THERMAL BARRIER THERMAL BARRIER TITLE: DRAWN BY: SOPREMA TECHNICAL SUPPORT, GGALLOWAY NO.: DATE: REVISION: DATE: 10.17.2018 SCALE: NTS DRAWING NUMBER: US.RPVC.06.01 PVC MEMBRANE, INSULATED, PIPE PENETRATION USAGE OF THIS DETAIL IS GOVERNED BY THE TERMS OF SERVICE FOR SOPREMA DETAILS. PLEASE CONSULT THESE TERMS OF SERVICE PRIOR TO UTILIZING THIS DRAWING. US CORPORATE ADDRESS 310 QUADRAL DRIVE WADSWORTH, OHIO 44281 www.soprema.us Tel:330.334.0066 WI LLI AM GRANT GALLOWAY PROJECT: DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE CUSTOM LAYERING NOTES: 1. SOPREMA DETAIL DRAWINGS: REFER TO SOPREMA AND OTHER RELATED PUBLISHED DOCUMENTATION, PRODUCT DATA SHEETS (PDS) AND SAFETY DATA SHEETS (SDS) FOR ADDITIONAL INFORMATION. ALL DETAIL DRAWINGS AND RELATED INSTALLATION GUIDELINES ARE PROVIDED BY SOPREMA FOR THE SOLE PURPOSE OF ISSUING A SOPREMA WARRANTY. ACCORDINGLY, THE DETAIL DRAWINGS ARE NOT OFFERED, AND SHOULD NOT BE CONSIDERED, AS A SUBSTITUTE FOR PROFESSIONAL DESIGN SERVICES. 2. HOT WORK: THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING APPROPRIATE CONDITIONS TO UTILIZE HEAT-WELDING EQUIPMENT. REFER TO LOCAL CODES AND BUILDING OWNER'S REQUIREMENTS FOR HOT WORK OPERATIONS. 3. PRIMER: WHERE NOT SHOWN OR INDICATED ON DETAIL DRAWINGS, REFER TO MATERIAL PRODUCT DATA SHEETS FOR PRIMER APPLICATION REQUIREMENTS. 4. PIPE FLASHING MUST EXTEND VERTICALLY A MINIMUM OF 8" FROM ROOF SURFACE. FIELD MEMBRANE PVC PIPE FLASHING EXTEND FLASHING FLASHING MEMBRANE A MINIMUM OF 3" BEYOND FASTENER PLATES TO ACCOMMODATE A MINIMUM 1.5" HEAT WELDED SEAM TO FIELD MEMBRANE SEPARATOR SHEET BASE SHEET/ANCHOR SHEET VAPOR RETARDER/AIR BARRIER DECK DECK DECK DECK DECK DECK DECK DECK RIB PROFILE SENTINEL UNIVERSAL SEALANT INSTALL A CONTINUOUS BEAD OF BUTYL SEALANT BELOW TOP EDGE OF PVC PIPE FLASHING AND INSTALL PIPE CLAMP AS SHOWN FLASHING MEMBRANE HEAT FLASHING MEMBRANE PRIOR TO INSTALLING TO FORM A MINIMUM 1/2" BEND UP THE VERTICAL SURFACE OF THE PENETRATION (PIPE FLASHING CUT AWAY FOR CLARITY) HEAT PIPE FLASHIN PRIOR TO INSTALLING TO FORM A 1/2" BEND ONTO THE FLASHING MEMBRANE AS SHOWN, HEAT WELD TO FLASHING MEMBRANE WRAP PVC PIPE FLASHING AROUND PENETRATION AND HEAT WELD A MINIMUM 1" SEAM AT VERTICAL LAP TERMINATE FIELD MEMBRANE BY SECURING PERIMETER WITH FASTENER PLATE A MINIMUM OF 2" FROM EDGE OF PIPE FLASHING AND SPACED A MAXIMUM OF 12" APART TO ACCOMMODATE A MINIMUM 2" HEAT WELDED SEAM SENTINEL UNIVERSAL SEALANT INSTALL A CONTINUOUS BEAD OF BUTYL SEALANT BELOW TOP EDGE OF PVC PIPE FLASHING AND INSTALL PIPE CLAMP AS SHOWN WRAP PVC PIPE FLASHING AROUND PENETRATION AND HEAT WELD A MINIMUM 1" SEAM AT VERTICAL LAP TERMINATE FIELD MEMBRANE BY SECURING PERIMETER WITH FASTENER PLATE A MINIMUM OF 1" FROM PENETRATION AND SPACED A MAXIMUM OF 12" THERMAL BARRIER COVERBOARD INSULATION INSULATION INSULATION INSULATION

DRAWING MUST BE VIEWED IN ADOBE READER TO ......HEAT PIPE FLASHIN PRIOR TO INSTALLING TO FORM A 1/2" BEND ONTO THE FLASHING MEMBRANE AS SHOWN, HEAT WELD TO FLASHING MEMBRANE WRAP PVC

  • Upload
    others

  • View
    6

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DRAWING MUST BE VIEWED IN ADOBE READER TO ......HEAT PIPE FLASHIN PRIOR TO INSTALLING TO FORM A 1/2" BEND ONTO THE FLASHING MEMBRANE AS SHOWN, HEAT WELD TO FLASHING MEMBRANE WRAP PVC

THERMAL BARRIERTHERMAL BARRIER

TITLE:

DRAWN BY: SOPREMA TECHNICAL SUPPORT, GGALLOWAY

NO.: DATE:REVISION:

DATE: 10.17.2018

SCALE: NTS

DRAWING NUMBER:

US.RPVC.06.01

PVC MEMBRANE,INSULATED,

PIPE PENETRATIONUSAGE OF THIS DETAIL IS GOVERNED BY THE TERMS OF SERVICE FOR SOPREMA DETAILS.

