From: Aloke Kumar Banerjee Sent: Monday, January 11, 2010 11:24 AMTo: Subhankar MukhopadhyaySubject: FW: MPL - 2 x 135 MW Thermal Power Plant - Ash Handling System - Transmittal No. C-961/KOL/AHS/Trans/E-016 dated 06.01.2010 received at our office on 08.01.2010Importance: High
fyna
From: [email protected] [mailto:[email protected]] Sent: Saturday, January 09, 2010 3:51 PMTo: Aloke Kumar Banerjee; Saswata SenguptaCc: [email protected]; [email protected]; [email protected]; [email protected]; [email protected]: MPL - 2 x 135 MW Thermal Power Plant - Ash Handling System - Transmittal No. C-961/KOL/AHS/Trans/E-016 dated 06.01.2010 received at our office on 08.01.2010Importance: High
M.N. DASTUR & COMPANY (P) LTD, CHENNAI E-MAIL TRANSMISSION 9th January 2010MD-26306ELE-33A
To: Macawber Beekay Pvt. Ltd, Kolkata
Attn: Mr. Aloke K. Banerjee, General Manager(Project)/
Mr. Saswata Sengupta, Sr. Design Executive(Projects)
E-mail: [email protected], [email protected]
Rpt: Madhucon Projects Limited, Hyderabad
Attn: Mr. G. Balaji Divakar, General Manager (Energy Division) E-mail:[email protected]
Rpt: Madhucon Projects Limited, Hyderabad
Attn: Mr.Ch.Raja Rao, General Manager Projects
E-mail:[email protected]
Attn Mr. C. S. P. Mukarji, Sr. Advisor (Technical)
Attn Mr. P. Ganga Rao, Manager (Elec)
E-mail: [email protected], [email protected],
[email protected], [email protected]
From: T. Mahendran, Project Manager,
M.N. Dastur & Company (P) Ltd, Chennai
Re: MPL- 2 x 135 MW Thermal Power Plant- Ash Handling System- Transmittal No. C-961/KOL/AHS/Trans/E-016 dated 06.01.2010 received at our office on 08.01.2010
Dear Sirs,
This has reference to your Transmittal referred above enclosing various documents/drawings for our reference/records. We have gone though the same and our observations on the same are given below for your kind reference and necessary action.
Sl. No.Drawing No. and TitleApproval StatusObservations
1CM7889, Rev-01, Outline Dimension Drawing for D160M Frame Challenger Motor (1 Sheet) Comments as Noted1) The paint shall be smoke grey of shade 692 for outdoor and Admiralty Grey of shade 697 for indoor.
2CT2790, Rev-01,Terminal Box Arrangement for D160M Frame Challenger Motor (1 Sheet) No Comments-
3NIL, Rev-01, Motor Data Sheet (1 Sheet) Comments as Noted1) Please specify the number of starts/hour.2) Please indicate the rated motor output at 50deg C.
3) Please indicate the no load current of the motor.
4) The paint shall be smoke grey of shade 692 for outdoor and Admiralty Grey of shade 697 for indoor. Please confirm.
5) Please indicate the slip @ 100% & at 75% load.
6) The starting current of the motor shall be 600% inclusive of the IS tolerance. Please confirm.
7) Please indicate the motor starting time at rated voltage.
4Superimposed Load TS on Motor TS Curve (at 100% VR) (Ref. D160M4P_7, Issue-A) & Current Time Curve (Ref. D160M4P_7, Issue-A for D160M/11KW/4 Pole Motor (1 Sheet) No Comments-
5.Eff. P.F. Vs. Load Curve (Ref. D160M4P_3, Issue-A) & Thermal Withstand Curve (Ref. D160M4P_2, Issue-A) for D160M/11KW/4 Pole Motor (1 Sheet)No Comments-
Regards,T. MahendranProject Manager
M. N. Dastur & Company (P) Ltd
Chennai.
SGGS:kpm
Pcc: Macawber Beekay Pvt. Ltd, Kolkata with two (2) sets of stamped copies of above drawings