27
Reputati ion Resou Ya This urces Resu murat.a api Tekni Kisikli C document is privileg ® RWD ults RWDI An Unit 4 Law Lawrence Dunstable LU6 1BD United Ki Tel: +44 Fax: +44 D SUBMI Mura akbas@y ik Ins.San Cad. No.4 Altuniza Ist t +90 21 intended for ged and/or co DI name and lo Canad nemos Ltd wrence Indu e Way e, Bedfords D ingdom 4 (0)1582 47 4 (0)1582 47 Agao Draft ITTED T at Akbas yapiteknik n. Proje V Sarkuysa ade-Uskud tanbul 16 651 85 the sole use onfidential. If ogo are regis da | USA ustrial Esta shire 70250 70259 ogla M ft Re Clad N TO kproje.com Ve Taah L an Ak Pla dar 5 80 of the party t you have rec stered tradem A | UK | ate Masla Istanbu epor dding RWDI # Novembe m Ltd.Sti aza to whom it is ceived this in marks in Cana India | C ak EG ul, Turke rt T Pres # 130013 er 12, 20 addressed a n error, please ada and the U China | H GYO P ey Tow ssures 32 013 sam mat g an and may cont e notify us im United States Hong Kong Projec wer A s SUBMI Samant Project mantha.fow Matteo Project tteo.pava Gary Project gary.clarke Anton Project nton.davie tain informatio mmediately. s of America | Singapo ct A2 ITTED B tha Fowle t Enginee wler@rwd o Pavarin t Enginee arini@rwd y Clarke t Manage [email protected] n Davies t Director es@rwdi. on that is ore BY er er di.com ni er di.com er com r .com www.r rwdi.com m

Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

  • Upload
    others

  • View
    1

  • Download
    0

Embed Size (px)

Citation preview

Page 1: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources Results

Reputation Resources Results

Yapi Teknik Ins.San. Proje Ve Taah Ltd.Sti

This document is intended

Reputation Resources Results

[email protected]

Yapi Teknik Ins.San. Proje Ve Taah Ltd.StiKisikli Cad. No.4 Sarkuysan Ak Plaza

This document is intended privileged and/or confidential. If you have received this in error, please notify us immediately.

® RWDI name and logo are registered trademarks in Canada and the Un

Reputation Resources Results

RWDI Anemos LtdUnit 4 Lawrence Industrial EstateLawrence WayDunstable, BedfordshireLU6 1BDUnited Kingdom Tel: +44 (0)1582 470250Fax: +44 (0)1582 470259

Draft

SUBMITTED TO

Murat [email protected]

Yapi Teknik Ins.San. Proje Ve Taah Ltd.StiKisikli Cad. No.4 Sarkuysan Ak Plaza

AltunizadeIstanbul

t +90 216 651 85 80

This document is intended for the sole use of the party to whom it is addressed and may contain information that isprivileged and/or confidential. If you have received this in error, please notify us immediately.

® RWDI name and logo are registered trademarks in Canada and the Un

Canada | USA | UK | India | China

RWDI Anemos Ltd Unit 4 Lawrence Industrial EstateLawrence Way Dunstable, BedfordshireLU6 1BD United Kingdom

+44 (0)1582 470250+44 (0)1582 470259

Agaogl

Draft

SUBMITTED TO

Murat Akbas [email protected]

Yapi Teknik Ins.San. Proje Ve Taah Ltd.Sti

Kisikli Cad. No.4 Sarkuysan Ak PlazaAltunizade-Uskudar

Istanbul 90 216 651 85 80

for the sole use of the party to whom it is addressed and may contain information that isprivileged and/or confidential. If you have received this in error, please notify us immediately.

® RWDI name and logo are registered trademarks in Canada and the Un

Canada | USA | UK | India | China

Unit 4 Lawrence Industrial Estate

Dunstable, Bedfordshire

+44 (0)1582 470250 +44 (0)1582 470259

Agaogla Maslak

Draft Report

Cladding PressuresNovember 12

SUBMITTED TO

[email protected]

Yapi Teknik Ins.San. Proje Ve Taah Ltd.StiKisikli Cad. No.4 Sarkuysan Ak Plaza

Uskudar

90 216 651 85 80

for the sole use of the party to whom it is addressed and may contain information that isprivileged and/or confidential. If you have received this in error, please notify us immediately.

® RWDI name and logo are registered trademarks in Canada and the Un

Canada | USA | UK | India | China

Unit 4 Lawrence Industrial Estate

Maslak Istanbul, Turkey

Report

Cladding PressuresRWDI #

November 12

[email protected]

Yapi Teknik Ins.San. Proje Ve Taah Ltd.Sti Kisikli Cad. No.4 Sarkuysan Ak Plaza

for the sole use of the party to whom it is addressed and may contain information that isprivileged and/or confidential. If you have received this in error, please notify us immediately.

® RWDI name and logo are registered trademarks in Canada and the Un

Canada | USA | UK | India | China

Maslak EGYOIstanbul, Turkey

Report – Tower A

Cladding PressuresRWDI # 1300132

November 12, 2013

for the sole use of the party to whom it is addressed and may contain information that isprivileged and/or confidential. If you have received this in error, please notify us immediately.

® RWDI name and logo are registered trademarks in Canada and the Un

Canada | USA | UK | India | China | Hong Kong | Singapore

EGYO ProjectIstanbul, Turkey

Tower A

Cladding Pressures1300132

, 2013

[email protected]

[email protected]

[email protected]

[email protected]

for the sole use of the party to whom it is addressed and may contain information that isprivileged and/or confidential. If you have received this in error, please notify us immediately.

® RWDI name and logo are registered trademarks in Canada and the United States of America

| Hong Kong | Singapore

Project

Tower A

Cladding Pressures

SUBMITTED BY

Samantha FowlerProject

[email protected]

Matteo PavariniProject Engineer

[email protected]

Gary ClarkeProject Manager

[email protected]

Anton DaviesProject Director

[email protected]

for the sole use of the party to whom it is addressed and may contain information that isprivileged and/or confidential. If you have received this in error, please notify us immediately.

ited States of America

| Hong Kong | Singapore

Project

Tower A2

SUBMITTED BY

Samantha FowlerProject Engineer

[email protected]

Matteo PavariniProject Engineer

[email protected]

Gary Clarke Project Manager

[email protected]

Anton Davies Project Director

[email protected]

for the sole use of the party to whom it is addressed and may contain information that is

| Hong Kong | Singapore

SUBMITTED BY

Samantha Fowler Engineer

[email protected]

Matteo Pavarini Project Engineer

[email protected]

Project Manager

[email protected]

Project Director

[email protected]

www.rwdi.comwww.rwdi.comwww.rwdi.com

Page 2: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources Results

Reputation Resources Results

TABLE OF CONTENTS1. INTRODUCTION

2. WIND TUNNEL TESTS

2.1

2.2

3. WIND CLIMATE

4. DETERMINING CLADDING

5. RECOMMENDED CLADDING

6. APPLICABILITY OF RES

6.1

6.2

Tables Table 1:

FiguresFigure 1:Figure 2:Figure 3:Figure 4:

Figure 5:

Figure 6:

Figure 7

Figure 8

Figure 9

Figure 10

Figure 1

Figure 1

Figure 13

AppendicesAppendix A:

Reputation Resources Results

TABLE OF CONTENTSINTRODUCTION

WIND TUNNEL TESTS

2.1 Study Model and Surroundings

2.2 Upwind Profiles

WIND CLIMATE

DETERMINING CLADDING

RECOMMENDED CLADDING

APPLICABILITY OF RES

6.1 The Proximity Model

6.2 Study Model

Tables Table 1:

Figures Figure 1: Figure 2: Figure 3: Figure 4:

Figure 5:

Figure 6:

Figure 7:

Figure 8:

Figure 9:

Figure 10

Figure 11

Figure 12

Figure 13

ppendicesAppendix A:

Reputation Resources Results

Agaogla Maslak EGYO Project Cladding PressuresRWDI#1300132November 12, 2013.

TABLE OF CONTENTSINTRODUCTION ................................

WIND TUNNEL TESTS

Study Model and Surroundings

Upwind Profiles

WIND CLIMATE ................................

DETERMINING CLADDING

RECOMMENDED CLADDING

APPLICABILITY OF RES

The Proximity Model

Study Model ................................

Drawing

Wind Tunnel Study Model Site Plan Directional Distribution of Local Wind Speeds Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Vertical Wall Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Left Side, A Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Inside Front Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2

Outside Front (fins), Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Roof Plan, A Recommended Wind Loads for Cladding Design, Peak

Outside FrontFigure 10: Recommended Wind Loa

Left Side, 1: Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Inside Front2: Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2

Outside Front (fins), Inside Front (fins)Figure 13: Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Roof Plan,

ppendices Appendix A: Wind Tunnel Procedures

Canada | USA | UK | India |

Agaogla Maslak EGYO Project Cladding Pressures

1300132 November 12, 2013.

TABLE OF CONTENTS................................

