29
User Guide W-200 Module temptimecorp.com

EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

  • Upload
    others

  • View
    5

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

UserGuideW-200Module

temptimecorp.com

Page 2: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Noticesandsafety

TemptimeLoRaWanenabledsolution EDGEW-200module Page2

1 Noticesandsafety

1.1.1 SafetyinstructionsIMPORTANTNOTE:Donotusethisproductforprotectionoraspartofanautomatedemergencysystemorasforanyotherapplicationthatinvolvesprotectingpeopleand/orproperty.CustomersandusersofTemptimeproductsareresponsibleformakingsurethattheproductisfitfortheintendedusage.Donotopentheproductcasinganddonotdisassembleormodifyinternalcomponentsinanymanner.Temptimeproductsdonotcontainanyinternalcomponentsthatrequireuserinterventionorrepair.Ifthedeviceshowssignsofimproperoperation,disconnectitimmediatelyfromitspowersourceandcontactTemptimetechnicalservices.

1.1.2 BatterywarningThisproductcontainsalithiumbattery.Makesureyourespectpolarity(+/-)wheninsertingbatteriesintoTemptimedevices.Reversingpolaritybyinsertingthebatteriesincorrectlycancausetheproducttoheatup,andmayleadtobatteryliquidleakage.UseonlybatteriesrecommendedbyTemptime.Donotchangebatterytypes,suchasrechargeable,alkalineandmagnesium,orusebatteriesofdifferentbrands,orevendifferenttypesofbatteriesofthesamebrand.Incorrectbatteriesmaycausethedevicetoheatup,andmayresultinafireorbatteryliquidleakage.Neverdisposeofbatteriesinfire.Donot

chargeregularbatteriesthatarenotspecificallyrechargeable.Whenthebatteryislow,orincasethebattery-operateddeviceinquestionremainsunusedforalengthyperiodoftime,removethebatteryfromthedeviceinordertoavoidanyriskofbatteryliquidleakage.Neverleavebatterieswithinthereachofchildren.Incaseofabatteryleak,avoidallcontactwiththeliquidpresentonthebatteries.Rinsewithclearwaterimmediatelyincasethebatteryliquidcomesintocontactwiththeeyes,mouthorskin.Contactadoctororemergencyserviceimmediately.Batteryliquidiscorrosiveandcandamagevision,orcauseblindnessorchemicalburns.

1.1.3 FCCstatementThisparagraphpertainsto915MHzEDGE™wirelessmodules.Thisdevicecomplieswithpart15oftheFCCrules.Operationissubjecttothefollowingtwoconditions:(1)Thisdevicemaynotcauseharmfulinterference,and(2)thisdevicemustacceptanyinterferencereceived,includinginterferencethatmaycauseundesiredoperation:FCCPart15§107-§109-§207-§247(Ed2008).

1.1.4 Canada—IndustryCanada(IC)Thisparagraphpertainsto915MHzEDGE™wirelessmodules.ThisdevicecomplieswithIndustryCanadalicense-exemptRSSstandard(s).Operationissubjecttothefollowingtwoconditions:(1)thisdevicemaynotcauseinterference,and(2)thisdevicemustacceptanyinterference,includinginterferencethatmaycauseundesiredoperationofthedevice.

1.1.5 ConformitywithEuropeanregulationsThisparagraphpertainsto868MHzEDGEwirelessmodules.TheCEmarkonthisproductindicatesthatTemptimedeclaresthatthisproductiscompliantwithRadioequipmentandTelecommunicationsTerminalequipment(R&TTE)directive1999/5/ECandtheLowVoltageDirective(LVD)2006/95/EC.Thefollowingstandardswereutilizedtomeettheessentialrequirementsofthesedirectives:EN301489-3v1.4.1(02),EN300220-2V2.1.2(R&TTE)&EN60950-1:2006/A11:2009(LVD).

Caution:AnychangesormodificationsnotexpresslyapprovedbyTemptimecouldvoidtheuser'sauthoritytooperatetheequipment.

1.1.7 WEEEcomplianceThiswirelessdevicecomplieswiththeessentialrequirementsandotherrelevantprovisionsoftheWasteElectricalandElectronicEquipmentDirective2002/96/EC(WEEEDirective).

1.1.8 EnvironmentalprotectionPleaserespectlocalregulationsconcerningdisposalofpackaging,unusedwirelessdevicesandtheiraccessories,andpromotetheirrecycling.

