA, 460 V RELQ-TAYCA, 575 V EDUS371705D-D ENGINEERING

1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

Cautions on product corrosion

Warning Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

Read the user’s manual carefully before using this product. The user’s manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

If you have any enquiries, please contact your local importer, distributor and/or retailer.

©All rights reserved 09/20 FS

●Specifications, designs and other content appearing in this brochure are current as of September 2020 but subject to change without notice.

EDU

S371705D-D

ENG

INEER

ING

DA

TA VR

V Aurora Series R

ELQ-TA

TJA / TA

YDA

/ TAYC

A H

EAT R

ECO

VERY 60 H

z DESIG

N M

AN

UA

L