1
Does the damper protect an escape route or an area with sleeping risk? YES: select this fire damper model Does the proposed fire damper model have an ES classification with a test report/assessment for this method in the proposed supporting construction (EN1366-2/EN13501-3)? NO NO YES YES No: Select a different fire damper model and/or manufacturer Will the fans be turned off in the occurrence of a fire or smoke alarm? YES: select this fire damper model Does the proposed fire damper model have an E classification with a test report/assessment for this method in the proposed supporting construction (EN1366-2/EN13501-3)? Curtain fire dampers are not recommended for closure against continuing air flow NO YES DW/145 Method 1 DW/145 Method 2 DW/145 Method 3 DW/145 Method 7 Masonry Wall DW/145 Method 1 DW/145 Method 2 DW/145 Method 4 DW/145 Method 5 Dry Wall Select supporting construction DW/145 Method 6 Fire Curtain NO No: Select a different fire damper model and/or manufacturer YES: select this fire damper model Does the proposed fire damper model have an E classification with a test report/assessment for this method in the proposed supporting construction (EN1366-2/EN13501-3) or a test report/assessment to BS476-20/22? NO YES YES No: Select a different fire damper model and/or manufacturer DW/145 Fire Damper Selection

DW/145 Fire Damper Selection - ADCAS€¦ · DW/145 Method 5 Dry Wall Select supporting construction DW/145 Method 6 Fire Curtain NO No: Select a different fire damper model and/or

  • Upload
    others

  • View
    12

  • Download
    3

Embed Size (px)

Citation preview

Page 1: DW/145 Fire Damper Selection - ADCAS€¦ · DW/145 Method 5 Dry Wall Select supporting construction DW/145 Method 6 Fire Curtain NO No: Select a different fire damper model and/or

Does the damper protect an escape

route or an area with sleeping risk?

YES:select this

fire dampermodel

Does the proposed fire damper modelhave an ES classification with a test

report/assessment for this method in the proposed supporting construction

(EN1366-2/EN13501-3)?

NO

NO

YES YES

No: Select a different fire dampermodel and/or manufacturer

Will the fans be turnedoff in the occurrence

of a fire orsmoke alarm?

YES:select this

fire dampermodel

Does the proposed fire damper modelhave an E classification with a test

report/assessment for this method in the proposed supporting construction

(EN1366-2/EN13501-3)?Curtain fire dampers are not recommended

for closure against continuing air flow

NO YES

DW/145 Method 1DW/145 Method 2DW/145 Method 3DW/145 Method 7

MasonryWall

DW/145 Method 1DW/145 Method 2DW/145 Method 4DW/145 Method 5

DryWall

Selectsupporting

construction

DW/145 Method 6Fire

Curtain

NO

No: Select a different fire dampermodel and/or manufacturer

YES:select this

fire dampermodel

Does the proposed fire damper modelhave an E classification with a test

report/assessment for this method in the proposed supporting construction

(EN1366-2/EN13501-3) or a testreport/assessment to BS476-20/22?

NO

YES YES

No: Select a different fire dampermodel and/or manufacturer

DW/145 Fire Damper Selection