12
CROSS REFERENCE EDISON BUSSMANN GOULD LITTELFUSE HCLR KTK-R ATMR KLKR Features • Branch circuit rated for 600 VAC • Compact dimensions • Fast-acting design responds quickly to both overload and short-circuit current Applications • Lighting • Resistive heating loads HCLR Specifications Fast-Acting Voltage Rating: HCLR: 600 VAC 300 VDC (15–20A) Ampere Rating: 0.5–30 Amps Interrupting Rating: 200,000 RMS Symmetrical Amps Current Limiting: Class CC Fuse Agency Approvals • UL Listed, Class CC, Guide JDDZ, File E162363 • CSA Certified HRCI-MISC per C22.2, No. 248.4 • CE Compliant DIMENSIONS Amps Ferrule (in) Length (in) 0.5 - 30 13/32 1-1/2 RMS SYMMETRICAL CURRENT IN AMPERES S D N O C E S N I E M I T 300 200 100 80 60 40 30 20 10 8 6 4 3 2 1 0.8 0.6 0.4 0.3 0.2 0.1 0.08 0.06 0.04 0.03 0.02 0.01 2 3 4 6 8 0 1 0 2 0 3 0 4 0 6 0 8 0 0 1 0 0 2 0 0 3 0 0 4 1 A 0 1 A 0 2 A 3 AMPERE RATING A 2 A 1 A 5 A 8 A 5 1 Characteristic Curves HCLR Current Limiting Class CC Fuses Part Number AMP Rating Pcs/Pkg Package Weight Price HCLR-5 0.5 10 0.2 lb $77.00 HCLR-75 0.75 $83.75 HCLR1 1 $73.25 HCLR1-5 1.5 $73.25 HCLR2 2 $73.25 HCLR2-5 2.5 $93.75 HCLR3 3 $73.25 HCLR3-5 3.5 $98.25 HCLR4 4 $77.75 HCLR5 5 $73.25 HCLR6 6 $76.50 HCLR7 7 $89.25 HCLR8 8 $77.75 HCLR9 9 $98.25 HCLR10 10 $73.25 HCLR12 12 $73.75 HCLR15 15 $73.25 HCLR20 20 $73.25 HCLR25 25 $77.75 HCLR30 30 $73.25 HCLR Current Limiting Class CC Fuses 1-800-633-0405 Circuit Protection tCPR-160 For latest prices, please check AutomationDirect.com

Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

Embed Size (px)

Citation preview

Page 1: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

CROSS REFERENCE

EDISON BUSSMANN GOULD LITTELFUSE

HCLR KTK-R ATMR KLKR

Features• Branch circuit rated for 600 VAC• Compact dimensions• Fast-acting design responds quickly to both

overload and short-circuit current

Applications• Lighting • Resistive heating loads

HCLR SpecificationsFast-ActingVoltage Rating: HCLR:

600 VAC 300 VDC (15–20A)

Ampere Rating: 0.5–30 Amps

Interrupting Rating: 200,000 RMS Symmetrical Amps

Current Limiting: Class CC Fuse

Agency Approvals• UL Listed, Class CC, Guide JDDZ,

File E162363• CSA Certified HRCI-MISC per C22.2,

No. 248.4• CE Compliant

DIMENSIONS

Amps Ferrule (in) Length (in)

0.5 - 30 13/32 1-1/2

RMS SYMMETRICAL CURRENT IN AMPERES

SD

NO

CE

S NI

EMIT

300

200

10080

60

40

30

20

10

8

6

4

3

2

1

0.8

0.6

0.4

0.3

0.2

0.10.08

0.06

0.04

0.03

0.02

0.01 2 3 4 6 8 01 02 03 04 06 08 001

002

003

004

1

A01

A02A3

AMPERERATINGA2A1 A5 A8

A51

Characteristic Curves

HCLR Current Limiting Class CC FusesPart Number

AMP Rating Pcs/Pkg Package

Weight Price

HCLR-5 0.5

10 0.2 lb

$77.00

HCLR-75 0.75 $83.75

HCLR1 1 $73.25

HCLR1-5 1.5 $73.25

HCLR2 2 $73.25

HCLR2-5 2.5 $93.75

HCLR3 3 $73.25

HCLR3-5 3.5 $98.25

HCLR4 4 $77.75

HCLR5 5 $73.25

HCLR6 6 $76.50

HCLR7 7 $89.25

HCLR8 8 $77.75

HCLR9 9 $98.25

HCLR10 10 $73.25

HCLR12 12 $73.75

HCLR15 15 $73.25

HCLR20 20 $73.25

HCLR25 25 $77.75

HCLR30 30 $73.25

HCLR Current Limiting Class CC Fuses

1 - 80 0 - 633 - 0405Circuit ProtectiontCPR-160

For latest prices, please check AutomationDirect.com

Page 2: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

Edison Fuses Selection Guide and General SpecificationsDescription General Purpose – Midget General Purpose – Small Dimension Electronic

