8
EN0B-0521GE51 R0113 AD20-P, AD34-P NON-SPRING RETURN DAMPER ACTUATOR 20/34 Nm (177/300 lb-in) FOR MODULATING CONTROL PRODUCT DATA GENERAL These direct-coupled damper actuators provide modulating control for: FEATURES ? air Dampers, ? VAV units, ? air handling units, ? ventilation flaps, ? louvers ? Self-centering shaft adapter ? Access cover to facilitate connectivity ? Declutch for manual adjustment ? Mechanical end limits ? Field-installable auxiliary switches ? Rotation direction selectable by switch ? Mountable in any orientation (no IP54 if upside down) ? CE certified SPECIFICATIONS Supply voltage 24 Vac/dc ±15%, 50/60 Hz; Control signal 0(2)...10 Vdc/ 0(4)...20 mA Selectable Input impedance >100 k? at 0(2)...10 V 500 ? at 0(4)...20 mA Power consumption AD20-P, AD34-P 6 VA / 3 W Ambient limits Ambient operating limits -20...+60 °C (-5...+140 °F) Ambient storage limits -40...+80 °C (-40...+175 °F) Relative humidity 5...95%, non-condensing Safety Protection standard IP54 as per EN60529 Protection class II as per EN 60730-1 Lifetime Full strokes 60000 Repositions 1.5 million Mounting Round damper shaft 10...27 mm (3/8...1-1/16") Square damper shaft 10...18 mm (3/8...11/16"); 45° steps Shaft length min. 22 mm (7/8") Feedback signal Limits ± 1 mA ...-0.5 m at 2...10 V Auxiliary switches Optional accessory ACCA-AD2034-SW2 Torque rating See table 1 page2 Runtime 95 sec (60 Hz) / 110 sec (50 Hz or dc supply) Rotation stroke 95° ±Dimensions see "Dimensions" on page 8 Weight 1.35 kg (3 lbs.) Noise rating 45 dB(A) max. at 1 m Software Class A as per EN 60730-1 AD20-P, AD34-P Data Sheet TA200864 1 Issue 2, 19/02/2013

ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

EN0B-0521GE51 R0113

AD20-P, AD34-P NON-SPRING RETURN DAMPER ACTUATOR

20/34 Nm (177/300 lb-in) FOR MODULATING CONTROL

PRODUCT DATA

GENERAL These direct-coupled damper actuators provide modulating control for:

FEATURES

?air Dampers,?VAV units,?air handling units,?ventilation flaps,?louvers

?Self-centering shaft adapter?Access cover to facilitate connectivity?Declutch for manual adjustment?Mechanical end limits?Field-installable auxiliary switches?Rotation direction selectable by switch?Mountable in any orientation (no IP54 if upside down)?CE certified

SPECIFICATIONS

Supply voltage 24 Vac/dc ±15%, 50/60 Hz;Control signal 0(2)...10 Vdc/ 0(4)...20 mA

SelectableInput impedance >100 k? at 0(2)...10 V

500 ? at 0(4)...20 mAPower consumptionAD20-P, AD34-P 6 VA / 3 WAmbient limitsAmbient operating limits -20...+60 °C (-5...+140 °F)Ambient storage limits -40...+80 °C (-40...+175 °F)Relative humidity 5...95%, non-condensingSafetyProtection standard IP54 as per EN60529Protection class II as per EN 60730-1LifetimeFull strokes 60000Repositions 1.5 millionMountingRound damper shaft 10...27 mm (3/8...1-1/16")Square damper shaft 10...18 mm (3/8...11/16");

45° stepsShaft length min. 22 mm (7/8")Feedback signalLimits ± 1 mA ...-0.5 m at 2...10 VAuxiliary switchesOptional accessory ACCA-AD2034-SW2Torque rating See table 1 page2Runtime 95 sec (60 Hz) / 110 sec (50 Hz

or dc supply)Rotation stroke 95° ±3°Dimensions see "Dimensions" on page 8Weight 1.35 kg (3 lbs.)Noise rating 45 dB(A) max. at 1 mSoftware Class A as per EN 60730-1

