51

Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Embed Size (px)

Citation preview

Page 1: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Dissolved Gas Analysis and its interpretation

techniques for Power Transformers

Adam Junid, Simin Li, Lingfeng Ni

October 21, 2008

Abstract

This report is an investigation on Dissolved Gas Analysis and its interpre-

tation techniques for power transformers. Aspects covered in this report

include sampling method guidelines, interpretation techniques and stan-

dards, results-based guidelines and recommendations. A case study is

used to demonstrate interpretation.

1

Page 2: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Acknowledgements:

We thank:

� Dr Toan Phung for his help and explanations on ELEC9712 (High VoltageSystem) topics

� Zulkarnain Muhamad and Ahmad Zarir Makhtar from Petronas Gas Berhad(CUF-Kerteh) for sharing practical DGA data and photos with us

� Yee Yen Fu and Nor Azhar Saad from Asean Bintulu Fertilizer for sharingDGA reports with us

2

Page 3: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Acronyms and Abbreviations

ANSI

American National Standards Institute, www.ansi.org

AS

Australian Standard, www.standards.org.au

ASTM

American Society for Testing and Materials

BS

British Standards

H2

Hydrogen

C2H2

Acetylene

C2H4

Ethylene

CH4

Methane

C2H6

Ethane

CM

Condition Monitoring

DG

Dissolved Gas

DGA

Dissolved Gas Analysis

3

Page 4: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

HPLC

High Performance Liquid Chromatography [Duval et al, 1977]

LTC

Load Tap Changer

OLTC

On-Load Tap Changer

PD

Partial Discharge

ppm

Parts per million

TCG

Total Combustible Gas

TDCG

Total Dissolved Combustible Gas

4

Page 5: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Glossary

Condition Monitoring

The monitoring a parameter of condition in machinery, such that a signi�cantchange is indicative of a developing failure. It is a component of predictivemaintenance [Wikipedia, 2008b]

Dissolved Gas Analysis

A method of measuring dissolved gases in transformer oil in order to:

1. Deduce the operating condition of the transformer

2. Estimate a transformer's future safe operating range

3. Estimate probability of transformer failure

Fault Gases

Hydrogen, Methane, Ethane, Ethylene, Acetylene, Carbon Monoxide, CarbonDioxide; which are used in DGA to diagnose transformer faults. The degreeof hydrogen unsaturation of the molecule correlates to the amount of energyreleased by the fault [Duval, 1989]

Fuller's Earth

A nonplastic clay or claylike earthy material used to purify mineral oil [Wikipedia, 2008d]

Furan

A colorless, �ammable, highly volatile liquid with a boiling point of about 31.4oC; produced by thermal decomposition of cellulose [Wikipedia, 2008g]

Hot Metal Gases

Ethylene(C2H4), Ethane (C2H6), Methane (CH4); produced when transformeroil contacts hot metal [Jakob et al, 2003]

On-Load Tap Changer

A Tap Changer that can be adjusted either manually or automatically while thetransformer is supplying power to loads

Pyrolysis

Thermal Decomposition [Wikipedia, 2008f]

5

Page 6: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

(Beta) Scission

The initial step in the chemistry of thermal cracking of hydrocarbons and theformation of free radicals [Wikipedia, 2008i]

Tap Changer

A mechanism for selecting a desired number of transformer windings to be used

X-Wax

Solid particles of carbon and other hydrocarbon products produced by trans-former heat, partial discharge or arcing. Excessive X-Wax buildup along paperinsulation increases its dielectric dissipation factor and may result in excessiveheating and increased risk of fault occurence [IEC 60599, 2007, 4.1, 5.8].

6

Page 7: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Contents

1 Introduction 121.1 Concepts . . . . . . . . . . . . . . . . . . . . . . 12

1.2 Applications . . . . . . . . . . . . . . . . . . . . 16

1.3 History . . . . . . . . . . . . . . . . . . . . . . . 17

2 Sampling 182.1 Guidelines . . . . . . . . . . . . . . . . . . . . . 18

2.2 O�ine sampling . . . . . . . . . . . . . . . . . 18

2.3 Online sampling . . . . . . . . . . . . . . . . . 19

2.3.1 Manual sampling while the transformeris on . . . . . . . . . . . . . . . . . . . . 19

2.3.2 Continuous automated online sampling 19

2.4 Sampling periodicity . . . . . . . . . . . . . . . 19

2.5 DGA inaccuracy due to poor sampling tech-nique . . . . . . . . . . . . . . . . . . . . . . . . 19

3 Gas extraction and measurement 213.1 Extraction methods . . . . . . . . . . . . . . . 21

3.2 Measurement equipment calibration . . . . . 21

3.3 DGA report guidelines . . . . . . . . . . . . . 21

4 Interpretation techniques 234.1 Guidelines . . . . . . . . . . . . . . . . . . . . . 23

4.1.1 Roger's Ratio method . . . . . . . . . 24

4.1.2 IEC 60599 Ratios method . . . . . . . 25

4.1.3 IEEE (�Key Gas�) and DornenburgRatios . . . . . . . . . . . . . . . . . . . 26

4.1.4 Duval Triangle Method . . . . . . . . . 28

4.1.5 Single ratios . . . . . . . . . . . . . . . 30

4.2 Relative diagnostic accuracies of DGA inter-pretation techniques . . . . . . . . . . . . . . . 30

4.3 DGA inaccuracies due to low DG concentra-tions and lab equipment error margins . . . . 31

4.4 Application to OLTCs . . . . . . . . . . . . . . 33

7

Page 8: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

4.5 Predicting fault locations within the trans-former based on DGA results . . . . . . . . . 34

4.6 Headspace Fault Gas . . . . . . . . . . . . . . 34

5 Case Study 355.1 Pre-trip DG . . . . . . . . . . . . . . . . . . . 35

5.2 Post-trip DG . . . . . . . . . . . . . . . . . . . 35

5.3 Duval Triangle method applied . . . . . . . . 36

5.4 Comparison with Youngblood (Cinergy) ratios 37

6 Future developments in DGA 396.1 Online continuous monitoring . . . . . . . . . 39

6.2 New analysis methods . . . . . . . . . . . . . . 40

6.3 New DGA interpretation techniques for biode-gradeable oil . . . . . . . . . . . . . . . . . . . . 40

7 Conclusion 42

8

Page 9: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

List of Figures

1. Figure 1: A chemcal bond diagram showing how (naphtenic) mineral oil,under heat or arcing, breaks down to form hydrocarbon gases