Fuse Type Fast-Acting Time-Delay Fast-Acting Ceramic Fast-Acting Glass Medium Time-

Delay GlassTime-Delay

CeramicTime-Delay

GlassFast-Acting

GlassTime-Delay Glass

Part Number MCL MOL MEQ MEN ABC AGC GMA GMC MDA MDL S500 S506

Voltage Rating 600 VAC 250 VAC 500 VAC 250 VAC

250 VAC (0.5 to 30A)

125VDC: (0.5 to 30A)

250VAC: (0.1 to 10A)

32VAC: (15 to 30A)

250VAC (0.063 - 3A)

125VAC (4 - 15A)

250VAC (0.5 - 3A)125VAC (4 - 10A)

250VAC125VDC

(20A)

250VAC: (0.0625 to 8A)

32VAC: (10 to 20A)

250VAC 250VAC

Amp Rating 0.5 to 50 0.5 to 30 0.25 to 30 0.5 to 30 0.5 to 30 0.10 to 30 0.063 to 15 0.5 to 10 0.5 to 20 0.0625 to 20 0.032 to 10 0.25 to 6.3

Interrupting Rating

100,000 RMS Amps 10,000 RMS Amps See specifications table on product pages

Current Limiting N/A N/A

Agency Approvals

UL Listed to 248.14, File E162443CSA Cert. C22.2 Part 59.2, LR 700489

UL Listed standard 248-14 UL Listed Guide and File nos. (ABC 0.25-20 A): (AGC 1/100-10 A) JDYX and E19180 UL Recognition Guide and File nos. (ABC 20-30A):(AGC 11-30) JDYX2 and E19180 CSA Certification Record No: 053787 C 000 and Class No: 1422 01 and 1422 30

Designed to UL/CSA 248-14 UL Listed, Guide JDYX, File E19180 63mA-6A UL Recognition, Guide JDYX2, File E19180, 7A-15A CSA Certified, File 053787_C_000, 63mA-6A Class 1422-01

UL Listed standard 248-14 UL Listed Card: MDA 2/10-20A , MDL 1/16-8A (Guide JDYX, File E19180 UL Recognized Card: MDA 25-30A MDL 9-30A (Guide JDYX2, File E19180) CSA Certification Card: MDA 2/10-15A (Class No. 1422-01)

UL Recognized Guide JDYX2, File E19180 Semko Approval VDE Approval BSI Approval IMQ Approval RoHS compliant

RoHS

Dimensions ferrule (in): 13/32 length (in): 1-1/2 1/4” x 1-1/4”, (6.3mm x 32mm)

0.197” x 0.788” (5mm x 20mm)

1/4” x 1-1/4”, (6.3mm x 32mm)

0.197” x 0.788” (5mm x 20mm)

Edison Fuses Selection Guide and General Specifications

DescriptionCurrent Limiting

Class J Class RK5 Class RK1 Class T Class L Class CCFuse Type Fast-Acting Time-Delay Time-Delay Extremely Fast-Acting Fast-Acting Fast-Acting Time-Delay

Part Number JHL JDL ECNR ECSR LENRK LESRK TJN TJS LCU HCLR HCTR EDCC

Voltage Rating

600VAC 450VDC

600VAC 300VDC*

250VAC125 VDC* (1-200A)250VDC* (201-600A)

600VAC 300VDC*

250VAC125 VDC* (10-60A)250VDC* (70-600A)

600VAC300VDC*

300VAC160 VDC (15-600A)

600VAC 600V600VAC300VDC (15-20A)

600VAC600VAC300VDC (0.5-2.25A) (20–30A)

Amp Rating 1 - 600 1 - 600 3 - 600 10 - 600 5 - 600 1 - 600 601 - 1200 0.5 - 30 0.25 - 30 0.5 - 30

