Upload
others
View
9
Download
0
Embed Size (px)
Citation preview
Dorot Fire ProtectionControl Valves
Ed
itio
n 0
2/20
17
Doro
t Fir
e P
rote
cti
on
Fire Protection Div.
Safety First!
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
2
General
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
Dorot, part of Matholding Group, is a leading manufacturer of fire protection hydraulic control valves.
Dorot Fire Protection Valves provide a reliable and comprehensive solution for all fire protection applications: from basic fire suppression systems to the most demanding fire protection applications. Dorot’s Fire Protection systems can be utilized in hazardous offshore and onshore locations, and/or corrosive environments such as refineries, platforms, FPSO’s, power generation plants etc.
Dorot offers a variety of water, foam and seawater fire protection valves for use in deluge, Pre-Action systems, pressure regulating, water level control, hydrants and monitors.
Dorot valves are made from a variety of materials such as Nickel-Aluminum-Bronze, Stainless Steel, Super Duplex, Bronze / Marine Bronze, Cast Steel and Ductile Iron.
Standard material valves such as Ductile Iron (ASTM A-536 65-45-12) and Cast Steel (WCB A-216) are coated as standard with zinc-enriched, high-build fusion-bonded epoxy (FBE) and a UV protective topcoat conforming to EN12944 C4 & C5 high & very high corrosion protection grades. Naval quality very high corrosion protection grade conforming to EN12944 C5M is available upon request. Other coating standards such as NORSOK or ANSI/NACE as well as coatings for special material valves such as austenitic Stainless Steel (CF8M/ASTM A-316) and Nickel Aluminum Bronze (ASTM B-148) can be supplied upon request.
F
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
Contents
Series 300 Basic Hydraulic Valves 4Series 100 Basic Hydraulic Valves 6Deluge Valve Range 8DE/HM Hydraulically Actuated Deluge Valve 8
DE/HRV Hydraulically Actuated, Anti-Columning Deluge Valve 8
DE/EL Electrically Actuated Remote Reset Deluge Valve 2/2 solenoid 9
DE/EL-MR Electrically Actuated Manual Reset Deluge Valve 2/2 solenoid 9
DE/RC Electrically Actuated Deluge Valve 3/2 solenoid 10
DE/RCL Electrically Actuated Manual Reset Deluge Valve 10
DE/RCE Electrically Actuated Manual Reset & Electric Remote Reset Deluge Valve 11
DE/EL(CN) Electrically Actuated Deluge Valve (Chinese standard) 11
DE/EL/HRV Electro-Hydraulically Actuated, Anti-Columning Deluge Valve 12
DE/PORV Pneumatically Actuated Deluge Valve 12
DE/EL/PORV Electro-Pneumatically Actuated Deluge Valve 13
DE/EL/PORV/DN Double-Interlock Pre-action, Electric-Pneumatic Release System 13
Pressure Reducing & Pressure Relief Valves 14PR/UL Pressure Reducing Valve 14
PS/UL Pressure Relief Valve 14
Local and Remote Actuated Monitor Valves 15MO/M Manually Actuated Monitor Valve 15
MO/RC Remote Hydraulic/Pneumatic Actuated Monitor Valve 15
MO/EL Electrically Actuated Monitor Valve 15
Water Level Control Valves 16FL Modulating Float Control Valve 16
FLEL Electric Float Control Valve 16
FLDI Differential Float Pilot Control Valve 17
AL Altitude Pilot Control Valve 17
Deluge Pressure Reducing Valve Range 18DE/HRV/PR Hydraulically actuated anti-columning Deluge Pressure Reducing Valve 18
DE/EL/HRV/PR Electrically or Hydraulically actuated Deluge Pressure Reducing Valve 18
DE/EL/PR Electrically actuated Deluge Pressure Reducing Valve 2/2 solenoid 19
DE/RC/PR Electrically actuated Deluge Pressure Reducing Valve 3/2 solenoid 19
DE/RCL/PR Electrically actuated Deluge Pressure Reducing Valve 3/2 solenoid 20
DE/PORV/PR Pneumatically actuated Deluge Pressure Reducing Valve 20
DE/EL/PORV/PR Electrically or Pneumatically actuated Deluge Pressure Reducing Valve 21
Hydrant Valve Range 21HY Hydraulic Hydrant Valve 21
HY/PR1 Hydraulic Pressure-Reducing Hydrant Valve 21
