14
ECLYPSE™Connected Terminal Unit Controller Overview The ECLYPSE Connected Terminal Unit Controller is designed to control terminal units such as fan coil units, chilled beams, ceilings, and heat pumps. It integrates a control, automation and connectivity server, a power supply, and dedicated I/Os in one convenient package. Each model supports BACnet/IP communication and is listed as a BACnet Building Controller (B- BC). These products feature wired and wireless advanced IP connectivity for efficient and reliable installation. The Connected Terminal Unit Controller comes with an embedded web server that enables web-based application configuration and an HTML5 visualization interface. It also features embedded scheduling, alarming, and logging. Control logic and graphic user interface can be customized as required for the application. Moreover, as part of the Smart Room Control solution, these controllers can control lighting fixtures (DALI, ON/OFF, dimming) and shades/ sunblind motors (24 VDC or 100-240 VAC, up/ down and angle rotation) through additional expansion modules. Applications £ Fan coil units £ Chilled beams £ Reversible ceilings with 6-way valves £ Heat pumps £ Smart Room Control solution Moreover, these HVAC applications can support different configurations (4 pipe, 2 pipe, ...) and different valve and actuator types (on/off, thermal, floating, 0-10 V, ...). Datasheet

ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

ECLYPSE™Connected Terminal UnitController

OverviewThe ECLYPSE Connected Terminal UnitController is designed to control terminal unitssuch as fan coil units, chilled beams, ceilings,and heat pumps.It integrates a control, automation andconnectivity server, a power supply, anddedicated I/Os in one convenient package.Each model supports BACnet/IP communicationand is listed as a BACnet Building Controller (B-BC).These products feature wired and wirelessadvanced IP connectivity for efficient andreliable installation.The Connected Terminal Unit Controller comeswith an embedded web server that enablesweb-based application configuration and anHTML5 visualization interface. It also featuresembedded scheduling, alarming, and logging.Control logic and graphic user interface can becustomized as required for the application.

Moreover, as part of the Smart Room Controlsolution, these controllers can control lightingfixtures (DALI, ON/OFF, dimming) and shades/sunblind motors (24 VDC or 100-240 VAC, up/down and angle rotation) through additionalexpansion modules.

Applications£ Fan coil units£ Chilled beams£ Reversible ceilings with 6-way valves£ Heat pumps£ Smart Room Control solutionMoreover, these HVAC applications can supportdifferent configurations (4 pipe, 2 pipe, ...) anddifferent valve and actuator types (on/off,thermal, floating, 0-10 V, ...).

D a t a s h e e t

Page 2: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

2 / 14 ECLYPSE™ Connected Terminal Unit Controller

Features & BenefitsIP Communication£ Increased speed and improved handling of

numerous trend logs that enableapplications such as advanced analytics thatrequire a large amount of data.

£ Experience faster response and save timewhen programming, configuring, creatingand viewing graphics, and upgrading yoursystem.

£ Control technicians can connect theECLYPSE Wi-Fi Adapter to the ECLYPSEConnected Terminal Unit Controller therebycreating a Wi-Fi Hotspot network. Thecontrol technician can then connectwirelessly to the system using a mobiledevice or laptop, for faster, easier systemconfiguration, programming, commissioningand servicing.

£ Hostname management allows the controllerto be addressed by a nickname to facilitatenetwork management.

Advanced IP ConnectivityThe different types of connections supported bythe ECLYPSE Connected Terminal UnitController are the following:

IP wired connectionInternal switch with two Ethernet ports allowsthe controllers to be wired in a star or daisy-chain topology. With a daisy-chain topology:£ Fewer wire runs to a centralized switch are

required, thereby achieving installation andcost reduction.

£ A laptop can be connected to the secondEthernet port for direct programming,configuration, and commissioning using EC-gfxProgram or ENVYSION.

Integrated Fail-Safe for Daisy-ChainingControllers feature an integrated fail-safe: incase of power failure to one of the daisy-chained controllers, communication data is stillrelayed to the following controller on the daisy-chain. This reduces the possibility that a singlepoint of failure will knock-out follow-oncontrollers, and minimizes disruption whenpower is cut to a controller for maintenanceoperations.