2. Figure [IEC 60599, 2007]: Scission energies required to produce particularcarbon-carbon bonds in fault gases

3. Figure 3: Table of DGA Fault Gases, in order of energy required to pro-duce them

4. Figure 4: Relative gas production with respect to oil temperature

5. Figure 5: Relative gas solubility with respect to temperature

6. Figure 6: Tables of dissolved Fault Gas ratios which indicate pyrolysis dueto overheating, partial discharge and arcing

7. Figure 7: Transformer oil sampling setup at drain point

8. Figure 8: Typical DGA sampling periodicity by utilities

9. Figure 10: Table of key gases used for particular DGA interpretations

10. Figure 9: Sampling syringe and 3-way valve set

11. Figure 11: Diagnostics using the Roger's Ratio approach

12. Figure 12: A �owchart approach to Roger's Ratio diagnostics

13. Figure 13: IEC 60599 Dissolved Gas Ratio Diagnostics

14. Figure 14: Simpli�ed diagnostics table for IEC 60599 interpretation

15. Figure 15: IEEE DGA diagnostic guidelines

16. Figure 16: IEEE de�nitions for transformer condition based on TDCG

17. Figure 17: IEEE recommendations for transformer operation and mainte-nance action, based on TDCG

18. Figure 18: The Duval Triangle

19. Figure 19: Comparison table of DGA interpretation technique accuracy

20. Figure 20: Plot showing DG reading errors increase as DG concentrationsget lower for factory (�) and routine (-) testing

21. Figure 21: Table showing variations in laboratory reading errors for mediumand low DG concentrations

22. Figure 22: DG concentration limits for transformers and separate OLTCtanks requiring attention

9

Page 10: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

23. Figure 23: Cinergy Monthly Watch Criteria for DG in LTCs

24. Figure 24: Youngblood (Cinergy) 90th percentile Fault Gas Ratios

25. Figure 31: Graphical representation of IEC 60599 DGA ratios

26. Figure 25: 11kV pre-trip DG concentrations

27. Figure 26: 11kV post-trip DG concentrations

28. Figure 27:11kV DG concentration percentages

29. Figure 29: CUF-K 11kV transformer incident ratios (2008) compared toYoungblood (Cinergy) 90th percentile Fault Gas Ratios

30. Figure 28: Duval Triangle applied to case study

31. Figure 30: Proposed graphical interpretation of IEC 60599 C2H4C2H6

ratioapplied to biodegradeable oil

32. Figure 32: IEC 60599 DGA interpretation technique �owchart

10

Page 11: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Standards and Recommended Practice

1. ANSI C57.104-1978: Guide for the detection and determination of gener-ated gases in oil-immersed transformers and their relation to the service-ability of the equipment

2. IEEE Std C57.104-1991: IEEE Guide for the Interpretation of Gases Gen-erated in Oil-Immersed Transformers

3. IEC 60567, 2006, Oil-�lled electrical equipment � Sampling of gases andof oil for analysis of free and dissolved gases � Guidance

4. IEC 60599-1999: The Interpretation of Gases in Transformer and OtherOil-�lled Electrical Equipment in Service

11

Page 12: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

1 Introduction

Dissolved Gas Analysis (DGA) is a method of diagnosing faults1 in electricalequipment having oil as a conductor insulator [Wikipedia, 2008a]. It may also bea good indicator of the likelihood [IEC 60599, 2007, 8.1.1] of transformer failure[Duval, 1989, Figures 8 and 9]. DGA interpretation techniques have become sosensitive and accurate that it has now become standard practice in transformeracceptance [Waukesha Electric, 2004], maintenance programs involving onlineCM [Wong, 2000, Osztermayer at al, 2003], and post-mortem equipment failurestudies [Schroeder, 2000].

This report focuses speci�cally on DGA2 and its interpretation techniques foroil-insulated power transformers, including oil at tap changers3. It also presentssampling method guidelines, gas extraction practice, maintenance recommen-dations4 based on interpretation techniques, and case studies.

1.1 Concepts

Transformer insulating oil, whether para�nic, naphthenic or aromatic containdissolved gases.

1It is also used in transformer factory acceptance tests, both before, during and after aheat run [IEC 60567, 2006, "Introduction"]

2Analysis of Furans, although not part of this report because they are considered �uids[Wikipedia, 2008g] at standard temperature and pressure, are useful in predicting buildup ofX-Wax at paper insulation that could possibly lead a future fault [IEC 60599, 2007, 5.8]. Oiladditives such as oxidation inhibitors, and the e�ect of copper sludge has on oil conductivityand tan δ are also not covered here.

3Winding and tap-changer oil should ideally be contained separately to ease troubleshoot-ing and fault location [Kramer, 2008, Reinhausen Grp, 2006].

4See Figure 17

12

Page 13: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 1: A chemcal bond diagram showing how (naphtenic) mineral oil,under heat or arcing, breaks down to form hydrocarbon gases (Taken from[Jakob, 2008, Slide 12])

The decomposition5 (Figure 1) of transformer oil6 under heat or arcing result inmore Fault Gases7 produced8 and dissolved9 in the oil than were there originally[Blackburn, 2008]10. Both the amount and types of Fault Gases produced are

5Also referred to as �thermal breakdown� [Wikipedia, 2008a, "Faults"]6There may be accompanying paper insulation breakdown (also referred to as cellulose

breakdown, or pyrolysis [Wikipedia, 2008f]), which result in Furanic compounds produced inthe oil, which can be interpreted using IEC 61198 to estimate the extent cellulose involvmentin the fault [IEC 60599, 2007, 4.2].

7Often referred to as DGA �Fault Gases� (see Figure 3)8Gas volume production is nearly quadratic with voltage, and linear with arc duration9Until saturation limits are reached [Blackburn, 2008, Slide 5]

10X-wax may also be produced [IEC 60599, 2007, 4.1: Decomposition of Oil]

13

Page 14: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Bond type Scission energy required

C −H 338 kJ/moleC − C 607 kJ/moleC = C 720 kJ/mole

Figure 2: Scission energies required to produce particular carbon-carbon bondsin fault gases [IEC 60599, 2007, 4.1].

related to the energy produced by the fault (Figure 2).The quantifying and historical trending of these Fault Gas ratios with respectto industry-wide interpretation guidelines are the basis of DGA interpretation[Jakob et al, 2003].

