48
SAIEE TUTORIAL PROTECTION APPLICATION CONSIDERATIONS FOR EARTHING SYSTEMS AND SECTION ON EARTHING SYSTEMS BY D G DUNCAN Ron Slatem and Associates (Acknowledgement to Ron Slatem and previous Eskom personnel)

Earthing of Electrical Systems

Embed Size (px)

Citation preview

Page 1: Earthing of Electrical Systems

SAIEE TUTORIAL

PROTECTION APPLICATIONCONSIDERATIONS

FOR

EARTHING SYSTEMS

AND

SECTION ONEARTHING SYSTEMS

BY D G DUNCAN

Ron Slatem and Associates

(Acknowledgement to Ron Slatem and previous Eskom personnel)

Page 2: Earthing of Electrical Systems

2

SYSTEM GROUNDING AND ASSOCIATEDPROTECTION ASPECTS

1.0 SYSTEM NEUTRAL GROUNDING (OR EARTHING)

1.1 Introduction

The principal objective for any power system, whether industrial or utility, is to continue to function inits entirety for as great a percentage of its operating life as possible. If it could be arranged that thesystem continued to function satisfactorily even when a fault has occurred, without disconnecting thefaulty element, this would be ideal. In the hope of achieving this objective the earliest power systemswere operated without the intentional connection to ground of any part of the system. The theory wasthat an accidental connection to ground would have no adverse effect on plant as no ground faultcurrents could flow. With no ground fault currents there could be no damage. Therefore the plant couldbe kept in service.

Unfortunately, it is physically impossible to have a system without any connection whatsoever toground. Even if there is no intentional connection, there is always the capacitance of the system toground which provides a path for current flow if a further connection to ground occurs. See fig 1a.Such currents would, of course, be of relatively low magnitude.

If the further, unintentional, connection to ground is a solid, "bolted" connection, the situation is stilltolerable as the effect of grounding one phase of an otherwise "ungrounded" system is merely to lift theother two phases to line voltage above ground. (Fig.lc). If the insulation to ground is designed towithstand such voltages continuously, the system can be operated in spite of the ground "fault"condition.

The first problem that is likely to arise is if a second phase should also develop a ground fault. Nowthere is a solid path for the flow of large fault currents and the condition is equivalent to a phase-to-phase fault. The second fault is highly unlikely to occur on the same circuit as the initial fault. Thistype of double ground fault on different circuits is called a "cross-country" fault and is often verydifficult to relay satisfactorily. It also requires the disconnection of two items of plant.

The second, and more serious problem arises if the ground fault is not a solid bolted fault, but an arc.The arc is of a low current level and tends to be highly unstable so it tends to quench and restrike as thesystem voltage alternates. Such restriking in a capacitively grounded circuit is called an "arcing-ground" and can give rise to extremely high transient overvoltages. These overvoltages can severelystress the insulation of the whole of the associated system and cause multiple insulation failures onother items of plant, leading to far greater disruption of the system than the removal of the initial faultyitem would have caused. The disruption is also likely to be more prolonged and more costly.

Because of bitter adverse experience of multiple insulation failures in many isolated neutral systems, ithas become increasingly common practice to provide systems with an intentional groundingconnection. The primary purpose of system grounding is to minimise the overvoltage and/or thermaldamage to the system in the event of an earth-fault.

System grounding reduces the severity of dynamic and transient overvoltages which develop if thesystem is subjected to a ground fault, particularily and can reduce thermal damage at the point of faultif the ground fault current is restricted.

Page 3: Earthing of Electrical Systems

3

The grounding connection is usually made via available neutral points on the apparatus, such as thetransformer neutral points on star connected windings, or via artificially derived neutral points. See fig1b.

In exceptional cases, at lower voltages up to 33kV, one corner of the system delta voltage triangle,instead of a neutral point, can be grounded. See fig 1c. This is normally only considered for systems ofvery limited extent e.g., the delta connected, stabilising winding of an auto-transformer which is eithernot used to supply load or which only supplies the local station auxiliary load.

The various available ways of grounding the system can each result in different levels of current andvoltage stress.

It is the purpose of this article to assist the planning engineer in deciding how to select the groundingmethod most suited to his needs. The basic reasons for grounding or not grounding are presented, andthe general practices and methods of grounding are reviewed. The SAIEE Workshop on neutralearthing at CSIR in June 1980 resulted in the recommendation of 300A earthing at medium voltages.inSouth Africa under the SABS Code of Practice 0200-1985 for Neutral Earthing of MV IndustrialPower Systems.

1.2 Definitions

The following varieties of system grounding are possible:-

1.2.1 Solid grounding

No intentional impedance in the grounding path (see note 2 on page 4)

1.2.2 Effective grounding

Based on the criterion that reduced insulation levels and reduced rated (80%) surge arresters can beused. (See note 1 on page 4) .

RO ≥ X1 and X0 ≤ 3X1

RO = Zero sequence resistance

X0 = Zero sequence reactance

X1 = Positive sequence reactance

1.2.3 Reactance grounding

Intentional insertion of reactance in the grounding path.

X0 ≤ 10 X1

Page 4: Earthing of Electrical Systems

4

1.2.4 Low Resistance Grounding

Intentional insertion of resistance into the system grounding path.

R0 ≥ 2 X0

1.2.5 High Resistance Grounding

The insertion of nearly the highest permissible resistance in the grounding connection.

R0 ≤ XC0/3

1.2.6 Grounding for serving line-ground loads

Z0 ≤ Z1

1.2.7 Ungrounded

No intentional system grounding connection.

1.2.8 Effects of method of Grounding

The typical levels of available ground fault current that can be expected from these types of systemgrounding are:-

1) Solidly grounded, effectively grounded and grounded for serving line-ground loads can result inthe same order of ground fault current as is available for three-phase short circuits usually ofthe order of several thousands of amperes.

2) Reactance grounded. Ground fault currents range from 25% to 60% of the three-phase level.These correspond to X0/X1 ratios of 10 and 3

3) Low resistance grounded: from as low as 50 amperes up to several thousand amperes.

4) High resistance grounded: ground fault currents up to 50 amperes. Usually less than 10amperes.

It must immediately be obvious that, the higher the level of ground fault current that can be expectedfrom the grounding method, the faster the protection must operate if excessive thermal damage is to beavoided.

If the grounding method limits the ground fault currents to very low levels, the protection can beslower in operation but the need for greater sensitivity increases. However, the protection must not betoo slow as to allow the ground fault to develop into a phase to phase fault.

Page 5: Earthing of Electrical Systems

5

There is always a trade-off between current stress and voltage stress. If you limit the current stress, yourun the risk of introducing voltage stress and also increase the relaying difficulty. The prime objectiveof system grounding is to limit current stress without introducing unacceptable voltage stress orrelaying difficulty.

1.2.8.1..Effectively Grounded.

Grounded through a grounding connection of sufficiently low impedance (inherent or intentionallyadded or both) that ground faults which may occurcannot build up voltages in excess of limitsestablished for apparatus, circuits, or systems so grounded.

NOTE 1 .

An A.C. system, or portion thereof, may be said to be effectively grounded when, for all points on thesystem or a specified portion thereof, the ratio of zero-sequence reactance (X0) to positive-sequencereactance (X1) is not greater than 3 and the ratio of zero-sequence resistance (R0) to positive-sequencereactance (X1) is not greater than 1.0 for any condition of operation and for any amount of connectedgenerator capacity. This definition is basically used in the application of line-to-neutral surge arresters.Surge arresters with less than line-to-line voltage ratings (80% arrestors) are applicable on effectivelygrounded systems. Insulation cost can be reduced by the use of effective earthing, but at the expense ofrelatively high fault current levels.

1.2.8.2..Grounded System.

A system of conductors in which at least one conductor or point (usually the middle wire or neutralpoint of a transformer or generator winding) is intentionally grounded, whether solidly or through acurrent-limiting device.

NOTE 2 Various degrees of grounding have been used, from solid or effective to the high-impedancegrounding obtained from a small grounding transformer erroneously used only to secure enoughground current for relaying, or to the high-resistance grounding which secures control of transientovervoltages but may not furnish sufficient current for ground-fault relaying. Figs,lb and lc show twopoints at which a system may be grounded and the corresponding voltage relationships.

1.2.8.3 Solidly grounded.

Grounded through an adequate ground connection in which no impedance has been insertedintentionally.

NOTE 3.

This term, though commonly used, is somewhat confusing since a transformer may have its neutralsolidly connected to ground, and yet the connection may be so small in capacity as to furnish only avery-high-impedance ground to the system to which it is connected. In order to define groundingpositively and logically as to degree, the term effective grounding has come into use. The term solidlygrounded will, therefore, be used only in referring to a solid metallic connection from system neutral toground; that is, with no impedance intentionally added in the grounding circuit. It does not imply thatthe system is necessarily effectively grounded.

Page 6: Earthing of Electrical Systems

6

1.2.8.4 Ungrounded.

A system, circuit, or apparatus without an intentional connection to ground except through potential-indicating or measuring devices or other very- high-impedance devices and the system capacitance.

NOTE 4.

Though called ungrounded, this type of system is in reality coupled to ground through the distributedcapacitance of its phase windings and conductors. In the absence of a ground fault, the neutral of anungrounded system, under reasonably balanced load conditions, will usually be close to groundpotential, being held there by the balanced electrostatic capacitance between each phase conductor andground. Fig. la shows an ungrounded system with voltage relations for balanced phase-to-groundcapacitances.

1.3 Factors Influencing Choice of Grounded or Ungrounded System

1.3.1 Service Continuity

As already indicated, a great number of industrial plant distribution systems have been operatedungrounded at one or more voltage levels for may years. In most cases this was done with the thoughtof gaining an additional degree of service continuity. The fact that any contact occurring between onephase of the system and ground is unlikely to cause an immediate outage to any load may represent anadvantage in many plants, varying in its importance according to the type of plant.

For the first grade shut-down supplies at Koeberg nuclear power station it is vital that the supplies areavailable even if a ground-fault should occur. The licensing authorities insist that the auxiliary systemsproviding these supplies must not be grounded. They claim that the zero-sequence capacitance of thesystem is so low that arcing fault currents will be self extinguishing. There should, therefore, be nodanger of arcing grounds causing excessive overvoltages, and multiple ground-faults.

Grounded systems, in most cases, are designed so that circuit protective devices will remove a faultycircuit from the system regardless of the type of fault. A phase-to-ground fault generally results in theimmediate isolation of the faulted circuit with the attendant outage of the loads on that circuit.However, experience has shown (4), in the greatest number of systems, that greater service continuitymay be obtained with grounded-neutral than with ungrounded-neutral systems.

1.3.2 Multiple Faults to Ground

We have seen that while a ground-fault on one phase of an ungrounded system generally does notcause a service interruption, the occurrence of a second ground fault on a different phase, before thefirst fault is cleared does result in an outage. If both faults are on the same feeder, that feeder will beopened. If the second fault is on a different feeder, both feeders may have to be de-energized.