IP wireless (Wi-Fi) connectionThe following types of Wi-Fi connections arepossible when using the ECLYPSE Wi-FiAdapter:

£ Wi-Fi Client - Connection to the building’sexisting Wi-Fi network or to anothercontroller’s Wi-Fi Hotspot or Access Point.

£ Wi-Fi Access Point - extending the building’swired IP network to your Wi-Fi Clientdevices.

£ Wi-Fi Hotspot - your own wireless areanetwork, for wireless communicationbetween the controllers, or with a mobiledevice or laptop for configuration,commissioning and servicing.

Both IP wired and wireless (Wi-Fi) connectionThe availability of both Ethernet ports and USBports for the Wi-Fi Adapter, allows forsimultaneous wired IP and Wi-Fi communicationon the same controller, allowing you to chooseand combine these connection methods. Forexample, Wi-Fi can be used between twocontrollers to jump a large atrium.

Connect from anywhereControl technicians, facility managers,occupants, and others can easily connect to thesystem, on-site or off-site, using the differentavailable tools:£ ENVYSION to create and view the graphical

interface£ EC-gfxProgram to create custom control

sequences£ myDC Control to view, edit, and configure

system operating parameters

BACnet/IP Device (pending)The ECLYPSE Connected Terminal UnitController is BTL-listed as a BACnet BuildingController (B-BC) and is certified WSP B-BC(Europe) and AMEV AS-A & AS-B (German-speaking countries). It supports BACnet/IP forfaster communication in comparison to thetraditional twisted pair communication bus.

No External TransformerSome models feature a 100-240 VAC universalpower supply input that allows for directconnection to the mains and do not requireexternal transformers, for improved reliabilityand reduced installation costs.Some models have a 24 VAC power supplyoutput that can be used to power analogdampers and valve actuators therebyeliminating the need for a transformer.

Page 3: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

ECLYPSE™ Connected Terminal Unit Controller 3 / 14

Dedicated Inputs & OutputsEach controller has specific IOs to fulfill any typeof installation:£ Universal inputs for using your preferred or

engineer-specified sensors.£ Sensor inputs to ensure optimal temperature

measurement processing.£ Digital inputs to accelerate the integration of

binary inputs such as window contacts.£ Powered Triac outputs for direct connection

of valves and actuators.£ Powered relay outputs for direct connection

of ventilator fans.£ Relay contact outputs for controlling

externally powered devices such as electricheater, fans, ...

£ Analog outputs to provide control signals forexternal peripherals.

£ Digital / Analog outputs for enhancedflexibility

Depending on the installation configuration andcontrolled equipment (valves, fans…), thesuitable model will allow for simplifiedinstallation and wiring, and eliminate the needfor additional external power supply.

eu.bac Certified Control Efficiency(pending)The eu.bac certification schemes guaranteesthe highest level of performance of the productsand systems, as defined in the EU-Directivesand relevant EN standards. This allows buildingowners to ensure that their building keepsperforming as well, or better than when it wasfirst commissioned.

Preloaded Application and GraphicsFaster programming and configurationThe ECLYPSE Connected Terminal UnitController is a plug and play device that savestime and money since no programming orgraphic design is needed as it comes withENVYSION™ Viewer and the associatedpreloaded applications and graphics are pre-installed.All standard terminal applications, such as fancoil units, chilled beams and ceilings, areincluded.

Direct web accessAlso, no additional tools are required; only aweb-browser is needed when you are using thepre-loaded application through ENVYSION. AnAllure™ EC-Smart-Vue sensor can also beused. However, if the pre-loaded applicationdoes not meet the application requirements, it ispossible to use EC-gfxProgram to program it.

HTML5 Visual InterfaceThe ECLYPSE Connected Terminal UnitController comes embedded with ENVYSIONViewer and xpressENVYSION.