WIND TUNNEL TESTS ................................

Study Model and Surroundings

Upwind Profiles ................................

................................

DETERMINING CLADDING

RECOMMENDED CLADDING

APPLICABILITY OF RESULTS

The Proximity Model ................................

................................

Drawing List

Wind Tunnel Study ModelSite Plan Directional Distribution of Local Wind SpeedsRecommended Wind Loads for Cladding Design, Peak Negative Pressures, Vertical WallRecommended Wind Loads for Cladding Design, Peak Negative Pressures, Left Side, A2 Recommended Wind Loads for Cladding Design, Peak Negative Pressures, Inside Front Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 Outside Front (fins), Recommended Wind Loads for Cladding Design, Peak Negative Pressures, Roof Plan, ARecommended Wind Loads for Cladding Design, Peak Outside FrontRecommended Wind LoaLeft Side, A2Recommended Wind Loads for Cladding Design, Peak Positive Pressures, Inside Front Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2 Outside Front (fins), Inside Front (fins)Recommended Wind Loads for Cladding Design, Peak Positive Pressures, Roof Plan, A

Wind Tunnel Procedures

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Tower A2

November 12, 2013.

TABLE OF CONTENTS ................................

................................

Study Model and Surroundings

................................

................................

DETERMINING CLADDING WIND LOADS FROM WIND

RECOMMENDED CLADDING DESIGN WIND LOADS

ULTS ................................

................................

................................

List for Model Construction

Wind Tunnel Study Model

Directional Distribution of Local Wind SpeedsRecommended Wind Loads for Cladding Design, Peak Negative Pressures, Vertical Wall Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

2 – Right SideRecommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 Outside Front (fins), Inside FrontRecommended Wind Loads for Cladding Design, Peak Negative Pressures, Roof Plan, A2 – Roof Plan at Z KAT, ARecommended Wind Loads for Cladding Design, Peak Outside Front Recommended Wind Loa

2 – Right SideRecommended Wind Loads for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2 Outside Front (fins), Inside Front (fins)Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

A2 – Roof Plan at Z KAT,

Wind Tunnel Procedures

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Istanbul, TurkeyTower A2

................................................................

................................................................

Study Model and Surroundings ................................

................................................................

................................................................

WIND LOADS FROM WIND

DESIGN WIND LOADS

................................

................................

................................................................

for Model Construction

Wind Tunnel Study Model

Directional Distribution of Local Wind SpeedsRecommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, Right Side

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 Inside Front

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, Roof Plan at Z KAT, A

Recommended Wind Loads for Cladding Design, Peak

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, Right Side

Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2 Outside Front (fins), Inside Front (fins)Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Roof Plan at Z KAT,

Wind Tunnel Procedures

Canada | USA | UK | India | China

Istanbul, Turkey

................................

................................

................................

................................

................................

WIND LOADS FROM WIND

DESIGN WIND LOADS

................................................................

................................................................

................................

for Model Construction

Directional Distribution of Local Wind SpeedsRecommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 Inside Front (fins)

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, Roof Plan at Z KAT, A2

Recommended Wind Loads for Cladding Design, Peak

ds for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2 Outside Front (fins), Inside Front (fins) Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Roof Plan at Z KAT, A2

China | Hong Kong | Singapore

................................................................

................................

................................................................

................................................................

................................................................

WIND LOADS FROM WIND TUNNEL TEST RESULTS

DESIGN WIND LOADS ................................

................................

................................

................................................................

Directional Distribution of Local Wind Speeds Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, 2 – Soffit Plan

Recommended Wind Loads for Cladding Design, Peak

ds for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, 2 – Soffit Plan

| Hong Kong | Singapore

................................

................................................................

................................

................................

................................

TUNNEL TEST RESULTS

................................

................................

................................................................

................................

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, Soffit Plan

Recommended Wind Loads for Cladding Design, Peak Positive

ds for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, Soffit Plan

| Hong Kong | Singapore

.........................................................

................................

...........................................................

................................

..........................................................

TUNNEL TEST RESULTS

.............................................................

................................................................

................................

.........................................................

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Positive Pressures,

ds for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2

Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

| Hong Kong | Singapore

.........................

...............................................

...........................

....................................................

..........................

TUNNEL TEST RESULTS ..............

.............................

................................

............................................

.........................

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2

Recommended Wind Loads for Cladding Design, Peak Negative Pressures,

Pressures,

ds for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2

Recommended Wind Loads for Cladding Design, Peak Positive Pressures,

www.rwdi.com

......................... 1 ............... 2

........................... 2

.................... 2

.......................... 2 .............. 2

............................. 3 .................................. 4

............ 4

......................... 4

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 –

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 –

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 –

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 –

Recommended Wind Loads for Cladding Design, Peak Negative Pressures, A2 –

Pressures, A2 –

ds for Cladding Design, Peak Positive Pressures, A2 –

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2 –

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2 –

Recommended Wind Loads for Cladding Design, Peak Positive Pressures, A2 –

www.rwdi.com

www.rwdi.com

Page 3: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources Results

Reputation Resources Results

1. Rowan Williams Davies & Irwin Inc. (RWDI) was retained by the proposed a multiconference facilities. exterior envelope of

The following table summarizes relevant information about the design team, results of the study and the governing parameters:

Project Details: ArchitectKey Results and Recommendations: Recommended Cladding Design Wind Loads

Range of Negative PressuresRange of Positive Pressures

Selected Analysis Parameters: Internal Pressures Basic Wind Speed per FBC 2001 Importance Factor on Wind

The wind tunnel test procedures met or exceeded the requirements set out in 7-10 Standard.the results and recommendations. Appendix A provides testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document Buildings (RD2

Reputation Resources Results

INTRODUCTIONRowan Williams Davies & Irwin Inc. (RWDI) was retained by the proposed Agaoglu Maslak a multi-tower development comprised of four phases, with hotel, residential, office, retail and conference facilities. exterior envelope of

The following table summarizes relevant information about the design team, results of the study and the governing parameters:

Project Details: Architect

Key Results and Recommendations:Recommended Cladding Design Wind Loads Negative Pressures Positive PressuresRange of Negative PressuresRange of Positive Pressures

Selected Analysis Parameters:Internal PressuresBasic Wind Speed per FBC 2001Importance Factor on Wind

The wind tunnel test procedures met or exceeded the requirements set out in Standard.

the results and recommendations. Appendix A provides testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document Buildings (RD2

Reputation Resources Results

Agaogla Maslak EGYO Project Cladding PressuresRWDI#1300132November 12, 2013.

INTRODUCTIONRowan Williams Davies & Irwin Inc. (RWDI) was retained by

Agaoglu Maslak tower development comprised of four phases, with hotel, residential, office, retail and

conference facilities. The exterior envelope of tower A

The following table summarizes relevant information about the design team, results of the study and the governing parameters:

Key Results and Recommendations:Recommended Cladding Design Wind Loads

Negative PressuresPositive Pressures

Range of Negative PressuresRange of Positive Pressures

Selected Analysis Parameters:Internal Pressures Basic Wind Speed per FBC 2001Importance Factor on Wind

The wind tunnel test procedures met or exceeded the requirements set out in Standard. The following sections outline the test methodology for the current study, and discuss

the results and recommendations. Appendix A provides testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document Buildings (RD2-2000.1), which is available upon request.

Canada | USA | UK | India |

Agaogla Maslak EGYO Project ing Pressures

1300132 November 12, 2013.

INTRODUCTIONRowan Williams Davies & Irwin Inc. (RWDI) was retained by

Agaoglu Maslak 1453tower development comprised of four phases, with hotel, residential, office, retail and

The objective of this study was to determine the wind loads for design of the tower A2.

The following table summarizes relevant information about the design team, results of the study and the governing parameters:

Key Results and Recommendations: Recommended Cladding Design Wind Loads

Negative Pressures Positive Pressures

Range of Negative Pressures Range of Positive Pressures

Selected Analysis Parameters:

Basic Wind Speed per FBC 2001 Importance Factor on Wind Speed

The wind tunnel test procedures met or exceeded the requirements set out in The following sections outline the test methodology for the current study, and discuss

the results and recommendations. Appendix A provides testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document

1), which is available upon request.

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Tower A2

November 12, 2013.

INTRODUCTION Rowan Williams Davies & Irwin Inc. (RWDI) was retained by

1453 Project in Istanbul, Turkey.tower development comprised of four phases, with hotel, residential, office, retail and

objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

Recommended Cladding Design Wind Loads

The wind tunnel test procedures met or exceeded the requirements set out in The following sections outline the test methodology for the current study, and discuss

the results and recommendations. Appendix A provides testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document

1), which is available upon request.