AD20-P, AD34-P Data Sheet TA200864 1 Issue 2, 19/02/2013

Page 2: ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

AD20-P, AD34-P Data Sheet

EN0B-0521GE51 R0113

MODELS

Product Identification System

20 = 20 Nm (177 lb-in)34 = 34 Nm (300 lb-in)

P = modulating24 = 24 V floating+ON/OFF230 = 230 V floating+ON/OFF

Fig. 1. Product Identification System

OPERATION / FUNCTIONS

Fig. 2. Setting units and control elements

2 AD20-P, AD34-P Data Sheet TA200864 Issue 2, 19/02/2013

2

3

5

6

7

8

4

Table 1. Models

order number torque max. damper

sizepower

consumptionnominal supply

voltage

AD20-PAD34-P

20 Nm

34 Nm24 Vac/dc 6 VA / 3 W

4.6 m2

7.8 m2

Run ModesThe function selection switch (see Fig. 3) is used to place the actuator into any one of five different modes:?2…10 V: modulating / floating / 2-position control; CW?0…10 V / Dir: modulating / floating / 2-position control; CW?Service/Off: actuator stops running?10…0 V / Rev: modulating / floating /2-position control; CCW ?10…2 V: modulating / floating / 2-position control; CCW

Fig. 3. Function selection switch

2.. 10V0.. 10V/ DirService/Off10.. 0V/ Dir10.. 2V

Service/OffIf the function selection switch is set to the "Service/Off" position, all rotary movement is cancelled, and all control signals are ignored, thus allowing the actuator to be safely manually operated.

Modulating Control ModeIf the actuator is wired for the modulating control mode(terminal 1 powered) the actuator will run according to the control signals applied.Alternatively, if the override is active (terminal 4 is powered), the actuator will ignore the Y-signal and move to a position of 0% of its max. stroke.

Power-Off BehaviorIf power is removed, the actuator retains its position.

Legend for Fig. 2:1 Self-centering shaft adapter2 Retainer clip3 Rotational angle scales (0...90° / 90...0°)4 Mechanical end limits 5 Declutch button6 Anti-rotation bracket7 Function selection switch8 Access cover

Page 3: ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

Data Sheet AD20-P, AD34-P

AD20-P, AD34-P Data Sheet TA200864 Issue 2, 19/02/2013 3

Fig. 5. Feedback signal in dependence upon current position of actuator (func. selection switch set to 0...10 V)

0

0

50

100

5 10

CU

RR

EN

T P

OS

ITIO

N O

F S

HA

FT

AD

AP

TE

R (

% O

F M

AX

. S

TR

OK

E)

FEEDBACK SIGNAL (V)

Feedback As long as terminal 1 is powered, the feedback signal will be generated according to the setting of the function selection switch.

Fig. 6. Adaption (func. selection switch set to 0...10 V)

The feedback can supply a 1 mA strong signal. If the sensing device is equipped with a "pull up" resistor, the feedback can control a max. return current of 0.5 mA at 2 V.

Sleep ModeWhen actuator reaches end stop or any obstacles blocking its running, it will fall into sleep mode automatically. Actuator will periodically start up and try to resume running, which will save energy significantly through whole service life.

OverridingIf a 24 V signal is applied to terminal 4 while terminal 1 is also powered, the actuator will ignore the control signal at terminal 3 and will instead move to a position of 0% of its max. stroke.

Dip SwitchesThe actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7).

Autoadapt will be carried out only if:-dip switch 2 ("autoadapt") is set to ON and

-the actuator is powered at terminal 1 and

-the control signal's value rises up into the upper dead band (i.e., to more than 9.76 V) or drops down into the lower dead band (i.e., to less than 0.24 [2.24] V), and if the shaft adapter can remain at the respective mechanical end limit for at least 3 seconds.

The actuator will then automatically recognize the new position and behave according to the solid "AFTER AUTOADAPT" line depicted in Fig 6.

Autoadapt OFFWhen dip switch 2 ("autoadapt") is set to OFF (default setting; available starting with Date Code 1308), the actuator will behave according to the dotted "BEFORE AUTOADAPT" line depicted in .

