Function overview Description Siemens SIP · 2008 6 Distance Protection / 7SA6 6 6/3 Protection functions Non-switched distance protection with 6 measuring systems (21/21N) High resistance earth-fault protection for single and three-phase tripping (50N, 51N, 67N) Earth-fault detection in isolated and resonant-earthed networks Tele (pilot) protection (85) Fault locator (FL) Power-swing detection/tripping (68/68T) Phase overcurrent protection (50/51/67) Switch-onto-fault protection (50HS) STUB bus overcurrent protection (50STUB) Overvoltage/undervoltage protection (59/27) Over/underfrequency protection (81O/U) Auto-reclosure (79) Synchro-check (25) Breaker failure protection (50BF) Thermal overload protection (49) Control function Commands f. ctrl. of CBs and isolators Monitoring functions Trip circuit supervision (74TC) Self-supervision of the relay Measured-value supervision Event logging/fault logging Oscillographic fault recording Switching statistics Front design Easy operation w. numeric keys Function keys LEDs for local alarm PC front port for convenient relay setting Communication interfaces Front interface for connecting a PC System interface for connecting to a control system via various protocols – IEC 61850 Ethernet – IEC 60870-5-103 protocol – PROFIBUS-FMS/-DP – DNP 3.0 1 serial protection data interface for teleprotection Rear-side service/modem interface Time synchronization via – IRIG-B or DCF 77 or – system interface SIPROTEC 4 7SA6 Distance Protection Relay for all Voltage Levels The SIPROTEC 4 7SA6 distance protection relay is a universal device for protection, control and automation on the basis of the SIPROTEC 4 system. Its high level of flexi- bility makes it suitable to be implemented at all voltage levels. With this relay you are ide- ally equipped for the future: it offers security of investment and also saves on operating costs. High-speed tripping time Low-impedance setpoints to protect also very short lines Self-setting power swing detection for fre- quencies up to 7 Hz Current transformer saturation detector ensures fast tripping and highest distance measurement accuracy Phase-segregated teleprotection for im- proved selectivity and availability Digital relay-to-relay communication by means of an integrated serial protection data interface Adaptive auto-reclosure (ADT) LSP2318-afp.tif Fig. 6/1 SIPROTEC 4 7SA6 distance protection relay

Distance Protection 7SA6

Embed Size (px)

DESCRIPTION

Distance Protection 7SA6

Citation preview

Page 1: Distance Protection 7SA6

Function overview

Description

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/3

Protection functions• Non-switched distance protection with

6 measuring systems (21/21N)• High resistance earth-fault protection

for single and three-phase tripping(50N, 51N, 67N)

• Earth-fault detection in isolated andresonant-earthed networks

• Tele (pilot) protection (85)• Fault locator (FL)• Power-swing detection/tripping (68/68T)• Phase overcurrent protection (50/51/67)• Switch-onto-fault protection (50HS)• STUB bus overcurrent protection

(50STUB)• Overvoltage/undervoltage protection

(59/27)• Over/underfrequency protection (81O/U)• Auto-reclosure (79)• Synchro-check (25)• Breaker failure protection (50BF)• Thermal overload protection (49)

Control function• Commands f. ctrl. of CBs and isolators

Monitoring functions• Trip circuit supervision (74TC)• Self-supervision of the relay• Measured-value supervision• Event logging/fault logging• Oscillographic fault recording• Switching statistics

Front design• Easy operation w. numeric keys• Function keys• LEDs for local alarm• PC front port for convenient relay

setting

Communication interfaces• Front interface for connecting a PC• System interface for connecting to a

control system via various protocols– IEC 61850 Ethernet– IEC 60870-5-103 protocol– PROFIBUS-FMS/-DP– DNP 3.0

• 1 serial protection data interface forteleprotection

• Rear-side service/modem interface• Time synchronization via

– IRIG-B or DCF 77 or– system interface

SIPROTEC 4 7SA6Distance Protection Relay for all Voltage Levels

The SIPROTEC 4 7SA6 distance protectionrelay is a universal device for protection,control and automation on the basis of theSIPROTEC 4 system. Its high level of flexi-bility makes it suitable to be implemented atall voltage levels. With this relay you are ide-ally equipped for the future: it offers securityof investment and also saves on operatingcosts.

− High-speed tripping time

− Low-impedance setpoints to protect alsovery short lines

− Self-setting power swing detection for fre-quencies up to 7 Hz

− Current transformer saturation detectorensures fast tripping and highest distancemeasurement accuracy

− Phase-segregated teleprotection for im-proved selectivity and availability

− Digital relay-to-relay communication bymeans of an integrated serial protectiondata interface

− Adaptive auto-reclosure (ADT)

LSP2

318-

afp

.tif

Fig. 6/1SIPROTEC 47SA6 distance protection relay

Page 2: Distance Protection 7SA6

The distance protection relay 7SA6 isnon-switched incorporating all the addi-tional functions for protection of overheadlines and cables at all voltage levels from5 to 765 kV.

All methods of neutral point connection(resonant earthing, isolated, solid orlow-resistance earthing) are reliably dealtwith. The unit can issue single or three-poleTRIP commands as well as CLOSE com-mands. Consequently both single-pole,three-pole and multiple auto-reclosure ispossible.

Teleprotection functions as well asearth-fault protection and sensitiveearth-fault detection are included. Powerswings are detected reliably andnon-selective tripping is prevented. The unitoperates reliably and selectively even underthe most difficult network conditions.

Cost-effective power system management

The SIPROTEC 4 units are numerical relayswhich also provide control and monitoringfunctions and therefore support the user inview of a cost-effective power system man-agement. The security and reliability ofpower supply is increased as a result of min-imizing the use of hardware.

The local operation has been designed ac-cording to ergonomic criteria. Large, easy-to-read backlit displays are provided.

The SIPROTEC 4 units have a uniform de-sign and a degree of functionality whichrepresents a benchmark-level of perfor-mance in protection and control. If the re-quirements for protection, control orinterlocking change, it is possible in the ma-jority of cases to implement such changes bymeans of parameterization using DIGSI 4without having to change the hardware.The use of powerful microcontrollers andthe application of digital measured-valueconditioning and processing largely sup-presses the influence of higher-frequencytransients, harmonics and DC components.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/4

ANSI Protection functions

21/21N Distance protection

FL Fault locator

50N/51N Directional earth-fault protection

67N

50/51/67 Backup overcurrent protection

50 STUB STUB-bus overcurrent stage

68/68T Power swing detection/tripping

85/21 Teleprotection for distance protection

27WI Weak-infeed protection

85/67N Teleprotection for earth-fault protection

50HS Switch-onto-fault protection

50BF Breaker-failure protection

59/27 Overvoltage/undervoltage protection

81O/U Over/underfrequency protection

25 Synchro-check

79 Auto-reclosure

74TC Trip circuit supervision

86 Lockout (CLOSE command inter-locking)

49 Thermal overload protection

IEE Sensitive earth-fault detection

Application

Fig. 6/2 Function diagram 1) Teleprotection schemes can useconventional signaling or serialdata exchange

Page 3: Distance Protection 7SA6

Connection techniques and housing withmany advantages

1/3, 1/2, 2/3, and 1/1-rack sizes:These are the available housing widths ofthe 7SA6 relays, referred to a 19" moduleframe system. This means that previousmodels can always be replaced. The height isa uniform 245 mm for flush-mountinghousings and 266 mm for surface-mountinghousings for all housing widths. All cablescan be connected with or without ring lugs.Plug-in terminals are available as an option.It is thus possible to employ prefabricatedcable harnesses. In the case of surfacemounting on a panel, the connection termi-nals are located above and below in theform of screw-type terminals. The commu-nication interfaces are located in a slopedcase at the top and bottom of the housing.The housing can also be supplied optionallywith a detached operator panel (refer toFig. 6/5), in order to allow optimum opera-tion for all types of applications.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/5

Construction

Fig. 6/3Flush-mounting housingwith screw-type terminals

Fig. 6/4Rear view of flush-mounting housing withcovered connection terminals and wirings

Fig. 6/5 Flush-mounting housing with plug-in terminals and detached operator panel

Fig. 6/6Surface-mounting housing with screw-typeterminals

Fig. 6/7Communication interfacesin a sloped case in a surface-mounting housing

LSP2

174-

afp

.tif

LSP2

166-

afp

.tif

LSP2

244-

afp

.ep

s

LSP2

237-

afp

.tif

LSP2

219-

afp

.ep

s

Page 4: Distance Protection 7SA6

Distance protection (ANSI 21, 21N)

The main function of the 7SA6 is a non-switched distance protection. By parallelcalculation and monitoring of all six imped-ance loops, a high degree of sensitivity andselectivity is achieved for all types of fault.The shortest tripping time is less than onecycle. All methods of neutral-point connec-tion (resonant earthing, isolated, solid orlow-resistance earthing) are reliably dealtwith. Single-pole and three-pole tripping ispossible. Overhead lines can be equippedwith or without series capacitor compensa-tion.

Four pickup methodsThe following pickup methods can be em-ployed alternatively:

• Overcurrent pickup I>>

• Voltage-dependent overcurrent pickupV/I

• Voltage-dependent and phase angle-dependent overcurrent pickup V/I/ϕ

• Impedance pickup Z<

Load zoneThe pickup mode with quadrilateral imped-ance pickup (Z<) is fitted with a variableload zone. In order to guarantee a reliablediscrimination between load operation andshort-circuit (especially on long high loadedlines), the relay is equipped with a selectableload encroachment characteristic. Imped-ances within this load encroachment char-acteristic prevent the distance zones fromunwanted tripping.

Absolute phase-selectivityThe 7SA6 distance protection incorporates awell-proven, highly sophisticated phase se-lection algorithm. The pickup of unfaultedphases is reliably eliminated. This phase se-lection algorithm achieves single-pole trip-ping and correct distance measurement in awide application range. Interference to dis-tance measurement caused by parallel linescan be compensated by taking the earth cur-rent of the parallel system into account.

This parallel line compensation can be takeninto account both for distance measure-ment and for fault locating.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/6

Protection functions

Fig. 6/9Voltage and angle- dependent overcurrentfault detection V / I / ϕ

Fig. 6/10

Angle pickup for the V / I / ϕ fault detection

Fig. 6/8Impedance fault detection Z<with quadrilateral characteristic

Fig. 6/11Distance zones with circlecharacteristic

Page 5: Distance Protection 7SA6

Six distance zonesFive independent distance zones and oneseparate overreach zone are available. Eachdistance zone has dedicated time stages,partially separate for single-phase andthree-phase faults. Earth faults are detectedby monitoring the earth current 3I0 and thezero-sequence voltage 3V0. The quadrilateraltripping characteristic allows use of separatesettings for the X and the R directions. Differ-ent R settings can be employed for earth andphase faults. This characteristic offers advan-tages in the case of faults with fault resistance.For applications to medium-voltage cableswith low line angles, it may be advantageousto select the distance zones with the optionalcircle characteristic.All the distance protection zones can be set toforward, reverse or non-directional.

Optimum direction detectionUse of voltages, which are not involved withthe short-circuit loop, and of voltage mem-ories for determination of the fault directionensure that the results are always reliable.

Elimination of interference signalsDigital filters render the unit immune to in-terference signals contained in the measuredvalues. In particular, the influence of DCcomponents, capacitive voltage transform-ers and frequency changes is considerablyreduced. A special measuring method is em-ployed in order to assure protection selec-tivity during saturation of the currenttransformers.

Measuring voltage monitoringTripping of the distance protection isblocked automatically in the event of failureof the measuring voltage, thus preventingspurious tripping.The measuring voltage is monitored by theintegrated fuse failure monitor. Distanceprotection is blocked if either the fuse fail-ure monitor or the auxiliary contact of thevoltage transformer protection switch oper-ates and in this case the EMERGENCY defi-nite-time overcurrent protection can beactivated.

Fault locator

The integrated fault locator calculates thefault impedance and the distance-to-fault.The results are displayed in ohms, kilome-ters (miles) and in percent of the line length.Parallel line compensation and load currentcompensation for high-resistance faults isalso available.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/7

Protection functions

Fig. 6/12 Power swing current and voltage wave forms

Power swing detection (ANSI 68, 68T)

Dynamic transient reactions, for instanceshort-circuits, load fluctuations, auto-reclosures or switching operations can causepower swings in the transmission network.During power swings, large currents alongwith small voltages can cause unwantedtripping of distance protection relays. Toavoid uncontrolled tripping of the distanceprotection and to achieve controlled trip-ping in the event of loss of synchronism, the7SA6 relay is equipped with an efficientpower swing detection function. Powerswings can be detected under symmetricalload conditions as well as during single-poleauto-reclosures.

Tele (pilot) protection for distance protection(ANSI 85-21)

A teleprotection function is available for fastclearance of faults up to 100 % of the linelength. The following operating modes maybe selected:

• POTT

• Directional comparison pickup

• Unblocking

• PUTT acceleration with pickup

• PUTT acceleration with Z1B

• Blocking

• Pilot-wire comparison

• Reverse interlocking

• DUTT, direct underreaching zone trans-fer trip (together with Direct TransferTrip function).

The carrier send and receive signals areavailable as binary inputs and outputs andcan be freely assigned to each physical relayinput or output. At least one channel is re-quired for each direction.

Common transmission channels are power-line carrier microwave radio and fiber-optic links. A serial protection data interfacefor direct connection to a digital communi-cation network or fiber-optic link is avail-able.

7SA6 also permits the transfer of phase-selective signals. This feature is particularlyadvantageous as it ensures reliable single-pole tripping, if single-pole faults occur ondifferent lines. The transmission methodsare suitable also for lines with three ends(three-terminal lines). Phase-selective trans-mission is also possible with multi-end ap-plication, if some user-specific linkages areimplemented by way of the integrated CFClogic.