�Key� Fault Gas Indication

Hydrogen H2 Partial Discharge, Heating, ArcingEthyleneC2H4, Ethane C2H6, Methane CH4 Hot metal

Acetylene C2H2 ArcingCarbon Monoxide CO, Carbon Dioxide CO2 Cellulose insulation degradation

Figure 3: Table of DGA Fault Gases, in order of energy required to producethem (Taken from [Jakob et al, 2003, Table 2])

By having baseline records and trending of DG content, transformer operatorsand owners would have a good indication how much their transformer oil hasdeteriorated, either due to age, overheating (see Figure 4), arcing or externalwater ingress.

14

Page 15: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 4: Relative gas production with respect to oil temperature (Taken from[Blackburn, 2008, Slide 13])

DGA is typically done by:

1. Taking an oil sample,

2. Quantifying gas content by using techniques such as liquid chromatogra-phy [Wikipedia, 2008e], and

3. Correlating the results11 with known standards and Fault Gas12 ratio13

guidelines to gauge the transformer's internal condition

11This may include headspace Fault Gas results (see Section 4.6), should the suspect faultbe large enough to produce large enough Fault Gas volume

12The degree of hydrogen unsaturation of the molecule correlates to the amount of energyreleased by the fault [Duval, 1989]

13Gas ratios are used because Fault Gas solubility with respect to oil temperature relativeto one another appears reasonably constant (see Figure 5). Thus DGA samples may be takeneven when the transformer has cooled and their relative ratios would remain similar.

15

Page 16: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 5: Relative gas solubility with respect to temperature (Taken from[Blackburn, 2008, Slide 6])

1.2 Applications

DGA concepts are applied to assess oil which insulates conductors, such astransformer cores and windings, and oil-insulated cables. By using DGA tech-niques, information about the equipment from which the oil sample was takenfrom can be deduced, e.g. has there been overheating (see Figure 414), has therebeen internal arcing within the oil (see Figure 6), has there been atmosphericingress. Such DGA interpretations would then be applied to estimate:

1. The transformer's most recent operating condition,

2. How much derating (or uprating) it should (or could) be safely operatedat in its remaining condition, and

3. How soon the next transformer oil change, �ltering, Fuller's Earth treat-ment or inspection should be.

14There are also other sources of gas production, such as from newly facbricated steel andvia reaction of steel with water in the oil [IEC 60599, 2007, 4.3]

16

Page 17: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Pyrolysis Ratios

Ethylene C2H4 60%Ethane C2H6 20%Methane CH4 20%

PD Ratios

Hydrogen H2 85%Methane CH4 5%Ethane C2H6 5%

Arcing Ratios

Acetylene C2H2 30%Hydrogen H2 60%Methane CH4 5%Ethylene C2H4 5%

Figure 6: Tables of dissolved Fault Gas ratios which indicate pyrolysis due tooverheating, partial discharge and arcing (Taken from [Blackburn, 2008, Slide16])

1.3 History

DGA has been used for transformer routine monitoring since the late 1960s[Duval, 1989]. In 2003, it was estimated that about a million DGA tests weredone annually at laboratories worldwide [Duval et al, 2003]15.

15This averages to more than 10 DGAs per minute, or > 1 DGA every 6 seconds

17

Page 18: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

2 Sampling

2.1 Guidelines

Transformer operators may obtain gas samples from the gas relays (or Buchholzrelays), but for more accurate and early diagnosis [Wikipedia, 2008a, "Usage"],DGA by careful oil sampling, gas extraction16 [Duval et al, 2003] and chro-matography is recommended. In all cases, sampling should not endanger theoperation of the equipment [IEC 60567, 2006, 4.1].

2.2 O�ine sampling

ASTM D3613 requires that transformer oil sampling be taken via a syringe[POA, 2007] and stopcock system [Duval, 1989] from a mineral-oil insulatedtransformer's drain point to ensure no oil contact with air.

Figure 7: Transformer oil sampling setup at drain point (Taken from[Alamo Transformer, 2008])

To minimise air ingress, it is important that the syringe not be pulled forcefully,i.e. the transformer oil's natural gravity �ow should be allowed to work the oilinto the syringe [NTT, 2001a].

16Internationally recognized standards for gas extraction from oil samples are IEC 60567(see Section 3.1) and ASTM D3612.

18

Page 19: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

2.3 Online sampling

2.3.1 Manual sampling while the transformer is on

Some oil-sampling contractors can obtain oil-samples from live transformers forDGA [IET, 2008], subject to transformer owner clearance of such practice.

2.3.2 Continuous automated online sampling

There are also manufacturers o�ering automated online sampling equipment forundissolved gases [Kelman, 2005-8]. However the gases such equipment detectfrom the headspace or Buchholz (gas) relay and are not dissolved, limiting therapidity of this CM diagnostic.

Continuous automated online sampling of DG o�ers cutting edge DGA CMaccuracy and diagnostics. This is addressed in Section 6.1.

2.4 Sampling periodicity

For new, overhauled, repaired, or newly oil-�ltered transformers, a recommendedmonthly sampling periodicity may be increased or decreased, depending onwhether DGA results show that gas content is stabilizing [Wikipedia, 2008a,"Monitoring"]. Once the DGA concentrations have acceptably stabilized, thetransformer operator may commence monitoring every one or two years. Someexamples of DGA periodicity practiced are as follows:

Operator Periodicity

NGC UK (1998) Annually [Esp et al, 1998]Petronas CUF-K (2008) Annually [Makhtar et al, 2008]Petronas MCOT (2004) Pending oil dielectric test per 2 years [Makhtar et al, 2008]

Shell (2000) Pending dielectric test per 4 yrs; nonsealed units [Shell, 2000]Syprotec (1995) Annually [Gibeault et al, 1995]Transgrid (2008) Annually [Transgrid, 2007]

Figure 8: Typical DGA sampling periodicity by utilities

2.5 DGA inaccuracy due to poor sampling technique

DGA readings may be skewed by poor sampling technique, which the samplingoperator must guard against, e.g.:

1. Contaminated oil sample containers [IET, 2008]

19

Page 20: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

2. Not allowing some oil to �ow to clean the drain valve piping before takinga sample [NTT, 2001a]17

3. Exposing the oil to sunlight [IEC 60567, 2006, 4.1]

4. Bubble in the syringe sample, in which case resampling is recommended[IEC 60567, 2006, 4.2.2]

5. Pre-existing oxygen in the sample [IEC 60599, 2007, 4.3]

Figure 9: Sampling syringe and 3-way valve set (Taken from [NTT, 2008b])

17Oil at the bottom of the tank may also be more susceptible to contaminants & di�erentDG levels [Ward, 2003]

20

Page 21: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

3 Gas extraction and measurement

3.1 Extraction methods

Gas extraction methods speci�ed in IEC 60567 include [IEC 60567, 2006, "Scope"]:

� Extraction by vacuum

� Extraction by displacement of the dissolved gases by bubbling a carriergas through the oil sample (stripping)

� Extraction by partitioning of gases between the oil sample and a smallvolume of the carrier gas at the head space

3.2 Measurement equipment calibration

Chromatography equipment accuracy is veri�ed and corrected by measuringgas content from calibrated gassed oil samples, known as gas-in-oil samples.Trained and competent personnel are required to maintain the calibration ofDGA extraction and chromatography equipment, which require re-calibration[IEC 60567, 2006, 8.6] prior to each sample and linearity checks [IEC 60567, 2006,9.1] every 6 months or following changes in apparatus or operating conditions.Given that di�erent labs have been known to report di�erent DGA quantities

for the sample oil sample, each DGA lab report should include the accuracymargins of the lab equipment used [Duval et al, 2005].