HY/PR2 Hydraulic Pressure-Reducing Hydrant Valve 21
Zero Pressure Foam Valve Range 22ZP/EL Foam Concentrate Electrically actuated Double chamber Control Valve 22
ZP/HM Slaved Hydraulic Pilot actuated Foam Concentrate Double chamber Control Valve 22
ZP/H Slaved Hydraulic actuated over the seat Foam Concentrate Double chamber Control Valve 23
3
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
4
Series 300 Basic Hydraulic Valves
Features• UL-listed with a wide range of control trims• Fast opening and soft closure operation• Drip-tight hermetic shut off to ANSI FCI 70-2• Simple and reliable design• Easy installation and maintenance• Double or single chamber• High-grade construction materials• Reliable pressure control from near zero
flow• Low pressure losses at high flow rates
Optional Features• Local or remote reset• Manual, Electric, Hydraulic, Pneumatic and
Pneu-electric UL-listed control trims• Explosion-proof, SIL redundant solenoids &
trim accesories• Sea water service
UL listingsThe valves are UL listed as “Fire Pump Relief Valves” (QXZQ.EX15231), ”Special Systems Water Control Valves” - Deluge (VLFT.EX15233) and “Special System Water Control Valves, Pressure-reducing and Pressure-control” (VLMT.EX15232) types. Consult the UL listing guide or contact Dorot for a complete list of approved applications and valve sizes (2”/ DN50 - 12”/ DN300)
SpecificationsSizes: Straight Flow 40-800 mm 11/2” - 32” Angle 40-200 mm 11/2” - 8”End Details:Flanged:ISO PN10, PN16 and PN25ANSI B16.42 class 150 & 300AS Tables D & E, JIS Additional options available upon requestThreaded:BSP or NPTGroovedPressure rating:250 psi for class # 150 375 psi for class # 300Temperature range: Water up to 80°C / 180°F max
MaterialsBody & Cover:Ductile Iron ASTM A-536Cast Steel ASTM A216 WCB or low temp. A352Stainless Steel CF8M, CF8Naval Bronze ASTM B61NAB Ni-Al-Bronze ASTM B148 C-95800Coating: UV Protected Fusion Bonded EpoxyOptional: Polyester, Halar & other coatings conforming to ISO-12944 C4, C5 & C5MMain valve trim: Stainless Steel & BronzeElastomers: Rubber, NR, NBR, EPDM, BUNA-NControl trim & Accesories: Brass, Bronze, SST Monel, Special Materials
* Additional materials & coatings available upon request
Dorot Series 300 are automatic, hydraulically actuated, diaphragm operated, globe and angle pattern control valves.The valves are designed for use in fire protection applications, including deluge, pre-action, pressure control, water, foam and seawater fire protection systems.The valves consist of three major components: the body, the cover, and the internal diaphragm assembly.
General DescriptionDorot UL listed basic untrimmed valve models: 30U, 30CU, 30AU
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
5
Series 300 Basic Hydraulic Valves
400 (16”)350 (14”)300 (12”)250 (10”)200 (8”)150 (6”)100 (4”)80 (3”)65 (21/2”)50 (2”)Valve Size
inchmminchmminchmminchmminchmminchmminchmminchmminchmminchmm
435/161100389/16980337/16850283/4730231/16600187/8480133/4350123/16310111/229291/16230FL
DIM
ENSI
ON
S
335/88552563525635201/2520153/83901333087/1624091/1623075/1618575/16185FH
3385024610246102152516415133309235720071707170W *
117/162901011/16272923081/1620563/4172.555/8142.545/16110315/1610035/892.531/482.5FR
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A87/16215TL
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A81/4209TH
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A27/1662TR
N/AN/AN/AN/AN/AN/AN/AN/A197/850516405111/16295913/16250N/AN/A83/16208AL
N/AN/AN/AN/AN/AN/AN/AN/A25635227/16570171/2445165/16415N/AN/A97/16240AH
N/AN/AN/AN/AN/AN/AN/AN/A1113/1630097/16240613/1617357/8150N/AN/A415/16125AB
N/AN/AN/AN/AN/AN/AN/AN/A143/16N/A71/16180513/1614757/16138N/AN/A43/16107AR
50 / 13.218.6 / 4.918.6 / 4.99.7 / 2.64.3 / 1.11.5 / 0.40.7 / 0.180.3 / 0.080.1 / 0.030.1 / 0.03Vol. Control Chamber lit./gal.