During disturbances in the signaling chan-nel receiver or on the transmission circuit,the teleprotection function can be blockedvia a binary input signal without losing thezone selectivity.

The control of the overreach zone Z1B(zone extension) can be switched over to theauto-reclosure function.

Transient blocking (current reversal guard)is provided for all the release and blockingmethods in order to suppress interferencesignals during tripping of parallel lines.

LSP2

208-

afp

.tif

Page 6: Distance Protection 7SA6

Under certain conditions on the power sys-tem it is necessary to execute remote trip-ping of the circuit-breaker. The 7SA6 relayis equipped with phase-selective in-tertripping signal inputs and outputs.

Weak-infeed protection:echo and/or trip (ANSI 27 WI)

To prevent delayed tripping of permissiveschemes during weak or zero infeed situa-tions, an echo function is provided.If no fault detector is picked up at the weak-infeed end of the line, the signal receivedhere is returned as echo to allow acceleratedtripping at the strong infeed end of the line.It is also possible to initiate phase-selectivetripping at the weak-infeed end. A phase-selective single-pole or three-pole trip isissued if a permissive trip signal (POTT orUnblocking) is received and if the phase-earth voltage drops correspondingly. As anoption, the weak infeed logic can beequipped according to a French specifica-tion.

Overvoltage protection, undervoltageprotection (ANSI 59, 27)

A voltage rise can occur on long lines thatare operating at no-load or that are onlylightly loaded. The 7SA6 contains a numberof overvoltage measuring elements. Eachmeasuring element is of two-stage design.The following measuring elements are avail-able:

• Phase-to-earth overvoltage

• Phase-to-phase overvoltage

• Zero-sequence overvoltageThe zero-sequence voltage can beconnected to the 4th voltage input orbe derived from the phase voltages.

• Positive-sequence overvoltage of the localend or calculated for the remote end ofthe line (compounding)

• Negative-sequence overvoltage

Tripping by the overvoltage measuringelements can be effected either at the localcircuit-breaker or at the remote station bymeans of a transmitted signal.

The 7SA6 is fitted, in addition, with threetwo-stage undervoltage measuring elements:

• Phase-to-earth undervoltage

• Phase-to-phase undervoltage

• Positive-sequence undervoltage

The undervoltage measuring elements canbe blocked by means of a minimum currentcriterion and by means of binary inputs.

Frequency protection (ANSI 81O/U)

Frequency protection can be used foroverfrequency and underfrequency protec-tion. Unwanted frequency changes in thenetwork can be detected and the load can beremoved at a specified frequency setting.Frequency protection can be used over awide frequency range (45 to 55, 55 to65 Hz). There are four elements (selectableas overfrequency or underfrequency) andeach element can be delayed separately.

Directional earth-fault protection forhigh-resistance faults (ANSI 50N, 51N, 67N)

In an earthed network it may happen thatthe distance protection´s sensitivity is notsufficient to detect high-resistance earthfaults. The 7SA6 protection relay thereforeoffers protection functions for faults of thisnature.

The earth-fault protection can be used withthree definite-time stages and one inverse-time stage (IDMT).

Inverse-time characteristics according toIEC 60255-3 and ANSI/IEEE are provided(see “Technical data”). A 4th definite-timestage can be applied instead of the 1st in-verse-time stage.

An additional logarithmic inverse-timecharacteristic is also available.

The direction decision is determined by theearth current and the zero-sequence voltageor by the negative-sequence components V2

and I2. In addition or as an alternative, thedirection can be determined with the earthcurrent of an earthed power transformer andthe zero-sequence voltage. Dual polarizationapplications can therefore be fulfilled. Alter-natively, the direction can be determined byevaluation of zero-sequence power. Eachovercurrent stage can be set in forward or re-verse direction or in both directions(non-directional).

The function is equipped with special digitalfilter algorithms, providing the eliminationof higher harmonics. This feature is particu-larly important for small zero-sequencefault currents which usually have a highcontent of 3rd and 5th harmonic.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/8

Protection functions

Fig. 6/13 Normal inverse

( )t =

014

10 02

.

/.

I IT

p

p

Fig. 6/14Transient earth-fault relay 7SN60

LSP2

209-

afp

.tif

Page 7: Distance Protection 7SA6

Inrush stabilization and instantaneousswitch-onto-fault tripping can be activatedseparately for each stage as well.

Different operating modes can be selected.The earth-fault protection is suitable forthree-phase and, optionally, for single-phase tripping by means of a sophisticatedphase selector. It may be blocked during thedead time of single-pole auto-reclosecycles or during pickup of the distance pro-tection.

Tele (pilot) protection for directionalearth-fault protection (ANSI 85-67N)

The directional earth-fault protection canbe combined with the available signalingmethods:

• Directional comparison

• BLOCKING

• UNBLOCKING

The transient blocking function (current re-versal guard) is also provided in order tosuppress interference signals during trippingof parallel lines.

The pilot functions for distance protectionand for earth-fault protection can use thesame signaling channel or two separate andredundant channels.

Backup overcurrent protection(ANSI 50, 50N, 51, 51N, 67)

The 7SA6 provides a backup overcurrentprotection. Two definite-time stages andone inverse-time stage (IDMTL) are avail-able, separately for phase currents and forthe earth current. The application can be ex-tended to a directional overcurrent protec-tion (ANSI 67) by taking into account thedecision of the available direction detectionelements. Two operating modes areselectable. The function can run in parallelto the distance protection or only duringfailure of the voltage in the VT secondarycircuit (emergency operation).

The secondary voltage failure can be de-tected by the integrated fuse failure monitoror via a binary input from a VT miniaturecircuit-breaker (VT m.c.b. trip).

Inverse-time characteristics according toIEC 60255-3 and ANSI/IEEE are provided(see “Technical data”).

Instantaneous high-speed switch-onto-faultovercurrent protection (ANSI 50HS)

Instantaneous tripping is required when en-ergizing a faulty line. In the event of largefault currents, the high-speed switch-onto-fault overcurrent stage can initiate very fastthree-pole tripping.

With smaller fault currents, instantaneoustripping after switch-onto-fault is also pos-sible with the overreach distance zone Z1Bor with pickup.

The switch-onto-fault initiation can be de-tected via the binary input “manual close”or automatically via measurement.

Earth-fault detection in systems with astar-point that is not effectively earthed

In systems with an isolated or resonantearthed (grounded) star-point, single-phaseearth faults can be detected. The followingfunctions are integrated for this purpose:

• Detection of an earth fault by monitoringof the displacement voltage

• Determination of the faulted phase bymeasurement of the phase-to-earth volt-age

• Determination of the earth-fault directionby highly accurate measurement of the ac-tive and reactive power components inthe residual earth fault current.

• Alarm or trip output can be selected in theevent of an earth-fault in the forward di-rection.

• Operation measurement of the active andreactive component in the residual earthcurrent during an earth-fault.

Earth-fault direction detection can also beeffected on the basis of the transientearth-fault principle by interfacing with theadditional unit 7SN60 (see Fig. 6/14). Pro-cedures for logging, time stamping andevent recording for the network controlsystem are standardized by the 7SA6.

Breaker failure protection (ANSI 50BF)

The 7SA6 relay incorporates a two-stagebreaker failure protection to detect failuresof tripping command execution, for exam-ple, due to a defective circuit-breaker. Thecurrent detection logic is phase-selectiveand can therefore also be used in single-poletripping schemes. If the fault current is notinterrupted after a settable time delay hasexpired, a retrip command or a busbar tripcommand will be generated. The breakerfailure protection can be initiated by all in-tegrated protection functions, as well as byexternal devices via binary input signals.

STUB bus overcurrent protection(ANSI 50(N)-STUB)

The STUB bus overcurrent protection is aseparate definite-time overcurrent stage. Itcan be activated via a binary input signalingthat the open line isolator (disconnector) isopen.

Separate settings are available for phase andearth faults.

Auto-recIosure (ANSI 79)

The 7SA6 relay is equipped with an auto-reclosure function (AR). The function in-cludes several operating modes:

• 3-pole auto-reclosure for all types offaults; different dead times are availabledepending on the type of fault

• 1-pole auto-reclosure for 1-phase faults,no reclosing for multi-phase faults

• 1-pole auto-reclosure for 1-phase faultsand for 2-phase faults without earth, noreclosing for multi-phase faults

• 1-pole auto-reclosure for 1-phase and3-pole auto-reclosure for multi-phasefaults

• 1-pole auto-reclosure for 1-phase faultsand 2-phase faults without earth and3-pole auto-reclosure for multi-phasefaults

• Multiple-shot auto-reclosure

• Interaction with an external device forauto-reclosure via binary inputs andoutputs

• Control of the internal AR function byexternal protection

• Interaction with the internal or anexternal synchro-check

• Monitoring of the circuit-breaker auxil-iary contacts

In addition to the above-mentioned operat-ing modes, several other operating princi-ples can be employed by means of theintegrated programmable logic (CFC).

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/9

Protection functions

Page 8: Distance Protection 7SA6

Auto-recIosure (cont’d) (ANSI 79)

Integration of auto-reclosure in the feederprotection allows evaluation of the line-sidevoltages. A number of voltage-dependentsupplementary functions are thus available:

• DLCBy means of dead-line check, reclosure iseffected only when the line is deenergized(prevention of asynchronous breaker clo-sure).

• ADTThe adaptive dead time is employed onlyif auto-reclosure at the remote station wassuccessful (reduction of stress on equip-ment).

• RDTReduced dead time is employed in con-junction with auto-reclosure where noteleprotection method is employed:When faults within the zone extensionbut external to the protected line areswitched off for rapid auto-reclosure(RAR), the RDT function decides on thebasis of measurement of the return volt-age from the remote station which has nottripped whether or not to reduce the deadtime.

Synchronism check (ANSI 25)

Where two network sections are switched inby control command or following a 3-poleauto-reclosure, it must be ensured that bothnetwork sections are mutually synchronous.For this purpose a synchro-check functionis provided. After verification of the net-work synchronism, the function releases theCLOSE command. Alternatively, reclosingcan be enabled for different criteria, e.g.checking that the busbar or line is not carry-ing a voltage (dead line or dead bus).

Fuse failure monitoring and other supervi-sion functions

The 7SA6 relay provides comprehensive su-pervision functions covering both hardwareand software. Furthermore, the measuredvalues are continuously checked for plausi-bility. Therefore the current and voltagetransformers are also included in this super-vision system.

If any measured voltage is not present dueto short-circuit or open circuit in the volt-age transformer secondary circuit, the dis-tance protection would respond with anunwanted trip due to this loss of voltage.

This secondary voltage interruption can bedetected by means of the integrated fusefailure monitor. Immediate blocking of dis-tance protection and switching to thebackup-emergency overcurrent protectionis provided for all types of secondary voltagefailures.

Additional measurement supervisionfunctions are

• Symmetry of voltages and currents

• Broken-conductor supervision

• Summation of currents and voltages

• Phase-sequence supervision.

Directional power protection

The 7SA6 has a function for detecting thepower direction by measuring the phase an-gle of the positive-sequence system's power.Fig. 6/15 shows an application example dis-playing negative active power. An indicationis issued in the case when the measured an-gle ϕ (S1) of the positive-sequence systempower is within the P - Q - level sector.This sector is between angles ϕ A and ϕ B.Via CFC the output signal of the directionalmonitoring can be linked to the "DirectTransfer Trip (DTT)" function and thus, asreverse power protection, initiate tripping ofthe CB.

Fig. 6/16 shows another application display-ing capacitive reactive power. In the case ofovervoltage being detected due to long linesunder no-load conditions it is possible toselect the lines where capacitive reactivepower is measured.

Trip circuit supervision (ANSI 74TC)

One or two binary inputs for each circuit-breaker pole can be used for monitoring thecircuit-breaker trip coils including the con-necting cables. An alarm signal is issuedwhenever the circuit is interrupted.

Lockout (ANSI 86)

Under certain operating conditions it is ad-visable to block CLOSE commands after aTRIP command of the relay has been issued.Only a manual “RESET” command un-blocks the CLOSE command. The 7SA6 isequipped with such an interlocking logic.

Thermal overload protection (ANSI 49)

For thermal protection of cables and trans-formers an overload protection with anearly-warning stage is provided. The ther-mal replica can be generated with the maxi-mum or mean value of the respectiveovertemperatures in the three phases, orwith the overtemperature corresponding tothe maximum phase current.

The tripping time characteristics are expo-nential functions according to IEC 60255-8and they take account of heat loss due to theload current and the accompanying drop intemperature of the cooling medium. Theprevious load is therefore taken into ac-count in the tripping time with overload. Asettable alarm stage can output a current ortemperature-dependent indication beforethe tripping point is reached.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/10

Protection functions ��������������� ������

�������������� ������

��

��

��

��

����

���

��

����

Fig. 6/15 Monitoring of active power direction

��

��

��

��

����

����

��

����

�������������

������������

Fig. 6/16 Monitoring of reactive power

Page 9: Distance Protection 7SA6

BCD-coded output of fault location

The fault location calculated by the unit canbe output for remote indication in BCDcode. The output of the fault location ismade in percent of the set line length with3 decimal digits.

Analog output 0 to 20 mA

Some measured values can be output as an-alog values (0 to 20 mA). On a plug-inmodule (Fig. 6/21) two analog channels aremade available. Up to two plug-in modulescan be installed in the 7SA6. As an option, 2,4 or no analog channels are available (pleaserefer to the selection and ordering data).The available measured values can be gath-ered from the technical data.