3.3 DGA report guidelines

IEC 60559 recommends that DGA interpretation reports should contain thefollowing [IEC 60599, 2007, 10.]:

1. Method of DGA

2. DG lab equipment sensitivity thresholds and accuracy

3. Transformer date of commissioning, rated voltage and power, sealed orvented, OLTC type, make and model

4. Oil volume, sampling date and location

5. Special incidents just before the sampling, e.g. tripping, alarm, repair,degassing, outage

6. Previous DGA results on the transformer

7. Indication of typical DG values for the equipment, inlcuding �healthy� and�fault� values, and identi�cation of the previous fault types

8. Recommended action, e.g.:

21

Page 22: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

(a) Revised oil sampling frequency

(b) Furanic compound analysis if CO2CO < 3

(c) Other tests, inspections or maintenance

22

Page 23: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

4 Interpretation techniques

4.1 Guidelines

DGA interpretation techniques take into account the amounts of �Key Gases�[Blackburn, 2008, "Analysis"] (see Figure 10) found in oil samples (in ppm) andtheir relative ratios to each other to arrive at conclusions about the transformercondition. These techniques include empirical approaches such as Roger's Ra-tios (IEEE - 1978)18, IEC 60599 Ratios [Blackburn, 2008], IEEE 57.104 Ratios[Jakob, 2008]19, and graphical methods such as the Duval Triangle.

Key Fault Gases Interpretation applied

C2H4, C2H6, CH4, H2 Thermal Fault: Overheated oilCO2, CO Thermal Fault: Overheated cellulose

H2, CH4, C2H6, C2H4 Electrical Fault, PD in OilH2, C2H2, C2H2, CH4, C2H6 Arcing In Oil

Figure 10: Table of key gases used for particular DGA interpretations (Takenfrom [Blackburn, 2008, "Analysis"])

The following gas ratio methods work best with diaphragm or hermeticallysealed transformers. Kan et al has also noted its applicability to nitrogen sealedtransformers with N2 replenishment, because release of fault gases are infrequentenough to treat the gas mixtures as being in equilibrium within the transformer[Kan et al, 1995, "CO2/CO value for transformers with gas space above oil",]20.It would be less accurate21 for transformers with open type conservators because:

1. The di�usion rate of H2 would be faster than the heavier Fault Gases

2. O2entering the transformer would a�ect the insulation paper's character-istics in terms of CO and CO2 retention [Kan et al, 1995, "Cases whereCO/CO2 method does not apply",].

To obtain data related to the transformer's most recent fault, the most recentDGA results should have gas concentrations from previous DGA results sub-tracted from it [IEC 60599, 2007, 6.1].

18Roger's Ratios originated from the Doernenburg method [Serveron, 2007, p8]19Also known as the �Key Gas Method� [Serveron, 2007, Table 3, p4]20Although it has been argued that the headspace gases are a�ected by headspace purging

[Woolley et al, 2994]21IEC60599 mentions there is no agreement yet on adjustment techniques to account for

gases esacping to the atmophere for ventilated transformers [IEC 60599, 2007, 6.1]

23

Page 24: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

4.1.1 Roger's Ratio method

Based on ratios of particular fault gases, a diagnostics summary using Roger'sRatios [Rogers, 1975]22 is as follows23:

C2H6CH4

C2H4C2H6

C2H2C2H4

Diagnosis

R < 10 R < 1 R < 0 Normal deteriorationR < 1 R < 1 R < 0.5 PD activityR < 1 R < 1 R < 0.5 Heating to 150 oCR > 1 R < 1 R < 0.5 Heating 150 - 300 oCR < 1 1 < R < 3 R < 0.5 Winding circulating current and overheatingR < 1 R > 3 R < 0.5 Overheated contactsR < 1 R < 1 0.5 < R < 3 Transient arcingR < 1 R > 1 R > 0.5 Transient arcing at power frequencyR < 1 R > 3 R > 3.0 Continuous sparkingR < 1 R < 1 R > 0.5 PD and tracking

Figure 11: Diagnostics using the Roger's Ratio approach (Taken from[Blackburn, 2008, Slide 20])

A manually faster approach to Roger's Ratio diagnostics may be done using thefollowing Roger's Ratio �owchart [Jakob, 2008, Slide 26]:

22Also found in Table 7 of ANSI/IEEE C57.104-197823For DGA diagnosis involving single ratios of CO2

CO, see Section 4.1.5.

24

Page 25: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 12: A �owchart approach to Roger's Ratio diagnostics (Taken from[Jakob, 2008, Slide 26])

4.1.2 IEC 60599 Ratios method

IEC 60599 has a similar diagnostic approach, using dissolved gas ratios [IEC 60599, 2007,5.3 (Table 2), 9, Figure 1]24:

The IEC 60599 ratios in Figure 13 above should only apply if one of the gasconcentrations exceeds typical values [IEC 60599, 2007, 5.3, Table 2 and 6.1c].The ratios may also be reproduced in a twin square, graphical format (Figure31, Appendix). In some cases, no diagnosis may be forthcoming from the above

table, in which case a simpli�ed diagnostics table may be applied:

24IEC 60599 [Duval et al, 2001] also speci�es that: (a) Faults are considered active if DGrates continue to rise at 10% per month for hermetically sealed transformers [IEC 60599, 2007,8.4]; and (b) Higher DG rates of increase such as 50% per week are considered very serious.

25

Page 26: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 13: IEC 60599 Dissolved Gas Ratio Diagnostics (Taken from[Miranda et al, 2005, Table II])

Case C2H2C2H4

CH4H2

C2H4C2H6

Partial Discharge < 0.2Discharge (Arcing) > 0.2Thermal fault < 0.2

Figure 14: Simpli�ed diagnostics table for IEC 60599 interpretation[IEC 60599, 2007, Table 3].