822 / 1810510 / 1123405 / 892245 / 540157 / 34680 / 17637 / 8222 / 4813 / 2912 / 26Weight kg/lbs
* Valve Width
Dimensions and Weights
Principle of Operation
FH
FL
W
AH
AR
AL
TH
TR
TL
FR
AB
FH
FL
W
AH
AR
AL
TH
TR
TL
FR
AB
FH
FL
W
AH
AR
AL
TH
TR
TL
FR
AB
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
6
Series 100 Basic Hydraulic Valves
Features• UL-listed with a wide range of control trims• Fast opening and soft closure operation• Drip-tight hermetic shut off to ANSI FCI 70-2• Simple and reliable design• Easy installation and maintenance• High-grade construction materials• Reliable pressure control from near zero flow• Exceptionally low pressure losses
Optional Features• Latched opening or remote reset• Manual, Electric, Hydraulic, Pneumatic and
Pneu-electric UL-listed control trims• Explosion-proof, SIL redundant solenoids &
trim accesories• Sea water service
UL listingsThe valves are UL listed as “Fire Pump Relief Valves” (QXZQ.EX15231), ”Special Systems Water Control Valves” - Deluge (VLFT.EX15233) and “Special System Water Control Valves, Pressure-reducing and Pressure-control” (VLMT.EX15232) types. Consult the UL listing guide or contact Dorot for a complete list of approved applications and valve sizes (2”/ DN50 - 10”/ DN250)
SpecificationsSizesStraight Flow 20-600 mm / 3/4” - 24” Angle 40-150 mm / 11/2” - 6”End Details:Flanged:ISO PN10, PN16 and PN25ANSI B16.42 class 150, 250 & 300AS Tables D & E, JIS Additional options available upon requestThreaded:BSP or NPTGroovedPressure rating:250 psi for class # 150 375 psi for class # 300Temperature range: Water up to 80°C / 180°F max
MaterialsBody & Cover:Ductile Iron ASTM A-536Cast Steel ASTM A216 WCB or low temp. A352Stainless Steel CF8M, CF8Naval Bronze ASTM B61NAB Ni-Al-Bronze ASTM B148 C-95800Coating: UV Protected Fusion Bonded EpoxyOptional: Polyester, Halar & other coatings conforming to ISO-12944 C4, C5 & C5MMain valve trim: Stainless Steel & BronzeElastomers: Rubber, NR, NBR, EPDM, BUNA-NControl trim & Accesories: Brass, Bronze, SST Monel, Special Materials
* Additional materials & coatings available upon request
Dorot Series 100 valves are automatic, hydraulically actuated, direct diaphragm sealing weir / globe type valves with proven and reliable design.The valves are designed for use in fire protection applications including deluge, pre-action, pressure control, water, foam and seawater fire protection systems.The valves consist of three major components: body, cover and diaphragm.The only moving part is the diaphragm.
* Pictures of models 44 & 77 are not shown in this page
General DescriptionDorot UL listed basic untrimmed valve models: 68, 44*, 77*
Model 68
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
7
Series 100 Basic Hydraulic Valves
450 (18”)400 (16”)350 (14”)300 (12”)250 (10”)200 (8”)150 (6”)100 (4”)80 (3”)50 (2”)Valve Size
inchmminchmminchmminchmminchmminchmminchmminchmminchmminchmm
435/161100389/169802213/165802213/1658021535181/8460155/1639012305113/16285713/16200L
77
DIM
ENSI
ON
S
493/16125039990193/8495193/8495171/24451511/16400125/163149230713/1620061/2166H
3385024610105/827093/8240820565/8170511/1614545/1611041/810535/1685R
2213/16580201/2520215/16540195/16490175/16440143/83651113/163009230713/1620061/2166W *
N/AN/A172 / 379167 / 368125 / 27686 / 19049 / 10824 / 5318.2 / 40.17.7 / 17Approx. Weight kg/lbs
281/8715281/8715N/AN/AN/AN/A256362013/16530171/843614356123/1631087/8228L
68
325/8830325/8830N/AN/AN/AN/A211/2546187/84811413/16378105/1626395/1623765/8169H
135/16340123/16310N/AN/AN/AN/A83/8215718057/8150411/1612041/810535/1685R
325/8830325/8830N/AN/AN/AN/A193/84951511/16400125/8320103/16260713/1620067/8175W *
460 / 1014433 / 955N/AN/A190 / 419123 / 27175 / 165.338 / 83.830 / 66.110 / 22Approx. Weight kg/lbs
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A123/831673/8188TL
44
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A55/1613541/2115TH
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A25315/842TR
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A713/1620043/8112W
N/AN/AN/AN/AN/AN/AN/AN/A11 / 243.2 / 7Approx. Weight kg/lbs
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A92307180613/16174N/AN/AAL
82
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A153801113/1630011278N/AN/AAH
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A33/168225/1660113/1647N/AN/AAR
N/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/AN/A1113/163009230713/16200N/AN/AW
N/AN/AN/AN/AN/AN/A45 / 99.221 / 46.218 / 39.6N/AApprox. Weight kg/lbs
* Valve Width
Principle of Operation
Dimensions and Weights
77/68 82 44
H
L
W
AH
AR
AL
THTR
TL
R
H
L
W
AH
AR
AL
THTR
TL
R
H
L
W
AH
AR
AL
THTR
TL
R
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
8
Deluge Valve Range
DE/HMHydraulically Actuated Deluge Valve
Hydraulic pilot actuated control valveThe valve maintains a closed position and instantly opens upon a hydraulic pressure drop in a pressurized sprinkler sensor line, limited to 7m above the valve or by manual emergency actuation.
