Distribution blocks 5ST250 SENTRON Protection, Switching, Measuring and Monitoring Devices Distribution blocks are used to realize single-, two-, three- and four-phase systems up to a rated current of 400 A. This enables to split power supply circuits in several load circuits with different cable cross-sections. 7 High thermic and mechanical robustness Distribution blocks are made of thermo- plastic with electrical and mechanical parts, which allows a usage under high thermic and mechanical load according to IEC 60947-7-1. Highlights 7 Fast mounting on DIN-Rail with click connection or on mounting plate with 2 x M5 screws 7 Place saving 7 Safety because of IP20 degree of pro- tection and no cap to open or remove Answers for infrastructure. © Siemens 2011

Distribution blocks 5ST250 - Siemens Global Website · This enables to split power supply circuits in several ... Distribution blocks 5ST250 Siemens · 2011 3 ... Distribution blocks

Embed Size (px)

Citation preview

Distribution blocks 5ST250

SENTRON Protection, Switching, Measuring and Monitoring Devices

Distribution blocks are used to realize single-, two-, three- and four-phase systems up to a rated current of 400 A. This enables to split power supply circuits in several load circuits with different cable cross-sections.

7 High thermic and mechanical robustness

Distribution blocks are made of thermo-plastic with electrical and mechanical parts, which allows a usage under high thermic and mechanical load according to IEC 60947-7-1.

Highlights

7 Fast mounting on DIN-Rail with click connection or on mounting plate with 2 x M5 screws

7 Place saving

7 Safety because of IP20 degree of pro-tection and no cap to open or remove

Answers for infrastructure.

© Siemens 2011

Distribution blocks

5ST250

2 Siemens · 2011

■ Technical specifications

5ST2 501 5ST2 502 5ST2 503

Standards,Certifications

IEC 60947-7-1

Degree of Protection IP20

Poles 4

Approved cable Copper

Conductor cross-section

• Inputs per pole- Solid/stranded to IEC mm² 1x1.5 … 16/2.5 … 16 1x6 … 25/6 … 35 1x10 … 35/10 … 50

Neutral mm² -- 1x6 … 25/6 … 35 --

• Outputs per pole- Solid/stranded to IEC Large mm² 8x1.5 … 10/2.5 … 10 2x1.5 … 10/1.5 … 16 3x6 … 25/10 … 35

Small mm² -- 5x1.5 … 6/1.5 … 6 8x1.5 … 16/2.5 … 16

Neutral Large mm² -- 6x1.5 … 10/1.5 … 16 --Small mm² -- 4x1.5 … 6/1.5 … 6 --

Screw torque

• Input lb/in 13.5 13.5 17.5Nm 1.5 1.5 2

Fitting connection PZ2 PZ2 Allen key (5mm)

• Output Large lb/in 7.2 13.5 13.5Nm 0.8 1.5 1.5

Fitting connection PZ1 PZ2 PZ2

Small lb/in -- 7.2 13.5Nm -- 0.8 1.5

Fitting connection -- PZ1 PZ2

Operational voltage

• IEC, max V 500 690 500

Overcurrent protection fuse

• Max Amp Rating A 80 125 160• Rated peak withstand current (Ipk) kA 21.6 24 20• Rated short-time withstand current (Icw 1s) kA 3 4.2 6.2

Block Dimension (D x H x W) mm 88x49x86 75x49x45 160.5x90x50

© Siemens 2011

Distribution blocks

5ST250

3Siemens · 2011

UL types

1)Only stranded2)copper jumper has been investigated for a 100A rating

General character and use for UL types

The terminal blocks covered by this catalogue are intended for use in the following applications and within the ratings specified.

Application:- Commercial appliances (such as business and EDP equip-

ment, etc.)- General industrial (such as motor controllers, pushbutton sta-

tions, etc.)

