Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

Embed Size (px)

Citation preview

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    1/39

    Technical Documentat ion

    Dynamic Modelling of Doubly-Fed

    Induction Machine Wind-Generators

    G m b H

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    2/39

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1

    DIgSILENT GmbHHeinrich-Hertz-Strasse 9D-72810 GomaringenTel.: +49 7072 9168 – 0Fax: +49 7072 9168- 88http://www.digsilent.de-mail: [email protected]

    Dynamic Modelling ofDoubly-Fed InductionMachine Wind-Generators

    Published byDIgSILENT GmbH, Germany

    Copyright 2003. All rightsreserved. Unauthorised copyingor publishing of this or any partof this document is prohibited.

    doc.TechRef, 14 August 2003

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    3/39

    1   I n t r o d u c t i o n

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2

    1 Introduction

    The electrical systems of several European countries contain large amounts of embedded wind generation and similar scenarios

    are foreseen in other parts of the world. This aspect, together with the significant size of new wind farm projects, requires

    realistic modelling capabilities of wind generators for proper assessment of power system planning and impact analysis of future

    wind generation.

     As a result of research and consulting activities of DIgSILENT, generic dynamic models of different types of wind power

    generation were developed. These models are now available in the standard Wind-Power  library of PowerFactory .

    This document describes a doubly-fed induction generator wind turbine model including all relevant components. At the same

    time, this document is a reference to all DFIG-related models of the Wind-Power  library.

    The presented models are mainly intended for stability analysis of large power systems. The proper response of the models to

    network faults was in the centre of interest, but the models can also be used for simulating the impact of wind fluctuations to

    power systems.

    There is no wind model included in this description. However, any type of stochastic or deterministic wind model, or measured

    wind speeds can be connected to the wind speed input of the presented model.

    The models are intended for balanced and unbalanced RMS calculations typically applied in stability studies. However, it is also

    possible to perform electromagnetic transient simulations with these models.

    The basic structure of the model is briefly described in this section and more thoroughly analyzed in the following sections.

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    4/39

    2   T h e D o u b l y - F e d I n d u c t i o n M a c h i n e C o n c e p t

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3

    2 The Doubly-Fed Induction Machine Concept

    DFIG

    External Grid

    Prime

    Mover 

    Grid Side

    Converter 

    Rotor Side

    Converter 

    Protection

    Control Control

    Figure 1: Doubly-Fed Induction Generator Concept 

    The general concept of a Doubly-Fed Induction Generator (DFIG) is shown in Figure 1.

    The prime mover, consisting of a pitch-angle controlled wind turbine, the shaft and the gear-box drives a slip-ring induction

    generator. The stator of the DFIG is directly connected to the grid, the slip-rings of the rotor are fed by self-commutated

    converters. These converters allow controlling the rotor voltage in magnitude and phase angle and can therefore be used for

    active- and reactive power control.

    In the presented model, the converters and controllers are represented to the necessary extent. Both the rotor- and the grid-

    side controllers are modelled in full detail, including fast current control loops. However, for many applications the fast control

    loops of the grid side converter can be approximated by steady state models.

    With the rotor side converter, the situation is different due to protective practices in DFIG. For protecting the rotor-side

    converter against over-currents, it is usual practice to bypass the rotor-side converter during system faults. Whether the DFIG is

    totally disconnected from the system or not, depends on the actual deepness of the voltage sag and on the applied protectionphilosophy. The correct modelling of the rotor bypass, usually called “crow bar protection”, is essential to assess voltage

    stability of large farms during faults in the transmission- or distribution network. For this reason, it is necessary to model even

    the fast current controls of the rotor side converter to effectively determine the operation of the crow bar. Other protection

    functions also found in DFIG such as over/under-speed and over/under-voltage are considered in the proposed model as wel

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    5/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   4

    3 The DFIG Wind-Generator Model

    3.1 Overview

    Prime Mover 

    (To Protection System)

    (From Protection System)

    omega..

    pt

    Pwind

    beta

        u

    bypass

    P;Q

        c    o    s    p     h . .

    Ifq_ref;Ifd_ref 

    Pref 

    iq;id

    Pfq;Pfd

    psis_..

    speed

    Pmq ; Pmd

    Irot

         I     f    q    ;     I . .

    Shaft*

    Pitch Control*

    Transformatio..*

    Current Measurement*

    V meas.StaVmea*

    ProtectionElmPro*

    Turbine*

    vw

    MPTElmMpt*

    PQ ControlElmGen*

    Qref 

    Current Control*

    DFIGElmAsm*

    Power MeasurementStaPqmea

    DFIG:      D      I     g      S      I      L      E      N      T

    Figure 2: Complete Scheme of the Doubly-Fed Induction Machine Wind Generator 

    The complete scheme of a doubly-fed induction machine wind generator is shown in Figure 2. The main components are:

    •  The prime mover consisting of the pitch angle controller, the wind turbine and the shaft (Pitch-Control, Turbine,

    Shaft) 

    •  Doubly-Fed induction generator (DFIG) 

    •  The control-system regulating active and reactive power of the DFIG through the rotor-side converter applying a

    maximum power tracking strategy (MPT, Power Measurement, PQ Control, Current Control, Current Measurement) 

    •  Protection-system (V meas., Protection) 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    6/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   5

    The models of all major components are described in the following sections. It is important to point out that these models can

    be used in combinations that differ from Figure 2, e.g. realizing power-dependent speed control instead of the speed-dependent

    power control.

     Additionally, the model can be extended by stochastic or deterministic wind-speed models, more sophisticated voltage and

    frequency control.

    3.2 Prime Mover and Controller

    The prime mover of a wind generator model represents the conversion of kinetic energy stored in the air flowing through the

    blades into rotational energy at the generator shaft.

    The prime-mover model is subdivided into three sub-models, which are

    •  The turbine that transforms the wind energy into rotational energy at the turbine shaft.

    •  Blade angle controller.

    •  Shaft coupling turbine and generator including the gear-box.

    3.2.1 Wind Turbine

    In this section all aspects related to the power conversion from kinetic wind energy to rotational energy that are of relevance

    for the stability model are explained.

    The kinetic energy of a mass of air m  having the speed vw is given by:

    2

    2  wk    v

    m E    ⋅=  (1)

    The power associated to this moving air mass is the derivative of the kinetic energy with respect to time.