Features:• UL certified• Simple structure• Remote reset - optional manual reset• Optional pressure reducing function
Applicable for:• Deluge• Single-Interlock Pre-Action• Water, Sea water and Foam
DE/HRVHydraulically Actuated, Anti-Columning Deluge Valve
Hydraulic pilot actuated control valveThe valve maintains a closed position and instantly opens upon a hydraulic pressure drop in a pressurized sprinkler system or by manual emergency actuation.
Features:• Simple structure• Remote reset - optional manual reset• The application is based on the UL listed valves• Optional pressure reducing function
Applicable for:• Deluge• Single-Interlock Pre-Action• Water, Sea water and Foam
30U-DE/HM
68-DE/HM
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
30U-DE/HRV
68-DE/HRV
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
9
Deluge Valve Range
DE/ELElectrically Actuated Remote Reset Deluge Valve 2/2 solenoid
Electric solenoid actuated control valveThe valve maintains a closed position and instantly opens by energizing a solenoid valve.
Features:• UL certified• Simple structure• Remote reset - optional manual reset (see DE/EL-MR)• Optional pressure reducing function
Applicable for:• Deluge• Single or double Interlock Pre-Action• Water, Sea water and Foam
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
30U-DE/EL
68-DE/EL
DE/EL-MRElectrically Actuated Manual Reset Deluge Valve 2/2 solenoid
Electric solenoid actuated control valveThe valve maintains a closed position and instantly opens by energizing a solenoid valve.
Features:• UL certified• Simple structure• Manual (local) reset• Optional pressure reducing function
Applicable for:• Deluge• Single or double Interlock Pre-Action• Water, Sea water and Foam
30U-DE/EL-MR
68-DE/EL-MR
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
10
DE/RCElectrically Actuated Deluge Valve 3/2 Solenoid
Electrically actuated, remote reset deluge valveThe valve maintains a closed position and instantly opens by energizing a solenoid valve or by manual emergency actuation.
Features:• UL certified• Simple structure• Remote reset - optional manual reset• Optional pressure reducing function
Applicable for:• Deluge• Single or double Interlock Pre-Action• Water, Sea water and Foam
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
30U-DE/RC
68-DE/RC
DE/RCLElectrically Actuated Manual Reset Deluge Valve
Electrically actuated, manual reset deluge valveThe valve maintains a closed position and instantly opens by energizing a solenoid valve or by manual emergency actuation. The valve will close only after a manual reset is activated.
Features:• UL certified• Simple structure• Latching operation• Optional pressure reducing function
Applicable for:• Deluge• Single or double Interlock Pre-Action• Water, Sea water and Foam
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
30U-DE/RCL
68-DE/RCL
Deluge Valve Range
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
11
DE/RCEElectrically Actuated, Latching Type, Manual Reset & Electric Remote Reset Deluge Valve
Electrically actuated, latching type, manual reset & electric remote reset deluge valveThe valve maintains a closed position and opens when the ‘Open’ solenoid valve is energized or by manual emergency actuation. The valve will be remotely closed by energizing the ‘Close’ solenoid valve or by manually pressing the RCE relay reset knob.