Commissioning and fault event analyzing

Special attention has been paid to commis-sioning. All binary inputs and outputs canbe displayed and activated directly. This cansimplify the wiring check significantly forthe user. The operational and fault eventsand the fault records are clearly arranged.For applications with serial protection datainterface, all currents, voltages and phasesare available via communication link at eachlocal unit, displayed at the front of the unitwith DIGSI 4 or with WEB Monitor1).A common time tagging facilitates the com-parison of events and fault records.

WEB Monitor - Internet technology simplifiesvisualization

In addition to the universal DIGSI 4 operat-ing program, the relay contains a WEBserver that can be accessed via a telecommu-nication link using a browser (e.g. InternetExplorer). The advantage of this solution isto operate the unit with standard softwaretools and at the same time make use of theIntranet/Internet infrastructure. Apart fromnumeric values, graphical displays in partic-ular provide clear information and a highdegree of operating reliability. Of course, itis also possible to call up detailed measuredvalue displays and annunciation buffers. Byemulation of the integrated unit operationon the PC it is also possible to adjust se-lected settings for commissioning purposes.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/11

Protection functions

Fig. 6/17 Web Monitor: Supported commissioning by phasor diagram

Fig. 6/18 Web Monitor: Display of the protection direction

LSP2

819.

tifLS

P281

8.tif

Page 10: Distance Protection 7SA6

With respect to communication, particularemphasis is placed on the customer require-ments in energy automation:

• Every data item is time-stamped at thesource, i.e. where it originates.

• Already during the process of communi-cation, information is assigned to thecause thereof (e.g. assignment of the indi-cation “circuit-breaker TRIP” to the cor-responding command).

• The communication system automaticallyhandles the transfer of large data blocks(e.g. fault recordings or parameter datafiles). The user has access to these featureswithout any additional programming ef-fort.

• For the safe execution of a control com-mand the corresponding data telegram isinitially acknowledged by the unit whichwill execute the command. After the re-lease and execution of the command afeedback signal is generated. At every stageof the control command execution partic-ular conditions are checked. If these arenot satisfied, command execution may beterminated in a controlled manner.

The units offer a high degree of flexibility bysupporting different standards for connec-tion to industrial and power automationsystems. By means of the communicationmodules, on which the protocols run, ex-change and retrofit is possible. Therefore,the units will also in future allow for opti-mal adaptation to changing communicationinfrastructure such as the application ofEthernet networks (which will also be usedincreasingly in the power supply sector inthe years to come).

Local PC interface

The serial RS232 PC interface accessiblefrom the front of the unit permits quick ac-cess to all parameters and fault event data.The use of the DIGSI 4 operating programis particularly advantageous during commis-sioning.

Service/modem interface

7SA6 units are always fitted with a rear-sidehardwired service interface, optionally asRS232 or RS485. In addition to thefront-side operator interface, a PC can be con-nected here either directly or via a modem.

Time synchronization interface

The time synchronization interface is a stan-dard feature in all units. The supported for-mats are IRIG-B and DCF77.

Reliable bus architecture

• RS485 busWith this data transmission via copperconductors, electromagnetic fault influ-ences are largely eliminated by the use oftwisted-pair conductors. Upon failure of aunit, the remaining system continues tooperate without any problem.

• Fiber-optic double ring circuitThe fiber-optic double ring circuit is im-mune to electromagnetic interference.Upon failure of a section between twounits, the communication system contin-ues to operate without disturbance. It isusually impossible to communicate witha unit that has failed. Should a unit fail,there is no effect on the communicationwith the rest of the system.

Retrofitting: Modules for every type ofcommunication

Communication modules for retrofittingare available for the entire SIPROTEC 4 unitrange. These ensure that, where differentcommunication protocols (IEC 61850,IEC 60870-5-103, PROFIBUS, DNP, etc.)are required, such demands can be met. Forfiber-optic communication, no externalconverter is required for SIPROTEC 4.

IEC 61850 protocol

The Ethernet-based IEC 61850 protocol isthe worldwide standard for protection andcontrol systems used by power supply cor-porations. Siemens was the first manufac-turer to support this standard. By means ofthis protocol, information can also be ex-changed directly between bay units so as toset up simple masterless systems for bay andsystem interlocking. Access to the units viathe Ethernet bus is also be possible withDIGSI. It is also be possible to retrieveoperating and fault messages and fault re-cordings via a browser. This Web monitorwill also provide a few items of unit-specificinformation in browser windows.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/12

Communication

Fig. 6/19IEC 60870-5-103 star-type RS232 copperconductor connection or fiber-optic connection

Fig. 6/20Bus structure for station bus with Ethernetand IEC 61850

Page 11: Distance Protection 7SA6

IEC 60870-5-103 protocol

IEC 60870-5-103 is an internation-ally standardized protocol for effi-cient communication withprotection relays. IEC 60870-5-103is supported by a number of protec-tion device manufacturers and isused worldwide. Supplements forthe control function are defined inthe manufacturer-specific part ofthis standard.

PROFIBUS-DP

PROFIBUS-DP is an industrialcommunications standard and issupported by a number of PLC andprotection device manufacturers.

DNP 3.0

DNP 3.0 (Distributed Network Pro-tocol, Version 3) is an internation-ally recognized protection and bayunit communication protocol.SIPROTEC 4 units are Level 1 andLevel 2 compatible.

Analog outputs 0 to 20 mA

2 or 4 analog output interfaces fortransmission of measured or faultlocation values are available for the7SA6. Two analog output interfacesare provided in an analog outputmodule. Up to two analog outputmodules can be inserted per unit.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/13

Communication

Fig. 6/21Fiber-optic communication module

Fig. 6/23Electrical communication module

Fig. 6/22Fiber-optic Ethernet communication module forIEC 61850 with integrated Ethernet switch

Fig. 6/24Output module 0 to 20 mA, 2 channels

Fig. 6/25Communication

LSP2

162-

afp

en.ti

f

LSP2

810.

tif

LSP2

207-

afp

.tif

LSP2

163-

afp

en.ti

f

Page 12: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/14

Communication

System solutions for protection and stationcontrol

Together with the SICAM power automa-tion system, SIPROTEC 4 can be used withPROFIBUS-FMS. Over the low-cost electri-cal RS485 bus, or interference-free via theoptical double ring, the units exchange in-formation with the control system. Unitsequipped with IEC 60870-5-103 interfacescan be connected to SICAM in parallel viathe RS485 bus or connected in star by fi-ber-optic link. Through this interface, thesystem is open for the connection of units ofother manufacturers (see Fig. 6/25).

Because of the standardized interfaces,SIPROTEC units can also be integrated intosystems of other manufacturers or inSIMATIC. Electrical RS485 or optical inter-faces are available. The optimum physicaldata transfer medium can be chosen thanksto opto-electrical converters. Thus, theRS485 bus allows low-cost wiring in the cu-bicles and an interference-free optical con-nection to the master can be established.

For IEC 61850, an interoperable system so-lution is offered with SICAM PAS. Via the100 Mbits/s Ethernet bus, the units arelinked with PAS electrically or optically tothe station PC. The interface is standard-ized, thus also enabling direct connection ofunits of other manufacturers to the Ethernetbus. With IEC 61850, however, the unitscan also be used in other manufacturers’systems. Units with an IEC 60870-5-103 in-terface are connected with PAS via theEthernet station bus by means of se-rial/Ethernet converters. DIGSI and theWeb monitor can also be used via the samestation bus.

Serial protection data interface

The tele (pilot) protection schemes can beimplemented using digital serial communi-cation. The 7SA6 is capable of remote relaycommunication via direct links or multi-plexed digital communication networks.The serial protection data interface has thefollowing features:

• Fast phase-selective teleprotection signal-ing for distance protection, optionallywith POTT or PUTT schemes

• Signaling for directional earth-fault pro-tection – directional comparison for highresistance faults in solidly earthed systems

• Echo-function

• Two and three-terminal line applicationscan be implemented without additionallogic

• Interclose command transfer with theauto-reclosure “Adaptive dead time”(ADT) mode

• Redundant communication path switchover is possible with the 7SA6 when 2 se-rial protection data interfaces are installed

• 28 remote signals for fast transfer ofbinary signals

• Flexible utilisation of the communicationchannels by means of the programmableCFC logic

• Display of the operational measured val-ues of the opposite terminal(s) withphase-angle information relative to acommon reference vector

• Clock synchronization: the clock in onlyone of the relays must be synchronizedfrom an external so called “Absolute Mas-ter” when using the serial protection datainterface. This relay will then synchronizethe clock of the other (or the two otherrelays in 3 terminal applications) via theprotection data interface.

• 7SA522 and 7SA6 can be combined viathe protection data interface.

The communication possibilities are identi-cal to those for the line differential protec-tion relays 7SD5 and 7SD610. The followingoptions are available:

• FO51), OMA12) module: Optical 820 nm,2 ST connectors, FO cable length up to1.5 km for link to communicationnetworks via communication convertersor for direct FO cable connection

• FO61), OMA22) module: Optical 820 nm,2 ST connectors, FO cable length up to3.5 km, for direct connection viamulti-mode FO cable

• FO171): For direct connectionup to 25 km3), 1300 nm, for mono-modefiber 9/125 μm, LC-Duplex connector

• FO181): For direct connectionup to 60 km3) 1300 nm, for mono-modefiber 9/125 μm, LC-Duplex connector

• FO191): For direct connectionup to 100 km3) 1550 nm, for mono-modefiber 9/125 μm, LC-Duplex connector

The link to a multiplexed communicationnetwork is made by separate communica-tion converters (7XV5662). These have a fi-ber-optic interface with 820 nm and STconnectors to the protection relay. The linkto the communication network is optionallyan electrical X21 or a G703.1 interface.

For operation via copper wire communica-tion (pilot wires), a modern communica-tion converter for copper cables is available.This operates with both the two-wire andthree-wire copper connections which wereused by conventional differential protectionsystems before. The communication con-verter for copper cables is designed for 5 kVinsulation voltage. An additional 20 kV iso-lation transformer can extend the field ofapplications of this technique into rangeswith higher insulation voltage requirements.With SIPROTEC 4 and the communicationconverter for copper cables a digital fol-low-up technique is available for two-wireprotection systems (typical 15 km) and allthree-wire protection systems using existingcopper communication links.

Communication data:

• Supported network interfaces G703.1 with64 kBit/s; X21/RS422 with 64 or 128 or512 kBit/s

• Max. channel delay time 0.1 ms to 30 ms(in steps of 0.1 ms)

• Protocol HDLC

• 32-bit CRC-check according to CCITTand ITU

• Each protection relay possesses a uniquerelay address

• Continuous communication link supervi-sion: Individual faulty data telegrams donot constitute an immediate danger, ifthey occur only sporadically. The statisti-cal availability, per minute and hour, ofthe serial protection data interface can bedisplayed.

Figure 6/26 shows four applications for theserial protection data interface on a two-terminal line.

1) For flush-mounting housing.

2) For surface-mounting housing.

3) For surface-mounting housing the internalfiber-optic module OMA1 will be deliveredtogether with an external repeater.

Page 13: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/15

Communication

Fig. 6/26Communication topologies for the serial protection data interface on a two-terminal line

Page 14: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/16

Communication

Three-terminal lines can also be protectedwith a tele (pilot) protection scheme by us-ing SIPROTEC 4 distance protection relays.The communication topology may then bea ring or a chain topology, see Fig. 6/27. In aring topology a loss of one data connectionis tolerated by the system. The topology isre-routed in a chain with less than 100 ms.To reduce communication links and to savemoney for communications, a chain topol-ogy may be generally applied.

Fig. 6/27 Ring or chain communication topology

Ring topology

Chain topology

Page 15: Distance Protection 7SA6

Connection for current and voltage trans-formers

3 phase current transformers with neutralpoint in the line direction, I4 connected assummation current transformer (=3I0):Holmgreen circuit

3 voltage transformers, without connectionof the broken (open) delta winding on theline side; the 3V0 voltage is derived inter-nally.

Alternative current measurement

The 3 phase current transformers are con-nected in the usual manner. The neutralpoint is in line direction. I4 is connected to aseparate neutral core-balance CT, thus per-mitting a high sensitive 3I0 measurement.

Note: Terminal Q7 of the I4 transformermust be connected to the terminal of thecore balance CT pointing in the same direc-tion as the neutral point of the phase cur-rent transformers (in this case in linedirection). The voltage connection iseffected in accordance with Fig. 6/28, 6/32or 6/33.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/17

Typical connection

Fig. 6/28 Example of connection for current and voltage transformers

Fig. 6/29 Alternative connection of current transformers for sensitiveearth-current measuring with core-balance current transformers

Page 16: Distance Protection 7SA6

Alternative current connection

3 phase current transformers with neutralpoint in the line direction, I4 connected to acurrent transformer in the neutral point ofan earthed transformer for directionalearth-fault protection. The voltage connec-tion is effected in accordance with Fig. 6/28,6/32 or 6/33.

Alternative current connection

3 phase current transformers with neutralpoint in the line direction, I4 connected tosummation current of the parallel line forparallel line compensation on overheadlines. The voltage connection is effected inaccordance with Fig. 6/28, 6/32 or 6/33.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/18

Typical connection

Fig. 6/30 Alternative connection of current transformers for measuringneutral current of an earthed power transformer

Fig. 6/31 Alternative connection of current transformers for measuringthe earth current of a parallel line

Page 17: Distance Protection 7SA6

Alternative voltage connection

3 phase voltage transformers, V4 connectedto broken (open) delta winding (Ven) foradditional summation voltage monitoringand earth-fault directional protection.The current connection is effected inaccordance with Fig. 6/28, 6/29, 6/30and 6/31.