ENVYSION Viewer – Web-based graphical userinterfaceThe embedded ENVYSION viewer provides fastloading of visual applications through native webpages with absolutely no browser plug-ins. Hostand view preloaded graphics, and accessschedules, alarms, and trend logs directly fromyour ECLYPSE Connected Terminal UnitController.

xpressENVYSION – Workflow oriented graphi-cal user interface configurationxpressENVYSION offers a simplified andstreamlined experience in a workflow oriented,drag & drop GUI environment while ENVYSIONstill offers the full customization features andediting environment.

Page 4: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

4 / 14 ECLYPSE™ Connected Terminal Unit Controller

ProgrammabilitySupports Distech Controls’ EC-gfxProgram,which makes Building Automation System(BAS) programming effortless by allowing you tovisually assemble building blocks together tocreate a custom control sequence for anyHVAC / building automation application.

Simplified Network CommissioningThe XpressNetwork Utility saves you time andexpense by giving you increased control overmultiple ECLYPSE controllers through devicediscovery and batch operations such asconfiguring and updating multiple ECLYPSEcontrollers on the network.In addition, with the embedded step by stepCommissioning Wizard, all configurationoperations can be setup and applied in one go.Increase productivity using the xpressNetworkCompanion mobile app, making it easier toidentify and locate a controller on the network.Use the QR Code marked on ECLYPSEcontrollers to easily collect key controller dataand to facilitate its network integration withxpressNetwork Utility.

Open to Web ServicesWith the RESTful API, the ECLYPSEConnected Terminal Unit Controller’s data canbe accessed from different applications, such asenergy dashboards, analytics tools, and mobileapplications. The RESTful API documentationexplains the implementation protocol for thisinterface.

MobilityThe controller can be remotely accessed toprogram, configure, or maintain the installationthus reducing costs associated with on-sitevisits. Through a mobile device or PC, a rangeof tasks can be performed using the followingfree-to-use tools and interfaces:£ ENVYSION web-based graphic design and

visualization interface

£ EC-gfxProgram graphical programminginterface

£ myDC Control mobile application£ XpressNetwork Companion controller data

collection utility

Alarms, Trend Log, Schedule SupportEmbedded alarms, trend log and schedulesupport allows for fully distributed data and logicproviding a more robust system. Embeddedtrend logs simplify system troubleshooting whencompared to a centralized system.

Email Notifications ServiceTechnicians & facility managers can receiveautomatic email notifications for system statusand alarms to ensure faster system servicingand response time. Email notification text canbe customized to provide pertinent informationabout the issue at hand.

FIPS 140-2 Level 1 CompliantFIPS 140-2 Level 1 compliance provides anenhanced level of security to protect data thecontroller is collecting and sharing making itsuitable for use in the most sensitiveenvironments.

Smart Room Control SupportThe Smart Room Control solution is an end-to-end system for the control of HVAC equipment,lighting, and shades/sunblinds, achieving thehighest levels of comfort for occupants whilecutting costs from installation time and wiring/material requirements to energy consumption.This solution combines:£ Lighting and shade/sunblind expansion

modules to control lights (DALI, on/off ordimming) and shades/sunblinds (24 VDC or100-240 VAC, up/down and angle rotation).

£ Multi-sensor combining motion andluminosity (Lux) sensors and equipped withan Infrared receiver that works with aconvenient remote control.

£ Wireless (infrared) personal remote controlfor increased occupant comfort.

£ Allure™ Series Communicating Sensors forincreased occupant comfort settings.

Page 5: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

ECLYPSE™ Connected Terminal Unit Controller 5 / 14

Allure™Series Communicating Sensor SupportThese controllers work with a wide range ofsensors, such as the Allure SeriesCommunicating Sensors that are designed toprovide intelligent sensing and control devicesfor increased user experience and energyefficiency.£ Allure EC-Smart-Vue sensors feature a

backlit-display and graphical menus thatprovide precise environmental zone control,with any combination of the following:temperature, humidity, CO2, and motionsensor.

£ Allure EC-Smart-Comfort sensors featurecolored LED indicators to provide userfeedback, rotary knobs to adjust the setpointoffset and fan speed, and an occupancyoverride push button. This sensor can alsobe expanded with a combination of up to 4add-on push button modules for lighting andshade/ sunblind control.

