15
T T T D E F G C 4.5 4 3 2 A B EXST 200 EXST 450 EXST 450 EXST 450 EXST 450 EXST 200 EXST 200 EXST 110 EXST 90 EXST 90 EXST 350 EXST 170 EXST 210 EXST 110 EXST 80 EXST 100 EXST 70 EXST 80 EXST 80 EXST 90 EXST 60 EXST 60 EXST 210 EXST 120 EXST 60 EXST 100 EXST 60 10 3 3 3 3 3 3 3 3 3 4 4 4 5 5 2 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 3 6 6 6 7 7 6 6 8 8 8 8 8 9 EXST 150 EXST 110 6"ø SA 14"x12" SA 10"x10" SA 11"ø EA 12"ø EA 10"ø EA 10"ø EA 8"ø EA 12"ø SA 16"ø SA 16"ø SA 12"ø SA 22"ø SA 16"x15" SA 7"ø SA 7"ø SA 8"ø SA 6"ø SA 7"ø EA 6"ø EA 14"ø SA 20"x18" SA 6"ø SA 37"/24" SA 37"/24" SA 22"ø SA 20"ø SA 8"ø SA 8"ø SA 55"/24" SA 44"/24" SA 20"x12" EA 32"x12" EA 26"x20" EA 16"x12" EA 14"x12" SA 5"ø SA 12"x12" SA 10 11 11 11 EXST 60 EXST 50 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 EXST 190 HWB-1 HWP-1 HWP-2 UH-2 UH-1 VAV-E VAV-E VAV-F VAV-G 1 VAV-E VAV-D VAV-B VAV-F NURSE STATION 146N MED 142 CLEAN SUPPLY 143 FILM WORK ROOM 141 TOILET 148 MD OFFICE 140 BLOCK MOLD 139 INFUSION 144 TOILET 145 MECHANICAL 154 ELECTRICAL 153 RESOURCE OFFICE 152 JAN 151 CL UTIL 150 SOIL UTIL 149 DM1.0 2 80"x24" RA 48"x24" RA 60"x24" RA 32"x24" RA 13 14 13 13 12 E 4.5 4 UH-1 UH-2 B-1 P-1 P-2 3/4"ø HWS 3/4"ø HWS 2"ø HWR 3/4"ø HWR 3/4"ø HWR 2"ø HWS 2"ø HWR 2"ø HWS 1"ø 2"ø 2"ø HWS 1 2 3 MECHANICAL 154 ELECTRICAL 153 A B C D E 1 2 3 4 5 6 7 1 2 3 4 5 6 7 A B C D E THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THE DOCUMENT TO WHICH THEY ARE AFFIXED, AND WE EXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHER PLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHER DOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDED TO BE USED FOR ANY PART OF PARTS OF THE PROJECT. © COPYRIGHT 2013 CHRISTNER INC. Revision Dwg No Sheet No Project No Date OZARKS MEDICAL CENTER 1100 KENTUCKY AVENUE WEST PLAINS, MISSOURI 65775 417-256-9111 STRUCTURAL ENGINEER ALPER-AUDI 1804 BORMAN CIRCLE DRIVE ST LOUIS, MISSOURI 63146 CORPORATE CHARTER NUMBER 314-432-8600 MEPFP ENGINEER BRiC PARTNERSHIP MISSOURI CERTIFICATE OF AUTHORITY: # 2002028690 343 S. KIRWOOD RD KIRKWOOD, MISSOURI 314-725-5889 CIVIL ENGINEER OVERLAND ENGINEERING 1598 IMPERIAL CENTER WEST PLAINS, MO 65775 417-256-8150 TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM 168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105 ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS CERTIFICATE OF AUTHORITY - 000842 C:\Users\margaretb\Documents\2209-02_MEP_Central_v16_margaretb.rvt 4/13/2016 9:26:04 AM CTC - INFUSION ADDITION AND RENOVATION DM1.0 15068 2/26/16 CONSTRUCTION DOCUMENTS MECHANICAL DEMO 1/8" = 1'-0" 1 MECHANICAL DEMO KEYED NOTES 1 REMOVE EXISTING SUPPLY AIR DEVICE AND EXISTING BRANCH DUCTWORK SHOWN HATCHED. REMOVE ALL ASSOCIATED HANGERS, BRACKETS, ETC. 2 REMOVE EXISTING DUCT SHOWN HATCHED BACK TO TERMINAL UNIT. REMOVE ALL ASSOCIATED HANGERS, BRACKETS, SUPPORTS, ETC. 3 REMOVE EXISTING RETURN GRILLE SHOWN HATCHED. 4 REMOVE EXISTING THERMOSTAT AND ALL ASSOCIATED WIRING BACK TO EQUIPMENT. 5 REMOVE EXISTING RADIENT HEAT TILE SHOWN DASHED AND ALL ASSOCIATED HANGERS, BRACKETS, SUPPORTS, CONTROLS, ETC. 6 REMOVE EXISTING SUPPLY AIR DEVICE AND DUCT SHOWN HATCHED BACK TO MAIN. REMOVE ALL ASSOCIATED BRACKETS, HANGERS, ETC. PATCH MAIN AIRTIGHT. REPAIR INSULATION TO MATCH EXISTING. 7 REMOVE EXISTING PORTION OF SUPPLY MAIN SHOWN HATCHED TO ALLOW FOR INSTALLATION OF NEW DUCTWORK. REMOVE ASSOCIATED HANGERS, BRACKETS, ETC. 8 REMOVE EXISTING EXHAUST DIFFUSER AND DUCT SHOWN HATCHED BACK TO MAIN. REMOVE ALL ASSOCIATED BRACKETS, HANGERS, ETC. PATCH MAIN AIRTIGHT. 9 REMOVE EXISTING FIRE DAMPER SHOWN HATCHED. PROVIDE NEW EXHAUST DUCT TO RE-CONNECT DUCTS. 10 REMOVE EXISTING AIR DEVICE AND DUCT SHOWN HATCHED. EXISTING FAN TO REMAIN. REMOVE EXISTING EXHAUST FAN ON ROOF AND CAP ROOF CURB AIR AND WATER TIGHT. 11 EXISTING EXHAUST AIR DUCT TO REMAIN. 12 EXISTING VAV BOX TO REMAIN. 13 EXISTING SUPPLY DUCT TO REMAIN. 14 EXISTING RETURN DUCT TO REMAIN. KEY PLAN PRE-DEMOLITION TESTING AND BALANCING 1 CONTRACTOR SHALL MEASURE AND RECORD AIRFLOW AT DEVICE PRIOR TO START OF DEMOLITION. SUBMIT TO ARCHITECT WITHIN ONE WEEK OF TAKING MEASUREMENTS. # # GENERAL NOTES 1 REFER TO SHEET M0.1 FOR ADDITIONAL NOTES THAT APPLY TO THIS SHEET. 2 FINAL RUNOUTS TO TERMINAL DEVICES SHALL BE 3/4" UNLESS OTHERWISE NOTED. 1/4" = 1'-0" 2 BOILER AND HEATING WATER PUMPS DEMO - ALTERNATE 1 KEYED NOTES - ALTERNATE 1 1 REMOVE EXISTING BOILER AND ASSOCIATED ACCESSORIES, CONTROLS, ETC. REMOVE EXISTING EXHAUST FLUE THROUGH ROOF. PATCH ROOF TO MATCH EXISTING AFTER NEW BOILER AND VENTS ARE INSTALLED. PROVIDE TEMPORARY WATERTIGHT COVER AS REQUIRED TO KEEP AIR AND WATER OUT. 2 REMOVE EXISTING HOT WATER PUMPS AND ASSOCIATED HYDRONIC ACCESSORIES, CONTROLS ETC. 3 REMOVE EXISTING BOILER CONTROL PANEL AND ALL ASSOCIATED BRACKETS, HANGERS, ETC. PATCH WALL TO MATCH EXISTING. # Revision Schedule No. Date Revisions

DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

Embed Size (px)

Citation preview

Page 1: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

TT

T

D E F GC

4.5

4

3

2

A B

EXST

200

EXST

450

EXST

450

EXST

450EXST

450

EXST

200

EXST

200EXST

110

EXST

90

EXST

90

EXST

350

EXST

170

EXST

210

EXST

110

EXST

80

EXST

100

EXST

70EXST

80

EXST

80

EXST

90

EXST

60

EXST

60EXST

210

EXST

120

EXST

60

EXST

100

EXST

60

10

3

3

3

3

3 3

3

3

3

4

4

4

5

5

22

1 1 1 1 1 1 1 1 1

1

1

1

1

1

1

1

3

6

6

6

7

7

6

6

8

8

8

8

8

9

EXST

150

EXST

110

6"ø SA

14"x12" SA

10"x10" SA

11"ø EA

12"ø EA

10"ø EA

10"ø EA

8"ø EA

12"ø SA

16"ø SA

16"ø SA

12"ø SA

22"ø SA

16"x15" SA7"ø SA

7"ø SA

8"ø SA 6"ø SA

7"ø EA

6"ø EA

14"ø SA20"x18" SA

6"ø SA

37"/24" SA

37"/24" SA

22"ø SA 20"ø SA

8"ø SA

8"ø SA

55"/24" SA

44"/24" SA20"x12" EA

32"x12" EA26"x20" EA

16"x12" EA

14"x12" SA

5"ø SA

12"x12" SA

10

11

11

11

EXST

60

EXST

50

1

1

1

1

1

1

1 1

1

1

1

1

1

1

1

1

1

1

11

1

EXST

190

HWB-1 HWP-1

HWP-2

UH-2UH-1

VAV-E

VAV-E

VAV-F

VAV-G

1

VAV-E

VAV-D

VAV-B

VAV-F

NURSE STATION

146N

MED

142

CLEAN SUPPLY

143

FILM WORK ROOM

141

TOILET

148

MD OFFICE

140BLOCK MOLD

139

INFUSION

144

TOILET

145

MECHANICAL

154

ELECTRICAL

153

RESOURCE OFFICE

152

JAN

151

CL UTIL

150SOIL UTIL

149

DM1.0

2

80"x24" RA 48"x24" RA

60"x24" RA

32"x24" RA

13

14

13

13

12

E

4.5

4

UH-1

UH-2

B-1 P-1P-2

3/4"ø HWS

3/4"ø HWS

2"ø HWR

3/4"ø HWR

3/4"ø HWR 2"ø HWS

2"ø HWR

2"ø HWS

1"ø2"ø

2"ø HWS

1

2

3

MECHANICAL

154

ELECTRICAL

153

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:0

4 A

M

CTC - INFUSION ADDITIONAND RENOVATION

DM1.015068

2/26/16

CONSTRUCTION DOCUMENTS

MECHANICAL DEMO

1/8" = 1'-0"1

MECHANICAL DEMO

KEYED NOTES

1 REMOVE EXISTING SUPPLY AIR DEVICE AND EXISTING BRANCH DUCTWORK SHOWN HATCHED.REMOVE ALL ASSOCIATED HANGERS, BRACKETS, ETC.

2 REMOVE EXISTING DUCT SHOWN HATCHED BACK TO TERMINAL UNIT. REMOVE ALLASSOCIATED HANGERS, BRACKETS, SUPPORTS, ETC.

3 REMOVE EXISTING RETURN GRILLE SHOWN HATCHED.

4 REMOVE EXISTING THERMOSTAT AND ALL ASSOCIATED WIRING BACK TO EQUIPMENT.

5 REMOVE EXISTING RADIENT HEAT TILE SHOWN DASHED AND ALL ASSOCIATED HANGERS,BRACKETS, SUPPORTS, CONTROLS, ETC.

6 REMOVE EXISTING SUPPLY AIR DEVICE AND DUCT SHOWN HATCHED BACK TO MAIN. REMOVEALL ASSOCIATED BRACKETS, HANGERS, ETC. PATCH MAIN AIRTIGHT. REPAIR INSULATION TOMATCH EXISTING.

7 REMOVE EXISTING PORTION OF SUPPLY MAIN SHOWN HATCHED TO ALLOW FOR INSTALLATIONOF NEW DUCTWORK. REMOVE ASSOCIATED HANGERS, BRACKETS, ETC.

8 REMOVE EXISTING EXHAUST DIFFUSER AND DUCT SHOWN HATCHED BACK TO MAIN. REMOVEALL ASSOCIATED BRACKETS, HANGERS, ETC. PATCH MAIN AIRTIGHT.

9 REMOVE EXISTING FIRE DAMPER SHOWN HATCHED. PROVIDE NEW EXHAUST DUCT TORE-CONNECT DUCTS.

10 REMOVE EXISTING AIR DEVICE AND DUCT SHOWN HATCHED. EXISTING FAN TO REMAIN.REMOVE EXISTING EXHAUST FAN ON ROOF AND CAP ROOF CURB AIR AND WATER TIGHT.

11 EXISTING EXHAUST AIR DUCT TO REMAIN.

12 EXISTING VAV BOX TO REMAIN.

13 EXISTING SUPPLY DUCT TO REMAIN.

14 EXISTING RETURN DUCT TO REMAIN.

KEY PLAN

PRE-DEMOLITION TESTING AND BALANCING

1CONTRACTOR SHALL MEASURE AND RECORD AIRFLOW AT DEVICE PRIOR TO START OFDEMOLITION. SUBMIT TO ARCHITECT WITHIN ONE WEEK OF TAKING MEASUREMENTS.

##

GENERAL NOTES

1 REFER TO SHEET M0.1 FOR ADDITIONAL NOTES THAT APPLY TO THIS SHEET.

2 FINAL RUNOUTS TO TERMINAL DEVICES SHALL BE 3/4" UNLESS OTHERWISE NOTED.

1/4" = 1'-0"2

BOILER AND HEATING WATER PUMPS DEMO - ALTERNATE 1

KEYED NOTES - ALTERNATE 1

1 REMOVE EXISTING BOILER AND ASSOCIATED ACCESSORIES, CONTROLS, ETC. REMOVEEXISTING EXHAUST FLUE THROUGH ROOF. PATCH ROOF TO MATCH EXISTING AFTER NEWBOILER AND VENTS ARE INSTALLED. PROVIDE TEMPORARY WATERTIGHT COVER AS REQUIREDTO KEEP AIR AND WATER OUT.

2 REMOVE EXISTING HOT WATER PUMPS AND ASSOCIATED HYDRONIC ACCESSORIES,CONTROLS ETC.

3 REMOVE EXISTING BOILER CONTROL PANEL AND ALL ASSOCIATED BRACKETS, HANGERS, ETC.PATCH WALL TO MATCH EXISTING.

#

Revision Schedule

No. Date Revisions

Page 2: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

E

1

2

2

222

2

2

3

44

EX

. 1-1

/4"

VA

CE

X. 3/4

" O

X

EX. 3/4" OX

EX. 3/4" OX

EX. 1-1/4" VAC

EX. 3/4" OX

EX. 1-1/4" VAC

EX. 3/4" OX

EX. 1-1/4" VAC

EX. 1/2" OX

EX. 3/4" VAC

EX. 1/2" OX

EX. 3/4" VAC

EX. 1/2" OXEX. 3/4" VAC

EX. 1/2" OX

EX. 1" VAC

EX. 1/2" OX

EX. 3/4" VAC

EX

. 1-1

/4"

VA

CE

X. 3/4

" O

X

EX. 1/2" OX

EX. 3/4" VAC

EX. 1/2" OX

EX. 3/4" VAC

EX. 1/2" OX

EX. 3/4" VAC

EX

. 1/2

" O

XE

X. 3/4

" V

AC

5

C D

4

4.5

A.9 B.8 C.8

5

6

6

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:0

5 A

M

CTC - INFUSION ADDITIONAND RENOVATION

DMG1.015068

2/26/16

CONSTRUCTION DOCUMENTS

MEDICAL GAS DEMO

1/4" = 1'-0"1

FIRST FLOOR MEDICAL GAS DEMO

KEYED NOTES

1 EXISTING MEDICAL GAS VALVE BOX TO REMAIN; NO WORK.

2 REMOVE MEDICAL GAS PIPING WITHIN THE WALL ANDQUICK CONNECT BOXES.

3 REMOVE MEDICAL GAS PIPING FROM THE POINTINDICATED TO THE QUICK CONNECT BOXES AS INDICATED.

4 REMOVE MEDICAL VACUUM PIPING WITHIN THE CORRIDORAS INDICATED.

5 REMOVE EXISTING OXYGEN MANIFOLD; REMOVE PIPING UPTO THE BUILDING. STUCTURE SHALL REMAIN.

6 INSTALL A TEMPERARY CAP ON THE EXISTING OXYGENPIPING ON EXTERIOR OF THE WALL.

#

KEY PLAN

Revision Schedule

No. Date Revisions

Page 3: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

GENERAL NOTES (HYDRONIC)

GENERAL NOTES (DEMOLITION)

GENERAL NOTES (ROOF PROTECTION)

GENERAL NOTES (AIR SIDE)

THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLYTHE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS,SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTINGDUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THE LOCATIONINDICATED ON THE DRAWINGS. THE CONTRACTOR SHALL BE PREPARED TOMAKE SOME ALTERATIONS TO NEW AND/OR EXISTING SERVICES TO FITACTUAL JOB CONDITIONS.