5ST2 504 5ST2 505 5ST2 507 5ST2 508 5ST2 511

Standards,Certifications

UL 1059 / UL 486E / IEC 60947-7-1UL File Nr. E80027 / XCFR2C22.2 No158 -1987 / XCFR8

UL 486E / IEC 60947-7-1UL File Nr. E80027 / XCFR2

Degree of Protection IP20

Poles 1

Approved cable Copper

Typ wiring

• Front/Back

Factory and field wiringPressure wire connector

Conductor cross-section

• Input- Solid and Stranded to UL Large AWG 1x8 … 4 1x8 … 2 1x8 … 2 / 0 1x2 … 4 / 0 1) 1x3 /

0 … 350 MCM- Solid and Stranded to IEC mm² 2.5 … 16 10 … 35 10 … 70 35 … 120 1) 95 … 185

- Solid and Stranded to UL Small AWG -- 1x14 ... 4 --- Solid and Stranded to IEC mm² -- 2.5 ... 25 --

• Output- Solid and Stranded to UL TOP AWG 4x14 … 10 6x14 … 4 6x14 … 41) 4x14 … 6 4x10 … 14- Solid and Stranded to IEC mm² 2.5 … 6 2.5 … 16 2.5 … 251) 1.5 … 16 2.5 … 6

- Solid and Stranded to UL Middle AWG -- 4x14 … 8 - Solid and Stranded to IEC mm² -- 1.5 … 10

- Solid and Stranded to UL Bottom AWG 3x8 … 4 -- 2x14 … 2 / 1x14 … 6- Solid and Stranded to IEC mm² 2.5 … 16 -- 2x6 … 35 / 1.5 … 16

Screw torque

• Input lb/in 13.5 31 35.7 170 230Nm 3 3.5 5 19 25

Fitting connection Allen key (4mm) Allen key (5mm) Allen key (6mm) Allen key (8mm)

• Output Large lb/in 13.5 17.5 31Nm 3 2 3.5

Fitting connection PZ2 Standard screwdriver

Small lb/in 7.2 -- 31Nm 0.8 -- 3.5

Fitting connection PZ1 -- Standard screwdriver

Amper per pole, max. A 80 115 160 230 310

Operational voltage

• UL, max. V 600• IEC, max. V 690

Overcurrent protection fuse

• Required class J

• Max Amp Rating A 80 125 160 250 350 • SCCR RMS Sym A kA 100• Rated peak withstand current (Ipk) kA 2.7 30 51• Rated short-time withstand current (Icw 1s) kA 1.9 4.4 11 21

Spacings

• Trough Air in (mm) 3 / 8 (9.5)

• Over Surface in (mm) 1 / 2 (12.7)

Flammability Rating UL94V-0

Block Dimension (D x H x W) mm 66x49x27 74x49x27 92x35x49 96x49x45 96x49x45

Connections with cable up to 16mm²

With connector or cable up to 16mm² 2)

side access for parallel connec-tion with copper bar (max. 16 x 5 mm)

-- --

© Siemens 2011

Distribution blocks

5ST250

4 Siemens · 2011

■ Selection and ordering data

*You can order this quantity or a multiple thereof

I U MW DT Order No. PG PS*) /

P. unit

PU Weight

1 item

A V Unit(s) Unit(s) kg

Distribution blocks

1-pole 80 600 1.5 5ST2 504 027 1 1 0.072

125 5ST2 505 027 1 1 0.146

160 2 5ST2 507 027 1 1 0.252

250 2.5 5ST2 508 027 1 1 0.440

350 5ST2 511 027 1 1 0.418

4-pole 80 500 5 5ST2 501 027 1 1 0.246

125 690 5.5 5ST2 502 027 1 1 0.352

160 500 9 5ST2 503 027 1 1 0.620

Copper jumper 32mm

1-phase 5ST2 506 027 14 1 0.012

For 5ST2 505

© Siemens 2011

Distribution blocks

5ST250

5Siemens · 2011

■ Dimensional drawings

5ST2 504

5ST2 507

5ST2 511

5ST2 505

5ST2 508

5ST2 501

© Siemens 2011

Siemens AGIndustry SectorBuilding Technologies DivisionPostfach 10 09 5393009 REGENSBURGGERMANY

www.siemens.com/lowvoltage

The information provided in this brochure contains descriptions or characteristics of perfor-mance which in case of actual use do not always apply as described or which may change asa result of further development of the products. An obligation to provide the respective char-acteristics shall only exist if expressly agreed in the terms of contract. Availability and techni-cal specifications are subject to change without notice.All product designations may be registered trademarks or product names of Siemens AG orsupplier companies whose use by third parties for their own purposes may violate the rightsof the owner.

© Siemens AG 2010 • PDF only: (E10003-E38-10T-G2431-7600) • PI 1110 En

5ST2 502

© Siemens 2011