Interrupting Rating 200,000 RMS Symmetrical Amps

Current Limiting Class J Class RK5 Class RK1 Class T Class L Class CC

Agency Approvals

UL Listed Class J Guide JDDZ File E162363CSA Certified HRCI-J per C22.2, No. 248.8 File 700489RoHS compliant

UL Listed Class J Guide JDDZ File E162363CSA Certified HRCI-J per C22.2, No. 248.8 File 700489

UL Listed, Class RK, Guide JDDZ, File E162363CSA Certified HRCI-R per C22.2, No. 248.12, File 700489 (LENRK CSA File 053787)

UL Listed, Class T, Guide JDDZ, File E162363CSA Certified HRCI-T per C22.2, No. 248.12, File 53787, Class 1422-02 & 1422-82

UL Listed, Std. 248-10CSA Certified, HRC-L C22.2 No. 248.10, Class 1422-02, File 53787

UL Listed to 248.4, Class CC, Guide JDDZ, File E162363, CSA certified HRCI-MISC per C22.2 No. 248.4, File 700489

Dimensions See product specification pages. ferrule (in): 13/32, length (in): 1-1/2* Self-certified DC ratings

Line OverviewThe Edison family of fuses, fuse blocks and fuse holders is di-vided into two classes:

1. Current Limiting: Class CC, Class J, Class L, Class RK, Class T2. General Purpose: Class M Midget and Small Dimension

The fuse selection guide below is a general summary of the specifications included for each fuse type. This selection guide does not include the many variables that can exist for specific situations such as local codes, unusual temperature, or other operating conditions. When selecting fuses, be sure to com-ply with any applicable PUBLIC SAFETY standards that apply to Overcurrent Protection Devices (OPD).

Selection Guide

1 - 80 0 - 633 - 0405Circuit ProtectiontCPR-140

For latest prices, please check AutomationDirect.com

Page 3: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

1/4”

Fuseblock 1/4”

Fuseblock

w/LED5mm

Fuseblock 5mm

Fuse block

w/LED

DN-F6L Series: EURO S 10H/35

DN-F6 Series:EURO S 10H/35

DN-F10L Series:EURO S 4LH/35

DN-F10 Series:EURO S 4LH/35

Fuse Terminal Blocks

Ordering InformationPartNumber

Pcs/Pkg Price Part

NumberPcs/Pkg Price Part

NumberPcs/Pkg Price Part

NumberPcs/Pkg Price

Gray Terminal Block DN-F6 25 $93.00–

DN-F10 50 $149.00–

DN-F6MN 7 $20.00 DN-F10MN 10 $22.7512-24 VAC/DC*

–DN-F6L24 10 $54.00

–DN-F10L24 10 $53.00

110 VAC/DC* DN-F6L110 10 $54.00 DN-F10L110 10 $53.00220 VAC/DC* DN-F6L220 10 $54.00 DN-F10L220 10 $53.00

Technical Specifi cationsStripping Length 12mm [0.47 in] 12mm [0.47 in] 10mm [0.39 in] 10mm [0.39 in]

Tightening Torque 2.0 N·m [17.7 lb·in] 2.0 N·m [17.7 lb·in] 0.6 N·m [5.3 lb·in] 0.6 N·m [5.3 lb·in]Density 100/m [30 pcs/ft] 100/m [30 pcs/ft] 100/m [30 pcs/ft] 100/m [30 pcs/ft]

UL Approval** 600V 30A 20-6 AWG 600V 30A 20-6 AWG 300V 15A 24-10 AWG 300V 15A 24-10 AWGCSA Approval 600V 30A 18-6 AWG 600V 30A 18-6 AWG 300V 8A 18-12 AWG 300V 8A 18-12 AWGVDE Approval 750V 8A – 750V 8A – 500V 8A 4mm² 500V 8A 4mm²

Fuse Size (not supplied) 1 1/4” X 1/4” 1 1/4” X 1/4” 5x20mm-5x25mm 5x20mm-5x25mmIndicator Type Non-indicating LED blown fuse indicator Non-indicating LED blown fuse indicator

Operating Temperature Ambient air temperature: -20°C to 85°C [-4°F to 185°F] / Relative humidity: 50% max at 40°C [104°F]; 90% max at 20°C [68°F]SCCR Rating 10kA per Table SB4.1, 2009, UL 508A, Maximum short circuit current rating for unmarked components

CE Conformity CE (EN 60947-1 / 60947-7-3)Agency File # UL E179129 / LR84816

Note: To obtain the most current agency approval information, see the Agency Approval Checklist section on the specifi c part number's web page.

