E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 1
E2-E3: CIVIL
CHAPTER-1
DESIGN OF RCC BUILDING
COMPONENTS
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 2
Design of RCC Building Components
1.0 Introduction
The procedure for analysis and design of a given building will depend
on the type of building, its complexity, the n umber of stories etc. First
the architectural drawings of the building are studied, structural system
is finalized sizes of structural members are decided and brought to the
knowledge of the concerned architect. The procedure for structural
design will involve some steps which will depend on the type of
building and also its complexity and the time available for structural
design. Often, the work is required to start soon, so the steps in design
are to be arranged in such a way the foundation drawings can b e taken
up in hand within a reasonable period of t ime.
Further, before starting the structural design, the following information
of data are required: (i) A set of architectural drawings;(ii) Soil
Investigation report (SIR) of soil data in lieu thereof; (iii) Location of
the place or city in order to decide on wind and seismic loadings;(iv)
Data for lifts, water tank capacities on top, special roof features or
loadings, etc.
Choice of an appropriate structural system for a given building is vital
for its economy and safety. There are two type of building systems: -
(a) Load Bearing Masonry Buildings.
(b) Framed Buildings.
(a) Load Bearing Masonry Buildings: - Small buildings like houses with small spans of beams, slabs generally
constructed as load bearing br ick walls with reinforced concrete slab
beams. This system is suitable for building up to four or less stories.(as
shown in fig. below). In such buildings crushing strength of bricks
shall be 100 kg/cm2
minimum for four stories. This system is adequate
for vertical loads it also serves to resists horizontal loads like wind &
earthquake by box action . Further, to ensure its action against
earthquake , i t is necessary to provide RCC Bands in horizontal &
vertical reinforcement in brick wall as per IS: 4326-1967( Indian
Standards Code of Practice for Earthquake Resistant Construction
of Buildings.) . In some Buildings, 115mm thick brick walls are
provided since these walls are incapable of supporting vertical loads,
beams have to be provide along their lengths to support adjoining slab
& the weight of 115mm thick brick wall of upper storey. These
beams are to rest on 230 mm thick brick walls or reinforced concrete
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 3
columns if required. The design of Load Bearing Masonry Buildings
are done as per IS:1905-1980 (Indian Standards Code of Practice
for Structural Safety of Buildings: Masonry Walls(Second
Revision).
Load bearing brick wall
Structural system
(b) Framed Buildings:-
In these types of buildings reinforced concrete frames are provided in
both principal directions to resist vertical loads and the vertical loads
are transmitted to vertical framing system i.e columns and Foundations.
This type of system is effective in resisting both vertical & horizontal
loads. The brick walls are to be regarded as non load bearing filler
walls only. This system is suitable for multi -storied building which is
also effective in resisting horizontal loads due to earthquake. In this
system the floor slabs, generally 100-150 mm thick with spans ranging
from 3.0 m to 7.0 m. In certain earthquake prone areas, even single or
double storey buildings are made framed structures for safety reasons.
Also the single storey buildings of large storey heights (5.0m or more )
,like electric substation etc. are made framed structure as brick walls
of large heights are slender and load carrying capacity of such walls
reduces due to slenderness.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 4
Framed
Structural system
2.0 Basic Codes for Design .
The design should be carried so as to conform to the following Indian
code for reinforced concrete design, published by the Bureau of Indian
Standards, New Delhi:
Purpose of Codes
National building codes have been formulated in different countries to
lay down guidelines for the design and construction of structure. The
codes have evolved from the collective wisdom of expert structural
engineers, gained over the years. These codes are periodically revised
to bring them in l ine with current research, and often, current trends.
The codes serve at least four distinct functions .
Firstly, they ensure adequate structural safety, by specifying certain
essential minimum requirement for design.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 5
Secondly, they render the task of the designer relatively simple; often,
the result of sophisticate analyses is made available in the form of a
simple formula or chart .
Thirdly, the codes ensure a measure of consistency among different
designers.
Finally, they have some legal validity in that they protect the structural
designer from any l iabili ty due to structural failures that are caused by
inadequate supervision and/or faulty material and construction.
(i)IS 456 : 2000 – Plain and reinforced concrete – code of practice
(fourth revision)
(ii) Loading Standards
These loads to be considered for structural design are specified in the
following loading standards:
IS 875 (Part 1-5) : 1987 – Code of practice for design loads (other
than earthquake) for buildings and structures (second revision )
Part 1 : Dead loads
Part 2 : Imposed (live) loads
Part 3 : Wind loads
Part 4 : Snow loads
Part 5 : Special loads and load combinations
IS 1893 : 2002 – Criteria for earthquake resistant design of
structure (fourth revision) .
IS 13920 : 1993 – Ductile detailing of reinforced concrete structure
subject to seismic forces.
Design Handbooks
The Bureau of Indian standards has also published the following
handbooks, which serve as useful supplement to the 1978 version of the
codes. Although the handbooks need to be updated to bring them in
line with the recently revised (2000 version) of the Code, many of the
provisions continue to be valid (especially with regard to structural
design provisions).
SP 16 : 1980 – Design Aids (for Reinforced Concrete) to IS 456 :
1978
SP 24 : 1983 – Explanatory handbook on IS 456 : 1978
SP 34 : 1987 – Handbooks on Concrete Reinforced and Detailing.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 6
General Design Consideration of IS: 456-2000.
The general design and construction of reinforced concrete buildings
shall be governed by the provisions of IS 456 –2000
Aim Of Design
The aim of design is achievement of an acceptable probability that structures being
designed shall, with an appropriate degree of safety –
Perform satisfactorily during their intended life.
Sustain all loads and deformations of normal construction & use
Have adequate durability
Have adequate resistance to the effects of misuse and fire.
Method Of Design –
Structure and structural elements shall normally be designed by Limit State
Method.
Where the Limit State Method cannot be conveniently adopted, Working
Stress Method may be used
Minimum Grade Of Concrete
The minimum grade of concrete for plain & reinforced concrete shall be as per table
below –
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 7
26.4 Nominal Cover to Reinforcement
26.4.1 Nominal Cover
Nominal cover is the design depth of concrete cover to all steel
reinforcements, including links. It is the dimension used in design and
indicated in the drawings. It shall be not less than the diameter of the bar.
26.4.2 Nominal Covers to Meet Durability Requirement
Minimum values for the nominal cover of normal weight aggregate concrete
which should be provided to all reinforcement, including links depending on
the condition of exposure described in 8.2.3 shall be as given in Table 16.
Table 16 Nominal Cover to Meet Durability Requirements
(Clause 26.4.2)
Exposure Nominal Concrete Cover in mm not Less Than
Mild 20
Moderate 30
Severe 45
Very Severe 50
Extreme 75
NOTES
1. For main reinforcement up to 12 mm diameter bar for mild exposure
the nominal cover may be reduced by 5 mm.
2. Unless specified otherwise, actual concrete cover should not deviate
from the required nominal cover by + 10 mm
3. For exposure condition ‘severe’ and ‘very severe’, reduction of 5 mm
may be made, where concrete grade is M35 and above.
26.4.2.1 However for a longitudinal reinforcing bar in a column nominal cover shall
in any case not be less than 40 mm, or less than the diameter of such bar. In
the case of columns of minimum dimension of 200 mm or under, whose
reinforcing bars do not exceed 12 mm, a nominal cover of 25 mm may be
used.
26.4.2.2 For footing minimum cover shall be 50 mm.
26.4.3 Nominal Cover to Meet Specified Period of Fire Resistance
Minimum values of nominal cover of normal-weight aggregate concrete to be
provided to all reinforcement including links to meet specified period of fire
resistance shall be as given in Table 16A.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 8
21.4 Minimum Dimensions of RC members for specified Period of Fire
Resistance
Design Load
Design load is the load to be taken for use in appropriate method of design. It is –
Characteristic load in case of working stress method &
Characteristic load with appropriate partial safety factors for limit state
design.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 9
Load Combinations
As per IS 1893 (Part 1): 2002 Clause no. 6.3.1.2, the following load cases have to be
considered for analysis:
1.5 (DL + IL)
1.2 (DL + IL ± EL)
1.5 (DL ± EL)
0.9 DL ± 1.5 EL
Earthquake load must be considered for +X, -X, +Z and –Z directions.