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Istanbul, TurkeyTower A2

Rowan Williams Davies & Irwin Inc. (RWDI) was retained by Project in Istanbul, Turkey.

tower development comprised of four phases, with hotel, residential, office, retail and objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

The wind tunnel test procedures met or exceeded the requirements set out in The following sections outline the test methodology for the current study, and discuss

the results and recommendations. Appendix A provides testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document

1), which is available upon request.

Canada | USA | UK | India | China

Istanbul, Turkey

Rowan Williams Davies & Irwin Inc. (RWDI) was retained by Project in Istanbul, Turkey.

tower development comprised of four phases, with hotel, residential, office, retail and objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

Leach Rhodes Walker Architects

Figures 4 to Figures -1.0 kPa +1.0 kPa to +1.75

+0.19 kPa, 36m/s 31.0

The wind tunnel test procedures met or exceeded the requirements set out in The following sections outline the test methodology for the current study, and discuss

the results and recommendations. Appendix A provides testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document

1), which is available upon request.

China | Hong Kong | Singapore

Rowan Williams Davies & Irwin Inc. (RWDI) was retained by Yapi TeknikProject in Istanbul, Turkey. The Agaoglu Maslak

tower development comprised of four phases, with hotel, residential, office, retail and objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

Leach Rhodes Walker Architects

Figures 4 to 8 Figures 9 to 13 1.0 kPa to -2.0 kPa

+1.0 kPa to +1.75 kPa

kPa, -0.19 kPa3-second Gust Speed at

The wind tunnel test procedures met or exceeded the requirements set out in The following sections outline the test methodology for the current study, and discuss

the results and recommendations. Appendix A provides additional background information on the testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document

| Hong Kong | Singapore

Teknik to study the wind loading on The Agaoglu Maslak

tower development comprised of four phases, with hotel, residential, office, retail and objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

Leach Rhodes Walker Architects

kPa kPa

kPa second Gust Speed at

The wind tunnel test procedures met or exceeded the requirements set out in The following sections outline the test methodology for the current study, and discuss

additional background information on the testing and analysis procedures for this type of study. For detailed explanations of the procedures and underlying theory, refer to RWDI’s Technical Reference Document -

| Hong Kong | Singapore

to study the wind loading on The Agaoglu Maslak

tower development comprised of four phases, with hotel, residential, office, retail and objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

Leach Rhodes Walker Architects

second Gust Speed at 10m in open terrain

The wind tunnel test procedures met or exceeded the requirements set out in Chapter 31The following sections outline the test methodology for the current study, and discuss

additional background information on the testing and analysis procedures for this type of study. For detailed explanations of the procedures

Wind Tunnel Studies for

| Hong Kong | Singapore

to study the wind loading on The Agaoglu Maslak EGYO Project is

tower development comprised of four phases, with hotel, residential, office, retail and objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

in open terrain

Chapter 31 of the ASCE The following sections outline the test methodology for the current study, and discuss

additional background information on the testing and analysis procedures for this type of study. For detailed explanations of the procedures

Wind Tunnel Studies for

www.rwdi.com

Page 1

to study the wind loading on Project is

tower development comprised of four phases, with hotel, residential, office, retail and objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

of the ASCE The following sections outline the test methodology for the current study, and discuss

additional background information on the testing and analysis procedures for this type of study. For detailed explanations of the procedures

Wind Tunnel Studies for

www.rwdi.com

to study the wind loading on Project is

tower development comprised of four phases, with hotel, residential, office, retail and objective of this study was to determine the wind loads for design of the

The following table summarizes relevant information about the design team, results of the study and

of the ASCE The following sections outline the test methodology for the current study, and discuss

additional background information on the testing and analysis procedures for this type of study. For detailed explanations of the procedures

Wind Tunnel Studies for

www.rwdi.com

Page 4: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources Results

Reputation Resources Results

2.

2.1

A 1:400 scale model of the proposed development was constructed using the architectural drawings listed in Table 1. presence of all surroundings within a fulllayer wind tunnel facility in

Photographs of the orientation plan showing the location of the

2.2

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was simulated in the testing by at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true north.

Upwind Terrain

Urban/Suburban terrain immediately upwind of the surrounding model, with open

3. In order to predict the fullthe wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at Istanbul.

The magnitude of the wind wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified for Istanbul

The wind climate for on the wind climate model, the strength of the wind versus wind direction. wind speeds from

Reputation Resources Results

WIND TUNNEL TESTS

Study Model and Surroundings

A 1:400 scale model of the proposed development was constructed using the architectural drawings listed in Table 1. presence of all surroundings within a fulllayer wind tunnel facility in

Photographs of the orientation plan showing the location of the

Upwind Profiles

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was simulated in the testing by at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true north.

Upwind Terrain

Urban/Suburban terrain immediately upwind of the surrounding model, with open

WIND CLIMATEIn order to predict the fullthe wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at Istanbul.

The magnitude of the wind wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

Istanbul in the TS498 Turkish Standard.

The wind climate for on the wind climate model, the strength of the wind versus wind direction. wind speeds from

Reputation Resources Results

Agaogla Maslak EGYO Project Cladding PressuresRWDI#1300132November 12, 2013.

WIND TUNNEL TESTS

Study Model and Surroundings

A 1:400 scale model of the proposed development was constructed using the architectural drawings listed in Table 1. The model was instrumented with presence of all surroundings within a fulllayer wind tunnel facility in

Photographs of the scale model in the boundary layer wind tunnel orientation plan showing the location of the

Upwind Profiles

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was simulated in the testing by at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true

Upwind Terrain

Urban/Suburban terrain – varying lengths of suburban and urban fetch immediately upwind of the surrounding model, with open

WIND CLIMATEIn order to predict the fullthe wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at

The magnitude of the wind wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

in the TS498 Turkish Standard.

The wind climate for Istanbulon the wind climate model, the strength of the wind versus wind direction. wind speeds from the data set as a function of return perio

Canada | USA | UK | India |

Agaogla Maslak EGYO Project ing Pressures

1300132 November 12, 2013.

WIND TUNNEL TESTS

Study Model and Surroundings

A 1:400 scale model of the proposed development was constructed using the architectural drawings The model was instrumented with

presence of all surroundings within a fulllayer wind tunnel facility in Dunstable, Bedfordshire

scale model in the boundary layer wind tunnel orientation plan showing the location of the

Upwind Profiles

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was simulated in the testing by appropriate roughness on the wind tunnel floor and flow conditioning spires at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true

varying lengths of suburban and urban fetch immediately upwind of the surrounding model, with open

WIND CLIMATEIn order to predict the full-scale wind pressures acting on the building as a funthe wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at

The magnitude of the wind velocity for the 50 year return period corresponded to a 3wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

in the TS498 Turkish Standard.

Istanbul is illustrated by the plots in Figure 3.on the wind climate model, the strength of the wind versus wind direction.

data set as a function of return perio

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Tower A2

November 12, 2013.

WIND TUNNEL TESTS

Study Model and Surroundings

A 1:400 scale model of the proposed development was constructed using the architectural drawings The model was instrumented with

presence of all surroundings within a fullDunstable, Bedfordshire

scale model in the boundary layer wind tunnel orientation plan showing the location of the

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true

varying lengths of suburban and urban fetch immediately upwind of the surrounding model, with open

WIND CLIMATE scale wind pressures acting on the building as a fun

the wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at

velocity for the 50 year return period corresponded to a 3wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

in the TS498 Turkish Standard.

is illustrated by the plots in Figure 3.on the wind climate model, the strength of the wind versus wind direction.

data set as a function of return perio

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Istanbul, TurkeyTower A2

WIND TUNNEL TESTS

Study Model and Surroundings

A 1:400 scale model of the proposed development was constructed using the architectural drawings The model was instrumented with

presence of all surroundings within a full-scale radius of 460 m, in RWDI’s 2.4 m Dunstable, Bedfordshire

scale model in the boundary layer wind tunnel orientation plan showing the location of the study site is given in Figure

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true

varying lengths of suburban and urban fetch immediately upwind of the surrounding model, with open terrain or

scale wind pressures acting on the building as a funthe wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at

velocity for the 50 year return period corresponded to a 3wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

in the TS498 Turkish Standard.

is illustrated by the plots in Figure 3.on the wind climate model, the strength of the wind versus wind direction.

data set as a function of return perio

Canada | USA | UK | India | China

Istanbul, Turkey

A 1:400 scale model of the proposed development was constructed using the architectural drawings The model was instrumented with 501

scale radius of 460 m, in RWDI’s 2.4 m Dunstable, Bedfordshire.

scale model in the boundary layer wind tunnel study site is given in Figure

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true

varying lengths of suburban and urban fetch terrain or water beyond.

scale wind pressures acting on the building as a funthe wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at

velocity for the 50 year return period corresponded to a 3wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

is illustrated by the plots in Figure 3.on the wind climate model, the strength of the wind versus wind direction.

data set as a function of return period.

