8
Description Cast resin, 50 Hz , three-phased distribution transformers with the following characteristics: Indoor use / Outdoor use with properly designed enclosure Thermal class F - Temperature rise 100 K Ambient 40 °C, altitude 1000 m MV windings encapsulated in cast resin Pre-impregnated LV windings Natural air cooling system (AN type) Core and frame covered with protective coating Standard These transformers comply with standards: IEC 60076-11, PrEN 50588 Ecodesign Directive EU 548-2014 Schneider Electric guarantees that its transformers are: C3* Climatic class E3 Environment class according to IEC 60076-16 F1 Fire behaviour class Almost partial discharge free - Acceptance level: - 10 pC Routine Test - 5 pC Special Test according to IEC 60076 standard * C2 Thermal shock test carried out at -50°C Standard fittings Trihal without enclosure (IP00): HV voltage variation by off circuit tapping links 4 bi-directional flat rollers 4 lifting holes 4 haulage holes on the underbase 2 earthing points 1 rating plate (on HV side) Trihal with IP31 metal enclosure (except underframe IP21): - 2 lifting lugs for transformer and enclosure assembly - 1 earthing point on enclosure - access to HV tapping by removing a bolted panel - enclosure final colour RAL9002 Ecodesign regulation EU 548-2014 Maximal Loss levels Statement on Loss tolerences: - No tolerance on transformer design - 5% tolerance for end user checks Additional data requested on the name plates - Loss level and measured values - Type and weight of mail materials used - CE Marking is MANDATORY Dry Type Transformers maximum loss levels according to Ecodesign: Insulation voltage MV 24 kV & LV 1.1 kV - A0Bk up to 630 kVA - A0Ak over 630 kVA Insulation voltage: MV 36 kV & LV 1.1 kV - A0 +15% Bk +10% 630 kVA - A0 +15% Ak +10% > 630 kVA Trihal - up to 3 150 kVA Cast Resin Transformers 01 A k C k B k A 0 eco design

Ecodesitrgn Trihal Final

Embed Size (px)

DESCRIPTION

dry type transformer for trihal

Citation preview

  • Description

    Cast resin, 50 Hz , three-phased distribution transformers with the following characteristics:Indoor use / Outdoor use with properly designed enclosure Thermal class F - Temperature rise 100 K Ambient 40 C, altitude 1000 m MV windings encapsulated in cast resin Pre-impregnated LV windings Natural air cooling system (AN type) Core and frame covered with protective coating

    Standard

    These transformers comply with standards: IEC 60076-11, PrEN 50588 Ecodesign Directive EU 548-2014Schneider Electric guarantees that its transformers are: C3* Climatic class E3 Environment class according to IEC 60076-16 F1 Fire behaviour class Almost partial discharge free - Acceptance level: - 10 pC Routine Test

    - 5 pC Special Test according to IEC 60076 standard

    * C2 Thermal shock test carried out at -50C

    Standard fittings

    Trihal without enclosure (IP00): HV voltage variation by off circuit tapping links 4 bi-directional flat rollers 4 lifting holes 4 haulage holes on the underbase 2 earthing points 1 rating plate (on HV side)

    Trihal with IP31 metal enclosure (exceptunderframe IP21): - 2 lifting lugs for transformer and enclosure assembly - 1 earthing point on enclosure - access to HV tapping by removing a bolted panel - enclosure final colour RAL9002

    Ecodesign regulation EU 548-2014

    Maximal Loss levels Statement on Loss tolerences: - No tolerance on transformer design - 5% tolerance for end user checks Additional data requested on the name plates - Loss level and measured values - Type and weight of mail materials used - CE Marking is MANDATORY Dry Type Transformers maximum losslevels according to Ecodesign:

    Insulation voltage MV 24 kV & LV 1.1 kV - A0Bk up to 630 kVA - A0Ak over 630 kVA Insulation voltage: MV 36 kV & LV 1.1 kV - A0 +15% Bk +10% 630 kVA - A0 +15% Ak +10% > 630 kVA

    Trihal - up to 3 150 kVACast Resin Transformers 01

    Ak

    Ck

    Bk

    A0

    ecodesign

  • 2

    015

    Sch

    neid

    er E

    lect

    ric. A

    ll rig

    hts

    rese

    rved

    .