AccessoriesEnd Covers Included Included Included Included

35mmDIN Rail

7.5 mmhigh

DN-R35S1 10 $28.00 DN-R35S1 10 $28.00 DN-R35S1 10 $28.00 DN-R35S1 10 $28.00DN-R35S1-2 2 $9.00 DN-R35S1-2 2 $9.00 DN-R35S1-2 2 $9.00 DN-R35S1-2 2 $9.00

15mmhigh

DN-R35HS1 10 $49.50 DN-R35HS1 10 $49.50 DN-R35HS1 10 $49.50 DN-R35HS1 10 $49.50DN-R35HS1-2 2 $12.00 DN-R35HS1-2 2 $12.00 DN-R35HS1-2 2 $12.00 DN-R35HS1-2 2 $12.00

End Brackets

DN-EB35 50 $39.50 DN-EB35 50 $39.50 DN-EB35 50 $39.50 DN-EB35 50 $39.50DN-EB35MN 20 $18.00 DN-EB35MN 20 $18.00 DN-EB35MN 20 $18.00 DN-EB35MN 20 $18.00DN-EB35-A 50 $28.50 DN-EB35-A 50 $28.50 DN-EB35-A 50 $28.50 DN-EB35-A 50 $28.50DN-EB35-A-10 10 $7.50 DN-EB35-A-10 10 $7.50 DN-EB35-A-10 10 $7.50 DN-EB35-A-10 10 $7.50DN-QEB35 50 $25.50 DN-QEB35 50 $25.50 DN-QEB35 50 $25.50 DN-QEB35 50 $25.50DN-QEB35-10 10 $7.50 DN-QEB35-10 10 $7.50 DN-QEB35-10 10 $7.50 DN-QEB35-10 10 $7.50

Angled Support Bracket DN-ASB1 50 $49.50 DN-ASB1 50 $49.50 DN-ASB1 50 $49.50 DN-ASB1 50 $49.50

Marking Tags DN-L*** orDN-LT****

500/100 various DN-L*** or

DN-LT****500/100 various DN-L*** or

DN-LT****500/100 various DN-L*** or

DN-LT****500/100 various

*Working voltage **For copper wire only ***On lever arm ****On terminal bodyNote: DN-F6 series fuse holders will accommodate the following AutomationDirect fuses: ABC, AGC, MDA and MDL Series.

DN-F10 series fuse holders will accommodate the following AutomationDirect fuses: GMA, GMC, S500, and S506 Series.For more information on accessories, see the DINnectors Accessories section of this chapter.

Fuse blocks are available for 1/4”, 5mm, Class CC and midg-et size fuses, either with or with-out a blown fuse LED. LED fuse blocks are polarity sensitive and are 35mm DIN-rail mountable. The hinge side is positive.

10 mm[0.39 in]

66 mm[2.6 in]

44 mm[1.73 in]

DN-F10 / DN-F10MN

10 mm[0.39 in]

66 mm[2.6 in]

44 mm[1.73 in]

DN-F10L10 mm[0.39 in]

52 m

m [2

.05

in]

82 mm[3.23 in]

DN-F6L10 mm[0.39 in]

52 m

m [2

.05

in]

82 mm[3.23 in]

DN-F6 / DN-F6MN

1 - 80 0 - 633 - 0405Terminal BlockstTBL-54

For latest prices, please check AutomationDirect.com

Page 4: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

Pressure Plate (with Quick Connect**) Modular Ferrule Fuse Blocks for Midget Class and CC Fuses

Clas

s

Part Number Pc/ pkg Price Volts Amps

Pole

s Wire Range¹ Torque Wt. Covers* (Sold Separately)solid and stranded

fine stranded lb·in [N·m] lb [kg] w/o

Indicationw/

Indication³Pc/ pkg

Mid

get

BMM603-1PQ 15 $66.00

600V AC/DC 30

1

18-10 AWG 18-10 AWG 20 [2.3]

0.05 [0.04]

CVR-CCM-QC$14.00

CVRI-CCM-QC$18.75 3

BMM603-2PQ 5 $39.00 2 0.15 [0.06]