THE SPACE ALLOWED FOR MECHANICAL (HVAC, PLUMBING, FIREPROTECTION) AND ELECTRICAL WORK ABOVE THE CEILING IS CRITICAL ANDREQUIRES COORDINATION BETWEEN TRADES. CONTRACTORS SHALLTHOROUGHLY FAMILIARIZE THEMSELVES WITH THE ARCHITECTURAL,STRUCTURAL, MECHANICAL, AND ELECTRICAL DRAWINGS PRIOR TOFABRICATION OR INSTALLATION OF ANY MATERIALS. DUCTWORK SHALLBE HUNG AS CLOSE AS POSSIBLE TO THE STRUCTURE ABOVE UNLESSINDICATED OTHERWISE. REWORK OF PIPING, DUCTWORK, EQUIPMENTLOCATION, CONDUIT, ETC. AS A RESULT OF POOR PLANNING,COORDINATION, OR SCHEDULING SHALL BE THE RESPONSIBILITY OF THECONTRACTOR.

ANY HOLES LEFT IN EXISTING WALL/ROOF CONSTRUCTION DUE TODEMOLITION OR NEW WORK SHALL BE PATCHED TO MATCH EXISTINGCONDITIONS.

PIPES/DUCTS/ETC. PENETRATING EXTERIOR WALLS AND ROOFS SHALL BESEALED WEATHER PROOF.

THERMOSTATS/TEMPERATURE SENSORS SHALL BE MOUNTED AT 48" A.F.F.TO THE TOP OF THERMOSTAT/TEMPERATURE SENSOR UNLESS NOTEDOTHERWISE. DO NOT MOUNT IN DIRECT SUNLIGHT OR NEAR HEATPRODUCING EQUIPMENT.

INSTALL H.V.A.C. SYSTEM IN ACCORDANCE WITH ALL STATE AND LOCALCODES.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OFANY FRAMING REVISIONS, EQUIPMENT LOCATIONS, ADDITION OF CONTROLS,ELECTRICAL CIRCUITING REVISIONS, ETC. THAT RESULT FROM USINGEQUIPMENT OTHER THAN INDICATED ON THE DRAWINGS. APPROVAL OF THESHOP DRAWINGS BY THE ENGINEER WILL NOT WAIVE THE CONTRACTOR OFTHIS RESPONSIBILITY.

THE CONTRACTOR SHALL HAVE THE FINAL RESPONSIBILITY FOR SYSTEMSTART UP AND TURN OVER TO THE OWNER.

ALL ITEMS INCLUDED ON THESE DRAWINGS AND THE SPECIFICATIONS SHALLBE INCLUDED IN THE CONTRACTOR'S BID. IF THE CONTRACTOR DOES NOTCLEARLY UNDERSTAND THESE PLANS OR IS NOT SURE OF THEIR MEANING,THE CONTRACTOR SHOULD OBTAIN THE ENGINEER'S WRITTEN EXPLANATIONAND INTERPRETATION PRIOR TO BID TIME. THE CONTRACTOR WILL BE HELDTO THE INTERPRETATION OF THE ENGINEER.

FIRE CAULK ALL PENETRATIONS THRU FIRE RATED PARTITIONS TO MAINTAINFIRE RATING OF PARTITION.

CAULK ALL PENETRATIONS THRU WALLS TO MINIMIZE SOUND PENETRATIONTHRU WALLS.

IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO COORDINATE ALLTEMPERATURE CONTROL SYSTEM REQUIREMENTS.

ANY DAMAGE TO THE SITE (SIDEWALKS, CURBS, ETC) OR TO THE BUILDINGAS A RESULT OF WORK PERFORMED UNDER THIS CONTRACT SHALL BEFIXED BY THE CONTRACTOR AT NO ADDITIONAL COST TO THE OWNER.

CONTRACTOR WILL BE RESPONSIBLE FOR ALL CUTTING AND PATCHING OFROOFS/WALLS/FLOORS AND CORE DRILLS REQUIRED TO COMPLETE THEIRRESPECTIVE WORK.

THE OWNER SHALL HAVE FIRST SALVAGE RIGHTS OF EQUIPMENT ANDMATERIALS REMOVED. ALL EQUIPMENT AND MATERIALS NOT CLAIMED BYTHE OWNER SHALL BE REMOVED FROM THE PREMISES BY THECONTRACTORS.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANYTEMPORARY FENCING AROUND THE LIFT SITE DURING LIFTS.

ALL EXISTING MECHANICAL EQUIPMENT, DUCTWORK, ETC. THAT SERVESSPACES ON OTHER FLOORS SHALL REMAIN AS IS. DO NOT DISCONNECT ORREMOVE ANY EQUIPMENT NOT SHOWN IN THESE PLANS.

REMOVE AND RE-INSTALL EXISTING LAY-IN CEILING AS REQUIRED TOCOMPLETE ALL DEMOLITION AND NEW WORK. REPLACE CEILING TILESDAMAGED DURING CONSTRUCTION WITH NEW TILES MATCHING EXISTING.

GENERAL NOTES

NOTE, ALL DUCTWORK OFFSETS ARE NOT SHOWN. THECONTRACTOR SHALL MODIFY DUCTS AND OFFSETS TO COORDINATEWITH THE BUILDING STRUCTURE AND ALL TRADE REQUIREMENTS.

ALL DUCTWORK SHALL BE CONSTRUCTED AND INSTALLED PER THELATEST VERSION OF THE S.M.A.C.N.A. H.V.A.C. DUCT CONSTRUCTIONSTANDARDS, UNLESS SPECIFIED MORE STRINGENTLY IN THESECONSTRUCTION DOCUMENTS.

90° DUCT ELBOWS SHALL BE EQUIPPED WITH SINGLE THICKNESSTURNING VANES MOUNTED TO A PREFABRICATED VANE RAIL.

ALL ELBOWS SHALL BE SUPPLIED WITH TURNING VANES, WHETHERSHOWN ON DOCUMENTS OR NOT.

ALL 90° AND 45° RECTANGULAR RADIUS ELBOWS TO BE FABRICATEDWITH AN INSIDE RADIUS NO LESS THAN 1/2 OF THE WIDTH OF THEDUCT - WHERE THE WIDTH OF THE DUCT IS DEFINED AS THEDIMENSION OF THE DUCT IN THE PLANE IN WHICH THE DUCT ISTURNING.

RECTANGULAR DUCTWORK SHALL BE SUPPORTED PER THES.M.A.C.N.A STANDARDS AND AT EACH CHANGE IN DIRECTION.

PROVIDE MANUAL, SINGLE BLADE, BALANCING DAMPERS WITH LOCKINGQUADRANT AND INTEGRAL POSITION INDICATOR ON ALL RUNOUTS TOSUPPLY AND EXHAUST AIR DEVICES - EXCEPT THOSE LOCATED INAREAS WITH PLASTER CEILINGS AND ARE NOT ACCESSIBLE (DAMPERSHALL BE INTEGRAL WITH THE AIR DEVICE IN THESE CASES.) PROVIDEHANDLE OFFSET TO ACCOMODATE EXTERNAL INSULATION.

PROVIDE MANUAL OPPOSED BLADE DAMPERS WITH LOCKINGQUADRANT AND INTEGRAL POSITION INDICATOR ON ALL RECTANGULARBRANCH DUCTS AND AIR DEVICE RUNOUTS THAT EXCEED 12" INHEIGHT. PROVIDE HANDLE OFFSET TO ACCOMODATE EXTERNALINSULATION.

MANUAL SPLITTER DAMPERS ARE NOT ACCEPTABLE.

NOT ALL OF THE ACCESS DOORS IN THE DUCT SYSTEMS OR PLENUMSARE SHOWN. PROVIDE ACCESS DOORS IN ALL DUCT SYSTEMS ORPLENUMS WHERE REQUIRED TO ACCESS AND MAINTAIN MOTORIZEDOR AUTOMATIC DAMPER BLADES AND LINKAGES.

ALL DUCTWORK SHALL BE SUPPORTED FROM ROOF OR FLOORSTRUCTURE ABOVE. DUCTWORK SHALL NOT LAY ON TOP OF CEILINGOR LIGHT FIXTURES.

FLEXIBLE DUCT RUNOUTS TO AIR DEVICES SHALL NOT EXCEED 5'-0" INLENGTH. FLEXIBLE RUNOUTS SHALL BE TRIMMED TO THE MINIMUMLENGTH NECESSARY TO MAKE THE CONNECTION.

WHERE DAMPER ACTUATORS ARE MOUNTED TO DUCTWORK ORPLENUMS PROVIDE A HEAVY GAGE BASE PLATE, ANGLE STIFFENERS,OR MOUNTING AS REQUIRED TO ELIMINATE DEFLECTION OFDUCTWORK DURING ACTUATOR OPERATION.

FLEXIBLE DUCT CONNECTIONS TO EQUIPMENT ARE NOT SHOWN ONTHE DRAWINGS. PROVIDE EXTRA WIDE FLEXIBLE CONNECTIONS ONTHE SUPPLY DUCT AND THE RETURN DUCT OF EACH ROOFTOP UNIT.PROVIDE STANDARD FLEXIBLE CONNECTIONS ON ALL BLOWER COILS,EXHAUST FANS, SUPPLY FANS, AIR HANDLING UNITS, AND DUSTCOLLECTOR.

PROVIDE 45° FLARED TAKEOFFS FOR ALL RECTANGULAR BRANCHCONNECTIONS TO THE MAIN DUCT.

ALL DAMPER ACTUATORS FOR DUCT SYSTEMS OR EQUIPMENT THATCOMMUNICATES DIRECTLY WITH THE OUTDOORS SHALL BE SPRINGRETURN TYPE TO CLOSE IN THE EVENT OF A POWER FAILURE.

PROVIDE 1-1/2 HOUR RATED FIRE DAMPERS IN THE DUCTWORKWHERE INDICATED ON THE PLANS AND REQUIRED BY CODE. FIREDAMPERS SHALL BE PROVIDED WITH AN ACCESS PANEL LARGEENOUGH TO PERMIT INSPECTION AND MAINTENANCE OF THE DAMPER.ACCESS PANELS TO FIRE DAMPERS SHALL BE PERMANENTLYIDENTIFIED ON THE EXTERIOR BY A NAMEPLATE WITH THE WORDS"FIRE DAMPER". THE LETTERS ON THE FIRE DAMPER LABELS SHALLNOT BE LESS THAN 1/2 INCH IN HEIGHT.

THE SPACE ABOVE THE SUSPENDED CEILINGS SHALL BE USED AS ARETURN AIR PLENUM. IT IS THE RESPONSIBILITY OF THE MECHANICALCONTRACTOR TO COORDINATE THE WORK OF OTHER TRADES TOPROVIDE ADEQUATE SPACE FOR THE FLOW OF RETURN AIR (250 FPMMAXIMUM VELOCITY). WHERE PARTITIONS EXTEND TO THECONSTRUCTION ABOVE, OPENINGS SHALL BE PROVIDED IN THEPARTITION ABOVE THE CEILING.

AREAS ABOVE THE CEILING SERVE AS A RETURN AIR PLENUM. ALLMATERIALS EXPOSED IN THE PLENUM SHALL HAVE A 25/50SMOKE/FLAME SPREAD RATING.

ALL DUCT RUNOUTS TO AIR DEVICES ARE TO BE THE SAME SIZE ASTHE NECK OF THE AIR DEVICE UNLESS NOTED OTHERWISE.

DIRECTIONAL ARROWS ON AIR DEVICES INDICATE THROWS FOR AIRDEVICE. VERIFY PROPER ADJUSTMENT OF THROW DEFLECTIONVANES OF ALL AIR DEVICES PRIOR TO BEGINNING BALANCING.

CONTRACTOR SHALL BALANCE EACH AREA OF COMPLETED WORK.THE CONTRACTOR SHALL BALANCE SUPPLY, RETURN, AND EXHAUSTAIR FLOWS AT EACH AIR DEVICE AFFECTED BY RENOVATION TOQUANTITY INDICATED ON THE DRAWINGS.

ALL NEW DUCT CONNECTIONS TO EXISTING DUCTWORK SHALL BESEALED AIRTIGHT.

ALL BATHROOM EXHAUST DUCTWORK SHALL BE INSULATED.

EXPOSED GALVANIZED DUCTWORK SHALL BE PAINTABLE. GENERALCONTRACTOR TO PAINT ALL EXPOSED DUCTWORK. FINAL COLOR TOBE APPROVED BY THE ARCHITECT.

THE CONTRACTOR SHALL COORDINATE SYSTEM SHUT-DOWNS, INCLUDINGHEATING WATER SYSTEM SHUT-DOWNS, WITH THE OWNER. PROVIDE AMINIMUM TWO DAY NOTICE PRIOR TO ANY SYSTEM SHUT-DOWN.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR DRAINING, FILLING, ANDVENTING OF ALL HYDRONIC SYSTEMS IMPACTED BY THIS PROJECT.

THESE PLANS ARE DIAGRAMMATIC IN NATURE. SINCE THEY REFLECTONLY THE AVAILABLE INFORMATION OBTAINED FROM EXISTING PLANS,SPECIFICATIONS, AND FIELD SURVEYS. THE EXACT LOCATION OFEXISTING DUCTWORK, PIPING, AND EQUIPMENT MAY DEVIATE FROM THELOCATION INDICATED ON THESE DRAWINGS. THE CONTRACTOR SHALLBE PREPARED TO MAKE SOME ALTERATIONS TO NEW AND/OR EXISTINGSERVICES TO FIT ACTUAL JOB CONDITIONS.

ITEMS SHOWN BOLD AND/OR DASHED ON THE DEMOLITION SHEETSINDICATE ITEMS TO BE REMOVED.

CROSS HATCHING INDICATES ITEMS TO BE REMOVED.

OWNER HAS FIRST RIGHT OF REFUSAL FOR ALL EQUIPMENT BEINGREMOVED. CONTRACTOR TO DISPOSE OF EQUIPMENT BEING REMOVEDBUT NOT RETAINED BY OWNER.

THE CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE A MINIMUMOF SEVEN DAYS PRIOR TO THE BEGINNING OF WORK THAT INVOLVES ACTIVITYON THE ROOF.

TRAFFIC OVER THE EXISTING ROOF SURFACES SHALL BE KEPT TO ANABSOLUTE MINIMUM.

THE CONTRACTOR AND THE OWNER'S REPRESENTATIVE SHALL INSPECT THEEXPOSED ROOFING SYSTEM PRIOR TO THE START OF CONSTRUCTION. ANYPREVIOUS DAMAGE OR DEFECTS OF THE ROOFING SYSTEM SHALL BEDOCUMENTED BY WRITING AND/OR PHOTOGRAPHS.

THE CONTRACTOR SHALL PLACE MINIMUM OF 48" WIDE, 1/2" THICK APPROVEDPROTECTION BOARDS (1 LAYER) MADE OF CONSTRUCTION GRADE PLYWOOD(ORIENTED STRAND BOARD WILL BE ACCEPTABLE) OVER ALL MEMBRANEROOFING THAT WILL HAVE CONSTRUCTION TRAFFIC. THIS ROOF PROTECTIONSHALL BE PROVIDED FOR THE ENTIRE AREA WITHIN THE LIMITS OF THE WORK.SUCH PROTECTION SHALL ALSO BE PROVIDED IN THE FORM OF A WALKWAYFROM THE ROOF ACCESS POINT TO THE PROTECTED CONSTRUCTION AREA.PROTECTION SHOULD BE WEIGHTED DOWN AS REQUIRED TO KEEP IT FROMBLOWING OFF ROOF FROM WIND.