China | Hong Kong | Singapore

A 1:400 scale model of the proposed development was constructed using the architectural drawings 501 pressure taps and

scale radius of 460 m, in RWDI’s 2.4 m

scale model in the boundary layer wind tunnel study site is given in Figure

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true

water beyond.

scale wind pressures acting on the building as a funthe wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at

velocity for the 50 year return period corresponded to a 3wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

is illustrated by the plots in Figure 3. on the wind climate model, the strength of the wind versus wind direction.

d.

| Hong Kong | Singapore

A 1:400 scale model of the proposed development was constructed using the architectural drawings pressure taps and

scale radius of 460 m, in RWDI’s 2.4 m

scale model in the boundary layer wind tunnel are study site is given in Figure 2.

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwiWind direction is defined as the direction from which the wind blows, measured clockwise from true

Wind Directions (Inclusive)

scale wind pressures acting on the building as a funthe wind tunnel data were combined with a statistical model of the local wind climate. The wind climate model was based on local surface wind measurements taken at Ataturk International Airport,

velocity for the 50 year return period corresponded to a 3wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

The upper two plots show, based on the wind climate model, the strength of the wind versus wind direction.

| Hong Kong | Singapore

A 1:400 scale model of the proposed development was constructed using the architectural drawings pressure taps and was tested in the

scale radius of 460 m, in RWDI’s 2.4 m ×

shown in Figure 1

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent analysis of the data from the model, was targeted to represent the following upwind terrain conditions. Wind direction is defined as the direction from which the wind blows, measured clockwise from true

Wind Directions (Inclusive)

10°

scale wind pressures acting on the building as a function of return period, the wind tunnel data were combined with a statistical model of the local wind climate. The wind

Ataturk International Airport,

velocity for the 50 year return period corresponded to a 3wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

The upper two plots show, based on the wind climate model, the strength of the wind versus wind direction. The lower plot shows the

| Hong Kong | Singapore

A 1:400 scale model of the proposed development was constructed using the architectural drawings was tested in the × 2.0 m boundary

in Figure 1

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent nd terrain conditions.

Wind direction is defined as the direction from which the wind blows, measured clockwise from true

Wind Directions (Inclusive)

to 360°

ction of return period, the wind tunnel data were combined with a statistical model of the local wind climate. The wind

Ataturk International Airport,

velocity for the 50 year return period corresponded to a 3-second gust wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

The upper two plots show, based The lower plot shows the

www.rwdi.com

Page 2

A 1:400 scale model of the proposed development was constructed using the architectural drawings was tested in the

2.0 m boundary

in Figure 1. An

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent nd terrain conditions.

Wind direction is defined as the direction from which the wind blows, measured clockwise from true

Wind Directions (Inclusive)

ction of return period, the wind tunnel data were combined with a statistical model of the local wind climate. The wind

Ataturk International Airport,

second gust wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

The upper two plots show, based The lower plot shows the

www.rwdi.com

A 1:400 scale model of the proposed development was constructed using the architectural drawings was tested in the

2.0 m boundary

An

Beyond the modeled area, the influence of the upwind terrain on the planetary boundary layer was appropriate roughness on the wind tunnel floor and flow conditioning spires

at the upwind end of the working section for each wind direction. This simulation, and subsequent nd terrain conditions.

Wind direction is defined as the direction from which the wind blows, measured clockwise from true

ction of return period, the wind tunnel data were combined with a statistical model of the local wind climate. The wind

Ataturk International Airport,

second gust wind speed of 36m/s at a height of 10 m in open terrain. This value is consistent with that identified

The upper two plots show, based The lower plot shows the

www.rwdi.com

Page 5: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources Results

Reputation Resources Results

4. TUNNEL TEST RESULTSFor design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

For elements exposed to wind on the external surface onlyapplied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects. sources of air leakag

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal pressure allowance values consideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures were augmented by an amount equal to the positive internal presspressures were obtained by augmenting the exterior positive pressure by an amount equal to the magnitude of the negative internal pressure.

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference across the element.

5. It is recommended that the wind loads presented year return period. The drawings in these figures have been zoned using the pressure indicated is the maximum pressure in that particular zone. For example, a would have pressures ranging from

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures measured across the fins.

Note thincluding an allowance for internal pressures. Design of the cladding to the provided wind loads will not necessarily prevent breakage due to impact by wind borne

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to the building's cladding system in the same manner as analytical methods.

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was which occurred on the negative wind loads were cladding wind load was +Figure

Reputation Resources Results

DETERMINING CLADDINGTUNNEL TEST RESULTSFor design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

For elements exposed to wind on the external surface onlyapplied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects. sources of air leakag

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal pressure allowance values consideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures were augmented by an amount equal to the positive internal presspressures were obtained by augmenting the exterior positive pressure by an amount equal to the magnitude of the negative internal pressure.

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference across the element.

RECOMMENDED CLADDINGIt is recommended that the wind loads presented year return period. The drawings in these figures have been zoned using the pressure indicated is the maximum pressure in that particular zone. For example, a would have pressures ranging from

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures measured across the fins.

Note that the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will not necessarily prevent breakage due to impact by wind borne

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to the building's cladding system in the same manner as analytical methods.

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was which occurred on the negative wind loads were cladding wind load was +Figure 11. The majority of the positive wind loads were

Reputation Resources Results

Agaogla Maslak EGYO Project Cladding PressuresRWDI#1300132November 12, 2013.

DETERMINING CLADDINGTUNNEL TEST RESULTSFor design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

For elements exposed to wind on the external surface onlyapplied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects. sources of air leakage include uniformly distributed small leakage pa

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal pressure allowance values consideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures were augmented by an amount equal to the positive internal presspressures were obtained by augmenting the exterior positive pressure by an amount equal to the magnitude of the negative internal pressure.

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference across the element.

RECOMMENDED CLADDINGIt is recommended that the wind loads presented year return period. The drawings in these figures have been zoned using the pressure indicated is the maximum pressure in that particular zone. For example, a would have pressures ranging from

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures measured across the fins.

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will not necessarily prevent breakage due to impact by wind borne

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to the building's cladding system in the same manner as analytical methods.

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was which occurred on various locations across the building facadethe negative wind loads were cladding wind load was +

. The majority of the positive wind loads were

Canada | USA | UK | India |

Agaogla Maslak EGYO Project ing Pressures

1300132 November 12, 2013.

DETERMINING CLADDINGTUNNEL TEST RESULTSFor design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

For elements exposed to wind on the external surface onlyapplied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects.

e include uniformly distributed small leakage pa

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal pressure allowance values were consideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures were augmented by an amount equal to the positive internal presspressures were obtained by augmenting the exterior positive pressure by an amount equal to the magnitude of the negative internal pressure.

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference

RECOMMENDED CLADDINGIt is recommended that the wind loads presented year return period. The drawings in these figures have been zoned using the pressure indicated is the maximum pressure in that particular zone. For example, a would have pressures ranging from

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures measured across the fins.

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will not necessarily prevent breakage due to impact by wind borne

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to the building's cladding system in the same manner as

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was

various locations across the building facadethe negative wind loads were in the range of cladding wind load was +1.75kPa, which occurred on t

. The majority of the positive wind loads were

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Tower A2

November 12, 2013.

DETERMINING CLADDINGTUNNEL TEST RESULTSFor design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

For elements exposed to wind on the external surface onlyapplied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects.

e include uniformly distributed small leakage pa

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal

were ±0.19consideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures were augmented by an amount equal to the positive internal presspressures were obtained by augmenting the exterior positive pressure by an amount equal to the magnitude of the negative internal pressure.

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference

RECOMMENDED CLADDINGIt is recommended that the wind loads presented year return period. The drawings in these figures have been zoned using the pressure indicated is the maximum pressure in that particular zone. For example, a would have pressures ranging from 1.26

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will not necessarily prevent breakage due to impact by wind borne

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to the building's cladding system in the same manner as

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was

various locations across the building facadein the range of kPa, which occurred on t

. The majority of the positive wind loads were

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Istanbul, TurkeyTower A2

DETERMINING CLADDINGTUNNEL TEST RESULTS For design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

For elements exposed to wind on the external surface onlyapplied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects.

e include uniformly distributed small leakage pa

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal

±0.19 kPa. consideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures were augmented by an amount equal to the positive internal presspressures were obtained by augmenting the exterior positive pressure by an amount equal to the magnitude of the negative internal pressure.