BMM603-3PQ 5 $50.00 3 0.20 [0.10]

BMM603-1PQ-1 1 $4.75 1 0.05 [0.04]

CC

BCM603-1PQ 15 $90.50 1 0.05 [0.04]

BCM603-2PQ 5 $47.25 2 0.15 [0.06]

BCM603-3PQ 5 $62.25 3 0.20 [0.10]

BCM603-1PQ-1 1 $6.50 1 0.05 [0.04]

Com

bo

BCCMM603-3PQ² 5 $66.00 3 0.20 [0.10]

¹ Ratings are for copper wire only.² Combination modular fuse block for use with transformers. Accepts two (2) Class CC and one (1) Midget class fuse.³ Open fuse indication requires 90V minimum and closed circuit to operate.*Once installed, the cover cannot be removed.**Quick connect terminal rated for 20A maximum.

Modular Ferrule Fuse Blocks for Midget Class and CC Fuses

Patented lockout/tagout

Universal marker label(DN-LA Series)

Test probe holes

Modular design for tool-less

snap together assembly

DIN rail and panel mount

DescriptionBCM Series for use with Class CC fuses EDCC, HCTR and HCLRBMM Series for use with Midget Class Midget fuses MCL, MEQ, MEN & MOL

Mounting35mm DIN rail or panel mount

SpecificationsMaterials:Base – ThermoplasticTerminals – Tin-plated bimetallic copperCovers – ThermoplasticScrews and pressure plates – Zinc-plated steelSCCR: 200kAFlammability rating:Blocks – UL 94V0, self-extinguishingCovers – UL 94HB, self-extinguishingOperating and storage temp range:Blocks – -40° to 120°C [-40° to 248°F]Covers – indicating -20° to 90°C [-4° to 194°F] non-indicating -40° to 120°C [-40° to 248°F]Wire: Cu – 75°/90°C [ 167°/194°F] Ring or Fork terminal to fit a #10-32 screw

Clear IP20 finger-safe cover(sold separately)

Compact footprint

Tin-plated bimetallic copper fuse clips

Agency ApprovalsFuse Blocks

• BCM – UL® Listed E14853 - IZLT BMM and BCCM UL Recognized E14853-IZLT2

• CSA® Certified 47235-6225-01• CE• RoHS Compliant• Conflict mineral free

• REACH Compliant

Covers• Covers are included in the overall UL Listing/Recognition

and CSA Certification• IP20 finger-safe• RoHS compliant• REACH Compliant

To obtain the most current agency approval information, see the Agency Approval Checklist section on the specific part number's web page.

R

2011/65/EU

Pressure plate with quick connect

tCPR-211Circuit Protectionw w w. a u to m at i o n d i re c t . c o m / c i r c u i t- p ro te c t i o n

For latest prices, please check AutomationDirect.com

Page 5: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

Modular Ferrule Fuse Blocks for Midget Class and CC FusesDimensions

in [mm]

Please see our website www.AutomationDirect.com for complete engineering drawings. Dimensions are approximate. Not for construction purposes.

BCM Series

BMM Series

1 - 80 0 - 633 - 0405Circuit ProtectiontCPR-212

For latest prices, please check AutomationDirect.com

Page 6: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

BCCMM603-3PQ

Modular Ferrule Fuse Blocks for Midget Class and CC FusesDimensions

in [mm]

Please see our website www.AutomationDirect.com for complete engineering drawings. Dimensions are approximate. Not for construction purposes.

tCPR-213Circuit Protectionw w w. a u to m at i o n d i re c t . c o m / c i r c u i t- p ro te c t i o n

For latest prices, please check AutomationDirect.com

Page 7: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

Fuse Blocks for Class CCand Midget Class Fuses

BC Series FuseblocksPart Number Amps Poles AWG Pcs/

PkgWt. (lbs.) Price

BC6032PQ0.1 to 30

218 - 8

8 0.16 Retired

BC6033PQ 3 6 0.22 Retired

BM Series FuseblocksPart Number Amps Poles AWG Pcs/

PkgWt. (lbs.) Price

BM6031PQ0.1 to 30

1

18 - 8

10 0.1 $45.00

BM6032PQ 2 8 0.16 Retired

BM6033PQ 3 6 0.22 Retired

DescriptionThese panel-mount fuse blocks are for use with Class CC Fuses (Edison EDCC, HCTR and HCLR).