Moreover, accidental eccentricity during earthquake can be such that it causes
clockwise or anticlockwise moments. So both clockwise & anticlockwise
torsion is to be considered.
Thus, ±EL above implies 8 cases, and in all, 25 cases must be considered.
It is possible to reduce the load combinations to 13 instead of 25 by not using negative
torsion considering the symmetry of the building.
Ductile Detailing As Per Is: 13920
• Provisions of IS 13920-1993 shall be adopted in all reinforced concrete
structures which are located in seismic zone III, IV or V
The provisions for reinforced concrete construction given in IS 13920-1993 shall
apply specifically to monolithic reinforced concrete construction. Precast and/or
prestressed concrete members may be used only if they can provide the same level of
ductility as that of a monolithic reinforced concrete construction during or after an
earthquake.
The definition of seismic zone and importance factor are given in IS 1893-2002.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 10
Stiffness
22.3.1 Relative Stiffness: The relative stiffness of the members may be based on
the moment of inertia of the section determined on the basis of any one of
the following definitions:
a) Gross
Section
The cross-section of the member ignoring
reinforcement
b) Transformed
Section
The concrete cross-section plus the area of
reinforcement transformed on the basis of modular
ratio
c) Cracked
Section
The area of concrete in compression plus the area of
reinforcement transformed on the basis of modular
ratio
The assumptions made shall be consistent for all the numbers of the
structure throughout any analysis.
22.3.2 For deflection calculations, appropriate values of moment of inertia as
specified in Annexure of IS 456-2000 should be used.
Structural Frames
22.4 The simplifying assumptions as given in 22.4.1 to 22.4.3 may be used in
the analysis of frames.
Arrangement Of Live Load
22.4.1 a) Consideration may be limited to combinations of:
1) Design dead load on all spans with full design live load on two
adjacent spans; and
2) Design dead load on all spans with dull design live load on alternate
spans.
22.4.1 b) When design live load does not exceed three-fourths of the design dead
load, the load arrangement may be design dead load and design live load
on all the spans.
Note: For beams continuous over support 22.4.1 (a) may be assumed.
22.4.2 Substitute Frame: For determining the moments and shears at any floor
or roof level due to gravity loads, the beams at that level together with
columns above and below with their far ends fixed may be considered to
constitute the frame.
22.4.3 For lateral loads, simplified methods may be used to obtain the moments
and shears for structures that are symmetrical. For unsymmetrical or very
tall structures, more rigorous methods should be used.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 11
Moment And Shear Cofficients For Continuous Beams
22.5.1 Unless more exact estimates are made, for beams of uniform cross-section
which support substantially uniformly distributed load over three or more
spans which do not differ by more than 15 percent of the longest, the
bending moments and shear forces used in design may be obtained using
the coefficients given in Tables below.
For moments at supports where two unequal spans meet or in case where
the spans are not equally loaded, the average of the two values for the
negative moment at the support may be taken for design.
Where coefficients given in Table below are used for calculation of
bending moments, redistribution referred to in 22.7 shall not be permitted.
22.5.2 Beams Over Free End Supports Where a member is built into a masonry wall which develops only partial
restraint, the member shall be designed to resist a negative moment at the
face of the support of W1/24 where W is the total design load and 1 is the
effective span, or such other restraining moment as may be shown to be
applicable. For such a condition shear coefficient given in Table below at
the end support may be increased by 0.05.
-------------------------------------------------------------------------------------------------------
BENDING MOMENT COFFICIENTS
-------------------------------------------------------------------------------------------------------
Span Moments Support Moments
-------------------------------------------------------------------------------------
Types of Load Near Middle At Middle At Support At Other
of End Span of interior next to the Interior
span end support Supports
-------------------------------------------------------------------------------------------------------
Dead load and 1 1 1 1
imposed load +-- +-- (- )-- (- )--
(fixed) 12 16 10 12
Imposed load 1 1 1 1
(not fixed) +-- +-- (- )-- (- )--
10 12 9 9
Note: For obtaining the bending moment, the coefficient shall be multiplied by
the total design load and effective span.
-------------------------------------------------------------------------------------------------------
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 12
-------------------------------------------------------------------------------------------------
SHEAR FORCE COFFICIENTS
-------------------------------------------------------------------------------------------------------
Type of Load At End At Support Next At All Other
Support to the end Support Interior Support
Outer side Inner Side
-------------------------------------------------------------------------------------------------------
Dead load and
imposed load 0.40 0.60 0.55 0.50
(fixed)
Imposed load 0.45 0.60 0.60 0.60
(not fixed)
Note: For obtaining the shear force, the coefficient shall be multiplied by the
total design load.
-------------------------------------------------------------------------------------------------------
Critical Sections For Moment And Shear
22.6.1 For monolithic construction, the moments computed at the face of the
supports shall be used in the design of the members at those sections. For
non-monolithic construction the design of the member shall be done
keeping in view 22.2.
22.6.2 Critical Section for Shear The shears computed at the face of the Support shall be used in the design
of the member at that section except as in 22.6.2.1
22.6.2.1 When the reaction in the direction of the applied shear introduces
compression into the end region of the member, sections located at a
distance less than d from the face of the support may be designed for the
same shear as that computed at distance d.
Redistribution Of Moments
22.7 Redistribution of moments may be done in accordance with 37.1.1 for limit state method and in accordance with B-1.2 for working stress
method. However, where simplified analysis using coefficients is adopted,
redistribution of moments shall not be done.
Effective Depth
23.0 Effective depth of a beam is the distance between the centroid of the area
of tension reinforcement and the maximum compression fibre, excluding
the thickness of finishing material not placed monolithically with the
member and the thickness of any concrete provided to allow for wear.
This will not apply to deep beams.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 13
Control Of Deflection
23.2 The deflection of a structure or part thereof shall not adversely affect the
appearance or efficiency of the structure or finishes or partitions. The
deflection shall generally be limited to the following:
a) The final deflection due to all loads including the effects of temperature,
creep and shrinkage and measured from the as-cast level of the supports of
floors, roofs and all other horizontal members, should not normally exceed
span/250.
b) The deflection including the effects of temperature, creep and shrinkage
occurring after erection of partitions and the application of finishes should
not normally exceed span/350 or 20mm whichever is less.
23.2.1 For beams, the vertical deflection limits may generally be assumed to be
satisfied provided that the span to depth ratio are not greater than the value
obtained as below:
a) Basic values of span to effective depth ratios for spans up to 10m:
Cantilever 7
Simply supported 20
Continuous 26
b) For spans above 10m, the values in (a) may be multiplied by 10/span in
metres, except for cantilever in which case deflection calculations should
be made.
c) Depending on the area and the type of steel for tension reinforcement, the
value in (a) or (b) shall be modified as per Fig. 4
d) Depending on the area of compression reinforcement, the value of span to
depth ratio be further modified as per Fig. 5
e) For flanged beams, the value of (a) or (b) be modified as per Fig. 6 and the
reinforcement percentage for use in fig. 4 and 5 should be based on area of
section equal to bf d.
Note: When deflections are required to be calculated, the method given
Annexure ‘C’ of IS 456-2000 may be used.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 14
Control Of Deflection – Solid Slabs
24.1 General
The provisions of 32.2 for beams apply to slabs also.
NOTES
1. For slabs spanning in two directions, the shorter of the two spans should be
used for calculating the span to effective depth rations.
2. For two-way slabs of shorter spans (up to 3.5 m) with mild steel
reinforcement, the span to overall depth rations given below may generally
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 15
be assumed to satisfy vertical deflection limits for loading class up to 3
kN/m2.
Simply supported slab 35
Continuous slabs 40
For high strength deformed bars of grade Fe 415,the values given above
should be multiplied by 0.8.
Simply supported slab 28
Continuous slabs 32
23.3 Slabs Continuous Over Supports
Slabs spanning in one direction and continuous over supports shall be
designed according to the provisions applicable to continuous beams.