    22

    02

    1

    2

    1ww

    k  vqvt 

    m

     E  P    ⋅⋅=⋅

    ∂⋅=

    ∂=  (2)

    where q  represents the mass flow given by the expression:

     Avq w  ⋅⋅= ρ   (3)

    ρ is the air density and A  the cross section of the air mass flow.

    Only a fraction of the total kinetic power can be extracted by a wind turbine and converted into rotational power at the shaft.

    This fraction of power (PWIND) depends on the wind speed, rotor speed and blade position (for pitch and active stall control

    turbines) and on the turbine design. It is usually denominated aerodynamic efficiency Cp :

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    7/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   6

    Figure 3: Typical Cp(β , λ) Characteristic 

     

    0 P  P Cp   Wind = (4)

    For a specific turbine design, the values of Cp are usually presented as a function of the pitch angle (β) and the tip speed ratio

    (λ). The tip speed ratio is given by:

    w

    TUR

    v

     R⋅= ω 

    λ   (5)

    R is the radius of the turbine blades and ωTUR  is the turbine speed.

    PowerFactory  allows the input of a two-dimensional lookup characteristic (for different values of β and λ) to define Cp. A two-

    dimensional, cubic spline-interpolation method is used for calculating points between actually entered values. The high accuracy

    of the interpolation method avoids the need of entering a large number of points (see also Figure 3).

     Alternatively, analytical approaches for approximating the Cp -characteristic could be used but since these data are usually

    available in tabular formats, no such model was included into the PowerFactory  standard Wind-Power-Library.

    Finally, the mechanical power extracted from the wind is calculated using:

    ( )   32 ,2

      wmech   vCp R P    ⋅⋅⋅⋅=   β λ π  ρ 

      (6)

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    8/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   7 

    The Cp -characteristic can be calculated using special software for aerodynamic designs that is usually based on blade-iteration

    techniques or it can be obtained from actual measurements.

    It has to be pointed out that the presented turbine model is based on a steady state approach and is not able to represent stall

    dynamics.

    The input/output diagram of the turbine model is depicted in Figure 4 and the input-, output- and parameter definitions are

    presented in Table 1 to

    Table 3.

     Figure 4: Input/Output Definition of Wind-Turbine

    Table 1:Input Definition of Wind-Turbine

    Input Symbol Description Unit

    beta   β (6) Blade pitch angle degrees

    vw vw (5,6) Wind Speed m/sec

    omega_tur   ωTUR (5) Turbine Angular Velocity rad/sec

    Table 2: Output Definition of Wind-Turbine

    Output Symbol Description Unit

    Pwind Pmech (6) Generated, Mechanical Power MW

    Table 3: Parameter-Definition of Wind-Turbine

    Output Symbol Description Unit

    R R (5,6) Rotor Blade Radius m

    rho   ρ (6) Air Densitiy kg/m3

    Cp Cp(β,λ) (6) Cp-Characteristic (2-dim. Lookup-table)

    beta

    Wind-Turbine

    vw

    omega_tur

    Pwind

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    9/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   8

    3.2.2 Blade Angle Control

    SERVOBLADE ANGLE CONTROLLER

    speedbeta_ref beta

    ref 

    Time ConstT-

    -PI controller 

    Ka,Tr,Ta

    Vrmin

    Vrmax

    {1/s}

    Ymin

    Ymax

    Limiter 

    rate_cl

    rate_op

    Blade Angle Control:      D      I     g      S      I      L      E      N      T

    Figure 5: Block Diagram of Blade Angle Controller

     Adjusting the blade angle allows varying the power coefficient Cp, and hence controlling the power generated by a wind turbine

    (see also Figure 3).

    The two common concepts are pitch-control and active-stall control. In a pitch-controlled wind turbine, the blades are turned

    into the wind for reducing the lift forces at the blades which lowers the power coefficient.

     Active-stall controlled wind turbines turn the blades out of the wind flow for disturbing the laminar air flow at the blades and

    hence reducing the generated power.

    The model presented here is generic and captures the main characteristics of pitch angle controls of existing wind generation

    technologies. Controller and servomechanism are depicted in Figure 5. The controller has a feedback of the generator speed.

    Its speed-reference is set to the maximum speed (usually above 20% nominal). The blade angle is at the minimum limit of the

    controller for all operating conditions below rated rotor speed. This minimum limit corresponds to the optimum blade angle1.

    The servomechanism model accounts for the associated time constant, rate-of-change limits and blade angle limitations.

     1  Blade-Angle optimization can be realized using a variable minimum blade angle limit 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    10/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   9

    Figure 6: Input/Output Definition of Blade Angle Controller

    Table 4: Input Definition of Blade Angle Controller

    Input Description Unit

    speed Speed Input (from Generator) p.u.

    Table 5: Output Definition of Blade Angle Controller

    Output Description Unit

    beta Blade Angle (Pitch-Angle) deg

    Table 6: Parameter Definition of Blade Angle Controller

    Parameter Description Unit

    Ka Blade Angle Controller Gain deg/p.u.

    Ta Blade Angle Controller Time Constant s

    Tr Lead Time Constant s

    T Servo Time Constant s

    rate_op Opening Rate of Change Limit deg/s

    rate_cl Closing Rate of Change Limit deg/s

    beta_max Max. Blade Angle deg

    beta_min Min. Blade Angle deg

    ref_speed Speed Reference p.u.

    Blade Angle Controllerspeed beta

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    11/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 0

    3.2.3 Shaft

    Figure 7: Spring-Mass Model of Second Order 

    pt

    Pwind

    speed_gen omega_gen

    TmecTwind

    tdif omega_tur -

    Gear BoxRPMnom

    RatePtPbase

    0

    1

    SpringK,D_shaft

    0

    1

    Mass_1TorqueD_turb,J

    Torque

    0

    1

    Shaft Model:

    0

    1

    0

    1

          D      I     g      S      I      L      E      N      T

    Figure 8: Block Diagram of Shaft

    DgDt

    ωgJg

    Jtωt

    K tg

    Dtg

    ω’ g

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    12/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 1

    Under normal operating conditions, variable speed generators are “decoupled” from the grid; that is, with appropriate controls,

    torsional shaft oscillations are filtered by the converters and almost not noticeable as harmonics of the generated power.

    However, during heavy faults, e.g. short circuits in the network, generator and turbine acceleration can only be simulated with

    sufficient accuracy if shaft oscillations are included in the model.