Specifications Terminal type: Pressure plate with quick connect terminal

Base: Thermoplastic

Clips: Bright tin-plated bronze

UL Flammability: 94V-0

Ratings: 600 VAC, 30 Amps

Agency Approvals• UL listed to 512 , Guide IZLT, File 14853• CSA C22.2 No. 39 Class 6225-01, File LR47235• CE Compliant

DescriptionThese panel-mount fuse blocks are for use with any 13/32” x 1-1/2” Class M Fuses (Edi-son MCL, MEQ, MEN and MOL).

Specifications Terminal type: Pressure plate with quick connect terminal

Base: Thermoplastic

Clips: Bright tin-plated bronze

UL Flammability: 94V-0

Ratings: 600 VAC, 30 Amps

Agency Approvals• UL Recognized to 512, Guide IZLT2,

File E14853• CSA C22.2, No.39, Class 6225-01, File 47235

CROSS REFERENCEEDISON OLD EDISON BUSSMANN GOULD LITTELFUSEBM6031PQ EM631-44 BM6031PQ 30321 L60030M-1PQ

BM6032PQ EM632-44 BM6032PQ 30322 L60030M-2PQ

BM6033PQ EM633-44 BM6033PQ 30323 L60030M-3PQ

CROSS REFERENCEEDISON OLD EDISON BUSSMANN GOULD LITTELFUSEBC6032PQ EMR632-77 BC6032PQ 30322R L60030C-2PQ

BC6033PQ EMR633-77 BC6033PQ 30323R L60030C-3PQ

1 - 80 0 - 633 - 0405Circuit ProtectiontCPR-214

For latest prices, please check AutomationDirect.com

Page 8: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

1.625" + 0.015"(41.28mm + 0.38mm)

2.375" + 0.015"(60.33mm + 0.38mm)

R

BUSSMANNCOOPER INDUSTRIESST. LOUIS, MO 63178MADE IN U.S.A.

75 C WIRE200,000A RMS SYMWITHSTAND RATING

Buss ®

30A 600V

CLASS CCFUSES ONLY

CU ONLY10 AWG 20 LBJN.

0.200" + 0.003"(5.08mm + 0.08mm)

0.425"(10.80mm)

1.530"(38.86mm)

0.200" + 0.003"(5.08mm + 0.08mm)

2 POLE 0.425"(10.80mm)

0.765"(19.43mm)

3 POLE

1.210" + 0.015"(30.73mm + 0.38mm)

Dimensional Data

0.42"(10.7mm)

1.53"(38.9mm)

0.42"(10.7mm)

0.77"(19.4mm)

3"(76.2mm)

1.22"(31.0mm)

1.5"(38.1mm)

0.36"(9.1mm)

0.86"(21.8mm)

1.63"(41.3mm)

2.38"(60.3mm)

CC Class Dimensions - inches(mm)

M Class Dimensionsinches(mm)

One Pole BM6031PQ

Two Pole BM6032PQ

Three Pole BM6033PQ

Three Pole BC6033PQ

Two Pole BC6032PQ

Fuse Blocks for Class CCand Midget Class Fuses

tCPR-215Circuit Protectionw w w. a u to m at i o n d i re c t . c o m / c i r c u i t- p ro te c t i o n

For latest prices, please check AutomationDirect.com

Page 9: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

Features• EHCC Series: High SCCR rated, UL Listed

CC holder with indicator option for 600VAC/DC

• EHM Series: UL Recognized midget holders

• Minimum 90VAC/DC required for illumination

• Rated for use with 75°C or 90°C wire, fine stranded wire, spade terminals and comb-bus bars. Use any higher temperature rated wire with appropriate derating.

• Complete range of UL Listed and high SCCR rated 1-phase and 3-phase finger-safe comb-bus bars and power feed lugs

• Polyester material is UL 94V0 rated, self extinguishing

• Multi-phase connections available for ganging up to 4 poles*

• Mounts on 35 mm DIN rail • IP20 rated• Spade terminals are accepted

(Max width-10mm, Min ID of slot 4mm Max ID of slot 5mm)

• Wire ferrules may not be used.