For TDCG baseline acceptance criteria, IEC 60599 allows transformer opera-tors to set their own thresholds, based on forensic evidence [IEC 60599, 2007,8.2]. IEC 60599 also presents an overall �owchart for its DGA interpretation,reproduced in Figure 32, Appendix.

4.1.3 IEEE (�Key Gas�) and Dornenburg Ratios

IEEE 57.104 also has a set of ratios for DG and headspace gas25 diagnosticsthat borrows from the Dornenburg method26:

25Fault Gases from may help asses the size of a recent large fault [IEC 60567, 2006, "In-troduction"]. Headspace Fault Gas analysis is addressed more completely in IEC 60599[IEC 60599, 2007, 7.]which uses Ostwald coe�cients to convert headspace Fault Gas con-centrations to a DG equivalent.

26Found in Tables 5 and 6 of ANSI/IEEE 57.104-1978

26

Page 27: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 15: IEEE DGA diagnostic guidelines (Taken from [Jakob, 2008, Slide29])

In addition, based on TDCG, IEEE 57.104 includes condition de�nitions (Figure16) and maintenance guidelines (Figure 17).

Figure 16: IEEE de�nitions for transformer condition based on TDCG (Takenfrom[Jakob, 2008, Slide 33])

DG concentration ratios below the above threshold values do not necessarilymean no fault is present, such results merely mean that the concentration valuesare not high enough to be able to estimate probabilities of an incipient fault[IEC 60599, 2007, 8.2.1, 8.3].

27

Page 28: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 17: IEEE recommendations for transformer operation and maintenanceaction, based on TDCG (Taken from [Jakob, 2008, Slide 34])

For new transformer oil TDCG baseline acceptance criteria, both IEC andIEEE guidelines allow the transformer operators to set their own thresholds[Jakob, 2008, Slide 31].

4.1.4 Duval Triangle Method27

A popular [Bandhopadhyay, 2006, Field et al, 2002] method that has been notedto be more accurate [Serveron, 2007, Table 7, p10]28 than the above three,the Duval triangle29 provides DGA fault diagnosis simply based on relativepercentages of CH4, C2H4 and C2H2, where the fault codes are [Delta-X, 2008]:

� PD : Partial discharge

27Found in Appendix B of IEC 60599-1991 [Delta-X, 2008]28Caveats to this accuracy [Delta-X, 2008] : (a) Because extremely low levels are related to

decreases in detection accuracy, detected gases involved in the triangle should be reasonablyabove the detection limit; (b) Existing gases that were detected in the original oil sample(during baseline sampling or before a suspect fault) should be subtracted out from the samplepercentages to be substituted into the triangle.

29Developed by Michael Duval of Hydro Quebec [Bandhopadhyay, 2006]

28

Page 29: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

� T1 : Low-range thermal fault (below 300 oC)

� T2 : Medium-range thermal fault (300-700 oC)

� T3 : High-range thermal fault (above 700 oC)

� D1 : Low-energy electrical discharge

� D2 : High-energy electrical discharge

� DT : Indeterminate - thermal fault or electrical discharge

Figure 18: The Duval Triangle (Taken from [Blackburn, 2008, Slide 22])

29

Page 30: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

4.1.5 Single ratios

CO2CO

30, O2N2

31 and C2H2H2

32 ratios may indicate paper insulation involvement infaults, excessive heating or contamination by OLTC oil respectively [Serveron, 2007,p11]. However, the diagnosis accuracy of CO2

CO and O2N2

have been disputed.

The CO2CO ratio is particularly nebulous33 because of its temperature depen-

dency and CO2's higher absorption rate into insulation paper relative to COat higher temperatures [Kan et al, 1994, 5. Conclusion]. For example, one nor-mal CO2

CO range has been de�ned as > 7, with CO2CO < 3 [IEC 60599, 2007, 5.4:

CO2/CO ratio]indicating severe overheating of paper insulation [Jakob, 2008,Slide 28]. However, studies by Kan et al have proposed that incipient faults mayactually be occuring at CO2

CO ratios < 10 because CO2 gets absorbed into insulat-ing the paper [Kan et al, 1995] at higher temperatures, depriving DGA samplesof a representative CO2 concentration. In addition to the CO2

CO temperature de-

pendence skew, Kan et al also noted that a CO2CO ratio method: (a) cannot apply

accurately to new transformer oil for the �rst six months because of a lack ofchemical equilibrium, and (b) cannot apply accurately to naturally circulated oilbecause of the greater likelihood of localised hotspots [Kan et al, 1995, "Caseswhere CO2/CO method does not apply",].

When applying the O2N2

ratio, it must be noted that ransformers that have notbeen Nitrogen-purged may have signi�cant amount of Oxygen already inside[Woolley et al, 2994]. A O2

N2ratio of < 3 may indicates excessive oxygen con-

sumption within the transformer [IEC 60599, 2007, 5.5].

IEC 60599 also noted that transformers with breahing apparatus (i.e. non-hermetically sealed transformers) may have CO2 coming in from external airthat could falsify diagnostic results [IEC 60599, 2007, 5.4].

In short, DGA involving these single ratios of CO2CO and O2

N2must be supplemented

by one of the methods mentioned in Section 4.1.

4.2 Relative diagnostic accuracies of DGA interpretationtechniques

Case studies using the IEEE �Key Gases� approach have shown that [Serveron, 2007,p5]:

1. There can be high rates of incorrect diagnosis

30This ratio has been noted to vary depending on transformer model and its operationalmode [Failhauer et al, 2006]. Due to a lack of diagnostic consistency or distinguishable pat-

terns, the CO2CO

ratio was removed from a data mining technique by Esp et al [Esp et al, 1998].31Transformers that have not been Nitrogen-purged may have signi�cant amount of Oxygen

already inside [Woolley et al, 2994]32 C2H2

H2ratios higher than 2 or 3 in the main tank indicates oil contamination from the

OLTC tank [IEC 60599, 2007, 5.5]33It has also been shown that CO2 levels in headspace can �uctuate by up to 500ppm per

day [Ward et al, 2000], depending on transformer loading.

30

Page 31: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

2. Some gas combinations do not �t into the speci�ed range of values andthus a diagnosis of the fault type cannot be given

Studies of DGA technique relative accuracies have shown that the Duval Tri-angle method has relatively good consistency and accuracy when taking into ac-count cases that are �undiagnosable� by the other methods [Muhamad et al, 2007].