    Shaft characteristics of wind generators are quite different from other types of generation due to the relatively low st iffness of 

    the turbine shaft. This results in torsional resonance frequencies in a range of about 0.5 to 2 Hz.

    The proposed model approximates the shaft by a two-mass model, represented by turbine- and generator inertia (see Figure

    7). The model according to Figure 7 and Figure 8 represents the turbine inertia and the coupling between turbine- and

    generator. The generator inertia however, is modelled inside the built-in induction machine model. The generator inertia is

    specified in the form of an acceleration time constant in the induction generator type. The inertia of the gear-box is not

    modelled separately but shall be included in the generator inertia.

    The spring-constant K and the corresponding damping coefficient D are related to the turbine-side.

    Shaft-models of higher order can easily be implemented by expanding the second order model. For stability analysis however, a

    second order model provides sufficient accuracy.

    Figure 9: Input/Output Definition of Shaft

    Table 7: Input Definition of Shaft

    Input Description Unit

    Pwind Turbine Power MW

    speed_gen Generator Speed p.u.

    Table 8: Output Definition of Shaft

    Output Description Unit

    omega_tur Turbine Speed (Angular Velocity) rad/s

    pt Mechanical Power at Generator Inertia p.u.

    Shaft

    Pwind

    speed_gen

    omega_tur

    pt

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    13/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 2

    Table 9: Parameter Definition of Shaft

    Parameter Description Unit

    Pbase Rated Power of Generator MW.

    D_turb Turbine Damping Nms/rad

    J_shaft Turbine Inertia kgm2

    K_shaft Shaft-Stiffness Nm/rad

    D_shaft Torsional Damping Nms/rad

    RPMnom Nominal Rotor Speed rpm

    3.3

     Generator Rotor-Side Converter and Controls

    The electrical characteristics and hence the modelling requirements vary considerably with the different types of generators. In

    this section the available models for doubly-fed induction machines are presented.

    Obviously, the equipment characteristics depend on the manufacturer. The models presented here reflect typical equipment and

    control structures.

    This section starts with a description of the DFIG including the rotor-side converter. The grid-side converter with controls is

    described in section 0, followed by a presentation of DFIG protections.

    3.3.1

     Asynchronous machine and Rotor Side Converter

    The doubly-fed induction machine model extends the usual induction machine by a PWM converter in series to the rotor

    impedance as shown in Figure 10. In this figure, Rs and Xs are the resistance and leakage reactance of the stator winding; Xm

    is the magnetizing reactance and Zrot is the rotor impedance.

    Rs Xs

    Xm

    Zrot

    U Ur   t  j r e

      ω −Ur Ur'= UDCUAC

    Figure 10: Equivalent Circuit of the Doubly-Fed Induction Machine with Rotor-Side Converter 

    The PWM converter inserted in the rotor circuit allows for a flexible and fast control of the machine by modifying magnitude and

    phase angle of the rotor voltage.

    It is assumed that a standard bridge consisting of six transistors builds the converter and that sinusoidal pulse width modulation

    is applied.

    In contrast to the normal induction machine model, in which the rotor is short-circuited, the winding ratio between rotor and

    stator is important for calculating actual DC voltages. The nominal rotor voltage that can be measured at the slip rings under

    open rotor conditions defines this winding ratio.

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    14/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 3

    For load flow calculations and transients initialization, only active power (AC-side), reactive power and the slip have to be

    specified. Internally, the corresponding modulation factors of the converter (Pmd, Pmq) are calculated and together with the

    power balance between the AC and DC side of the converter, DC voltage and DC current are obtained.

    During time domain simulations the converter is controlled through the pulse width modulation indices Pmd and Pmq which

    define the ratio between DC voltage and the AC-voltage at the slip rings. The modulation indices Pmd and Pmq are defined in a

    rotor-oriented reference frame.

    For more details about the built-in DFIG model, please refer to the corresponding Model Description  of the Technical Reference 

    Manual .

    3.3.2 Rotor-Side Converter Controller

    (To Protection System)

    (From Protection System)

    Irot

    bypass

    P;Q

    phim

    Ifq_ref;Ifd_ref 

    Pref 

    Ifq;Ifd

    Pfq;Pfd

    psis_r;psis_i

    iq;id

    Pmq ; Pmd

    Transformatio..*

    Current Measurement*

    PQ ControlElmGen*

    Qref 

    Current Control*

    Figure 11: Main Components of the Rotor-Side Converter Controller (Composite Model Frame) 

    The basic diagram (Frame) of the rotor-side converter controllers is shown in Figure 11.

    The rotor-side converter is controlled by a two stage controller. The first stage consists of very fast current controllers

    regulating the machine’s rotor currents to reference values that are specified by a slower power-controller (second stage).

    The rotor-side current-controller operates in a stator-flux oriented reference frame. Hence, rotor currents must first be

    transformed into a stator-flux oriented reference frame (psis_r, psis_i, see Figure 11).

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    15/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 4

    3.3.2.1

     Rotor-Current Controller

    The block Current Measurement  transforms rotor currents from the original, rotor-oriented reference frame to stator-flux

    orientation. Additionally, the magnitude (in kA) of the rotor-current phasor is calculated and sent to the rotor current protectionmodel. For considering flux-measurement delays (or flux-observer delays), a delay time constant can be entered.

    This transformation decomposes the rotor currents into a component that is in-phase with stator flux (d-component) and a

    component that is orthogonal to stator flux (q-component). The q-component of the rotor current directly influences the torque,

    why the q-axis can be used for torque- or active power control. The d-axis component is a reactive current component and can

    be used for reactive power- or voltage control.

    x3

    Rotor-Side Converter 

    Current Control

    x4

    Pmd

    Pmq

        u     d

        u    q

    yi1

    yi

    bypass

        o     1     6

    Ird

    Ird_ref 

    Irq_ref 

    Irqmodule limiter 

    Max

    0

    1

    0

    1

    non-windup PIKq,Tq

    MinPmq

    MaxPmq

    0

    1

    (1/(1+sT))Tr 

    (1/(1+sT))Tr 

    -

    -

    non-windup PIKd,Td

    MinPmd

    MaxPmd

    0

    1

    Current Control:

    2

    1

    3

    4

    0

    0

    1

          D      I     g      S      I      L      E      N      T

    Figure 12: Block Diagram of Rotor-Current Controller

    The block-diagram depicted in Figure 12 is the implementation of the rotor-current controller. There are two independent

    proportional-integral-(P-I-) controllers, one for the d-axis component, one for the q-axis component. The output of the current

    controller defines the pulse-width modulation indices in stator-flux orientation.