Alternative voltage connection

3 phase voltage transformers, V4 connectedto busbar voltage transformer for synchro-check.

Note: Any phase-to-phase or phase-to-earthvoltage may be employed as the busbar volt-age. Parameterization is carried out on theunit. The current connection is effected inaccordance with Fig. 6/28, 6/29, 6/30and 6/31.

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/19

Typical connection

Fig. 6/32 Alternative connection of voltage transformers for measuring thedisplacement voltage (e-n voltage)

Fig. 6/33 Alternative connection of voltage transformers for measuring thebusbar voltage

Page 18: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/20

Technical data

General unit data

Analog inputs

Rated frequency 50 or 60 Hz (selectable)

Rated current Inom 1 or 5 A (selectable)

Rated voltage Vnom 80 to 125 V (selectable)

Power consumptionWith Inom = 1 AWith Inom = 5 AFor IE, sensitive with 1 AVoltage inputs

Approx. 0.05 VAApprox. 0.30 VAApprox. 0.05 VA≤ 0.10 VA

Overload capacity of current circuit(r.m.s.)

Thermal

Dynamic (peak value)

500 A for 1 s150 A for 10 s20 A continuous1250 A (half cycle)

Earth currentSensitive

Dynamic (peak value)

300 A for 1 s100 A for 10 s15 A continuous750 A (half cycle)

Thermal overload capacity of volt-age circuit

230 V continuous

Auxiliary voltage

Rated voltages 24 to 48 V DC60 to 125 V DC110 to 250 V DCand 115 to 230 V AC (50/60 Hz)

Permissible tolerance -20 % to +20 %

Superimposed AC voltage(peak-to-peak)

≤ 15 %

Power consumptionQuiescentEnergized

Approx. 5 WApprox. 12 W to 18 W, depending ondesign

Bridging time during failure of theauxiliary voltage

For Vaux = 48 V and Vaux ≥ 110 VFor Vaux = 24 V and Vaux = 60 V

≥ 50 ms≥ 20 ms

Binary inputs

Quantity7SA610*-*A/E/J7SA610*-*B/F/K7SA6*1*-*A/E/J7SA6*1*-*B/F/K7SA6*2*-*A/E/J7SA6*2*-*B/F/K7SA6*2*-*C/G/L

Rated voltage rangePickup threshold

Functions are freely assignable

57132021293324 to 250 V, bipolar17 or 73 or 154 V DC, bipolar

Pickup/reset voltage thresholdsRanges are settable by means ofjumpers for each binary input

19 V DC/10 V DC or 88 V DC/44 V DC,or 176 V DC/88 V DC bipolar(3 nominal ranges 17/73/154 V DC)

Maximum permissible voltage 300 V DC

Current consumption, energized Approx. 1.8 mA

Input impulse suppression 220 nF coupling capacitance at 220 Vwith a recovery time >60 ms

Output contacts

“Unit ready” contact(live status contact)

1 NC/NO contact1)

Command/indication relay

Quantity7SA610*-*A/E/J7SA610*-*B/F/K7SA6*1*-*A/E/J7SA6*1*-*B/F/K7SA6*2*-*A/E/J7SA6*2*-*B/F/K7SA6*2*-*C/G/L

5 NO contacts, 3 NC/NO contact1)

5 NO contacts,12 NO contacts, 4 NC/NO contacts1)

8 NO contacts, 4 power relays2)

19 NO contacts, 5 NC/NO contacts1)

26 NO contacts, 6 NC/NO contacts1)

11 NO contacts, 8 power relays2)

NO/NC contact

Switching capacityMakeBreak, high-speed trip outputsBreak, contactsBreak, contacts (for resistive load)Break, contacts(for τ = L/R ≤ 50 ms)

1000 W / VA1000 W / VA30 VA40 W

25 VA

Switching voltage 250 V

Permissible total current 30 A for 0.5 seconds5 A continuous

Operating time, approx.NO contactNO/NC contact (selectable)Fast NO contactHigh-speed NO trip outputs

8 ms8 ms5 ms< 1 ms

Power relayfor direct control of disconnectoractuator motors

Switching capacityMake for 48 to 250 VBreak for 48 to 250 VMake for 24 VBreak for 24 V

1000 W/ VA1000 W/ VA500 W/ VA500 W/ VA

Switching voltage 250 V

Permissible total current 30 A for 0.5 seconds5 A continuous

Max. operating time 30 s

Permissible relative operating time 1 %

LEDs

RUN (green)ERROR (red)LED (red),function can be assigned7SA6107SA6*1/2/3

Quantity11

714

1) Can be set via jumpers.

2) Each pair of power relays is mechanicallyinterlocked to prevent simultaneous closing.

Page 19: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/21

Technical data

PROFIBUS fiber-opticOnly for flush-mounting housingFor surface-mounting housingBaud rateOptical wavelengthPermissible attenuationDistance

ST connectorOptical interface with OLM4)

Max. 1.5 Mbaudλ = 820 nmMax. 8 dB for 62.5/125 µm fiber

500 kbit/s 1.6 km 1500 kbit/s 530 m

Protection data interface

Quantity 1

FO51), OMA12): Fiber-optic interfacewith clock recovery for direct con-nection up to 1.5 km or for connec-tion to a communication converter,820 nm

For multi-mode fiber 62.5/125 μm,ST connectorsPermissible fiber attenuation 8 dB

FO61), OMA22): Fiber-optic interfacefor direct connection up to 3.5 km,820 nm

For multi-mode fiber 62.5/125 μm,ST connectorsPermissible fiber attenuation 16 dB

FO171): for direct connection up to24 km3), 1300 nm

For mono-mode fiber 9/125 μm,LC-Duplex connectorPermissible fiber attenuation 13 dB

FO181): for direct connection up to60 km3), 1300 nm

For mono-mode fiber 9/125 μm,LC-Duplex connectorPermissible fiber attenuation 29 dB

FO191): for direct connection up to100 km3), 1550 nm

For mono-mode fiber 9/125 μm,LC-Duplex connectorPermissible fiber attenuation 29 dB

Relay communication equipment

External communication converter 7XV5662-0AA00 with X21/RS422 orG703.1 interface

External communication converterfor linking the optical 820 nm inter-face of the unit (FO5/OMA1 optionwith clock recovery) to theX21/RS422/G703.1 interface of thecommunication network

FO interface with 820 nm with clockrecovery

Electrical X21/RS422 interface

Electrical G703.1 interface

Electrical X21/RS422 or G703.1 inter-face settable by jumperBaud rate settable by jumper

Max. 1.5 km with 62.5/125 µm multi-mode fiber to protection relay

64/128/512 kbit (settable by jumper)max. 800 m, 15-pin connector to thecommunication network

64 kbit/s max. 800 m, screw-type ter-minal to the communication network

External communication converter 7XV5662-0AC00 for pilot wires

External communication converterfor linking the optical 820 nm inter-face of the unit (FO5/OMA1 optionwith clock recovery) to pilot wires.

FO interface for 820 nm with clockrecovery

Electrical interface to pilot wires

Typical distance: 15 km max.

Max. 1.5 km with 62.5/125 µm multi-mode fiber to protection relay, 128 kbit

5 kV-isolated

Unit design

Housing 7XP20

Dimensions Refer to part 17 f. dimension drawings

Degree of protection acc. toEN 60529

Surface-mounting housingFlush-mounting housingFrontRearFor the terminals

IP 51

IP 51IP 50IP 20 with terminal cover put on

WeightFlush-mounting 1/3 x 19"housing 1/2 x 19"

2/3 x 19"1/1 x 19"

Surface-mounting 1/3 x 19"housing 1/2 x 19"

1/1 x 19"

4 kg6 kg8 kg10 kg6 kg11 kg19 kg

Serial interfaces

Operating interface for DIGSI 4 (front of unit)

Connection Non-isolated, RS232,9-pin subminiature connector(SUB-D)

Baud rate 4800 to 115200 baudsetting as supplied: 38400 baud;parity 8E1

Time synchronization

DCF77/ IRIG-B signal (format IRIG-B000)

Connection 9-pin subminiature connector(SUB-D)(terminal with surface-mountinghousing)

Voltage levels 5 V, 12 V or 24 V (optional)

Service/modem interface for DIGSI 4 / modem / service

Isolated RS232/RS485

Dielectric testDistance for RS232Distance for RS485

9-pin subminiature connector(SUB-D)500 V / 50 HzMax. 15 mMax. 1000 m

System interface

IEC 61850 EthernetIEC 60870-5-103 protocolPROFIBUS-FMSPROFIBUS-DPDNP 3.0

Isolated RS232/RS485

Baud rateDielectric testDistance for RS232Distance for RS485

9-pin subminiature connector(SUB-D)4800 to 38400 baud500 V / 50 HzMax. 15 mMax. 1000 m

PROFIBUS RS485Dielectric testBaud rateDistance

500 V / 50 HzMax. 12 Mbaud1 km at 93.75 kBd; 100 m at 12 MBd

4) Conversion with external OLMFor fiber-optic interface please complete order number at 11th positionwith 4 (FMS RS485) or 9 and Order Code L0A (DP RS485) or 9 andOrder Code L0G (DNP 3.0) and additionally a suitable external repeater.

1) For flush-mounting housing.

2) For surface-mounting housing.

3) For surface-mounting housing the internal fiber-optic module (OMA1)will be delivered together with an external repeater.

Page 20: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/22

Technical data

Electrical tests

Specifications

Standards IEC 60255 (product standards)IEEE Std C37.90.0/.1/.2; UL 508VDE 0435Further standards see “Individual func-tions”

Insulation tests

Standards IEC 60255–5 and 60870-2-1

High-voltage test (routine test)

All circuits except for powersupply, binary inputs,high-speed outputs,communication and timesynchronization interfaces

2.5 kV (r.m.s.), 50 Hz

Auxiliary voltage, binaryinputs and high-speed outputs(routine test)

3.5 kV DC

only isolated communicationinterfaces and time synchroniza-tion interface (routine test)

500 V (r.m.s.), 50 Hz

Impulse voltage test (type test)All circuits except for communi-cation interfaces and timesynchronization interface, class III

5 kV (peak); 1.2/50 µs; 0.5 Ws,3 positive and 3 negative impulses inintervals of 5 s

EMC tests for noise immunity; type tests

Standards IEC 60255-6/-22 (product standard)EN 61000-6-2 (generic standard),VDE 0435 part 301DIN VDE 0435-110

High-frequency testIEC 60255-22-1 class III andVDE 0435 Section 303, class III

2.5 kV (peak); 1 MHz; τ = 15 μs;400 surges per s; test duration 2 s,Ri = 200 Ω

Electrostatic dischargeIEC 60255-22-2 class IVand IEC 61000-4-2, class IV

8 kV contact discharge; 15 kV airdischarge; both polarities; 150 pF;Ri = 330 Ω

Irradiation with HF field, frequencysweepIEC 60255-22-3 (report) class III

IEC 61000-4-3, class III

10 V/m; 80 to 1000 MHz: 80 % AM;1 kHz10 V/m; 800 to 960 MHz: 80 % AM;1 kHz10 V/m; 1.4 to 2 GHz: 80 % AM; 1 kHz

Irradiation with HF field, single fre-quenciesIEC 60255-22-31, IEC 61000-4-3,class IIIamplitude/pulse modulated

10 V/m; 80, 160, 450. 900 MHz;80 % AM; 1 kHz; duty cycle > 10 s900 MHz; 50 % PM, repetition fre-quency 200 Hz

Fast transient disturbance/burstsIEC 60255-22-4 andIEC 61000-4-4, class IV

4 kV; 5/50 ns; 5 kHz;burst length = 15 ms;repetition rate 300 ms; both polarities;Ri = 50 Ω; test duration 1 min

High-energy surge voltages(SURGE),IEC 61000-4-5 installation class IIIAuxiliary supply

Impulse: 1.2/50 µs

Common mode: 2 kV; 12 Ω; 9 µFDifferential mode:1 kV; 2 Ω; 18 µF

Analog measurement inputs, binaryinputs, relays output

Common mode: 2 kV; 42 Ω; 0.5 µFDifferential mode: 1 kV; 42 Ω; 0.5 µF

Line-conducted HF, amplitude-modulated, IEC 61000-4-6, class III

10 V; 150 kHz to 80 MHz; 80 % AM;1 kHz

Power system frequency magneticfieldIEC 61000-4-8, class IV;IEC 60255-6

30 A/m continuous; 300 A/m for 3 s;

50 Hz0.5 mT; 50 Hz

Oscillatory surge withstandcapability, IEEE Std C37.90.1

2.5 kV (peak); 1 MHzτ = 50 μs; 400 surges per second,test duration 2 s, Ri = 200 Ω

Fast transient surge withstandcapability, IEEE Std C37.90.1

4 kV; 5/50 ns; 5 kHz; burst length = 15 msrepition rate 300 ms, ; both polarities;test duration 1 min; Ri = 50 Ω

Radiated electromagneticinterference IEEE Std C37.90.2

35 V/m; 25 to 1000 MHz,amplitude and pulse-modulated

Damped oscillationsIEC 60694, IEC 61000-4-12

2.5 kV (peak value); polarity alternating100 kHz; 1 MHz; 10 and 50 MHz;Ri = 200 Ω

EMC tests for noise emission; type test

Standard EN 61000-6-3 (generic standard)

Radio noise voltage to lines, onlyauxiliary voltageIEC-CISPR 22

150 kHz to 30 MHzLimit class B

Radio interference field strengthIEC-CISPR 22

30 to 1000 MHzLimit class B

Harmonic currents on the networklead at 230 V AC, IEC 61000-3-2

Class A limits are observed

Voltage fluctuations and flickeron the network incoming feeder at230 V AC, IEC 61000-3-3