The longer a ground is allowed to remain on an ungrounded system, the greater is the likelihood of asecond ground occurring on another phase, resulting in an outage. The advantage of an ungroundedsystem, in not immediately dropping load upon the occurrence of a ground fault, may largely bedestroyed by the practice of ignoring a ground until a second one occurs and repairs are required torestore service. With an ungrounded system it is extremely important that an

Page 7: Earthing of Electrical Systems

7

organised maintenance programme be provided so that grounds are located and removed as soon aspossible after their detection.

An adequate detection system, possibly in conjunction with an audible alarm, is considered essentialfor operation of an ungrounded system. In addition, it is advisable in ungrounded systems to employground-fault tracing equipment which permits maintenance personnel to locate a ground with thesystem energised and without the necessity of interrupting service on any circuit during the process offault locating.

Experience has shown that multiple “cross country” ground faults are rarely, if ever, experienced ongrounded-neutral systems. A possible exception to this rule is the case of double circuit overhead lineswhere high power footing resistances can result in a ground fault on both circuits due to a lightningstroke to the tower. This is a double “back-flash”.

1.3.3 Arcing Fault Burndowns

In recent years, especially in low-voltage power systems, there have been many reported cases ofarcing fault burndowns in which severe damage to or complete destruction of electrical equipment hasbeen caused by the energy of arcing fault currents (5). In typical cases an arcing fault becomesestablished between two or more phase conductors in an ungrounded system, or between phaseconductor(s) and ground in a solidly grounded-neutral system. The fault arc causes the release ofenormous amounts of energy at the fault site, resulting in the violent generation of hot gases and arcplasma. The accompanying heat is so intense that it vaporises copper or aluminium conductors andsurrounding steel enclosures and distills toxic and flammable gases from organic insulation systems.Frequently, the devastation is so complete that the equipment involved must be totally replaced.

It is characteristic of arcing fault burndowns that the normal phase-overcurrent devices do not operateto remove the initial fault quickly. Arcing fault current levels may be so low that such devices areeither not actuated at all (fault currents are below pickup settings) or are actuated only after a longperiod of time, too late to prevent burndown.

It is generally recognised that prevention of arcing fault burndowns, at the present state of protectivesystem design, must rely upon fast and sensitive detection of the arcing fault current, accompanied byinterruption of the faulty circuit within approximately 5 to 20 cycles, (100-400ms). In the solidlygrounded-neutral system, this fast, sensitive detection is possible since an arcing fault will produce acurrent in the ground path, either because the fault begins as a line-to-ground fault or because it willalmost instantly involve ground even though initiated as a line-to-line arcing fault. Under normal(nonground fault) conditions there is no significant current in the ground return path; therefore,monitoring the solidly grounded-neutral system for currents in the ground circuit provides an easymeans for detecting and removing destructive arcing faults to ground. This type of protection isuniversally applicable throughout the power system, and the sensitivity and speed of such relaying isindependent of load current values and phase-overcurrent device settings. Relays are being introducedwhich recognise the high frequency signature of an arcing ground fault

Thus, the solid and low-resistance grounded-neutral systems provide a basis for easily securingprotection against ruinous (phase-to-ground) arcing fault burndowns. The ungrounded and high-impedance grounded systems, on the other hand, while generally being less likely to experience arcingfaults, provide less protection against arc blast and flash hazard. No system has completely reliable anduniversally applicable means of protection against low-level line-to-line arcing fault burndowns.

1.3.4 Location of Faults

Page 8: Earthing of Electrical Systems

8

On an ungrounded system, a ground fault does not open the circuit. Some means of detecting thepresence of a ground on the system should be installed. Voltage transformers connected to indicate thepotential from each phase to ground will show the presence of a ground fault and which phase isinvolved, but will not show on which feeder the fault has occurred. Locating a ground fault on one ofthe several feeders may require the removal from service of one feeder at a time until the grounddetector indicates that the faulted feeder has been removed from the system. Should it happen that thesame phase of two different feeders becomes faulted to ground at the same time, the faulted feederscannot be located by removing them from the system one at a time. It may be necessary to remove allfeeders and restore them to service one at a time, checking the ground detector as each feeder isrestored. Such detection methods inevitably result in considerable disruption of the supply continuity.

The location of a grounded feeder on an ungrounded system may be facilitated by use of various typesof locating apparatus. For example, an interrupted direct voltage or superimposed audio signal may beapplied to the feeder bus and the tracing current detected in the grounded feeders. Some operators havereported success using 1ocation apparatus not requiring the deenergizing of system feeders.

This, of course, has the advantage of permitting location of grounds without waiting for light loadperiods on the system.

An accidental ground on a grounded system is both indicated and at least partially located by anautomatic interruption of the accidentally grounded circuit or piece of equipment.

1.3.5 Safety

Many of the hazards to personnel and property existing in some industrial electrical systems are theresult of poor or nonexistent grounding of electrical equipment and metallic structures. It is importantto note that regardless of whether or not the system neutral is grounded, safety considerations requirethorough grounding of equipment and structures.

Proper grounding of a low voltage (600 V or less) distribution system may result in less likelihood ofaccidents to personnel than leaving the system supposedly ungrounded. The knowledge that a circuit isgrounded generally will result in greater care on the part of the workman.

It is erroneous to believe that on an ungrounded system a person may contact an energized phaseconductor without personal hazard. As Fig. la shows, an ungrounded system with balanced phase-to-ground capacitance has normal line-to-neutral voltage existing between any phase conductor andground. To contact such a conductor accidentally or intentionally, may present a serious, perhapslethal, shock hazard in most instances. The capacitve current which can flow may be in the order ofamps at medium voltages.

During the period a ground fault remains on one phase of an ungrounded system, personnel contactingone of the other phases and ground are subjected to voltage 1,73 times that which would beexperienced on a solidly neutral-grounded system. The voltage pattern would be the same as shown inFig. lc.

Other hazards of shock and fire may result from inadequate grounding of equipment in either groundedor ungrounded systems. Accidental grounds are inevitable. The current path to ground for a winding-to-frame insulation breakdown in a motor may include greasy shavings or other materials that would beignited by sparks or localised heating. Such a high-impedance ground circuit may not permit enoughcurrent flow to operate protective devices, with the result that a potential fire and safety hazard mayexist for some time. There is the hazard of shock to personnel from such a condition should they bridge

Page 9: Earthing of Electrical Systems

9

all or part of the high-impedance ground path, for example, contacting the frame of the faulty machine.This hazard is particularly bad because there are more possible victims than in the case of personsfamiliar with electric systems working on a circuit.

1.3.6 Abnormal Voltage Hazards

The posssible overvoltages on the ungrounded system may cause more frequent failure of equipmentthan if the system were grounded. In some cases these overvoltages have caused failures on more thanone unit of equipment at the same time. These multiple failures are not necessarily confined to onefeeder but may involve equipment on several different feeders.

A fault on one phase of an ungrounded system places a sustained increased voltage on the insulation ofungrounded phases in a three-phase system. This overvoltage is 1,73 times the voltage normally on theinsulation. This or other sustained overvoltages or the transient overvoltages on the ungrounded systemmay not immediately cause failure of insulation, but may tend to reduce the life of the insulation.

The reduced overvoltages experienced on grounded systems are less likely to damage equipment orinsulation.

1.4 Power System 0vervoltages (See Refs. 9, ch 5).

Some of the more common sources of overvoltage on a power system are the following:

(1) Lightning(2) Switching surges(3) Static(4) Contact with a higher voltage system(5) Line-to-ground faults(6) Resonant conditions(7) Restriking ground faults

1.4.1 Lightning (See Ref,10)

Most industrial systems are effectively shielded against direct lightning strokes. Many circuits areeither underground in ducts or within grounded metal conduits or race-ways. Even open-wire circuitsare often shielded by adjacent metallic structures and buildings. Surge arresters applied at the incomingservice, limit the surge voltages within the plant resulting from strokes to the exposed service lines,other arrester applications may be necessary within the plant to protect low impulse strength devicessuch as rotating machines. Where a plant is supplied from a substation stepping down from somehigher voltage, surge arresters may be required on the low side of the transformer to protect plantequipment from surges passed by the high side arresters and reflected through the transformer.

On the power system there are many thousands of kilometres of overhead lines and transformers etc.,directly exposed to lightning. The protection of this plant against lightning overvoltages is a separatestudy. The system grounding does, however, have some influence on lightning arrester applicationsince it affects the system insulation level required. All forms of grounding, other than effectivegrounding, require the use of 100% arresters. The arrester ratings are based on the "sound phase"voltages which can arise during a ground-fault on one phase. These voltages exceed 80% of the normalsystem line-line voltage for all forms of grounding other than effective grounding.

Page 10: Earthing of Electrical Systems

10

For the latter case, arresters having 80% of the reseal value of those for non-effectively groundedsystems, can be used. This permits the use of lower system insulation levels.

1.4.2 Switching Surges

Normal switching operations in the system can cause overvoltages. These are generally not more thanthree times normal voltage and are of short duration. Overcurrent devices such as circuit breakers orfuses, in general, interrupt a circuit at a normal current zero at which time the stored energy in theinductance of the circuit is zero.

The overvoltages thus developed result from transient oscillation in the circuit capacitance andinductance, there being stored energy in the circuit capacitance at the time of current interruption. Moreserious overvoltages can be produced by devices which interrupt by forcing current zero. Such devicesas current-limiting fuses must be carefully applied because of this overvoltage problem. In low-voltagesystems, however, the standards for current-limiting fuses require that the maximum peak voltageoccurring during circuit interruption shall not exceed 3000 V; this is less than the crest of the normalhigh-potential voltage applied to 600-V class equipment.

Neutral grounding is not likely to reduce the total magnitude of overvoltage produced by lightning orswitching surges. It can, however, distribute the voltage between phases and reduce the possibility ofexcessive voltage stress on the phase-to-ground insulation of a particular phase.

1.4.3 Static

Buildup of overvoltage on power system conductors due to static charge is not usually a problem inmodern plants with metal-enclosed circuits and equipment. Static charge on moving belts can build upvoltages which can be transmitted to the power system unless motor frames are properly grounded.0verhead open-wire lines may be subject to static overvoltages resulting from certain atmosphericconditions. A system ground connection, even of relatively high resistance, can effectively preventstatic voltage buildup.

1.4.4 Contact with Higher Voltage System

Contact with a higher voltage system may be caused by a broken high-voltage conductor falling on alower voltage conductor where both lines cross or are carried on the same poles, or by breakdownbetween the high- and low-voltage windings of a transformer. If the low-voltage system is ungrounded,the high voltage will remain on the low-voltage system causing breakdown of insulation, possibly atseveral points. An effectively grounded low-voltage system, though resulting in high values of faultcurrent for this condition, will hold the system neutral close to ground potential and greatly reduce theovervoltages to ground on the low-voltage system.