23.4 Slabs Monolithic with Supports Bending moments in slabs (except flat slabs)
constructed monolithically with the supports shall be calculated by taking such
slabs either as continuous over supports and capable of free, or as members of a
continuous frame work with the supports, taking into account the stiffness of such
support. If such supports are formed due to beams which justify fixity at the
support of slabs, then the effects on the supporting beam, such as, the bending of
the web in the transverse direction of the beam, wherever applicable, shall also be
considered in the design of the beams.
23.4.1 For the purpose of calculation of moment in slabs in a monolithic structure, it
will generally be sufficiently accurate to assumed direct members connected to
the ends of such slab are fixed in position and direction at the end remote from
their connection with the slab.
26.5 Requirement Of Reinforcement For Structural MEMBER
26.5.1 Beams
26.5.1.1 Tension reinforcement
(a) Minimum reinforcement:- The minimum area of tension reinforcement shall
not be less than that given by the following:-
As = 0.85
bd fy
where
As = minimum area of tension reinforcement.
b = breadth of beam or the breadth of the web of T-beam.
d = effective depth, and
fy = characteristic strength of reinforcement in M/mm2
(b) Maximum reinforcement:- the maximum area of tension reinforcement shall not exceed 0.04bD.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 16
26.5.1.2 Compression reinforcement
The maximum area of comparison reinforcement shall not exceed 0.04 bd.
Comparison reinforcement in beams shall be enclosed by stirrups for effective lateral
restraint.
26.5.1.3 Side face reinforcement
Where the depth of the web in the beam exceeds 750mm, side face reinforcement
shall be provided along the two faces. The total area of such reinforcement shall be
not less than 0.1 % of the web area and shall be distributed on the equally on the two
face at spacing not exceeding 300mm or web thickness whichever is less.
26.5.1.4 Transverse reinforcement in beam for shear torsion
The transverse reinforcement in beam shall be taken around the outer most tension &
compression bars. In T-beams and I-beams, such reinforcement shall pass around
longitudinal bars located close to the outer face of the flange.
26.5.1.5 Maximum spacing of shear reinforcement
Maximum spacing of shear reinforcement means long by axis of the member shall not
exceed 0.75 d for vertical stirrups and d for inclined stirrups at 45” where d is the
effective depth on the section under consideration. In no case shall be spacing exceed
300mm.
26.5.1.6 Minimum shear reinforcement
Minimum shear reinforcement in the form of stirrups shall be provided such that:
Asv 0.4
bsv 0.87 fy
Where
Asv = total cross-sectional area of stirrups legs effective in shear.
Sv = stirrups spacing along the length of the member
B = breadth of the beam or breadth of the web of flange beam, and
fy = characteristic strength of the stirrups reinforcement in N/mm2 which shall not
taken greater than 415 N/mm2
Where the maximum shear stress calculated is less than half the permissible value in
member of minor structure importance such as lintels, this provision need not to be
complied with.
26.5.1.7 Distribution of torsion reinforcement
When a member is designed for torsion torsion reinforcement shall be provided as
below:
a) the transverse reinforcement for torsion shall be rectangular closed stirrups
placed perpendicular to the axis of the member. The spacing of the stirrups
shall not exceed the list of x1, x1+y1/4 and 300 mm, where x1, y1 are
respectively the short & long dimensions of the stirrup.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 17
b) Longitudinal reinforcement shall be place as closed as is practicable to the
corner of the cross section & in all cases, there shall be atleast one longitudinal
bar in each corner of the ties. When the cross sectional dimension of the
member exceed 450 mm additional longitudinal bar shall be provided to
satisfied the requirement of minimum reinforcement & spacing given in
26.5.1.3.
26.3.2 Minimum Distance between Individual Bars
(a) The horizontal distance between two parallel main reinforcing bars shall
usually be not-less than the greatest of the following:
(i) Dia of larger bar and
(ii) 5 mm more than nominal maximum size of coarse aggregate.
(b) When needle vibrators are used it may be reduced to 2/3rd
of nominal
maximum size of coarse aggregate,
Sufficient space must be left between bars to enable vibrator to be immersed
(c) Where there are two or more rows of bars, bars shall be vertically in line and
the minimum vertical distance between bars shall be 15 mm, 2/3rd of nominal
maximum size of aggregate or the maximum size of bars, whichever is greater.
26.5.2 Slabs
The rule given in 26.5.2.1 and 26.5.2.2 shall apply to slabs in addition to those given
in the appropriate clause.
26.5.2.1 Minimum reinforcement
The mild steel reinforcement in either direction in slabs shall not be less than 0.15
percent of the total cross-sectional area. However, this value can be reduced to 0.12
percent when high strength deformed bars or welded wire fabric are used.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 18
26.5.2.2 Maximum diameter
The diameter of reinforcing bars shall not exceed one eight of the total thickness of
slab.
26.3.3 Maximum distance between bars - Slabs
1) The horizontal distance between parallel main reinforcement bars shall not be
more than three times the effective depth of solid slab or 300 mm whichever is
smaller.
2) The horizontal distance between parallel reinforcement bars provided against
shrinkage and temperature shall not be more than five times the effective depth of a
solid slab or 300 mm whichever is smaller.
Torsion reinforcement - Slab
Torsion reinforcement is to be provided at any corner where the slab is simply
supported on both edges meeting at that corner. It shall consist of top and bottom
reinforcement, each with layers of bars placed parallel to the sides of the slab and
extending from the edges a minimum distance of one-fifth of the shorter span. The
area of reinforcement in each of these four layers shall be three-quarters of the area
required for the maximum mid-span moment in the slab.
D-l.9 Torsion reinforcement equal to half that described in D-l.8 shall be provided at a
corner contained by edges over only one of which the slab is continuous.
D-1.10 Torsion reinforcements need not be provided at any comer contained by edges
over both of which the slab is continuous.
26.5.3 Columns
A. Longitudinal Reinforcement a. The cross sectioned area of longitudinal reinforcement shall be
not less than 0.8% nor more than 6% of the gross sec tional area of
the column. Although it is recommended that the maximum area
of steel should not exceed 4% to avoid practical difficult ies in
placing & compacting concrete.
b. In any column that has a larger cross sectional area than that
required to support the load, the minimum percentage steel must
be based on the area of concrete resist the direct stress & not on
the actual area.
c. The bar should not be less than 12 mm in diameter so that it is
sufficiently rigid to stand up straight in the column forms durin g
fixing and concerting.
d. The minimum member of longitudinal bars provided in a column
shall be four in rectangular columns & six in circular columns.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 19
e. A reinforced concrete column having helical reinforcement must
have at least six bars of longitudinal rein forcement with the
helical reinforcement. These bars must be in contact with the
helical reinforcement & equidistance around its inner
circumference.
f. Spacing of longitudinal should not exceed 300 mm along
periphery of a column.
g. In case of pedestals, in which the longitudinal reinforcement is
not taken into account in strength calculations, nominal
reinforcement should be not be less than 0.15% of cross
sectional area.
B. Transverse Reinforcement
a. The diameter of lateral ties should not be less than ¼ of t he
diameter of the largest longitudinal bar in no case should not
be less than 6 mm.
b. Spacing of lateral ties should not exceed least of the
following:-
Least lateral dimension of the column.
16 times the smallest diameter of longitudinal bars to be
tied.
300mm.
Shear
40.1 Nominal Shear Stress
The nominal shear stress in beams of uniform depth shall be obtained
by the following equation:
τv = Vu/ b.d
where
Vu = shear force due to design loads;
b = breadth of the member, which for flanged section shall be taken as
the breadth of the web, bw; and
d = effective depth.
40.2.3 With Shear Reinforcement
Under no circumstances, even with shear re inforcement, shall the
nominal shear stress in beams should not exceed given in Table 20.
40.2.3.1 For solid slabs, the nominal shear stress shall not exceed half
the appropriate values given in Table 20.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 20
40.3 Minimum Shear Reinforcement
When τv, is less than τc given in Table 19, minimum shear
reinforcement shall be provided in accordance with 26.5.1.6.