    For limiting harmonics, the magnitude of the pulse-width modulation index is limited to the parameter Max. Both P-I-controllers

    are equipped with non-windup limiters.

    By activating the additional input signal bypass, the pulse-width modulation indices are immediately set equal to zero, which is

    equivalent to blocking and bypassing the rotor-side converter (“Crow-Bar protection”, see section 3.5).

    Because the modulation index of the doubly-fed induction machine must be defined in a rotor-oriented reference frame, the

    outputs of the rotor-current controller have to be transformed back from stator-flux-orientation to rotor-orientation. This

    transformation is realized by the block Transformation .

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    16/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 5

    Figure 13: Input/Output Definition of Rotor-Current Measurement

    Table 10: Input Definition of Rotor-Current Measurement

    Input Description Unit

    cosphim Cosine of rotor angle

    sinphim Sine of rotor angle

    id Rotor-Current (d-axis, in rotor-oriented reference frame) p.u.

    iq Rotor-Current (q-axis, in rotor-oriented reference frame) p.u.

    psis_r Stator Flux, real part p.u.

    psis_i Stator Flux, imaginary part p.u.

    Table 11: Output Definition of Rotor-Current Measurement

    Output Description Unit

    ifd Rotor-Current (d-axis, Stator-Flux Orientation) p.u.

    ifq Rotor-Current (q-axis, Stator-Flux Orientation)

    Irot Rotor-Current (Magnitude of current-phasor) kA  

    Table 12: Parameters of Rotor-Current Measurement

    Parameter Description Unit

    Tm Measurement Delay Time s

    Urrated Rated Rotor Voltage kV

    Srated Rated Power of DFIG MVA  

    Rotor-CurrentMeasurement

    cosphim

    sinphim

    id

    iq

    psis_r

    psis_i

    ifd

    ifq

    Irot

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    17/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 6

    Figure 14: Input/Output Definition of Rotor- Current Controller

    Table 13: Input-Definition of Rotor- Current Controller

    Input Description Unit

    bypass Bypass-Signal

    Iq_ref q-Axis Current Reference p.u.

    Ifq q-Axis Current p.u.

    Id_ref d-Axis Current Reference p.u.

    Id d-Axis Current p.u.

    Table 14: Output-Definition of Rotor-Current Controller 

    Output Description Unit

    Pmq q-Axis Pulse Width Modulation Index

    Pmd d-Axis Pulse Width Modulation Index

    Table 15: Parameter-Definition of Rotor- Current Controller

    Parameter Description Unit

    Tr Current Measurement Time Constant sec

    Kq q-Axis Gain p.u

    Tq q-Axis Time Constant sec

    Kd d-Axis Gain p.u

    Td d-Axis Time Constant sec

    MinPmq Min. q-Axis Pulse-Width Modulation Index p.u

    MinPmd Min. d-Axis Pulse-Width Modulation Index p.u

    MaxPmq Max. q-Axis Pulse-Width Modulation Index p.u

    MaxPmd Max. d-Axis Pulse-Width Modulation Index t p.u

    Max Max. Magnitude of Pulse-Width Modulation Index p.u

    Rotor-CurrentController

    bypass

    Ifq_ref 

    Ifq

    Ifd_ref 

    Ifd

    Pmq

    Pmd

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    18/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 7 

    Figure 15: Input/Output Definition of Rotor-dq-Transformation

    Table 16: Input Definition of Rotor-dq-Transformation

    Input Description Unit

    cosphim Cosine of Rotor-Angle

    sinphim Sine of Rotor-Angle

    Pfd d-Axis Modulation Index (Stator-Flux Orienation)

    Pfq q-Axis Modulation Index (Stator-Flux Orientatin)

    psis_r Stator-Flux, Real Part p.u.

    psis_i Stator-Flux, Imaginary Part p.u.

    Table 17: Output Definition of Rotor-dq-Transformation

    Output Description Unit

    Pmd d-Axis Modulation Index (Rotor-Orientation)

    Pmq q-Axis Modulation Index (Rotor-Orientation)

    Rotor-dq-Transformation

    cosphim

    sinphim

    Pfd

    Pfq

    psis_r

    psis_i

    Pmdd

    Pmq

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    19/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 8

    3.3.2.2

     Power-Controller

    xQ

    x2

    xP

    Reactive Power Control

    Active Power Control

    Active and Reactive Power Control

    Rotor Side Converter 

    x1

    Ifd_ref 

    Ifq_ref 

    bypas..

    Q

    Qref 

    P

    Pref 

    module limiter 

    Max

    0

    1

    0

    1

    non-windup PIKp,Tp

    MinIfq

    MaxIfq

    0

    1

    (1/(1+sT)Ttr 

    -

    -

    non-windup PIKq,Tq

    MinIfd

    MaxIfd

    0

    1

    (1/(1+sT)Ttr 

    PQ Control:

    1

    2

    3

    4

    0

    1

    0

          D      I     g      S      I      L      E      N      T

    Figure 16: Block-Diagram of PQ-Controller 

    D-axis and q-axis component of the rotor current are controlled to reference values specified by active- and reactive power

    controllers according to Figure 16. Similar to the rotor-current controller, the power controller regulates active- and reactive

    power by independent P-I-controllers. The P-I-controllers are equipped with non-windup limiters. The output limits the

    magnitude of the rotor-current reference. In contrast to the output-limiter in Figure 12, the q-axis-component (active current

    component) is prioritized.

     Voltage control can either be realized by connecting a voltage controller behind the reactive power reference or by replacing the

    reactive power controller by a voltage controller defining the d-axis current reference.

    Figure 17: Input/Output Definition of PQ-Controller

    PQ-Controller

    bypass

    Pref 

    P

    Qref 

    Q

    Ifd_ref 

    Ifq_ref 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    20/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   1 9

    Table 18: Input Definition of PQ-Controller

    Input Description Unitbypass Bypass-Signal

    Pref Active Power Reference p.u.

    P q-Axis Current p.u.

    Qref d-Axis Current Reference p.u.