1.4.5 Line-to-ground Faults

A common source of sustained overvoltage on an ungrounded system is caused by one phase of athree-phase system becoming grounded. In this case the insulation of the other phases is subjected to1.73 above normal voltage. An effectively grounded-neutral system would not result in thisovervoltage. While this voltage seldom approaches the insulation levels of equipment and circuits, thecumulative effect of higher than normal voltage stresses may somewhat reduce insulation life.

Page 11: Earthing of Electrical Systems

11

1.4.6 Resonant Conditions

An ungrounded system may be subjected to resonant overvoltages. With the high phase-to-groundcapacitance of larger systems, there may be a condition of approximate circuit resonance during a line-to-ground fault through an inductance such as a faulty coil in a motor starter. The voltage to ground ofthe unfaulted phases will then be considerably in excess of line-to-line voltage. An overvoltage due toresonant or near-resonant conditions can be encountered on a small system where tuned inductive-capacitive circuits are used for such purposes as operation of welders. For example, if the welder isequipped with a series capacitor for power factor improvement, the voltage across the capacitor andacross the transformer winding are each many times the supply line-to-line voltage. A fault between thecapacitor and the welder transformer imposes this high voltage on the insulation of the ungroundedsystem. A grounded-neutral system would prevent this overvoltage by holding the phases to theirapproximate normal voltage to ground.

Ferro-resonant conditions can also cause excessive overvoltages if the system is grounded through ahigh inductance which can saturate. Such an inductance might arise if the system is grounded through arelatively small transformer such as a voltage transformer or neutral earthing compensator (NEC, nowcalled a neutral electromagnetic coupler).

Transient saturation of the iron core of the grounding device results in a value of inductance whichresonates with the system zero-sequence shunt capacitance. The overvoltages are produced by aphenomenon known as "neutral inversion". Due to the resonant condition, the system neutral movesoutside of the system voltage triangle and the phase-ground voltages can be as high as 5-8 times thenormal values. The phenomenon is illustrated in Figs 2 a & b Reference 14,15.

1.4.7 Restriking Ground Faults

Field experience and theoretical studies have shown that arcing, restriking, or vibrating ground faultson ungrounded systems, can under certain conditions, produce surge voltages as high as six timesnormal.

The conditions necessary for producing these overvoltages require that the dielectric strength of the arcpath builds up at a higher rate after each extinction of the arc than it did after the preceding extinction.This phenomenen is unlikely to take place in open air between stationary contacts because such an arcpath is not likely to develop sufficient dielectric recovery strength. It may occur in confined areaswhere the pressure may increase after each conduction period. Neutral grounding is effective inreducing transient voltage buildup from such intermittent ground faults by reducing neutraldisplacement from ground potential and reducing the destructive effectiveness of any high-frequencyvoltage oscillations following each arc initiation or restrike.

Resistance grounding is particularly effective since it provides the necessary damping to preventvoltage build up.

1.5 Cost

Grounded-neutral systems may cost from nothing to several percent more than ungrounded-neutralsystems, depending upon system voltage and whether the system to be grounded is an existing or a newsystem. Equipment for 380/220-V star-connected systems almost universally provides for systemneutral grounding and therefore does not involve any extra cost. Star-connected unit substations for

Page 12: Earthing of Electrical Systems

12

grounding 500-V systems are standard but may cost up to 6 percent more than delta-connectedsubstations. In addition, there is the cost of the resistor or other grounding impedance, if used, and thepossible additional cost of relaying.

For system voltages of 3,3/6,6/11/22/44 kV delta-connected transformers are common. Therefore, thereis generally a transformer price increase for grounding these systems. The grounding resistor andground relaying represent an extra cost.

Systems from 66kV upwards are usually star-connected and effectively grounded in this country.

Considerable savings in cost of the transformer insulation can be effected at these voltages by usinggraded insulation. There is no additional cost associated with grounding such systems.

To change existing systems to grounded operation may be very expensive because it may be necessaryto add grounding transformers and their protective equipment, grounding impedance if required, andpossibly a third current transformer in all circuits to obtain ground-fault relaying on all three phases.

1.6 Trends in Application of System Grounding

The basic reasons for system grounding are the following:

(1) To limit the difference of electric potential between all uninsulated conducting objects in alocal area.

(2) To provide for isolation of faulty equipment and circuits when a fault occurs.

(3) To limit overvoltages appearing on the system under various conditions.

As previously stated many industrial power system operators believe that an ungrounded system offersgreater service continuity than a grounded system, because a line-to-ground fault does not causeimmediate tripping of the faulted circuit. On the other hand, a second ground fault on another phase ofanother circuit from the original fault causes a phase-to-phase fault, large short-circuit current flow(with attendant hazards), and tripping of both faulted circuits.

Consequently, a major factor to consider in selecting a grounded or ungrounded system is the quality ofelectrical maintenance available. Well-maintained ungrounded systems, in which the first ground faultis promptly located and corrected, probably have greater service continuity than solidly groundedsystems.

Great care must be taken to ensure that the zero sequence capacitance of such ungrounded systems islow or serious overvoltages could arise (Figs.3a & 3b & 4a) (Refs. 14 chapter 1 and Refs. 16 chapter6).

Ungrounded systems are definitely not recommended unless a full transient overvoltage study indicatesthat they will not produce excessive overvoltages.

However, many users whose maintenance practices are not quite so extensive feel that a grounded-neutral system gives them more continuous service than an ungrounded system.

There has been an increasing trend toward grounding industrial systems in order to overcome some ofthe disadvantages attributed to ungrounded operation. In recent years a substantial percentage of new

Page 13: Earthing of Electrical Systems

13

industrial substation transformers have been purchased with star-connected low-voltage windings withinsulated neutral brought to external termination suitable for neutral grounding.

In new installations, these transformers offer the advantage that they can be operated ungrounded,while having the neutral available for grounding, if desired, at some future time. After the SAIEEWorkshop of 1980, the recommended practice is resistive grounding of MV systems, limited to 300Aper transformer or grounding point

1.6.1 High-Voltage systems (above 66 kV)

Systems above 66kV are nearly always solidly grounded, because these are usually transmissioncircuits with open lines in which, in most cases, grounded-neutral-type (80%) lightning arresters aredesirable for better overvoltage protection and lower cost. In addition, rotating equipment is seldomconnected directly to these systems; hence, limited ground-fault current, to prevent burning oflaminations, is a less important factor than in the medium-voltage systems. Inaddition, voltages above 66kV are not usually carried inside buildings; hence shock hazards due tohigh fault currents are not a factor. Finally, the cost of grounding resistors at these voltages is high.

1.6.2 Industrial vs. Utility Practice

The characteristics and operation of industrial power systems differ in some respects from thoseencountered in utility systems; therefore it may be expected that grounding practices would also bedifferent. Such is the case, although the basic principles of neutral grounding are followed in both typesof systems.

A comparison of the pertinent characteristics of the two types of systems is given and summarized inTable I.

Utility practice in recent years has followed the recommendation of 300A resistance grounding. Manysuch networks feed industrial or municipal systems. This method requires the use of ungrounded-neutral-type lightning arresters and reduced ground fault currents. Solid grounding offers savings inthe use of graded insulation in transformers at 66kV and above. A large percentage of ground faults onutility systems occurs as insulator flashovers on overhead lines and the high ground-fault current due tosolid grounding does not cause expensive damage to equipment at the point of fault.

In the case of industrial power systems, resistance grounding is preferred for voltage levels from 2,2 to33kV. The principal reason for this practice is to ensure reduced magnitudes of ground-fault currentand consequent reduction in possible damage at the point of fault. This is a particularly importantfactor in the case of ground faults in the windings of motors and generators. Although a ground fault oflimited magnitude and duration may cause sufficient damage to require the replacement of severalcoils, the desired result is obtained when the damage is confined to the coils and the machinelaminations are left intact.

Page 14: Earthing of Electrical Systems

14

TABLE 1 Industrial vs. Utility Grounding Practice

Industrial UtilityDesirability of high continuity ofpower

Yes Yes

Predominant method of conductingpower

Cable Overhead lines

Percent of system subject tolighning hazard

Small Large

Investment in lightning arresters Small LargePredominance of voltage levelsabove 11kV

Few systems Many systems

Rotating equipment at distributionand transmission levels

Yes in most cases Not in the usual case

1.7 Methods of System Grounding of the System Neutral

Most grounded systems employ some method of grounding the system neutral at one or more points.These methods (see Fig.4) are referred to as the following:

(1) Solid grounding see fig 4b(2) Resistance grounding see fig 4e(3) Reactance grounding see fig 4 d(4) Ground-fault-neutralizer grounding see fig 4c

Table II Sytem Characteristics with Various Grounding MethodsUngrounded Essentially solid grounding Reactance

groundingGround-faultneutralizer

Resistancegrounding

Solid Low-valuereactor

High-valuereactor

Resistance

Current for phase-to-ground fault inpercent of three-phase fault current

Less than 1% Varies,may be100% orgreater

Usuallydesigned toproducte 25to 100%

25 to 60 %for X0/X1 of10 to 3

Nearly zerofault current

5 to 20 %

Transientovervoltages

Very high Notexcessive

Notexcessive

Very high Not execessive Notexecessive

Automaticsegregation offaulty zone

No Yes Yes Yes No Yes

Lightning arrestors Ungrounded-neutral type

Grounded-neutraltype

Grounded-neutral typeif current is60 % orgreater

Ungrounded-neutral type

Ungrounded-neutral type

Ungrounded-neutral type

Remarks Not recom-mended due toovervoltagesand non-segregation offault

Generally used on systems(1) 600 volts and belowand (2) over 15 kV

Notrecommended due toexcessiveovervoltages

Best suited forhigh-voltageoverhead lineswhere faultsmay be self-healing

Generallyused onindustrialsystems of2,2 to 33kV

Table II gives the characteristics of the different methods of grounding.

Page 15: Earthing of Electrical Systems

15

Each method, as named, refers to the nature of the external circuit from system neutral to ground ratherthan to the degree of grounding. In each case the impedance of the generator or transformer, whoseneutral is grounded, is in series with the external circuit. Thus, a solidly grounded generator ortransformer may or may not furnish effective grounding to the system, depending on its impedance.

1.7.1 Solid Grounding

Solid grounding (fig 4b) refers to the connection of the neutral of a generator, power transformer, orgrounding transformer, directly to the station ground or to the earth. Because of the reactance of thegrounded generator or transformer in series with the neutral circuit, a solid ground connection does notprovide a zero-impedance neutral circuit.

It is most important to realise that if the reactance of the generator or transformer is too great withrespect to the total system reactance, the objectives sought in grounding, principally freedom fromtransient overvoltages, may not be achieved. Thus, it is necessary to determine the degree of groundingprovided in the system. A good guide in answering this question is the magnitude of ground-faultcurrent in relation to the three-phase fault current, the higher the ground fault amount in relation to thethree-phase current, the greater the degree of grounding in the system. In terms of resistance andreactance, effective grounding of a system has been defined in Note 1.

