14
Easy Config Configuration tool for COUNTIS and DIRIS Operating instructions EN

Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

  • Upload
    others

  • View
    8

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

Easy ConfigConfiguration tool for COUNTIS and DIRIS

Operating instructions EN

Page 2: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

2 Easy Config - Ref. 541 456 A

CONTENTS

1. PRESENTATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2. INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

3. STARTING UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

4. PRESENTATION OF THE FUNCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

4.1 NEW FILE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

4.2 SAVE FILE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.3 OPEN FILE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

4.4 GET FROM DEVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

4.5 SEND TO DEVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

5. PROFILE MANAGEMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5.1 CHANGE PASSWORDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

5.2 SEND COMMANDS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

Page 3: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

3Easy Config - Ref. 541 456 A

1. PRESENTATIONEasy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement products equipped with a communication port. Once created, the configuration can be sent directly to the products via a MODBUS or Ethernet commu-nication bus or saved as a file on the user's PC.

2. INSTALLATIONStart up the installation using the setup.exe file found in the Easy Config folder, and follow the installation wizard.

3. STARTING UPTo start up Easy Config, go to the "Start" menu, "All Programs/Socomec/Easy Config" and open Easy Config.

The following screen is displayed after the software is started up:

Page 4: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

4 Easy Config - Ref. 541 456 A

4. PRESENTATION OF THE FUNCTIONS

5 functions can be accessed from 5 buttons

• Create a configuration file

• Save the created configuration file to the PC

• Open a previously saved configuration file from the PC

• Recover the configuration of a connected product via the communication bus

• Export a configuration to a connected product via the communication bus

4.1. New File

This function is used to create a complete configuration file by accessing all the product settings.

The configuration is split into categories found under tabs. The tabs available may differ according to the product to be configured.

By way of an example, the tabs shown in the rest of the document correspond to the DIRIS A80. The same logic can be applied to each of the COUNTIS meter and DIRIS measurement products:

Click on the "NEW" button to bring up the following screen:

The user chooses a device name ("New Device" by default) and the type of product for which he wishes to create a configuration file from a drop-down selection. "A80" is used in our example to create a configuration for a DIRIS A80.

Page 5: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

5Easy Config - Ref. 541 456 A

4. PRESENTATION OF THE FUNCTIONS

Click on OK to bring up the DIRIS A80 configuration screen:

The structure of this screen is similar for all COUNTIS and DIRIS products to be configured, only the tabs will differ depending on the functions available on the product.

Type and name of the product and error log, if applicable

Selected configuration tab

Pop-up help

User profileFunction buttons

Configuration tabs

Page 6: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

6 Easy Config - Ref. 541 456 A

4. PRESENTATION OF THE FUNCTIONS

Network tab

This menu is used to select the network type, the nominal network voltage value and the current and voltage transformer para-meters.

If values outside of the device's specifications are chosen, an error message appears around the value and on the left-hand side of the screen:

Page 7: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

7Easy Config - Ref. 541 456 A

4. PRESENTATION OF THE FUNCTIONS

Periods tab

This menu can be accessed by clicking the "Periods" tab. In this menu, the user chooses the integration periods for the average and maximum Current, Power, Voltage and Frequency electrical values. The load curves synchronization period and type para-meters can also be set from this menu.

Quality tab

The parameters relating to the detection of events associated with the network quality are defined in this menu. The user chooses the corresponding detection threshold and hysteresis for the Voltage Sag, Voltage Swell and Voltage Interruption. The detection of Current Overload can also be accessed via this menu.

Page 8: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

8 Easy Config - Ref. 541 456 A

RCM tab

This menu is used to define the trigger thresholds for Residual Current Monitoring and the residual current curves recording para-meters.

In the same way, the trigger thresholds for the earth currents are defined via this menu.

Definition of the IΔn and Ipe trigger thresholds:Using a table, the user selects up to 5 coordinates for the residual current, depending on the load current, so as to define the trig-ger thresholds. The corresponding trigger curve, shown on the right of the screen, is automatically updated based on the points selected. The same principle is used for the IΔn and Ipe trigger curves.

The trigger hysteresis and the delay for the alarm are also defined via the "IΔn Threshold" and "Ipe Threshold" menus.

Configuration of a 2-point IΔn curve with a hysteresis of 5% (default configuration):

Points are added by clicking the key and deleted by clicking the key.

4. PRESENTATION OF THE FUNCTIONS

Page 9: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

9Easy Config - Ref. 541 456 A

Configuration of a 5-point IΔn curve with a hysteresis of 10%:

After having defined the trigger thresholds, the user must use the "RCM Event Configuration" menu to select the alarm acknow-ledgement type, the option of synchronising the recording of short RCM and Quality curves and the duration parameters for the long curves. In total, 60 short curves and 8 long curves can be recorded.

The input and output states (1 input - 1 output or 2 outputs, depending on the reference) are defined from the "Input" and "Output" menus. These menus are used to define the type of inputs and outputs. For example, the Output may be allocated to the appea-rance of an alarm on IΔn or Ipe via a change of state and the Output to the acknowledgement of the alarm:

4. PRESENTATION OF THE FUNCTIONS

Page 10: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

10 Easy Config - Ref. 541 456 A

4.2 Save File

This function is used to save the configuration created as a file. This file may be reopened at a later date to modify it and/or send it to a product.