Page 3: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Noticesandsafety

TemptimeLoRaWanenabledsolution EDGEW-200module Page3

1.1.9 RoHScomplianceThe wireless device is in compliance with the restriction of the use of certain hazardous substances in electrical and electronic equipment Directive 2002/95/EC (RoHS Directive). Do not dispose of this product with household trash. Temptime recycles this product under certain conditions. Please contact us for more information.

1.1.10 DisclaimerandlimitationofliabilityTemptime assumes no responsibility for any loss or claims by third parties which may arise through the use of this product. This document is non-contractual and subject to change without notice.

© 2017 Temptime. All rights reserved. Temptime, the Temptime logo, EDGEConnect Mobile, Temptime EDGE, and EDGECloud are the exclusive property of Temptime. All other brands mentioned are the property of their respective owners. Specifications subject to change without notice

September2017 Ref:COMMEDGEW-200Module UserGuide Rev.02

Page 4: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Noticesandsafety

TemptimeLoRaWanenabledsolution EDGEW-200module Page4

TableofContents

1 Noticesandsafety.............................................................................................................2

2 Introduction.......................................................................................................................6

2.1 Overview.........................................................................................................................................6

2.2 Mainmodulefeatures.....................................................................................................................7

2.3 Availablesensortypes.....................................................................................................................8

2.4 Packagecontents.............................................................................................................................9

3 Gettingstarted.................................................................................................................10

3.1 Requirements................................................................................................................................10

3.2 Productdescription.......................................................................................................................10

3.3 Typicalinstallation.........................................................................................................................11

3.4 Howtocheckyourmodule’swirelesssignal.................................................................................12

3.5 Requirementsandrecommendations...........................................................................................13

3.6 PlacingyourEDGEmoduleforbestwirelessperformance...........................................................13

3.7 Preparingmountingkitwithamagnet(optional).........................................................................14

4 ExternalSmartSensors.....................................................................................................15

4.1 ConnectingSmartSensors™..........................................................................................................15

4.2 PlacingSmartSensors™.................................................................................................................17

5 Externaldigitalsensors.....................................................................................................20

5.1 Connectingthesensor...................................................................................................................21

5.2 Placingthesensor..........................................................................................................................21

6 Internalsensor..................................................................................................................23

6.1 Placingmoduleswithaninternalsensor.......................................................................................23

7 Temperature/humiditySmartSensors™...........................................................................24

7.1 Connectingthesensor...................................................................................................................24

7.2 Placingthesensor..........................................................................................................................25

8 ActivatingtheEDGEW-200module..................................................................................26

Page 5: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Noticesandsafety

TemptimeLoRaWanenabledsolution EDGEW-200module Page5

8.1 Refreshingthemoduledisplaywithashortpress........................................................................27

9 Appendix-Troubleshooting..............................................................................................28

10Index................................................................................................................................29

Page 6: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Introduction

TemptimeLoRaWanenabledsolution EDGEW-200module Page6

2 Introduction

CongratulationsandthankyouforchoosingtheTemptimeEDGEW-200wirelessmonitoringsolution.

ThisdocumentpresentsanoverviewoftheEDGEW-200wirelessmodule,followedbypracticalinstructionstogetyourmoduleupandrunningquicklyaspartofyouroverallEDGELoRasolution.DetailedconfigurationinstructionsandsoftwaresettingsareprovidedinthedocumentationforEDGEW-200companionsoftwareapplications:

• EDGEConnectMobile,aTemptimemobileappforiOSandAndroidusedtosetupEDGEW-200modules

• EDGEConnect,anTemptimewebapplicationofferingacompletesensormonitoringinterface

Thisdocumentfocusesonthephysicalaspectsofthemoduleandcompatiblesensors.PleaseseetheEDGEConnectwebapplicationuserguideandtheEDGEConnectMobileapplicationuserguidefordetailsonthosepartsofthesolution.

2.1 OverviewTheTemptimeEDGEW-200isawirelesstemperatureandhumiditydevicethatintegratesLoRaWAN™technologytoofferverylongrangewirelessconnectivity–upto10miles(16km)line-of-sight.ThismoduleconnectswirelesslytoyourLoRaWAN™receiverinstalledatyoursite,whichtransmitslocallycollectedsensordataviatheInternettotheCloud.TheEDGEConnectwebapplicationisthenusedtoviewandmanagesensorsonaneverydaybasis,withtheEDGEConnectMobileapplicationusedtouploadconfigurations.