In most generators, solid grounding, that is without external impedance, may permit the maximum ground-fault current from the generator to exceed the maximum three-phase fault current which the generator candeliver and for which its windings are braced. Consequently, neutral-grounded generators should begrounded through a reactor which will limit the ground-fault current to a value no greater than the generatorthree-phase fault current. A generator has a lower zero sequence impedance than positive sequenceimpedance.

Most modern large generators are unit-connected with their step-up transformers.

The generator transformer LV winding is delta-connected and, together with the generator, forms an"island" whose earthing can be decided on the basis of minimising the stator iron damage caused byearth faults. High resistance or resonant grounding is most common. Refs. (1) .......

Surge arresters for grounded-neutral service (rated near but not less than 80% of line-to-line voltage)require that the system be effectively grounded. This will carry with it a line-to-ground circuit currentof at least 60% of the three-phase short-circuit value.

1.7.2 Resistance Grounding

In resistance grounding (fig 4e), the neutral is connected to ground through one or more resistors. Inthis method, with the resistors normally used and excepting for transient overvoltages, the line-to-ground voltages which exist during a line-to-ground fault are nearly the same as for an ungroundedsystem.

A system properly grounded by resistance is not subject to destructive transient overvoltages. Forresistance-grounded systems at 15 kV and below, such overvoltages will not ordinarily be of a seriousnature, unless the resistance exceeds the following boundary limits:

Page 16: Earthing of Electrical Systems

16

R0 ≤ XC0 /3, R0 ≥ 2 X0 .

Resistance grounding may be either of two classes, high resistance or low resistance, distinguished bythe magnitude of ground-fault current permitted to flow. Both types are designed to limit transientovervoltages to a safe level (within 250% of normal); however, the high-resistance method usuallydoes not require immediate clearing of a ground fault since the fault current is limited to a very lowlevel. This low level, typically in the order of 5 A, must be at least equal to the system totalcapacitance-to-ground charging current, 3 x IC0/phase. The protective scheme associated with high-resistance grounding is often detection and alarm rather than immediate tripout. Generally, the use ofhigh-resistance grounding with alarm only should be avoided on systems where the line-to-ground faultcurrent exceeds 10 A.

The low-resistance method has the advantage of immediate and selective clearing of the groundedcircuit but requires that the minimum ground-fault current be large enough, usually 300A or more, toactuate the applied ground-fault relay positively. High-resistance grounding is a method that can beapplied to existing medium-voltage ungrounded systems to obtain the transient overvoltage protectionwithout the modification expense of adding ground relays to each circuit.

Systems grounded through resistors generally require surge arresters suitable for use on ungrounded-neutral circuits, that is, with a voltage rating at least equal to line-to-line voltage.

The reasons for limiting the current by resistance grounding may be one or more of the following:

(1) To reduce burning and melting effects in faulted electric equipment such as switchgear,transformers, cables and rotating machines.

(2) To reduce mechanical stresses in circuits and apparatus carrying fault currents.

(3) To reduce electric-shock hazards to personnel caused by stray ground-fault currents in theground return path.

(4) To reduce the arc blast or flash hazard to personnel who may have accidentally caused or whohappen to be in close proximity to the ground fault.

(5) To reduce the momentary line voltage dip occasioned by occurrence and clearing of a groundfault.

(6) To secure control of transient overvoltages while at the same time avoiding the shutdown of afaulty circuit on the occurrence of the first ground fault (high-resistance grounding).

(7) Slower and therefore cheaper ground-fault protection can be used.

(8) Practically negligible fault-breaking duty on circuit breakers clearing ground-faults - thereforeless maintenance.

(9) Reduced telephone interference.

Page 17: Earthing of Electrical Systems

17

1.7.3 Reactance Grounding.

The term reactance grounding (fig 4e) describes the case in which a reactor if connected between thesystem neutral and ground or where a neutral electromagnetic coupler (NEC) or grounding transformer,having its neutral directly grounded, is provided. The value of the zero-sequence reactance of thesegrounding devices is usually chosen to satisfy the requirement that

X0/X1 ≤ 10.

Since the ground-fault current which may flow in a reactInce-grounded system is a function of theneutral reactance, the magnitude of ground-fault current is often used as a criterion for describing thedegree of grounding. In a reactance-grounded system, the available ground-fault current should be at

least 25 percent (X0/X1 ≤ 10) and preferably 60 percent (X0/X1 ≤ 3) of the three-phase fault current

to prevent serious transient overvoltages (both satisfy X0 ≤ l0X1 ). This is considerably higher thanthe minimum fault current desirable in a resistance-grounded system and, therefore, reactancegrounding is usually not considered an alternative to resistance grounding.

1.7.4 Ground-Fault Neutralizer (Petersen coil) (See Ref.11).

A ground-fault neutralizer (fig 4c) is a special case of a reactor connected between the neutral of asystem and ground and having a specially selected, relatively high value of reactance. It should benoted that failures in solid insulation such as paper, varnished cambric, and rubber are not self-healing,as insulator flashovers can be, and are not extinguished by the use of the ground-fault neutralizer. SeeFig. 5

A line-to-ground fault causes line-to-neutral voltage to be impressed across the neutralizer, whichpasses an inductive current. This current is 180ø out of phase and is approximately equal in magnitude(when the neutralizer is tuned to the system) to the resultant of the system-charging current of thecapacitance of the two unfaulted phases.

The inductive and capacitive components of current neutralize each other, and the only remainingcurrent in the fault is due to resistance, insulator leakage, and corona. This current is relatively small,and, as it is in phase with the line-to-neutral voltage, the current and voltage pass through a zero valueat the same instant. In addition, the rate of rise of recovery voltage on the faulted phase is very low.Therefore, the arc is extinguished without restriking, and flashovers are quenched without removingthe faulted line section from service.

On systems for which ground-faults in air are relatively frequent, ground- fault neutralizers may bevery useful by reducing the number of circuit breaker operations required to remove faults, thusimproving service continuity. They have been used primarily on systems above 15 kV consistinglargely of overhead transmission lines. They have also been used on unit connected generators andgeneration transformers.

In some cases, where it has not been deemed desirable by the plant operators to trip a circuit on theoccurrence of a ground fault, special arrangements have been used to limit the damage due to the flowof charging current and yet be able to locate the faulty feeder easily. One method is to use a ground-fault neutralizer in the neutral to limit the ground-fault current and to reduce switching surges to safevalues. In some cases it may be desirable to pass enough ground-fault current to operate relays that

Page 18: Earthing of Electrical Systems

18

give a signal or trip the breaker of the faulty feeder. This is done by a current-sensing relay incombination with a resistor in parallel with the neutralizer. Because of the current to be switched, apower circuit breaker should be used for switching the resistor. The resistor and relay are selected as ifonly the resistor were used, such a scheme is expensive and is employed only in very special cases.

One of the characteristics of resonance-grounded systems is that care must be taken to keep theground-fault neutralizer tuned to the system capacitance to minimize the development of transientovervoltages. Thus, when sections of the system are switched on or off, it may be necessary toadjust the neutral reactance by changing the neutralizer tap. This operation may be accomplishedby providing in the powerhouse an ammeter and control switch for remote control of a motor-driven tap changer on the neutralizer, so that when parts of the system are switched, the neutralizermay be readjusted at that time.

Self tuning reactors are now available in the market, but the cost needs to be weighed against theadvantages of the earthing with a neutralizer.

1.8 Grounding at Points other than System Neutral

In some cases, systems, particularly low-voltage systems (600 V and below), are grounded at somepoint other than the system neutral. This has been done to obtain a grounded system at a minimumexpense where existing delta transformer connections do not provide access to the system neutral.

1.8.1 Corner-of-the-Delta Grounding

In some systems of limited physical extent, grounding of one phase or"corner-of-the delta" hassometimes been done as a means of obtaining a grounded system. (see Fig 1c) A particular casewhere this has been fairly extensively used in the Eskom network is for grounding the deltastabilising winding of HV auto-transformers.

By this means the LV system is grounded and ground faults can be detected and relayed withoutthe additional expense of NECS or other grounding devices. Usually the corner is connected toground via a current transformer which is often built into the power transformer.

It has the disadvantage that the normal line-ground voltages on two of the phases are higher thanthey would be for a neutral grounded system. Also, a fault to ground on one of the other phasesresults in fault currents of phase-fault magnitude.

1.9 Selection and Design of System Grounding Arrangements

The best way to obtain the system neutral for grounding purposes in three-phase systems is to usesource transformers or generators with wye-connected windings. The neutral is then readilyavailable.

The alternative is to apply grounding transformers.

Page 19: Earthing of Electrical Systems

19

1.9.1 Grounding Transformers

System neutrals will usually not be available in systems of 40kV and less. When existing delta-connected systems are to be grounded, grounding transformers may be used to obtain the neutral.Grounding transformers may be either of the zig-zag or star-delta connected type. The type ofgrounding transformer most commonly used is a three-phase zig-zag transformer with nosecondary winding. The internal connection of this transformer is illustrated in Fig.6a Theimpedance of the transformer to three-phase currents is high so that when there is no ground faulton the system, only a small magnetizing current flows in the transformer winding. The transformerimpedance to ground current, however, is low so that it allows high ground current to flow. Thetransformer divides the ground current into three equal components; these currents are in phasewith each other and flow in the three windings of the grounding transformer. The method ofwinding is seen from Fig 6b to be such that when these three equal currents flow, the current inone section of the winding of each leg of the core is in a direction opposite to that in the othersection of the winding on that leg.

This tends to force the ground-fault current to have equal division in the three lines and accounts forthe low impedance of the transformer-to-ground currents.

A star-delta-connected three-phase transformer or transformer bank can also be utilized for systemgrounding. As in the case of the zig-zag grounding transformer, the usual application is to accomplishreactance or resistance-type grounding of an existing ungrounded system. The delta connection must beclosed to provide a path for the zero sequence current and the delta voltage rating is selected for anystandard value. A resistor inserted between the primary neutral and ground, as shown in Fig.7 providesa means for limiting ground-fault current to a level satisfying the criteria for resistance-groundedsystems. For this arrangement, the voltage rating of the star winding need not be greater than thenormal line-to-neutral system voltage. For high-resistance grounding it is sometimes more practical oreconomical to apply the limiting resistor in the secondary delta connection. Three single-phasedistribution class transformers are used, with the primary star neutral connected directly to ground. Thesecondary delta is closed through a resistor which effectively limits the primary ground-fault current tothe desired low level. For this alternative application, the voltage rating of each of the transformerwindings forming the star primary should not be less than the system line-to-line voltage.

The rating of a grounding transformer, measured as the available system energy in kilovoltamperes, isequal to rated line-to-neutral voltage in kilovolts times rated neutral current. Most groundingtransformers are designed to carry their rated current for a limited time only, such as 10.0 s or 1.0 min.Consequently, they are much smaller in size than an ordinary three-phase continuously ratedtransformer with the same rating for the available system energy measured in kilovoltamperes.