Features:• UL certified• Simple structure• Latching operation• Optional pressure reducing function
Applicable for:• Deluge• Single or double Interlock Pre-Action• Water, Sea water and Foam
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
30U-DE/RCE
68-DE/RCE
DE/EL(CN)Electrically Actuated Deluge Valve (Chinese standard)
Electrically actuated, manual reset deluge valveThe valve maintains a closed position and instantly opens by energizing a solenoid valve or by manual emergency actuation. The valve will close only after a manual reset is activated.
Features:• Chinese standard certified• Simple structure• Manual local reset• Optional pressure reducing function
Applicable for:• Deluge• Single-Interlock Pre-Action• Water, Sea water and Foam
68-DE/EL (CN)
68-DE/EL (CN)
F
Deluge Valve Range
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
12
DE/PORVPneumatically Actuated Deluge Valve
Pneumatic actuated deluge valve.The valve maintains a closed position and instantly opens upon an air/gas pressure drop in a pressurized sprinkler system or by manual emergency actuation
Features:• UL certified• Simple structure• Remote reset - optional manual reset• Optional pressure reducing function
Applicable for:• Deluge• Dry pipe• Single-Interlock Pre-Action• Water, Sea water and Foam
DE/EL/HRVElectro-Hydraulically Actuated, Anti-Columning Deluge Valve
Electrically and/or Hydraulically actuated control valveThe valve maintains a closed position and instantly opens upon an hydraulic pressure drop in a pressurized sprinkler system or by energizing a solenoid valve or by manual emergency actuation.
Features:• UL certified• Simple structure• Remote reset - optional manual reset• Optional pressure reducing function
Applicable for:• Deluge• Single-Interlock Pre-Action• Water, Sea water and Foam
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
68-DE/EL/HRV
30U-DE/PORV
68-DE/PORV
Deluge Valve Range
30U-DE/EL/ HRV
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
13
DE/EL/PORVElectro-Pneumatically Actuated Deluge Valve
Electrically and/or Pneumatically actuated control valveThe valve maintains a closed position and instantly opens upon an air/gas pressure drop in a pressurized sprinkler system or by energizing a solenoid valve or manual emergency actuation.
Features:• UL certified• Simple structure• Remote reset - optional manual reset• Optional pressure reducing function
Applicable for:• Deluge• Dry pipe• Non-Interlock, Single-Interlock Pre-Action• Water, Sea water and Foam
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
30U-DE/EL/PORV
68-DE/EL/PORV
DE/EL/PORV/DNDouble-Interlock Pre-action, Electric-Pneumatic Release System
Pneumatically and Electrically actuated control valveThe valve maintains a closed position and instantly opens upon an air/gas pressure drop in a pressurized sprinkler system and by simultaneously energizing a solenoid valve, or manual emergency activation
Features:• UL certified• Simple structure• Remote reset - optional manual reset• Optional pressure reducing function
Applicable for:• Double-Interlock Pre-Action• Water, Sea water and Foam
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
30U-DE/EL/PORV/DN
68-DE/EL/PORV/DN
Deluge Valve Range
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
14
PR/ULPressure Reducing Valve
Hydraulic pressure-reducing valveThe valve maintains a preset fixed downstream pressure, regardless of upstream pressure or flow fluctuations.
Pressure rating, adjustment range & features:• UL Listed pressure rating/maximum upstream pressure (psi)
Class 150 (ISO PN16) - 175-250psi Class 300 (ISO PN25) - 375psi
• UL listed downstream Pressure adjustment range under VLMT EX.15232 & VLMT EX.xxxxx file (consult) Class 150 (ISO PN16) 30-165 psi Class 300 (ISO PN25) 30-165 psi
• Combination Deluge Pressure reducing valves Class 150 (ISO PN16) & Class 300 (ISO PN25) 50-300 psi
• Other / Optional Pressure adjustment range: 15-360 psi • Reliable pressure control from near zero flow to full flow with
no need for additional throttling plug or by-pass valves• Exhibits the same low pressure losses as in the basic valve• Simple structure
Applicable for:• Water, Sea water and Foam
PS/ULPressure Relief Valve
Hydraulic pressure relief valveThe valve maintains a steady preset upstream pressure. Should the upstream pressure exceed the required set point, the valve opens, releasing excessive pressure. When the pressure falls below the preset level, the valve closes drip tight.