Figure1–W-200modulescommunicatewiththeCloudviaalocalreceiver

Page 7: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Introduction

TemptimeLoRaWanenabledsolution EDGEW-200module Page7

2.2 Mainmodulefeatures• EDGEW-200wirelesstemperatureandhumiditydataloggingmodulewithLCD

• UnlimiteddatastorageonEDGECloud;upto4,000readingsinmodulememory

• LoRaWAN™wirelessconnectivity

• BluetoothSmart®wirelessconnectivity

• Varioussupportedtemperatureandhumidityranges(detailsinnextsection)

• CalibrationparametersembeddeddirectlyinEDGESmart-Sensors(forease-of-useandstandardexchangeforperiodiccalibration)

• ISO17025(COFRAC)calibration,Temptimecertifiedcalibration,orNISTtraceablecalibrationuponrequest

• Automaticandspontaneousalarmtransmission(transmittedastheyoccur)

• Configurablehigh/lowalarmthreshold,alerts,regulartransmissioninterval

• AutomaticwirelessconnectiontoLoRaWAN™enabledreceiver

Page 8: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Introduction

TemptimeLoRaWanenabledsolution EDGEW-200module Page8

2.3 AvailablesensortypesEDGEW-200modelsareavailablewithseveraldifferentsensoroptions,asdescribedbelow:

Sensortype Ranges No.sensors Cable Application

Internaldigitaltemperaturesensor

0°Cto+50°C(32°Fto122°F)

1 n/aAmbienttemperaturemeasurement

Externaldigitaltemperaturesensor

-40°Cto+80°C(-40°Fto176°F)or-40°Cto+120°C(-40°Fto248°F)

1Roundwhitecable(1mor3.3ftinlength)

Freezers,refrigerators,andcoldrooms;ovens,incubators,andwaterbaths

Externaldigitaltemperature+humiditysensor

Temperature:-40°Cto+100°C(-40°Fto212°F)Relativehumidityfrom0to99.9%

1dualsensor

Roundwhitecable

Variousstorage,medicalandtraceabilityuses

SmartPT100sensor

-100°Cto+150°(-148°Fto302°F)

1Roundorangecable(3.5mor11.5ftinlength)

Ultra-low-temperature(ULT)freezers,typically-80°C

-200°Cto+50°C(-328°Fto122°F)

1Roundorangecable(1.4mor4.6ftinlength)

Liquidnitrogen(LN2)tanks

Table1-EDGEW-200sensoroptions

PleasechecktheTemptimewebsite(www.Temptimecorp.com)orcontactyourauthorizedrepresentativeforup-to-dateproductinformation.

ThesensorsusedwithEDGEW-200modulessupportavarietyoftemperatureandhumidityranges.However,inallcasestheW-200moduleitselfmustbeusedwithinitssupportedoperatingrange:0°to+50°C(32°Fto122°F)

Page 9: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Introduction

TemptimeLoRaWanenabledsolution EDGEW-200module Page9

2.4 Packagecontents• 1EDGEW-200wirelessmodule(withorwithoutInternaltemperaturesensor)

• 1Lithiumbattery

• 1Antenna

• 1Externalsensorwithcable

• 1Calibrationcertificatepersensor(ifpurchasedwithcalibrationoption)

• 1mountingkitwithplasticholder,magnet,screws,andVelcro®

• 1setofplasticcableholdersandcableties

• 1flatcableadaptor

Page 10: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Gettingstarted

TemptimeLoRaWanenabledsolution EDGEW-200module Page10

3 Gettingstarted

3.1 Requirements• TemptimeLoRaGatewayReceiver(P/N20-5005)installedandsetupforCloudconnectivityvia

EDGEConnectWebApplication

• TemptimeEDGEConnectMobile™applicationinstalledonacompatiblemobiledevice(availableforiOSandAndroidoperatingsystems)andrequiredforconfiguration

• PleasereadEDGEConnect™andEDGEConnectMobile™UserManualscarefully.

3.2 ProductdescriptionEDGEW-200modulesareavailableeitherwithinternaltemperaturesensors,orexternalsensorsasshownbelow.Themodulesthemselvesareidenticalinbothcases(otherthantheexternalsensorcable).Therearetwovariationsofexternalsensors,SmartPT100sensorsanddigitalsensors.Bothofwhichwillbeexplainedinthefollowingsections.