    Q d-Axis Current p.u.

    Table 19: Output-Definition of PQ-Controller

    Output Description Unit

    Ifq_ref q-Axis Current Reference p.u.

    Ifd_ref d-Axis Current Reference p.u.

    Table 20: Parameter Definition of PQ-Controller

    Parameter Description Units

    Ttr Measuring time constant sec

    Kp Active Power Control Gain p.u

    Tp Active Power Control Time Constant sec

    Kq Reactive Power Control Gain p.u

    Tq Reactive Power Control Time Constant sec

    MinIfq Min. q-axis current reference p.u

    MinIfd Min. d-axis current reference p.u

    MaxIfq Max. q-axis current reference p.u

    MaxIfd Max. d-axis current reference p.u

    Max Max. current magnitude reference p.u

    3.3.3 Maximum Power Tracking

     According to the classical control strategy the active power dispatch of wind-turbines is permanently optimized. Hence, the wind

    turbine operates with maximum possible active power output, depending on actual wind speed.

     As shown in Figure 3 there is, for every wind speed, an optimum mechanical speed (optimum λ). Assuming that the wind

    turbine always operates at this optimum point, the actual wind speed and hence the maximum possible active power can be

    calculated from the mechanical speed, without the necessity of wind-speed measurements.

    Calculating the table of max. power versus mechanical speed  and applying the maximum power as active power reference to

    the PQ-controller drives the wind turbine into the optimum point. In the PowerFactory  model, the power vs. speed characteristic

    (or MPT-characteristic) is defined using a linearly interpolated table.

     Alternatively, many doubly-fed induction machines are operated using a slightly different control-scheme, in which active power

    is measured and mechanical speed is calculated by the inverse MPT-characteristic. In this case, the calculated speed is sent as

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    21/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 0

    speed-reference to a speed-controller. Replacing the active power controller according to Figure 16 by a speed-controller and

    connecting an inverse MPT table to the speed-reference point realizes this alternative control scheme.

    Figure 18; Input/Output Definition of MPT-Characteristic

    Table 21: Input Definition of MPT-Characteristic

    Input Description Unit

    speed Mechanical Speed p.u.

    Table 22: Output Definition of MPT-Characteristic

    Output Description Unit

    Pref Active Power Reference p.u.

    Table 23: Parameter Definition of MPT-Characteristic

    Parameter Description Unit

    array_MPT Array of Power Reference Points p.u.

    speed MPT-Characteristic Pref 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    22/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 1

    3.4 Grid-Side-Converter with Controls

         L     1

         C     1

    PWM U1

    Figure 19: Grid-Side Converter 

    The grid-side converter consists of a 6-pulse bridge (PWM U1 in Figure 19), the AC-inductance (L1) and the DC-capacitance

    (C1).

    Like the rotor-side converter, the grid-side PWM converter is modelled using a fundamental frequency approach. The input

    variables Pmr and Pmi, together with the DC-voltage, define magnitude and phase angle of the AC-voltage at the PWM-

    converter’s AC-terminal. The pulse-width modulation indices Pmr and Pmi are referred to the so-called global reference frame ,

    which is in EMT-simulations a steady state reference frame and which rotates with reference frequency (mechanical speed of 

    the reference machine) in case of an RMS simulation. However, the reference frame has no influence to the system’s

    performance, as long as all quantities are given in the correct reference frames.

    More information about the PWM-controller, the AC-inductance and the DC-capacitance can be found in the corresponding

    Model Descriptions .

    The basic diagram of the grid-side controller is shown in Figure 20.

    The modulation indices of the Converter  are imposed from a Current Control  through a reference frame transformation ( ph- 

    transf ). The Current Control  operates in an AC-voltage oriented reference frame. It contains two current control loops: direct

    (active-) and quadrature (reactive-) axis current components (id  and iq ). The reference of the direct axis current component

    (id_ref ) is set by DC voltage control . The reference of the quadrature axis current component (id_ref  ) is, kept constant (const.

    reactive power) in this case.

    For defining the AC-voltage oriented reference frame, a PLL (phase-locked-loop) is required measuring the voltage angle. The

    PLL-output is used for transforming the current measurement into the voltage-oriented reference frame (dq- transf) and for

    transforming the controller outputs (pulse-width modulation indices) back to the global reference frame ( ph-transf ).

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    23/39

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    24/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 3

    The grid-side controller (Figure 21) is very similar to the rotor-side current controller (Figure 12). However, since it operates in

    a voltage-oriented reference frame and not in a flux-oriented reference frame the role of d- and q-axis is inverted: the d-axis

    component defines active-current and the q-axis component defines reactive current.

    Figure 22: Input/Output Definition of Grid-Side Current Controller

    Table 24: Input Definition of Grid-Side Current Controller

    Input Description Unit

    Id_ref d-Axis Current Reference p.u.

    Id d-Axis Current p.u.

    Iq_ref q-Axis Current Reference p.u.

    Iq q-Axis Current p.u.

    Table 25: Output Definition of Grid-Side Current Controller

    Output Description Unit

    Pmd d-Axis Pulse Width Modulation Index

    Pmq q-Axis Pulse Width Modulation Index

    Table 26: Parameter Definition of Grid-Side Current Controller

    Parameter Description Units

    Kd d-axis proportional gain p.u.

    Td d-axis integral time constant Sec

    Kq q-axis proportional gain p.u

    Tq q-axis integral time constant Sec

    Tr Current measurement time constant Sec

    Min_Pmd Min. d-axis modulation factor p.u.

    Min_Pmq Min. q-axis modulation factor p.u.

    Max_Pmd Max. d-axis modulation factor p.u.

    Max_Pmq Max. q-axis modulation factor p.u.

    Grid-Side CurrentController

    Id_ref 

    Id

    Iq_ref 

    Iq

    Pmd

    Pmq

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    25/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 4

    Fmeas

    cosphi

    sinphi

        y     i

    om

        o    m_

        n    o    m

    dom

         K    p    p     h     i

         K     i    p     h     i

    dphi

    ii

    rr 

    vi

    vr 

    1/(2pi)

    cos(x)

    sin(x)

    1/s

    K/s_limK

    dommin

    dommax

    KKp

    PLL:

    0

    1

    0

    1

    2

          D      I     g      S      I      L      E      N      T

    Figure 23: Block-Diagram of PLL

    Figure 24: Basic-Data-Page of PLL Showing Node-Reference 

    The reference angle of the current controller is provided by a PLL (phase locked loop). The PLL is a PowerFactory  built-in model

    that refers directly to a bus-bar or terminal. The block-diagram is shown in Figure 23, however, the input voltage is not defined

    by a composite model but directly by a node-reference in the input-dialogue box of the PLL, as shown in Figure 24.