STORAGE OF MATERIALS ON EXISTING ROOF WILL NOT BE ALLOWED.

THE CONTRACTOR SHALL REMOVED DAILY ALL PROJECT DEBRIS FROM ALLROOFING SURFACES.

THE CONTRACTOR SHALL ADVISE THE OWNER'S REPRESENTATIVE WHEN WORKON THE ROOF IS COMPLETE AND THE PROTECTION BOARDS HAVE BEENREMOVED. THE CONTRACTOR AND THE OWNER'S REPRESENTATIVE SHALLEXAMINE ALL ROOF SURFACES WHERE WORK HAS OCCURED AND WILL REPAIRALL DEFECTS NOT PREVIOUSLY DOCUMENTED.

CONTRACTOR SHALL BE RESPONSIBLE FOR ANY DAMAGE TO THE BUILDING,ROOF, STRUCTURAL FRAMING, ETC. INCURRED DURING CONSTRUCTION.

CONTRACTOR SHALL UTILIZED A LICENSED APPLICATOR OF THE EXISTINGROOFING SYSTEM TO REPAIR ANY AND ALL DAMAGE INCURRED DURING THECOURSE OF CONSTRUCTION.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

1.

2.

1.

2.

3.

4.

1.

2.

3.

4.

5.

6.

7.

8.

9.

TV

D

R R

D

M M

S4H - 600

24" x 12"

24" x 12"

H

T

N

CWS

CWR

DTS

DTR

G

C

CR

A

LPS

MPS

LPC

MPC

HPS

HPC

CPD

H

HR

RS

RL

RD

VL

D

MWL

FOV

FOR

FOS

K A

R

M

S

S

M

B

CL

GAS

FS

U

HEATING AND AIR CONDITIONING ABBREVIATIONSPIPING SPECIALTIES

MISCELLANEOUS

GENERAL CONSTRUCTION CONTRACTOR

HEATING & AIR CONDITIONING CONTRACTOR

PLUMBING CONTRACTOR

ELECTRICAL CONTRACTOR

AUTOMATIC CONTROL SUB-CONTRACTOR

FIRE PROTECTION CONTRACTOR

KITCHEN EQUIPMENT CONTRACTOR

EQUIPMENT OR PLUMBING FIXTURE DESIGNATION

RISER DESIGNATION

(RISER INDICATION P=PLUMBING, P =KITCHEN, P =ACID)

(RISER NUMBER)

DETAIL DESIGNATION

(DETAIL NUMBER)

(SHEET NUMBER WHERE DETAIL IS FOUND)

SECTION DESIGNATION

(SECTION NUMBER)

(SHEET NUMBER WHERE SECTION IS FOUND)

KEYED NOTES

REVISIONS

ACCESS PANEL

NEW CONNECTION

SA SOUND ATTENUATOR

FLEXIBLE CONNECTIONFC

SPLITTER DAMPER

VOLUME DAMPERVD

TV TURNING VANES

RETURN, EXHAUST, OR OUTSIDE AIR DUCT

DISCHARGE OR SUPPLY AIR DUCT

INCLINED DROP IN THE DIRECTION OF AIR FLOW

INCLINED RISE IN THE DIRECTION OF AIR FLOW

FIRE DAMPER (F) SMOKE DAMPER (S)

MOTORIZED DAMPER (ELECTRIC OR PNEUMATIC)MD

FXD FLEXIBLE DUCT

CEILING AIR DEVICE

SIDEWALL AIR DEVICE

(SUPPLY AIR - TYPE 4 - LOCATION:

(AIR QUANTITY - CFM) H - HIGH SIDEWALL

L - LOW SIDEWALL

C - CEILING

F - FLOOR OR SILL

AIR DEVICE DESIGNATION

(SIZE:

1st FIGURE SIDE SHOWN)

DUCT SIZE DESIGNATION:

(1st FIGURE SIDE SHOWN. SIDE SHOWN IS SHEET METAL

SIZE, ALLOWANCE HAS BEEN MADE FOR INTERIOR INSULATION

WHERE SPECIFIED.)

HUMIDISTAT

T THERMOSTAT

TN THERMOSTAT NITE

CONDENSING WATER SUPPLY

CONDENSING WATER RETURN

DUAL TEMPERATURE SUPPLY

DUAL TEMPERATURE RETURN

CHILLED WATER SUPPLY

CHILLED WATER RETURN

COMPRESSED AIR

LOW PRESSURE STEAM

MEDIUM PRESSURE STEAM

LOW PRESSURE CONDENSATE

MEDIUM PRESSURE CONDENSATE

HIGH PRESSURE STEAM

HIGH PRESSURE CONDENSATE

CONDENSATE PUMP DISCHARGE

HOT WATER SUPPLY

HOT WATER RETURN

REFRIGERANT SUCTION

REFRIGERANT LIQUID

REFRIGERANT DISCHARGE

VENT LINE (OTHER THAN PLUMBING)

DRAIN LINE (OTHER THAN PLUMBING)

MAKE - UP WATER LINE

FUEL OIL VENT

FUEL OIL RETURN

FUEL OIL SUPPLY

AP

FINISH FLOOR ELEVATION

ABOVE FINISH FLOOR

TOP ELEVATION

BOTTOM ELEVATION

F.F.E.

A.F.F.

T.E

B.E

F.L. FLOW LINE

INVERT ELEVATIONINV.

CENTER LINE

HALON SUB-CONTRACTOR

(MIXING OR BY-PASS AS INDICATED)

FLOW MEASURING DEVICE

COMBINATION BALANCING & MEASURING DEVICE

TEE (SIDE OUTLET DOWN)

FLEXIBLE PIPE CONNECTION

SOC SHUT-OFF COCK

PRESSURE REDUCING VALVE

TEMPERATURE AND PRESSURE RELIEF VALVE

FLOW CONTROL VALVE (GPM INDICATED)

VALVE W/ SUPERVISORY SWITCH

THERMOMETER (TUBE OR DIAL AS INDICATED)TH

DIAPHRAM VALVE

MOTORIZED VALVE

PIPE GUIDES

ANCHORS

DIRECTION OF FLOW

DV

MV

PRV

FLOW SWITCH

BUTTERFLY VALVE

PRESSURE GAUGE

SOLENOID VALVE

PG

T&PR

FCV

BFV

SLV

STEAM TRAP

ECCENTRIC REDUCER

ELBOW (TURNED DOWN)

ELBOW (TURNED UP)

FMD

ECR

BMD

TEE (SIDE OUTLET UP)

CONCENTRIC REDUCER

EXPANSION JOINT

AIR VENT (AUTOMATIC)

AIR VENT (MANUAL)

RELIEF VALVE

AVA

CCR

EX

AVM

FC

RV

BALL VALVE

UNION

STRAINER

BALANCING COCK

GLOBE VALVE

CHECK VALVE

GATE VALVE

BC

BLV

STR

GV

GLV

CV

PETES PLUG

3 - WAY VALVE

STOP AND WASTE VALVE

HOSE END VALVE

LUBRICATED VALVE

SWV

TWV

HEV

LPV

NOTE: NOT ALL SYMBOLS OR ABBREVIATIONS MAY BE USED.

G.C.C.

H.A.C

P.C.

E.C.

A.C.S.

F.P.C.

H.S.C

K.E.C.

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:1

7 A

M

CTC - INFUSION ADDITIONAND RENOVATION

M0.115068

2/26/16

CONSTRUCTION DOCUMENTS

LEGEND AND SYMBOLS

Revision Schedule

No. Date Revisions

Page 4: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

FE

C

FE

C

FEC

A.9 B.8 C.8 D E F

R3

R2

R1

7

6

5

9

4.5

4

3

2

B

EXST

200

EXST

450

EXST

450

EXST

450EXST

450

EXST

200

EXST

200 EXST

110

EXST

90

EXST

90

EXST

350

EXST

170

EXST

120

EXST

110

EXST

210

EXST

110

EXST

80

EXST

100

EXST

70EXST

80

EXST

80

EXST

90

EXST

60

EXST

60

EXST

210

EXST

120

EXST

60

EXST

100

EXST

60

S-2

140

S-3

220

S-3

220

S-2

180

S-2

170

S-2

185

S-1

70

S-1

70

S-2

140

S-2

140S-2

140

S-2

120S-2

120

S-2

140

S-2

120S-2

120S-2

130

S-2

130

S-2

130

S-2

180

S-2

190

S-1

75

S-1

80

S-1

80

S-1

80

S-3

285

12"x7" SA

10"ø SA

10"ø SA

6"ø SA

10"ø SA

8"ø SA

8"ø SA

12"ø SA

S-1

80

S-2

120

S-2

120

S-1

80

S-1

80

S-1

80

S-1

80

S-4

300

VAV

4

VAV

3

VAV

5

VAV

J

VAV

2

CAV

1

10

R-3

805

R-1

300

E-2

180

47"x13" RA

34"x13" SA

8"ø SA

12"x11" SA

EXST

190

R-2

435

I

R-4

I

R-4

I

R-4

I

R-4

I

R-4

I

R-4

I

R-4

14"x13" SA

8"ø SA

14"x12" SA

8"ø SA8"ø SA

8"ø SA12"x12" SA

10"x10" SA

6"x6" SA

8"ø SA

6"ø SA

10"x9" SA

12"ø SA

8"ø SA

8"x8" SA

10"x10" SA

12"x10" SA

16"ø SA

8"ø SA

8"ø SA

8"ø SA 9"ø SA

8"ø SA

10"x9" SA

18"x12" RA

6"x6" SA

8"x8" SA

7"ø EA 6"x6" SA

10"ø EA8"ø EA

10"x10" SA

6"x6" SA

12"x8" SA

12"ø EA

11"ø EA

16"x12" EA

7"ø EA

8"ø EA

7"ø SA

16"ø SA

8"ø EA

7"ø EA

16"x15" SA

6"ø SA

14"x12" SA

1

23

R

E-1

75

E-2

180

E-4

1000

E-4

2675

FFU-1

235

FFU-3

370

FFU-2

270

FFU-5

370

EF

6

EF

7

S-1

70

9"ø SA

8"ø SA

8"ø SA

EXST

60

EXST

50

EXST

150

FFU-4

370

32"x12" EA 26"x20" EA

20"x12" EA

55"/24" SA

24"/44" SA8"ø SA

8"ø SA

14

8

8

8 8

88

8

8 8

8

8

8

8

14"x12" SA

12"x12" SA

5"ø SA

6"ø SA

6"ø SA

6"ø SA

6"ø SA

6"ø SA

6"ø SA

10"ø

SA

11"ø SA7"ø SA

12"ø SA16"ø SA

20"ø SA22"ø SA

16"ø SA14"ø SA

6"ø SA

37"/24" SA

86"ø SA

37"/24" SA

24"ø SA

14"ø SA

8"ø SA

6"ø SA

6"ø SA

7"ø SA 7"ø EA

7"ø SA

8"x24" SA18"x18" SA

VAV

F

8"x24" SA

12"x8" SA12"x8" SA

12"x8" SA 12"x8" SA

9"x6" SA

9"x6" SA

22"ø SA

6"ø EA

EXST

60

12"ø SA

6"ø SA

6"ø SA

6

6"ø EA

6"ø EA

5

5

9"ø EA

7

8

8

8

8

8

8

89

11

12

13

HWB-1AS-1 HWP-1

HWP-2

UH-2UH-1

D

6"x6" SA

5"ø

EA

R

18"x12" SA

S-2

280I

R-4

7"x7" SA6"ø SA

6"ø SA

16"x11" SA

3

M1.0

I

R-4

4

M1.0

D

VAV - F

VAV - G

VAV - E

VAV - E

VAV - E

VAV - D

VAV - B

VAV - B

1

1

1

17

17

1616

M2.0

2

1

1

4

10

M

MM

M 15 10"x10" RAR-1

205

15

60"x

24"

RA

48"x24" RA 32"x24" RA

19

18

12"x

6"

SA

M1.0

5

S-1

70

24"x

8"

SA

2

2

Level 10' - 0"

Level 214' - 0"

7 66.5

VAV

3

11"x16" SA 9"ø SA 34"x13" SA

8"x24" SA

NURSE STATION

115

PASSAGE

114

LIGHT

Level 10' - 0"

Level 214' - 0"

7 6.5

8"x9" SA

10"ø SA4" STORM

PASSAGE

114

NURSE CALL LIGHTCAN LIGHT

D

FFU-5

370

FFU-2

270

R-3

805

FFU-4

370

FFU-3

370

FFU-1

235

R-1

300

R-1

205

MM

M

M

18

19 10

4

15

15

R-2

435

6"x6" SA

7"ø EA

10"x10" RA

12"x8" SA

6"x6" SA

5"ø EA

10"ø EA10"x9" SA

18"x12" RA

10"x9" SA

12"x6" SA

6"ø EA

6"x6" SA

5"ø EA

10"x9" SA

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:2

1 A

M

CTC - INFUSION ADDITIONAND RENOVATION

M1.015068

2/26/16

CONSTRUCTION DOCUMENTS

MECHANICAL NEW DUCTWORK

1/8" = 1'-0"1

MECHANICAL NEW WORK

KEYED NOTES

1 RE-BALANCE EXISTING EXHAUST GRILL TO CFM SHOWN.

2 TERMINATE 47" X 13" RETURN AIR DUCT IN PLENUM SPACE WITH BELLMOUTHFITTING.

3 30" X 34 " SUPPLY AIR DUCT UP TO RTU-2.

4 BALANCE DAMPER TO 50CFM.

5 TERMINATE WITH BRICK VENT. COORDINATE EXACT LOCATION OF VENT WITHMASONRY SPACING.

6 47" X 13" RETURN AIR DUCT UP TO ROOFTOP UNIT. TRANSITION DUCT ASNECESSARY TO CONNECT TO UNIT.

7 22" X 22" EXHAUST AIR DUCT UP TO NEW EXHAUST FAN. TRANSITION DUCT ASNECESSARY TO CONNECT TO FAN. PROVIDE OFFSETS TO CONNECT TO NEWEXHAUST AIR DEVICE.