Figure2–EDGEW-200wirelessmodule(examplewithexternalPT100sensor)

LCD display with module name, temperature, signal and battery indicators

Push-button EDGE Smart Sensor connector for external sensors

Page 11: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Gettingstarted

TemptimeLoRaWanenabledsolution EDGEW-200module Page11

3.3 TypicalinstallationAtypicalinstallationthereforeinvolvesoneormoreEDGEW-200modulesandaLoRaWAN™receiver.

Long-rangewirelessconnectivityenablesEDGEW-200modulestobeplacednearlyanywhereinyourbuildingorsite.Incaseswherethesignalisnotstrongenough,asecondLoRaWANreceivermayberequired.PleasecontactTemptimeserviceteamforsupport.

Page 12: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Gettingstarted

TemptimeLoRaWanenabledsolution EDGEW-200module Page12

3.4 Howtocheckyourmodule’swirelesssignalNote ThissectionassumesthatyourTemptimeLoRaWAN™receiver(20-50005)isinstalled,

configured,andrunningproperly.SeeTemptimeEDGELoRaGatewayReceiverConfigurationGuideformoredetailsonthereceivercomponent.

ToseewhetheranEDGEW-200moduleiswithinwirelessrangeofthereceiver:

1. Pressthepushbuttononthefrontofthemodule(shortpress).

2. Ifthemoduledetectsareceiver,thetext“ACK_RECEIVED”(acknowledgmentreceived)isdisplayedinthelowerleft-handcornerofthescreen.Otherwise“ACK_NOT_RECEIVED”isdisplayed(seeAppendix-Troubleshootingonpage28ofthisdocument).

Figure3–ConfirmingconnectionwithLoRaGatewayreceiver

3. Ifrequired,testvariousrangesbyplacingyourmoduleatdifferentlocationsaroundyoursiteandrepeatingthistest.

Thisinformalsitetestingprocedurewillenableyoutoverifythatallyourmodulesarecommunicatingcorrectly.

Excessiveobstruction,interference,orharshconditionscanaffectwirelessperformance.PleasecontactTemptimetechnicalsupportforspecificcasesifyouhaveamodulethatishavingdifficultyreachingthereceiver.

Page 13: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Gettingstarted

TemptimeLoRaWanenabledsolution EDGEW-200module Page13

3.5 Requirementsandrecommendations• TheEDGEGatewayreceiverrunscontinuously,24/7/365,andshouldbeconnectedtoan

UninterruptiblePowerSupply(UPS)thatprotectsagainstpowersurgesandprovidespowertobackupthereceiver.

• TheEDGEConnectwebapplicationwillshowanalertclearlyonthecomputerscreenifamoduleisnotcommunicating.YoumayalsoverifyconnectionsbypressingthepushbuttonontheEDGEW-200moduleandmakingsure“ACK_RECEIVED”isdisplayed.

• Recommendedmaintenanceandcalibrationproceduresshouldbefollowed.

3.6 PlacingyourEDGEmoduleforbestwirelessperformanceForoptimaloperation,followtheserecommendationswhenphysicallyplacingyourdevice:

• Donotplacethemodulewithin40cm(16in.)ofanothermodule.• Makesurethewirelessmoduleisnotplacedonanelectricalconduitorcabletray(suchasfor

computernetworkcables).• Forbestresults,placethemodulesothatitfacesthegeneraldirectionofthereceiver.• Keepabout20cm(8in.)ofclearspacearoundthemodule.Forexample,amodulethatis

“stuck”betweentworefrigeratorsmaynotcommunicateeffectively.• Makesureallcables,ifany,arefirmlyattachedandthatsensorsareproperlyinsertedinthe

appropriatechamber.

Page 14: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Gettingstarted

TemptimeLoRaWanenabledsolution EDGEW-200module Page14

3.7 Preparingmountingkitwithamagnet(optional)YourEDGEW-200moduleincludesaplasticholdersoyoucanmountthedeviceeasilyonvarioussurfaces.Inadditiontotheprovidedscrews,youwillalsofindamagneticpadwithadhesivebackingthatyoucanattachtotheholderandthenadheretheholdertometalsurfaceseasily.