Limits are observed

Mechanical stress test

Vibration, shock stress and seismic vibration

During operation

Standards IEC 60255-21 and IEC 60068-2

VibrationIEC 60255-21-1, class 2IEC 60068-2-6

Sinusoidal10 to 60 Hz: ± 0.075 mm amplitude;60 to 150 Hz: 1 g accelerationfrequency sweep 1 octave/min20 cycles in 3 orthogonal axes

ShockIEC 60255-21-2, class 1IEC 60068-2-27

Semi-sinusoidalAcceleration 5 g, duration 11 ms,3 shocks on each of the 3 axes in bothdirections

Seismic vibrationIEC 60255-21-2, class 1IEC 60068-3-3

Sinusoidal1 to 8 Hz: ± 3.5 mm amplitude(horizontal axis)1 to 8 Hz: ± 1.5 mm amplitude(vertical axis)8 to 35 Hz: 1 g acceleration(horizontal axis)8 to 35 Hz: 0.5 g acceleration(vertical axis)Frequency sweep 1 octave/min1 cycle in 3 orthogonal axes

During transport

Standards IEC 60255-21 and IEC 60068-2

VibrationIEC 60255-21-1, class 2IEC 60068-2-6

Sinusoidal5 to 8 Hz: ± 7.5 mm amplitude;8 to 150 Hz: 2 g accelerationFrequency sweep 1 octave/min20 cycles in 3 orthogonal axes

ShockIEC 60255-21-2, class 1IEC 60068-2-27

Semi-sinusoidalAcceleration 15 g, duration 11 ms,3 shocks on each of the 3 axes in bothdirections

Continuous shockIEC 60255-21-2, class 1IEC 60068-2-29

Semi-sinusoidalAcceleration 10 g, duration 16 ms,1000 shocks on each of the 3 axes inboth directions

Page 21: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/23

Technical data

Climatic stress tests

Standard IEC 60255-6

Temperatures

Type-tested acc. to IEC 60068-2-1and -2, test Bd

-25 °C to +85 °C / -13 °F to +185 °F

Temporarily permissible operatingtemperature, tested for 96 h(Legibility of display may be im-paired above +55 °C / +131 °F)

-20 °C to +70 °C / -4 °F to +158 °F

Recommended permanent operat-ing temperature acc. to IEC 60255-6

– Limiting temperature duringpermanent storage

– Limiting temperature duringtransport

-5 °C to +55 °C / +23 °F to +131 °F

-25 °C to +55 °C / -13 °F to 131 °F

-25 °C to +70 °C / -13 °F to +158 °F

Humidity

Permissible humidity stress:It is recommended to arrange theunits in such a way that they are notexposed to direct sunlight or pro-nounced temperature changes thatcould cause condensation.

Annual average on ≤ 75 % relativehumidity; on 56 days per year up to93 % relative humidity; condensationis not permitted.

Functions

Distance protection (ANSI 21, 21N)

Types of pickup Overcurrent pickup (I>);Voltage-dependent overcurrentpickup (V< / I>);Voltage-dependent and phase an-gle-dependent overcurrent pickup(V< / I> / ϕ>);Impedance pickup (Z<)

Types of tripping Three-pole for all types of faults;Single-pole for single-phase faults /otherwise three-pole;

Single-pole for single-phase faults andtwo-pole phase-to-phase faults /otherwise three-pole

Characteristic Quadrilateral or circle

Distance protection zones 6, 1 of which as controlled zoneAll zones can be set to forward, re-verse, non-directional or inactive

Timer stages for tripping delay

Setting range

6 for multi-phase faults3 for single-phase faults0 to 30 s or deactivated (steps 0.01 s)

Zone setting X(for distance zones and Z< starting)

0.050 to 600 Ω (1A) / 0.01 to 120 Ω (5A)

(step 0.001 Ω)

Resistance setting(for quadrilateral distance zones andZ< starting)

Phase-to-phase faults andphase-to-earth faults

0.05 to 600 Ω (1A) / 0.01 to 120 Ω (5A)

(step 0.001 Ω)

Line angle 10 ° to 89 °

Inclination angle forquadrilateral characteristic

30° to 90° (step 1°)

Zone setting Zr

(for circle characteristic)0.050 to 600 Ω(1 A)/0.010 to 120 Ω(5 A)

(step 0.001 Ω)

Threshold angle α for increasedresistance tolerance (circle charac.)

10 to 90 ° (step 1°)

Overcurrent pickup I>>(for I>>, V</I>, V</I>/ϕ>)

0.25 to 10 A (1A) / 1.25 to 50 A (5A)

(step 0.01 A)

Minimum current pickup I>(for V</I>, V</I>/ϕ> and Z<)

0.05 to 4 A (1A) / 0.25 to 20 A (5A)

(step 0.01 A)

Minimum current pickup Iϕ>(for V</I>, V</I>/ϕ>)

0.1 to 8 A (1A) / 0.5 to 40 A (5A)

(step 0.01 A)

Undervoltage pickup (for V</I>and V</I>/ϕ>)

VPH-e<VPH-PH<

20 to 70 V (step 1 V)40 to 130 V (step 1 V)

Load angle pickup (for V</I>/ϕ>)Load angle ϕLoad angle ϕ

30 ° to 80 °90 ° to 120 °

Load zone (for Z<)

Load angleResistance

Impedances within the load zone donot cause pickup in pickup mode Z<;Load zones for phase-to-phase andphase-to-earth faults can be set sepa-rately20 ° to 60 °0.1 to 600 Ω (1A) / 0.02 to 120 Ω (5A)

Earth-fault detectionEarth current 3I0>

Zero-sequence voltage 3V0>for earthed networksfor resonant-earthed networks

0.05 to 4 A (1A) / 0.25 A to 20 A (5A)

(step 0.01 A)

1 to 100 V (step 1 V) or deactivated10 to 200 V (step 1 V)

Earth impedance matchingParameter formatsSeparately settable for

RE/RL and XE/XL

k0 and ϕ (k0)

RE/RL and XE/XL or k0 and ϕ (k0)Distance protection zone Z1 andhigher distance zones (Z1B, Z2 to Z5)-0.33 to +7.00 (step 0.01)0 to 4 (step 0.01) and - 135 ° to 135 °(step 0.01 °)

Parallel line matchingRM/RL and XM/XL

For parallel compensation0 to 8 (step 0.01)

Phase preference on doubleearth-faults in resonant-earthed /non-earthed networks

Phase preference or no preference(selectable)

Direction decision for all types offaults

Direction sensitivity

With fault-free voltages and/or volt-age memoryDynamically unlimited

Page 22: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/24

Technical data

TimesShortest trip time(measured at the fast relay;refer to the terminalconnection diagram)Shortest trip time (measured atthe high-speed trip outputs)Reset time

Approx. 17 ms for fN = 50 HzApprox. 15 ms for fN = 60 Hz

Approx. 12 ms at 50 HzApprox. 10 ms at 60 HzApprox. 30 ms

Tolerances For sinusoidal measured variables

Response values (in conformitywith DIN 57435, Part 303)V and IAngle (ϕ)

≤ 5 % of setting value≤ 3 °

Impedances(in conformity with DIN 57435,Part 303)

ΔX

X≤ 5 % for 30 ° ≤ ϕSC ≤ 90 °

ΔR

R≤ 5 % for 0 ° ≤ ϕSC ≤ 60 °

Time stages 1 % of setting value or 10 ms

Fault locator

Output of the distance to fault X, R (secondary) in ΩX, R (primary) in ΩDistance in kilometers or in % of linelength

Start of calculation With trip, with reset of pickup, withbinary input

Reactance per unit length 0.005 to 6.5 Ω/km(1A) / 0.001 to1.3 Ω/km(5A)

(step 0.001 Ω/km)

Tolerance For sinusoidal quantities≤ 2.5 % line length for30 ° ≤ ϕSC ≤ 90 ° and VSC/Vnom > 0.1

BCD-coded output of fault location

Indicated value Fault location in % of the line length

Output signals Max. 10:d[1 %], d[2 %], d[4 %], d[8 %],d[10 %], d[20 %], d[40 %], d[80 %],d[100 %], d[release]

Indication range 0 % to 195 %

Tele (pilot) protection for distance protection (ANSI 85-21)

Modes of operation PUTT (Z1B acceleration); DUTT;PUTT (acceleration with pickup);POTT; Directional comparison;Reverse interlockingPilot-wire comparison; Unblocking;Blocking

Additional functions Echo function(refer to weak-infeed function)Transient blocking for schemes withmeasuring range extension

Transmission and reception signals Phase-selective signals available formaximum selectivity with single-poletripping; signals for 2- and 3-end-lines

Weak-infeed protection (ANSI 27-WI)

Operating modes with carrier (sig-nal) reception and no fault detection

EchoEcho and trip with undervoltage

Undervoltage phase-earth 2 to 70 V (step 1 V)

Time delay 0 to 30 s (step 0.01 s)

Echo impulse 0 to 30 s (step 0.01 s)

TolerancesVoltage thresholdTimer

≤ 5 % of setting value or 0.5 V1 % of setting value or 10 ms

Direct transfer trip (DTT)

Direct phase-selective tripping viabinary input

Alternatively with or withoutauto-reclosure

Trip time delay 0 to 30 s (step 0.01 s)

Timer tolerance 1 % of setting value or 10 ms

Power swing detection (ANSI 68, 68T)

Power swing detection principle Measurement of the rate of change ofthe impedance vector and monitoringof the vector path

Max. detectable power swing fre-quency

Approx. 7 Hz

Operating modes Power swing blocking and/orpower swing tripping for out-of-stepconditions

Power swing blocking programs All zones blocked; Z1/Z1B blocked;Z2 to Z5 blocked; Z1, Z1B, Z2blocked

Detection of faults during powerswing blocking

Reset of power swing blocking for alltypes of faults

Backup overcurrent protection (ANSI 50 (N), 51 (N), 67)

Operating modes Active only with loss of VT secondarycircuit or always active

Characteristic 2 definite-time stages / 1 inverse-timestage

Instantaneous trip afterswitch-onto-fault

Selectable for every stage

Definite-time stage (ANSI 50, 50N)

Phase current pickup IPH>> 0.1 to 25 A (1A) / 0.5 to 125 A (5A)

(step 0.01 A)

Earth current pickup 3I0>> 0.05 to 25 A (1A) / 0.25 to 125 A (5A)

(step 0.01 A)

Phase current pickup IPH> 0.1 to 25 A (1A) / 0.5 to 125 A (5A)

(step 0.01 A)

Earth current pickup 3I0> 0.05 to 25 A (1A) / 0.25 to 125 A (5A)

(step 0.01 A)

Time delay 0 to 30 s (step 0.01 s) or deactivated

TolerancesCurrent pickupDelay times

≤ 3 % of setting value or 1 % IN

1 % of setting value or 10 ms

Operating time Approx. 25 ms

Page 23: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/25

Technical data

Inverse-time stage (ANSI 51, 51N)

Phase current pickup IP 0.1 to 4 A (1A) / 0.5 to 20 A (5A)

(step 0.01 A)

Earth current pickup 3I0P 0.05 to 4 A (1A) / 0.25 to 20 A (5A)

(step 0.01 A)

Tripping time characteristics acc. toIEC 60255-3

Normal inverse; very inverse;extremely inverse; long time inverse

Tripping time characteristics acc. toANSI/IEEE(not for DE region, see selection andordering data 10th position)

Inverse; short inverse; long inverse;moderately inverse; very inverse;extremely inverse; definite inverse

Time multiplier for IEC charac. T Tp = 0.05 to 3 s (step 0.01 s)

Time multiplier for ANSI charac. D DIP = 0.5 to 15 s (step 0.01 s)

Pickup threshold Approx. 1.1 I/Ip (ANSI: I/Ip = M )

Reset threshold Approx. 1.05 x I/Ip (ANSI: I/Ip = M )

TolerancesOperating time for 2 ≤ I/Ip ≤ 20 ≤ 5 % of setpoint ± 15 ms

Directional earth-fault overcurrent protectionfor high-resistance faults in systems with earthed star point(ANSI 50N, 51N, 67N)

Characteristic 3 definite-time stages / 1 inverse-timestage or 4 definite-time stages or3 definite-time stages / 1 V0invers. stage

Phase selector Permits 1-pole tripping for single-phase faults or 3-pole tripping formulti-phase faults selectable for everystage

Inrush restraint Selectable for every stage

Instantaneous trip afterswitch-onto-fault

Selectable for every stage

Influence of harmonicsStages 1 and 2 (I>>> and I>>)

Stages 3 and 4(I> and inverse 4th stage)

3rd and higher harmonics are com-pletely suppressed by digital filtering

2nd and higher harmonics are com-pletely suppressed by digital filtering

Definite-time stage (ANSI 50N)

Pickup value 3I0>>> 0.5 to 25 A (1A) / 2.5 to 125 A (5A)

(step 0.01 A)

Pickup value 3I0>> 0.2 to 25 A (1A) / 1 to 125 A (5A)

(step 0.01 A)

Pickup value 3I0> 0.05 to 25 A (1A) / 0.25 to 125 A (5A)

(step 0.01 A)Neutral (residual) current trans-former with normal sensitivity(refer to ordering data, position 7);0.003 to 25 A (1A) / 0.015 to 125 A (5A)

(step 0.001 A)Neutral (residual) current trans-former with high sensitivity (refer toordering data, position 7)

Pickup value 3I0, 4th stage 0.05 to 25 A (1A) / 0.25 to 125 A (5A)