    NRJED315631EN

    02Cast Resin Transformers

    02 2015

    2

    015

    Sch

    neid

    er E

    lect

    ric. A

    ll rig

    hts

    rese

    rved

    .

    Trihal - 7.2 kV and 12 kV A0AkCast Resin Transformers

    02 2015

    Trihal IP00

    Dimensions and weights without enclosure housing (IP00)Dimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions aredifferent (consult us).

    D

    M

    C

    ED

    I

    A

    earthingterminal

    tapping links

    J J L

    E/2

    B

    125 (160)

    40 (50)

    H

    13

    Trihal IP31

    Dimensions and weights with IP31 metal enclosureDimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    D

    C

    BD

    I

    A

    earthingterminal

    125 (160)

    40 (50)

    13

    tappinglinks

    Electrical characteristicsRated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50

    Primary voltage (V) 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000 10000

    Isolation level (kV) 12 12 12 12 12 12 12 12 12 12 12 12

    Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400

    Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

    Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn

    Losses (W) - no-load losses 520 620 750 900 1100 1300 1550 1800 2200 2600 3100 3800

    Losses (W) - load losses at 120C 3400 3900 4500 5630 7100 8000 9000 11000 13000 16000 19000 22000

    Rated impedance voltage (%) 6 6 6 6 6 6 6 6 6 6 6 6

    Max altitude (m) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

    Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40

    Nature of HV/LV windings AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI AI/AI

    Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Dimensions (mm) - Lenght A 1290 1350 1370 1420 1500 1530 1620 1700 1830 1880 2050 2330

    - Width B 680 800 800 800 800 800 950 950 950 1230 1230 1270

    - Height C 1340 1430 1510 1550 1570 1720 1880 1940 2140 2220 2250 2680

    - Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

    - Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

    - Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

    - Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

    Weight without enclosure (kg) 1180 1400 1600 1780 2080 2400 3020 3600 4180 5160 6240 10060

    Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Dimensions (mm) - Lenght A 1650 1700 1800 1800 1800 1900 2150 2150 2130 2180 2350 2630

    - Width B 950 1020 1020 1020 1020 1100 1170 1170 980 1230 1230 1270

    - Height C 1750 1900 2050 2050 2050 2480 2480 2480 2440 2620 2650 3080

    - Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

    - Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

    - Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

    - Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

    Weight with enclosure (kg) 1340 1580 1790 1870 2270 2620 3320 3900 4470 5470 6565 10470

  • 2

    015

    Sch

    neid

    er E

    lect

    ric. A

    ll rig

    hts

    rese

    rved

    .

    NRJED315631EN

    03Cast Resin Transformers

    02 2015

    Trihal - 7.2 kV and 12 kV A0Bk

    Trihal IP31

    Dimensions and weights with IP31 metal enclosureDimensions and weights are for guidance only, and are provided for a single-voltagetransformer with the following HV insulation lev-els and low voltages. Only the definitive drawings following from the order will commit us contrac-tually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    D

    C

    BD

    I

    A

    earthingterminal

    125 (160)

    40 (50)

    13

    tappinglinks

    Trihal IP00

    Dimensions and weights withoutenclosure housing (IP00)Dimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    D

    M

    C

    ED

    I

    A

    earthingterminal

    tapping links

    J J L

    E/2

    B

    125 (160)

    40 (50)