A grounding transformer should be connected to the system in such a manner that the system willalways be grounded. Fig 8a shows a grounding transformer with an individual line breaker forconnection directly to the main bus of the system. Fig 8b shows a means of connecting a groundingtransformer to a system without an individual line breaker. In this case, the grounding transformer isconnected between the main transformer bank and its breaker. If the grounding ransformer is connectedas shown in Fig 8b, there should be one grounding transformer for each delta-connected banksupplying power to the system, or enough grounding transformers to assure at least one groundingtransformer on the system at all times. When the grounding ransformer is so connected, it is includedin the protective system of the main transformer.

If all grounded sources should trip, and the system grounding connection lost, any ungrounded sourcesshould be disconnected automatically. Thus ungrounded sources would be tripped if all groundingtransformer breakers in arrangement of Fig 8a should trip. If there are three or more transformers

Page 20: Earthing of Electrical Systems

20

feeding a bus and only two of these transformers have grounding sources, the ungrounded transformerswould be disconnected automatically if those with grounding transformers as per Fig 8b should havetheir associated breakers opened.

1.9.2 Suggested Grounding Methods, Low-Voltage systems (600 V and Below)

Low voltage systems are generally operated solidly grounded, one reason for this is that no expense isnecessary for reactors. Another reason is that low-voltage switchgear almost universally uses direct-acting series trip devices, such devices may require high current magnitudes to detect faults to ground,unless supplementary ground- fault relaying is used.

For these reasons, solid grounding is used extensively on systems rated 600 V and below. For suchsystems, it is especially important to provide low-impedance return paths for ground-fault currents inthe equipment grounding network. Provided the ground-fault current is not limited to a value less thanthe pickup value of the circuit breaker instantaneous trip, damage from high-fault-current magnitude isminimized because low-voltage protective devices are extremely fast in operation. If the fault is anarcing one, and the root-mean-square current is less than that required to operate the circuit breakerinstantaneous or short-time trip element, then ground-fault sensing may be required to prevent theburndown of equipment, as indicated earlier in this section.

1.9.3 Medium-Voltage Systems (3,3 to 33 kV)

Medium-voltage industrial power systems are usually resistance grounded. In this range of systemvoltages, limiting ground-fault current is highly desirable in the usual industrial power system.Connection of rotating machines directly at voltages of up to 11 kV is common, hence resistancegrounding is used to reduce the damage which may result due to a ground fault in the machinewindings.

In medium-voltage systems, when ground-fault protection is desired, it is provided by using a standardovercurrent relay connected in the residual circuit of the phase-current transformers or to a window ordoughnut-type (zero-sequence) core-balance current transformer which encloses all the phaseconductors. When any loads are connected line to neutral, then the window or doughnut-type currenttransformers must also enclose the neutral conductor. The cable sheath earthing strap must not passthrough the CT. Positive tripping can be accomplished with low magnitudes of ground-fault current.For this reason resistance grounding is commonly used except for those cases where the size of thesystem is so small that the maximum available fault current is not too high to be objectionable.

At the present time, there are 3,3-11 kV systems in operation without the system neutral adequatelygrounded. More and more engineers, however, are applying resistance neutral grounding to thesesystems.The conventional method is to provide sufficient ground-fault current to enable selectiverelaying through the application of residual or ground relays.

Some design engineers feel that it is desirable to ground the system neutral so that the ground-faultcurrent is of a very small magnitude, just enough to stabilize the neutral to prevent severe transientovervoltages upon the occurrence of restriking grounds. This does not cause a load shutdown due to aground fault, while at the same time it eliminates the transient-overvoltage hazard. It does not,however, eliminate all types of overvoltage. The value of ground-fault current permitted to flowshould be the same as, or somewhat greater than, the total system current (3x Ico) resulting from thecapacitive coupling to ground inherent in all elements of the system. Capacitively coupled-to-groundelements include cables, overhead lines, transformer and rotating machine windings, surge capacitors

Page 21: Earthing of Electrical Systems

21

(with their star point earthed), and power factor capacitors, Expressed in another manner, the kilowattrating of the resistor should be the same as, or somewhat greater than, the total available systemcharging energy to ground measured in kilovoltamperes. The high-resistance grounding practice couldbe employed with the circuits as shown in Fig.8. The only difference in the various methods ofresistance grounding is the amount of ground-fault current that flows. Where selective ground relayingis required, considerably higher values of ground-fault current are required.

1.9.4 High-voltage Systems (Above 66kv)

Systems above 66kv are nearly always effectively grounded, because these are usually transmissioncircuits with open lines in which, in most cases, grounded-neutral service surge arresters are desirablefor better overvoltage protection and lower cost. In addition, rotating equipment is seldom connecteddirectly to these systems; hence limiting ground-fault currents to prevent burning of laminations is aless important factor than in medium-voltage systems. In addition, voltages above 11kv are not usuallycarried inside buildings, hence personnel hazards due to high fault currents are not a factor. Finally, thecost of resistors for resistance grounding at these voltages is high.

The use of partially or fully graded insulation of the HV windings of transformers also requires that theassociated system is effectively earthed to make full use of grading.

1.10 Criteria for Limiting-Transient-0vervoltages (See Ref,12)

Transient overvoltages can be limited effectively to safe values if the following criteria are observed:

(1) In resistance-grounded systems, the resistor ground-fault current should be at least equal to, butpreferably greater than, the charging current of the system.

(2) In reactance-grounded systems the ratio of Xo/X1 should be 10 or less, where Xo is the zero-sequence inductive reactance of the system including that of the neutral reactance and X1 is thepositive-sequence inductive reactance of the system.

(3) Where a combination of grounding transformer and neutral- grounding resistor is used, thegrounding transformer impedance should be low relative to the neutral resistance. The ratio ofRo/Xo should be equal to or greater than 2, where Ro is the zero- sequence resistance of thecircuit, including the neutral resistor, and Xo is the zero-sequence inductive reactance of thecircuit, including that of the transformer and resistor.

1.11 Selection of System Grounding Points

1.11.1 Ground at Each Voltage Level

It is necessary to ground at each voltage level to achieve the advantages of neutral grounding in allparts of the system. (See Fig.9) For example, if the 11kV system in this diagram were not grounded,this level would have all the characteristics of an ungrounded system; at the same time, the 33-kV and380- volt levels would have the characteristics of grounded-neutral systems. Each voltage level may begrounded at the neutral lead of a generator, power transformer bank, or grounding transformer. Anygenerator or transformer used for grounding should, as far as possible, be one which is alwaysconnected to the system. Alternatively, a sufficient number of generators or transformers should begrounded to ensure there is at least one ground connection on the system at all times.

Page 22: Earthing of Electrical Systems

22

1.11.2 Ground at the Power Source and Not at the Load

The use of an available neutral at the load point, such as a star- delta step-down transformer or a star-connected motor, is not recommended as a point for system grounding. The principal disadvantage isthat a number of these load neutrals must be grounded to ensure that the system remains grounded ifone or more of these loads is out of service.

Consequently, ground-fault current may be excessively high when all grounded points are in service.Since power sources are fewer in number than loads and are less likely to be disconnected, they arepreferred as grounding points. (See Fig 10.)

Other disadvantages of grounding at the load are the following:

(1) Standard low-voltage unit substations have delta-connected primaries; therefore, specialtransformers are required if the primaries are to be used as grounding points.

(2) Since the ground-fault current is dependent on the number of feeders or grounding points inoperation, it may vary widely depending on system operating conditions. This makes selectiverelaying more difficult and may require additional directional ground relaying to avoid falsetripping of healthy feeder circuits.

1.11.3 Ground Each Major Source Bus Section

When there are two or more major source bus sections, each section should have at least one grounded-neutral point, since the bus-tie circuit may be open. If there are two or more power sources per bussection, there should be provision for grounding at least two sources on each section.

1.11.4 Neutral Circuit Arrangements

When the method of grounding and the grounding point have been selected for a particular powersystem, the next question to consider is how many generator or transformer neutrals will be used forgrounding and whether (1) each neutral will be connected independently to ground, or (2) a neutral buswith single-ground connection will be established.

1.11.5 Single Power Source

When a power system has only one source of power (generator or transformer), grounding may beaccomplished by connecting the source neutral to earth either directly or through a neutral impedance.Provision of a switch or circuit breaker to open the neutral circuit is not necessary because neutralcircuits have practically zero potential with respect to ground except during the short interval of a fault,hence breakdowns are not likely. Also, it is not desirable to operate the system ungrounded by havingthe ground connection open while the generator or transformer is in service. In addition, the neutralswitching equipment greatly increases the cost of grounding.

In the event that some means of disconnecting the ground connection is required in a particular case, ametal-clad circuit breaker should be used rather than an open disconnect switch for indoor installations.The latter is hazardous to personnel if a ground fault should occur at the time the switch is opened orclosed.

Page 23: Earthing of Electrical Systems

23

1.11.6 Multiple Power Sources

When there are only a few generators or power transformer banks at a station, individual neutralimpedances are frequently used. With this arrangement, the neutral of each generator or maintransformer bank is connected directly to its neutral impedance without intervening switchingequipment. No special operating instructions are required since each impedance is automaticallyconnected whenever this source is disconnected.

Where only two sources are involved, use of individual neutral impedances is preferable to the use of acommon ground impedance. When several sources are involved, however, the ground current isincreased each time a source is added and may be raised to levels which are undesirably high.

In the case of resistance grounding, each resistor must be rated for sufficient current to ensuresatisfactory relaying when operating independently. Consequently, the total ground current with severalresistors will be several times the minimum required for effective relaying.

When individual resistors are used, circulation of third-harmonic currents between paralleledgenerators is not a problem since the resistance limits the circulating current to negligible values.

When there are more than two or three generators or power-supply transformer banks at one station, itis possible to use only one resistor. Each power source is then connected to the resistor through aneutral bus and neutral switching equipment. This arrangement keeps the ground-fault current to apractical minimum, since the ground current from the station is never greater than can be suppliedthrough a single resistor. It also ensures the same value of ground current regardless of the number ofgenerators or transformers in use and simplifies ground relaying.

The primary purpose of the neutral breakers is to isolate the generator or transformer neutrals from theneutral bus when the source is taken out of service, because the neutral bus is energized during groundfaults. This additional switching complication must be weighed against the increase in ground faultcurent with many sources

Circuit breakers are preferred to disconnecting switches for indoor installations to assure safety topersonnel. If disconnecting switches are used, as in some outdoor installations, they should be elevatedor metal enclosed and interlocked in such a manner as to prevent their operation except when thetransformer primary and secondary switches or generator main and field breakers are open.