0 0. 2 4

0

50

100

5.0 0.0 19.76

UPPER DEAD BAND (9.76 to 10.0 V)

CONTROL SIGNAL (V)

FIN

AL

PO

SIT

ION

OF

SH

AF

T A

DA

PT

ER

(%

OF

MA

X. S

TR

OK

E)

RANGE OF PROP.ACT. MOVEMENT

(0.24 to 9.76 V)

LOWER DEAD BAND (0 to 0.24 V)

Fig. 4. Final actuator position in dependence upon

Modulating Control ModeIf the actuator is wired for the modulating control mode(terminal 1 powered) the actuator will run according to the control signals applied.Alternatively, if the override is active (terminal 4 is powered), the actuator will ignore the Y-signal and move to a position of 0% of its max. stroke.

AutoadaptAutoadapt ONIn autoadapt, the actuator re-maps its feedback and control signals in accordance with repositioned mechanical end limits (see Fig 6 ) and thus recognizes their new positions..

1: 1:

2: 2:

Y = 0[2] ... 10V Y = 0[2] ... 10V

AUTOADAPT OFF AUTOADAPT ON

2NO

1

HONEYWELL

2NO

1

0

NEW POSITION OF UPPER

MECHANICAL END LIMIT

OLD POSITION OF UPPER

MECHANICAL END LIMIT

NEW POSITION OF LOWER

MECHANICAL END LIMIT

OLD POSITION OF LOWER

MECHANICAL END LIMIT

AFTER AUTOADAPT

0(BEFORE)

100(BEFORE)

CU

RR

EN

T P

OS

ITIO

N O

FS

HA

FT

AD

AP

TE

R(%

OF

MA

X.

ST

RO

KE

)

CONTROL SIGNAL (V)

FIN

AL

PO

SIT

ION

OF

SH

AF

T A

DA

PT

ER

(%

OF

MA

X. S

TR

OK

E)

95

0

10.0

0(AFTER)

100(AFTER)

BEFORE AUTOADAPT

EN0B-0521GE51 R0113

Page 4: ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

AD20-P, AD34-P Data Sheet

4 AD20-P, AD34-P Data Sheet TA200864 Issue 2, 19/02/2013

Limitation of Rotation StrokeTwo mechanical end limits (adjustable in 5° increments) are provided to limit the angle of rotation as desired (see Fig. 9).

Fig. 9. Mechanical end limits

Manual AdjustmentThe gear train can be disengaged using the declutch button, permitting the actuator shaft to be manually rotated to any position. The feedback signal will then follow the new position.

The mechanical end limits must be securely fastened in place. It is important that they properly mesh with the rotational angle scales when the screws are tightened.

NOTE: Auxiliary Switches

End switch functionality is provided by optional accessory ACCA-AD2034-SW2.

ACCA-AD2034-SW2 provides auxiliary switches which are freely adjustable between 0 and 90 °

INSTALLATIONThese actuators are designed for single-point mounting.

Mounting InstructionsAll information and steps are included in the installation instructions supplied with the actuator.

Mounting PositionThe actuators can be mounted in any desired orientation (no IP54 if mounted upside down; see Fig. 10). Choose an orientation permitting easy access to the actuator's cables and controls.

Mounting Bracket and ScrewsIf the actuator is to be mounted directly on a damper shaft, use the mounting bracket and screws included in the delivery package.

Voltage/Current Control SignalIn its default shipping position, dip switch 1 is set to OFF (voltage control; Y = 0 [2] … 10 V). Setting dip switch 1 to ON results in current control (Y = 0 [4] … 20 mA). Dip switch 2 is RESERVED for future use.

Floating and 2-Position Control ModeIf the actuator is wired for the floating or 2-position control mode (terminal 1 not powered), the actuator will operate according the signal from its control inputs (terminal 3 and terminal 4).

Position IndicationThe edge (see arrow in Fig. 8) of the hub adapter indicates the rotation angle position with respect to the rotational angle scales (0...90° / 90...0°).

0

30

60

0

30

60

Fig. 8. Position indication

Fig. 10. Mounting for IP54

EN0B-0521GE51 R0113

Page 5: ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

Data Sheet AD20-P, AD34-P

Fig. 11. Access cover (AD20-P)

Self-Centering Shaft AdapterThe self-centering shaft adapter can be used for shafts having various diameters (10...27 mm [3/8...1-1/16"]) and shapes (square or round). In the case of short shafts, the shaft adapter may be reversed and mounted on the duct side.