    H

    13

    Electrical characteristicsRated power (kVA) 250 315 400 500 630

    Rated frequency (Hz) 50 50 50 50 50

    Primary voltage (V) 10000 10000 10000 10000 10000

    Isolation level (kV) 12 12 12 12 12

    Secondary voltage at no-load (V) 400 400 400 400 400

    Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

    Vector groups Dyn Dyn Dyn Dyn Dyn

    Losses (W) - no-load losses 520 623 750 900 1100

    Losses (W) - load losses at 120C 3800 4550 5500 6425 7600

    Rated impedance voltage (%) 6 6 6 6 6

    Max altitude (m) 1000 1000 1000 1000 1000

    Max ambiental temperature (C) 40 40 40 40 40

    Nature of HV/LV windings AI/AI AI/AI AI/AI AI/AI AI/AI

    Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630

    Dimensions (mm) - Lenght A 1270 1290 1320 1370 1410

    - Width B 680 800 800 800 800

    - Height C 1340 1410 1510 1530 1660

    - Roller pitch D 520 670 670 670 670

    - Frame width E 645 795 795 795 795

    - Roller diam. F 125 125 125 125 125

    - Roller width G 40 40 40 40 40

    Weight without enclosure (kg) 1140 1260 1460 1640 1880

    Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630

    Dimensions (mm) - Lenght A 1650 1700 1800 1370 1900

    - Width B 950 1020 1020 800 1100

    - Height C 1750 1900 2050 1530 2300

    - Roller pitch D 520 670 670 670 670

    - Frame width E 645 795 795 795 795

    - Roller diam. F 125 125 125 125 125

    - Roller width G 40 40 40 40 40

    Weight with enclosure (kg) 1300 1440 1650 1830 2100

  • 2

    015

    Sch

    neid

    er E

    lect

    ric. A

    ll rig

    hts

    rese

    rved

    .

    NRJED315631EN

    04Cast Resin Transformers

    02 2015

    Trihal - 17.5 kV and 24 kV A0Ak

    Electrical characteristics for insulation levelRated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50

    Primary voltage (V) 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000 2000

    Isolation level (kV) 24 24 24 24 24 24 24 24 24 24 24 24

    Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400

    Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

    Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn

    Losses (W) - no-load losses 520 620 750 900 1100 1300 1550 1800 2200 2600 3100 3800

    Losses (W) - load losses at 120C 3400 3900 4500 5630 7100 8000 9000 11000 13000 16000 19000 22000

    Rated impedance voltage (%) 6 6 6 6 6 6 6 6 6 6 6 6

    Max altitude (m) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000

    Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40

    Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Dimensions (mm) - Lenght A 1720 1800 1900 1900 1900 1900 2150 2140 2250 2360 2450 2720

    - Width B 990 1020 1100 1100 1100 1100 1170 1130 1170 1230 1230 1270

    - Height C 1730 2050 2300 2300 2300 2300 2480 2440 2480 2680 2900 3060

    - Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

    - Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

    - Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

    - Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

    Weight with enclosure (kg) 1360 1590 1820 2000 2220 3060 3140 3810 4530 5495 6560 8970

    D

    M

    C

    ED

    I

    A

    earthingterminal

    tapping links

    J J L

    E/2

    B

    125 (160)

    40 (50)

    H

    13

    Trihal IP00

    Dimensions and weights withoutenclosure housing (IP00)Dimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    D

    C

    BD

    I

    A

    earthingterminal

    125 (160)

    40 (50)

    13

    tappinglinks

    Trihal IP31

    Dimensions and weights with IP31 metal enclosureDimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Dimensions (mm) - Lenght A 1320 1365 1410 1460 1480 1630 1660 1740 1850 1960 2050 2320

    - Width B 730 810 820 830 830 850 950 950 970 1230 1230 1270

    - Height C 1430 1520 1600 1640 1770 1810 1970 2140 2180 2280 2500 2660

    - Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

    - Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

    - Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

    - Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

    Weight without enclosure (kg) 1180 1400 1600 1780 2000 2840 2840 3460 4180 5120 6160 8520

  • 2

    015

    Sch

    neid

    er E

    lect

    ric. A

    ll rig

    hts

    rese

    rved

    .

    NRJED315631EN

    05Cast Resin Transformers

    02 2015

    Trihal - 17.5 kV and 24 kV A0Bk

    Insulation level: 17.5 kV and 24 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630

    Dimensions (mm) - Lenght A 1300 1330 1360 1430 1480

    - Width B 730 810 810 820 830

    - Height C 1430 1520 1600 1640 1790

    - Roller pitch D 520 670 670 670 670

    - Frame width E 645 795 795 795 795

    - Roller diam. F 125 125 125 125 125

    - Roller width G 40 40 40 40 40

    Weight without enclosure (kg) 1140 1360 1520 1720 2040

    Electrical characteristics for insulation levelRated power (kVA) 250 315 400 500 630

    Rated frequency (Hz) 50 50 50 50 50

    Primary voltage (V) 20000 20000 20000 20000 20000

    Isolation level (kV) 24 24 24 24 24

    Secondary voltage at no-load (V) 400 400 400 400 400

    Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

    Vector groups Dyn Dyn Dyn Dyn Dyn

    Losses (W) - no-load losses 520 620 750 900 1100

    Losses (W) - load losses at 120C 3800 4550 5500 6425 7600

    Rated impedance voltage (%) 6 6 6 6 6

    Max altitude (m) 1000 1000 1000 1000 1000

    Max ambiental temperature (C) 40 40 40 40 40

    D

    M

    C

    ED

    I

    A

    earthingterminal

    tapping links

    J J L

    E/2

    B

    125 (160)