8 RE-BALANCE EXISTING SUPPLY AIR GRILLE TO CFM SHOWN.

9 RE-BALANCE EXISTING EXHAUST DUCT BALANCING DAMPER TO CFM SHOWN.

10 BALANCE DAMPER TO 100 CFM.

11 RE-BALANCE EXISTING VAV BOX TO 1350 CFM.

12 RE-BALANCE EXISTING VAV BOX TO 1130 CFM.

13 RE-BALANCE EXISTING VAV BOX TO 1650 CFM.

14 RE-BALANCE EXISTING SUPPLY AIR GRILLE TO PRE-DEMOLITION CFM.

15 MOUNT RETURN AIR GRILLE ON WALL 6" A.F.F.

16 PROVIDE 4" WIDE FLEXIBLE CONNECTOR IN DUCTWORK AT EXPANSION JOINT.

17 PROVIDE BALANCING DAMPER IN VERTICLE DROP.

18 BALANCE DAMPER TO 80 CFM.

19 BALANCE DAMPER TO 100 CFM.

NOT TO SCALE2COMPUNDING PHARMACY ISOMETRIC

#

GENERAL NOTES

1 REFER TO SHEET M0.1 FOR ADDITIONAL NOTES THAT APPLY TO THIS SHEET.

2 REFER TO SHEET M2.0 FOR ROOM NUMBERS.

1/4" = 1'-0"3

VAV 115 DUCTWORK SECTION 1/4" = 1'-0"

4NURSE AREA MECANICHAL DUCTWORK SECTION

1/4" = 1'-0"5

COMPUNDING PHARMACY

PHARMACY AIR BALANCING

NAME NUMBERPRIMARY SUPPLY

AIRFLOWEXHAUSTAIRFLOW

RETURN AIRFLOWAT GRILLE

SUPPLY AIRFLOWAT FFU

AIR CHANGESPER HOUR

NEG PRESSURE MIXING ROOM 144 80 145 300 235 30

POS PRESSURE MIXING ROOM 143 100 165 805 740 30

ANTE 142 100 35 205 270 30

HAZ DRUG STORAGE 141 50 115 435 370 30

Revision Schedule

No. Date Revisions

1 Date 1 ADDENDUM 1

2 03/10/16 ADDENDUM 2

Page 5: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

FE

C

FE

C

FEC

T

TT

T T

T

A.9 B.8 C.8 D E

R3

R2

R1

7

6

5

C

9

4.5

4

3

B 10

VAV

3

3/4"ø HWS

3/4"ø HWR

3/4"ø HWS

3/4"ø HWS

3/4"ø HWS

3/4"ø HWR

3/4"ø HWS3/4"ø HWR

1 1/4"ø HWS

1 1/4"ø HWR

2"ø HWS

2"ø HWR1 1/4"ø HWS1 1/4"ø HWR

1 1/4"ø HWS1 1/4"ø HWR

2"ø HWS

2"ø HWR

1 1/4"ø HWS

1 1/4"ø HWR

1"ø HWS

1"ø HWR

3/4"ø HWS

3/4"ø HWR

1"ø HWS

1"ø HWR 3/4"ø HWR

3/4"ø HWS

VAV

5

VAV

4

VAV

2

CAV

1

INFUSION BAY

110

INFUSION BAY

109

PASSAGE-1

124-1

TOILET

127

TOILET

128

INFUSION BAY

129

INFUSION BAY

130

INJECTIONS

103

SOILED UTILITY

104

INFUSION BAY

106

INFUSION BAY

108

TOILET

107

VOLUNTEER

125

PASSAGE

105

PASSAGE

114

PASSAGE

124

NURSE STATION

115

INFUSION BAY

131

EXISTING MECHANICAL

146

WAITING-1

101-1

EXISTING ELEC

145

NEG PRESSURE MIXINGROOM

144

POS PRESSURE MIXINGROOM

143

ANTE

142

PHARMACY

140

INFUSION BAY

111

INFUSION BAY

112

COMFORT AREA

126

HAZ DRUG STORAGE

141

INFUSION BAY

123

INFUSION BAY

116

RECEPTION

102

PREP AREA

132

INFUSION BAY

117

INFUSION BAY

118

INFUSION BAY

119INFUSION BAY

120

INFUSION BAY

121

INFUSION BAY

122

INFUSION BAY

113

PASSAGE

114

VAV

E-3

VAV

E-2

3/4"ø HWS

1/2"ø HWS

1/2"ø HWR

VAV

E

VAV

G

1/2"ø HWR

1/2"ø HWS

3/4"ø HWR

VAV J

CAV 1

VAV 2

VAV 5

VAV-J

3/4"ø HWS

3/4"ø HWR

M2.0

2

3

33 3

4

4

10RPC-1

RPC-2

RPC-3 RPC-4

CLEAN EQUIPMENT

126A

VAV 3

VAV 4

A.9 B.8 C.8 D

R3

R2

R1

7

6

5

C

9

4.5

4

B

8

8.1

8.3

6.5

RTU

2

EF

5

EF

8

EXISTING CURBCAP AIR ANDWATER TIGHT

1 1/4"øCOND

8

REFER TO SHEETP1.2 FOR NATURALGAS CONNECTIONS.

E

4.5

4

HWP

001

HWP

002

HWB

001

UH-1

UH-2

AS-1

3/4"ø COND

2"ø HWR

2"ø HWS

2"ø HWS

2"ø HWR

3/4"ø HWS 3/4"ø HWR

3/4"ø HWR

3/4"ø HWS

1

2

6 5 7 7

9

9

9

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:2

4 A

M

CTC - INFUSION ADDITIONAND RENOVATION

M2.015068

2/26/16

CONSTRUCTION DOCUMENTS

MECHANICAL NEW PIPINGAND ROOF PLAN

1/8" = 1'-0"1

MECHANICAL NEW WORK

1/4" = 1'-0"3

ADDITION ROOF PLAN

KEYED NOTES

1 ROUTE CONDENSATE PIPE THROUGH ACID NEUTRALIZER AND ALONG FLOOR TOEXISTING FLOOR DRAIN. PROVIDE WALK PROTECTION OVER PIPE WHERE PIPING ISIN WALKWAY.

2 TERMINATE CONDENSATE PIPE OVER EXISTING FLOOR DRAIN.

3 SEAL ALL DUCT, PIPING, CONDUIT, TUBE, ETC. PENETRATIONS THROUGH WALLSAIRTIGHT.

4 PROVIDE DIFFERENTIAL PRESSURE SENSOR IN PIPING AT THIS LOCATION TOCONTROL VFD SPEED OF PUMPS.

5 MOUNT NEW BOILER ON EXISTING CONCRETE PAD. MECHANICALLY CONNECTBOILER TO PAD.

6 EXTEND NEW VENT AND INTAKE PIPE THROUGH ROOF WITH CONCENTRIC VENT KIT.

7 MOUNT NEW HOT WATER PUMPS ON EXISTING STAND.

8 TERMINATE CONDENSATE PIPE OVER ROOF DRAIN. PROVIDE PIPE SUPPORTS ATMINIMUM OF EVERY 6' 0" AND AT ALL CHANGES IN DIRECTION.

9 PAINT ALL NEW PIPING TO MATCH EXISTING COLOR SCHEME.

10 MOUNT NEW CONTROL PANEL ON WALL A MINIMUM OF 48" A.F.F.

#

GENERAL NOTES

1 REFER TO SHEET M0.1 FOR ADDITIONAL NOTES THAT APPLY TO THIS SHEET.

2 FINAL RUNOUTS TO TERMINAL DEVICES SHALL BE 3/4" UNLESS OTHERWISE NOTED.

1/4" = 1'-0"2

BOILER AND HEATING WATER PUMP REPLACEMENT - ALTERNATE 1

Revision Schedule

No. Date Revisions

Page 6: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:2

7 A

M

CTC - INFUSION ADDITIONAND RENOVATION

M3.015068

2/26/16

CONSTRUCTION DOCUMENTS

MECHAINCAL SCHEDULES

ROOFTOP UNIT SCHEDULE

PLAN MARK

MFG MODEL

ELECTRICAL SUPPLY FAN EXHAUST FAN COOLING

REFRIG. COMP. QTY.

GAS HEATING FILTER UNIT SIZE (IN)

OPER. WT.(LB) NOTESVOLT. Hz. PH.

SUPPLY AIRFLOW(CFM)

MIN OSA(CFM) FAN TYPE

ESP(IN-WG)

MOTOR AIRFLOW(CFM)

ESP(IN-WG)

MOTOR TOT. CAP.(BTU/H)

SENS. CAP.(BTU/H)

EAT DB(°F)

EAT WB(°F)

LAT DB(°F)

LAT WB(°F) ROWS FPI

APD(IN-WG)

FACE VEL.(FPM)

TOTAL CAP.(MBH)

EAT DB(°F)

LAT DB(°F) INPUT (MBH) TURN DOWN TYPE

FACE AREA(SF)

APD(IN-WG) L W HHP ECM HP ECM

RTU 2 DAIKIN APPLIED DPS015 460 60 3 3290 3180 SWSI AF 1.60 4 Yes 3850 0.50 1.0 Yes 180198 118717 92.9 73.8 56.0 56.0 6 15 0.20 194 R410A 2 320 7.5 107.5 400 10:1 2 inch MERV 8 18.0 0.05 91 97 56 2670 1, 2, 3, 4, 5, 6, 7

AIR DEVICE SCHEDULE

TYPE MARK MANUFACTURER MODEL STYLE CONNECTION SIZE

FACE

MAX FLOW THROW (FT)MAX NCLEVEL

AIR TERMINAL STATICPRESSURE (IN-WG) MATERIAL FINISH MOUNTING TYPE NOTESLENGTH WIDTH

S-1 TITUS OMNI PLAQUE 6"ø 24" 24" 80 4 30 0.10 STEEL BWE LAY-IN 2

S-2 TITUS OMNI PLAQUE 8"ø 24" 24" 180 12 30 0.10 STEEL BWE LAY-IN 2

S-3 TITUS OMNI PLAQUE 10"ø 24" 24" 420 12 30 0.10 STEEL BWE LAY-IN 2

S-4 TITUS OMNI PLAQUE 10"ø 24" 24" 420 12 30 0.10 STEEL BWE SURFACE MOUNT 1

R-1 TITUS 355FL 35 DEGREE DEFLECTION GRILLE 12"x6" 12" 8" - - 30 0.10 ALUMINUM BWE SURFACE MOUNT 1

R-2 TITUS 355FL 35 DEGREE DEFLECTION GRILLE 12"x10" 20" 8" - - 30 0.10 ALUMINUM BWE SURFACE MOUNT 1

R-3 TITUS 355FL 35 DEGREE DEFLECTION GRILLE 18"x12" 20" 12" - - 30 0.10 ALUMINUM BWE SURFACE MOUNT 1

R-4 TITUS 350 35 DEGREE DEFLECTION GRILLE 22"x22" 24" 24" - - 30 0.10 STEEL BWE LAY-IN 2, 3

E-1 TITUS 350 35 DEGREE DEFLECTION GRILLE 6"ø 24" 24" - - 30 0.10 STEEL BWE LAY-IN 2

E-2 TITUS 350 35 DEGREE DEFLECTION GRILLE 8"ø 24" 24" - - 30 0.10 STEEL BWE LAY-IN 2

E-4 TITUS 350 35 DEGREE DEFLECTION GRILLE 24"x24" 24" 24" - - 30 0.10 STEEL BWE LAY-IN 2

EXHAUST FAN SCHEDULE

PLAN MARK

MANUFACTURER MODEL CFM AREA SERVEDSTATIC PRESSURE

(IN-WG) NOMINAL RPM INLET DbA INLET SONES

ELECTRICAL

SPECIFIC PRODUCT DESCRIPTION LOCATION NOTESMOTOR POWER (HP) VOLTAGE PHASE

EF 5 COOK ACE-B 180C7B 2570 ADDITION 1.0 1152 66 14.0 1.0 120 1 DOWN BLAST, CENTRIFUGAL, DIRECT DRIVE ADDITION ROOF 1

EF 6 COOK GC-124 120 TOILET 127 0.1 900 33 1.6 0.1 120 1 RECESSED CEILING FAN TOILET 127

EF 7 COOK GC-124 120 TOILET 126 0.1 900 33 1.6 0.1 277 1 RECESSED CEILING FAN TOILET 126

EF 8 COOK ACE-B 180C7B 1000 ADDITION 1.0 1152 66 14.0 1.0 120 1 DOWN BLAST, CENTRIFUGAL, DIRECT DRIVE ADDITION ROOF 1, 2

NOTES:1. PROVIDE WITH PACKAGED CONTROL SYSTEM TO CONTROL RTU, ASSOCIATED VAV BOXES, EF-5, EF-8, P-1, P-2, AND B-1.2. PROVIDE WITH 18" SEISMIC ROOF CURB.3. REFER TO MEP1.0 FOR ADDITIONAL ELECTRICAL REQUIREMENTS.4. PROVIDE WITH DISCONNECT SWITCH AND FIELD POWERED 115V GFI OUTLET.5. PROVIDE WITH ONE VARIABLE SPEED COMPRESSOR AND ONE FIXED SPEED COMPRESSOR.6. PROVIDE WITH DIFFERENTIAL ENTHALPY CONTROLLED 100% ECONOMIZER.7. PROVIDE WITH OUTSIDE AIR MEASURING STATION.

NOTES:1. PROVIDE WITH INTEGRAL BALANCING DAMPER.2. PROVIDE WITH EARTHQUAKE CLIPS.3. PROVIDE WITH RETURN AIR BOOT, REFER TO DETAIL 11/M4.0 FOR REQUIREMENTS.

NOTES:1. PROVIDE WITH SEISMIC ROOF CURB, BIRD SCREEN, AND MOTORIZED DAMPER.2. PROVIDE WITH COMPATIBLE FLASHING TO MATCH EXISTING METAL ROOF.

AIR TERMINAL UNIT SCHEDULE W/ HW HEAT

PLAN MARK

MANUFACTURER MODEL ASSOCIATED RTU UNIT SIZE

OUTLET SIZE CFM HOT WATER HEAT COIL

APD (IN WC)

MAX NC LEVELS

NOTESWIDTH HEIGHT MAX MIN CAPACITY (MBH) CFMEAT DB

(°F)LAT DB

(°F) EWT (°F) LWT (°F) GPM ROWS RADIATED DISCHARGE

CAV 1 TITUS DESV AC-1 8 12" 10" 630 630 20.7 630 55.0 85.0 180 132.4 0.9 2 .25 20 19 1

VAV 2 TITUS DESV AC-1 8 12" 10" 765 230 6.7 240 55.0 80.3 180 135.3 0.3 1 .15 24 22 1

VAV 3 TITUS DESV RTU-2 9 14" 13" 880 270 15.0 550 55.0 80.0 180 148.5 1.0 1 .1 22 19 1

VAV 4 TITUS DESV RTU-2 10 14" 13" 1010 310 15.6 570 55.0 80.0 180 149.6 1.1 1 .12 24 20 1

VAV 5 TITUS DESV RTU-2 92 14" 13" 800 240 9.9 300 55.0 85.2 180 146.7 0.6 1 .08 20 18 1

NOTES:1. CONTROLLER SHALL BE COMPATIBLE WITH NEW SMALL BUILDING CONTROL SYSTEM. COORDINATE REQUIREMENTS WITH RTU MANUFACTURER.

FAN FILTER AIR TERMINALS

TYPE MARK MANUFACTURER MODEL CONNECTION SIZE

FACE

FLOW FAN HP FILTER TYPEAIR TERMINAL STATIC

PRESSURE (IN-WG) MATERIAL FINISH MOUNTING TYPE WEIGHT (LBS) NOTESLENGTH WIDTH

FFU-1 PRICE FFU-HE 16"x20" 24" 24" 235 1/3 HEPA 0.30 STAINLESS STEEL BWE SURFACE MOUNT 53 1, 2

FFU-2 PRICE FFU-HE 16"x20" 24" 24" 270 1/3 HEPA 0.30 STAINLESS STEEL BWE SURFACE MOUNT 53 1, 2

FFU-3 PRICE FFU-HE 16"x20" 24" 48" 370 1/3 HEPA 0.30 STAINLESS STEEL BWE SURFACE MOUNT 76 1, 2

FFU-4 PRICE FFU-HE 16"x20" 24" 48" 370 1/3 HEPA 0.30 STAINLESS STEEL BWE SURFACE MOUNT 76 1, 2

FFU-5 PRICE FFU-HE 16"x20" 24" 48" 370 1/3 HEPA 0.30 STAINLESS STEEL BWE SURFACE MOUNT 76 1, 2

NOTES:1. PROVIDE WITH ECM MOTOR FOR CONSTANT CFM CONTROL AND ROOM-SIDE REPLACEABLE HEPA FILTER.2. PROVIDE WITH DISCONNECT SWITCH.

BOILER SCHEDULE (ALTERNATE 1)

PLAN MARK

MANUFACTURER MODEL INPUT RATE (MBH) MAXIMUM WORKING PRESSURE (PSIG) FUEL TYPE RELIEF VALVE SETTING (PSIG) EWT (°F) LWT (°F) FLOW (GPM)MINIMUM FLOW

(GPM) HEAD LOSS (FT. HEAD) FULL LOAD EFFICIENCY OPERATING WEIGHT (LBS) CAPACITY (GAL) MODULATION VOLTS/PH. VENTILATION AIR DIAMETER NOTES

HWB 001 RAYPAK 850A 850 160.0 NATURAL GAS 60.0 140.0 180.0 41 41 10.0 94% 628 5.8 5:1 120/1 6" 1, 2, 3

HEATING WATER PUMP SCHEDULE (ALTERNATE 1)

PLAN MARK

SERVICE MANUFACTURER MODEL TYPE GPMHEAD LOSS

(FT-HD) PUMP RPM

ELECTRICAL DATA (NOTE 1)

NOTESMOTOR HP VOLTAGE PHASE

HWP 001 BOILER SYSTEM BELL AND GOSSETT 1.5AB IN-LINE MOUNTED CENTRIFUGAL PUMP 41.0 50 1725 2.0 480 3 1

HWP 002 BOILER SYSTEM BELL AND GOSSETT 1.5AB IN-LINE MOUNTED CENTRIFUGAL PUMP 41.0 50 1725 2.0 480 3

NOTES:1. PROVIDE WITH 60 PSIG PRESSURE RELIEF VALVE.2. PROVIDE WITH FACTORY MOUNTED DIRECT VENT KIT.3. PROVIDE WITH CONDENSATE NEUTRALIZATION KIT.