£ Allure EC-Smart-Air sensors combineprecise environmental sensing in a discreetand alluring enclosure for temperature,humidity, and CO2.

Page 6: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

6 / 14 ECLYPSE™ Connected Terminal Unit Controller

Model Selection

Connected Terminal Unit ControllerModel ECY-PTU-107 ECY-PTU-207 ECY-PTU-208 ECY-TU-203Supply Voltage Input 100-240 VAC 100-240 VAC 100-240 VAC 24 VACPoints 12 16 16 16Universal Inputs 3 3 3 3Digital Inputs 2 2 2 2Sensor Inputs 1 1 1 1Relay Contact Outputs(typ. Electric Heater)

1 1 1 1

Relay Outputs(typ. Fan Speeds)

3 (Line-Powered

3 (Line-Powered

3 (Line-Powered

3 (Unpowered)

Powered Triac Outputs(typ. Valves)

2 (Line-Powered)

2 (Line-Powered)

2 (24 VAC) 2 (24 VAC)

Analog Outputs - 4 4 2Digital / Analog Outputs - - - 224 VAC Power Supply Outputs - -ENVYSION ViewerPreloaded Apps

AccessoriesECLYPSE Wi-Fi Adapter Wi-Fi Adapter for ECLYPSE Connected Controllers.

Page 7: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

ECLYPSE™ Connected Terminal Unit Controller 7 / 14

Product SpecificationsPower Supply InputFor ECY-PTU-107, ECY-PTU-207, and ECY-PTU-208Voltage 100-240 VAC; ±10%Frequency Range 50 to 60 HzOvercurrent protection 4.0 A external circuit breaker type CDevice Insulation Type Double Insulation

Overvoltage Category II - 2.5 kVPower Consumption 5 W + all external loadsMaximum Consumption 4 A

For ECY-TU-203Voltage 24 VAC; ±15%; Class 2Frequency Range 50 to 60 HzOvercurrent protection 2.0 A fast acting, 5x20mm (GMA-2A) internal fuseDevice Insulation Type Double Insulation

Overvoltage Category II - 2.5 kVPower Consumption 5 W + all external loadsMaximum Consumption 2 A

EnvironmentalOperating Temperature +5°C to +40°CStorage Temperature -20°C to +70°CRelative Humidity 0 to 90% Non-condensingIngress Protection Rating IP30 (with terminal block covers and strain relief)Nema Rating 1Altitude < 2000 mPollution Degree 2

CommunicationsEthernet Connection Speed 10/100 Mbps£ Addressing IPv4 or HostnameBACnet Listing BTL, WSP B-BCBACnet Interconnectivity BBMD forwarding capabilitiesBACnet Profile BACnet Building Controller (B-BC)), AMEV AS-A and AS-B (pending)BACnet Transport Layer IPWeb Server Protocol HTML5Web Server Application Interface REST API

Page 8: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

8 / 14 ECLYPSE™ Connected Terminal Unit Controller

Supported Wireless Connectivity:£ Wireless Adapter Optional, USB Port Connection£ Wi-Fi Communication Protocol IEEE 802.11b/g/n£ Wi-Fi Network Types Client, Access Point, Hotspot

SubnetworkCommunication RS-485Cable Cat 5e, 8 conductor twisted pairConnector RJ-45Topology Daisy-chain configurationMaximum number of supported room devices per controller combined 4Supported room devices:£ Allure EC-Smart-Vue Series1

£ Allure EC-Smart-Comfort Series£ Allure EC-Smart-Air Series1

£ EC-Multi-Sensor SeriesSupported expansion modules per controller:£ ECx-Light-4 / ECx-Light-4D / ECx-Light-4DALI 2£ ECx-Blind-4 / ECx-Blind-4LV 21. A controller can support a maximum of two Allure Series Communicating Sensor models equipped with a CO2sensor. The remaining connected Allure Series

Communicating Sensor models must be without a CO2sensor.