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    26/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 5

    Figure 25: Input/Output Definition of PLL (Built-In Model) 

    Table 27: Output Definition of PLL

    Output Description Unit

    Fmeas Measured Frequency Hz

    sinphi Sine of Voltage Angle

    cosphi Cosine of Voltage Angle

    Table 28: Parameter Definition of PLL

    Parameter Description Unit

    Kp Controller Gain

    Ki Integration Gain 1/a

    ommax Upper Frequency Limit p.u.

    ommin Lower Frequency Limit p.u.

    The input/output definition of the transformation blocks carrying out the transformation from the global reference system to the

     AC-voltage oriented reference system and back are shown in Figure 26.

    Figure 26: Input/Output Definition of Grid-dq-Transformation

    Grid-dq-Transformation

    iq

    idir

    ii

    sinphi

    cosphi

    PLL

    cosphi

    sinphi

    Fmeas

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    27/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 6

    Table 29: Input Definition of Grid-dq-Transformation

    Input Description Unitir Real Part of Input Signal in Global Reference System p.u.

    ii Im. Part of Input Signal in Global Reference System p.u.

    sinphi Cosine of Reference Angle

    cosphi Cosine of Reference Angle

    Table 30: Output Definition of Grid-dq-Transformation

    Output Description Unit

    id d-Axis Current p.u.

    iq q-Axis Current p.u.

    Figure 27: Input/Output Definition of Phase-Transformation

    Table 31: Input Definition of Phase-Transformation

    Input Description Unit

    id d-Axis Component of Input Signal p.u.

    iq q-Axis Component of Input Signal p.u.

    sinphi Cosine of Reference Angle

    cosphi Cosine of Reference Angle

    Table 32: Output Definition of Phase-Transformation

    Output Description Unit

    ir Real Part of Output Signal p.u.

    ii Im. Part of Output Signal p.u.

    Phase-Transformation

    ii

    irid

    iq

    sinphi

    cosphi

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    28/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 7 

    3.4.1.2

     DC-Voltage Controller

    xidref 

    id_ref udc

    udc_ref 

    dudc{K (1+1/sT)}Kudc,Tudc

    Min_idref 

    Max_idref 

    -

    DC Voltage Control:

    0

    1

          D      I     g      S      I      L      E      N      T

    Figure 28: DC-Voltage Controller 

    The P-I-controller shown in Figure 28 controls the DC-voltage and sets the d-axis current reference. Time constant and gain of the controller must be set in accordance with the DC-capacitance (see Figure 19).

    Figure 29: Input/Output Definition of DC-Voltage Controller

    Table 33: Input Definition of DC-Voltage Controller

    Input Description Units

    udc_ref DC-Voltage, Reference Value p.u.

    udc DC-Voltage sec

    DC-VoltageController

    id_ref 

    udc_ref 

    udc

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    29/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 8

    Table 34: Output Definition of DC-Voltage Controller

    Ouput Description Units

    id_ref d-Axis Current Reference p.u.

    Table 35: Parameter Definition of DC-Voltage Controller

    Parameter Description Units

    Kudc Proportional Gain p.u.

    Tudc Integral Time Constant sec

    Min_idref Min. d-axis current reference p.u.

    Max_idref Max. d-axis current reference p.u

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    30/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   2 9

    3.5 Protection

    CrowBar 

    u

    speed

    Irot

    bypass

    TripVoltage

    TripSpeed

    Rotor BypassMaxIrotor, tbypass

    Max

    0

    1

    2

    VoltageProtMaxVoltage1,ttripMaxV1, ..

    SpeedProtMaxSpeed1,ttripMaxS1, Ma..

    Protection:

    0

    1

    2

          D      I     g      S      I      L      E      N      T

    Figure 30: Block Diagram of DFIG-Protection

    The following protective functions are implemented in the block diagram according to Figure 30:

    1.  Under-/Over-Voltage

    2.  Under-/Over-Speed

    3.  Rotor-Over-Current (“Crow-Bar Protection”)

    The Under/Over-Voltage unit supervises the voltage at the HV side of the transformer and has four voltage levels, two for

    under-voltage and two for over-voltage. If this protective unit triggers the machine breaker is opened.

    The Under/Over-speed protection unit supervises the generator speed and consists of four levels, two for under-speed and twofor over-speed. If this protective unit triggers the machine breaker is opened.

    Rs Xs

    Xm

    Zrot

    U Ur   t  j r e

      ω −Ur Ur'=

     AdditionalImpedance

    Figure 31: Equivalent Circuit Diagram of DFIG During Crow-Bar Protection 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    31/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3 0

    The Crow-Bar protection is specific to doubly-fed induction generators and protects the rotor-side converter against over-

    currents. When the rotor current exceeds a threshold value, the converter is blocked and bypassed through an additional

    impedance (see Figure 31). This additional impedance reduces the amount of reactive power absorbed by the machine and

    improves the torque characteristic during voltage sags. While the Crow-Bar is inserted, the integral actions of the rotor-side

    controllers are set to zero (see Figure 12 and Figure 16) for minimizing discontinuities in the rotor current when the Crow-Bar is

    removed. Those discontinuities would eventually lead to subsequent operations of the Crow-Bar protection. When the Crow-Bar

    is released, the rotor side converter is unblocked. For simulating cases, in which doubly-fed induction generators remain in the

    system during faults, as recommended by the latest E.ON. guidelines, the operation of the Crow-Bar protection does not open

    the machine breaker. For simulating synchronous operation of Crow-Bar protection and machine breaker, the model can easily

    be modified.