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference

RECOMMENDED CLADDINGIt is recommended that the wind loads presented year return period. The drawings in these figures have been zoned using the pressure indicated is the maximum pressure in that particular zone. For example, a

1.26 kPa to 1.5

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will not necessarily prevent breakage due to impact by wind borne

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to the building's cladding system in the same manner as

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was

various locations across the building facadein the range of -1.0kPa, which occurred on t

. The majority of the positive wind loads were

Canada | USA | UK | India | China

Istanbul, Turkey

DETERMINING CLADDING WIND LOADS FROM WIND

For design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

For elements exposed to wind on the external surface onlyapplied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects.

e include uniformly distributed small leakage pa

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal

Note that this allowanconsideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures were augmented by an amount equal to the positive internal presspressures were obtained by augmenting the exterior positive pressure by an amount equal to the

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference

RECOMMENDED CLADDING It is recommended that the wind loads presented in Figures 4 through year return period. The drawings in these figures have been zoned using the pressure indicated is the maximum pressure in that particular zone. For example, a

1.5kPa.

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will not necessarily prevent breakage due to impact by wind borne

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to the building's cladding system in the same manner as

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was

various locations across the building facade0kPa to -1.5

kPa, which occurred on the . The majority of the positive wind loads were in the range of +1.0

China | Hong Kong | Singapore

WIND LOADS FROM WIND

For design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

For elements exposed to wind on the external surface only, an internal pressure allowance must be applied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects.

e include uniformly distributed small leakage pa

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal

Note that this allowanconsideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures were augmented by an amount equal to the positive internal pressure. Likewise, the net peak positive pressures were obtained by augmenting the exterior positive pressure by an amount equal to the

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference

DESIGN WIND LOADSin Figures 4 through

year return period. The drawings in these figures have been zoned using the pressure indicated is the maximum pressure in that particular zone. For example, a

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will not necessarily prevent breakage due to impact by wind borne debris.

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to the building's cladding system in the same manner as would wind loads calculated by code

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was

various locations across the building facade (Figure1.5kPa. The largest recommended positive

he Right Side (Figure 10in the range of +1.0

| Hong Kong | Singapore

WIND LOADS FROM WIND

For design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

, an internal pressure allowance must be applied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects.

e include uniformly distributed small leakage paths over the building’s envelop

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal

Note that this allowanconsideration of pressures induced by auxiliary mechanical systems.

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures ure. Likewise, the net peak positive

pressures were obtained by augmenting the exterior positive pressure by an amount equal to the

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference

DESIGN WIND LOADSin Figures 4 through 13

year return period. The drawings in these figures have been zoned using 0.25 the pressure indicated is the maximum pressure in that particular zone. For example, a

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will

debris.

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to

would wind loads calculated by code

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was

(Figures 4, 6 and 8kPa. The largest recommended positive

Right Side (Figure 10in the range of +1.0kPa to +

| Hong Kong | Singapore

WIND LOADS FROM WIND

For design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

, an internal pressure allowance must be applied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects.

ths over the building’s envelop

The wind loads provided are net pressures which include an allowance for windpressure based on a building without any large or significant openings. The resulting internal

Note that this allowance doesn’t include any

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures ure. Likewise, the net peak positive

pressures were obtained by augmenting the exterior positive pressure by an amount equal to the

For elements exposed to wind on opposite surfaces such as parapets, fins and cpressure acting on the element was determined by measuring the instantaneous pressure difference

DESIGN WIND LOADS be consid.25 kPa increments so that

the pressure indicated is the maximum pressure in that particular zone. For example, a

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to

would wind loads calculated by code

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was

s 4, 6 and 8). The majority of kPa. The largest recommended positive

Right Side (Figure 10) and on kPa to +1.5

| Hong Kong | Singapore

WIND LOADS FROM WIND

For design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on botexternal surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

, an internal pressure allowance must be applied to the measured external pressure in order to determine the net pressure applicable for design. In strong winds, the internal pressures are dominated by air leakage effects. Important

ths over the building’s envelop

The wind loads provided are net pressures which include an allowance for wind-induced internal pressure based on a building without any large or significant openings. The resulting internal

ce doesn’t include any

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures ure. Likewise, the net peak positive

pressures were obtained by augmenting the exterior positive pressure by an amount equal to the

For elements exposed to wind on opposite surfaces such as parapets, fins and canopies, the net pressure acting on the element was determined by measuring the instantaneous pressure difference

DESIGN WIND LOADSbe considered for the 50

kPa increments so that the pressure indicated is the maximum pressure in that particular zone. For example, a 1.5 kPa zone

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to

would wind loads calculated by code

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and "positive pressure" acts inward. The largest recommended negative cladding wind load was -

). The majority of kPa. The largest recommended positive

) and on Surface 1 in 1.5kPa.

www.rwdi.com

Page 3

WIND LOADS FROM WIND

For design of cladding elements, the net wind load acting across an element must be considered. The results provided in this report include the contributions of the wind loads acting on both the external surface (measured directly on the scale model during the wind tunnel test) and internal surface of the element (determined through analytical methods and the wind tunnel test data).

, an internal pressure allowance must be applied to the measured external pressure in order to determine the net pressure applicable for

Important ths over the building’s envelope.

induced internal pressure based on a building without any large or significant openings. The resulting internal

ce doesn’t include any

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures ure. Likewise, the net peak positive

pressures were obtained by augmenting the exterior positive pressure by an amount equal to the

anopies, the net pressure acting on the element was determined by measuring the instantaneous pressure difference

DESIGN WIND LOADS ered for the 50-

kPa increments so that kPa zone

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to

would wind loads calculated by code

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and -2.0 kPa,

). The majority of kPa. The largest recommended positive

Surface 1 in

www.rwdi.com

For design of cladding elements, the net wind load acting across an element must be considered. h the

external surface (measured directly on the scale model during the wind tunnel test) and internal

, an internal pressure allowance must be applied to the measured external pressure in order to determine the net pressure applicable for

Important

induced internal pressure based on a building without any large or significant openings. The resulting internal

ce doesn’t include any

To obtain the net peak negative pressure on the building's cladding, the negative exterior pressures ure. Likewise, the net peak positive

pressures were obtained by augmenting the exterior positive pressure by an amount equal to the

anopies, the net pressure acting on the element was determined by measuring the instantaneous pressure difference

kPa increments so that kPa zone

Wind loads have been provided for the elevation walls of the tower and separately for the fin features (figures 7 and 12). In these cases the local recommended pressures shown are differential pressures

at the recommended wind loads are for cladding design for resistance against wind pressure, including an allowance for internal pressures. Design of the cladding to the provided wind loads will

Note that the wind loads provided in this report include the effects of the directionality in the local wind climate. These loads do not contain safety or load factors and are to be applied to

would wind loads calculated by code

"Negative pressure" or suction is defined to act outward normal to the building's exterior surface and a,

). The majority of kPa. The largest recommended positive

Surface 1 in

www.rwdi.com

Page 6: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources Results

Reputation Resources Results

6.

6.1

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings model used for the wind tunnel tests reflected the currentand include, where appropriate, known offIf, at a later date, additional buildings besides those considered in the tested configuration are construcallowance for possible future changes in surroundings, our final recommended cladding design wind loads do not go below a minimum of

6.2

The reconstructed using the architectural information listed in Table 1that deviate substantially from the above those presented in this report. Therefore, if the design changes, RWDI should be contacted and requested to review the impact on the wind loads.

Reputation Resources Results

APPLICABILITY OF RES

The Proximity Model

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings model used for the wind tunnel tests reflected the currentand include, where appropriate, known offIf, at a later date, additional buildings besides those considered in the tested configuration are constructed or demolished near the project site, then some load changes could occur. To make some allowance for possible future changes in surroundings, our final recommended cladding design wind loads do not go below a minimum of

Study Model

The results presented in this report pertain to the scale model of the proposed development, constructed using the architectural information listed in Table 1that deviate substantially from the above those presented in this report. Therefore, if the design changes, RWDI should be contacted and requested to review the impact on the wind loads.

Reputation Resources Results

Agaogla Maslak EGYO Project Cladding PressuresRWDI#1300132November 12, 2013.

APPLICABILITY OF RES

The Proximity Model

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings model used for the wind tunnel tests reflected the currentand include, where appropriate, known offIf, at a later date, additional buildings besides those considered in the tested configuration are

ted or demolished near the project site, then some load changes could occur. To make some allowance for possible future changes in surroundings, our final recommended cladding design wind loads do not go below a minimum of

Study Model

sults presented in this report pertain to the scale model of the proposed development, constructed using the architectural information listed in Table 1that deviate substantially from the above those presented in this report. Therefore, if the design changes, RWDI should be contacted and requested to review the impact on the wind loads.