PLEASE CONSULT THESE TERMS OF SERVICE PRIOR TO UTILIZING THIS DRAWING.

US CORPORATE ADDRESS310 QUADRAL DRIVE

WADSWORTH, OHIO 44281www.soprema.usTel:330.334.0066

W I L L I A M G R A N T G A L L O W A YPROJECT:

DRAWING MUST BE VIEWED IN ADOBE READER TO ENABLE CUSTOM LAYERING

NOTES:1. SOPREMA DETAIL DRAWINGS: REFER TO SOPREMA AND OTHER RELATED PUBLISHED DOCUMENTATION, PRODUCT DATA SHEETS (PDS) AND SAFETY DATA SHEETS (SDS) FOR ADDITIONAL

INFORMATION. ALL DETAIL DRAWINGS AND RELATED INSTALLATION GUIDELINES ARE PROVIDED BY SOPREMA FOR THE SOLE PURPOSE OF ISSUING A SOPREMA WARRANTY. ACCORDINGLY, THEDETAIL DRAWINGS ARE NOT OFFERED, AND SHOULD NOT BE CONSIDERED, AS A SUBSTITUTE FOR PROFESSIONAL DESIGN SERVICES.

2. HOT WORK: THE CONTRACTOR IS RESPONSIBLE FOR DETERMINING APPROPRIATE CONDITIONS TO UTILIZE HEAT-WELDING EQUIPMENT. REFER TO LOCAL CODES AND BUILDING OWNER'SREQUIREMENTS FOR HOT WORK OPERATIONS.

3. PRIMER: WHERE NOT SHOWN OR INDICATED ON DETAIL DRAWINGS, REFER TO MATERIAL PRODUCT DATA SHEETS FOR PRIMER APPLICATION REQUIREMENTS.4. PIPE FLASHING MUST EXTEND VERTICALLY A MINIMUM OF 8" FROM ROOF SURFACE.

FIELD MEMBRANE

PVC PIPE FLASHING

EXTEND FLASHING FLASHING MEMBRANE AMINIMUM OF 3" BEYOND FASTENER PLATES

TO ACCOMMODATE A MINIMUM 1.5" HEATWELDED SEAM TO FIELD MEMBRANE SEPARATOR SHEET

BASE SHEET/ANCHOR SHEET

VAPOR RETARDER/AIR BARRIER

DECKDECKDECKDECKDECKDECKDECKDECK

RIB PROFILE

SENTINEL UNIVERSAL SEALANTINSTALL A CONTINUOUS BEAD OF BUTYL SEALANT

BELOW TOP EDGE OF PVC PIPE FLASHINGAND INSTALL PIPE CLAMP AS SHOWN

FLASHING MEMBRANE

HEAT FLASHING MEMBRANE PRIOR TO INSTALLING TO FORM AMINIMUM 1/2" BEND UP THE VERTICAL SURFACE OF THE PENETRATION(PIPE FLASHING CUT AWAY FOR CLARITY)

HEAT PIPE FLASHIN PRIOR TO INSTALLINGTO FORM A 1/2" BEND ONTO THE FLASHING MEMBRANE

AS SHOWN, HEAT WELD TO FLASHING MEMBRANE

WRAP PVC PIPE FLASHING AROUND PENETRATION ANDHEAT WELD A MINIMUM 1" SEAM AT VERTICAL LAP

TERMINATE FIELD MEMBRANE BY SECURING PERIMETERWITH FASTENER PLATE A MINIMUM OF 2" FROM EDGE OF PIPEFLASHING AND SPACED A MAXIMUM OF 12" APARTTO ACCOMMODATE A MINIMUM 2" HEAT WELDED SEAM

SENTINEL UNIVERSAL SEALANTINSTALL A CONTINUOUS BEAD OF BUTYL SEALANT

BELOW TOP EDGE OF PVC PIPE FLASHINGAND INSTALL PIPE CLAMP AS SHOWN

WRAP PVC PIPE FLASHING AROUND PENETRATION ANDHEAT WELD A MINIMUM 1" SEAM AT VERTICAL LAP

TERMINATE FIELD MEMBRANE BY SECURING PERIMETERWITH FASTENER PLATE A MINIMUM OF 1" FROMPENETRATION AND SPACED A MAXIMUM OF 12"

THERMAL BARRIER

COVERBOARD

INSULATION

INSULATION

INSULATION

INSULATION