40.4 Design of Shear Reinforcement
When τv , is exceeds τ c , given in Table 19, shear reinforcement shall
be provided in any of the following forms:
a) Vertical stirrups,
b) Bent-up bars along with stirrups, and Where bent -up bars are
provided, their contribution towards shear resistance shall not be more
than half that of the total shear reinforcement.
Shear reinforcement shall be provided to carry a shear equal to Vu – τ c b d. the
strength of shear reinforcement Vus shall be calculated as below:
a) For Vertical Stirrups:
0.87 fy Asv d
Vus = ___________
Sv
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 21
b) For inclined stirrups or a series of bars bent up at different cross –section:
0.87 fy Asv d
Vus = ___________ (Sin ά + Cos ά)
Sv c) For single bar or single group of parallel bars, all bent up at the same
cross sections:
Vus = 0.87 fy Asv Sin ά
Where
Asv = total cross –sectional area of stirrups legs or
bent-up bar within a distance Sv,
Sv = spacing of the stirrups or bent-up bars along the
length of the member.
τ v = nominal shear stress,
τ c = design shear strength of the concrete,
b = breadth of the member which for flanged beams,
shall be taken as the breadth of the web bw.
fy = characteristic strength of the stirrup or bent-up
reinforcement which shall not be taken greater
than 415 N/mm2,
ά = angle between the inclined stirrup or bent up bar
and the axis of the member not less than 45o,
and
d = effective depth
Development Length Of Bars
26.2 Development of Stress in Reinforcement
The calculated tension or compression in any bar at any section shall be developed on
each side of the section by an appropriate development length or end anchorage or by
a combination thereof.
Development length Ld is given by
Ld = υσst /4τbd
υ = nominal diameter of bar, τbd = design bond stress
σst = stress in bar at the section considered at design load
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 22
Design bond stress in limit state method for plain bars in tension is given in
clause 26.2.1.1
For deformed bars conforming to IS 1786 these values are to be increased by
60 %.
For bars in compression, the values of bond stress for bars in tension is to be
increased by 25 percent
B. Shear reinforcement (STIRRUPS)
Development length and anchorage requirement is satisfied, in case of stirrups and
transverse ties, when Bar is bent –
• Through an angle of at least 90 degrees (round a bar of at least its own dia) &
is continued beyond for a length of at least 8 φ, or
• Through an angle of 135 degrees & is continued beyond for a length of at least
6 φ or
• Through an angle of 180 degrees and is continued beyond for a length of at
least 4 φ
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 23
As per IS-875(Part-1)-1987
0.16-0.23STEEL WORK -ROOFING
0.65MANGLORE TILES
0.15GI SHEET -ROOFING
0.16AC SHEET -ROOFING
78.5STEEL
18LIME -PLASTER
21CEMENT-PLASTER
6-10TIMBER
21-27STONE MASONRY
19-20BRICK MASONRY
25REINFORCED CONCRETE
24PLAIN CONCRETE
kN/m2kN/m3
UNIT WEIGHT
MATERIAL
DEAD LOADS – UNIT WEIGHTS OF SOME MATERIALS/BUILDING COMPONENTS
4.0STAIRS-NOT LIABLE TO OVER CROWDING
5.0- LIABLE TO OVER CROWDING
7.5–HEAVY VEHICLES
4.0GARRAGES –LIGHT VEHICLES
10.0STACK ROOM IN LIBRARIES ,BOOK STORES
5.0-10 FACTORIES & WAREHOUSES
5.0- WITHOUT FIXED SEATING
4.0- WITH FIXED SEATING
SHOPS,CLASS ROOMS,WAITINGS ROOMS,
RESTAURANTS,WORK ROOMS,THEATRES ETC
4.0– WITHOUT SEPARATE STORAGE
2.5 OFFICIAL – WITH SEPARATE STORAGE
2.0 RESIDENTIAL
LIVE LOAD
(kN/m2)TYPE OF FLOOR USAGE
LIVE LOADS ON FLOORS AS PER IS-875(Part-2)-1987
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 24
Steps for Design of a Multi -Storeyed Building:-
Manual Method of Analysis & Design : -
Step1: Study of architectural Drawings :- Before proceeding for
structural design of any building it is ensure that approved working
drawings are available in the office. All working drawings i.e. each
floor plan , elevations, sec tions, are studied thoroughly & discrepancy
if any brought to the notice of concern Architect for
rectification/correction. The problems coming in finalization of
structural configuration may also be intimated to concern Architect for
rectification/correction if any.
Step2: Finalization of structural Configuration . After receiving
corrected working drawing from the architectural wing, t he structural
system is finalized. The structural arrangements of a building is so
chosen as to make it efficient in resisting vertical as well as horizontal
loads due to earthquake. The span of slabs co chosen that thickness of
slab 100-150mm and slab panels, floor beams, and columns, are all
marked and numbered on the architectural plans. Now the building is
ready for structural design to start.
0.75 ROOF WITHOUT ACCESS
1.5 ROOF WITH ACCESS
LIVE LOADS ON ROOFS
12.0WEATHER MAKER
10.0MDF ROOM
6.0 OMC ROOM,DDF ROOM,POWER PLANT,
BATTERY ROOM
6.0 SWITCH ROOM(NEW TECHNOLOGY)
LIVE LOAD
(kN/m2)TYPE OF FLOOR USAGE
LIVE LOADS ON FLOORS OF T.E.BLDGS
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 25
ISOMETRIC VIEW OF FRAMED STRUCTURE
Step3: Load Calculation and analysis . For each floor or roof, the
loading intensity of slab is calculated taking into account the dead load
of the slab, finish plaster, et c. including partitions and the live load
expected on the floor, depending on the usage of the floor or roof. The
linear loading of beams, columns, walls, parapets, etc. also calculated.
Step3 (a): Preliminary Sizes of structural members. Before
proceeding for load calculation preliminary sizes of slabs, beams,&
columns decided. In manual load calculation preliminary sizes of
structural members should be judicially f ixed as once load calculation
& analysis is done i t is not easy to revise the same. But in computer
aided analysis & design it can be revised easily.
Slab:- The thickness of the slab decided on the basis of
span/d ratio assuming appropriate modification factor.
Beam : The width the beam generally taken as the width of
wall i .e 230 or 300 mm. The width of beam is help full in
placement of reinforcement in one layer & more width is
help full in resisting shear due to torsion. The depth of
beam is generally taken as 1/12 th (for Heavy Loads) to
1/15 th (for Lighter Loads) of span.
Column:- Size of column depends upon the moments from
the both the direction and the axial load. Preliminary
Column size may be finalized by approximately calculation
of axial load & moments.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 26
Procedure for vertical load calculation on Columns:
Step(i): First , the load from slab (including Live load & Dead Load) is
transferred on to the adjoining beams using formulas given
below|: -
For computation of shear force on beams & reactions on
columns, an equivalent uniformly distributed load per linear
meter of beam may be taken as :
Equivalent u.d.l. on short beam of slab panel = w B/4.0
Equivalent u.d.l. on long beam of slab panel = w B/4 x [2 -(B/L)]
Where w is the total load on the slab panel in Kn/Sqm & L & B are
long span & short spans of slab panel respectively.
Step(ii): Over this load, the weight of wall (if any), self weight of
beam etc. are added to get the load on beam (in running
metre).
Step(iii):The load (in running metre) on each beam is calculated as in
Step 1 & Step 2 .
Step(iv):Then the loads from the beams are transferred to the columns.
Step(v):Step (i) to Step (v) is repeated for each floor.
Step(vi):These loads at various floors on each column are then added to
get the total loads on each column, footing and the whole
building.
Step4: Horizontal (Seismic) Load Calcultaion:
The Horizontal Load Calculation or the Load Calculations for Seismic
case is carried out as per the Indian Standard Code IS:1893 -2002.
The loads calculated in Para -II above at various floor l evels are
modified as per the requirement of Para 7.3.1 of IS:1893 -2002.
The Seismic Shear at various floor levels is calculated for the whole
Building using the values from IS 1893-2002.