HardwareProcessor Sitara ARM processorCPU Speed 600 MHzMemory 4 GB Non-volatile Flash (applications & storage)Real Time Clock (RTC) Real Time Clock with rechargeable battery

Supports SNTP network time synchronizationRTC Battery 20 hours charge time, 20 days discharge time

Up to 500 charge / discharge cyclesCryptographic Module FIPS 140-2 Level 1 CompliantCommunications Ports:£ Ethernet 2 switched RJ-45 Ethernet portsIntegrated fail-safe for daisy-chaining In case of power failure to one of the controllers,

communication data is still relayed to the following controller on the daisy-chain

£ USB Connections 2 × USB 2.0 Ports 1 × Micro-USB 2.0 Port

£ Subnet RJ-45Status Indicators Green LEDs: Power status, and Ethernet Traffic

Orange LEDs: Controller status, and Ethernet Speed

Page 9: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

ECLYPSE™ Connected Terminal Unit Controller 9 / 14

MechanicalDimensions£ Without terminal block covers 142 × 145 × 57 mm

5.71 145.00

5.54 140.84

5.60 142.22

Front

2.24 56.88

Profile

Inches [Millimeters]

.24 6.04

5.07 128.76

.24 6.04

5.08 129.01

.31 7.99.31 7.99

Back

.05 1.38

£ With terminal block covers 195 × 145 × 57 mm5.71 145.00

7.67 194.85

Front

2.24 56.88

Profile

5.71 145.00

7.67 194.85

Front

2.24 56.88

Profile

Inches [Millimeters]

5.07 128.76

1.30 33.04

1.30 33.04

5.08 129.01

.31 7.99.31 7.99

Back

5.07 128.76

1.30 33.04

1.30 33.04

5.08 129.01

.31 7.99.31 7.99

Back

Shipping weight 0.6 kgMaterial Flame retardant ABSEnclosure Rating Plastic housing, UL94-5VB flammability ratingColor BlueInstallation Direct din-rail mounting or wall-mounting1. All materials and manufacturing processes comply with the RoHS directive and are marked according to the Waste Electrical and Electronic Equipment (WEEE)

directive

Standards & Regulations (pending)CE - Emission EN 61000-6-3: 2007 + A1: ed.2011; Generic standards for residential,

commercial and light-industrial environmentsCE - Immunité EN 61000-6-1: 2007; Generic standards for residential

commercial and light-industrial environmentsUL Listed (CDN & US) UL 61010-1 Safety Requirements For Electrical Equipment

For Measurement, Control, And Laboratory Use – Part 1: General RequirementsFCC This device complies with FCC rules part 15, subpart B, class B

Page 10: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

10 / 14 ECLYPSE™ Connected Terminal Unit Controller

Specifications – InputsUniversal Inputs (UI)GeneralInput Type Universal; software configurable

ContactType Dry contact (0-3.3 VDC)

CounterType Dry contact (0-3.3 VDC)Maximum Frequency 1 Hz maximumMinimum Duty Cycle 500 milliseconds On / 500 milliseconds Off

0 to 10 VDCRange 0 to 10 VDC (40 kΩ input impedance)

Resistance/ThermistorType 10 kΩ Type II, III (10 kΩ @ 25ºC)

Sensor Inputs (SI)GeneralInput Type Sensor; software configurable

ContactType Dry contact (0-3.3 VDC)

CounterType Dry contact (0-3.3 VDC)Maximum Frequency 1 Hz maximumMinimum Duty Cycle 500 milliseconds On / 500 milliseconds Off

ResistanceType 10 kΩ Type II, III (10 kΩ @ 25ºC)Accuracy ±0.1°C @ 25°C

Digital Inputs (DI)GeneralInput Type Digital; software configurable

ContactType Dry contact (0-3.3 VDC)

CounterType Dry contact (0-3.3 VDC)Maximum Frequency 100 Hz maximumMinimum Duty Cycle 5 milliseconds On / 5 milliseconds Off

Power Supply (Vref)Output (Vref) 5 VDC for polarization (I < 1 mA)

Page 11: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

ECLYPSE™ Connected Terminal Unit Controller 11 / 14

Specifications – OutputsTriac OutputsGeneral

For ECY-PTU-107 and ECY-PTU-207Output Type TriacVoltage Range 0 or 100-240 VAC (same as device power supply)Maximum Current per Output 0.5 A continuousInrush Current 1 A @ 15% duty cycle for a 10-minute periodCommon Terminal 1 per pair of outputs