1. Cleanthebackoftheholderwithamildcleanseroralcohol.

2. Removetheprotectionfromtheadhesivepadonthemagnetandplacethemagnetonthebackoftheholder

3. Placetheholderandmagnetdownonaflatsurfaceandpressdownstronglyfor30secondstofirmlyattachthemagnet.

Page 15: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

ExternalSmartSensors

TemptimeLoRaWanenabledsolution EDGEW-200module Page15

4 ExternalSmartSensors

TheproceduresdescribedinthisdocumentassumethatyourEDGELoRaGatewayreceiverisupandrunning,andthatyouhavecreatedanaccountontheEDGEConnectwebapplication(withavouchertoauthorizeCloudaccess).ThissectionfocusesonthephysicalaspectsoftheEDGEW-200module.

ThisimageshowsaEDGEW-200modulewithanexternalPT100sensor,connectedviaEDGESmartSensortechnology.

Figure4–EDGEW-200wirelessmodulewithPT100sensor

4.1 ConnectingSmartSensors™TheEDGEW-200moduleandexternalPT100sensors(anddualtemperature/humiditysensors)providedbyTemptimeareindependentofeachotherwithrespecttocalibration.Acalibratedexternalsensorstoresitsowncalibrationparametersdirectly,andthuscanbeusedwithanyEDGEW-200module.

EDGEW-200moduleswithsupportforexternalsensorsuseaspeciallydesignedTemptimeSmartSensortechnologythatoffersseveralkeyadvantageswithrespecttoconventionalsolutions:

• CalibrationcorrectionparametersarestoreddirectlyintheSmartSensor

• Plugandplayfunctionalitywithnospecialconfigurationonyourpart

• Moduleindependencefromsensortype:anysupportedTemptimesensorcanbeusedwithanygivenEDGEW-200module,simplifyingrepairs,swaps/standardexchange,andcalibrationcycles

Page 16: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

ExternalSmartSensors

TemptimeLoRaWanenabledsolution EDGEW-200module Page16

(Note:ifyouchangethesensoronafunctioningEDGEW-200module,youmustreconfigurethemoduleontheserver-sideusingtheEDGEConnectWebapplication.)

Figure5–ConnectingyourEDGEW-200wirelessmodulewithanexternalsensor

Thisfeatureoffersaneffectivewaytohandlesensorsatcalibrationtime(dependingonyourstandardoperatingprocedure)withoutleavingyourequipmentunattended.Simplyhaveacalibratedsensoron-handandswapitwiththeonethatneedscalibration.

Insert the cable from your module into the keyed plug on the EDGE Smart Sensor connector.

Page 17: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

ExternalSmartSensors

TemptimeLoRaWanenabledsolution EDGEW-200module Page17

4.2 PlacingSmartSensors™

4.2.1 Generalnoteaboutsensorplacement

• GiventheextremetemperaturerangestypicallyhandledbyPT100sensors,pleasebesuretousethePT100-compatiblemountingsystemprovidedwithyourfreezer,oven,nitrogentank,orotherequipment.

Asmentionedearlier,theEDGEwirelessmonitoringsystemsupportsthreedifferentPT100temperaturesensors,eachdesignedforadifferentapplicationandtemperaturerange.PlacementofyourPT100sensor(s)dependsontheequipmentyouintendtomonitor,asdescribedbelow.

Inallcasesdescribedinthissection,theplasticconnectorjoiningthemoduleandthesensormustbeinthesametemperaturespaceasthemodule,notthesensor.

Note WhenroutingthecableforanyEDGEsensor,avoiddirectcontactwithorcloseproximityplacementofthesensorcablingwithanyhighvoltagewiring.Cablingshouldbeplacedwithnolessthanaminimumof5cm(2inches)distancefromhighvoltagecomponents.Also,avoidrunningthesensorcableinparallelwithhighvoltagewiring.

Yourequipmentmaybedifferentthanthatdescribedhere.Contactthemanufacturerofyourequipmentforinstructionsregardingproperplacementofthesensor.

4.2.2 PT100:-100°Cto+150°C

WheninstallingaPT100sensorinanultra-low-temperature(ULT)freezer,itiseasiesttoproceedwithathawedfreezer.

Whenpossible,routethesensorthroughthesameaccessportusedbytheunitcontrolsensororanaccessoryport,suchasthatshownbelowinFigure6.

WhenroutingthePT100sensorthroughthesameportusedbythecontrolsensor,Temptimerecommendsinstallingthesensoronlyafterthefreezerhasreachedathawedstate.