Calculation of horizontal loads on buildings
(As per is-1893-2002)
Sample example for horizontal load calculation
(I) Building is on seismic zone-iv (II) Foundation type isolated footings
As per clause 7.5.3 of IS-1893-2002 Design base shear v b
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 27
Vb = Ah W (F)
Where Ah = Design Horizontal acceleration spectrum value as per 6.4.2
of the code
= (Z/2) (I/R) (Sa/g)
Where Z = Zone factor as per table 2 of IS Code (1893-2002)
= 0.24 (in this case)
I = Importance factor as per table 6 of IS-1893-2002)
= 1.5 (Assuming that the bldg. is T.E. Bldg.)
R = Response reduction factor as per table 7 of IS code
= 3.0 (for ordinary R.C. Moment resist ing frame (OMRF)
(Sa/g) = Average response acceleration coefficient for soil type
& appropriate natural periods and lamping of the
structure.
For calculating of (Sa/g) value as above we have to calculate value of
T i.e. Fundamental National Period (Seconds) ( Clause 7.6 of IS Code)
T = 0.075 h 0 .7 5
(For RC Frame building)
= 0.0 85 h 0 .7 5
(For Steel frame building)
h = Height of building in Meter
In case of building with brick in fills walls.
T = 0.09 h /d 1 / 2
Where h = height of building in Meter
and d = Base dimension of the building at the plinth level in
Meter along the considered direction of the lateral
force.
Value of (Sa/g) is to be read from fig 2 on page 16 of IS Code
depending upon Soil condition & Fundamental Natural period T.
Or the value of (Sa/g) may be calculated on the basis of Following.
Formulas:-
(i) For rocky, or hard soil sites
(Sa/g) = 1+15 T if 0.00≤T≤ 0.10
= 2.50 if 0.10≤T≤ 0.40
=1.00/T if 0.40≤T≤ 4.00
(ii) For medium soil sites
(Sa/g) = 1+15 T if 0.00≤T≤ 0.10
= 2.5 0 if 0.10≤T≤0.55
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 28
= 1.36/T if 0.55≤T≤ 4.00
(iii) For soft soil si tes
(Sa/g) = 1+15 T if 0.00≤T≤
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 29
A
B
C
2 b
ays @
7.5
m C
/C
TYPICAL FLOOR PLAN
Bldg. is three storey with Each
storey of 5.0m height
4 bays @ 4.0 m C/C
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 30
164.9
157.99
47.01
Frame with EQ Loads
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 31
Calculating Seismic weight of building per frame for frame (B)
Length bldg = 16.00 M
C/C distance of frames = 7.50 M
Density of R.C.C = 25 KN/m3
Floor slab = 0.15×16.00×7.50×25 = 450 KN (A)
Column below slab = 0.300×(0.70-0.15)×16.00×25
= 0.30×0.55×16.00×25=66 KN (B)
Columns = 0.30×0.60×(5.00+5.00)/2 ×25× 5 = 112.5 KN (C)
Live load = 600 kg/m2 = 6.00 kn/m
2
As per table 8 of code when live load is above 3.00 kn/m2 50% of l ive
load to be considered for lamp mass calculation.
Lump mass at First Floor = 0.50×6.00×16×7.50 = 360 KN (D)
Total lamp mass first floor & second floor (Assuming same L.L. on
S.F.)
(A)+(B)+(C)+(D) = 450+66+112.50+360
= 988.50 KN
(ii) Wight lamped at terrace Floor slab: -
= 0.13×16.00×7.50×25 = 390 KN (E)
Beam below slab = 0.23×(0.60-0.15)×16.00×25
= 0.23×0.45×16.00×25
= 41.4.KN (F)
Columns = 0.30×0.600×5.00/2×25×5 = 56.25 KN (G)
L.L. = Nil During Earthquake = 0. ( As per the clause 7.3.2 of the
code the imposed load on roof need not to be considered )
Total lamped mass at terrace level = (E)+(F)+(G)
= 390+41.40+56.25=487.65 KN
Total weight of building per framed per inner frame
F.F = 988.50 KN
S.F. = 988.50 KN
Terrace = 487.65 KN
2464.65 KN
Putting all values in Formulas (F)
LL-- FFRRAAMMEE
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 32
Vb = Design base shear
= (z/z)(I/R(Sa/g) w
Value of T = 0.09 h/Vd
H = Height of bldg. = 15.00 m (3x5.0=15.00m )
d = 16.00 m
T = 0.09×15.00/V 16.00 = 0.3375 = 0.34
For medium soils
For T = 0.34
Sa/g = 2.50
Vb = 0.24/2×1.50/3.00×2.50×2465.65 = 369.85 KN
Distribution base shear is done using formula (clause 7.7)
F i = w i h i 2
/ ∑ w j h j 2
x Vb
Where Fi = Design lateral force at floor i
W i = Seismic weight of f loor i
h i = height of floor in m from base.
n = number of story’s in the building is equal to number of levels at
which masses are located.
Vb = 369.85 KN
Floor W i KN h i (m) W i h i 2 F i
F.F.
S.F.
Terrace level
988.50
988.50
487.65
6.00
11.00
16.00
35586
119608.5
124800
47.01 KN
157.99
164.85
∑w ih i 2 = 279994.5 ∑ = 369.85 KN
Step5. Vertical Load Analysis :
A) General:
The skeleton frame work of a multi storied R.C.C. framed structure is
made up of a system of columns, beams and slabs. It is presumed that
the reinforcements are always so arran ged that all joints of the frame
are monolithic.
In view of the uncertain property of material creep, shrinkage and a
number of approximate simplifying assumptions made in the detailed
analysis of multi storied framed structures (such as conditions of end
restraints etc.) it is considered sufficient to obtain reasonable accuracy
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 33
of analysis for the design of structure. If the normal moment
distribution is applied to all joints, the work involved is enormous.
However with certain assumptions, it is possible to analyze the frames
and get results which will be adequate for design purposes.
To simplify analysis the three dimensional multistoried R.C.C. framed
structure are considered as combinations of planer framed in two
directions. It is assumed that each of these planer frames act
independently of the frames.
Procedure for Frame analysis for calculation of moments in
Columns & beams:
Step(i): First , the load from slab (including Live load & Dead Load) is
transferred on to the adjoining beams using formulas given
below|: -
For computation of Bending Moments in beams , an equivalent
uniformly distributed load per linear meter of beam may be taken as :
Equivalent u.d.l. on short beam of slab panel = w B/3.0
Equivalent u.d.l. on long beam of slab panel = w B/6 x [ 3 -(B/L)2
]
where w is the total load on the slab panel in Kn/Sqm & L & B are
long span & short spans of slab panel respectively.
Step(ii): Over this load, the weight of wall (if any), self weight of
beam etc. are added to get the load on beam (in running
Meter).
Step(iii):The load (in running Meter) on each beam is calculated as in
Step 1 & Step 2.
Step(iv):Step (i) to Step (ii i) is repeated for each floor
Step(v):Then these loads are used as u.d.l on a particular frame for
analysis by moment distribution method as described in the next
section.
b) Method Of Analysis:
Analysis of large framed structures beams too Cumbersome with the
classical method of structure analysis such a Clapeyron’s theorem of
three moments, Castingil iano’s therefore of least work, Poison’s
method of virtual work etc. Therefore, i t become necessary to evolve
simpler methods.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 34
Some of these are: -
a.) Hardy cross method of moment distribution.
b.) Kani’s method of iteration.
C) Hardy Cross Method Of Moment Distribution:
In this method, the ‘balancing’ and ‘carry-over’ constitute one cycle
and it has been found the ‘carry-over’ values converge fast enough to
become quite insignificant after four cycle of operation. it is,
therefore, often adequate to stop the computation after four cycles.
The frame is analyzed by this method either:
i . Floor-wise assuming the columns to be fixed for ends.
or
ii . Taking the frame as a whole. The whole frame analysis can be
carried out for several alternative loading arrangements for
obtaining maximum positive and negative bending moment.
Generally frames are analyzed floor -wise for the worst
conditions of loading.