Canada | USA | UK | India |

Agaogla Maslak EGYO Project ing Pressures

1300132 November 12, 2013.

APPLICABILITY OF RES

The Proximity Model

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings model used for the wind tunnel tests reflected the currentand include, where appropriate, known offIf, at a later date, additional buildings besides those considered in the tested configuration are

ted or demolished near the project site, then some load changes could occur. To make some allowance for possible future changes in surroundings, our final recommended cladding design wind loads do not go below a minimum of

Study Model

sults presented in this report pertain to the scale model of the proposed development, constructed using the architectural information listed in Table 1that deviate substantially from the above those presented in this report. Therefore, if the design changes, RWDI should be contacted and requested to review the impact on the wind loads.

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Tower A2

November 12, 2013.

APPLICABILITY OF RES

The Proximity Model

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings model used for the wind tunnel tests reflected the currentand include, where appropriate, known offIf, at a later date, additional buildings besides those considered in the tested configuration are

ted or demolished near the project site, then some load changes could occur. To make some allowance for possible future changes in surroundings, our final recommended cladding design wind loads do not go below a minimum of ±1.0

sults presented in this report pertain to the scale model of the proposed development, constructed using the architectural information listed in Table 1that deviate substantially from the above those presented in this report. Therefore, if the design changes, RWDI should be contacted and requested to review the impact on the wind loads.

Canada | USA | UK | India |

Agaogla Maslak EGYO Project – Istanbul, TurkeyTower A2

APPLICABILITY OF RES

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings model used for the wind tunnel tests reflected the currentand include, where appropriate, known off-site structures expected to be completed in the near future. If, at a later date, additional buildings besides those considered in the tested configuration are

ted or demolished near the project site, then some load changes could occur. To make some allowance for possible future changes in surroundings, our final recommended cladding design wind

1.0kPa.

sults presented in this report pertain to the scale model of the proposed development, constructed using the architectural information listed in Table 1that deviate substantially from the above information;those presented in this report. Therefore, if the design changes, RWDI should be contacted and requested to review the impact on the wind loads.

Canada | USA | UK | India | China

Istanbul, Turkey

APPLICABILITY OF RESULTS

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings model used for the wind tunnel tests reflected the current

site structures expected to be completed in the near future. If, at a later date, additional buildings besides those considered in the tested configuration are

ted or demolished near the project site, then some load changes could occur. To make some allowance for possible future changes in surroundings, our final recommended cladding design wind

sults presented in this report pertain to the scale model of the proposed development, constructed using the architectural information listed in Table 1

information; the results for the revised design may differ from those presented in this report. Therefore, if the design changes, RWDI should be contacted and requested to review the impact on the wind loads.

China | Hong Kong | Singapore

ULTS

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings

state of development at the time of testing site structures expected to be completed in the near future.

If, at a later date, additional buildings besides those considered in the tested configuration are ted or demolished near the project site, then some load changes could occur. To make some

allowance for possible future changes in surroundings, our final recommended cladding design wind

sults presented in this report pertain to the scale model of the proposed development, constructed using the architectural information listed in Table 1. Should there be any design changes

the results for the revised design may differ from those presented in this report. Therefore, if the design changes, RWDI should be contacted and

| Hong Kong | Singapore

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings

state of development at the time of testing site structures expected to be completed in the near future.

If, at a later date, additional buildings besides those considered in the tested configuration are ted or demolished near the project site, then some load changes could occur. To make some

allowance for possible future changes in surroundings, our final recommended cladding design wind

sults presented in this report pertain to the scale model of the proposed development, Should there be any design changes

the results for the revised design may differ from those presented in this report. Therefore, if the design changes, RWDI should be contacted and

| Hong Kong | Singapore

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings

state of development at the time of testing site structures expected to be completed in the near future.

If, at a later date, additional buildings besides those considered in the tested configuration are ted or demolished near the project site, then some load changes could occur. To make some

allowance for possible future changes in surroundings, our final recommended cladding design wind

sults presented in this report pertain to the scale model of the proposed development, Should there be any design changes

the results for the revised design may differ from those presented in this report. Therefore, if the design changes, RWDI should be contacted and

| Hong Kong | Singapore

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings

state of development at the time of testing site structures expected to be completed in the near future.

If, at a later date, additional buildings besides those considered in the tested configuration are ted or demolished near the project site, then some load changes could occur. To make some

allowance for possible future changes in surroundings, our final recommended cladding design wind

sults presented in this report pertain to the scale model of the proposed development, Should there be any design changes

the results for the revised design may differ from those presented in this report. Therefore, if the design changes, RWDI should be contacted and

www.rwdi.com

Page 4

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings

state of development at the time of testing site structures expected to be completed in the near future.

If, at a later date, additional buildings besides those considered in the tested configuration are ted or demolished near the project site, then some load changes could occur. To make some

allowance for possible future changes in surroundings, our final recommended cladding design wind

sults presented in this report pertain to the scale model of the proposed development, Should there be any design changes

the results for the revised design may differ from those presented in this report. Therefore, if the design changes, RWDI should be contacted and

www.rwdi.com

The cladding design wind loads determined by the wind tunnel tests and aforementioned analytical procedures are applicable to the particular configuration of surroundings modeled. The surroundings

state of development at the time of testing site structures expected to be completed in the near future.

If, at a later date, additional buildings besides those considered in the tested configuration are ted or demolished near the project site, then some load changes could occur. To make some

allowance for possible future changes in surroundings, our final recommended cladding design wind

sults presented in this report pertain to the scale model of the proposed development, Should there be any design changes

the results for the revised design may differ from those presented in this report. Therefore, if the design changes, RWDI should be contacted and

www.rwdi.com

Page 7: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Û³°´±§»» Ö±¾ Ì·¬´»

ÌßÞÞÔÛÍ

Page 8: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation

Reputation Resources Results

TABLE 1The drawings and information listed below were received from were used to construct the scale model of the proposed be any design changes that deviate from this list of drawings, the results may change. Therefore, if changes in the design area made, it is recommended treview their potential effects on wind conditions.

Resources Results

TABLE 1The drawings and information listed below were received from were used to construct the scale model of the proposed be any design changes that deviate from this list of drawings, the results may change. Therefore, if changes in the design area made, it is recommended treview their potential effects on wind conditions.

Resources Results

TABLE 1: DRAWING LIST FOR MODThe drawings and information listed below were received from were used to construct the scale model of the proposed be any design changes that deviate from this list of drawings, the results may change. Therefore, if changes in the design area made, it is recommended treview their potential effects on wind conditions.

File Name

AgaogluAyazaga

AgaogluAyazaga

Canada | USA | UK | India | China

DRAWING LIST FOR MODThe drawings and information listed below were received from were used to construct the scale model of the proposed be any design changes that deviate from this list of drawings, the results may change. Therefore, if changes in the design area made, it is recommended treview their potential effects on wind conditions.

File Name

AgaogluAyazaga

AgaogluAyazaga

Canada | USA | UK | India | China

DRAWING LIST FOR MODThe drawings and information listed below were received from were used to construct the scale model of the proposed be any design changes that deviate from this list of drawings, the results may change. Therefore, if changes in the design area made, it is recommended treview their potential effects on wind conditions.

File Name

AgaogluAyazaga-10

AgaogluAyazaga-10

Canada | USA | UK | India | China

DRAWING LIST FOR MODThe drawings and information listed below were received from were used to construct the scale model of the proposed be any design changes that deviate from this list of drawings, the results may change. Therefore, if changes in the design area made, it is recommended treview their potential effects on wind conditions.