Tonegatethepossibilityofcondensationdrippingontheelectronics,avoidroutingthecableincloseproximitytoanyelectricalenclosures.

MountthePT100sensorasclosetotheunitcontrolsensoraspossible.Whenpossible,werecommendmountingthesensorwithin5cm(2inches)ofthecontrolsensor.

WhenmountingthePT100sensor,avoiddirectcontactwiththewallofthefreezer.Thiswillensurethesensorismountedtopermitmeasurementofairtemperatureonly.

Page 18: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

ExternalSmartSensors

TemptimeLoRaWanenabledsolution EDGEW-200module Page18

WedonotrecommendinstallingthesensorthroughthedoorgasketonaULTfreezer.Thisleadstoexcessiveicebuild-upandpossibledoordamageaswellaslongercompressorruntimesthatmayresultinothermechanicalproblems.

Theorangecable,whichsupportstemperaturesfrom-200°Cto+50°C,maybeplacedinsidethefreezer.Makesureyouattachthesensorusingtheprovidedcable-tiesandresealanyopeningsyoumayhaveunsealedtoinsertthesensorusingpermagumsealant.

Figure6–SamplePT100(-100°Cto+150°C)forULTfreezer

Page 19: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

ExternalSmartSensors

TemptimeLoRaWanenabledsolution EDGEW-200module Page19

4.2.3 PT100:-200°Cto+50°C

PT100sensorsforLN2/cryogenictanksmustbemounted,whenapplicable,incloseproximitytotheunitdisplaysensor.

Toavoidtemperaturemeasurementdisappearances,Temptimerecommendsmountingthesensoratthesameheightasthedisplaysensor.

Asanexample,somefreezershaveanaccesspanelonthebackoftheunitinwhichyoumayroutethesensorcableupthebackwall.Placethecableunderthetankgasketutilizingthenotchatthe12o’clockposition.Werecommendtheinstallationofpermagumsealantwherethecablepassesthroughthenotch.

Dependingonwhetherstoringinvapororliquidphase,placethesensoratadepthsuitableforpropertemperaturemonitoring.

Figure7–PT100(-200°Cto+50°C)fornitrogen/cryogenictank

Page 20: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Externaldigitalsensors

TemptimeLoRaWanenabledsolution EDGEW-200module Page20

5 Externaldigitalsensors

ThisimageshowsaEDGEW-200modulewithanexternaldigitalsensor.

Figure8–EDGEW-200modulewithexternaldigitalsensor(optionalcablelengths)

Dependingonthedesignofthespacetobemonitored,youmaybeabletopassthesensorthroughanaccessportoropening.Werecommendthatyouusetheaccessportoropeningifoneisavailable.

1. Wheninstallationpermitsroutingthesensorcablingthroughanaccessportoropening,connectthemaleendofthesensorfirmlyintothefemaleendoftheEDGEwirelessmodule.

2. Wheninstallationrequirespassagethroughthedoorgasketseal,connectthemaleendofthesensorintothefemaleendoftheprovidedflatcableadaptorbyjoiningtheconnectors(withoutunscrewingthem).ThenconnecttheotherendoftheflatcableintotheendoftheEDGEwirelessmodule.

ExternaldigitalsensorsdonotconnecttomodulesviatheEDGESmartSensorsolution.Therefore,calibrationparametersmustbemanagedusingtheEDGEConnectwebapplicationandEDGEConnectMobileapplicationforuploadthemtothemodule.

Page 21: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Externaldigitalsensors

TemptimeLoRaWanenabledsolution EDGEW-200module Page21

5.1 ConnectingthesensorSimplyjointhesensorcabletothemodulecableasshownhere:

Figure9–EDGEW-200modulewithexternaldigitalsensor(optionalcablelengths)

5.2 Placingthesensor1. IfyouhaveanEDGEmodulewithoneormoreexternalsensors,thebestsolutionistousethe

accessportoropeningtoinsertthesensor(s).Otherwise,runthetemperaturesensorintotheenclosureviathedoorjoint,takingcaretoplacetheflatcableflushwiththejoint.

Installationthroughthedoorgasketonfreezersmaycauseicebuild-upinsidethefreezerand/oronthefreezerdoor.Thismayresultindamagetothefreezerdoorifnotproperlymaintained.Whenusedwithincubators,useoftheflatcablemaycausecondensation,whichcouldpotentiallyincreasetheriskofcontamination.

