5
The company reserves the right to make changes of technical data without prior notice 28 CIRCULAR DUCT FANS AKU EKO Application Insulated circular duct fans AKU EKO are used in low-to medium-pressure ducted systems. Fans are suitable for air supply or exhaust of residential buildings, warehouses, bathrooms, lavatories, auxiliary premises and other premises where the heat recovery is not required, also as boost fans in ventilation systems. Features Connection diameter - 125 mm to 315 mm; 3 /h; Easily mounted in any position; Backward-curved impeller; Fan speed 100% controllable via 0-10 V signal; Acoustically insulated; Sizes 125, 160, 200, 250, 315. Construction Casing: galvanized sheet steel, powder coated; Acoustic and thermal wall insulation – 50mm; Fan: centrifugal impeller and external rotor motor; Motor protection integrated into motor electronics; Motor protection class: IP44 (AKU EKO 125 only) / IP54; Terminal box protection class: IP55. Installation Device can only be used indoors; Not suitable for polluted air or volatile and explosive gases. Speed control options 10 kΩ potentiometer; External signal 0-10 VDC/PWM from user controller; EC Fans with EC motors Diameter size Product name AKU 125 EKO Circular duct fans with EC-type motor

EC - Øland Online · AKU 250 EKO AKU 315 EKO The fan characteristic curves were determined in accordance with EN ISO 5801. The sound levels were determined in accordance with DIN

  • Upload
    others

  • View
    0

  • Download
    0

Embed Size (px)

Citation preview

Page 1: EC - Øland Online · AKU 250 EKO AKU 315 EKO The fan characteristic curves were determined in accordance with EN ISO 5801. The sound levels were determined in accordance with DIN

The company reserves the right to make changes of technical data without prior notice28

CIRC

ULA

R D

UCT

FA

NS

AKU EKO

ApplicationInsulated circular duct fans AKU EKO are used in low-to medium-pressure ducted systems. Fans are suitable for air supply or exhaust of residential buildings, warehouses, bathrooms, lavatories, auxiliary premises and other premises where the heat recovery is not required, also as boost fans in ventilation systems.

Features

› Connection diameter - 125 mm to 315 mm;› 3/h;› Easily mounted in any position;› Backward-curved impeller;› Fan speed 100% controllable via 0-10 V signal;› Acoustically insulated;›

Sizes 125, 160, 200, 250, 315.

Construction

› Casing: galvanized sheet steel, powder coated;› Acoustic and thermal wall insulation – 50mm;› Fan: centrifugal impeller and external rotor motor;› Motor protection integrated into motor electronics; › Motor protection class: IP44 (AKU EKO 125 only) / IP54;› Terminal box protection class: IP55.

Installation ›› Device can only be used indoors;› Not suitable for polluted air or volatile and explosive gases.

Speed control options

› 10 kΩ potentiometer;› External signal 0-10 VDC/PWM from user controller;›

EC

Fans with EC motors

Diameter size

Product name

AKU 125 EKO

Circular duct fans with EC-type motor

Page 2: EC - Øland Online · AKU 250 EKO AKU 315 EKO The fan characteristic curves were determined in accordance with EN ISO 5801. The sound levels were determined in accordance with DIN

The company reserves the right to make changes of technical data without prior notice 29

Type Dimensions [mm]

B W H M N øD E FAKU 125 EKO 400 410 325 205 166 125 440 330

AKU 160 EKO 550 485 340 149 193 160 590 405

AKU 200 EKO 600 545 425 170 260 200 640 465

AKU 250 EKO 600 545 425 194 235 250 640 465

AKU 315 EKO 437 595 475 298 238 315 477 515

AKU EKO

CIRCULA

R DU

CT FAN

S

Circular duct fans with EC-type motor

Page 3: EC - Øland Online · AKU 250 EKO AKU 315 EKO The fan characteristic curves were determined in accordance with EN ISO 5801. The sound levels were determined in accordance with DIN

The company reserves the right to make changes of technical data without prior notice30

Stat

ic p

ress

ure

[Pa]

Air flow [m3/h]

AKU 125 EKOAKU 160 EKOAKU 200 EKO

The fan characteristic curves were determined in accordance with EN ISO 5801. The sound levels were determined in accordance with DIN 45635 resp. ISO 3744 at a distance of 1 m from the fan.