It is sometimes desirable to operate with only one generator neutral breaker closed at a time toeliminate any circulating harmonic or zero-sequence currents. When the generator whose neutral isgrounded is to be shut down, another generator is grounded by means of its neutral breaker before themain and neutral breaker of the first one is opened. However, with similar generators and reasonablyequal load division, circulating currents are negligible, and it is often found practical to operate withneutral breakers of two or more generators closed. This simplifies operating procedure and increasesassurance that the system will be grounded at all times.

In the case of multiple transformers, all neutral isolating devices may be normally closed because thepresence of delta-connected windings (which are nearly always present on at least one side of eachtransformer) minimizes circulation of harmonic current between transformers.

When total ground-fault currents with several individual resistors would exceed about 1000 to 4000 A,it is suggested that neutral switchgear and a single resistor be considered for resistance-groundedsystems.

Page 24: Earthing of Electrical Systems

24

1.12 Calculation of Ground-Fault Currents

The magnitude of current which will flow in the event of a line- to-ground fault on a grounded systemis usually determined by the reactance of the grounded apparatus, the reactance of the lines or cablesleading to the fault, and the resistance and reactance of the ground return path including any intentionalgrounding resistance or reactance. For interconnected systems, calculation of the current may be rathercomplicated. For simpler cases, an approximation of the available fault current may be obtained.

1.12.1 Resistance Grounding

When a single line-to-ground fault occurs on a resistance- grounded system, a voltage appears acrossthe resistor (or resistors), nearly equal to the normal line-to-neutral voltage of the system.

In low resistance grounded systems, the resistor current is approximately equal to the current in thefault. Thus, the current is practically equal to line-to-neutral voltage divided by the number of ohms ofresistance used. Resistors have a voltage rating equal to line-to-neutral voltage and an ampere ratingequal to the current which flows when this voltage is applied to the resistor. Thus, for example, amaximum ground- fault current of approximately 1000 A will be obtained on a system when using a1000-A resistor. This very simple method of calculating the ground-fault current is only suitable whenthe ground-fault current is small compared to the three-phase fault current.

The method just outlined applies to faults on lines or buses or at the terminals of machines ortransformers. If the fault is internal to a rotating machine or transformer, the ground-fault current willbe less. The reduction in current is primarily due to the intemal voltage of the apparatus. In the case ofstar- connected equipment, this internal voltage is at full value at the terminals and is zero at theneutral. If the fault occurs at the neutral of any apparatus, no voltage will appear across the systemgrounding resistor, so the fault current will be zero. At intermediate points in the winding between theneutral and a terminal, the fault current will be intermediate between zero and the current due to aterminal fault. For example, at a point 10 percent of the winding length from neutral, the ground-faultcurrent will be approximately 10 percent of the value for a terminal fault. For a fault anywherebetween this point and a terminal, the current will be more than 10 percent of the amount for a terminalfault.

In the case of delta-connected machines, the internal voltage to neutral may be considered to be 100percent at the terminals and 50 percent at the midpoint of the windings. The midpoints have the lowestpotential with respect to the electric neutral of any part of the winding. Therefore, a ground fault at anypoint in the winding will produce a ground-fault current of 50 percent or more of the line terminal faultvalue.

1.12.2 Reactance Grounding

In a reactance-grounded system with a single line-to-ground fault, the ground-fault current may becomputed from the following expression, where resistance may usually be neglected:.

Ig = 3E / [X1 + X2 + X0 + 3 (XN + XGP )] (Eq 1 ) where

X1 = system positive-sequence reactance in ohms per phase

Page 25: Earthing of Electrical Systems

25

X2 = system negative-sequence reactance in ohms per phase

X0 = system zero-sequence reactance in ohms per phase

XN = reactance of neutral grounding reactor in ohms

XGP = reactance of the ground return circuits in ohms

E = line-to-neutral voltage in volts

Ig = ground-fault current in amperes

1.12.3 Solid Grounding

In a system with a solid neutral connectionto ground, the ground fault current for a single line toground fault may be calculated from the followingequation:-

Ig = 3E / [X1 + X2 + X0 + 3 XGP] (Eq 2 )

where the symbols have the same meaning given above

1.13 Selection of Grounding Equipment Ratings(See IEEE Std 32-1972, Neutral Grounding Devices)

Grounding resistors, reactors, and grounding transformers are normally rated to carry current for alimited time only. The standard time interval rating usually applicable with relays arranged to protectthe grounding equipment is 10 s.

The voltage rating of a grounding resistor should be the line- to-neutral voltage rating of the system.

The insulation class of a reactor is determined by the system line-to-neutral voltage. The voltage ratingmay be less than line-to-neutral voltage and is calculated by multiplying the rated current by theimpedance of the reactor.

The voltage rating of a grounding transformer should be system line-to-line voltage.

Grounding resistors are rated in terms of the current that will flow through the resistor with ratedresistor voltage applied.

The rated current of a grounding reactor is the thermal current rating. It is the root-mean-square neutralcurrent in amperes that the reactor will carry for its rated time without exceeding standard temperaturelimitations.

If a grounding transformer neutral is solidly connected to ground, the current that will flow during aground fault is primarily determined by the reactances of the grounding transformer and the system towhich it is connected. When a resistor is used between neutral and ground, the current rating of thegrounding transformer is based on the resistor rated current. In either case, the transformer is rated tocarry the required current for rated time without exceeding its rated temperature limits. Many systemgrounding devices are short-time rated. Care must be exercised in their application to ensure thatcurrent will be automatically interrupted before the thermal limits of components are exceeded.

Page 26: Earthing of Electrical Systems

26

Due consideration must be taken in systems using Auto Reclose on lines, as the total time for all faultsbefore a lock out must be used in calculating thermal requirements.

1.13.1 Resistor Ratings

For low-resistance grounded-neutral systems, the determination of the resistor value in ohms, thus themagnitude of groundfault current, is based on the following:

(1) Providing sufficient current for satisfactory performance of the system relaying scheme.

(2) Limiting ground-fault current to a value which will minimize damage at the point of faultwithout resulting in system overvoltages.

In most cases, the ground-fault current is limited by the neutral resistor to a value considerably lessthan that which would flow for a three-phase fault. To determine the minimum ground-fault currentrequired, a diagram of the system must be available, giving ratings of current transformers and types ofrelays for each circuit. This diagram should include consideration of future changes.

The magnitude of ground-fault current must be sufficient for operation of all relays which furnishground-fault protection. In general, if the current is high enough to operate the relays on the largercircuits, it will be adequate for the smaller circuits. The ground currents required for satisfactoryoperation of various types of relays, expressed in terms of current transformer rating, are given in TableIII. Note that the ground-fault current under all system operating conditions must equal or exceed theminimum required for relaying each circuit connected to the system. This value is established byselecting the highest of those currents which meet the requirements of the several conditions set forthin Table III.

Table III Selection of a Grounding ResistorType of Relaying

Equipment Protected Ground Overcurrent % Differential % Other %Star connectedgenerators and motors

100 100 *

Delta connectedgenerators, motors andtransformers

40 40

L:ines and cables 20 # ** Pilot wire - 100Current balance - 100

Buses 50 &Note:- Values given are minimum recommended ground fault currents in percentage of rated primary

current of the associated CTs

* If ground fault differential is added to the generator, the ground fault current may belimited to lower values (If other sytem requirements permit)

** When phase relays must be set to wait for other breakers to clear any through phase-to-phase fault, required ground current may have to be as high as 50% of the CT rating toprevent maltripping.

# Where ground overcurrent relays for lines and cables also serve for back up protectionfor machines or transformers, this value should be 100%.

Page 27: Earthing of Electrical Systems

27

& Based on current differential. If voltage differential is provided, ground fault currentmay be limited to lower values.

1.13.2 Reactor Ratings

The reactance of a neutral-grounding reactor should be chosen to limit the ground current and thecurrent in the faulted phase to the desired value. In order to minimize transient overvoltages, theground-fault current must not be less than 25 percent of three-phase fault current.

This corresponds to a ratio of X0 / X1 = 10.

For reactance grounding of generators, the current in any winding must not exceed the three-phase faultcurrent. This corresponds to a ratio of X0 / X1 = 10. This establishes the criteria for maximum andminimum value of neutral reactance. If the neutral reactance is selected in accordance with thefollowing relationship, the current in the winding of the faulted phase will not exceed the three-phasecurrent of the machine regardless of system reactance (ref 9, chs 5-7):

XN = (X1 - X0 ) / 3 (Eq 3)

where :-X1 = system positive-sequence reactance in ohms per phase

X0 = system zero-sequence reactance in ohms per phase

XN = reactance of neutral grounding reactor in ohms

However, the current that flows through the generator neutral reactor itself is not independent ofsystem constants and may often exceed the three-phase fault current of the machine. The current ratingof a neutral reactor is determined by the number and characteristics of system sources and whether theyare grounded or ungrounded.

This rating (the thermal-current rating) can be calculated by the following equation:

Ig = 3E / [X1 + X2+ X0+ 3 (XN + XGP) (Eq 4)

where:-X1 = system positive-sequence reactance in ohms per phase

X2 = system negative-sequence reactance in ohms per phase

X0 = system zero-sequence reactance in ohms per phase

XN = reactance of neutral grounding reactor in ohms

XGP = reactance of the ground return circuits in ohms

E = line-to-neutral voltage in volts

Page 28: Earthing of Electrical Systems

28

Ig = ground-fault current in amperes

NOTE:- For X1 of generators and synchronous motors, use transient reactance. For X2 ofgenerators, synchronous and induction motors, use subtransient reactance.

The neutral-grounding reactor should be selected to carry the available current under all practicaloperating conditions. With any given condition of connected grounded-neutral sources, the addition ofungrounded-neutral sources and loads will increase the current flow through the grounded-neutralconnections.

1.13.3 Grounding-Transformer Ratings

The electrical specifications of a grounding transformer are the following:

Voltage the line-to-line voltage of the system

Current the maximum neutral current

Time the transformer is usually designed to carry rated current for a short time such as 10 or60 s; for high-resistance grounding, the rating may need to be continuous.

Reactance this quantity is a function of the initial symmetrical available system three-phase short-circuit energy measured in kilovoltamperes

Determination of grounding-transformer reactance, when used to effect reactance-type grounding, isbased on the following criterion:

The X0 / X1 ratio should not exceed 10, and preferably not exceed 3, in order to eliminate thepossibility of transient overvoltages from a forced current zero interruption. This maximum limitationof 3 for the X0 / X1 ratio, will also satisfy the criteria for an effectively grounded system and permit theapplication of line-to-ground voltage rated surge arresters for greater economy and protection. Theratios specified must be met at any location in the system where the reduced-rating arresters are to beapplied.

In a system having a grounding transformer, its reactance is the principal part of Xo in the precedingcriterion. Also, the positive-sequence reactance X1 is equal to the reactance of the system to initialsymmetrical root-mean-square three-phase short-circuit current. The value of X1 used in these limitingratios should be based on subtransient reactance of rotating machines and the system configuration orconnections which will result in the maximum available three-phase short-circuit energy measured inkilovoltamperes. Thus, the grounding-transformer reactance is a function of the initial symmetricalsystem three-phase short-circuit energy measured in kilovoltamperes.