2. Cleanthesurfaceforthesensorusingalcoholtoremoveanygreaseordirt.

3. Attachoneoftheplasticcableholderstothesensor,removetheprotectivestripfromtheadhesive,andplacetheholderonthecleanspotinsidetheenclosure.

Insert the cable from your module into the keyed plug on the sensor connector.

Page 22: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Externaldigitalsensors

TemptimeLoRaWanenabledsolution EDGEW-200module Page22

4. Placethesensor/flatribboncableconnectorontheinsideofthechamberinthesamemanner,asshownhere:

Figure10–Sensorinsiderefrigeratorchamber(moduleswithexternalsensoronly)

5. Yourmountingkitincludesaplasticholderthatcanbemountedusingtheprovidedmagnet,screwsorVelcro®.ChoosethemethodthatismostappropriateforyoursituationandplacetheEDGEmoduleasdescribedinsection3.6PlacingyourEDGEmoduleforbestwirelessperformance.

6. Forexample:

Figure11–EDGEmodulemountedontherefrigeratordoor

7. Attachorcoiltheexcesscableneatly.

Page 23: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Internalsensor

TemptimeLoRaWanenabledsolution EDGEW-200module Page23

6 Internalsensor

EDGEW-200moduleswithintegratedtemperaturedonothaveacableprotrudingfromthesideofthemodule,andyoudonothavetoconnectasensoryourself.

Figure12–Modulewithinternaltemperaturesensor

6.1 PlacingmoduleswithaninternalsensorDependingonyourrefrigeratororfreezermodel,itmaybebettertoleavethemodulesittingonashelfinsidethechamberratherthanstickingittoasidewall.

Thisisparticularlyrelevantwhenyouhavecarriedoutamappingstudyanddeterminedtheideallocationforthesensor.Inthatcase,makesurethatthesensordoesnotinterferewithloadingandunloadingyourproduct(s)andthatthelocationdoesnotrepresentariskforeitheryourproduct(s)orthesensor.

LCD display with module name, temperature, signal and battery indicators

Push-button

Page 24: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Temperature/humiditySmartSensors™

TemptimeLoRaWanenabledsolution EDGEW-200module Page24

7 Temperature/humiditySmartSensors™

Figure13–Dualtemperature&humiditysensor

TheEDGEW-200wirelesshumidity/temperaturemodulemonitorsbothrelativehumiditylevelsandtemperature.Thismoduleisgenerallyusedinvarioustypesofstorage,medicalandtraceabilityapplications.Thewhitesensorshownabovecontainsboththehumidityandtemperaturesensor.

ThissensorconnectsviatheEDGESmartSensorconnector,andthuswillcontaincalibrationparametersdirectlyifthesensorwascalibratedbyTemptime.

7.1 ConnectingthesensorConnect the sensor and wireless module by joining the connectors.

Insertsensor

connectorRotateringtolockintoplace

LCD display with module name, temperature, humidity, signal and battery indicators

Push-button Temptime Smart Sensor connector for external sensors

Page 25: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Temperature/humiditySmartSensors™

TemptimeLoRaWanenabledsolution EDGEW-200module Page25

Figure14–Alignandpressfirmlytojoinconnectors

7.2 PlacingthesensorMounttheEDGEmoduleinthedesiredlocationusingtheprovidedplasticholder,whichyoumayattachusingamagnetorVelcro®tape.ChoosethemethodthatworksbestforyourlocationandplacetheEDGEW-200moduleasdescribedearlierin3.6PlacingyourEDGEmoduleforbestwirelessperformance.Usetheprovidedplasticcableholderstoattachorcoiltheexcesscableneatly.

WhenroutingthecablefortheEDGEsensor,avoiddirectcontactwithorcloseproximityplacementofthesensorcablingwithanyhighvoltagewiring.Cablingshouldbeplacedwithnolessthanaminimumof5cm(2inches)distancefromhighvoltagecomponents.Also,avoidrunningthesensorcableinparallelwithhighvoltagewiring.

Forallothermanufacturers’equipment,contactthemanufactureroftheinstrumentforinstructionsregardingproperplacementofthesensor.

Page 26: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

ActivatingtheEDGEW-200module

TemptimeLoRaWanenabledsolution EDGEW-200module Page26

8 ActivatingtheEDGEW-200module

ThissectionassumesthatyourEDGELoRaWAN™receiverisupandrunningandwithinwirelessrangeoftheEDGEW-200moduleyouaretryingtoconnect.

