4

Click here to load reader

Domestic Water/Space Heating Multiple Boiler Controlleraerco.com/.../document/KCBoilerCombinationControlPanelGuide.pdf · COMBINATION CONTROL PANEL MODEL CCP Domestic Water/Space

Embed Size (px)

Citation preview

Page 1: Domestic Water/Space Heating Multiple Boiler Controlleraerco.com/.../document/KCBoilerCombinationControlPanelGuide.pdf · COMBINATION CONTROL PANEL MODEL CCP Domestic Water/Space

COMBINATION CONTROL PANELMODEL CCP

Domestic Water/Space HeatingMultiple Boiler Controller

Concept

AERCO International recommends individual KC waterheating and space heating systems wherever possible.Individual water heaters and boilers achieve maximumefficiency and precise temperature control. However,when factors such as existing indirect storage waterheaters, restricted fuel input, or space limitations areconditions to be met, AERCO KC Boilers can be used in adual service role.

Combination System Description

In order to accommodate the requirements for both spaceheating and the production of domestic hot water, multipleKC style boilers can be used in a combination spaceheating and domestic water heating plant. Boiler modulesare piped in a multiple boiler arrangement as they wouldbe in a multiple unit space heating plant. See CombinationBoiler Plant Sizing section for recommendations on num-ber of modules required. The necessary number of mod-ules for domestic water production are isolated from theheating system in the supply piping by means of a nor-mally closed two way motorized valve. An external hotwater storage generator is used to convert boiler water toproduce potable water through a closed loop coil. Upondemand for domestic water, the isolated (combinationduty) boilers produce a constant temperature supply(70.220F) by operating in the internal setpoint mode.

The AERCO Combination Control Panel (CCP) is anaccessory panel designed to work in conjunction with anAERCO Model 168 Boiler Management System (BMS) tocontrol the firing of the combination boiler modules andthe associated accessories for domestic water production.The CCP panel allows operation of the combination boilermodules to produce domestic water through the externalgenerator coil, and activates the circulating pump betweenthe boilers and the coil. The CCP uses a simple tankaquastat to start domestic water production. It allowscontrol of up to four KC Boilers (Boiler Control Code -6) inthe constant set point mode, and allows a transfer of themotorized valve and the control of the modules to theBMS when the space heating requires their added input.

By utilizing a CCP Panel in tandem with a Model 168Boiler Management System, the KC Boilers efficiency willbe maximized. Only the required energy (input) for

domestic water will be used, and the heating plant canoperate at lowest required temperatures for space heatingto maximize condensing efficiency.

Domestic Water Mode

The tank aquastat, or domestic water demand device, iswired to the CCP to signal a demand for domestic water.The CCP supplies 12VDC to the dry contacts of thedomestic water demand device (aquastat). Upon ademand for domestic water, the CCP enables the com-bination boiler modules to begin firing to their internalsetpoint temperature. Each module will automaticallymodulate its input to meet the requirement of domesticwater production. The closed motorized valve isolates thenormally higher temperature boiler water from the heatingsystem. The circulating pump between the combinationmodules and the coil is activated simultaneously with thecombination modules. The boilers and pump will operatecontinually until the domestic water aquastat is satisfied.

Heating Mode

The Boiler Management System (BMS) will activate theheating plant and sequence/modulate the heating-onlyboilers in the selected mode. When all dedicated heatingmodules are operating at 100% input, the BMS will closethe Auxiliary contacts wired to the CCP Panel. The CCPwill then activate the motorized valve to open pipingbetween the heating system loop and the combinationboiler loop. The CCP supplies line voltage (120/1/60)directly to the valve operator. The valve must be a threewire control type with power open/power closed operator.Operator timing on motorized valves should be in the 8 to45 second range, and must be equipped with a dry con-tact SPST N.O. end switch. When the valve reaches thefull open position, the dry contact end switch of the valvewill close, signaling the supply piping between the heat-ing-only and combination boilers is open. This transferscontrol of the combination modules percentage of firinginput to the BMS. The BMS will then add the combinationmodules to the heating system, and modulate them totheir required input level. The boiler modules will besequenced at the adjusted percentage as set in the BMS.As the added input from the combination modules allowthe heating load (setpoint) to satisfy, the auxiliary contactsof the BMS will open. The motorized valve will then be

Page 2: Domestic Water/Space Heating Multiple Boiler Controlleraerco.com/.../document/KCBoilerCombinationControlPanelGuide.pdf · COMBINATION CONTROL PANEL MODEL CCP Domestic Water/Space

driven closed by the CCP Panel. The combination boilerswill be de-activated until needed either for domestic wateror for heating again. If domestic water is called for whilethe valve is open for heating the CCP will automaticallyclose the motorized valve and transfer the control of thecombination modules back to domestic water production.

Combination Plant Sizing

The required size of a combination boiler plant is notnecessarily the simple sum of the heating modules andthe domestic water modules. ASHRAE has documentedand developed a method of sizing combination plantsbased on the diversity of the loads. ASHRAE Systems1984 Handbook published a researched method of estab-lishing a relationship of domestic water load to heatingload, and a table of recommended percentage of addi-tional BTUH to be added to the heating plant to handleboth loads.