Pressure rating, adjustment range & features:• UL listed pressure rating/maximum pressure (psi)
Class 150 (ISO PN16) - 250 psi max. Class 300 (ISO PN25) - 375 psi max
• UL listed maximum relief pressure (psi): Class 150 (ISO PN16) - 175 psi & 205 psi Class 300 (ISO PN25) - 375 psi
• Reliable pressure control from near zero flow to full flow with no need for additional throttling plug or by-pass valves
• Exhibits the same low pressure losses as in the basic valve• Simple structure
Applicable for:• Water, Sea water and Foam
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
30-PR/UL
Pressure Reducing & Pressure Relief Valves
30-PS/UL
77-PS/UL
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
15
Local and Remote Actuated Monitor Valves
MO/MManually Actuated Monitor Valve
The valve is manually actuated by a selector valve which allows the user to open or close the valve quickly and effortlessly, even under high pressure conditions.
Features:• Effortless open/close actuation• Fast response• Simple and reliable design• Easy installation and maintenance• The application is based on the UL listed valves
MO/RCRemote Hydraulic/Pneumatic Actuated Monitor Valve
A 3-way relay valve, actuated by hydraulic or pneumatic pressure command, which opens or closes the main valve. The standard valve is supplied in the “normally closed” position. The “normally open” position is optional.
Features:• Fast response, even for long control lines• Simple and reliable design• Easy installation and maintenance• The application is based on the UL listed valves
MO/ELElectrically Actuated Monitor Valve
The valve is electrically actuated by a 3-way solenoid valve which remotely opens and closes the valve.
Features:• Low power electric actuation• Simple and reliable design• Easy installation and maintenance• The application is based on the UL listed valves
77-MO-M
77-MO-RC
77-MO-EL
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
16
Water Level Control Valves
FLModulating Float Control Valve
The main valve is controlled by a float assembly, located in the tank or reservoir and set to the required maximum water level. The valve constantly maintains the maximum level.
Features:• Accurate level control• Simple and reliable design• Easy installation and maintenance• The application is based on the UL listed valves
FLELElectric Float Control Valve
The main valve is actuated by a 3-way solenoid to an electric sensor float, located in the tank/reservoir. The sensor provides open and close commands to the solenoid valve. The main valve fully opens and closes drip tight upon command, when the solenoid is de-energized, thus enabling accurate and reliable differential level control. Optional Addition: dinamic surge-preventing closing.
Features:• Accurate differential level control• Low power electric actuation• Fast response• Simple and reliable design • Easy installation and maintenance• The application is based on the UL listed valves
30-FL
68-FL
30-FLEL
68-FLEL
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
17
Water Level Control Valves
FLDIDifferential Float Pilot Control Valve
The main valve is controlled by a float assembly, closing it when the water reaches maximum level, and opening it when the water drops to its preset minimum level. The differential between the maximum and the minimum levels is adjustable.Optional addition: dynamic, surge preventing shutoff.
Features:• Accurate differential level control• Adjustable differential• Fast response• Simple and reliable design • Easy installation and maintenance• The application is based on the UL listed valves
ALAltitude Pilot Control Valve
The main valve is actuated by a highly sensitive altitude pilot, located outside the tank. The pilot opens or closes the valve in response to the static pressure of the water. The pilot allows for differential adjustments between the maximum and minimum level.Optional addition: dynamic, surge preventing shutoff.
Features:• Accurate differential level control• Fast response• Easy access - no float is located in the tank\reservoir• Simple and reliable design • Easy installation and maintenance• The application is based on the UL listed valves
30-FLDI
68-FLDI
30-AL
68-AL
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
18
Deluge Pressure Reducing Valve Range
DE/HRV/PRHydraulically actuated anti-columning Deluge Pressure Reducing Valve
Hydraulically activated, Pilot-controlled Deluge/Pre-Action Pressure Reducing valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when the hydraulic pressure drops in a pressurized sensor line, tripping a hydraulic relay. When tripped, the valve regulates to a steady, preset downstream pressure, regardless of upstream pressure or flow rate fluctuations. An emergency manual release valve is fitted as standard.
Features:• UL certified• Simple structure• Easy installation and maintenance• Remote reset - optional manual reset (DE/HRV/PR-MR)
Applicable for:• Deluge or Single-Interlock Pre-Action type valves• Dry pipe• Water, Sea water and Foam
30U-DE/HRV/PR
DE/EL/HRV/PRElectrically or Hydraulically actuated Deluge Pressure Reducing Valve
Electrically or Hydraulically, Pilot-controlled Deluge/Pre-Action Pressure Reducing valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when the hydraulic pressure drops in a water pressurized sensor line, releasing a hydraulic relay, or by an electric command. When tripped, the valve regulates to a steady, preset downstream pressure, regardless of upstream pressure or flow rate fluctuations. An emergency manual release valve is fitted as standard.