Method % No Diagnoses % Wrong Diagnoses

IEEE Key Gas Method 0 58IEEE Rogers Ratios 33 35Dornenburg Ratios 26 3

IEC Basic Gas Ratios 15 8IECDuval Triangle 0 4

Figure 19: Comparison table of DGA interpretation technique accuracy (Takenfrom [Duval et al, 2005, Table 3])

Although the Dornenburg method appears more accurate than the Rogers,Thang et al noted that [Thang et al, 2000]:

� Although Dornenburg's method appears relatively more accurate, it is alsomore susceptible to a non-interpretation result.

� Although the Duval Triangle o�ers relative greater accuracy, it forces theuser into a transformer fault diagnosis because it has no area to accountfor gase ratios due to operational aging. Thus the Duval triangle shouldonly be applied after the gases have been scrutinized for normalcy.

4.3 DGA inaccuracies due to low DG concentrations andlab equipment error margins

IEC 60567 [IEC 60567, 2006, Table 5], IEC 60599 [IEC 60599, 2007, 6.2] andstudies by Duval et al have noted that DG volume reading inaccuracies increaseat very low concentrations of DG [Duval et al, 2005]:

31

Page 32: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 20: Plot showing DG reading errors increase as DG concentrations getlower for factory (�) and routine (-) testing (Taken from [Duval et al, 2005,Figure 1])

However, correction factors may be applied to minimise this [Duval et al, 2005].Duval et al also noted that DG reading errors for controlled medium and low DGconcentration oil samples varied signi�cantly from laboratory to laboratory34:

At medium gas concentrations At low gas concentrations

Best lab ±3% ±22%Average ±15% ±30%Worst lab ±65% ±64%

Figure 21: Table showing variations in laboratory reading errors for mediumand low DG concentrations (Taken from [Duval et al, 2005, Table 2])

34IEC 60567 [IEC 60567, 2006, 9.3]mentions methods of how to minimize this, includingthe storage of oil samples in fridges

32

Page 33: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

To reduce the likelihoods of false readings resulting in incorrect DGA diag-nosis35, both IEC 60567 [IEC 60567, 2006, 10] and Duval et al recommendthat DGA laboratories publish their lab's accuracy �gures on all test reports[Duval et al, 2005].

4.4 Application to OLTCs

The DG production pattern in an OLTC oil tank is di�erent from that of themain tank. For example, more Acetylene (C2H2

H2) is produced36 (see Section

4.1.5). DG concentration limits for �untight OLTCs� that may require attentionhave been presented by Blackburn [Blackburn, 2008, Slide 14]:

Fault Gas Transformer OLTC

Hydrogen (H2) 60 - 150 75 - 150Carbon Monoxide (CO) 540 - 900 400 - 850Carbon Dioxide (CO2) 5100 - 13000 5300 - 12000

Methane (CH4) 40 - 110 35 - 130Ethane (C2H6) 50 - 90 50 - 70Ethylene (C2H4) 60 - 280 110 - 250Acetylene (C2H2) 3 - 50 80 - 270

Figure 22: DG concentration limits for transformers and separate OLTC tanksrequiring attention (Taken from [Blackburn, 2008, Slide 14])

Guidelines also exist from CM consultants (Figure ) as well as CM contractors,who provide model-speci�c [Jakob et al, 2008, Slides 21-22]DG concentrationlimits for OLTCs.

LTC type Hydrogen H2 Acetylene C2H2 Ethylene C2H4

Vented > 1500 ppm > 1000 ppm > 1000 ppmSealed > 5000 ppm > 9000 ppm > 12000 ppmVacuum > 10 ppm > 5 ppm > 100 ppm

Figure 23: Cinergy Monthly Watch Criteria for DG in LTCs (Taken from[Jakob et al, 2008, Slide 19])

35Incorrect DGA diagnosis would also result in unnecessary downtime and resources wastedto inspect a transformer [Duval et al, 2005]

36 C2H2H2

ratios higher than 2 or 3 in the main tank indicates oil contamination from the

OLTC tank [IEC 60599, 2007, 5.5]

33

Page 34: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Youngblood et al of Cinergy have also provided LTC DGA ratio limits basedon empirical data [Youngblood, 2003]:

Gas ratio LimitEthylene(C2H4)Acetylene(C2H2)

0.3378Ethylene(C2H4)

Acetylene(C2H2)+Hydrogen(H2)0.500

Ethylene(C2H4)+Ethane(C2H6)+Methane(CH4)Acetylene(C2H2)+Hydrogen(H2)

0.9157Ethane(C2H6)Methane(CH4)

0.2067Ethylene(C2H4)Ethane(C2H6)

4.83

Figure 24: 90th percentile Fault Gas Ratios (Taken from [Jakob et al, 2003])

4.5 Predicting fault locations within the transformer basedon DGA results

In general, once DGA DG concentration and ratio limits indicate an increas-ing faults within the transformer, operators will arrange for the transformershutdown and inspection. Often the inspection may take weeks because thefault may not be visually apparent upon detailed winding and core inspection[Makhtar et al, 2008]. Given that equivalent heat areas of transformer cores

and winding di�er, some work has been done by Zama et al on estimating thelikelihood of the fault lying in the windings or the core, based on C2H4

C2H6ratioss

[Zama et al, 2008, Part F].

4.6 Headspace Fault Gas

Analysis of headspace gas collected from transformer Buchholz or gas relaysfor analysis [Wikipedia, 2008c] are technically not part of DGA, since theyare not dissolved, and are a�ected by headspace purging [Woolley et al, 2994]and solubility equilibrium �uctutations that may only stabilise after 15 hours[Ward et al, 2000]. However, excess Fault Gases from this headspace may behelpful in assessing the size of a recent fault [IEC 60567, 2006, "Introduction"].Headspace Fault Gas analysis is partially addressed in Figure 15, and morecompletely in IEC 60599 [IEC 60599, 2007, 7.]which uses Ostwald coe�cientsto convert headspace Fault Gas concentrations to a DG equivalent.

34

Page 35: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

5 Case Study

A case study involving an 11kV transformer37 trip at in 2008 is referred [Makhtar et al, 2008].Pre and post trip DG results are presented, and an interpretation suggested viaapplication of the Duval Triangle method.

5.1 Pre-trip DG

DG concentrations from a sample taken on 28 March 2008 are as follows:

Figure 25: 11kV pre-trip DG concentrations (Taken from [Makhtar et al, 2008]).

5.2 Post-trip DG

DG concentrations from a sample taken on 8 July 2008 after a trip incident areas follows:

37Transformer is sealed but not Nitrogen packed, and has on o�-circuit LTC in the same oilcompartment as the transformer main winding [Makhtar et al, 2008].