Application• EHM: Edison MCL, MOL, MEQ, MEN, or

midget fuses• EHCC: Edison HCLR, HCTR, EDCC fuses,

or class CC fuses

Agency Approvals/ Standards Class CC

• UL File E300536 Guide IZLT Listed

• CSA File 47235, Class 6225-01• CE Compliant• RoHS, Reach

Agency Approvals/ Standards Midget

• UL File E300536 IZLT2 Recognized

• CSA File 47235, Class 6225-30• IEC 60269-2• CE Compliant• RoHS, Reach

Modular Fuse Holders for Class CC & Midget Class Fuses

Modular Fuse Holder Selection Table

Series Size

Max Voltage &

CurrentIEC UL Phase

ConfigurationFuse Holder

Without Indication

Box Qty.

Pkg. Wt. (lb.)

PriceFuse Holder with NEON Indication

Product Weight

(lb.)Box Qty. Price

EHM Midget Class

UL600V/30A

IEC690V/32A

• • 1 poleEHM1DU 1 0.12 $8.50 EHM1DIU 0.12 1 $11.50

EHM1DU-12 12 1.42 $87.00 EHM1DIU-12 1.42 12 $116.75

• • 2 poleEHM2DU 1 0.24 $17.75 EHM2DIU 0.24 1 $23.50

EHM2DU-6 6 1.42 $90.50 EHM2DIU-6 1.42 6 $119.75

• • 3 poleEHM3DU 1 0..36 $26.75 EHM3DIU 0.36 1 $36.00

EHM3DU-4 4 1.42 $91.25 EHM3DIU-4 1.42 4 $122.75

EHCC Class

CCUL

600V/30A

•• 1 poleEHCC1DU 1 0.12 $10.00 EHCC1DIU 0.12 1 $13.00

EHCC1DU-12 12 1.42 $103.00 EHCC1DIU-12 1.42 12 $133.25

•• 2 poleEHCC2DU 1 0.24 $20.75 EHCC2DIU 0.24 1 $26.75

EHCC2DU-6 6 1.42 $105.75 EHCC2DIU-6 1.42 6 $137.50

•• 3 poleEHCC3DU 1 0.36 $31.25 EHCC3DIU 0.36 1 $40.75

EHCC3DU-4 4 1.42 $106.75 EHCC3DIU-4 1.42 4 $139.00

* To add additional poles, see multi-pole connection kit JV-L in accessories. One JV-L kit is sufficient to gang up to 4 poles. • UL Recognized, CSA •• UL Listed, CSA

1 - 80 0 - 633 - 0405Circuit ProtectiontCPR-216

For latest prices, please check AutomationDirect.com

Page 10: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

EHM Midget Class / EHCC Class CC

Modular Fuse Holder SpecificationsPart Number

w/o IndicationPart Number w/ Indication

Holder Size

Max Voltage & Current

Number of poles

Wire Range

Maximum Torque

Operating Temperature

SCCR Rating

Terminal Rating

Flammability Rating

EHM1DU EHM1DIU

EHM Midget Classand

10x38

UL/CSA 600V/30A

IEC 690V/32A

1

18-4 AWG(0.8-21 mm²)

30 lb-in(3.4 N•m)maximum

-20˚C to +90˚C -4˚F to 194˚F (indicating)

-20˚C to +120˚C -4˚F to 248˚F

(non-indicating)

100kArms sym

Solid, Stranded,

Fine stranded, Spade lug,

Comb-bus bar; Single and dual wire;

75˚C and 90˚C Cu wire

UL 94V0self-extinguishing

EHM1DU-12 EHM1DIU-12EHM2DU EHM2DIU

2EHM2DU-6 EHM2DIU-6EHM3DU EHM3DIU

3EHM3DU-4 EHM3DIU-4EHCC1DU EHCC1DIU

EHCC Class CC

UL/CSA 600V/30A

1

200kArms sym

EHCC1DU-12 EHCC1DIU-12EHCC2DU EHCC2DIU

2EHCC2DU-6 EHCC2DIU-6EHCC3DU EHCC3DIU

3EHCC3DU-4 EHCC3DIU-4

Fuse Holder Dimensions mm [inches]

CHCC and EHM Wire Range, Type and TorqueWire Range Conductor Type Number of Conductors Torque

18-14 AWG (0.8-2.0 mm²)

Solid, Stranded

Single 20 lb-in (2.3 N•m)

18-16 AWG (0.8-1.3 mm²)Dual

25 lb-in (2.8 N•m)