NOTES:1. PROVIDE WITH INVERTER READY MOTOR FOR VFD.

Revision Schedule

No. Date Revisions

Page 7: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

HWS

HOSE-ENDVALVE

HWR

DISCHARGE DUCT

2-WAY CONTROL VALVE

CIRCUIT SETTERM.A.V.

AIR VALVE

AIR TERMINAL BOX

HEATING COIL

VAV

BALL VALVE

NOTE: PROVIDE INSULATION ON ALL VALVES, FITTINGS, &

DURING COOLING CYCLE.EXPOSED COIL TO PREVENT CONDENSATION

BASERAIL

NEOPRENE GROMMET

RELIEF VALVE

THERMOMETER (TYP.)

PRESSURE GAGE

SHUT-OFF VALVE

FLUE VENT EXHAUST (BY V.C)

DRAIN LINE

FLOOR

FLOOR DRAIN6" THICK HOUSEKEEPING PAD

UNION

AQUASTAT

INTAKE VENT (BY V.C.)BOILER PUMP

NOTE: PROVIDE CONDENSATE NEUTRALIZATION KIT.

BOILER

OPENING & FRAMING BYMECHANICAL CONTRACTOR

COMBUSTION AIRINTAKE. VENT PIPETYPE: STAINLESS STEEL

EXHAUSTAIR. VENTPIPE TYPE:STAINLESS STEEL.

ROOF

SCREEN PERMANUFACTURER'SREQUIREMENTS

PROVIDE 2" AIR GAP ALLAROUND VENT PIPE THRUROOF.

OPENING & SEALINGMECHANICAL CONTRACTOR

3' MIN

3' MIN

1' MIN

SEE ARCHITECTURALPLANS FOR ROOFFLASHING REQUIREMENTS.

BACKDRAFT DAMPER

INTEGRAL GRILLE

FILTER

DISCHARGE DUCT

AIR FLOW

AIR FLOW

GALVANIZED HOUSING

ADJUSTABLEMOUNTINGBRACKETS

FORWARD CURVEINJECTION MOLDED FAN

PIPE SIZE SAMEAS UNIT DRAINCONNECTION

FURNACEDRAIN PAN

1/4" BELOW TOPOF DRAIN PAN

OPEN END

TERMINATE ATROOF DRAIN

NOTE:DRAIN PIPING DETAIL IS TYPICALFOR ALL CONDENSATE DRAINCONNECTIONS ON RTU

NEGATIVE STATIC PRESSUREAT DRAIN CONNECTIONX=1" + (1"FOR EACH 1" OF MAX. NEGATIVE STATIC PRESSURE)Y=HALF OF 'X'

"X"

"Y"

CONDUIT

WOOD NAILER(TYP.)

NON-FERROUSSCREW OR BOLTS

14" MINIMUMABOVE ROOF

MOTORIZED BACKDRAFTDAMPER EXHAUST DUCT - SEE

FLOOR PLAN FOR SIZE

PREFAB. INSUL. CURBWITH WOOD NAILER (SEEARCHITECTURAL DRAWINGSFOR CURB INSTALLATIONDETAIL)

FLASHING

CURB CAP MUSTBE LEVEL

EXHAUST FAN

BOILER

THREADED CAP/TEST PORT

UNION

CONNECT TO EQUIPMENT

REFER TO PLANSFOR PIPE SIZE

TERMINATE VENT TO ATMOSPHERE, TURNDOWN WITH INSECT SCREEN

GAS REGULATOR VENT LINE

SLOPE TOPREVENTMOISTUREBUILD-UP.

GAS SUPPLY REFERTO PLANS FOR SIZE

SHUT-OFF VALVE

DRIP LEG

GAS PRESSUREREGULATOR WITH VENT

MANUAL VENT

6" MIN1/2" MIN IPS

SUPPLY ORRETURN MAIN

1" MIN DRAIN4" MIN

NOTES:1. TYPICAL FOR ALL HIGH POINTS, LOW POINTS AND POCKETS.2. LOW POINT DRAINS SHALL BE 2" MINIMUM ON 6" AND LARGER MAINS.

1" DUCT LINER

24"x24" R.A. GRILL(TYP.) OR AS NOTEDOTHERWISE

22"

MINIMUM

12"

10"x22"OPENINGEXCEPT ASNOTED

SUPPORTFROMSTRUCTUREABOVE.

FACE TOWARDS RETURN AIR DUCTWHERE POSSIBLE. TURN AWAYFROM INTERIOR WALLS WHEREOUTLET IS CLOSER THAN

FASTEN FLEXDUCT TO ELBOW.

FLEX DUCT SEE PLANSFOR SIZES.

CEILING TEE WIRE SUPPORT

CEILING TEE

SUPPLY AIR DEVICESEE PLANS ANDSCHEDULE FOR TYPE.

RIGID ROUND RADIUS ELBOW,FASTEN TO NECK OF SUPPLY AIRDEVICE, SEE PLANS FOR SIZES.

ONE ONEACH SIDEOF HANGAR.

HOLD IN PLACE WITHMINIMUM OF 3 CLAMPS.SEE MANUFACTURER'SRECOMMENDATIONS.

VERTICAL SUPPORT

SHIELD ORSADDLE AS REQUIRED

COVER WITHINSULATION ANDVAPOR BARRIER

PIPE CLAMPDIRECT TO PIPE

STIFFENER CLAMP

HANGER ROD

ROD STIFFENER(WHERE REQUIRED)

SWAY BRACE

SWIVEL FASTENER(TYPICAL)

AS REQUIRED

ROD SIZED FORLOAD AND SPACING

CLEVIS PIPE HANGER

PIPE INSULATIONAS SPECIFIED

PIPE SIZES 1/2"-10"

PROTECTIVE INSULATIONSHIELD

NOTES:1. PIPE HANGERS SHALL BE OVERSIZED AS REQUIRED TO ACCOMODATE. THICKNESS OF INSULATIONSPECIFIED. HANGAR SHALL NOT COME INTO CONTACT WITH THE INSULATION DIRECTLY, EITHER AT THEVERTICAL YOKE OR AT THE POINT OF SUPPORT. FOR REQUIREMENTS ON INSULATION SHIELD USED WITH PIPEHANGERS, SEE SPECIFICATIONS.

1'-0"

CLEVIS CROSS BRACE

HANGER

INSULATED PIPE HANGER LATERAL PIPING RESTRAINT

LONGITUDINAL PIPING RESTRAINT

JOIST STRUCTURE

JOIST CLAMP

JOIST CLAMP

REFER TO ARCHITECTURALDRAWINGS FOR ROOF TYPEAND FLASHINGREQUIREMENTS.

SEISMIC CURB

WOOD NAILER

ALUMINUM COUNTERFLASHING WITH HEMMEDDRIP EDGE

WEATHER SEAL

PACKAGED ROOFTOP UNIT

NEOPRENE GASKET

TYPICAL ROOFTOP UNIT

6" THICK BATT INSULATION

(2) LAYERS OF3/4" TYPE "X"DRYWALL FORACOUSTICS

2"x2"x1/8" SUPPORTANGLE IRON AROUNDINSIDE OF CURB WITH(2) INTERMEDIATEANGLES CENTEREDEQUALLY.

3" MIN THICKCONCRETE

2" MIN ANCHOREMBEDMENT

1/4" DRILLCURB

DETAIL B

1/4" X 3-1/4" WEDGE-TYPECONCRETE ANCHOR MINIMUM 3PER LONG SIDES AND 2 PERSHORT SIDES OF CURB.

EQUIPMENT

DETAIL A

STAINLESS STEEL 1 1/2"WIDE STRAP 16" LONG;INSTALL 3 ON LONG SIDES OFCURB, 2 ON SHORT SIDES OFCURB.

SEE DETAIL "A"

SEE DETAIL "B"

BEND STRAP UP AFTERRTG IS SET AND ATTACHTO RAIL.

(4) #12-14X1 1/4" HWH #2 STAINLESSSTEEL TEK SCREWS THROUGHCURB TO ATTACH STRAP TO CURB.ATTACH STRAP AT VERTICLE METALSTRUT OF CURB.

(4) #12-14X1 1/4" HWH #2STAINLESS STEEL TEKSCREWS.

WOOD NAILER

NOTES:1. CONTRACTOR SHALL SUBMIT SEISMIC DETAIL DRAWINGS BASED ON ACTUAL EQUIPMENT AND CURBSELECTED.

NEOPRENEGASKET

MULTI-PORTPRESSURE GAUGE(0-100 PSIG)

SNUBBER (TYP.)

VERTICAL PUMP

TRIPLE DUTYVALVE

FLEXIBLE CONNECTION

CONCENTRIC INCREASER(WHERE REQUIRED)

SEISMIC RESTRAINT ECCENTRIC REDUCER(AS REQUIRED)

SHUT-OFF VALVE

SUCTION DIFFUSER W/STRAINER

FLEXIBLE CONNECTION

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:2

8 A

M

CTC - INFUSION ADDITIONAND RENOVATION

M4.015068

2/26/16

CONSTRUCTION DOCUMENTS

MECHANICAL DETAILS

NOT TO SCALE1AIR TERMINAL BOX (2-WAY VALVE) DETAIL

NOT TO SCALE8BOILER ANCHORING DETAIL

NOT TO SCALE3BOILER PIPING DETAIL

NOT TO SCALE4BOILER VENT DETAIL

NOT TO SCALE5CEILING MOUNTED EXHAUST FAN DETAIL

NOT TO SCALE6CONDENSATE DRAIN PIPING DETAIL1

NOT TO SCALE7EXHAUST FAN DETAIL

NOT TO SCALE2GAS CONNECTION TO HOT WATER BOILERS DETAIL

NOT TO SCALE9

MANUAL VENTS AND DRAINSNOT TO SCALE

11RETURN AIR BOOT

NOT TO SCALE12

TYPICAL LAY-IN SQUARE DIFFUSER

NOT TO SCALE13PIPING SUPPORT

NOT TO SCALE14ROOFTOP UNIT CURB DETAIL

12" = 1'-0"10

VERTICAL PUMP PIPING DETAIL

Revision Schedule

No. Date Revisions

Page 8: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

EXP. TANKET-1

AIRSEPARATOR

AS-1

HOT WATER BOILERB-1

P

1

EXISTING FLOOR DRAIN

CONDENSATE NEUTRALIZER KIT

P

2

THERMOMETER (TYP.)

BALL VALVE (TYP.)

STRAINER (TYP.)

UNION (TYP.)

BALANCING VALVE (TYP.)

TEMPERATURE/PRESSURE GAUGE (TYP.)

DRAIN (TYP.)

PRESSURE RELIEF VALVE PIPED TO FLOOR DRAIN(SET AT 60 PSI)

NOTE: SEE INLINE PUMP DETAIL ON SHEETM4.0 FOR ARRANGEMENT OF SPECIALTIES

HWS

HWR

HWS

SHOT FEEDER

2" 2"

2"

2"

2" 2"

3/4"

3/4"

2"

1/2"

TO SYSTEM

S

FAN FILTER

SAEA

RA

MEXHAUST AIR DAMPER

SPACE DIFFERENTIAL PRESSURE

H L

SEQUENCE OF OPERATION FOR COMPOUNDING PHARMACY

1. MAINTAIN POSITIVE AIR PRESSURE (0.01 INCH WATER COLUMN) BETWEEN THEPHARMACY AND THE ANTE ROOM BY MODULATING THE FAST ACTING MOTORIZEDDAMPER. PROVIDE TSI MODEL RPC30 OR APPROVED EQUAL TO CONSTANTLYMONITOR THE DIFFERENTIAL AIR PRESSURE BETWEEN THE PHARMACY AND THEANTE ROOM. THE CONTROLLER SHALL HAVE A LOCAL VISUAL MEANS TOINDICATE WHENEVER POSITIVE DIFFERENTIAL PRESSURE IS NOT MAINTAINED.

2. FFU-3 AND FFU-4 WILL BE PROVIDED WITH INTEGRAL CONTROLS TO MEETSCHEDULED SUPPLY AIRFLOW REQUIREMENTS.

RPC-1

1. MAINTAIN POSITIVE AIR PRESSURE (0.01 INCH WATER COLUMN) BETWEEN THE ANTEROOM AND THE HAZARDOUS DRUG STORAGE ROOM BY MODULATING THE FASTACTING MOTORIZED DAMPER. PROVIDE TSI MODEL RPC30 OR APPROVED EQUAL TOCONSTANTLY MONITOR THE DIFFERENTIAL AIR PRESSURE BETWEEN THEANTE ROOM AND THE HAZARDOUS DRUG STORAGE ROOM. THE CONTROLLER SHALLHAVE A LOCAL VISUAL MEANS TO INDICATE WHENEVER POSITIVE DIFFERENTIALPRESSURE IS NOT MAINTAINED.

2. FFU-1 WILL BE PROVIDED WITH INTEGRAL CONTROLS TO MEET SCHEDULED SUPPLYAIRFLOW REQUIREMENTS.

RPC-2

1. MAINTAIN POSITIVE AIR PRESSURE (0.01 INCH WATER COLUMN) BETWEEN THEANTE ROOM AND THE POSITIVE PRESSURE MIXING ROOM BY MODULATING THEFAST ACTING MOTORIZED DAMPER. PROVIDE TSI MODEL RPC30 OR APPROVEDEQUAL TO CONSTANTLY MONITOR THE DIFFERENTIAL AIR PRESSURE BETWEENTHE ANTE ROOM AND THE POSITIVE PRESSURE MIXING ROOM. THE CONTROLLERSHALL HAVE A LOCAL VISUAL MEANS TO INDICATE WHENEVER POSITIVEDIFFERENTIAL PRESSURE IS NOT MAINTAINED.

2. FFU-2 WILL BE PROVIDED WITH INTEGRAL CONTROLS TO MEET SCHEDULEDSUPPLY AIRFLOW REQUIREMENTS.

RPC-3

1. MAINTAIN NEGATIVE AIR PRESSURE (0.01 INCH WATER COLUMN) BETWEEN THE ANTEROOM AND NEGATIVE PRESSURE MIXING ROOM BY MODULATING THE FASTACTING MOTORIZED DAMPER. PROVIDE TSI MODEL RPC30 OR APPROVED EQUAL TOCONSTANTLY MONITOR THE DIFFERENTIAL AIR PRESSURE BETWEEN THEANTE ROOM AND THE NEGATIVE PRESSURE MIXING ROOM. THE CONTROLLER SHALLHAVE A LOCAL VISUAL MEANS TO INDICATE WHENEVER POSITIVE DIFFERENTIALPRESSURE IS NOT MAINTAINED.

2. FFU-5 WILL BE PROVIDED WITH INTEGRAL CONTROLS TO MEET SCHEDULED SUPPLYAIRFLOW REQUIREMENTS.

RPC-4

SEQUENCE OF OPERATION FOR BOILER PLANT (ALTERNATE 1)

NEW BOILER 'B-1' SHALL MODULATE ITS FIRING VIA ITS ONBOARD CONTROLLER TO MAINTAIN LOOP WATERTEMPERATURE. TEMPERATURES SHALL BE RESET LINEARLY FROM 180°F (ADJ) WHEN IT'S 150°F(ADJ) OUTSIDE TO 120°F(ADJ) WHEN IT'S 70°F(ADJ) OUTSIDE. PROVIDE AN ALARM AND STATUS TO THE NEW SMALL BUILDING CONTROLLER.

NEW PUMPS, P-1 AND P-2, ARE TO BE CONTROLLED IN A PRIMARY STAND BY CONFIGURATION. THE PRIMARY PUMPSHALL RUN CONTINUOUSLY. UPON A FAILURE OF THE PRIMARY PUMP, AS SENSED BY A CT SWITCH, THE STAND-BYPUMP SHALL START AND AN ALARM SHALL BE SENT TO THE NEW SMALL BUILDING CONTROLLER. THE PRIMARY STAND-BY DESIGNATION SHALL BE ALTERNATED WEEKLY.