    Figure 32: Input/Output Definition of DFIG-Protection

    Table 36: Input Definition of DFIG-Protection

    Input Description Units

    Irot Rotor Current Magnitude kA  

    speed Generator Speed sec

    u Bus-Bar Voltage p.u

    Table 37: Output Definition of DFIG-Protection

    Output Description Units

    bypass Bypass-Signal (for Crow-Bar Insertion)

    DFIG-Protectionbypass

    Irot

    speed

    u

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    32/39

    3   T h e D F I G W i n d - G e n e r a t o r M o d e l

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3 1

    Table 38: Parameter Definition of DFIG-Protection

    Parameter Description Units

    MaxIrotor Rotor Current for Crow Bar Insertion kA  

    tbypass Crow Bar Insertion Time sec

    MaxSpeed1 Overspeed Setting step 1 p.u

    ttripMaxS1 Overspeed Time Setting step 1 sec

    MaxSpeed2 Overspeed Setting step 2 p.u

    ttripMaxS2 Overspeed Time Setting step 2 sec

    MinSpeed1 Underspeed Setting step 1 p.u

    ttripMinS1 Underspeed Time Setting step 1 sec

    MinSpeed2 Underspeed Setting step 2 p.u

    ttripMinS2 Underspeed Time Setting step 2 sec

    MaxVoltage1 Overvoltage Setting step 1 p.u

    ttripMaxV1 Overvoltage Time Setting step 1 sec

    MaxVoltage2 Overvoltage Setting step 2 p.u

    ttripMaxV2 Overvoltage Time Setting step 2 sec

    MinVoltage1 Undervoltage Setting step 1 p.u

    ttripMinV1 Undervoltage Time Setting step 1 sec

    MinVoltage2 Undervoltage Setting step 2 p.u

    ttripMinV2 Undervoltage Time Setting step 2 sec

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    33/39

    4   S i m u l a t i o n E x a m p l e s

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3 2

    4 Simulation Examples

    In this section the behaviour of the proposed DFIG model under different types of system faults is presented.

    4.1 Three-Phase Fault Far from Wind Generation

    In this case, a three phase fault cleared after 200 ms causing a voltage depression of about 25% is simulated. The results are

    presented in Figure 33 to Figure 35.

    4.0003.0002.0001.0000.00 ..

    1.200

     0.80

     0.40

     0.00

    -0.400

    -0.800

    PQ Control: Total Active Power (P)

    4.0003.0002.0001.0000.00 ..

    1.000

     0.00

    -1.000

    -2.000

    -3.000

    PQ Control: Total Reactive Power (Q)

    4.0003.0002.0001.0000.00 ..

    1.200

     1.00

     0.80

     0.60

     0.40

     0.20

     0.00

    T3WT1: AC Voltage at HV side (u)

    DIgSILENTDoubly-fed Induction Generator - Example Plot-1

     

    Date: 5/26/2003

     Annex: /1

          D      I     g      S      I      L      E      N      T

    Figure 33: Three-Phase Fault Far from Wind Generation, Connection Point 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    34/39

    4   S i m u l a t i o n E x a m p l e s

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3 3

    4.0003.0002.0001.0000.00 ..

    7.500

    5.000

    2.500

     0.00

    -2.500

    -5.000

    -7.500

    G1d: Stator Reactive Power 

    4.0003.0002.0001.0000.00 ..

    5.500

    5.000

    4.500

    4.000

    3.500

    3.000

    G1d: Stator Active Power 

    4.0003.0002.0001.0000.00 ..

     0.50

     0.25

     0.00

    -0.250

    -0.500

    -0.750

    PWM U1: Grid Side Converter Active Power 

    4.0003.0002.0001.0000.00 ..

     0.00

    -0.100

    -0.200

    -0.300

    -0.400

    PWM U1: Grid Side Converter Reactive Power 

    DIgSILENTDoubly-fed Induction Generator - Example Plot-2

     

    Date: 5/26/2003

     Annex: /2

          D      I     g      S      I      L      E      N      T

    Figure 34: Three-Phase Fault Far from Wind Generation, Stator- and Grid-Side Results 

    4.0003.0002.0001.0000.00 ..

    4.500

    4.400

    4.300

    4.200

    4.100

    4.000

    Prime Mover: Wind Power 

    4.0003.0002.0001.0000.00 ..

    3.000

    2.000

    1.000

     0.00

    -1.000

    Prime Mover: Blade pitch Angle

    4.0003.0002.0001.0000.00 ..

    1.000

     0.99

     0.98

     0.97

     0.96

     0.95

     0.94

    G1d: Generator Speed

    DIgSILENTDoubly-fed Induction Generator - Example Plot-3

     

    Date: 5/26/2003

     Annex: /3

          D      I     g      S      I      L      E      N      T

    Figure 35: Three-Phase Fault Far from Wind Generation, Mechanical Variables 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    35/39

    4   S i m u l a t i o n E x a m p l e s

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3 4

    Figure 33 shows that the total active and reactive power at the connection point is quickly restored. The active power of the

    stator has an oscillatory component due to torsional oscillations that is almost perfectly damped by the active power controller

    of the grid-side converter (Figure 34). The speed deviations are not large enough to cause a variation of the blade angles the

    pitch control.

    4.2 Three Phase Fault Close to Wind Generation

    In this case, a three phase fault cleared after 400 ms causing a voltage depression of about 85% is simulated assuming that the

    under-voltage protection is set to avoid the disconnection from the grid under these circumstances. The results are presented

    in Figure 36 to Figure 38.

    In this case, it takes longer to restore total active and reactive power than in the previous case, due to the operation of the

    crow bar (Figure 36). The total reactive power is almost zero during the fault and is negative during the time between clearing

    the fault and removing the crow bar protection at t=0.5s. In this case, the speed deviation is larger than in the previous case

    and the blade angle is increased to reduce the power extracted from the wind.

    The reactive power absorbed by the generator during the time that the crow bar is inserted may have a negative impact on the

    voltage stability of the system when a significant number of units are connected. The modelling of the operation of this

    protective function should be particularly considered in the design of transmission systems connecting large wind farms to utility

    grids.

    4.0003.0002.0001.0000.00 ..

    1.200

     0.80

     0.40

     0.00

    -0.400

    -0.800

    PQ Control: Total Active Power (P)

    4.0003.0002.0001.0000.00 ..

    1.000

     0.00

    -1.000

    -2.000

    -3.000

    PQ Control: Total Reactive Power (Q)

    4.0003.0002.0001.0000.00 ..