The method is described in the following steps .
Step1: Calculate the st iffness of all members. E nter them in the
calculation scheme.
Step2: Calculated the distribution factor at al l joints from the
stiffness. Enter them in the calculation scheme.
Step3: Look the joints and calculate the fixed -end moments. Enter
them in the calculation scheme.
Step4: Unlock the joint one by one by applying imaginary external moments
at each joint which nullifier the unbalanced moment at the joint. Distribute the
imaginary external moment among all members
Meeting at the joint in proportion to their relative stiffnes s and enter
these value in the scheme. This operation is called balancing.
Step5: Enter the carry-over moments at the far in the scheme.
Step6: Repeat steps 4 & 5, till the carry-over moments become
insignificant .
Step7: Balance the unbalanced moment obtai ned from the last
carry-over operation.
Step8: Add the initial fixed-end moments, balancing moments and
carry-over moments to get the final end moments in beam
& columns.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 35
A sample of moment distribution method is shown on next two
pages.
CALCULATION OF DISTRIBUTION FACTOR FOR FRAME ANALYSIS
S.NO. JOINT MEMBE
R Size in Cm
Mo ment o f
Iner t i a
Cm4 ( I )
Leng
th of
mem
ber
Cm
K=I /L Su m K D.F .
1
B D
A-I I I
Right
beam 30 45 227812.50 600 379 .69
1030 .58
0 .37
Lo wer
Col . 30 45 227812.50 350 650 .89 0 .63
2
B-II I
Left
beam 30 45 227812.50 600 379 .69
1802 .01
0 .21
Right
beam 30 60 540000.00 700 771 .43 0 .43
Lo wer
Col . 30 45 227812.50 350 650 .89 0 .36
3 C-II I
Left
beam 30 60 540000.00 700 771 .43
1422 .32
0 .54
Lo wer
Col . 30 45 227812.50 350 650 .89 0 .46
4
A-II
Upper
co l . 30 45 227812.50 350 650 .89
1681 .47
0 .39
Right
beam 30 45 227812.50 600 379 .69 0 .23
Lo wer
Col . 30 45 227812.50 350 650 .89 0 .39
5
B-I I
Left
beam 30 60 540000.00 600 900 .00
2973 .21
0 .30
Upper
co l . 30 45 227812.50 350 650 .89 0 .22
Right
beam 30 60 540000.00 700 771 .43 0 .26
Lo wer
Col . 30 45 227812.50 350 650 .89 0 .22
6
C-I I
Left
beam 30 60 540000.00 700 771 .43
2073 .21
0 .37
Upper
co l . 30 45 227812.50 350 650 .89 0 .31
Lo wer
Col . 30 45 227812.50 350 650 .89 0 .31
7
A-I
Upper
co l . 30 45 227812.50 350 650 .89
1572 .99
0 .41
Right
beam 30 45 227812.50 600 379 .69 0 .24
Lo wer
Col . 30 45 227812.50 420 542 .41 0 .34
8
B-I
Left
beam 30 45 227812.50 600 379 .69
2344 .42
0 .16
Upper
co l . 30 45 227812.50 350 650 .89 0 .28
Right
beam 30 60 540000.00 700 771 .43 0 .33
Lo wer
Col . 30 45 227812.50 420 542 .41 0 .23
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 36
9
C-I
Left
beam 30 60 540000.00 700 771 .43
1964 .73
0 .39
Upper
co l . 30 45 227812.50 350 650 .89 0 .33
Lo wer
Col . 30 45 227812.50 420 542 .41 0 .28
FRME ANALYSIS BY MOMENT DISTRIBUTION METHOD
I I I
U.d. l .
28 6 .00
U.D.L
24 7.00
0 .63 0.37 30X45 0.21 0.43 0.36 30X60 0 .54 0.46
0 -84.00 Int .FEM 84.00 0 -98.00 Int .FEM 98.00 0
bal . 52.92 31.08 2 .94 6.02 5.04 -52.92 -45.08
C.O. 14.63 1.47 15.54 0.74 -26.46 2 .52 -12.66
BAL -10.14 -5 .96 2 .14 11.06 3.66 5 .48 4.66
Total 57.41 -57.41 104.62 17.82
-
115.76 53.08 -53.08
Total 38.28 4 .06 -34.87
BAL -17.43 BAL -0.42 BAL 12.99
C.O. 26.46 C.O. 3 .01 C.O. -22.54
29.25 1 .47 -25.32
0 0 0
0 .39 0 .22 0 .31
II 25 6 .00 20 7 .00
0 .39 0.23 0 .3 0 .22 0.26 0 .37 0.31
0 -75.00 Int .FEM 75.00 0 -81.67 Int .FEM 81.67 0
29.25 17.25 2 1 .47 1.73 -30.22 -25.32
C.O. 17.22 1 8 .63 5.39 -15.11 0 .87 -20.22
BAL -17.43 -10.28 -0 .58 -0 .42 -0 .5 15.5 12.99
29.04 -67.03 85.05 6.44 -95.55 67.82 -32.55
Total 41.81 15.18 -51.01
BAL -7.26 3 .66 2 .08
C.O. 14.63 0 .74 -12.66
34.44 10.78 -40.43
0 0 0
0 .41 0 .28 0 .33
I 28 6 .00 30 7 .00
0 .34 0.24 0 .16 0.23 0.33 0 .39 0.28
0 -84.00 Int .FEM 84.00 0
-
122.50 Int .FEM 122.50 0
28.56 20.16 6 .16 8.86 12.71 -47.78 -34.3
C.O. 0 3 .08 10.08 0 -23.89 6 .36 0
BAL -6.02 -4 .25 2 .09 3.01 4.31 2 .46 1.76
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 37
22.54 -65.01 102.33 11.87
-
129.37 83.54 -32.54
A B C
Step6. Horizontal Load Analysis:-
Frame analysis for horizontal loads calculated in step 4 is carried out
by using :-
(a)Approximate Method: -
i) Canti lever method.
ii) Portal method.
Approximate methods are used for preliminary designs only. For final
design we may use exact method i.e (i) Slope deflection or matrix
methods (ii) Factor method.
We will not discuss these methods in detail as now modern computer
package as STAAD PRO is available for analysis.
Step7: Design Of Coulmn,Foundations, Beams & Slabs:
After load calculation & anal ysis for vertical & horizontal loads,
design of Columns ,Foundations, Beams, Slabs and are to be carried
out as per the various clauses of IS codes, IS 456 -2000, IS:1893-2002,
IS:13920-1993 etc.
The Design of Column, Foundation, Beams and Slabs are discussed in
details in following section.
A. Design of columns: - With the knowledge of (i) Vertical load (ii)
Moments due to horizontal loads on either axis;(i ii) Moments due to
vertical loads on either axis, acting on each column, at all floor levels
of the building, columns are designed by charts of SP-16(Design Aids)
with a load factor of 1.5 for vertical load effect and with a load factor
of 1.2 for the combined effects of the vertical and the horizontal loads.
The step confirms the size of columns assumed in the architectural
drawings. The design of each column is carried out from the top of
foundation to the roof, varying the amount of steel reinforcement for
suitable groups for ease in design. Further, slenderness effects in ea ch
storey are considered for each column group.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 38
Important Considerations in design of Columns: -
(i)Effective height of column :- The effective height of a column is
defined as the height between the points of contra flexure of the
buckled column. For effective column height refer table 28 (Annexure
E) of IS: 456-2000.
For framed structure effective height of column depends upon relative
stiffness of the column & various beams framing into the column at its
two ends. (Refer Annexure E of IS: 456-2000.)
(ii)Unsupported Length : - The unsupported length l , of a compression
member shall be taken as the clear distance between end restraints
except that:-
In beam & slab construction, it shall be the clear distance between the
floor & under side of the shallower beam framing into the columns in
each direction at the next higher floor level.
(iii) Slenderness limits for columns : - The unsupported length between
end restraints shall not exceed 60 times the least lateral dimension of a
column.
(iv) Minimum Eccentricity : - All columns shall be designed for
minimum eccentricity equal to unsupported length of column/500 plus
least lateral dimension/30, subject to a minimum of 20 mm.