Simply expressed,

Domestic Water Load = Diversity FactorHeating Load

The diversity factor is then converted to a percentageincrease in the base heating load plant from Table A.

DiversityFactor

DomesticHeating %Load to beadded toHeatingBoiler

2

60%

Table A

1 .8

50% 40%

.6 .5 .4 .3

30% 20% 10% 0%

Example -

From conventional calculations on a typical design:

Space Heating Load = 2840 MBHDomestic Water Load = 1705 MBHDivers i ty =Factor

1705 MBH = .602 8 4 0 M B H

From Table A, a diversity factor of .60 indicates a mini-mum of 30% of the domestic water heating load require-ment should be added to the heating load for Total BoilerPlant Capacity.

Total Plant Capacity =2840 MBH + (.30X 1705 MBH) = 3352 MBH

Total LoadOutput/Boiler

= 3352 MBH Output = 4KC Boilers870 MBH/Boiler

Component Design

Domestic water sizing for a combination plant should bedone in accordance with ASHRAE and ASPE standards.The storage tank size should be adequate for smalldomestic water draws without short cycling the domestictank aquastat. The combination of recovery and storageshould be as prescribed in the ASHRAE/ASPE methods.

The recovery of the storage tank coil exchanger shouldbe based on a temperature drop of 2OF, or the sametemperature drop as the heating system that the plantsupplies. When sizing the circulating pump between thecombination boiler(s) and the tank coil, the flow of thepump must be greater than the minimum module flow of25 gpm per module. The head of the pump must becapable of overcoming the pressure drop of the boilers,the tank coil, and the frictional resistance of all piping/accessories between them. Air elimination and expansionaccessories may be required in the coil loop as well as themain heating loop.

Page 3: Domestic Water/Space Heating Multiple Boiler Controlleraerco.com/.../document/KCBoilerCombinationControlPanelGuide.pdf · COMBINATION CONTROL PANEL MODEL CCP Domestic Water/Space

Recommended Piping and Wiring Details

Figure 1 -- Four Boiler Combination Plant Piping

Figure 2 -- Four Boiler Combination Plant Wiring

Page 4: Domestic Water/Space Heating Multiple Boiler Controlleraerco.com/.../document/KCBoilerCombinationControlPanelGuide.pdf · COMBINATION CONTROL PANEL MODEL CCP Domestic Water/Space

Sequence of Operation

The four KC Boiler Combination plant shown in Figures 1and 2 is typical of plant piping and wiring arrangements.The KC boilers dedicated for heating-only must beordered for Control Mode -5 for BMS mode operation.The boilers for combination duty must be ordered forCombination Mode -6. The Combination mode boilersinternal setpoint should be adjusted to the design watertemperature used to size the coil in the storage/generator.The tank aquastat should be set at the desired domesticwater tank temperature.

As the tank aquastat closes sensing a demand for domes-tic water recovery, the CCP will activate the coil pump andCombination Boilers #1 & #2. The boilers will modulatetheir own input as needed to maintain their setpoint. Theboilers will automatically reduce their input as the coilwater temperature approaches setpoint. Under heavyload, the boilers will increase their input for maximumrecovery. The boilers and coil circulating pump will con-tinue to operate until the tank aquastat is satisfied.

The system start within the Model 168 Boiler ManagementSystem(BMS) activates the heating system circulatingpump and the heating-only modules. Heating Boilers #I &

#2 will fire normally as controlled by the BMS and modu-late input up as the heating load increases. When bothdedicated heating modules reach 100% input, the BMSAuxiliary contacts will close, activating the CCP panel.The CCP will then open the motorized valve in the supplypiping. When the valve reaches 100% open, the endswitch will allow the CCP to transfer the control of bothcombination boilers to the BMS. The BMS will modulatethe input of all four boilers to meet the needs of the heat-ing system.

As the heating system temperature increases to therequired system setpoint, the auxiliary contacts of theBMS will open. The opening of the Auxiliary contacts canbe adjusted from the keyboard of the BMS. As the auxil-iary contacts open, the CCP closes the motorized valve toisolate the domestic loop from the heating loop. Thecontrol of the combination boilers is also returned to theirinternal setpoint controls, and will only fire upon a signalfor domestic water production. If the domestic tank aquas-tat closes while the motorized valve is open for heating,the CCP will automatically close the valve and returnCombination Boilers #I & #2 back to domestic recoveryservice. This internal feature provides priority to domesticwater heating.

Represented by:

HEAT EXCHANGERS • WATER HEATERS • BOILERS

CONTROL VALVES • STEAM GENERATORS

HOT WATER SYSTEMSAERCO INTERNATIONAL, INC. • 159 PARIS AVE., P.O. BOX 128 • NORTHVALE, N.J. 07647-0128

(201)768-2400. FAX 201-768-7789

CCP-1 12/95 5M

4