4.3. Open File

A configuration file which has previously been stored on the PC may be called up and modified. The tabs described for the creation of a configuration file can be used in the same way.

4. PRESENTATION OF THE FUNCTIONS

Page 11: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

11Easy Config - Ref. 541 456 A

4.4. Get from Device

The user can recover the configuration for a product from a COUNTIS or DIRIS via the communication bus; it can then be modified, saved as a file or sent to the product.

Before doing so, the communication parameters will have to be entered in the window which appears automatically once the "Get from Device" button is clicked.

The following menu is displayed:

4.5. Send to Device

To send the configuration to the COUNTIS or DIRIS via the communication bus, the communication parameters must be entered in the window which appears automatically once the "Send to Device" button is clicked.

5. PROFILE MANAGEMENT3 types of user can use Easy Config: "Basic User", "Administrator" and "Super User". Each of the users has a different level of rights.

Create a configuration and save to PC

Send a configuration to a device

Send a command to a device

Manage passwords

Basic User ✓Administrator ✓ ✓Super User ✓ ✓ ✓ ✓

4. PRESENTATION OF THE FUNCTIONS

Page 12: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

12 Easy Config - Ref. 541 456 A

5.1. Change passwords

By default, the passwords are

Basic User: no password

Administrator : SocoAdm

Super User: sOcOmec

To change the passwords, first log in as "Super User" by clicking on "Change Profile" at the top right of the screen. The following screen appears, allowing the passwords to be changed:

5.2 Send Commands

To send commands to the COUNTIS or DIRIS, the "Super User" profile must be used and you must connect to the products via the communication bus. In this configuration, the "COM" and "Commands" tabs appear to enable the communication parameters for the COUNTIS and DIRIS to be changed and to send commands to these products: Date/Time, reinitialisation of the energy meters, the average/max electrical values and the load curve, RCM and Quality events for the DIRIS A80, as shown on the following screens:

5. PROFILE MANAGEMENT

Page 13: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

13Easy Config - Ref. 541 456 A

5. PROFILE MANAGEMENT

Page 14: Easy Config - Socomec · 2013. 11. 15. · Easy Config - Ref. 541 456 A 3 1. PRESENTATION Easy Config is a software tool used to configure the ranges of COUNTIS meters and DIRIS measurement

VALID FOR FRANCE

www.socomec.com

hEAD OFFICE

SOCOMEC GROUPS.A. SOCOMEC capital 10 951 300 €R.C.S. Strasbourg B 548 500 149B.P. 60010 - 1, rue de Westhouse F-67235 Benfeld Cedex - FRANCE

InTERnATIOnAL SALES DEPARTMEnT

SOCOMEC1, rue de Westhouse - B.P. 60010 F - 67235 Benfeld Cedex - FRANCETel. +33 (0)3 88 57 41 41 Fax +33 (0)3 88 74 08 [email protected]

Socomec worldwide

In EUROPE

BELGIUMB - 1190 Brussel Tel. +32 (0)2 340 02 30 [email protected]

FRANCEF - 94132 Fontenay-sous-Bois Cedex Tel. +33 (0)1 45 14 63 30 [email protected]

GERMANYD - 76275 Ettlingen Tel. +49 (0)7243 65 29 2 0 [email protected]

ITALYI - 20098 San Giuliano Milanese (MI) Tel. +39 02 9849821 [email protected]

POLAND01-625 Warszawa Tel. +48 91 442 64 11 [email protected]

SLOVENIASI - 1000 Ljubljana Tel. +386 1 5807 860 [email protected]

SPAINE - 08310 Argentona (Barcelona) Tel. +34 93 741 60 67 [email protected]

ThE NEThERLANDSNL - 3991 CD Houten Tel. +31 (0)30 760 0901 [email protected]

ThE UNITED KINGDOMHitchin Hertfordshire SG4 0TY Tel. +44 (0)1462 440033 [email protected]

TURKEY34775 Istanbul Tel. +90 (0) 216 540 71 20 [email protected]

In ASIA

NORTh EAST ASIAP.R.C 200052 Shanghai - China Tel. +86 (0)21 5298 9555 [email protected]

SOUTh EAST ASIA & PACIFICUBI TECHPARK - 408569 Singapore Tel. +65 65 07 94 90 [email protected]

SOUTh ASIA122001 Gurgaon, Haryana - India Tel. +91 124 4562 700 [email protected]

non

con

trac

tual

doc

umen

t. ©

201

2, S

ocom

ec S

A. A

ll rig

hts

rese

rved

.

To h

elp

prot

ect t

he e

nviro

nmen

t, th

is d

ocum

ent h

as b

een

prin

ted

on P

EFC

pap

er (P

rogr

amm

e fo

r th

e E

ndor

sem

ent o

f For

est C

ertif

icat

ion)

In MIDDLE EAST

UNITED ARAB EMIRATESDubai, U.A.E. Tel. +971 (0) 4 29 98 441 [email protected]

In nORTh AMERICA

USA, CANADA & MEXICOCambridge, MA 02142 USA Tel. +1 617 245 0447 [email protected]

YOUR DISTRIBUTOR

• 4e_couv_SCP_2012_25092012.indd 6 12/10/12 16:48

Ref

. 541

456

A E

N -

11/

12