14-10 AWG (2.0-5.2 mm²)

30 lb-in (3.4 N•m)

12-10 AWG (3.3-5.2 mm²)

Single8-4 AWG (8.3-21.1 mm²) Stranded, Fine Stranded

18-14 AWG (0.8-2.0 mm²) Spade Terminal

N/A Comb Bus

Modular Fuse Holders for Class CC & Midget Class Fuses

tCPR-217Circuit Protectionw w w. a u to m at i o n d i re c t . c o m / c i r c u i t- p ro te c t i o n

For latest prices, please check AutomationDirect.com

Page 11: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

Accessories

JV-L

FP2

JV-L

Note: Will not work with retired design fuse holders shipped before November 1, 2009. *Roll pin punch or installation tool is required to install handle pins (Tool not sold by Automationdirect.com).

Handle Pin Dimensions Diameter = 0.0625 in [1.58 mm] Length = 0.632 in [16.07 mm]

AccessoriesPart Number Description Pcs/Pkg Price

FP-2 Fuse puller for fuse dia. 13/32” - 13/16”. Fuse type: 0-60A, 250V; 0-30A, 600V 1 $16.75

JV-L* (Not Field Installable)

Multi-pole connection kit to connect new design multiple Class CC and Midget Class fuse holders together. Kit consists of 6 con-nectors and 3 handle pins to connect up to 4 fuse holders.

$7.00

tCPR-223Circuit Protectionw w w. a u to m at i o n d i re c t . c o m / c i r c u i t- p ro te c t i o n

For latest prices, please check AutomationDirect.com

Page 12: Edison HCLR Current Limiting Class CC Fuses · PDF fileHCLR Current Limiting Class CC Fuses tCPR-160 Circuit Protection 1-800-633-0405 ... Fuse Type Fast-Acting Time-Delay Fast-Acting

Cross Reference Guide

CROSS REFERENCE GUIDE By manufacturers type reference or series number. Ampere ratings must be added for ordering purposes.

FUSE TYPE VOLT EDISON BRUSH/ DORMAN BUSSMANN MERSEN /

GOULD GEC/CEFCO LITTELFUSE

UL CLASS CURRENT LIMITING FUSES (CSA CLASS)

CC (HRCI-CC)

Time-Delay 600 EDCC – LP-CC ATDR – CCMR

Time-Delay 600 HCTR – FNQ-R ATQR – KLDR

Fast-Acting 600 HCLR HCLR KTK-R ATMR CTK-R KLKR

RK1 Time-Delay Dual Element250 LENRK – LPN-RK-SP A2DR – LLNRK

600 LESRK – LPS-RK-SP A6DR – LLSRK

RK5 Time-Delay Dual Element250 ECNR – FRN-R TR – FLNR

600 ECSR – FRS-R TRS – FLSR

JTime-Delay Dual Element 600 JDL – LPJ AJT – JTD

High-Speed AC Drive 600 JHL – DFJ HSJ – –

T Extremely Fast-Acting300 TJN – JJN A3T – JLLN

600 TJS – JJS A6T – JLLS

UL CLASS GENERAL PURPOSE FUSES

Midget

Fast-Acting600 MCL MCL KTK ATM CTK KLK

250 MOL MOL BAF/BAN OTM – BLF

Time-Delay500 MEQ MEQ FNQ ATQ – FLQ

250 MEN MEN FNM TRM – FLM

1/4”x 1-1/4” CeramicFast-Acting

250/125 ABC ABC ABC GAB – 314

1/4”x 1-1/4” Glass 250/32 AGC AGC AGC GGC – 312

1/4”x 1-1/4” CeramicTime-Delay

250 MDA MDA MDA – – 326

1/4”x 1-1/4” Glass 250/32 MDL MDL MDL GDL – 313

5x20 mm GlassFast-Acting 250/125 GMA GMA GMA GGM – 235

Medium Time-Delay 250/125 GMC GMC GMC GSC – –

5x20 mm GlassFast-Acting 250 S500 BDB GDB GSB – 217

Time-Delay 250 S506 BDC GDC GDG – 218

Fuse Puller

Fuse Puller FP-2 – old - 38072 new - FP-2 – FP-2 – – –

1 - 80 0 - 633 - 0405Circuit ProtectiontCPR-224

For latest prices, please check AutomationDirect.com