Features:• UL certified• Simple structure• Easy installation and maintenance• Remote reset - optional manual reset (DE/EL/HRV/PR-MR)
Applicable for:• Deluge or Single-Interlock Pre-Action type valves• Dry pipe• Water, Sea water and Foam
30U-DE/EL/HRV/PR
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
19
DE/EL/PRElectrically actuated Deluge Pressure Reducing Valve 2/2 solenoid
Electrically-controlled Deluge/Pre-Action Pressure Reducing valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when a 2w solenoid-valve is energized. When tripped, the valve regulates to a steady, preset downstream pressure, regardless of upstream pressure or flow rate fluctuations. It closes drip-tight when the solenoid-valve is de-energized. An emergency manual release valve is fitted as standard.
Features:• UL certified• Simple structure• Easy installation and maintenance• Remote reset - optional manual reset (DE/EL/PR-MR)
Applicable for:• Deluge or Single-Interlock Pre-Action type valves• Dry pipe• Water, Sea water and Foam
30U-DE/EL/PR
DE/RC/PRElectrically actuated Deluge Pressure Reducing Valve 3/2 solenoid
Electrically-controlled Deluge/Pre-Action Pressure Reducing valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when a 3w solenoid-valve is energized. When tripped, the valve regulates to a steady, preset downstream pressure, regardless of upstream pressure or flow rate fluctuations. It closes drip-tight when the solenoid-valve is de-energized. An emergency manual release valve is fitted as standard.
Features:• UL certified• Simple structure• Easy installation and maintenance• Remote reset - optional manual reset (DE/RC/PR-MR)
Applicable for:• Deluge or Single-Interlock Pre-Action type valves• Dry pipe• Water, Sea water and Foam
30U-DE/RC/PR
Deluge Pressure Reducing Valve RangeCAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
20
Deluge Pressure Reducing Valve Range
DE/RCL/PRElectrically actuated Deluge Pressure Reducing Valve 3/2 solenoid
Electrically-controlled Deluge/Pre-Action Pressure Reducing, Manual Reset valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when a 3w solenoid-valve is energized. The valve must be manually reset following automatic activation using the RCL relay’s knob. When tripped, the valve regulates to a steady, preset downstream pressure, regardless of upstream pressure or flow rate fluctuations. An emergency manual release valve is fitted as standard.
Features:• UL certified• Simple structure• Easy installation and maintenance• Manual reset
Applicable for:• Deluge or Single-Interlock Pre-Action type valves• Dry pipe• Water, Sea water and Foam
30U-DE/RCL/PR
DE/PORV/PRPneumatically actuated Deluge Pressure Reducing Valve
Pneumatically-Activated, Pilot-controlled Deluge/Pre-Action Pressure Reducing valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when the pneumatic pressure drops in a gas pressurized sensor line, tripping a hydraulic relay. When tripped, the valve regulates to a steady, preset downstream pressure, regardless of upstream pressure or flow rate fluctuations. An emergency manual release valve is fitted as standard.
Features:• UL certified• Simple structure• Easy installation and maintenance• Remote reset - optional manual reset (DE/PORV/PR-MR)
Applicable for:• Deluge or Single-Interlock Pre-Action type valves• Dry pipe• Water, Sea water and Foam
30U-DE/PORV/PR
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
21
DE/EL/PORV/PRElectrically or Pneumatically actuated Deluge Pressure Reducing Valve
Electrically or Pneumatically, Pilot-controlled Deluge/Pre-Action Pressure Reducing valve, actuated by the pipeline pressure. The valve is closed in its normal, set position and opens when the pneumatic pressure drops in a gas pressurized sensor line, releasing a hydraulic relay, or by an electric command. When tripped, the valve regulates to a steady, preset downstream pressure, regardless of upstream pressure or flow rate fluctuations. An emergency manual release valve is fitted as standard.
Features:• UL certified• Simple structure• Easy installation and maintenance• Remote reset - optional manual reset (DE/EL/PORV/PR-MR)
Applicable for:• Deluge or Single-Interlock Pre-Action type valves• Dry pipe• Water, Sea water and Foam
30U-DE/EL/PORV/PR
HY
HYHydraulic Hydrant ValveThe valve is manually actuated by a selector valve which allows the user to open or close the valve quickly and effortlessly, even under high pressure conditions. Opening and closing speed are controlled by an in-line orifice.