35

Page 36: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 26: 11kV post-trip DG concentrations (Taken from[Makhtar et al, 2008]).

5.3 Duval Triangle method applied

Tabulating the above results,

Gas 4ppm %

Methane (CH4) 546-2=544 34.4Ethylene (C2H4) 430 27.1Acetylene (C2H2) 607 38.4

Figure 27: 11kV DG concentration percentages (Taken from[Makhtar et al, 2008]).

and plotting the intersects,

36

Page 37: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 28: Duval Triangle applied to case study (Taken from[Makhtar et al, 2008]).

we obtain a Duval Triangle that suggests a D2 Fault: High energy arcing withpower follow-through, and possible carbonization and metal fusion [IEC 60599, 2007,5.2].

5.4 Comparison with Youngblood (Cinergy) ratios

The post-incident DG concentration ratios are compared to failure probabilityratios given by Youngblood (Cinergy):

37

Page 38: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Gas ratio Limit Pre-incident Post-incident Pfailure

Ethylene(C2H4)Acetylene(C2H2)

0.3378 NILNIL 0.708 210%

Ethylene(C2H4)Acetylene(C2H2)+Hydrogen(H2)

0.500 0 0.878 176%Ethylene(C2H4)+Ethane(C2H6)+Methane(CH4)

Acetylene(C2H2)+Hydrogen(H2)0.9157 0.004 0.205 22.3%

Ethane(C2H6)Methane(CH4)

0.2067 0 0.051 24.7%Ethylene(C2H4)Ethane(C2H6)

4.83 0 15.36 318%

Figure 29: CUF-K 11kV transformer incident ratios (2008) comparedto Youngblood (Cinergy) 90th percentile Fault Gas Ratios (Taken from[Jakob et al, 2003] and [Makhtar et al, 2008])

38

Page 39: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

6 Future developments in DGA

Some future developments in DGA include [Blackburn, 2008, Slide 33]:

� Online continuous monitoring that is more reliable and a�ordable

� New analysis methods involving gases with C3 bonds

� New DGA interpretation techniques for biodegradeable oil

6.1 Online continuous monitoring

Although not yet widespread, online DGA monitoring systems have been inuse38 since 1980 [Yamada et al, 1981]. Advantages include [Lindgren, 2003, Side20]:

1. Theoretically more accurate diagnosis, including better resolution of ratesof DG, e.g. to discriminate between faults and contamination by OLTCoil

2. The ability to uprate individual transformers and run it closer to thermallimits

3. Since lab DGA often contains air, online monitoring will have much betterresolution of actual air leaks in the transformer

4. Possible capture of DG at higher temperature solubility limits, thus negat-ing the e�ects of DGA inaccuracy at low DG concentration levels (seeFigure 20)

5. Lower-cost online or portable dissolved hydrogen concentration monitorsbeing used to decide whether a complete DGA is necessary [Belanger et al, 1977]

Some disadvantages are that [Duval et al, 2003, "On-Line Monitoring Devices"]:

1. Many of the online DGA monitors mentioned in [Duval et al, 2003, TableVI] do not detect all Fault Gases, i.e. they detect mainly H2, C2H2, CHX ,CO , CO2 which �ag arcing faults well, but are less e�ective for detectinglow and medium overheating

2. Being mostly located outdoors, they may have have poorer maintenance,resulting in poorer accuracy relative to indoor DGA lab equipment

3. Detection responses for online DGA monitors utilising fuel cells are di�er-ent for each Fault Gas

4. Engineers are still challenged to produce online DGA monitoring devicesthat are accurate, reliable and economical

Online DGA systems should use one of the more accurate extraction [Duval et al, 2003]and diagnostic techniques mentioned in Section 4.1 [Serveron, 2007, p11-12].

38Duval in 2003 estimated that about 18000 online DGA monitors had been installed world-wide [Duval et al, 2003].

39

Page 40: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

6.2 New analysis methods

The DGA interpretation techniques mentioned in Section 4 utilize DG ratiosinvolving C1 and C2 bonds. However, IEC 60599 mentions that more preciseanalysis methods are possible if the DG ratios involving C3 bonds are scruti-nized as well [IEC 60599, 2007, 5.7]. This implies that methods such as theDuval Triangle (Section 4.1.4) could be modi�ed and re�ned to involve an anal-ogous, square shaped percentage-ratio-reference chart, given enough forensicDGA data [IEC 60599, 2007, 8.1.2] to verify the chart's demarcations and diag-nostic accuracy.

6.3 New DGA interpretation techniques for biodegrade-able oil

Studies have shown that biodegradeable oils tend to release about three timesmore ethane (C2H6) than mineral oil during thermal heating tests. This wouldresult in IEC 60599 DGA interpretations having to be modi�ed for biodegrade-able oils, in particular, the C2H4

C2H6ratio:

40

Page 41: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Figure 30: Proposed graphical interpretation of IEC 60599 C2H4C2H6

ratio appliedto biodegradeable oil (Taken from [IEC 60599, 2007, Annex B] and edited tore�ect ethane production data from [Muhamad et al, 2008, Fig. 8]).

41

Page 42: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

7 Conclusion

DGA methods have been used since the 1980s to gauge transformer conditionfor:

1. factory acceptance tests,

2. site acceptance tests (e.g. for new oil),

3. predictions of remaining time to next transformer maintenance, and

4. post-mortem fault analysis

DGA sampling involves careful preparation of oil samples to ASTM D3613.

The extraction of gas from oil requires calibrated lab equipment compliant toIEC 60567.

The actual DGA interpretation technique may rely on many di�erent methodsmentioned in IEC and IEEE standards; the Duval Triangle method being oneof the more consistent methods.