Canada | USA | UK | India | China

DRAWING LIST FOR MODThe drawings and information listed below were received from were used to construct the scale model of the proposed Agaogla Maslak EGYO Projectbe any design changes that deviate from this list of drawings, the results may change. Therefore, if changes in the design area made, it is recommended t

Canada | USA | UK | India | China | Hong Kong | Singapore

DRAWING LIST FOR MODEL CONSTRUCTIONThe drawings and information listed below were received from Leach Rhodes Walker Architects

Agaogla Maslak EGYO Projectbe any design changes that deviate from this list of drawings, the results may change. Therefore, if changes in the design area made, it is recommended that RWDI be contacted and requested to

File Type

.dwg

.skp

| Hong Kong | Singapore

EL CONSTRUCTIONLeach Rhodes Walker Architects

Agaogla Maslak EGYO Projectbe any design changes that deviate from this list of drawings, the results may change. Therefore, if

hat RWDI be contacted and requested to

File Type

.dwg

.skp

| Hong Kong | Singapore

EL CONSTRUCTIONLeach Rhodes Walker Architects

Agaogla Maslak EGYO Projectbe any design changes that deviate from this list of drawings, the results may change. Therefore, if

hat RWDI be contacted and requested to

Date Received

| Hong Kong | Singapore

Page

EL CONSTRUCTIONLeach Rhodes Walker Architects

Agaogla Maslak EGYO Project. Should there be any design changes that deviate from this list of drawings, the results may change. Therefore, if

hat RWDI be contacted and requested to

Date Received

13/01/03

13/01/03

www.rwdi.com

Page 1 of 1

EL CONSTRUCTION

Leach Rhodes Walker Architects and . Should there

be any design changes that deviate from this list of drawings, the results may change. Therefore, if hat RWDI be contacted and requested to

Date Received

13/01/03

13/01/03

www.rwdi.com

and . Should there

be any design changes that deviate from this list of drawings, the results may change. Therefore, if hat RWDI be contacted and requested to

www.rwdi.com

Page 9: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Û³°´±§»» Ö±¾ Ì·¬´»

Ú×ÙËËÎÛÍ

Page 10: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Wind Tunnel Study ModelTower A Agaogl

Wind Tunnel Study ModelTower A2

Agaogla Maslak EGYO Project

Wind Tunnel Study Model

Maslak EGYO Project

Wind Tunnel Study Model

Maslak EGYO Project – Istanbul, Turkey

Wind Tunnel Study Model

Istanbul, Turkey

Istanbul, Turkey

Project #1

Project #1300132

300132

Figure:

Date: November 12

1

Date: November 12, 2013

1

, 2013

Page 11: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 12: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Note: Wind Speeds shown are 3-second Gust Wind Speeds (m/s) at 10 m height in Open Terrain

Agaogla Maslak EGYO Project - Istanbul Project # 1300132 Date: Oct. 30, 2013

Figure No. 3Directional Distribution of Local Wind Speeds

0.0

5.0

10.0

15.0

20.0

25.0

30.0

35.0

40.0

45.0

50.0

1 10 100 1000 10000Mean Recurrence Interval (years)

Predicted Wind Speed TS-498 Code Wind Speed

0

5

10

15

20

25

30

35N

10 2030

40

50

60

70

80

E

100

110

120

130

140150

160170S

190200210

220

230

240

250

260

W

280

290

300

310

320330

340 350

Extreme WindsCorresponding to a 50-year return period

0

5

10

15

20

25

30

35N

10 2030

40

50

60

70

80

E

100

110

120

130

140150

160170S

190200210

220

230

240

250

260

W

280

290

300

310

320330

340 350

Common WindsCorresponding to a 1-month return period

Page 13: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 14: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 15: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 16: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 17: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 18: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 19: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 20: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 21: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 22: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 23: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z
Page 24: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources

APP

OVERVIECLADD

A.1

A.1.1

RWDI'snaturaand specspireswaterrepresentScalingbetweensimulatedpredictexamupwindwater

Windfrom tany wThe w

It is psurroundTheseand/o

A.1.2

ThisPredictresistwindbuildingpressupressushortbasedsimultanean inst

1 W1984

2 LongIn

esources Resu

PPENDI

OVERVIEWCLADDING

Wind

Wind Tunnel Tes

RWDI's boundaal wind appspecially

es have beenr, to built

esent theng factors

between the eated in thecting theple, this

nd of ther in the distance.

directiontrue north.

wind directThe wind tunne

prudent toounding bu

These may incand/or lower lim

Measuremen

study addctions ofthe windpressureng with p

essure, theessures are

as 0.5 tobased on the

taneousnstrumented w

Wind speed p1984 with am

Longitudinalnternational

esults

NDIX A:

W OF WWIND LOADS

d Tunne

Wind Tunnel Tes

boundary layeapproachi

designedbeen selectedilt-up urban

most apps are alsoexpected

the wind tunneeffect of changesprocedursite, versusstance.

on is definedth. The test

ection to betunnel test is typ

o take stepsbuildings fonclude requmits on the

Measurement

addressesthese loads

nd loads. Thee study.pressureroot-meameasured

to 1 secondmeasuredpressures

umented wind tunne

profiles overamendments

turbulenceLondon, 1984

Canada

WIND

WIND TUNNELD LOADS

el Test a

Wind Tunnel Tests

r wind tung the mode

d turbulenceected to s

ban terrainappropriate

so introducedwind spe

tunnel. Thechangesre distingsus a sho

ed as theest mode

be simulats typically conducted fo

eps to ensufor shelte

equirementhe reduct

Techniques

the locaoads are r

The techThe bastaps tha

ean-squareed at each tapond at fulled upperes are alsotunnel stu

er terrain witto 1993.

ence intensities1984 with amend

anada | USA

ND TU

TUNNELD LOADS

t and Ana

unnel facilimodeled aence gene

simulaten. During

of theseoduced at thespeed andThe full-sca

in the eaguishes be

short fetch o

the directionmodel (study mode

ted by rotaty conducted fo

ensure thatter. Build

ements to teseduction that is

Techniques

l wind prequirednique thatis of the

that adequatee of pressu

each tap usingscale. The

level meanso recordeddy mode

th roughness

es over terraamendments

SA | UK |

NNEL

TUNNEL PROCEDURES

nalysis M

ility simularea by hav

generators, ofour bas

ng the tests,four bas

the analysturbulence

scale propeearth’s surfac

between theof suburban

on from whmodel andotating the

y conducted for 36 w

the safetyding codes

test with thes permitted c

ressuresin order

that is usedapproach

adequately coveessure fluctuatng a systeThe measu

mean dynamded for post

l is provided

hness changes

errain with roughness to 1993.

India | C

EL PRO

PROCEDURES

Methods

lates thehaving a longor spires,

basic terraintests, the upw

basic profiles,ysis stage

ence properoperties are

face roughnessthe flowsban terrai

which the wand surroundthe model to

36 wind direct

safety of a strcodes often conta

the moretted compa

that actthat the c

used to makeoach is to instcover the ex

uctuationssystem capabmeasured data

dynamic pressupost-test pr

ded in Figu

s for flat or h

oughness ch

China | H

ROCEDUR

PROCEDURES FOR

thods

mean speedong workat the u

n conditions,upwind pes, for direct

to accountrties, andderived us

oughness onows generated

in immed

wind blowsoundings) is

to the appections at 10°

ructure iscontain specsignificant

mpared to the code a

act on thecladding

make these pnstrumentxterior arand the

pable of responddata are conve

essure in therocessinggure 1.

hilly sites. It

hanges for

ong Kong

DURES

FOR TH

speed profking sectiupwind end.ons, rangrofile inections w

unt for remand the bas

using theon the planetaated by a

mmediately upw

ows in degrs mounted

appropriatet 10° interv

s not entirspecific pnt surrouhe code a

exteriorsystem credictions

nt a rigideas exposedpeak negat

esponding toconvertedhe wind tunneg if requir

em No. 8401

flat or hilly

| Singapore

ES

E PRE

ofile and tuon with a

end. Flooanging from

the windwith similamaining m

asic upwindESDU methodo

anetary boundauniform

upwind of the

grees measumounted on a tu

e angle invals.

rely deperovisionsnding bu

he code analytical

envelopecan be des

ns consistswind tunn

osed to wnegative and

to pressuinto pres

tunnel. Tred. A typ

84011, ESDU

y sites. Item

ngapore

Page

PREDICTION

turbulencea roughen

oor roughnessopen te

nd tunnel iar upwindminor diffe

nd flow condmethodology

boundary layeopen wate

the site w

measured cturntable,n the wind

dependent onns to addressbuildings removed

approach.

e of thedesigned tos of conduct

tunnel modewind. Theand peak

essure fluctuatessure coeffTime seriestypical examp

Internationa

m No. 84030

www.r

A1 of 3

ICTION OF

ence of theoughened floor

ghness andterrain, or

is set tod terrain.fferences

conditionsogy1, 2 forayer. For

water fetchwith open

lockwiseallowing

nd tunnel.

on specificess this.emoved,

oach.

building.to safely

conducting amodel of the

The meanpositive

uctuations ascoefficients

es of theample of

nal London,

030, ESDU

rwdi.comwdi.com

Page 25: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources

A.1.3

Carrypressulikelihdifferentlocal wcladdthe desrequirperiodsfactorsafety fact

Windwindtypicalocation,analyseachopenwind tunn

In ordeintegrthis integwindrecordedthroughpeakvalid p

The secondtermsmathematThe tload studand lsmoothrobust.

A.1.4

In strongbut areffect

3 Irw29

4 IrwAerodynam

esources Resu

Consider

ying out theessure coeff

hood of dent directwind climateing loads,

design liferements

ods of 50rs are app

safety factors, a

records takenclimate

cally usedon, typica

ysed to deteof 36 windterrain.

nd tunnel.

der to prrated withntegration.record isded wind

ough the wpressure

d peak responses fo

second methodms, this can

mathematicalime histostudies whelower qua

smoothing of eobust.