HY/PR1Hydraulic Pressure-Reducing Hydrant ValveThe valve is manually actuated, allowing the user to open or close the valve quickly and effortlessly, even under high pressure conditions. Opening and closing rates are regulated by in-line orifices and pressure is limited to a preset level.
HY/PR2Hydraulic Pressure-Reducing Hydrant ValveThe valve is manually actuated by a selector valve which allows the user to open or close the valve quickly and effortlessly, even under high pressure conditions. Downstream pressure is dynamically determined using an adjustable set point pilot valve.
Features:• Effortless open/close actuation• Controlled response• Simple and reliable design• Easy installation and maintenance
Deluge Pressure Reducing & Hydrant Valve Range
HY/PR1
HY/PR2
CAMERA-READY LOGOTYPE FOR TYPE L AND TYPE R LISTING MARKSThese Marks are registered by Underwriters Laboratories Inc.
The minimum height of the registered trademark symbol ® shall be 3/64 of an inch. When the overall diameter of the UL Mark is less than 3/8 of an inch, the trademark symbol may be omitted if it is not legible to the naked eye.
The font for all letter forms is Helvetica Condensed Black, except for the trademark symbol ®, which isHelvetica Condensed Medium. No other fonts are acceptable.
Please Note:The word "MARINE" should only be used for UL Classified marine products.
200-195D 20M/11/97
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
22
Zero Pressure Foam Valve Range
ZP/ELZero Pressure Foam Concentrate Electrically actuated Double chamber Control Valve
The valve is installed downstream of the foam concentrate tank and is closed in its normal set position by the master’s main line pressure.When the valve´s 3/2 solenoid is actuated it allows the valve to be forced open by the upstream pressure of its master’s valve water mains. This allows the foam concentrate valve to open even with zero upstream line pressure, ensuring fail safe supply of foam concentrate through the foam proportioner, downstream of the main master valve.
ZP/HMSlaved Hydraulic Pilot actuated Zero Pressure Foam Concentrate Double chamber Control Valve
The valve is installed downstream of the foam concentrate tank and is closed in its normal set position by the master’s main line pressure. The slave valve is forced open through the pilot valve by the upstream pressure of its master’s valve water mains. This allows the foam concentrate valve to open even with zero upstream line pressure, ensuring fail safe supply of foam concentrate through the foam proportioner, downstream of the main master valve.
30U-ZP/EL
30U-ZP/HM
Features:• Electrically select either water only or
foam operation through the system• Full St. St. construction• Double chamber zero pressure
operated by deluge water mains• Electric remote actuation and remote
reset, manual emergency actuation• The application is based on
UL listed Valves
Applicable for:• Control of water & seawater, AFFF
concentrate foam systems
Features:• Full St. St. construction• Double-chamber, zero-pressure,
fail-safe operation by its master valve’s water mains
• Electric remote actuation and remote reset including local manual emergency actuation
• The application is based on UL listed valves
Applicable for:• Control of water & seawater, AFFF
concentrate foam systems
Dorot Fire Protection
Edition 02/2017
Fire Protection Div.
23
Zero Pressure Foam Valve Range
ZP/HZero-Pressure, Foam-Concentrate, Over-the-Seat Hydraulic-Actuated, Double-Chamber, Hydraulic Control Slave Valve
The valve is installed downstream of the foam concentrate holding tank and is closed in its normal, set position. The slave valve is forced open by its master valve’s downstream pressure rise when it opens. This allows the foam concentrate valve to open even with zero upstream line pressure, ensuring fail safe supply of foam concentrate through the foam proportioner downstream of the main master valve.
30U-ZP/HFeatures:• Full St. St. construction• Double-chamber, zero-pressure,
fail-safe operation by its master valve’s water mains
• Electric remote actuation and remote reset including local manual emergency actuation
• The application is based on UL listed valves
Applicable for:• Control of water & seawater, AFFF
concentrate foam systems
ReliabilityReliability
Innovation
ExpertiseInnovation
Expertise
Fire Protection Div.
Via Carlo Dell’Acqua, 7 • 20027 Rescaldina MI [email protected] • www.dorot.com • C.F./P.I. 02211910027
www.dorot.comHundreds of companies in the industrial, civil engineering, municipal and agricultural segments around the world have chosen DOROT’s innovative and field-proven technologies. Since its establishment in 1946, DOROT leads the hydraulic control valves market with continued innovation, uncompromising excellence and firm commitment to its customers, consulting and supporting them through all stages of a project and overcoming challenges in R&D, design, implementation, and maintenance.