    1.200

     1.00

     0.80

     0.60

     0.40

     0.20

     0.00

    T3WT1: AC Voltage at HV side (u)

    DIgSILENTDoubly-fed Induction Generator - Example Plot-1

     

    Date: 5/26/2003

     Annex: /1

          D      I     g      S      I      L      E      N      T

    Figure 36: Three-Phase Fault Close to Wind Generation, Connection Point 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    36/39

    4   S i m u l a t i o n E x a m p l e s

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3 5

    4.0003.0002.0001.0000.00 ..

    8.000

    4.000

     0.00

    -4.000

    -8.000

    -12.00

    G1d: Stator Reactive Power 

    4.0003.0002.0001.0000.00 ..

    6.000

    4.000

    2.000

     0.00

    -2.000

    -4.000

    G1d: Stator Active Power 

    4.0003.0002.0001.0000.00 ..

    1.200

     0.80

     0.40

     0.00

    -0.400

    -0.800

    -1.200

    PWM U1: Grid Side Converter Active Power 

    4.0003.0002.0001.0000.00 ..

    4.000

    3.000

    2.000

    1.000

     0.00

    -1.000

    PWM U1: Grid Side Converter Reactive Power 

    DIgSILENTDoubly-fed Induction Generator - Example Plot-2

     

    Date: 5/26/2003

     Annex: /2

          D      I     g      S      I      L      E      N      T

    Figure 37: Three-Phase Fault Close to Wind Generation, Stator- and Grid-Side Results 

    4.0003.0002.0001.0000.00 ..

    4.400

    4.300

    4.200

    4.100

    4.000

    3.900

    Prime Mover: Wind Power 

    4.0003.0002.0001.0000.00 ..

     0.30

     0.20

     0.10

     0.00

    -0.100

    Prime Mover: Blade pitch Angle

    4.0003.0002.0001.0000.00 ..

    1.140

    1.100

    1.060

    1.020

     0.98

     0.94

    G1d: Generator Speed

    DIgSILENTDoubly-fed Induction Generator - Example Plot-3

     

    Date: 5/26/2003

     Annex: /3

          D

          I     g      S      I      L      E      N      T

    Figure 38: Three-Phase Fault Close to Wind Generation, Mechanical Variables 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    37/39

    4   S i m u l a t i o n E x a m p l e s

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3 6

    4.3 Single Phase Fault Close to Wind Generation

    In this case, a single phase fault cleared after 400 ms causing a total voltage depression in phase A at the HV side of the

    machine transformer is simulated assuming that the under-voltage protection is set to avoid the disconnection from the grid

    under this circumstances. The results are presented in Figure 39 to Figure 41.

    In this case, the total active power does not decrease during the fault as in the previous case due to the fault type. However,

    the increasing rotor current causes the Crow-Bar protection to trip. Consequently, the total reactive power absorption

    significantly increases until the crow bar protection is removed at t=0.5s. The speed deviation is less than in the previous case

    and the blade angle is kept constant.

    In contrast to the previous cases, this case was simulated using an instantaneous-value representation of the AC-system (EMT-

    simulation). This more accurate model uses fifth-order generator models, including stator transients and differential equations

    for all network components.

    1.000.750.500.25-0.00 [s]

    2.00

    1.00

    -0.00

    -1.00

    PQ Control: Total Active Power (P)

    1.000.750.500.25-0.00 [s]

    2.00

    1.00

    -0.00

    -1.00

    -2.00

    PQ Control: Total Reactive Power (Q)

    1.000.750.500.25-0.00 [s]

    2.00

    1.00

    -0.00

    -1.00

    -2.00

    T3WT1: Phasenspannung L1/OS-Seite in p.u.

    DIgSILENTDoubly-fed Induction Generator - Example Results at Connection Point

     

    Date: 8/11/2003

     Annex: 1 /1

          D      I     g      S      I      L      E      N      T

    Figure 39: Single-Phase Fault Close to Wind Generation, Connection Point 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    38/39

    4   S i m u l a t i o n E x a m p l e s

    D y n a m i c M o d e l l i n g o f D o u b l y - F e d I n d u c t i o n M a c h i n e W i n d - G e n e r a t o r s   3 7 

    1.000.750.500.25-0.00 [s]

    9.00

    6.00

    3.00

    0.00

    -3.00

    -6.00

    G1d: Stator Reactive Power 

    1.000.750.500.25-0.00 [s]

    7.50

    5.00

    2.50

    0.00

    -2.50

    -5.00

    G1d: Stator Active Power 

    1.000.750.500.25-0.00 [s]

    3.00

    2.00

    1.00

    0.00

    -1.00

    PWM U1: Grid Side Converter Active Power 

    1.000.750.500.25-0.00 [s]

    3.00

    2.00

    1.00

    0.00

    -1.00

    PWM U1: Grid Side Converter Reactive Power 

    DIgSILENTDoubly-fed Induction Generator - Example Active/Reactive Power 

     

    Date: 8/11/2003

     Annex: 1 /2

          D      I     g      S      I      L      E      N      T

    Figure 40: Single Phase Fault Close to Wind Generation, Stator- and Grid-Side Results 

    1.000.750.500.25-0.00 [s]

    4.40

    4.30

    4.20

    4.10

    4.00

    3.90

    Turbine: Wind Power 

    1.000.750.500.25-0.00 [s]

    0.15

    0.10

    0.05

    0.00

    -0.05

    -0.10

    -0.15

    Pitch Control: Blade pitch Angle

    1.000.750.500.25-0.00 [s]

    1.14

    1.10

    1.06

    1.02

    0.98

    0.94

    G1d: Generator Speed

    DIgSILENTDoubly-fed Induction Generator - Example Mechanical Results

     

    Date: 8/11/2003

     Annex: 1 /3

          D      I     g      S      I      L      E      N      T

    Figure 41: Single-Phase Fault Close to Wind Generation, Mechanical Variables 

  • 8/9/2019 Dynamic Modelling of Doubly-Fed Induction Machine Wind Generators

    39/39

    5   C o n c l u s i o n s

    5 Conclusions

    The PowerFactory  standard library of generic models for simulating DFIG-based wind power plants was described using a

    typical DFIG-example. The models include the conversion from wind- to mechanical energy, pitch control, maximum power

    tracking and controllers for the rotor-side- and grid-side converters.

    The described models can easily be extended for different reactive and active power control schemes.

     All block diagrams, equations and input/output definitions were presented in this document allowing to use the PowerFactory 

    standard library efficiently.

    Simulation examples showing the dynamic response of the described models illustrate the validity and accuracy of the

    presented approach