Internal P

ong winds,re usually

effect. Important

win, P.A., “29 (1988), pg

win, P.A. aAerodynamics

esults

Consideration o

the proceduoefficients ex

ifferent wections, the

mate to prads, it is app

fe of thethat consor 100 yea

applied. Fos, are used to

taken frommodel.to gener

cally providedeterminend sectorsThis coinc

redict theth the wind

on. In ones used to

nd speed andind speed

e is geneesponses fo

method iscan be thought

model ofstory method

where thequality reco

erratic behav

ernal Pressure All

nds, air leakagey of less stant sources

Pressure Modpg. 69-78.

and Sifton,cs, 77 & 78

Canada

ion of the Local Wi

edures dexpected fowind directe measurroduce pre

ppropriatee structur

consider theyears areFor Limit

used to repre

om one orIn areas

erate a betde an inathe probab

s at an upncides wit

the claddingnd climate

method,to determand direct

ed and dirrated. Then,

esponses for any des

the Upcrossought of aof the wind

thod (first mthe extent andecords RWDI

ehaviour of

essure Allow

akage effesignificances of ai

Model Techn

V. L., “Risk(1998), pg.

anada | USA

Local Win

describedfor a given w

ections andred pressuredicted pto conside

re. Theintended

re often useStates Dessent the u

r more locateas affectedbetter databanadequateobabilitiesupper leve

th the he

g wind lomate model.

the histoine the fu

ection andrection dat

Then, through any desired retu

ossing Methodas an anad statistics

method desand quality

RWDI typicaof the wind

wances Considering Localized Breac

ects dominance, are the

r leakage

Techniques for Cl

sk Considera. 715-723.

SA | UK |

nd Clima

in the prven wind diand the var

essure coeffpeak pressuder peak

choicentended use of

used for cDesign, re

ent the ultimate stat

ocations nead by hurr

database sincesampleof exceedl reference

height used

oads forThere a

storical (or sfull-scale

the winddata on anough the

eturn period a

Method asanalytical r

cs is useddescribed

ty of thecally revend statisti

Considering Localized Breac

nate the ithe operat

eakage include

Cladding Loads”

derations for

India | C

d Climate

revious sectrection.rying strengths

coefficients aessures as

loads assocof returnthe build

ladding desreturn peri

mate state load

near to therricanes once full sca

for statisteding vari

ence height, typd to measu

a givenare two methodssimulatedcladding

nd tunnelan hour-by

use of eod are dete

describedrepresentat

used in placeabove) iswind reco

everts to thecs to be

Considering Localized Breac

internal pation of mechan

ude uniforml

Loads”, Jour

Internal Pres

China | H

sections deteHowever

engths ofare integr

as a functiassociated

n periodding. Fodesign, toiods of 700ding.

e study sior typhoons,

scale measustical purposes.ious hou

ght, typicallyeasure the

return pemethods typ

ated as is theng wind pr

predictioby-hour bas

xtreme vae determined.

bed by Irwinesentation of

ace of thes typically

ecords perthe Upcross

more read

Considering Localized Breac

pressures.mechanica

ly distributed

rnal of Wind

Pressures”, Journa

ong Kong

determines, in orderwinds that

rated withon of retuwith retuwill be

For Allowato which app700 or 1700

ite are getyphoons, Monte

surementsposes. Trly mean

y taken toreference

period, thetypically used

the case wressuresns for tha

asis, a timevalue fitting

in3 and Irwthe firstdetailedy used byrmit it. Inossing Method

eadily imple

Considering Localized Breaches in

es. Other fcal ventilatiobuted sma

nd Engineeri

Journal of W

| Singapore

nes the peakr to accoun

that may beth statistica

eturn periodeturn periods

governedble Stressappropriat

1700 years,

enerally usMonte Carlo

ements, if avahe data iwind sp

o be 600 mence dynami

the wind tunused byith hurricanfor each

that directime historyng techniq

win and Smethod,wind recoy RWDI fo

In areas ofMethod sin

emented

es in the Building F

factors thation systems

small leakag

ing and Indu

Wind Engineer

ngapore

Page

peak localaccount for the

be expectedcal recordsod. In theods compa

ned by locaess Designate load os, without

used to deo simulatiilable forn either cas

peeds fromm (2000 ftc pressu

tunnel resuRWDI to

canes or typhoonseach hour, g

on. Byy of theques, stat

Sifton4. Iin which

ecords themsefor cladd

of shorternce it enaand is thus

uilding F

that influensystems and the

e paths

ndustrial Aerodynam

neering and

www.r

A2 of 3

externale varying

pected fromds of the

the case ofcomparable to

ocal codegn, returnor safety

thout load or

derive theions arer a givencase are

om withinft) abovere in the

esults areperform

typhoons)iven thesteppingresulting

statistically

n simplech a fitted

themselves.ing wind

r recordsenables athus more

açade

uence them,the stackover the

odynamics

and Industrial

rwdi.com

)

hem,

wdi.com

Page 26: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z

Reputation Resources

buildindue toThe intepotentDuringThererocks to

To evasimultanelocatedmeasugenerconsideUsingthat maoccurrareas)or foropenithe ex

For buwindows,an openconside

The ifailurescladddebris.

esources Resu

ng’s enveto airbornenternal pr

potential glassng a majoe are many

ocks to tree b

evaluate thetaneous

ocated on bumeasurements

rated atdered since

ng an in-housemay occurring. Lowe

eas), and higher buildingsng probabxternal pr

buildings thatows, the potentopening isderations of a nom

nternal pes due toing to thes.

esults

envelope andne debrisressure a

ass breakage,or storm

many typesranches. La

the internameasurements

building waements taken i

the cornence multi

house appoccur at selectedLower probab

gher probabngs that have

obabilities, interessures.

that usepotential fos also ve

ons of a nom

pressureto pressue provided

Canada

and larger lin a winds

allowanceeakage, the in

event, glof project

. Larger p

nal pressements arwalls than areas

ners of thple leaka

approach, theseected op

obabilities aobabilitieshave a lanternal pr

large missfor breakagevery low,

ons of a nominally se

allowancessure increa

ded wind loa

anada | USA

eakage paths.ndstorm and

wances can benternal compaass breakage

ectiles that projectiles

essures resure taken

that sharewhere la

he floor pkage sourceshese datapening locare usedare usedrge numberessures

ssile impaeakage dueow, and the

y sealed build

ces are apases causads will not

SA | UK |

paths. Theseand open doobe influencedcompartmentaeakage can

that typicallyes impacting th

esulting frduring thethe same

arge pressuplate. Aces tend

data are anacations andin lower w

used in highenumber of ope

are deter

mpact resistanto windbor

the internading.

applied tocaused by

not necessa

India | C

These largedoors or w

uenced by manytmentalizationcan be diffe

y cause gng the bu

rom domthe wind tunne

same interessure diffe

A single opto reduce

analyzed toand for awind speed

gher wind speedoperable wrmined fo

stant glazborne debrnal pressu

to help reducelocalized

necessarily prevent

China | H

ger leakagewindows,

many factoron of the

fferent sizesglass breakage,

building wou

ominant opentunnel testrnal volume.

fferencesopening

educe the magnto determinea range of

speed areasspeed area

windowsfor the same

ing everywheris is very

essures used

educe thezed breaches

event breakage

ong Kong

eakage pathsin cases

rs includinbuilding

zes and occueakage, raould be ra

openings itest betweenume. Ofcan occu(worst case

magnitudene the rangeof probab(i.e., – n

as (i.e., –or doors

same level of

ywhere, andy low. As

used are a

the possibilhes in theeakage du

| Singapore

include wcases where they

ng the sizand the

occur at vranging inare events.

n the bubetween pairs

Of particuoccur such as

ase) scenae of the iange of inbilities of

non-hurrican– hurricane/typhoons. Usingof risk as

and do nots a result,at or nea

lity of subsequente facade.ue to impact

ngapore

Page

window bthey are opeze and locatinternal vovarious locn size from

e events.

building enveof pressu

cular interas those

scenario isnternal pnternal pr

of these opencane/non-

cane/typhoonng these dom

that assumed

not have opethe probab

near the m

subsequentfacade. Design

mpact by wind

www.r

A3 of 3

breakageoperable.ocation ofvolumes.ocations.om small

envelope,essure taps

rest arethat aretypically

pressure.ressuresopenings-typhoon

cane/typhoon areas)dominant

assumed for

operableobability of

minimum

subsequent facaden of thend borne

rwdi.comwdi.com

Page 27: Draft Report – Tower A 2maslak1453yonetim.com/docs/wind-test/RUZGAR-TESTLERI-A2.pdfDESIGN WIND LOADS..... for Model Construction – Right Side Inside Front 2 – Roof Plan at Z