    40 (50)

    H

    13

    Trihal IP00

    Dimensions and weights withoutenclosure housing (IP00)Dimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    D

    C

    BD

    I

    A

    earthingterminal

    125 (160)

    40 (50)

    13

    tappinglinks

    Trihal IP31

    Dimensions and weights with IP31 metal enclosureDimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    Insulation level: 7.2 kV and 12 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630

    Dimensions (mm) - Lenght A 1650 1700 1800 1370 1900

    - Width B 950 1020 1020 800 1100

    - Height C 1750 1900 2050 1530 2300

    - Roller pitch D 520 670 670 670 670

    - Frame width E 645 795 795 795 795

    - Roller diam. F 125 125 125 125 125

    - Roller width G 40 40 40 40 40

    Weight with enclosure (kg) 1300 1440 1650 1830 2100

  • 2

    015

    Sch

    neid

    er E

    lect

    ric. A

    ll rig

    hts

    rese

    rved

    .

    NRJED315631EN

    06Cast Resin Transformers

    02 2015

    Trihal - 36 kV A0Ak

    D

    C

    BD

    I

    A

    earthingterminal

    125 (160)

    40 (50)

    13

    tappinglinks

    Trihal IP31

    Dimensions and weights with IP31metal enclosureDimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    D

    M

    C

    ED

    I

    A

    earthingterminal

    tapping links

    J J L

    E/2

    B

    125 (160)

    40 (50)

    H

    13

    Trihal IP00

    Dimensions and weights withoutenclosure housing (IP00)Dimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    Insulation level: up to 36 kV - low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Dimensions (mm) - Lenght A 1990 1990 2030 2030 2080 2240 2310 2370 2450 2780 3000 3340

    - Width B 1220 1220 1230 1240 1250 1310 1330 1350 1380 1490 1560 1670

    - Height C 2090 2090 2250 2250 2290 2460 2530 2720 2760 3030 3110 3150

    - Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

    - Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

    - Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

    - Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

    Weight with enclosure (kg) 1890 1895 2200 2245 2500 3260 3740 4320 5060 7650 9760 13760

    Insulation level: up to 36 kV - low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Dimensions (mm) - Lenght A 1490 1490 1530 1530 1580 1740 1810 1870 1950 2280 2500 2840

    - Width B 800 870 880 880 890 920 1000 1010 1030 1230 1260 1340

    - Height C 1790 1790 1950 1950 1990 2160 2230 2420 2460 2630 2710 2750

    - Roller pitch D 520 670 670 670 670 670 820 820 820 1070 1070 1070

    - Frame width E 645 795 795 795 795 795 945 945 945 1195 1195 1195

    - Roller diam. F 125 125 125 125 125 125 125 125 125 160 160 200

    - Roller width G 40 40 40 40 40 40 40 40 40 50 50 70

    Weight without enclosure (kg) 1660 1660 1960 2000 2240 2960 3420 3980 4700 7220 9260 13180

    Electrical characteristics for insulation level: up to 36 kVARated power (kVA) 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150

    Rated frequency (Hz) 50 50 50 50 50 50 50 50 50 50 50 50

    Primary voltage (V) 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000 30000

    Isolation level (kV) 36 36 36 36 36 36 36 36 36 36 36 36

    Secondary voltage at no-load (V) 400 400 400 400 400 400 400 400 400 400 400 400

    Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

    Vector groups Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn Dyn

    Losses (W) - no-load losses 598 712 862 1037 1265 1495 1782 2070 2530 2990 3565 4370

    Losses (W) - load losses at 120C 3740 4264 4950 6193 7810 8800 9900 12100 14300 17600 20900 24200

    Rated impedance voltage (%) 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5 6.5

    Max ambiental temperature (C) 40 40 40 40 40 40 40 40 40 40 40 40

  • 2

    015

    Sch

    neid

    er E

    lect

    ric. A

    ll rig

    hts

    rese

    rved

    .