(step 0.01 A)Neutral (residual) current trans-former with normal sensitivity(refer to ordering data, position 7);0.003 to 25 A (1A) / 0.015 to 125 A (5A)

(step 0.001 A)Neutral (residual) current trans-former with high sensitivity(refer to ordering data, position 7)

Time delay for definite-time stages 0 to 30 s (step 0.01 s) or deactivated

TolerancesCurrent pickupDelay times

≤ 3 % of setting value or 1 % Inom

1 % of setting value or 10 ms

Command / pickup times 3I0>>>and 3I0>>

Approx. 30 ms

Command / pickup times 3I0> and3I0, 4th stage

Approx. 40 ms

Inverse-time stage (ANSI 51N)

Earth-current pickup 3I0P 0.05 to 4 A (1A) / 0.25 to 20 A (5A)(step 0.01 A)Neutral (residual) current trans-former with normal sensitivity(refer to ordering data, position 7)0.003 to 4 A (1A) / 0.015 to 20 A (5A)(step 0.001 A)Neutral (residual) current trans-former with high sensitivity (refer toordering data, position 7)

Tripping characteristics acc. toIEC 60255-3

Normal inverse; very inverse;extremely inverse; long time

ANSI/IEEE tripping characteristic(not for region DE, see selection andordering data, position 10)

Inverse; short inverse; long inverse;moderately inverse; very inverse;extremely inverse; definite inverse

Inverse logarithmic tripping charac-teristics (not for regions DE and US,see selection and ordering data,position 10)

Pickup threshold

t T T= −3 0 3 0

3 0

3 0I I

I

IPmax Pp

ln

1.1 to 4.0 x I/Ip (step 0.1 s)

Time multiplier for IEC charac. T Tp = 0.05 to 3 s (step 0.01 s)

Time multiplier for ANSI charac. D DI0P = 0.5 to 15 s (step 0.01 s)

Pickup threshold Approx. 1.1 I/Ip (ANSI: I/Ip = M)

Inverse logarithmic pickup threshold 1.1 to 4.0 x I/I0P (step 0.1)

Reset threshold Approx. 1.05 I/I0P (ANSI: I/Ip = M)

ToleranceOperating time for 2 ≤ I/Ip ≤ 20 ≤ 5 % of setpoint ± 15 ms

Zero-sequence voltage protection V0inverse

Tripping characteristic tV

V

=−

2

0

4

s

0inv min

Compensated zero-sequence power Sr = 3I0 ⋅ 3V0 ⋅ cos (ϕ - ϕcomp.)

Direction decision (ANSI 67N)

Measured signals for directiondecision

3I0 and 3V0 or3I0 and 3V0 and IY (star point currentof an earthed power transformer) or3I2 and 3V2 (negative-sequencesystem) or zero-sequence power Sr orautomatic selection of zero-sequenceor negative-sequence quantities de-pendent on the magnitude of thecomponent voltages

Min. zero-sequence voltage 3V0 0.5 to 10 V (step 0.1 V)

Min. current IY

(of earthed transformers)0.05 to 1 A (1A) / 0.25 to 5 A (5A)

(step 0.01 A)

Min. negative-sequence voltage 3V2 0.5 to 10 V (step 0.1 V)

Min. negative-sequence current 3I2 0.05 to 1 A (1A) / 0.25 to 5 A (5A)

(step 0.01 A)

Page 24: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/26

Technical data

Inrush current blocking, capable of being activated for each stage

Component of the 2nd harmonic 10 to 45 % of the fundamental(step 1 %)

Max. current, which cancels inrushcurrent blocking

0.5 to 25 A (1A) / 2.5 to 125 A (5A)(step 0.01 A)

Tele (pilot) protection

For directional earth-fault protection (ANSI 85-67N)

Operating modes Directional comparison, blocking,unblocking

Additional functions Echo (see function “weak infeed”);transient blocking for schemes withparallel lines

Send and receive signals Suitable for 2 and 3 end-lines

Instantaneous high-speed switch-onto-fault overcurrent protection(ANSI 50HS)

Operating mode Active only after CB closing;instantaneous trip after pickup

Pickup current I>>> 1 to 25 A (1A) / 5 to 125 A (5A)

(step 0.01 A)

Reset ratio Approx. 0.90

TolerancesCurrent starting ≤ 3 % of setting value or 1 % IN

Shortest tripping timeWith reference to fast relaysWith high-speed trip to outputs

Approx. 12 msApprox. 8 ms

Voltage protection (ANSI 59, 27)

Operating modes Local tripping and/or carrier trip forremote end

Overvoltage protection

Pickup values VPH-E>>, VPH-E>(phase-earth overvoltage)

1 to 170 V (step 0.1 V)

Pickup values VPH-PH>>, VPH-PH>(phase-phase overvoltage)

2 to 220 V (step 0.1 V)

Pickup values 3V0>>, 3V0>(3V0 can be measured via V4 trans-formers or calculated by the relay)(zero-sequence overvoltage)

1 to 220 V (step 0.1 V)

Pickup values V1>>, V1>(positive-sequence overvoltage)Measured voltage

2 to 220 V (step 0.1 V)

Local positive-sequence voltage orcalculated remote positive-sequence voltage (compounding)

Pickup values V2>>, V2>(negative-sequence overvoltage)

2 to 220 V (step 0.1 V)

Reset ratio (settable) 0.5 to 0.98 (step 0.01)

Undervoltage protection

Pickup values VPH-E<<, VPH-E<(phase-earth undervoltage)

1 to 100 V (step 0.1 V)

Pickup values VPH-PH<<, VPH-PH<(phase-phase undervoltage)

1 to 170 V (step 0.1 V)

Pickup values V1<<, V1<(positive-sequence undervoltage)

1 to 100 V (step 0.1 V)

Blocking of undervoltage prot. stages Minimum current; binary input

Reset ratio (settable) 1.01 to 1.20 (step 0.01)

Time delays

Time delay for all stages 0 to 100 s (step 0.01 s) or deactivated

Command / pickup time Approx. 30 ms

Command/pickup time for 3V0

stagesApprox. 30 ms or 65 ms (settable)

TolerancesVoltage limit valuesTime stages

≤ 3 % of setting value or 1 V1 % of setting value or 10 ms

Frequency protection (ANSI 81)

Number of frequency elements 4

Setting range 45.5 to 54.5 Hz(in steps of 0.01) at fnom = 50 Hz55.5 to 64.5 Hz(in steps of 0.01) at fnom = 60 Hz

Delay times 0 to 600 s or ∞ (in steps of 0.01 s)

Operating voltage range 6 to 230 V (phase-to-earth)

Pickup times Approx. 80 ms

Dropout timesHysteresisDropout condition

Approx. 80 msApprox. 20 mHzVoltage = 0 V and current = 0 A

TolerancesFrequencyDelay times

15 mHz for VPH-PH: 50 to 230 V1 % of the setting value or 10 ms

Thermal overload protection (ANSI 49)

Factor k acc. to IEC 60255-8 0.1 to 4 (steps 0.01)

Time constant τ 1 to 999.9 min (steps 0.1 min)

Thermal alarm stage ΘAlarm/ΘTrip 50 to 100 % referred to trippingtemperature (steps 1 %)

Current-based alarm stage IAlarm 0.1 to 4 A (1A) / 0.5 to 20 A (5A)

(steps 0.01 A)

Calculating mode forovertemperature

Θmax, Θmean, Θ with Imax

Pickup time characteristic( )

t =−

−τ ln

I I

I I2

2 2

2

pre

nomk

Reset ratioΘ/ΘAlarm

Θ/ΘTrip

I/ IAlarm

Approx. 0.99Approx. 0.99Approx. 0.97

Overload measured values Θ/ΘTrip L1; Θ/ΘTrip L2; Θ/ΘTrip L3;Θ/ΘTrip

Tolerances Class 10 % acc. to IEC 60255-8

Breaker failure protection (ANSI 50BF)

Number of stages 2

Pickup of current element 0.05 to 20 A (1A) / 0.25 to 100 A (5A)

(step 0.01 A)

Time delays T11phase, T13phase, T2 0 to 30 s (steps 0.01 s) or deactivated

Additional functions End-fault protectionCB pole discrepancy monitoring

Drop-off (overshoot) time, internal ≤ 15 ms, typical; 25 ms, max.

TolerancesCurrent limit valueTime stages

≤ 5 % of setting value or 1 % Inom

1 % of setting value or 10 ms

Page 25: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/27

Auto-reclosure (ANSI 79)

Number of auto-reclosures Up to 8

Operating mode Only 1-pole; only 3-pole, 1 or 3-pole

Operating modes with line voltagecheck

DLC – dead-line checkADT – adaptive dead timeRDT – reduced dead time

Dead times T1-PH, T3-PH, TSeq 0 to 1800 s (step 0.01 s) or deactivated

Action times 0.01 to 300 s (step 0.01 s) or deactivated

Reclaim times 0.5 to 300 s (step 0.01 s)

Start-signal monitoring time 0.01 to 300 s (step 0.01 s)

Additional functions Synchro-check request3-phase intertrippingInterCLOSE command to the remoteendCheck of CB ready stateBlocking with manual CLOSE

Voltage limit values for DLC, ADT,RDT

Healthy line voltage PH-E

Dead line voltage PH-E

30 to 90 V (step 1 V)2 to 70 V (step 1 V)

TolerancesTime stagesVoltage limit values

1 % of setting value or 10 ms≤ 3 % of setting value or 1 V

Synchro-check (ANSI 25)

Initiate options Auto-reclosure;Manual CLOSE controlControl commands

Operating modesWith auto-reclosure

For manual closureand control commands

Synchro-checkLine dead/busbar liveLine live/busbar deadLine and busbar deadBypassing

As for auto-reclosure

Permissible voltage difference 1 to 60 V (step 0.1 V)

Permissible frequency difference 0.03 to 2 Hz (step 0.01 Hz)

Permissible angle difference 2 to 80 ° (step 1°)

Max. duration of synchronization 0.01 to 600 s (step 0.01 s) or deactivated

Release delay with synchronousnetworks

0 to 30 s (step 0.01 s)

Minimum measuring time Approx. 80 ms

TolerancesTime stagesVoltage limit values

1 % of setting value or 10 ms≤ 2 % of setting value or 1 V

Earth-fault detection for compensated / isolated networks

Zero-sequence voltage 3V0 1 to 150 V (step 1 V)

Phase selection with phase voltagesV< and V>

10 to 100 V (step 1 V)

Directional determination Active / reactive power measurements

Minimum current for directionaldetermination

3 to 1000 mA (steps 1 mA)

Angle correction for core-balanceCT

0 to 5 ° at 2 operating points(step 0.1 °)

Operating modes Only indication; indication and trip

Technical data

Delay times 0 to 320 s (step 0.01 s)

Pickup time Approx. 50 ms

Earth-fault measured values Active and reactive componentof earth-fault current IEEac, IEEreac

TolerancesVoltage limit valuesCurrent limit valuesTime stages

≤ 5 % of setting value or 1 V≤ 10 % of setting value1 % of setting value or 10 ms

Trip circuit supervision (ANSI 74TC)

Number of supervisable trip circuits Up to 3

Number of required binary inputsper trip circuit

1 or 2

Indication relay 1 to 30 s (step 1 s)

Additional functions

Operational measured values

Representation Primary, secondary and percentagereferred to rated value

Currents 3 x IPhase ; 3I0; IE sensitve; I1; I2; IY;3I0PAR

Tolerances Typ. 0.3 % of indicated measuredvalue or 0.5 % Inom

Voltages 3 x VPhase-Earth; 3 x VPhase-Phase; 3V0,V1, V2, VSYNC, Ven

Tolerances Typ. 0.25 % of indicated measuredvalue or 0.01 % Vnom

Power with direction indication P, Q, S

TolerancesP: for ⏐cos ϕ⏐ = 0.7 to 1 andV/Vnom, I/Inom = 50 to 120 %Q: for ⏐sin ϕ⏐ = 0.7 to 1 andV/Vnom , I/Inom = 50 to 120 %S: for V/Vnom, I/Inom = 50 to120 %

Typical ≤ 1%

Typical ≤ 1%

Typical ≤ 1%

FrequencyTolerance

f≤ 10 mHz

Power factor

Tolerance for ⏐cos ϕ⏐ = 0.7 to 1

p.f. (cos ϕ)

Typical ≤ 0.02

Load impedances with directionalindication

3 x RPhase-Earth, XPhase-Earth

3 x RPhase-Phase, XPhase-Phase

Earth-fault measured values Active and reactive componentof earth-fault current IEEac, IEEreac

Overload measured values Θ/ΘTrip L1; Θ/ΘTrip L2; Θ/ΘTrip L3;Θ/ΘTrip

Long-term mean values

Interval for derivation of mean value 15 min / 1 min; 15 min / 3 min;15 min / 15 min

Synchronization instant Every ¼ hour; every ½ hour; everyhour

Values 3 x IPhase; I1; P; P+; P-; Q; Q+; Q-; S

Page 26: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/28

Technical data

Minimum/maximum memory

Indication Measured values with date and time

Resetting CyclicallyVia binary inputVia the keyboardVia serial interface

ValuesMin./max. of measured values

Min./max. of mean values

3 x IPhase; I1; 3 x VPhase-Earth;3 x VPhase-to-phase; 3V0; V1;P+; P-; Q+; Q-; S; f; power factor (+);power factor (–)3 x IPhase; I1; P; Q; S