In a system otherwise ungrounded, the grounding-transformer reactance Xgt in ohms per phase requiredto provide any specified X0 / X1 ratio is given by the following expression:

X0 / X1 x EL2 x 1000

__________________________________________________________System Symnetrical Three-Phase Short-circuit Energy in Kilovoltamperes (Eq 5)

where EL is the line-to-line voltage.

Page 29: Earthing of Electrical Systems

29

When a grounding transformer is solidly grounded, care should be taken that its reactance is selected ata value low enough to provide sufficient fault current for tripping relays and circuit breakers.

1.14 AutoTransformers Power

Autotransformers are quite frequently used in electric utility power transmission and distributionsystems. Their use in industrial power systems as a part of the power distribution system is relativelyinfrequent. Autotransformers are quite common, however, in control and utilization equipment.Systems using autotransformers may be subject to dangerous fundamental- frequency overvoltageduring system faults or to high-frequency or steep wave front transient overvoltages on the linesoriginating from lightning or switching surges. In general, solidly grounding the neutral of theautotransformer is a satisfactory means of eliminating overvoltages. The disadvantages of solid-neutralgrounding is that third-harmonic currents and telephone interference may become excessive in certaincases. These harmonic problems can usually be eliminated by the use of a tertiary delta on theautotransformer.

Where auto transformers are used as step-up or step-down transformers in 11 and 22kV systems,problems arise when the auto transformer neutral is grounded in otherwise resistively earthed systems.This additional ground poit must comply with the designed fault current limitation and the associatedprotection must allow for the bi-directional flow of fault current.

In many cases the only solution is to leave the neutral ungrounded as the complication of the protectioncannot be easily and cost effectively solved. The zero sequence impedance of the un grounded autotransformer is difficult to determine and may have to be measured on site in order to setb the protectioncorrectly.

1.15 Systems with Utility Supply

Some industrial systems are directly connected at their operating voltage to utility systems. When suchis the case, the scheme of grounding the industrial system should be properly coordinated with that forthe utility system.

If two systems are interconnected by means of a transformer bank, at least one winding of the bank willnormally be connected in delta, and this delta-connected winding will make each system independentfrom the standpoint of grounding.

Generators with unit-connected transformers usually are equipped with high-resistance neutralgrounding for the following purposes:

(1) Minimize transient overvoltages

(2) Provide a positive indication of a ground fault

(3) Limit ground-fault current to a value low enough to permit an orderly shut-down of thegenerator without risking severe arc damage.

As in any other high-resistance grounded system, the grounding resistor is chosen to provide ground-fault current at least as great as the system capacitive charging current. Depending on the system

Page 30: Earthing of Electrical Systems

30

voltage and ground current, it may be more economical to ground the generator neutral through theprimary of a single phase distribution-type transformer with a low-voltage high-current resistor on thesecondary than to ground the neutral directly through a high-voltage low-current resistor. When adistribution transformer is used, its primary voltage should be no less than the line-to-neutral voltage ofthe generator. In fact, to decrease the transformer-magnetizing inrush current on occurrence of aground fault, a transformer rated for full line- to-line voltage is often used. In all cases, the zero-sequence circuit design should respect the boundary limit of R0 = 2X0 .

Ground faults are detected in this scheme either by a current relay in series with the grounding resistor,or by a voltage relay in parallel with the resistor. If the voltage-relay sensor is chosen, possible falseoperation on third-harmonic voltage, sometimes present, can be avoided by the use of a third-harmonic- voltage attenuation filter. In either case, no coordination with relays elsewhere in the powersystem is needed.

The physical size of the grounding transformer is influenced by the expected duration of groundcurrent. If the generator will be operated with a ground fault for several hours, the transformer shouldbe rated to carry ground current continuously. However, the short-time overload capacity oftransformers permits a considerably smaller and less expensive transformer to be used if the generatoris tripped off the line immediately or promptly after a fault is detected.

1.16 Three-Phase Four-Wire Systems

In these systems, single-phase loads are connected between phase conductors and the neutralconductor. The neutral conductor is insulated over its entire length, except where it is grounded at itssource of supply, in NE systems. There are also systems where there are multiple earths at variouspoints on an otherwise insulated neutral conductor, ie. PME systems. PME systems can increase thedifficulty of detecting ground faults.

The neutrals of such systems should be grounded such that during a ground fault the voltage betweenany phase conductor and ground does not appreciably exceed normal line-to-ground voltage. Four-wiresystems should thus be effectively grounded in such a manner that the ground-fault currents areapproximately equal to three-phase fault currents. This is usually accomplished by direct connection oftransformer bank neutrals to ground without any intentional neutral impedance.

Where the risk to personnel touching the system is small, as with low voltage systems which areeffectively three wire, the use of high resistance or Neutralizer grounding is used to reduce the chanceof outages and to minimise damage at the point of fault. This type of application has to be viewed inthe light of legislation which may prohobit such instalations at low voltage if the risk to personnel isincreased.

Page 31: Earthing of Electrical Systems

31

1.17 Standards References

The following standards publications were used as references in preparing this lecture and are useful inthe interpretation of its meaning:

ANSI Cl-1971 National Electrical Code (NFPA 70-1971) 2,5

IEEE Std. 32-1972, Neutral Grounding Devices 3

NEMA Std SG 4-1968, AC High-Voltage Circuit Breakers 4

IEEE Std 142-1972 Recozmended Practice for grounding of Industrial & Cozmercial Power Systems"The IEEE Green Book"

References

(1) AIEE Committee Report. Application Guide for the Grounding of Synchronous GeneratorSystems. AIEE Transactions (Power Apparatus and Systems), vol 72, June 1953, pp 517-526.

(2) AIEE Committee Report. Application Guide on Methods of Neutral Grounding ofTransmission Systems. AIEE Transactions (Power Apparatus and Systems), vol 72, Aug 1953,pp 663-668.

(3) AIEE Committee Report. Present-Day Grounding Practices on Power Systems; Third AIEEReport on System Grounding. AIEE Transactions, vol 66, pp 1525-1551.

(4) ARBERRY, J.P.E. The Use of 600-Volt and 460-Volt Power Systems with Grounded Neutrals.AIEE National Power Conference Proceedings, Pittsburgh, Pa., Apr 1950.

(5) KAUFMANN, R.H., and PAGE, J.C. Arcing-Fault Protection for Low-Voltsge PowerDistribution Systems - Nature of the Problem. AIEE Transactions (Power Apparatus andSystems), vol 79, June 1960, pp 160-167.

(6) SHIELDS, F.J. The Problem of Arcing Faults in Low-Voltage Power Distribution Systems.IEEE Transactions on Industry and General Applications, vol IDA-3, Jan/Feb 1967, pp 15-25.

7) FORBES, B.G. Locating Grounds on 480-Volt, 3-phase Delta Systems, Power Generation, Sept1949, pp 60-61.

(8) FOX, F.K., GROTTA, H.J, and TIPTON, C.H. High-Resistance Grounding of 1400-Volt DeltaSystems with Ground-Fault Alarm and Traceable Signal to Fault. IEEE Transactions onIndustry and General Applications, vol IGA-1, Sept/Oct 1965 pp 366-372.

(9) BEEMAN, D.L, Ed. Industrial Power Systems Handbook. New York, McGraw-Hill, 1955,chs.5-7.

(10) VAUGHAN, H.R. Protection of Industrial Plants Against Insulation Breakdown andconsequential Damage. AIEE Transactions, vol 65, Aug/Sept 1946, pp 592-596.

(11) AIEE committee Report. Application of Ground-Fault Neutralizers. Electrical Engineering, vol72, July 1953, pp 606.

(12) Electrical Transmission and Distribution Reference Book, fourth edition, WestinghouseElectric Corporation, Sept 1950, chs 11 and 19.

(13) Neutral Grounding in HV Transmission, Ilillheim and Waters - Elsevier.(14) Transients in Power Systems. Harold A. Petersen, ch,10 Dover.(15) Transient Performance of Electric Power Systems, Rudenberg chapters 48 and 49.(16) Circuit Analysis of Ac Power Systems. Vol I. - Edith clarke. Whiley.

Additional References

BARNETT, H.G. Why Ground Low-Voltage Distribution Systems? Mill and Factory, May 1951.

Page 32: Earthing of Electrical Systems

32

BEEMAN, D.L. System Neutral Grounding in Industrial Plants. AIEE National Power ConferenceProceedings. Pittsburgh, Pa., Apr 1950.

BLOOMQUIST, W.C. Grounding of Industrial Systems, General Electric Review. Aug 1951.

BRERETON, D.S, and HICKOK, H.N. System Neutral Grounding for Chemical Plant Power Systems.AIEE Transactions (Applications and Industry) vol 74, Nov 1955, pp 315-320.

JOHNSON, A.A. Grounding Principles and Practice III: Generator- Neutral Grounding Devices.Electrical Engineering, vol 64, Mar 1945, pp 92-99.

Interim Report of American Research Committee on Grounding. News Bulletin of the InternaitonalAssociation of Electrical Inspectors. Mar 1944.

STRONG, W.F. Neutral Versus Corner-of-the-Delta Grounding. Electrical World., Sept 25, 1950.

THACKER, H.B. Grounded Versus Ungrounded Low-Voltage AC Systems. Association of Iron andSteel Engineers Paper and Discussion. Iron and Steel Engineer, Apr 1954, pp 65-72.

1.18 Symbols Used

R0 = Zero sequence resistance of grounding pathX0 = Zero sequence reactance of grounding pathZ0 = Zero sequence impedance of grounding pathX1 = Positive sequence reactance to grounding pointR1 = Positive sequence resistance to grounding pointZ1 = Positive sequence impedance to grounding pointXc0 = Zero sequence capacitive reactance of systemRN = Neutral grounding resistor resistanceXN = Neutral grounding resistor

Page 33: Earthing of Electrical Systems

33

2.0 PROTECTION ASPECTS OF LIMITED EARTH FAULT

2.1 RESTRICTED EARTH FAULT (REF)

The SABS recommendations are for the use of resistance earthing, with a limit of 300A pertransformer and a total of 900A with multiple transformers in parallel.

With larger transformers, typically 20 MVA at 6.6 kV, the CT ratio would be possibly 2000/1.

A problem which needs to be covered with correct design is the requirement to cover 90% of thewinding by use of REF (see fig 11). With the typical large CT ratio given above, use of a 5% currentrelay (with stabilising resistor) would only allow pick up at 100 amps, ignoring CT magnetisingcurrent. This is inadequate for covering 90% of the winding as with one transformer and 300A E/Favailable, only 66% of the winding is protected.

The typical REF relay using 20mA pick must be used, as this has a primary pick up of typically 50Awith CT magnetising current. This is still only 85% coverage, but is acceptable. However, REF for a40 MVA transformer is more difficult.