200 EKO Lwa total, dB(A)

Lwa, dB(A)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

Inlet 68 52 66 60 56 54 51 52Outlet 80 56 74 76 74 69 64 63Surrounding 58 39 56 52 49 45 41 42Measured at 805 m3/h, 170 Pa

160 EKO Lwa total, dB(A)

Lwa, dB(A)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

Inlet 65 49 63 60 49 51 48 46Outlet 74 52 68 70 67 64 61 58Surrounding 54 36 52 49 42 41 38 36Measured at 413 m3/h, 211 Pa

125 EKO Lwa total, dB(A)

Lwa, dB(A)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

Inlet 59 41 54 56 45 45 40 44Outlet 65 43 58 62 57 57 52 49Surrounding 47 28 43 44 36 34 31 29Measured at 207 m3/h, 95 Pa

CIR

CU

LAR

DU

CT

FA

NS

AKU EKO

Fan 125 EKO 160 EKO 200 EKOElectrical dataPhase/Votage/Frequency [V/Hz] ~1,230/50 ~1,230/50 ~1,230/50Max. power consumption [kW] 0,051 0,083 0,168Max. current [A] 0,40 0,75 1,40Wiring diagram No. 1 No.1 No. 3Fan speed controller MTP010 MTP010 MTP010Technical dataMax. airflow [m3/h] 419 632 1101Fan impeler speed [min-1] 4521 3200 3380Weight [kg] 12,3 19,0 25,0Ambient temperature limits [°C] -20/50 -25/60 -25/45Protection class: motor IP 44 IP 54 IP 54Protection class: terminal box IP 55 IP 55 IP 55Impeler Backwards curved Backwards curved Backwards curvedEcodesign dataClasification* NRVU NRVU NRVUSound power level [dB(A)] 50 56 60Nominal flow rate [m3/s] 0,05 0,12 0,21Nominal external pressure [Pa] 340 259 321Static efficiency of fans used in accordance with Regulation No 327/2011

[%] 31,7 35,9 38,8

ErP Compliance 2018 2018 2018* NRVU - non-residential ventilation unit.

Page 4: EC - Øland Online · AKU 250 EKO AKU 315 EKO The fan characteristic curves were determined in accordance with EN ISO 5801. The sound levels were determined in accordance with DIN

The company reserves the right to make changes of technical data without prior notice 31

Stat

ic p

ress

ure

[Pa]

Air flow [m3/h]

AKU 250 EKOAKU 315 EKO

The fan characteristic curves were determined in accordance with EN ISO 5801. The sound levels were determined in accordance with DIN 45635 resp. ISO 3744 at a distance of 1 m from the fan.

315 EKO Lwa total, dB(A)

Lwa, dB(A)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

Inlet 76 59 73 67 68 65 58 55Outlet 87 64 75 84 81 76 72 67Surrounding 65 47 61 60 58 54 48 45Measured at 1553 m3/h, 120 Pa

250 EKO Lwa total, dB(A)

Lwa, dB(A)

125 Hz 250 Hz 500 Hz 1 kHz 2 kHz 4 kHz 8 kHz

Inlet 73 57 70 64 66 59 53 52Outlet 84 62 77 80 78 73 68 64Surrounding 63 45 60 56 56 49 44 42Measured at 1049 m3/h, 120 Pa

AKU EKO

CIR

CU

LAR

DU

CT FA

NS

Fan 250 EKO 315 EKOElectrical dataPhase/Votage/Frequency [V/Hz] ~1,230/50 ~1,230/50Max. power consumption [kW] 0,170 0,380Max. current [A] 1,75 2,50Wiring diagram No. 1 No. 2Fan speed controller MTP010 MTP010Technical dataMax. airflow [m3/h] 1184 1642Fan impeler speed [min-1] 2860 3400Weight [kg] 25 31Ambient temperature limits [°C] -20/60 -25/55Protection class: motor IP 54 IP 54Protection class: terminal box IP 55 IP 55Impeler Backwards curved Backwards curvedEcodesign dataClasification* NRVU NRVUSound power level [dB(A)] 63 67Nominal flow rate [m3/s] 0,22 0,33Nominal external pressure [Pa] 380 541Static efficiency of fans used in accordance with Regulation No 327/2011

[%] 37,4 44,6

ErP Compliance 2018 2018* NRVU - non-residential ventilation unit.

Page 5: EC - Øland Online · AKU 250 EKO AKU 315 EKO The fan characteristic curves were determined in accordance with EN ISO 5801. The sound levels were determined in accordance with DIN

The company reserves the right to make changes of technical data without prior notice32

PE - yellow-greenBU - blueBN - brownYE - yellowWH - whiteRD - redBN/BK - brown/black

CIR

CU

LAR

DU

CT

FA

NS

Wiring diagram No. 1 (1~230V)

Wiring diagram No. 2 (1~230V)

AKU EKO

Wiring diagram No. 3 (1~230V)