Stroke Limitation with Mechanical End LimitsThe mechanical end limits enable the stroke to be limited from 0...90° in increments of 5°.

WiringConnecting to the Power SupplyIn order to comply with protection class II, the power source of 24 V actuators must be reliably separated from the network power supply circuits as per DIN VDE 0106, part 101.

Access CoverTo facilitate wiring the actuator to the controller, the access cover can be detached from the actuator.

IMPORTANTRemove power before detaching the access cover.Once the access cover has been removed, pleasetake care to avoid damaging any of the parts now accessible

Depending upon the model, the access cover may have one or two terminal blocks, including a layout with a description for each of the terminals.

AD20-P, AD34-P Data Sheet TA200864 Issue 2, 19/02/2013 5

EN0B-0521GE51 R0113

Page 6: ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

AD20-P, AD34-P Data Sheet

6 AD20-P, AD34-P Data Sheet TA200864 Issue 2, 19/02/2013

Wiring Diagrams AD20-P / AD34-P

A1: Wired for MODULATING A2: Wired for 2-POSITION CONTROL A3: Wired for FLOATING CONTROL

24 V~/+

Y 0[2] ... 10 V / 0[4] ... 20 mA

OVERRIDE OPTION

POS 0[2] ... 10 V

345 2 1 !

24 V~/+

34 2

CCW

!

CCW CW

34 2

24 V~/+ !

ACCA-AD2034-SW2

S1

S2

S3

S4

S5

S6

S1 S4S2 S5

S3 S6A C

B D45

090

900

A

B

C

D

AS1 AS2

EN0B-0521GE51 R0113

AUXILIARY SWITCHES

100/230 Vac5 A (resistive load)3 A (inductive load)

AUXILIARY SWITCHESAUXILIARY SWITCHES

Page 7: ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

Data Sheet AD20-P, AD34-P

S1S2

S3A

BS4S5

S6 C

D45

090

900

A

B

C

D

The auxiliary switches are field-installable parts providing two SPDT freely-adjustable switches.

OPTIONAL ACCESSORIESThe following optional accessories can be ordered separately.

Auxiliary Switch KitOrder no.: ACCA-AD2034-SW2

AD20-P, AD34-P Data Sheet TA200864 Issue 2, 19/02/2013 7 EN0B-0521GE51 R0113

Page 8: ds AD20-P AD34-P - Honeywell · 2020-03-13 · Dip Switches The actuator is equipped with two dip switches accessible after removing the access cover (see Fig. 7). Autoadapt will

AD20-P, AD34-P Data Sheet

8 AD20-P, AD34-P Data Sheet TA200864 Issue 2, 19/02/2013

DIMENSIONS

DISPOSAL

Please send any comments about this or any other Trend technical publication to [email protected]© 2012 Honeywell Technologies Sàrl, ECC Division. All rights reserved. Manufactured for and on behalf of the Environmental and Combustion Controls Division ofHoneywell Technologies Sàrl, Z.A. La Pièce, 16, 1180 Rolle, Switzerland by its Authorized Representative, Trend Control Systems Limited.Trend Control Systems Limited reserves the right to revise this publication from time to time and make changes to the content hereof without obligation to notify any person of such revisions or changes.

Trend Control Systems LimitedAlbery House, Springfield Road, Horsham, West Sussex, RH12 2PQ, UK. Tel:+44 (0)1403 211888 Fax:+44 (0)1403 241608 www.trendcontrols.com

Trend Control System USA6670 185th Avenue NE, Redmond, Washington 98052, USA. Tel:(425) 869-3900 Fax:(425) 869-8445 www.trend-americas.com

WEEE Directive: At the end of their useful life the packaging and product should be disposed of by a suitable recycling centre. Do not dispose of with normal household waste. Do not burn.

EN0B-0521GE51 R0113

ANTI-ROTATION BRACKET

103 mm

48 m

m

95°

223 m

m92 mm

1000 m

mmin. 60 mm

230 mm (+/- 0.5 mm)

22.6 mm

2 mm

132 ... 152 mm

0

SHAFTADAPTER

SHAFT ADAPTER(REAR)

20 mm

13 mm

7 mm