Energy meters

Four-quadrant meters WP+; WP-; WQ+; WQ-

Tolerancefor ⏐cos ϕ⏐ > 0.7 and V > 50 %Vnom and I > 50 % Inom

5 %

Analog measured value output 0 to 20 mA

Number of analog channels 2 per plug-in moduleAlternatively 1 or 2 or no plug-inmodule (Refer to ordering data,position 11 and Order code forposition 12)

Indication range 0 to 22 mA

Selectable measured values Fault location [%];fault location [km]; VL23 [%]; IL2

[%]; |P| [%]; |Q| [%];breaking current Imax-primary

Max. burden 350 Ω

Oscillographic fault recording

Analog channels 3 x IPhase, 3I0, 3I0 PAR

3 x VPhase, 3V0, VSYNC, Ven

Max. number of available recordings 8, backed-up by battery if auxiliaryvoltage supply fails

Sampling intervals 20 samplings per cycle

Total storage time > 15 s

Binary channels Pickup and trip information; numberand contents can be freely configuredby the user

Max. number of displayed binarychannels

40

Control

Number of switching units Depends on the number of binary /indication inputs and indication /command outputs

Control commands Single command / double command1, 1 plus 1 common or 2 pole

Feed back CLOSE, TRIP, intermediate position

Interlocking Freely configurable

Local control Control via menu, function keys,control keys (if available)

Remote control Control protection, DIGSI,pilot wires

Further additional functions

Measured value supervision Current sumCurrent symmetryVoltage sumVoltage symmetryPhase sequenceFuse failure monitorPower direction

IndicationsOperational indications

System disturbance indication

Earth-fault indication

Buffer size 200

Storage of indications of the last8 faults, buffer size 600

Storage of indications of the last8 faults, buffer size 200

Switching statistics Number of breaking operations perCB poleSum of breaking current per phaseBreaking current of last trip operationMax. breaking current per phase

Circuit-breaker test TRIP/CLOSE cycle, 3 phasesTRIP/CLOSE per phase

Dead time for CB TRIP / CLOSEcycle

0 to 30 s (steps 0.01 s)

Commissioning support Operational measured values, c.-b.test, status display of binary inputs,setting of output relays, generationof indications for testing serial inter-faces

Phase rotation adjustment Clockwise or anti-clockwise

CE conformity

This product complies with the directive of the Council of the EuropeanCommunities on the approximation of the laws of the Member States relat-ing to electromagnetic compatibility (EMC Council Directive 89/336/EEC)and concerning electrical equipment for use within specified voltage limits(Low-voltage directive 73/23/EEC).

This conformity is proved by tests conducted by Siemens AG in accordancewith Article 10 of the Council Directive in agreement with the genericstandards EN 61000-6-2 and EN 61000-6-4 for the EMC directive and withthe standard EN 60255-6 for the low-voltage directive.

This device is designed and produced for industrial use.

The product conforms with the international standard of the seriesIEC 60255 and the German standard VDE 0435.

Page 27: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/29

Selection and ordering data Description Order No.

7SA61 distance protection relay for all voltage levels 7SA61��-�����-����

Housing, number of LEDsHousing width 1/3 19", 7 LEDs 0Housing width 1/2 19", 14 LEDs 1Housing width 1/1 19", 14 LEDs 2Housing width 2/3 19", 14 LEDs 3

Measuring input (4 x V, 4 x I)IPH = 1 A1), Ie = 1 A (min. = 0.05 A) 1IPH = 1 A1), Ie = sensitive (min. = 0.003 A) 2IPH = 5 A1), Ie = 5 A (min. = 0.25 A) 5IPH = 5 A1), Ie = sensitive (min. = 0.003 A) 6

Rated auxiliary voltage (power supply, binary inputs)24 to 48 V DC, binary input threshold 17 V3) 260 to 125 V DC2), binary input threshold 17 V3) 4110 to 250 V DC2), 115 to 230 V AC, binary input threshold 73 V3) 5

Binary/ Indication/ Fast High-speed Power Flush- Flush- Surface-indica- command relay4) trip output relay5) mounting mounting mountingtion outputs incl. housing/ housing/ housing/inputs live status screw-type plug-in screw-type

contact terminals terminals terminals

For 7SA6105 4 5 � A5 4 5 � E5 4 5 � J7 6 � B7 6 � F7 6 � K

For 7SA61113 5 12 � A13 5 12 � E13 5 12 � J13 4 8 5 � M13 4 8 5 � N13 4 8 5 � P20 9 4 � B20 9 4 � F20 9 4 � K

For 7SA61221 13 12 � A21 13 12 � E21 13 12 � J21 12 8 5 � M21 12 8 5 � P21 12 8 5 � R29 21 12 � B29 21 12 � F29 21 12 � K29 20 8 5 � N29 20 8 5 � Q29 20 8 5 � S33 12 8 � C33 12 8 � G33 12 8 � L

For 7SA61321 13 12 � A21 12 8 5 � M

1) Rated current can be selected bymeans of jumpers.

2) Transition between the two auxiliaryvoltage ranges can be selected bymeans of jumpers.

3) The binary input thresholds areselectable in three stages by means ofjumpers, exception: versions withpower relays have some binary inputswith only two binary input thresh-olds.

4) Fast relays are identified in theterminal connection diagram.

5) Power relay for direct control ofdisconnector actuator motors.Each pair of contacts is mechanicallyinterlocked to prevent simultaneousclosure.

Operator panel with:- 4-line backlit display,- function keys,- numerical keys,- PC interface

see pages 6/32to 6/35

���

Page 28: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/30

Selection and ordering data Description Order No.

7SA63 distance protection relay for all voltage levels 7SA63��-�����-����

Housing, number of LEDsHousing width 1/2 19", 14 LEDs 1Housing width 1/1 19", 14 LEDs 2

Measuring input (4 x V, 4 x I)IPH = 1 A1), Ie = 1 A (min. = 0.05 A) 1IPH = 1 A1), Ie = sensitive (min. = 0.003 A) 2IPH = 5 A1), Ie = 5 A (min. = 0.25 A) 5IPH = 5 A1), Ie = sensitive (min. = 0.003 A) 6

Rated auxiliary voltage (power supply, binary inputs)24 to 48 V DC, binary input threshold 17 V3) 260 to 125 V DC2), binary input threshold 17 V3) 4110 to 250 V DC2), 115 to 230 V AC, binary input threshold 73 V3) 5

Binary/ Indication/ Fast High-speed Power Flush- Flush- Surface-indica- command relay4) trip outputs relay5) mounting mounting mountingtion- outputs incl. housing/ housing/ housing/inputs live status screw-type plug-in screw-type

contact terminals terminals terminals

For 7SA63113 5 12 � A13 5 12 � E13 5 12 � J13 4 8 5 � M13 4 8 5 � N13 4 8 5 � P20 9 4 � B20 9 4 � F20 9 4 � K

For 7SA63221 13 12 � A21 13 12 � E21 13 12 � J21 12 8 5 � M21 12 8 5 � P21 12 8 5 � R29 21 12 � B29 21 12 � F29 21 12 � K29 20 8 5 � N29 20 8 5 � Q29 20 8 5 � S33 12 8 � C33 12 8 � G33 12 8 � L

1) Rated current can be selected by means of jumpers.

2) Transition between the two auxiliary voltage ranges can be selected by means of jumpers.

3) The binary input thresholds are selectable in three stages by means of jumpers, exception:versions with power relays have some binary inputs with only two binary inputs thresholds.

4) Fast relays are identified in the terminal connection diagram.

5) Power relay for direct control of disconnector actuator motors.Each pair of contacts is mechanically interlocked to prevent simultaneous closure.

Operator panel with:- backlit graphic display for

single-line diagram- control keys,- key-operated switches,- function keys,- numerical keys,- PC interface

see pages 6/32to 6/35

���

LSA

2539

-ag

pen

.ep

s

Page 29: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/31

Selection and ordering data Description Order No.

7SA64 distance protection relay for all voltage levels 7SA64��-�����-����

Housing, number of LEDsHousing width 1/2 19", 14 LEDs 1Housing width 1/1 19", 14 LEDs 2

Measuring input (4 x V, 4 x I)IPH = 1 A1), Ie = 1 A (min. = 0.05 A) 1IPH = 1 A1), Ie = sensitive (min. = 0.003 A) 2IPH = 5 A1), Ie = 5 A (min. = 0.25 A) 5IPH = 5 A1), Ie = sensitive (min. = 0.003 A) 6

Rated auxiliary voltage (power supply, binary inputs)24 to 48 V DC, binary input threshold 17 V3) 260 to 125 V DC2), binary input threshold 17 V3) 4110 to 250 V DC2), 115 to 230 V AC, binary input threshold 73 V3) 5

Binary/ Indication/ Fast High-speed Power Flush- Flush-indica- command relay4) trip outputs relay5) mounting mountingtion- outputs incl. housing/ housing/inputs live status screw-type plug-in

contact terminals terminals

For 7SA64113 5 12 � A13 5 12 � J13 4 8 5 � M13 4 8 5 � P20 9 4 � B20 9 4 � K

For 7SA64221 13 12 � A21 13 12 � J21 12 8 5 � M21 12 8 5 � R29 21 12 � B29 21 12 � K29 20 8 5 � N29 20 8 5 � S33 12 8 � C33 12 8 � L

Units withdetached operator panel with- backlit graphic display- control keys- key-operated switches- function keys- numerical keys- PC interface

1) Rated current can be selected by means of jumpers.

2) Transition between the two auxiliary voltage ranges can be selected by means of jumpers.

3) The binary input thresholds are selectable in three stages by means of jumpers, exception:versions with power relays have some binary inputs with only two binary inputs thresholds.

4) Fast relays are identified in the terminal connection diagram.

5) Power relay for direct control of disconnector actuator motors.Each pair of contacts is mechanically interlocked to prevent simultaneous closure.

see pages 6/32to 6/35

���

LSA

2540

-ag

pen

.ep

s

Page 30: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/32

Selection and ordering data Description Order No. Order code

7SA6 distance protection relay for all voltage levels 7SA6���-�����-���� ���

Region-specific default settings / language settings1)

Region DE, language: German ARegion World, language: English (GB) BRegion US, language: English (US) CRegion FR, French DRegion World, Spanish ERegion World, Italian F

Port BEmpty 0System interface, IEC 60870-5-103 protocol, electrical RS232 1System interface, IEC 60870-5-103 protocol, electrical RS485 2System interface, IEC 60870-5-103 protocol, optical 820 nm, ST connector 3System interface, PROFIBUS-FMS Slave2), electrical RS485 4System interface, PROFIBUS-FMS Slave2), optical 3), double ring 3), ST connector 62 analog outputs, each 0.....20 mA 7System interface, PROFIBUS-DP, electrical RS485 9 L 0 ASystem interface, PROFIBUS-DP, optical 820 nm, double ring 3), ST connector 9 L 0 BSystem interface, DNP 3.0, electrical RS485 9 L 0 GSystem interface, DNP 3.0, optical 820 nm, ST connector3) 9 L 0 HSystem interface, IEC 61850, 100 Mbit/s Ethernet, electrical, duplicate,RJ45 plug connectors 9 L 0 RSystem interface, IEC 61850, 100 Mbit/s Ethernet, optical, double, ST connector4) 9 L 0 S

1) Definitions for region-specific default settings and functions:Region DE: preset to f = 50 Hz and line length in km, only IEC

inverse characteristic can be selected, directional earth (ground)fault protection: no logarithmic inverse characteristic, no direction decisionwith zero-sequence power Sr; distance protection can be selected withquadrilateral or circle characteristic.

Region US: preset to f = 60 Hz and line length in miles, ANSI inversecharacteristic only, directional earth (ground) fault protection:no logarithmic inverse characteristic, no direction decisionwith zero-sequence power Sr, no U0 inverse characteristic.

Region World: preset to f = 50 Hz and line length in km, directional earth (ground) faultprotection: no direction decision with zero-sequence power Sr,no U0 inverse characteristic.

Region FR: preset to f = 50 Hz and line length in km, directional earth (ground)fault protection: no U0 inverse characteristic, no logarithmic inversecharacteristic, weak infeed logic selectable between French specificationand world specification.

2) For SICAM energy automation systems.

3) Optical double ring interfaces are not available with surface mounting housings.

4) For surface mounting housing applications please order the relay with electrical Ethernet interfaceand use a separate fiber-optic switch.

see pages6/33 to 6/35

���

Page 31: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/33

Selection and ordering data Description Order No. Order code

7SA6 distance protection relay for all voltage levels 7SA6���-�����-���� ���

Port C and port DPort C: DIGSI/modem, electrical RS232,Port D: empty 1Port C: DIGSI/modem, electrical RS485,Port D: empty 2Port C and Port D installed 9 M ��

Port CDIGSI/modem, electrical RS232 1DIGSI/modem, electrical RS485 2

Port DProtection data interface: optical 820 nm, two ST connectors, FO cable length up to 1.5 kmFor direct connection via multi-mode FO cable or communication networks 1) AProtection data interface: optical 820 nm, two ST connectors, FO cable length up to 3.5 kmFor direct connection via multi-mode FO cable BTwo analog outputs, each 0...20 mA KProtection data interface: optical 1300 nm, LC-Duplex connectorFO cable length up to 24 km for direct connection via mono-mode FO cable2) GProtection data interface: optical 1300 nm, LC-Duplex connectorFO cable length up to 60 km for direct connection via mono-mode FO cable2)3) HProtection data interface: optical 1550 nm, LC-Duplex connectorFO cable length up to 100 km for direct connection via mono-mode FO cable2)4) J

see pages6/34 and 6/35

���

1) For suitable communicationconverters 7XV5662 (optical toG703.1/X21/RS422 or optical to pilotwire) see "Accessories".