CT

EA

M

BI - FAN STATUS

BO - FAN START/STOP

TM

TDASA

AO - ZONE DAMPER

AI - DISCHARGE AIR TEMPAI - AIR FLOW

AO - REHEATING VALVE

HW

M

HWS HWR

AI - ZONE SETPOINT ADJUST

AI - ZONE TEMP

BI - ZONE OVERIDECO2

AI - ZONE CARBON DIOXIDE PPM

GENERAL

THE ROOFTOP UNIT AND VAV BOXES SHALL BE CONTROLLED BY A PACKAGED CONTROL SYSTEM THAT COMMUNICATESBETWEEN THE BOXES AND RTU.

THE RTU AND VAV BOXES SHALL COMMUNICATE WITH THE INTEGRATED CONTROL SYSTEM AND ACCEPT SCHEDULINGAND SETPOINT UPDATES FROM THE SYSTEM MANAGER. RTU AND VAV BOX CONTROL SHALL BE HANDLED LOCALLY ATTHE UNIT LEVEL SO THAT THEY ARE NOT DEPENDENT ON NETWORK COMMUNICATIONS. ALL DEVICES SHALL BEAUTOMATICALLY PLACED UNDER OCCUPIED OR UNOCCUPIED OPERATION, WITH OCCUPIED AND UNOCCUPIED HEATINGAND COOLING TEMPERATURE SETPOINTS AND AIR FLOWS. AN ADJUSTABLE SCHEDULE SHALL BE SET AT THE SYSTEMINTERFACE, INCLUDING WEEKEND AND HOLIDAY SCHEDULES, MULTIPLE OCCUPANCY PERIODS PER DAY, AND MIDNIGHTCROSSOVER AS DETERMINED BY THE OWNER. THE INTEGRATED SYSTEM CONTROLLER SHALL STORE ANDGRAPHICALLY DISPLAY TREND INFORMATION FOR ALL DEVICES.

SUPPLY FAN CONTROL

THE SUPPLY FAN RUNS CONTINUOUSLY. SUPPLY FAN VFD WILL MODULATE THE FAN SPEED BASED ON A PID INTERNALTO THE RTU UNIT CONTROLLER MAINTAINING A STATIC PRESSURE SET POINT SENT FROM THE SYSTEM INTERFACE.THE STATIC PRESSURE SET POINT WILL BE RESET AS TO ENSURE THAT AT LEAST ONE VAV BOX DAMPER IS GREATERTHAN 95% (ADJUSTABLE) OPEN AND NO VAV BOXES ARE IN A STARVED CONDITION. THE SYSTEM SHALL ENSURE THIS BYUPDATING THE PRESSURE SET POINT BETWEEN A USER DEFINED MINIMUM AND MAXIMUM DUCT PRESSURE SET POINTEVERY 10 MINUTES.

SAFETIES

ALL SAFETY DEVICES SHALL BE INTERLOCKED TO THE RTU CONTROL CIRCUIT TO INITIATE A UNIT ALARM THAT WILL BESENT TO THE SYSTEM INTERFACE THROUGH THE NETWORK. FAULT CONDITIONS SHALL SHUT THE UNIT DOWN ANDSTOP THE SUPPLY FAN OPERATION. ALARMS HAVE THE CAPABILITY OF BEING RELAYED REMOTELY VIA EMAIL OR TEXTMESSAGE FROM THE SYSTEM INTERFACE, IF ENABLED AND CONNECTED TO THE BUILDING LAN.

HEAT/COOL CHANGE OVER

BY DEFAULT, THE CONTROL TEMPERATURE WILL BE USED BY THE RTU UNIT CONTROLLER TO DETERMINE THEAPPROPRIATE HEAT/COOL MODE AND WILL BE EQUAL TO THE “AGGREGATE” SPACE TEMPERATURE. IN MOST CASES, THEAGGREGATE SPACE TEMPERATURE WILL BE THE WARMEST ZONE TEMPERATURE ASSIGNED TO THE RTU. HOWEVER, IFANY ZONE TEMPERATURE DROPS BELOW THE OCCUPIED HEATING SETPOINT OF THE RTU, THIS ZONE TEMPERATUREWILL BE USED AS THE AGGREGATE. WHEN THE CONTROL TEMPERATURE RISES ABOVE THE RTU’S OCCUPIED COOLINGSETPOINT OF 65 (ADJUSTABLE), THE RTU WILL TRANSITION INTO A COOLING MODE AND MODULATE/STAGE IT’S COOLINGTO MAINTAIN THE DISCHARGE COOLING SETPOINT. WHEN THE CONTROL TEMPERATURE DROPS BELOW THE OCCUPIEDHEATING SETPOINT OF 63 (ADJUSTABLE), THE RTU WILL TRANSITION INTO A HEATING MODE AND MODULATE/STAGE THEHEATER TO MAINTAIN THE DISCHARGE HEATING SETPOINT. THE PURPOSE OF THE DEFAULT OCCUPIED SETPOINTS ISTO ENSURE THAT THE RTU WILL CONTINUALLY OPERATE IN THE COOLING MODE DURING OCCUPIED HOURS. IF THECONTROL TEMPERATURE IS INBETWEEN THE RTU’S OCCUPIED HEATING AND COOLING SETPOINTS, THE RTU WILL BEPUT INTO A “FAN ONLY” MODE,IN WHICH IT IS ONLY PROVIDING VENTILATION AIR.

DISCHARGE TEMPERATURE CONTROL

THE RTU CONTROLLER WILL MONITOR THE SUPPLY AIR TEMPERATURE AND OPERATE THE HEATING AND COOLINGCONTROLS IN SEQUENCE AS REQUIRED TO MAINTAIN A DISCHARGE AIR TEMPERATURE AT THE CURRENT DISCHARGEAIR SETPOINT.

WHEN IN COOLING MODE, THE RTU WILL SEQUENCE THE COOLING OUTPUTS TO MAINTAIN A DISCHARGE SETPOINT OF 55DEGREES F (ADJUSTABLE). GAS HEATING WILL AUTOMATICALLY BE INITIATED TO MAINTAIN A DISCHARGE AIRTEMPERATURE AT THE DISCHARGE COOLING SETPOINT WHEN THE MIXED AIR TEMPERATURE OF THE UNIT DROPSBELOW THIS VALUE. WHEN IN HEATING MODE, THE RTU WILL SEQUENCE HEATING TO MAINTAIN A DISCHARGE SETPOINTOF 85 DEGREES F (ADJUSTABLE). WHEN THE OUTSIDE AIR TEMPERATURE IS BELOW 65°F (ADI) AND ALL THE VAV BOXESARE AT THEIR MINIMUM COOLING POSITION OR ARE IN HEATING MODE, THE SYSTEM SHALL RESET THE SUPPLY AIRTEMPERATURE SET POINT INCREMENTALLY UP TO 65°F (ADI) AS THE OUTSIDE AIR TEMPERATURE REDUCES FROM 65°F(ADI) TO 55°F (ADI). IF ANY ZONE IS UNABLE TO MEET IT'S COOLING MODE SET POINT, THE SUPPLY AIR TEMPERATURESHALL BE REDUCED INCREMENTALLY TO 55°F YBUTK SPACE IS SATISFIED.

ECONOMIZER

WHEN THE OUTSIDE AIR ENTHALPY IS LOWER THAN THE RETURN AIR ENTHALPY, THE RTU WILL MODULATE THE OUTSIDEAIR DAMPER AND THE RETURN AIR DAMPER AS REQUIRED TO MAINTAIN THE DISCHARGE AIR TEMPERATURE AT THECURRENT DISCHARGE SETPOINT. IF UNABLE TO MEET THE DISCHARGE SETPOINT SOLELY WITH THE ECONOMIZER, THERTU WILL BEGIN TO ENGAGE MECHANICAL COOLING WITH THE OUTSIDE AIR DAMPERS OPEN.

POWERED EXHAUST FAN

RTU EXHAUST FAN SHALL MODULATE BASED UPON BUILDING PRESSURE SENSOR. IF THE ECONOMIZER DAMPER ISCLOSED OR THE BUILDING PRESSURE IS BELOW SETPOINT AND THE EXHAUST FAN SPEED IS BELOW 5% (ADJUSTABLE)FOR A PERIOD OF 120 SECONDS (ADJUSTABLE), THE EXHAUST FAN SHALL BE TURNED OFF UNTIL BUILDING PRESSURE ISRESTORED OR THE ECONOMIZER DAMPER RETURNS TO AT LEAST MINIMUM POSITION. BUILDING PRESSURE SHALL BEMAINTAINED AT A NEGATIVE .01" WG DURING OCCUPIED MODE AND NEUTRAL DURING UNOCCUPIED MODE.

MORNING WARM-UP

MORNING WARM UP SHALL BE INITIATED IF THE CONTROL TEMPERATURE IS BELOW THE MORNING WARM UP SETPOINTWHEN THE RTU ENTERS THE OCCUPIED MODE. DURING THIS TIME, THE RTU SHALL MAINTAIN AN ADJUSTABLEDISCHARGE HEATING SETPOINT UNTIL THE MORNING WARM-UP SETPOINT HAS BEEN SATISFIED. THE RTU CONTROLLERSHALL KEEP THE OA DAMPERS CLOSED FOR AN ADJUSTABLE AMOUNT OF TIME AT THE BEGINNING OF THE OCCUPANCYPERIOD.

EXHAUST FAN EF-6 AND EF-7

EXHAUST FAN EF-6 AND EF-7 SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS AND SHALL BE OFF WHEN BUILDING IS INUNOCCUPIED MODE.

EXHAUST FANS EF-5 AND EF-8

EXHAUST FANS EF-5 AND EF-8 SHALL RUN CONTINUOUSLY DURING OCCUPIED HOURS AND SHALL BE INTERLOCKED WITHRTU-1'S SCHEDULE. WHEN RTU-1 IS IN UNOCCUPIED MODE, THE FANS SHALL BE OFF.

GENERAL

THE CONTROLLER MODULATES THE PRIMARY AIR DAMPER OF THE TERMINAL BOX FOR COOLING AND MODULATESTHE HOT WATER VALVE FOR HEATING. THE AHU MUST PROVIDE COOL SUPPLY AIR DURING OCCUPIED TIMES. THECURRENT SETPOINT WILL HOLD THE VALUE OF ONE OF THE FOLLOWING DETERMINED BY THE SCHEDULE (ADJUSTABLE)AND HEATING OR COOLING MODE: OCCUPIED COOLING SETPOINT, OCCUPIED HEATING SETPOINT, UNOCCUPIED COOLINGSETPOINT, OR UNOCCUPIED HEATING SETPOINT. THE NIGHT COOL SETPOINT AND NIGHT HEAT SETPOINT ARE SET TO THESAME VALUE OF THE PARENT AHU.

THE CONTROL FLOW MINIMUM AND MAXIMUM WILL HOLD THE VALUE EITHER THE COOL FLOW MINIMUM AND MAXIMUM(ADJUSTABLE) OR THE HEAT FLOW MINIMUM AND MAXIMUM (ADJUSTABLE), DETERMINED BY THE COOLING OR HEATINGMODE.

COOLING MODE

THE CONTROLLER WILL TRANSITION INTO COOLING MODE WHEN THE CONTROL TEMP IS ABOVE THE CURRENT SETPOINT.THE CONTROLLER MODULATES THE PRIMARY AIR DAMPER OF THE TERMINAL BOX BETWEEN THE COOL FLOW MINIMUMAND COOL FLOW MAXIMUM TO MAINTAIN THE ROOM TEMPERATURE SETPOINT. IF THE DEMAND FOR COOLINGINCREASES, THE FLOW SETPOINT IS INCREASED. THE HOT WATER CONTROL VALVE IS IN THE FULL BY-PASS POSITIONDURING COOLING MODE. IF THE RTU SUPPLY TEMPERATURE IS GREATER THAN THE CONTROL TEMP, THE FLOW SETPOINTIS OVERRIDDEN BY THE SYSTEM MANAGER TO MAINTAIN ITS MINIMUM VALUE.

HEATING MODE

THE CONTROLLER WILL TRANSITION INTO HEATING MODE WHEN THE CONTROL TEMP IS BELOW THE CURRENT SETPOINT.THE CONTROLLER SETS THE PRIMARY AIR DAMPER OF THE TERMINAL BOX TO THE HEAT FLOW MINIMUM AND MODULATESTEH HOT WATER VALVE TO MAINTAIN THE ROOM TEMPERATURE SETPOINT. THE VALVE SHALL MODULATE TO MAINTAIN THEDISCHARGE AIR SETPOINT. IF THE ROOM TEMPERATURE SETPOINT IS NOT MAINTAINED AT OR ABOVE THE CURRENTSETPOINT, THE PRIMARY AIR DAMPER SHALL MODULATE OPEN AND THE HEATING CONTROLS SHALL MODULATE THEHEATING VALVE TO MAINTAIN THE DISCHARGE TEMPERATURE SETPOINT. IF THE RTU IS PROVIDING HEAT AND THE DATRISES ABOVE 85°F, THE VAV REHEAT WILL BE OVERRIDDEN TO OFF BY THE SYSTEM MANAGER TO PREVENT AN EXCESSIVELYHOT LEAVING AIR TEMPERATURE.

OCCUPIED/UNOCCUPIED MODES

OCCUPIED/UNOCCUPIED MODES SHALL BE DETERMINED VIA AN ADJUSTABLE SCHEDULE. THE ZONE SENSORS SHALL BEPROVIDED WITH AN OVERRIDE BUTTON TO ALLOW AN OCCUPANT TO CHANGE THE UNIT TO THE OCCUPIED MODE IF IT ISCURRENTLY IN THE UNOCCUPIED MODE. THE OVERRIDE TIME SHALL BE ADJUSTABLE BY THE OWNER AND SHALL BE SETDURING COMMISSIONING OF THE SYSTEM.

RTU-1 SEQUENCE OF OPERATION SINGLE DUCT HOT WATER REHEAT SEQUENCE OF OPERATION

EXHAUST FANS SEQUENCE OF OPERATION

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:2

8 A

M

CTC - INFUSION ADDITIONAND RENOVATION

M5.015068

2/26/16

CONSTRUCTION DOCUMENTS

MECHANICAL CONTROLSAND SCHEMATICS

NOT TO SCALE1

MECHANICAL HEATING SCHEMATIC - ALTERNATE 1

NOT TO SCALE4FFU CONTROLS SCHEMATIC

Revision Schedule

No. Date Revisions

NOT TO SCALE5EXHAUST FAN CONTROLS DIAGRAM

NOT TO SCALE6

VARIABLE AIR VOLUME TERMINAL UNIT CONTROLSDIAGRAM

Page 9: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

A.9 B.8 C.8 D E

R3

R2

R1

7

6

5

C

9

4.5

4

3

B

1

MEP1.0

2

MEP1.0

3

MEP1.0

5

MEP1.0

8

8.1

8.3

6.5

7

MEP1.0

10

MEP1.0

WAP,ETR

8

MEP1.0

3

MEP1.1

2

MEP1.1

5

MEP1.1

4

MEP1.1

8

MEP1.1

6

MEP1.1

7

MEP1.1

1

MEP1.1

11

MEP1.0

10

MEP1.1

6

MEP1.0

2

2

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:3

0 A

M

CTC - INFUSION ADDITIONAND RENOVATION

MEP0.015068

2/26/16

CONSTRUCTION DOCUMENTS

REFLECTED CEILING PLAN

1/4" = 1'-0"1

REFLECTED CEILING PLAN

GENERAL NOTES

1 REFER TO INDIVIDUAL DISCIPLINES FOR LEGOND AND SYMBOLS.

Revision Schedule

No. Date Revisions

1 Date 1 ADDENDUM 1

2 03/10/16 ADDENDUM 2

Page 10: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

A.9B

QUADREC

QUADREC

LIGHT SWITCHNURSE CALL

INFUSION BAY

109

VACUUM OXYGEN

FUTURE MONITORVACUUMSLIDE

2' -

10 1

/2"

1' -

6"

QUADREC

QUADREC

LIGHT SWITCH

NURSE CALL

INFUSION BAY

111

VACUUM

OXYGEN

FUTURE MONITOR

VACUUMSLIDE

2' -

10 1

/2"

1' -

6"

7

QUADREC

QUADREC

LIGHT SWITCH

88.18.3

NURSE CALL

INFUSION BAY

113

VACUUM

OXYGEN

FUTURE MONITORVACUUMSLIDE

1' -

6"

2' -

10 1

/2"

4' -

0"