Or emin ≥ l/500+ D/30 ≥ 20 mm
Where l= unsupported length of column in mm.
D=Lateral dimension of column in the direction under
consideration in mm.
(v)Design Approach : - The design of column is complex since it is
subjected to axial loads & moments which may very independentl y.
Column design required: -
I. Determination of the cross sectional dimension. II. The area of longitudinal steel & its distribution.
III. Transverse steel .
The maximum axial load & moments acting along the length of the
column are considered for the design of the column section either by
the working stress method or limit state method.
The transverse reinforcement is provided to impart effective lateral
support against buckling to every longitudinal bar. It is either in the
form of circular rings of polygonal links (lateral ties).
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 39
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 40
B. Design of foundations: - With the knowledge of the column loads
and moments at base and the soil data, foundations for columns are
designed
The following is a list of different types of foundations in order to
preference with a view to economy: (i) Individual footings (ii)
Combination of individual and combined footings (iii) Strip footings
with retaining wall acting as strip beam wherever applicable; (iv) Raft
foundations of the types (a) Slab (b) beam -slab.
The brick wall footings are also designed at this stage. Often, plinth
beams are provided to support brick walls and also to act as earthquake
ties in each principal direction. Plinth beams, retaining wall if any, are
also designed at this stage, being considered as part of fou ndations.
Important Considerations in design of Foundations: -
a) Introduction: - Foundations are structural elements that transfer
loads from the building or individual column to the earth. If these
loads are to be properly transmitted, foundations must be designed
to prevent excessive settlement or rotation, to minimize differential
settlement and to provide adequate safety against sliding and over
turning.
b) Depth of foundation:-
Depth of foundation below ground level may be obtained by using Rankine's
formula
2
p 1 – Sin Ø
h = - - - - - - - - - - - - - - -
γ 1 + Sin Ø
Where
h = Minimum depth of foundation
p = Gross bearing capacity
γ = Density of soil
Ø = Angle of Repose of soil
c) Recommendations of is 456 -2000, limit state design, bending,
shear, cracking & development
i) To determine the area required for proper transfer of total load on the soil, the
total load (the combination of dead, live and any other load without multiplying it
with any load factor) need be considered.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 41
Total Load including Self Weight
Plan Area of footing = -------------------------------------
Allowable bearing capacity of soil
i i) IS 1904 – 1978, Code of Practice for Structural S afety of Buildings : shallow foundation, shall govern the general details.
iii) Thickness of the edge of footing: -(Reference clause 34.1.2 )
The thickness at the edge shall not be less than 15 cm for footing on
soils.
iv) Dimension of pedestal: -
In the case of plain Cement Concrete pedestals, the angle between the plane passing
through the bottom edge of the pedestal and the corresponding junction edge of the
column with pedestal and the horizontal plane shall be governed by the expression.
100 qo
Tan α (should not be less than) 0.9 x ----------- + 1
Fck
Where
qo = Calculated maximum bearing pressure at the base of
the
pedestal/footing in N/mm2
fck = Characteristic strength of concrete at 28 days in
N/mm2
(v) Bending Moment
PLAIN
CONCRETE
PEDESTAL
α
Column
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 42
(Reference Clauses- 34.2.3.1 & 34.2.3.2)
ISOLATED COLUMN FOOTING
The bending Moment will be considered at the face of column, Pedestal or wall
and shall be determined by passing through the section a vertical place which
extends completely across the footing, and over the entire area of the footing or,
one side of the said plane.
FACE OF
PEDESTA
L
X Y
X Y
COLUMN
PEDESTAL BASE
FACE OF
COLUMN
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 43
(vi)Shear
(Reference Clause 33.2.4.1)
The shear strength of footing is governed by the following two factors:-
a) The footing acting essentially as a wide beam, with a potential diagonal
crack intending in a plane across the entire width, the critical section for
this condition shall be assumed as a vertical section located from the face
of the column, pedestal or wall at a distance equal to the effective depth of
the footing in case of footings on soils.
For One Way Bending Action
For one way shear action, the nominal shear stress is calculated as follows:-
Vu
τv = -------
b.d
Where
τv = Shear stress
Vu = Factored vertical shear force
b = Breadth of critical section
d = Effective depth
τv < τc ( τc = Design Shear Strength of Concrete Based on % of longitudinal
tensile reinforcement refer Table 61 of SP-16)
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 44
CRITICAL SECTION FOR ONE -WAY SHEAR
(For Two Way Bending Action)
For two may bending action, the following should be checked in punching shear.
Punching shear shall be around the perimeter 0.5 time the effective depth away from
the face of column or pedestal.
For two way shear action, the nominal shear stress is calculated in accordance
with lause 31.6.2 of the code as follows:-
Vu
τv = ----------
b0.d
Where
τv = Shear stress
b0 = Periphery of the critical section
d = Effective depth
Vu = Factored vertical shear force
B
A
CR IT IC A
L SECT IO
N
d
d
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 45
When shear reinforcement is not provided, the nominal shear stress at the critical
section should not exceed [Ks. τc]
Where
Ks = 0.5 + Bc (But not greater than 1)
Short dimension of column or pedestal
Bc = ----------------------------------------------------
Long dimension of column or pedestal
τc = 0.25 fek N/mm2
Note:-It is general practice to make the base deep enough so that shear reinforcement
is not required.
(vii)Development Length
(Reference Clause 34.2.4.3)
The critical section for checking the development length in a footing shall be assumed
at the same planes as those described for bending moment in clause 34.2.3 of code (as
discussed 4.5 of the handout) and also at all other vertical planes where abrupt
changes of section occur.
(viii) Reinforcement:- The Min % of steel in footing slab should be 0.12% &
max spacing should not be more than 3 times effective depth or 450 mm whichever
is less. (Reference Clause 34.3)
Only tensile reinforcement is normally provided. The total reinforcement shall be laid
down uniformly in case of square footings. For rectangular footings, there shall be a
central band, equal to the width of the footings. The reinforcement in the central band
shall be provided in accordance with the following equation.
Reinforcement in central Band width 2
-------------------------------------------------- = ------
Total reinforcement in short direction B + 1
Where
Long side of footing
B = ---------------------------
Short side of footing
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 46
(ix)Transfer of Load at the Base of Column
(Reference Clause 34.4)
The compressive stress in concrete at the base of column or pedestal shall be
transferred by bearing to the top of supporting pedestal or footing.
The bearing pressure on the loaded area shall not exceed the permissible bearing
stress in direct
A1
Compression multiplied by a value equal to ------
A2
but not greater than 2
Where
A1 = Supporting area for bearing of footing, which is sloped or
stepped footing may be taken as the area of the lower base of
the largest frustum of a pyramid or cone contained wholly with
in the footing and having for its upper base, the area actually
loaded and having side slope of one vertical to two horizontal.
A2 = Loaded area at the column base.
For limit state method of design, the permissible bearing stress shall be = 45 fek
4.91 If the permissible bearing stress is exceeded either in column concrete or in
footing concrete, reinforcement must be provided for developing the excess force.
The reinforcement may be provided either by extending the longitudinal bars into
the footing or by providing dowels in accordance with the code as give in the
following:-
1) Minimum area of extended longitudinal bars or dowels must be 0.5% of
cross sectional area of the supported column or pedestal.
2) A minimum of four bars must be provided.
3) If dowels are used their diameter should not exceed the diameter of the
column bars by more than 3 mm.
4) Enough development length should be provided to transfer the
compression or tension to the supporting member.
5) Column bars of diameter larger than 36 mm, in compression only can be
dowelled at the footing with bars of smaller diameters. Te dowel must
extend into the column a distance equal to the development length of the
column bar. At the same time, the dowel must extend vertically into the
footing a distance equal to the development length of the dowel.
E2-E3/Civil Rev date: 01-04-2011
BSNL India For Internal Circulation Only Page: 47
C. Design of Floor slabs:-. Design of floor slabs and beams is taken up with the First Floor & upwards .The
slabs are designed as one-way or two-way panels, taking the edge conditions of the supporting edges in to
account, with the loading already decided as per functional use of slab panel.