TheEDGEW-200temperature/humiditymodulerunsonbatterypower.ToactivateyourEDGEW-200moduleandenableittocommunicateviayourEDGEGatewayreceiverandtheCloud,followthesesteps:

1. Inserttheprovidedbattery,ifnotalreadyinstalled,makingsuretorespectthepolarity(seeimageprintedinsidebatteryslot).Werecommendthatyouuseamanualscrewdriver,beingcarefulnottoover-tightenthescrews.

Figure15–Removethebackcoverandinsertbattery

2. Waitduringthebootsequence,whilethedevicedisplaysvariousinformation,suchastheserialnumber,etc.

3. Oncethebootiscomplete,pressthepushbuttononthefrontoftheEDGEW-200module.4. Ifareceiveriswithinwirelessrange,themoduleestablishesthewirelessconnection

automaticallyandACK_Receivedisdisplayedonthescreen.

è

5. SeeEDGEConnectandEDGEConnectMobiledocumentationformoredetailsonactivationandsettings.

Page 27: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

ActivatingtheEDGEW-200module

TemptimeLoRaWanenabledsolution EDGEW-200module Page27

8.1 RefreshingthemoduledisplaywithashortpressYoumayrefreshtheEDGEW-200displaywiththelatestsensorreadingsbyperformingashortpressonthemodule’spushbutton.Pressthebuttonbrieflytoupdateandviewthecurrentreading.

Page 28: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Appendix-Troubleshooting

TemptimeLoRaWanenabledsolution EDGEW-200module Page28

9 Appendix-Troubleshooting

Ifyouarehavingdifficultieswithyourconfiguration,lookatthesefrequentlyaskedquestionsbeforecontactingtechnicalsupport.

ThereisnothingdisplayedontheEDGEmodulescreen.WhatshouldIdo?First,checktomakesurethebatteryisinstalledandthatitisinsertedintherightdirection(+/-accordingtotheimageinthebatteryslot).Trytestingtheunitwithabatterythatisknowntobeofthecorrectsizeandvoltage(3.6VLithium,3600mA).ContacttechnicalsupportifthebatteryisOKandstillnothingisdisplayedonthescreen.

Ipressthebuttonfor3secondsbutmyEDGEW-200moduledoesnotconnecttomyreceiver;whatshouldIdo?Ifyourmoduledisplays“ACK_NOT_RECEIVED”insteadof“ACK_RECEIVED”whenyoupressthebutton,trybringingthemoduleclosertoyourreceiverforabetterwirelessconnection.Also,checktomakesurethereceiverisworkingproperly.

TheEDGEmoduleisproperlyconnectedtotheCloud.Whydon’tIgetanytemperaturereadings?Thisisusuallyduetoaloosecableorimproperlyconnectedtemperaturesensor.CheckthecablebetweentheEDGEmoduleandthesensor.Unplugthesensorandplugitbackin.Makesuretherearenoexposedwires.Tryadifferentsensor.

Canexternalsensorsbesubmergedinglycol?Yes,forallmetal-tippedsensors,butnotthedualtemperature/humiditysensor(withthewhiteTeflon/PTFEcasing).To“absorb”suddenvariationsintemperature,suchasthosecausedbyopeningandclosingthechamberdoor,youmaysubmergethemetalpartofthesensoringlycolorglycerol.Thislimitsinconsequentialtemperaturevariationsrecordedbythesensor.Checkyourlaboratory’sQualityguideforrecommendationsandmakesuretouseavolumeofglycolthatcorrespondstothevolumeofproduct(s)youaremonitoring.Toachievethesameresults,youmayalsodelaythetransmissionofalarmsviathesoftwareandleavethesensorsexposed.

Page 29: EDGE W-200 Module User Guide-rev2 · EDGE Smart Sensor connector for external sensors. Getting started ... Long-range wireless connectivity enables EDGE W-200 modules to be placed

Index

TemptimeLoRaWanenabledsolution EDGEW-200module Page29

10 Index

ACK_NOT_RECEIVED,12,28ACK_RECEIVED,12,13,28Battery,2,9,26,28Cloudconnectivity,10EDGEConnectMobile,6,10,20,26EDGEConnect,6,13,15,16,20,26