2) For surface -mounting housing appli-cations an internal fiber-optic module820 nm will be delivered in combina-tion with an external repeater.

3) For distances less than 25 km, two opticalattenuators 7XV5107-0AA00 are requiredto avoid optical saturation of the receiverelement.

4) For distances less than 50 km, two opticalattenuators 7XV5107-0AA00 are requiredto avoid optical saturation of the receiverelement.

Page 32: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/34

Selection and ordering data Description Order No.

7SA6 distance protection relay for all voltage levels 7SA6���-�����-����

Functions 1Trip mode Thermal overload BCD-coded output

protection (ANSI 49) for fault location

3-pole 03-pole � 13-pole � 23-pole � � 31/3-pole 41/3-pole � 51/3-pole � 61/3-pole � � 7

Functions 2Distance protection Power swing de- Parallel linepickup (ANSI 21, 21N) tection (ANSI 68, 68T) compensation

I> AV< / I> BQuadrilateral (Z<) CQuadrilateral (Z<), V< / I> / ϕ DQuadrilateral (Z<) � FQuadrilateral (Z<), V< / I> / ϕ � GV< / I> �

1) JQuadrilateral (Z<) �

1) KQuadrilateral (Z<), V< / I> / ϕ �

1) LQuadrilateral (Z<) � �

1) NQuadrilateral (Z<), V< / I> / ϕ � �

1) P

Functions 3Auto-reclosure Synchro- Breaker failure pro- Over/undervoltage protection(ANSI 79) check (ANSI 25) tection (ANSI 50BF) V>, V< (ANSI 27, 59)

Over/underfrequency protection(ANSI 81)

A� B

� C� � D

� E� � F� � G� � � H

� J� � K� � L� � � M� � N� � � P� � � Q� � � � R

Functions 4Directional earth- Earth-fault Measured valuesfault protection, detection extendedearthed networks compensated/ Min, max, mean(ANSI 50N, 51N, isolated67N) networks

0� 1

�2) 2�

2)� 3

� 4� � 5� �

2) 6� �

2)� 7

1) Only with position 7 ofOrder No. = 1 or 5.

2) Only with position 7 ofOrder No. = 2 or 6.

Page 33: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/35

Selection and ordering data Description Order No.

7SA6 distance protection relay for all voltage levels 7SA6���-�����-����

Tripm

ode,

3-po

le

Tripm

ode 1

or3-

pole

Pickup

I>Pick

upV

</I>Z

<(q

uadr

ilate

ral)

V</I>/ϕ

Power

swin

g dete

ctio

n

Parall

ellin

eco

mpe

nsatio

nAut

o-re

closu

reSy

nchro

-che

ckBre

aker

failu

re

prot

ectio

nVol

tage

prot

ectio

n

Freq

uenc

y prot

ectio

n

Earth

-faul

t pro

tect

ion

dire

ctio

nal f

orea

rthed

netw

orks

Earth

-faul

t dire

ctio

nal

for co

mpe

nsat

ediso

lated

netw

orks

Ove

rload

prot

ectio

n

Mea

sure

dva

lues

, ex-

tende

d,m

in. m

ax. m

ean

� � � 1 A B 0

� 1 A B 1

� � � � � � �1)

� 3 B D 6

� � � � � � �1)

� � 3 B D 7

� � � � � � � �1)

� 3 B M 6

� � � � � � � �1)

� � 3 B M 7

� � � � � � � � � � 3 G H 4

� � � � � � � � � � � 3 G H 5

� � � � � � �2)

� � � � � � 7 P R 4

� � � � � � �2)

� � � � � � � 7 P R 5

1) Only with position 7 of Order No. = 2 or 6.

2) Only with position 7 of Order No. = 1 or 5.

Preferential types

Functions 1

Page 34: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/36

AccessoriesAccessories Description Order No.

DIGSI 4Software for configuration and operation of Siemens protection unitsrunning under MS Windows 2000/XP Professionaldevice templates, Comtrade Viewer, electronic manual includedas well as “Getting started” manual on paper, connecting cables (copper)

BasisFull version with license for 10 computers, on CD-ROM(authorization by serial number) 7XS5400-0AA00

ProfessionalDIGSI 4 Basis and additionally SIGRA (fault record analysis),CFC Editor (logic editor), Display Editor (editor for defaultand control displays) and DIGSI 4 Remote (remote operation) 7XS5402-0AA00

Professional + IEC 61850DIGSI 4 Basis and additionally SIGRA (fault record analysis),CFC Editor (logic editor), Display Editor (editor for defaultand control displays) and DIGSI 4 Remote (remote operation)+ IEC 61850 system configurator 7XS5403-0AA00

IEC 61850 System configuratorSoftware for configuration of stations with IEC 61850 communication underDIGSI, running under MS Windows 2000 or XP Professional EditionOptional package for DIGSI 4 Basis or ProfessionalLicense for 10 PCs. Authorization by serial number. On CD-ROM 7XS5460-0AA00

SIGRA 4(generally contained in DIGSI Professional, but can be ordered additionally)Software for graphic visualization, analysis and evaluation of fault records.Can also be used for fault records of devices of other manufacturers(Comtrade format). Running under MS Windows 2000/XP Professional.Incl. templates, electronic manual with license for 10 PCs.Authorization by serial number. On CD-ROM. 7XS5410-0AA00

Connecting cable (copper)Cable between PC/notebook (9-pin connector) and protection unit (9-pin connector)(contained in DIGSI 4, but can be ordered additionally) 7XV5100-4

Voltage transformer miniature circuit-breakerRated current 1.6 A; thermal overload release 1.6 A;overcurrent trip 6 A 3RV1611-1AG14

Manual for 7SA6English, V4.61 and higher C53000-G1176-C156-5

Page 35: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/37

Description Order No. Size ofpackage

Supplier Fig.

Connector 2-pin3-pin

C73334-A1-C35-1C73334-A1-C36-1

11

SiemensSiemens

6/356/36

Crimp CI2 0.5 to 1 mm2

connector0-827039-10-827396-1

40001

AMP 1)

AMP 1)

CI2 1 to 2.5 mm20-827040-10-827397-1

40001

AMP 1)

AMP 1)

Type III+ 0.75 to 1.5 mm20-163083-70-163084-2

40001

AMP 1)

AMP 1)

Crimping For Type III+tool and matching female

for CI2and matching female

0-539635-10-539668-20-734372-11-734387-1

1

1

AMP 1)

AMP 1)

AMP 1)

AMP 1)

19"-mounting rail C73165-A63-D200-1 1 Siemens 6/34

Short-circuit links For current terminalsFor other terminals

C73334-A1-C33-1C73334-A1-C34-1

11

SiemensSiemens

6/376/38

Safety cover for terminals largesmall

C73334-A1-C31-1C73334-A1-C32-1

11

SiemensSiemens

6/46/4

Fig. 6/34 Mounting rail for 19" rack

LSP2

089-

afp

en.ti

f

Fig. 6/352-pin connector

LSP2

090-

afp

en.e

ps

Fig. 6/363-pin connector

LSP2

091-

afp

en.e

ps

Fig. 6/37Short-circuit linkfor current con-tacts

LSP2

093-

afp

en.e

ps

Fig. 6/38Short-circuit linkfor voltage contacts/indications contacts

LSP2

092-

afp

en.e

ps

1) Your local Siemens representative can inform you onlocal suppliers.

Accessories Description Order No.

Opto-electric communication convertersOptical to X21/RS422 or G703.1 7XV5662-0AA00Optical to pilot wires 7XV5662-0AC00

Additional interface modulesProtection data interface FO 5, OMA1, 820 nm, multi-mode FO cable,ST connector, 1.5 km C53207-A351-D651-1Protection data interface FO 6, OMA2, 820 nm, multi-mode FO cable,ST connector, 3.5 km C53207-A351-D652-1Protection data interface FO 17, 1300 nm, mono-mode FO cable,LC-Duplex connector, 24 km C53207-A322-B115-3Protection data interface FO 18, 1300 nm, mono-mode FO cable,LC-Duplex connector, 60 km C53207-A322-B116-3Protection data interface FO 19, 1550 nm, mono-mode FO cable,LC-Duplex connector, 100 km C53207-A322-B117-3

Optical repeatersSerial repeater (2-channel), opt. 1300 nm, mono-mode FO cable,LC-Duplex connector, 24 km 7XV5461-0BG00Serial repeater (2-channel), opt. 1300 nm, mono-mode FO cable,LC-Duplex connector, 60 km 7XV5461-0BH00Serial repeater (2-channel), opt. 1550 nm, mono-mode FO cable,LC-Duplex connector, 100 km 7XV5461-0BJ00

Page 36: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/38

Connection diagram

Fig. 6/39Connection diagram

Fig. 6/40Serial interfaces

LSA

2532

-ag

pen

.ep

s

1) Starting from unit version ..../EE.

Page 37: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/39

Connection diagram

Fig. 6/41Connection diagram

Note: For serial interfaces see Fig. 6/40.

LSA

2532

-ag

pen

.ep

s

Page 38: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/40

Connection diagram

Fig. 6/42Connection diagram

1) Starting from unit version .../EE.

2) High-speed trip outputs in versions 7SA6*1*-*M, 7SA*1*-*N, 7SA*1*-*P.Time advantage of high-speed relays over fast relays: approx. 5 ms

3) Time advantage with fast relay approx. 3 ms.

4) Version with 3-pole tripping.

5) Version with 1/3-pole tripping.

Note: For serial interfaces see Fig. 6/40.

LSA

2545

-ag

pen

.ep

s

Page 39: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/41

Fig. 6/43Connection diagram

1) Version with 3-pole tripping.

2) Each pair of contacts is mechanically interlocked to prevent simultaneous closure.

3) Version with 1/3-pole tripping.

Note: For serial interfaces see Fig. 6/40.

LSA

2545

-ag

pen

.ep

s

Connection diagram

Page 40: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/42

Connection diagram

Fig. 6/44Connection diagram

1) 7SA613 is only available in a2/3 x 19" flush-mountinghousing.

2) Starting from unit version.../EE

3) Time advantage with fastrelay approx. 3 ms.

4) High-speed trip outputs inversions 7SA6*2*-*M,7SA6*2*-*P, 7SA6*2*-*R.Time advantage of high-speedrelays over fast relays:approx. 5 ms

5) Version with 3-pole tripping.

6) Version with 1/3-pole tripping.

Note: For serial interfaces see Fig. 6/40.

LSA2546-agpen.eps

Page 41: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/43

Connection diagram

Fig. 6/45 Connection diagram

1) Starting from unit version.../EE.

2) High-speed trip outputs inversions 7SA6*2*-*N,7SA6*2*-*Q, 7SA6*2*-*S.

3) Time advantage with fastrelay approx. 3 ms.

4) Version with 3-pole tripping.

5) Version with 1/3-poletripping.Time advantage of high-speed relays over fast relays:approx. 5 ms.

Note: For serial interfacessee Fig. 6/40.

LSA2546-agpen.eps

Page 42: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/44

Connection diagram

Fig. 6/46 Connection diagram

1) Version with 3-pole tripping.

2) Each pair of contacts ismechanically interlockedto prevent simultaneous closure.

3) Version with 1/3-pole tripping.

Note: For serial interfaces see Fig. 6/40.

LSA2546-agpen.eps

Page 43: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/45

Dimension drawings in mm / inch

Front view

Fig. 17/251/3 x 19” surface-mounting housing,terminals at top and bottom

Side view

Fig. 17/24Housing for panel flush mounting/cubicle mounting (1/3 x 19")

Dimension drawings for SIPROTEC 41/3 x 19" housing (7XP20)

Rear view7SA610, 7SD61, 7SJ64

Rear view7SJ61, 7SJ62, 7UT612,7UM611

Panel cutout

Side view

Page 44: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/46

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 41/2 x 19" flush-mounting housings (7XP20)

Side view 1 Side view 2 Panel cutout

Rear view 17SA61/63, 7UM621, 7UM623,7SJ64

Rear view 27SJ63, 7UM612, 6MD63

Rear view 37SA522, 7SD52/53

Fig. 17/261/2 x 19" flush-mounting housing

Rear view 47UT613

Page 45: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/47

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 42/3 x 19" flush-mounting housings (7XP20)

Side view

Fig. 17/272/3 x 19" flush-mounting housing for 7SA613

Rear view Panel cutout

Page 46: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/48

Dimension drawings in mm / inch

Dimension drawings for SIPROTEC 41/1 x 19" flush-mounting housings (7XP20)

Side view 1 Side view 2

Panel cutout Rear view 17SA6, 7UM622, 7SJ64, 7UT633, 7UT635

Rear view 37SA522, 7SD52/53

Rear view 27SJ63, 6MD63

Fig. 17/28in 1/1 x 19" flush-mounting housing

* Terminals M and L additionally for 7UT635 and 7SJ647 only** Terminals H and G not for 7SJ645 and 7SJ647

Page 47: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/49

Dimension drawings in mm / inch

Front view1/1 x 19" surface-mounting housing 7XP20(without sloped FO case)

Front view1/2 x 19" surface-mounting,terminals at top and bottomhousing 7XP20

Side view

Dimension drawings for SIPROTEC 41/2 and 1/1 x 19" surface-mounting housings(7XP20)

Fig. 17/291/2 and 1/1 x 19" surface-mounting housing

Page 48: Distance Protection 7SA6

Siemens SIP · 2008

6 Distance Protection / 7SA6

6

6/50

Dimension drawings in mm / inch

Fig. 17/30Housing with detached or nooperator panel

Dimension drawings for SIPROTEC 41/2 and 1/1 x 19" housingswith detached operator panel

Detached operator panel (side view) Rear view Panel cutout