GLOVES AND SHARPS

C.8

QUADREC

QUADREC

LIGHT SWITCH

NURSE CALL

INFUSION BAY

129

OXYGEN

VACUUM

VACUUMSLIDE

2' -

10 1

/2"

FUTURE MONITOR

1' -

6"

QUAD REC

OXYGEN

VACUUM

NURSE CALL

INFUSION BAY

108

DATA

FUTURE MONITOR

VACUUMSLIDE

1' -

6"

2' -

6"

5' -

0"

4' -

0"

Level 10' - 0"

6 5 4.5 4

QUADREC

QUADREC

OXYGEN

VACUUMNURSECALL

NURSECALLNURSE

CALL

NURSECALL

QUADREC

QUADREC

QUADREC

QUADREC

QUADREC

QUADREC

INFUSION BAY

116

INFUSION BAY

117

INFUSION BAY

118

INFUSION BAY

119

OXYGEN

VACUUM

OXYGEN

VACUUM

OXYGEN

VACUUM

DATADATADATA DATA

FUTUREMONITOR

FUTUREMONITOR

FUTUREMONITOR

FUTUREMONITOR

VACUUMSLIDE

VACUUMSLIDE VACUUM

SLIDE

VACUUMSLIDE

1' -

6"

2' -

10 1

/2"

DATADATA

C

QUAD REC

DUPLEX REC

1' -

6"

3' -

6"

C

QUAD REC

DATA

1' -

6"

Level 10"

FIN FLOOR0"

Level 10' - 0"

654.54

NURSECALL NURSE

CALL

QUADREC

OXYGEN

VACUUM

OXYGEN

VACUUM

OXYGEN

VACUUM

DATA

DATA

OXYGEN

VACUUM

QUADREC

QUADREC

DATA

NURSECALL

DATA DATA

NURSECALL

MONITOR

FUTUREMONITOR

FUTUREMONITOR

FUTUREMONITOR

VACUUMSLIDE

VACUUMSLIDE VACUUM

SLIDE

VACUUMSLIDE

10

MEP1.1

2' -

10 1

/2"

1' -

6"

INFUSION BAY

120

INFUSION BAY

121

INFUSION BAY

122

INFUSION BAY

123

6

MEP1.0

Level 10"

FIN FLOOR0"

Level 10' - 0"

C

11

MEP1.0

QUADREC

QUADREC

LIGHTSWITCH

NURSE CALL

FUTURE MONITOR

INFUSION BAY

122

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:3

3 A

M

CTC - INFUSION ADDITIONAND RENOVATION

MEP1.015068

2/26/16

CONSTRUCTION DOCUMENTS

SECTION VIEWS

3/8" = 1'-0"1

INFUSION BAY 109 3/8" = 1'-0"

2INFUSION BAY 111

3/8" = 1'-0"3

INFUSION BAY 113

3/8" = 1'-0"5

INFUSION BAY 129 3/8" = 1'-0"

7INFUSION BAY 106 & 108

3/8" = 1'-0"10

INFUSION BAYS - WEST

3/8" = 1'-0"8

COMFORT AREA CASEWORK 3/8" = 1'-0"

9VOLUNTEER WORK AREA

3/8" = 1'-0"11

INFUSION BAYS - EAST

Revision Schedule

No. Date Revisions

3/8" = 1'-0"6

INFUSION BAY 122

Page 11: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

6.5

QUAD RECDATA

REC

Level 1100'-0"

1

MEP1.1

1' -

6" 3

' - 2

"

6.5

REC

QUAD RECDATA

1

MEP1.1

1' -

6"3

' - 2

"

5

MEP1.1

DATAREC

QUAD REC

DATA

REC

1' -

6"

3' -

10"

4

MEP1.1

EYEWASH

8

MEP1.1

REC

DATA

1' -

6" QUAD

REC

3' -

2"

D 8

MEP1.1

REC

REC REC

DATA

LIGHTSWITCH

1' -

6"

4' -

0"

3' -

4"

4.5 46

MEP1.1

7

MEP1.1

QUAD REC

RECDATA

DATA

QUAD REC

DATA

REC

DATA /QUAD REC

DATA /QUAD REC

(2) REC(2) REC

2' -

4 1

/4"

3' -

2"

3' -

10"

1' -

6"

Level 10"

FIN FLOOR0"

Level 10' - 0"

B.8C3

MEP1.1

2

MEP1.1

NURSE CALLMASTER

REC

DATA

REC

DATA

REC

DATA

REC

DATA

THERMOSTATTHERMOSTAT

3' -

0"4

' - 8

"

Level 10"

FIN FLOOR0"

Level 10' - 0"

C11

MEP1.0

QUAD REC

QUADREC

LIGHTSWITCH

DATA

LIGHT SWITCH

QUAD REC NURSE CALL

VACUUM

1' -

6"

2' -

10 1

/2"

4' -

0"

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:3

5 A

M

CTC - INFUSION ADDITIONAND RENOVATION

MEP1.115068

2/26/16

CONSTRUCTION DOCUMENTS

SECTION VIEWS

3/8" = 1'-0"3

NURSE STATION WORK COUNTER 2 3/8" = 1'-0"

2NURSE STATION WORK COUNTER 1

3/8" = 1'-0"4

ANTE ROOM SOUTH ELEVATION 3/8" = 1'-0"

5ANTE ROOM EAST ELEVATION

3/8" = 1'-0"6

PHARMACY WORK COUNTER 3/8" = 1'-0"

7PHARMACY NORTH ELEVATION

3/8" = 1'-0"8

PHARMACY EAST ELEVATION

3/8" = 1'-0"1

NURSE STATION CASEWORK

3/8" = 1'-0"10

INFUSION BAY 123

Revision Schedule

No. Date Revisions

Page 12: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:3

5 A

M

CTC - INFUSION ADDITIONAND RENOVATION

MEP 2.015068

2/26/16

CONSTRUCTION DOCUMENTS

MECHANICAL EQUIPMENTSCHEDULE

MECHANICAL EQUIPMENT ELECLECTRICAL DATA SCHEDULEPLAN MARK

DISCRIPTION /LOCATION HORSEPOWER

APPARENTLOAD VOLTAGE PHASE

CIRCUITBREAKER

POLESNEMA ENCL.

TYPE

STARTER DISCONNECT CONTROL DEVICE

PANEL FEEDER SIZE / RACEWAY REMARKSFURNISHED BY INSTALLED BY TYPEAUXILIARYCONTACTS LOCATION FURNISHED BY INSTALLED BY TYPE

SWITCHSIZE FUSE SIZE LOCATION FURNISHED BY WIRE BY

EF 5 EXHAUST FAN 1 1920 VA 208 V 1 2 3R EC EC NI NO/NC -- EC EC N1 20A 15 AT UNIT MC MC L1A (2) #8 AND (1) #10 GND IN 3/4" CONDUIT NOTE 3

EF 6 EXHAUST FAN -- 200 VA 120 V 1 1 1 EM EM -- -- AT UNIT EM EM TS 20A NF AT UNIT MC MC L1A (2) #12 AND (1) #12 GND IN 3/4" CONDUIT NOTE 5

EF 7 EXHUAST FAN -- 200 VA 120 V 1 1 1 EM EM -- -- AT UNIT EM EM TS 20A NF AT UNIT MC MC L1A (2) #12 AND (1) #12 GND IN 3/4" CONDUIT NOTE 5

EF 8 EXHAUST FAN 1 1920 VA 208 V 1 2 3R EC EC NI NO/NC -- EC EC N1 20A 15 AT UNIT MC MC L1A (2) #8 AND (1) #10 GND IN 3/4" CONDUIT NOTE 3

FFU-1 158 FAN FILTER UNIT -- 500 VA 120 V 1 1 1 EM EM -- -- AT UNIT EM EC TS 20A NF AT UNIT MC MC L1A (2) #12 AND (1) #12 GND IN 3/4" CONDUIT

FFU-2 151 FAN FILTER UNIT -- 504 VA 120 V 1 1 1 EM EM -- -- AT UNIT EM EC TS 20A NF AT UNIT MC MC L1A (2) #12 AND (1) #12 GND IN 3/4" CONDUIT

FFU-3 155 FAN FILTER UNIT -- 600 VA 120 V 1 1 1 EM EM -- -- AT UNIT EM EC TS 20A NF AT UNIT MC MC L1A (2) #12 AND (1) #12 GND IN 3/4" CONDUIT

FFU-4 150 FAN FILTER UNIT -- 600 VA 120 V 1 1 1 EM EM -- -- AT UNIT EM EC TS 20A NF AT UNIT MC MC L1A (2) #12 AND (1) #12 GND IN 3/4" CONDUIT

FFU-5 152 FAN FILTER UNIT -- 600 VA 120 V 1 1 1 EM EM -- -- AT UNIT EM EC TS 20A NF AT UNIT MC MC L1A (2) #12 AND (1) #12 GND IN 3/4" CONDUIT

HWB 001 CONDENSINGHEAT BOILER

-- 1 1 EM EM -- -- AT UNIT EM EM NI 30A NF AT UNIT MC MC L1A (2) #12 AND (1) #12 GND IN 3/4" CONDUIT NOTE 4

HWP 001 HOT WATER PUMP 2 2826 VA 480 V 3 3 1 EXISTING EC -- -- AT UNIT EC EXISTING -- -- -- AT UNIT MC MC L1A (3) #12 AND (1) #12 GND IN 3/4" CONDUIT NOTE 1

HWP 002 HOT WATER PUMP 2 2826 VA 480 V 3 3 1 EXISTING EC -- -- AT UNIT EC EXISTING -- -- -- AT UNIT MC MC L1A (3) #12 AND (1) #12 GND IN 3/4" CONDUIT NOTE 1

RTU 2 ROOF TOP UNIT -- 28018 VA 480 V 3 3 3R EM EM TS 60A NF AT UNIT MC MC L1A (3) #8 AND (1) #8 GND IN 3/4" CONDUIT NOTE 2

NOTES:

1) REUSE EXISTING STARTERS AND CIRCUITS. DISCONNECT PUMP FOR REMOVAL AND PROVIDE NEW FLEXIBLE CONNECTION FROM STARTERS LOCATED ADJACENT TO PUMPS. SLIGHTLY ADJUST LOCATION OF ONE OF THE STARTERS THAT IS BLOCKED BY PIPING TO ALLOW DOOR TO OPEN.

2) PROVIDE 3P-45A BREAKER IN EXISTING SWITCHBOARD "MDP". PROVIDE 120V CIRCUIT TO RECEPTACLE USING EXISTING CIRCUIT SERVING MECHANICAL STORAGE.

3) PROVIDE COMBINATION LOCAL FUSED MOTOR STARTER IN MECHANICAL / ELECTRICAL ROOM.

4) PROVIDE A MAINTAINED MUSHROOM HEAD PUSH BUTTON ADJACENT TO THE EXISTING FIRE ALARM PULL STATION AT THE EXIT OF THE ROOM. CIRCUIT THE BOILER THROUGH THE PUSH BUTTON. PROVIDE LABEL "BOILER EMERGENCY SHUT OFF".

5) EF-6 & EF-7 SHARES SAME CIRCUIT.

LEGEND

EC - ELECTRICAL CONTRACTOREM - EQUIPMENT MANUFACTURERMC - MECHANICAL CONTRACTORNF - NON FUSEDNO/NC - NORMALLY OPEN/NORMALLY CLOSEDTS - TOGGLE SWITCHNI - NON INTERRUPTING

Revision Schedule

No. Date Revisions

Page 13: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

OX

VAC

K A

MEDICAL GAS ABBREVIATIONSPIPING SPECIALTIES

MISCELLANEOUS

GENERAL CONSTRUCTION CONTRACTOR

HEATING & AIR CONDITIONING CONTRACTOR

PLUMBING CONTRACTOR

ELECTRICAL CONTRACTOR

AUTOMATIC CONTROL SUB-CONTRACTOR

EQUIPMENT OR PLUMBING FIXTURE DESIGNATION

RISER DESIGNATION

(RISER INDICATION P=PLUMBING, P =KITCHEN, P =ACID)

(RISER NUMBER)

DETAIL DESIGNATION

(DETAIL NUMBER)

(SHEET NUMBER WHERE DETAIL IS FOUND)

SECTION DESIGNATION

(SECTION NUMBER)

(SHEET NUMBER WHERE SECTION IS FOUND)

KEYED NOTES

REVISIONS

ACCESS PANEL

NEW CONNECTION

OXYGEN PIPING

MEDICAL VACUUM PIPING

AP

FINISH FLOOR ELEVATION

ABOVE FINISH FLOOR

TOP ELEVATION

BOTTOM ELEVATION

F.F.E.

A.F.F.

T.E

B.E

F.L. FLOW LINE

INVERT ELEVATIONINV.

CHECK VALVE

IN LINE BALL VALVE

CV

NOTE: NOT ALL SYMBOLS OR ABBREVIATIONS MAY BE USED.

G.C.C.

H.A.C

P.C.

E.C.

A.C.S.

V

O OXYGEN OUTLET - LATCH KEY TYPE

VACUUM OUTLET - LATCH KEY TYPE

LOCKED OPEN IN LINE BALL VALVE

LOCKED CLOSED IN LINE BALL VALVE

VALVE BOX (RECESSED)

PRESSURE REGULATOR

LOCAL ALARM

MASTER ALARM PANAL

AREA ALARM

PRESSURE RELIEF VALVE

MAIN LINE GAUGE

0-100 PSI (0-690 KPA) PRESSURE SWITCH

0-200 PSI (0-1380 KPA) PRESSURE SWITCH

VACUUM SWITCH

PRESSURE/VACUUM SENSOR

MAP

VB

AA

MVS MEDICAL VACUUM SYSTEM

BOS BULK OXYGEN SUPPLY

OM OXYGEN MANIFOLD

THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINEDFROM SPECIFICATIONS, EXISTING PLANS AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING PIPING, ANDEQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THESE DRAWINGS. CONTRACTOR SHALL BE PREPAREDTO MAKE SOME ALTERATIONS TO SERVICES TO FIT ACTUAL JOB CONDITIONS.

PIPING DRAWINGS ARE TO BE CONSIDERED SCHEMATIC AND ARE NOT INTENDED TO INDICATE ALL CHANGES INDIRECTION. ALL NECESSARY FITTINGS TO BE FURNISHED AND INSTALLED BY CONTRACTOR. PIPE AND FITTINGS MUSTBE INSTALLED SO THAT ALL PIPE AND/OR INSULATION COMPLETELY CLEARS ALL NEARBY STRUCTURES, PIPING ANDITEMS BY OTHER CONTRACTORS. ALL PIPE SIZES SHOWN ARE MINIMUMS.

VERIFY EXACT LOCATION, CONDITION, ELEVATION AND SIZES OF UTILITIES AT SITE BEFORE PROCEEDING WITHWORK.

COORDINATE THE INSTALLATION OF ALL PIPING, VALVES, AND EQUIPMENT WITH GENERAL CONTRACTOR ANDRELATED STRUCTURAL, MECHANICAL, ELECTRICAL, AND FIRE PROTECTION CONTRACTORS.

PROTECT ALL ADJACENT AREAS DURING ALL PHASES OF CONSTRUCTION.

ANY HOLES LEFT IN WALL CONSTRUCTION DUE TO WORK SHALL BE PATCHED AND PAINTED BY CONTRACTOR TOMATCH CONSTRUCTED CONDITIONS. COORDINATE FINISH AND MATERIALS WITH ARCHITECT.

VERIFY THAT ALL VALVES IN THE MEDICAL GAS PIPING ARE IN THE FULLY OPEN POSITION.

ALL PIPING SHALL BE CONCEALED IN CHASE, WALL, CEILING, FLOORING, ETC. UNLESS OTHERWISE NOTED. PIPINGSHOWN OUTSIDE OF WALL FOR CLARITY ONLY.

EQUIPMENT AND FIXTURE SYMBOLOGY ON PLANS MAY NOT REFLECT ACTUAL TYPE. REFER TO SPECIFICATIONS FORFIXTURE OR EQUIPMENT TYPE.

FIRE CAULK ALL PIPING PENETRATIONS THROUGH FIRE RATED PARTITIONS TO MAINTAIN FIRE RATING OF PARTITION.FIRESTOP ALL PENETRATIONS THROUGH FIRE-RATED FLOORS AND WALLS CREATED BY NEW WORK WITH "SPECSEALSSS" OR EQUAL.