For ECY-PTU-208 and ECY-TU-203Output Type TriacPower Source Internal on-board 24 VAC power supplyVoltage Range See on-board 24 VAC power supplyCurrent See on-board 24 VAC power supplyCommon Terminal 1 per pair of outputs

Digital (On/Off)

For ECY-PTU-107 and ECY-PTU-207Voltage Range 0 or 100-240 VAC (same as device power supply)

For ECY-PTU-208 and ECY-TU-203Voltage Range 0 or 24 VAC

PWMApplication Typically Thermal Valve ControlRange Adjustable period from 2 to 65 seconds

FloatingMinimum Outputs 2 consecutive outputsMinimum Pulse On/Off Time 500 millisecondsDrive Time Period Adjustable from 10 to 600 seconds

Powered Relay OutputsFor ECY-PTU-107, ECY-PTU-207, and ECY-PTU-208Output Type DigitalApplication Typically Fan SpeedsSupplied Voltage Same as device power supplyCurrent 3.0 A max. (inductive or resistive load) for the total sum of the 3 outputsResting State Normally OpenCommon Terminal Shared

Page 12: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

12 / 14 ECLYPSE™ Connected Terminal Unit Controller

Unpowered Relay OutputsFor ECY-TU-203Output Type DigitalApplication Typically Fan SpeedsSupplied Voltage No voltage suppliedSupported Voltage 100-277 VACCurrent 3.0 A max. (inductive or resistive load) for the total sum of the 3 outputsProtection Must be protected with an external circuit breaker or fast acting,

high breaking fuse in accordance with the controlled load (3 A max. / min voltage according to the controlled load)

Resting State Normally OpenCommon Terminal Shared

Digital Relay Contacts OutputsGeneralOutput Type DigitalApplication Typically Electric HeaterProtection Must be protected with an external circuit breaker or fast acting,

high breaking fuse in accordance with the controlled load (10 A max. / min voltage according to the controlled load)

ContactType Dry contactVoltage Range:£ ECY-PTU-107 / ECY-PTU-207 / ECY-PTU-208 100-240 VAC£ ECY-TU-203 100-277 VACCurrent 9.0 A max. on a resistive load (2 kW @ 230 VAC)Resting State Normally OpenCommon Terminal Dedicated digital

Analog OutputsFor ECY-PTU-207 ECY-PTU-208 and ECY-TU-203

GeneralOutput Type AnalogVoltage Range 0-10 VDC linearCurrent 5 mA max.

24 VAC OutputsFor ECY-PTU-208 and ECY-TU-203Power Source Internal on-board 24 VAC power supplyVoltage Range See on-board 24 VAC power supplyCurrent See on-board 24 VAC power supply

Page 13: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

ECLYPSE™ Connected Terminal Unit Controller 13 / 14

On-board 24 VAC Power SupplyFor ECY-PTU-208 and ECY-TU-203Voltage Range 24 VAC; ± 10%Frequency 50 HzCurrent 700 mA max. on a resistive load (16 VA @ 24 VAC)Peak current 850 mAShort-circuit protection:£ ECY-PTU-208 Integrated Fail Safe£ ECY-TU-203 FuseOverload protected Yes

Digital-Analog OutputsFor ECY-TU-203Output Type Digital Triac or Analog; software configurableTriac Output Mode See Triac Output specificationsAnalog Output Mode See Analog Output specifications

Page 14: ECLYPSE™Connected Terminal Unit - Distech · and is listed as a BACnet Building Controller (B-BC). These products feature wired and wireless advanced IP connectivity for efficient

14 / 14 ECY-PTU Europe_DS_11_EN

Specifications subject to change without notice.ECLYPSE, Distech Controls, the Distech Controls logo and Allure are trademarks of Distech Controls Inc. BACnet is a registered trademark of ASHRAE; BTL is a reg-

istered trademark of the BACnet Manufacturers Association. All other trademarks are property of their respective owner.©, Distech Controls Inc., 2014 - 2015. All rights reserved.