The design of floor slab is carried out as per clause 24.4 & 37.1.2 & Annexure D of IS: 456-2000.
The Bending moment coefficients are to be taken from table- 26 of the code depending upon the support
condition & bending moment calculated & reinforcement steel may be calculated from the charts of SP-16. The
slab design for particular floor may be done in tabular form as shown below.
SLAB DESIGN
Name of project: -
Level of s lab
Sla
b
ID
Edge
condi t i
on
Total
load in
KN/Sq
.m w
Shor
t
span
lx
m
long
spa
n
l y
m
ly/
lx
1 .5
*w* lx
*lx
s lab
th ic
knes
s in
mm
Shor t span Mo ment KN -M
Stee l
in
shor t
span
Lon g sp an mo ment KN-M
Stee l
in
long
span
αx
(+)
Αx
( - )
mux
+
mux
-
Stee
l
Αy
(+) αy( - )
muy
+
muy
- Stee l
1 2 3 4 5 6 7 8 9 1 0 11=
7 x 9
12=
7
x10
13 1 4 15
16=
7
x14
17=
7
x15
1 8
S1
Two
Adj .
Edge.
Discon
t.
(Case
No.4)
8 .50 3 .5
0
5.2
5
1 .
5
156.8
0 120
0.05
6
0.07
5 8 .78
11.7
6
0 .03
5
0.047
5 .49 7 .37
S2
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 48
Method of calculation of steel from Tables of SP -16 for slab design
Determine the main reinforcement required for a slab with the
following data:
Factored moment Mu 9.60 kN.mper Metre width
Depth of slab 10 cm
Concrete mix M 20
Characteristic strength a) 415 N/mm2
Method Of Referring To Tables For Slabs
Referring to table 35 (for fck=20 & fy = 415 N/mm2), directly we get
the following reinforcement for a moment of resistance of 9.60 kN.m
per Metre width:
8 mm dia at 13 cm spacing
or 10 mm dia at 210 cm spacing
Reinforcement given in the table is based on a cover of 15 mm or bar
diameter which- ever is greater.
Check for Deflection:-Slab is also checked for control of Deflection
as per clause 23.2.1, 24.1 & Fig 4. of the IS:456-2000.
D. Design of floor Beams:-. The beams are designed as continuous
beams, monolithic with reinforced concrete columns with their far ends
assumed fixed. The variation in the live load position is taken into
account by following the two-cycle moment distribution. the moments
are applied a face correction to reduce them to the face of the
members. The moments due to horizontal loads are added to the above
moments. Each section of the beam is designed for load factor of 1.5
for vertical load effect and with a load factor of 1.2 for the combined
effects of the vertical and the horizontal loads.
The effect of the shear due to vertical and horizontal loads is also
similarly taken care of. It may be noted that the shear component due
to wind or earthquake may be significant and it may affect the size and
the range of shear stirrups. Bent - up bars are not effective for
earthquake shear due to its alternating natu re. The beam design can be
easily done by a computer program which will give reinforcement at
various cri tical sections along the length of the beam and also shear
stirrups required it saves considerable time and labour of a designer.
In manual method span of a beam is generally designed at three
sections i .e at two supports & at Mid span. The each section is
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 49
designed for factored Moment, Shear & equivalent shear for Torsion if
any at a section.
Two examples of beam design are given below illustrat ing calculation
of steel reinforcement with help of SP -16.
Example1.Singly Reinforced Beam
Determine the main tension reinforcement required for a rectangular
beam section with the following data:
Size of beam 30 X 60 cm
Concrete mix M 20
Characteristic strength 415 N/mm2 of reinforcement
Factored moment 170 kN.m
Assuming 20 mm dia bars with 25 mm clear cover,
Effective depth= 600 – 25 – 20/2 = 565 mm
From Table D for f y = 415 N/ mm2
and fck = 20 N/mm2
Mu, l im/bd2
= 2.76 N/ mm2
= 2.76/1000 X (1000)2
= 2.76 X 103
kN/m2
Mu, l im = 2.76 X 103 bd
2
= 2.76 X 103
X 0.300 X0.565X0.565
= 264.32 kN.m
Actual moment of 170 kN.m is less than M u, l im. The section is therefore
to be designed as a singly reinforced (under -reinforced) rectangular
section.
Referring to table 2 of SP-16 we have to calculate Mu/bd2
Mu/bd2
= 170 x106/(300x 565 x565) = 1.78
From Table 2. p t =0.556
A s t=0.556 x 300x 565/100 =942.42mm2=9.42 cm
2
Example2.Doubly Reinforced Beam
(i)Determine the main reinforcements required for a rectangular
with the following data :
Size of beam 30×60cm
Concrete mix M 20
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 50
Characteristic strength of 415/Nmm2
Reinforcement
Factored moment 320Kn.m
Assuming 20 mm dia bars with 25 mm clear cover,
D=600-25 – 20/ 2 =565 mm
From table D, for f y= 415 N/mm2 and fck = 20N/mm
2
Mu2 lim/bd2= 2.76 N/mm
2 = 2.76 × 10
3 KN/m
2
Mu2 lim= 2.76 × 103×0.300×0.565×0.565
= 264.32 KN-M
Actual moment of 320 Kn.M is greater than Mu2 lim hence the section
is to be designed as a doubly reinforced section .
Reinforcement from Table 50
Mu/bd2= 320 × 10
6/ (300×565
2 ) = 3.34 N/mm
2
d’/d = (25+10)/565 = 0.062
Next higher value of d1/d = 0.1, will be used for referring to
Table 50
For Mu/bd2 = 3.34 and d
’/d = 0.10,
p t = 1.152, pc = 0.207
As t = 1.152 x 300x 565/100 =1952.64 mm2 =19.52 cm
2
And
Asc = 0.207 x 300x 565/100 =350.86 mm2 =3.51 cm
2
(ii) Determine the Shear reinforcement (vertical stirrups ) required
for the same beam section if factored shear force is V u =250 KN.
Shear stress τ v = Vu /bd = 250 × 103
/(300× 565) =1.47
N/mm2
τv < τmax( 2.8 N /mm2) hence section is adequate regarding shear
stress.
From table 61 for p t=1.15 τc=0.65 N/mm2
Shear capacity of concrete section = τc × b× d
= 0.65 × 300
×565/1000=110.18 kN
Shear to be carried by stirrups V u s=Vu - τc × b× d = 250 - 110.18
=139.82 kN
Vu s/d = 139.82/56.5 = 2.47 kN/cm
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 51
Referring to table 62 for steel f y = 415 N/mm2 Provide 8 mm
diameter two legged vertical stirrups at 140 mm spacing.
TABLES FOR DESIGN
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 52
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 53
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 54
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 55
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 56
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 57
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 58
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 59
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 60
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 61
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 62
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 63
Detailing As Per Is 13920
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 64
HOOP SPACING
HOOP SPACING< d/4 and 8 db
B = BREADTH OF BEAMdb = DIAMETER OF LONGITUDINAL BAR
2d
d
2d
db
50 m max 50 m max
MIN 2 BARS FOR FULL LENGTHALONG TOP AND BOTTOM FACEAS > MIN. BdAS < MAX Bd
> d /2
BEAM REINFORCEMENT37
E2-E3/Civil Rev date: 01-04-11
BSNL India For Internal Circulation Only Page: 65
Questions:-
1. Which are the important BIS Codes/handouts used for structural
design of RCC buildings?
2. In which seismic zones provisions of IS 13920 is to be adopted
for all reinforced concrete structures?
3. (a) What are the basic values of span to effective depth ratios for
beams as per IS 456 for span upto 10meter for –
(i) Cantilever
(ii) Simply supported
(iii) Continuous
(b) What are the basic values of span to overall depth ratios for two-
way slabs upto 3.5 m span & with Fe415 steel reinforcement and
loading class upto 3KN/m2?
4. What are the provisions of IS 456 for nominal cover to meet
durabili ty requirements? As per IS 456 how much minimum
cover should be provided for –
a) Column b) Footing