FURNISH AND INSTALL CONCRETE EQUIPMENT PAD FOR ALL EQUIPMENT SUPPLIED BY THIS CONTRACTOR. PADSHOULD BE A MINIMUM OF 4" THICK AND EXTEND 6" PAST EDGE OF EQUIPMENT IN ALL DIRECTIONS.

ALL ITEMS INCLUDED ON THESE DRAWINGS AND THE SPECIFICATIONS SHALL BE INCLUDED IN THE CONTRACTOR'S BID.ANY ITEMS THAT ARE UNCLEAR OR FOUND TO BE INCORRECT BY THE CONTRACTOR SHALL BE BROUGHT, IN WRITING,TO THE ATTENTION OF THE ARCHITECT AND ENGINEER PRIOR TO THE BID DUE DATE.

CAULK ALL PIPING PENETRATIONS THROUGH WALLS TO MINIMIZE SOUND PENETRATION THROUGH WALLS.

INVERT ELEVATIONS ARE BASED ON FIRST FLOOR LEVEL BEING SET AT 100'-0".

AREA ABOVE CEILINGS SERVE AS A RETURN AIR PLENUM. ALL MATERIALS EXPOSED IN THE PLENUM SHALL HAVE A25/50 SMOKE/FLAME SPREAD RATING. NO PVC PIPING ALLOWED ABOVE CEILING. ALL PIPING (SANITARY AND VENT)TO BE CAST IRON ABOVE CEILING. ALL GAS PIPING ABOVE CEILING TO BE STEEL WITH WELDED JOINTS. ALLPOLYPROPYPLENE WATER PIPING ABOVE CEILING SHALL BE INSULATED WITH FIBERGLASS INSULATION TO ACHIEVE25/50 SMOKE/FLAME SPREAD RATING.

MAKE ALL FINAL MEDICAL GAS CONNECTIONS TO MEDICAL GAS FIXTURES AND EQUIPMENT NOTED ON PLANS.

ALL EXPOSED PIPING IN FINISHED SPACES SHALL BE PROVIDED WITH A WHITE PVC JACKET.

VERIFY THAT REMOVAL OF THE PIPING NOTED FOR DEMOLITION DOES NOT ADVERSELY EFFECT ANY FIXTURES TOREMAIN AND THAT NO DEAD ENDS ARE LEFT IN PIPING.

OWNER SHALL BE GIVEN SALVAGE RIGHTS TO ALL MEDICAL GAS FIXTURES INDICATED FOR REMOVAL. CONTRACTORSHALL DISPOSE OF ALL UN-SALVAGED FIXTURES AND PIPING OFF-SITE IN AN ENVIRONMENTALLY ACCEPTABLEMANNER.

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:3

5 A

M

CTC - INFUSION ADDITIONAND RENOVATION

MG0.115068

2/26/16

CONSTRUCTION DOCUMENTS

LEGEND AND SYMBOLS

Revision Schedule

No. Date Revisions

Page 14: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

FE

C

FE

C

FEC

A.9 B.8 C.8 D

E

R3

R2

R1

7

6

5

C

9

4.5

4

8

8.1

8.3

6.5

NEG PRESSURE

MIXING ROOM

144

EXISTING ELEC

145

ANTE

142

POS PRESSURE

MIXING ROOM

143

EXISTING

MECHANICAL

146

PHARMACY

140

PREP AREA

132

INFUSION BAY

131

INFUSION BAY

130

INFUSION BAY

129

TOILET

128

TOILET

127

COMFORT AREA

126

PASSAGE

124

NURSE STATION

115

INFUSION BAY

113

INFUSION BAY

112

INFUSION BAY

111

INFUSION BAY

110

INFUSION BAY

109

INFUSION BAY

108

TOILET

107

INFUSION BAY

106

SOILED UTILITY

104

PASSAGE

105

INJECTIONS

103

WAITING

101

RECEPTION

102

HAZ DRUG

STORAGE

141

SUITE ENTRY

100

PASSAGE

114

INFUSION BAY

123

INFUSION BAY

116

INFUSION BAY

117

INFUSION BAY

122

INFUSION BAY

121

INFUSION BAY

118

INFUSION BAY

119

INFUSION BAY

120

1

2

3

45

55

4

6

6

6

6

6

6

6

6

7

7

7

77

7 7

77

7 7

7

7

7

7

7

7

6

3/4" OX

1-1/4" VAC

EX. 3/4" OX

EX. 1-1/4" VAC

EX. 1/2" OX

EX. 3/4" VAC

3/4

" O

X

1-1

/4"

VA

C

1/2

" O

X1"

VA

C

3/4

" O

X

1-1

/4"

VA

C

7

6

1/2

" O

X

3/4

" V

AC

3/4" VAC1/2" OX

3/4" VAC1/2" OX

3/4" VAC1/2" OX

3/4

" O

X

1"

VA

C

1/2

" O

X

3/4

" V

AC

3/4" VAC1/2" OX

1/2

" O

X3/4

" V

AC

1/2

" O

X3/4

" V

AC

8

9

EX. 3/4" OX

1-1/4" VAC

EX. 3/4" OX

1-1/4" VAC

SYMBOLS AND ABBREVIATIONS

OXYGEN (OX)

MEDICAL VACUUM (VAC)

DOWN

NOT TO SCALE

FINISHED FLOOR

CONNECTION TO EXISTING SYSTEM

INDICATED AREA

PIPE BREAK

KEYED NOTE

EXISTING

DN

NTS

#

F.F.

EX.

APPLICABLE CODES/STANDARDS:

2006 IBC; INTERNATIONAL BUILDING CODE

2006 IPC; INTERNATIONAL PLUMBING CODE

NFPA 99; 2012 EDITION

THESE PLANS ARE DIAGRAMMATIC IN NATURE SINCE THEY REFLECT ONLY THE AVAILABLE INFORMATION OBTAINEDFROM SPECIFICATIONS, EXISTING PLANS AND FIELD SURVEYS. THE EXACT LOCATION OF EXISTING PIPING, ANDEQUIPMENT MAY DEVIATE FROM THE LOCATION INDICATED ON THESE DRAWINGS. CONTRACTOR SHALL BE PREPAREDTO MAKE SOME ALTERATIONS TO SERVICES TO FIT ACTUAL JOB CONDITIONS.

PIPING DRAWINGS ARE TO BE CONSIDERED SCHEMATIC AND ARE NOT INTENDED TO INDICATE ALL CHANGES INDIRECTION. ALL NECESSARY FITTINGS TO BE FURNISHED AND INSTALLED BY CONTRACTOR. PIPE AND FITTINGS MUSTBE INSTALLED SO THAT ALL PIPE AND/OR INSULATION COMPLETELY CLEARS ALL NEARBY STRUCTURES, PIPING ANDITEMS BY OTHER CONTRACTORS. ALL PIPE SIZES SHOWN ARE MINIMUMS.

VERIFY EXACT LOCATION, CONDITION, ELEVATION AND SIZES OF UTILITIES AT SITE BEFORE PROCEEDING WITHWORK.

COORDINATE THE INSTALLATION OF ALL PIPING, VALVES, AND EQUIPMENT WITH GENERAL CONTRACTOR ANDRELATED STRUCTURAL, MECHANICAL, ELECTRICAL, AND FIRE PROTECTION CONTRACTORS.

PROTECT ALL ADJACENT AREAS DURING ALL PHASES OF CONSTRUCTION.

ANY HOLES LEFT IN WALL CONSTRUCTION DUE TO WORK SHALL BE PATCHED AND PAINTED BY CONTRACTOR TOMATCH CONSTRUCTED CONDITIONS. COORDINATE FINISH AND MATERIALS WITH ARCHITECT.

VERIFY THAT ALL VALVES IN THE MEDICAL GAS PIPING ARE IN THE FULLY OPEN POSITION.

ALL PIPING SHALL BE CONCEALED IN CHASE, WALL, CEILING, FLOORING, ETC. UNLESS OTHERWISE NOTED. PIPINGSHOWN OUTSIDE OF WALL FOR CLARITY ONLY.

EQUIPMENT AND FIXTURE SYMBOLOGY ON PLANS MAY NOT REFLECT ACTUAL TYPE. REFER TO SPECIFICATIONS FORFIXTURE OR EQUIPMENT TYPE.

FIRE CAULK ALL PIPING PENETRATIONS THROUGH FIRE RATED PARTITIONS TO MAINTAIN FIRE RATING OF PARTITION.FIRESTOP ALL PENETRATIONS THROUGH FIRE-RATED FLOORS AND WALLS CREATED BY NEW WORK WITH "SPECSEALSSS" OR EQUAL.

FURNISH AND INSTALL CONCRETE EQUIPMENT PAD FOR ALL EQUIPMENT SUPPLIED BY THIS CONTRACTOR. PADSHOULD BE A MINIMUM OF 4" THICK AND EXTEND 6" PAST EDGE OF EQUIPMENT IN ALL DIRECTIONS.

ALL ITEMS INCLUDED ON THESE DRAWINGS AND THE SPECIFICATIONS SHALL BE INCLUDED IN THE CONTRACTOR'S BID.ANY ITEMS THAT ARE UNCLEAR OR FOUND TO BE INCORRECT BY THE CONTRACTOR SHALL BE BROUGHT, IN WRITING,TO THE ATTENTION OF THE ARCHITECT AND ENGINEER PRIOR TO THE BID DUE DATE.

CAULK ALL PIPING PENETRATIONS THROUGH WALLS TO MINIMIZE SOUND PENETRATION THROUGH WALLS.

INVERT ELEVATIONS ARE BASED ON FIRST FLOOR LEVEL BEING SET AT 100'-0".

AREA ABOVE CEILINGS SERVE AS A RETURN AIR PLENUM. ALL MATERIALS EXPOSED IN THE PLENUM SHALL HAVE A25/50 SMOKE/FLAME SPREAD RATING. NO PVC PIPING ALLOWED ABOVE CEILING. ALL PIPING (SANITARY AND VENT)TO BE CAST IRON ABOVE CEILING. ALL GAS PIPING ABOVE CEILING TO BE STEEL WITH WELDED JOINTS. ALLPOLYPROPYPLENE WATER PIPING ABOVE CEILING SHALL BE INSULATED WITH FIBERGLASS INSULATION TO ACHIEVE25/50 SMOKE/FLAME SPREAD RATING.

MAKE ALL FINAL MEDICAL GAS CONNECTIONS TO MEDICAL GAS FIXTURES AND EQUIPMENT NOTED ON PLANS.

ALL EXPOSED PIPING IN FINISHED SPACES SHALL BE PROVIDED WITH A WHITE PVC JACKET.

VERIFY THAT REMOVAL OF THE PIPING NOTED FOR DEMOLITION DOES NOT ADVERSELY EFFECT ANY FIXTURES TOREMAIN AND THAT NO DEAD ENDS ARE LEFT IN PIPING.

OWNER SHALL BE GIVEN SALVAGE RIGHTS TO ALL MEDICAL GAS FIXTURES INDICATED FOR REMOVAL. CONTRACTORSHALL DISPOSE OF ALL UN-SALVAGED FIXTURES AND PIPING OFF-SITE IN AN ENVIRONMENTALLY ACCEPTABLEMANNER.

GENERAL NOTES

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:3

7 A

M

CTC - INFUSION ADDITIONAND RENOVATION

MG1.115068

2/26/16

CONSTRUCTION DOCUMENTS

MEDICAL GAS FLOOR PLAN

1/4" = 1'-0"1

FIRST FLOOR MEDICAL GAS NEW WORK

FIRST FLOOR KEY PLAN

KEYED NOTES

1 GENESYS FULLY AUTOMATIC OXYGEN MANIFOLD; 4CYLINDERS. CONNECT 3/4" OX TO EXISTING PIPING ONTHE EXTERIOR OF THE BUILDING AT THE LCOATIONINDICATED. USE THE EXISTING ELEMENT PROTECTION.

2 EXISTING MEDICAL GAS VACUUM EQUIPMENT SHALLREMAIN. NO WORK.

3 EXISTING MEDICAL GAS VALVE BOX TO REMAIN; NO WORK.

4 CONNECT VAC TO EXISTING VAC PIPING AT THE LOCATIONINDICATED.

5 CONNECT 3/4" OX TO EXISTING OX PIPING AT THELOCATION INDICATED.

6 1/2" OX DN; 3/4" VAC DN. EXTEND PIPING TO DESIGNATEDQUICK CONNECTION LOCATIONS. SEE MEP SECTIONS FORADDITIONAL INFORMATION.

7 INSTALL A MEDICAL GAS OXYGEN, VACUUM, AND VACUUMSLIDE QUICK CONNECT STATION.

8 MEDICAL GAS ALARM PANEL (OX, VAC).

9 INSTALL EXPANSION JOINTS ON ALL PIPING CROSSING THEAREA INDICATED.

#

Revision Schedule

No. Date Revisions

Page 15: DM1 - Amazon Simple Storage Service · t t t c d e f g 4.5 4 3 2 a b exst 200 exst 450 exst 450 exst 450 exst 450 exst 200 exst 200 exst 110 exst 90 exst 90 exst 350 exst 170 …

A

B

C

D

E

1 2 3 4 5 6 7

1 2 3 4 5 6 7

A

B

C

D

E

THE SEAL (S) AND SIGNATURE(S) APPLY ONLY TO THEDOCUMENT TO WHICH THEY ARE AFFIXED, AND WEEXPRESSLY DISCLAIM ANY RESPONSIBILITY FOR ALL OTHERPLANS, SPECIFICATIONS, ESTIMATES, REPORTS, OR OTHERDOCUMENTS OR INSTRUMENTS RELATING TO OR INTENDEDTO BE USED FOR ANY PART OF PARTS OF THE PROJECT.© COPYRIGHT 2013 CHRISTNER INC.

Revision Dwg No Sheet No

Project No

Date

OZARKS MEDICAL CENTER1100 KENTUCKY AVENUEWEST PLAINS, MISSOURI 65775417-256-9111

STRUCTURAL ENGINEERALPER-AUDI1804 BORMAN CIRCLE DRIVEST LOUIS, MISSOURI 63146CORPORATE CHARTER NUMBER314-432-8600

MEPFP ENGINEERBRiC PARTNERSHIPMISSOURI CERTIFICATE OFAUTHORITY: # 2002028690343 S. KIRWOOD RDKIRKWOOD, MISSOURI314-725-5889

CIVIL ENGINEEROVERLAND ENGINEERING1598 IMPERIAL CENTERWEST PLAINS, MO 65775417-256-8150

TEL 314 725 2927 | FAX 314 725 2928 | CHRISTNERINC.COM

168 NORTH MERAMEC | ST. LOUIS, MISSOURI 63105

ARCHITECTS | DESIGNERS | PLANNERS | LANDSCAPE ARCHITECTS

CERTIFICATE OF AUTHORITY - 000842

C:\U

sers

\marg

are

tb\D

ocum

ents

\2209-0

2_M

EP

_C

entr

al_

v16_m

arg

are

tb.r

vt

4/1

3/2

016 9

:26:3

8 A

M

CTC - INFUSION ADDITIONAND RENOVATION

MG2.115068

2/26/16

CONSTRUCTION DOCUMENTS

MEDICAL GAS ISOMETRIC

1PLUMBING ISOMETRIC - MEDICAL GAS

1

1

1

1

1

1

1

1

1

1

1

11

1

1

1

1

1

2

3

4

EX. 3/4" OX

EX. 1-1/4" VAC

3/4" OX

1" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

EX. 3/4" OX

EX. 1-1/4" VAC

EX. 3/4" OX

1-1/4" VAC

EX. 3/4" OX

1-1/4" VAC

EX. 3/4" OX

EX. 3/4" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

1/2" OX

3/4" VAC

3/4" OX

1-1/4" VAC

1/2" OX

3/4" VAC3/4" OX

1-1/4" VAC

1/2" OX

3/4" VAC

KEYED NOTES

1 INSTALL A MEDICAL GAS OXYGEN, VACUUM, AND VACUUMSLIDE QUICK CONNECT STATION.

2 EXISTING MEDICAL GAS VALVE BOX TO REMAIN; NO WORK.

3 CONNECT TO EXISTING 3/4" OX AT THE LOCATIONINDICATED; EXTERIOR OF BUILDING.

4 MEDICAL OXYGEN MANIFOLD; EXTERIOR.

#

Revision Schedule

No. Date Revisions