    NRJED315631EN

    07Cast Resin Transformers

    02 2015

    Trihal - 36 kV A0Bk

    D

    M

    C

    ED

    I

    A

    earthingterminal

    tapping links

    J J L

    E/2

    B

    125 (160)

    40 (50)

    H

    13

    Trihal IP00

    Dimensions and weights withoutenclosure housing (IP00)Dimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    D

    C

    BD

    I

    A

    earthingterminal

    125 (160)

    40 (50)

    13

    tappinglinks

    Trihal IP31

    Dimensions and weights with IP31 metal enclosureDimensions and weights are for guidance only, and are provided for a single-voltage transformer with the following HV insulation levels and low voltages. Only the definitive drawings following from the order will commit us contractually. For other voltages, impedance voltages and dual-voltages, weights and dimensions are different (consult us).

    Insulation level: up to 36 kV- low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630

    Dimensions (mm) - Lenght A 1990 1970 1970 2000 2070

    - Width B 1220 1220 1220 1230 1250

    - Height C 2090 2090 2110 2250 2290

    - Roller pitch D 520 670 670 670 670

    - Frame width E 645 795 795 795 795

    - Roller diam. F 125 125 125 125 125

    - Roller width G 40 40 40 40 40

    Weight with enclosure (kg) 1885 1870 2040 2165 2480

    Insulation level: up to 36 kV low voltage 400 V to 433 VRated power (kVA) 250 315 400 500 630

    Dimensions (mm) - Lenght A 1490 1470 1470 1500 1570

    - Width B 800 870 870 880 890

    - Height C 1790 1790 1810 1950 1990

    - Roller pitch D 520 670 670 670 670

    - Frame width E 645 795 795 795 795

    - Roller diam. F 125 125 125 125 125

    - Roller width G 40 40 40 40 40

    Weight without enclosure (kg) 1660 1640 1800 1920 2220

    Electrical characteristics for insulation levelRated power (kVA) 250 315 400 500 630

    Rated frequency (Hz) 50 50 50 50 50

    Primary voltage (V) 30000 30000 30000 30000 30000

    Isolation level (kV) 36 36 36 36 36

    Secondary voltage at no-load (V) 400 400 400 400 400

    Tappings (%) +/- 5 +/- 5 +/- 5 +/- 5 +/- 5

    Vector groups Dyn Dyn Dyn Dyn Dyn

    Losses (W) - no-load losses 598 712 862 1037 1265

    Losses (W) - load losses at 120C 4180 4990 6050 7054 8360

    Rated impedance voltage (%) 6.5 6.5 6.5 6.5 6.5

    Max ambiental temperature (C) 40 40 40 40 40

  • 2

    015

    Sch

    neid

    er E

    lect

    ric. A

    ll rig

    hts

    rese

    rved

    .

    NRJED315631EN

    08Cast Resin Transformers

    02 2015

    The contrator must ensure that cables and busbars are adequately supported to prevent mechanical stresses from being imposed on the transformer terminals, busbars or bushings.

    Connections - Trihal transformers without enclosure housing (IP00)The winding resin coating and the plug-inconnectors dont ensure any protection against touch when the transformer is energized. The contrator must ensure that cables and busbars are adequately supported to preventmechanical stresses from being imposed on the transformer terminals, busbars or bushings.

    120

    mini

    cable support

    HVLV n

    120

    mini

    HV and LV standard connection

    X

    X

    X

    X

    LV

    HV

    SM

    1000

    19

    SM

    1000

    18

    Insulation (kV)

    Dimension X (mm)

    Full wall Grid wall

    7.5 90 300

    12 120 300

    17.5-24 220 300

    Minimum clearances required

    Minimum clearances required HV and LV standard connection

    200 mm

    500 mm*

    200

    mm

    200

    mm

    LV

    HV

    HVn

    cab

    le s

    upp

    ort

    cab

    le s

    upp

    ort

    LV

    Connections -Trihal transformers withIP31 metal enclosure

    SM

    1000

    21

    SM

    1000

    20

    LV terminations HV terminations

    40

    14

    1533

    3380

    4 x 14

    23.5

    33

    50100

    4 x 14

    2550

    80 40160

    4 x 16

    3550

    3370

    4 x 14

    23.5

    33

    160 to 400 kVA*thickness 5

    500 to 800 kVA*thickness 6

    1600 kVA*thickness 12

    2000 kVA* thickness 10

    1000 to 1250 kVA*thickness 10

    *Valid for aluminium terminations.

    2500 kVA* thickness 2u10

    50

    13

    SM

    1000

    23

    SM

    1000

    22

    2014 Schneider Electric. All trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. 998-1247929_GMA-GB