2.2 Pilot wire protection (PW)

As given above, PW protection also can have a sensitivity problem (see fig 12). As the typical relayhas a worst case sensitivity of 25% on Blue phase, use with a 600/1 CT would result in a pick up ofonly 150A which is not desireable.

This problem is made more unacceptable where the relay does not combine the differential currentfrom both sides to create the operating quantity. Thus for a fault at the remote end of two or moreparallel feeders, the pick current could be greater than 300A and no operation would occur for earthfaults.

2.3 Multiple Earths When using Auto Transformers

The accepted practice of using low cost auto transformers to step up or down between 11 and 22 kVhas resulted in the transformers being positioned at some remote position from the substation with theprotection.

Where sensitive earth fault protection is used for overhead lines, maloperation can occur when theseauto transformers have their neutrals earthed (see fig 13). The fault on a line causes earth fault infeedsfrom all electrically connected earths. Even though the auto transformer may not have a delta windingfor a low impedance source, it can supply sufficient current, typically more than 4 amps, which willcause a healthy line with it’s auto transformer to trip incorrectly.

Either no auto transformer neutrals should be earthed when on lines or double winding transformerswith suitably low zero sequence impedance for earthing the secondary system must be used.

2.4 Sensitive Earth Fault Relays used on Rings or Hospital Bypas Busbars

Where Sensitive Earth Fault (SEF) relays are used, maloperation can occur when a ring or Bypassbusbar is closed (see fig 14). This is caused by differences in impedance of especially over head linesand busbars. This difference between phase impedances cuases an apparent earth fault current in both

Page 34: Earthing of Electrical Systems

34

circuits, but of opposite direction. This primary residual current will cause sensitve earth fault relays tomal-operate. The sensitve earth fault needs to be switched off when such switching is undertaken.

With limited earth fault currents and the associated increase in sensitity of relay settings, the abovemalfunction can also occur for normal earth fault relays, when additional impedance such as a poorlink contact occurs.

This is usually associated with closure of the “ring” as the current is already flowing in the previoussystem configuration. The line volt drops are small and are unable to break down a surface fim,causing a phase to be “open circuit” and thus creating primary residual currents.

For the case where sensitive earth fault protection must be applied to parallel OHL feeders, anadditional monitoring relay may be necessary to overcome mal-tripping.

2.5 Sensitive Settings with Earth Fault Relays of Low Burden

The modern static relays have very low burdens. This has created a problem with transient stability formotor starting and for transformer magnetising in rush (see fig 15)

With low earth fault currents, protection has to be set with adequate sensitivity. Although the currentis limited and fault damage is thus reduced, faults should still be clreared as soon as possible so that anearth fault does not develop into a phase-phase fault.

This combination of sensitivity, fast operation and low burden causes the relay to malfunction becauseof CT saturation. STABILISING RESISTORS must be used in many of these applications.

2.6 Contactor Fault Breaking Capability

For many motor circuits fused contactors are used when the switching duty is high.

As the contactor has a limited fault breaking capability, the High Set instantaneous element ofprotection relays is disabled. With limited earth fault, the contactor is fully capable of breaking earthfault current. However, if the fault is a phase-phase-earth fault, a fast earth fault relay could drop thecontactor out such that it attempts to break the phase phase fault current, which could damage thecontactor.

A possible solution is to delay the earth fault relay, but this has a cascade effect on all upstreamprotection with regarg to increased time. The preferred method is to use relays with an internal blockfuntion if any phase exceeds typically 4x full load current, where overcurrent protection will correctprotect the circuit.

2.7 Maltripping Caused By Capacitance

Again with the more sensitive settings used with limited earth fault ciurrent, care must be taken withthe current derived from cable capacitance or wave shaping capacitors.

Wave shaping capacitors of various forms are often used for the protection of motors againsttransients, with typical values of 0.3 uF.

At 11 kV, the typical earth fault infeed from capacitance could be:-

Wave Shaping Capacitor (0.3uF) 1.8 amps

Page 35: Earthing of Electrical Systems

35

4 kM 120mm² PEX cable (1.33 uF) 7.96 amps

For the above, the earth fault protection must not be too sensitive, as maloperation will occur,especially where ring core Cts are used to improve sensitivity.

2.9 High Voltage Lines With Multiple Earthed Transformer Tees

Where 132 kV rings are used in Municipalities, the system is often used without full switching stations(see fig 16) This results in tees off the lines to feed step down transformers, which have the 132 kVneutral earthed as the transformer insulation is usually fully graded.

Each of these earthed neutrals feeds earth fault current into the system during an earth fault on the HVsystem.

The source substation for the line thus sees only part of the total earth fault current and this can resultin the earth fault relay being unable to correctly clear the fault.

Various methods are used to allow correct operation to occur, but many of these compromises mayrequire sequential tripping of tee breakers until the source breaker correctly trips. Fault throwing at apoint near the fault is also a possibility, but is not a recommended practice on high fault level lines.

The number of teed (earthed) feeders off a ring should be limited with the size of the transformers earthfault contribution also being taken into account.

Page 36: Earthing of Electrical Systems

36

A

B

C

PHASE TO GROUND

CAPACITANCE

A B

C

GROUND

(a) UNGROUNDED SYSTEM

A

B

C

A B

CGROUND

(c) UNGROUNDED DELTA SYSTEM

VOLTAGES TO GROUND UNDER STEADY STATE CONDITIONS

FIGURE 1

A

B

C

A B

C

GROUND

(b) GROUNDED STAR SYSTEM

Page 37: Earthing of Electrical Systems

37

(a) SYSTEM SUBJECT TO FERRO RESONANCE

(c) UNGROUNDED DELTA SYSTEM

VOLTAGES TO GROUND UNDER STEADY STATE CONDITIONS

FIGURE 2

Xco

STRAY ZERO

SEQUENCE

CAPACITANCE

EARTHING DEVICE

(USUALLY A

VOLTAGE

TRANSFORMER)

A

C B

INVERTED NEUTRAL

GROUND

NORMALSYSTEM

NEUTRAL

VA-G

V B-G

VC-G

Page 38: Earthing of Electrical Systems

38

Page 39: Earthing of Electrical Systems

39

Page 40: Earthing of Electrical Systems

40

GROUNDING METHODS

FIGURE 4

XoN

(a) UNGROUNDED

XoN

(c) REACTANCE GROUNDED

XoN

(b) SOLIDLY GROUNDED

Xo

XN

XN 0

XN 0

= XN

3x

NEUTRAL REACTOR

or

PETERSEN COIL

Page 41: Earthing of Electrical Systems

41

GROUNDING METHODS

FIGURE 4

Xo

N

(d) REACTANCE GROUNDED

XN 0

GROUNDING TRANSFORMER

Xo

NEC

XN 0

XoN

(e) RESISTANCE

Xo

RN

RN 0

RN 0

= RN

3x

GROUNDED

Page 42: Earthing of Electrical Systems

42

DGD0001

I b I cI n

G

In

Ib

Ic

TRANSFORMER

BC

N

In

A

GROUND-FAULT

NEUTRALIZER

Ib

Ic

I c I b

In

V NA

I b I c+ 2In

V NA V CA

Ic

V BA

Ib

I b I c+

GROUND-FAULT-CURRENT PATTERN IN SYSTEM

GROUNDED BY MEANS OF A GROUND-FAULT NEUTRALIZER

FIG. 5

Page 43: Earthing of Electrical Systems

43

DGD0002

LINE LEADS

NEUTRAL LEAD

SCHEMATIC DIAGRAM OF CONNECTIONS

FIG. 6a

WINDINGS SHOWN ON CORE

CONNECTIONS OF THREE-PHASE ZIG-ZAGGROUNDING TRANSFORMER

LINE

LEADS

NEUTRAL

LEAD

CONNECTIONS OF THREE-PHASE ZIG-ZAGGROUNDING TRANSFORMER

FIG. 6b

Page 44: Earthing of Electrical Systems

44

DGD0003

STAR DELTA TRANSFORMER USED AS

GROUNDING TRANSFORMER

FIG. 7

GROUNDING

TRANSFORMER

GROUNDING

RESISTOR

FIG. 8

GROUNDING

TRANSFORMER

GROUNDING

RESISTOR

GROUNDING TRANSFORMER ON A DELTA-CONNECTED

OR GROUNDED POWER SYSTEM

Page 45: Earthing of Electrical Systems

45

DGD0004

GROUND REQUIRED HERE TO GROUND

NEUTRAL OF 33kV SYSTEM

FIG. 9

132kV SYSTEM

GROUND REQUIRED HERE TO GROUND

NEUTRAL OF 11kV SYSTEM

GROUND REQUIRED HERE TO GROUND

NEUTRAL OF 380V SYSTEM

33kV SYSTEM

11kV SYSTEM

380V SYSTEM

GROUND

HEREGROUND

HERE

GROUNDING

TRANSFORMER

FIG. 10

DO

NOT

GROUND

HERE

MOTOR

IF POWER SOURCES ARE

DELTA-CONNECTED, ADD

GROUNDING TRANSFORMER

RATHER THAN GROUND

AT LOAD

GROUND AT THE SOURCE AND NOT AT THE LOAD

EACH VOLTAGE LEVEL IS GROUNDED INDEPENDENTLY

Page 46: Earthing of Electrical Systems

46

DGD0005

REDUCING EARTHFAULT WRT POSITION

OF FAULT ON WINDING

FIG. 11

VPN33%

VPN66%

ONLY 100A

RN (300A LIMIT)

VPN1/3

RN=

FIG. 12

PWPW

600/1

300A

150A

150A

PW FAILURE TO OPERATE WHEN TOTAL CURRENT

IS NOT USED FOR RELAY OPERATION

Page 47: Earthing of Electrical Systems

47

DGD0006

FIG. 13

SEF

SEF

75A

300A

AUTO-TRFR

FIG. 14

I C = 0

POOR LINK

CONTACT

APPARENT

E/F = I C

NO E/F CURRENT

IN THIS RELAY

E/F

E/F

MALOPERATION OF BOTH EARTHFAULT RELAYS

WITH A POOR LINK CONTACT IN A CLOSED RING

EARTHED AUTO-TRANSFORMER CAN

CAUSE HEALTHY LINE TRIP

Page 48: Earthing of Electrical Systems

48

DGD0007

FIG. 15

XIC

(1-X)IC

R

Z = CT RESISTANCE

WHEN SATURATED

SPLIT OF X AND 1-X DEPENDS

ONLY ON Z OF BLUE PHASE TO

Z OF EARTHFAULT CIRCUIT

FIG. 16

E/F

INFEED

I E/F SMALL

INFEED

TOTAL

E/F HIGH

USE OF STABILISING RESISTOR TO PREVENT

EARTHFAULT MALOPERATION WITH LOW BURDEN RELAYS

REDUCTION OF EARTHFAULT CURRENT FROM

SOURCE WITH MULTIPLE LINE TEES