Some future developments in DGA include [Blackburn, 2008, Slide 33]:

� Online continuous monitoring that is more reliable and a�ordable

� New analysis methods involving gases with C3 bonds

� New DGA interpretation techniques for biodegradeable oil

42

Page 43: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

References

[Alamo Transformer, 2008] Alamo Transformer, 2008, "Dissolved Gas Test-ing", http://www.alamotransformer.com/DGA1.

htm, viewed 21 October 2008

[Bandhopadhyay, 2006] Bandyopadhyay, M.N. 2006, "Trnas-former Diagnostics in Practical Field",www.ece.cmu.edu/~electricityconference/

2006/Bandyopadhyaydoc%20Paper.pdf, viewed 13September 2008

[Belanger et al, 1977] Belanger, G. and Duval, M. 1977, �Monitor for hy-drogen dissolved in transformer oil�, IREQ

[Blackburn, 2008] Blackburn, T.R. 2008, ��Use of Dissolved Gas Anal-ysis to Monitor the Condition of oil-impregnated In-sulation�, Advanced Techniques for Condition Mon-

itoring coursepack, March 2008, Kuala Lumpur

[Delta-X, 2008] Delta-X Research, 2008, "The Duval Triangle DGADiagnostic Method", www.deltaxresearch.com/

triangle.htm, viewed 13 September 2008

[Esp et al, 1998] Esp, D.G. and Carillo, M. et al, 1998, �Data miningapplied to transformer oil analysis data, ConferenceRecord of the 1998 IEEE International Symposium

on Electrical Insulation, Arlington, Virginia, USA,June 7-10, 1998

[Duval et al, 1977] Duval, M. and Lamarre, C. 1977, �The characteriza-tion of electrical insulating oils by high-performanceliquid chromatography�, Hydro-Quebec Institute ofResearch

[Duval, 1989] Duval, M. 1989, �Dissolved Gas Analysis: It cansave your transformer�, IEEE Electrical Insulation

Magazine, Nov/Dec 1989 � Vol. 5, No. 6

[Duval et al, 2001] Duval, M. and dePablo, A. 2001, �Interpretationof Gas-In-Oil Analysis Using New IEC Publication60599 and IEC TC 10 Databases�, IEEE Electrical

Insulation Magazine, March/April 2001

[Duval et al, 2003] Duval, M. and CIGRÉ, 2003, �New Techniques forDissolved Gas-in-Oil Analysis�, IEEE Electrical In-

sulation Magazine, March/April 2003 � Vol. 19,No. 2

43

Page 44: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

[Duval et al, 2005] Duval, M. and Dukarm, J. et al, 2005, �Im-proving the Reliability of Transformer Gas-in-OilDiagnosis�, IEEE Electrical Insulation Magazine,July/August 2005 � Vol. 21, No. 4.

[Failhauer et al, 2006] Feilhauer, W. and Handschin, E. 2006, �Interpre-tation of Dissolved Gas Analysis Using Dempster-Shafer 's Theory of Evidence�, 9th International

Conference on Probabilistic Methods Applied to

Power Systems, June 11-15, 2006, Stockholm, Swe-den

[Field et al, 2002] Field, N. and Kramer, S. et al, 2002,"Condition-Based Rankingof Power Transformers",www.weidmann-tds.cn/huiyi/Seminar%202002%

20Las%20Vegas/SAntoszPaper.pdf, Weidmann-ACTI Conference Las Vegas, Nevada, November 8,2002, viewed 13 September 2008

[Gibeault et al, 1995] Gibeault, J.P. and Kirkup, J.K. 1995, �Early de-tection and continuous monitoring of dissolved keyfault gases in transformers and shunt reactors�,Electrical Electronics Insulation Conference, 1995

[IEC 60567, 2006] IEC 60567, 2006, �Oil-�lled electrical equipment �Sampling of gases and of oil for analysis of free anddissolved gases � Guidance�

[IEC 60599, 2007] IEC 60599, 2007, �Mineral oil-impregnated electri-cal equipment in service - Guide to the interpreta-tion of dissolved and free gases analysis�

[IET, 2008] IET, 2008, "Do we need to switch o�???", http://www.theiet.org/Forums/forum/messageview.

cfm?catid=226&threadid=6445&enterthread=y,11kV Transformer Oil Sampling, viewed 13September 2008

[Jakob, 2008] Jakob, F, 2008, �Application of Dissolved Gas Anal-ysis�, Transcomma 2008, 20 April 2008, KualaLumpur

[Jakob et al, 2003] Jakob, F. and Jakob, K. et al, 2003, "Use of gasconcentration ratios to interpret OLTC and OCBdissolved gas data", ieeexplore.ieee.org/iel5/8829/27951/01247901.pdf?arnumber=1247901,viewed 13 September 2008

44

Page 45: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

[Jakob et al, 2008] Jakob, K. and Jakob, F. 2008, �LTC Diagnostics�,Transcomma 2008, 20 April 2008, Kuala Lumpur

[Kan et al, 1994] Kan, H. and Miyamoto, T. et al, 1994, �Absorptionof CO2 and CO gases and Furfural in insulating oilinto paper insulation in oil-immersed transformers�,Conference Record of the 1994 EEE International

Symposium on Electrical Insulation, Pittsburgh, PAUSA, June 5-8, 1994

[Kan et al, 1995] Kan, H. and Miyamoto, T. 1995, �Proposals for anImprovement in Transformer Diagnosis Using Dis-solved Gas Analysis (DGA)�, IEEE Electrical Insu-

lation Magazine, November/December 1995 - Vol.11, No. 6.

[Kelman, 2005-8] Kelman Ltd, 2005-8, "Trans�x Transformer GasAnalyser", kelman.co.uk/index.php?option=

com_content&task=view&id=127&Itemid=67,viewed 20 August 2008

[Kramer, 2008] Kramer, A. 2008, "On-Load TapChangers for Power Transform-ers", books.google.com/books?id=

_r2O7D-rzBwC&pg=PT112&lpg=PT112&dq=kramer+

reinhausen&source=web&ots=0Duv8Gl4Vq&sig=

pDWJTEvPWdtRgQhniKPc-v28vLY&hl=en&sa=

X&oi=book_result&resnum=8&ct=result,

andDGAsearchathttp://www.reinhausen.

com/en/DesktopDefault.aspx/tabid-204/

searchcall-68/68_keepvisible-true/

redirected-1/?/sid-2947734/mid-68/tid-5/

ct-0/q-DGA//k-/et-4/rpp-3/sar-False/t-/

p-0/ap-True/cat-/cr-0/pr-0/icp-False/

icc-False/ifc-False/sl-2/sp-0/cs-/, viewed20 August 2008

[Lindgren, 2003] Lindgren, S. 2003, "Power Transformer AssetManagement On-Line DGA - The New Ballgame",www.bplglobal.net/eng/knowledge-center/

download.aspx?id=173, EPRI Substation Equip-

ment Diagnostics Conference XI, viewed 13September 2008

[Makhtar et al, 2008] Makhtar, Z. and Muhamad, Z. 2008, E-mail andFacebook correspondence on CUF-K 11kV trans-former incident, DGA results and sampling peri-odcity

45

Page 46: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

[Miranda et al, 2005] Miranda, V. and Castro, A.R.G. 2005, �Improvingthe IEC Table for Transformer Failure Diagnosis�,IEEE transactions on Power Delivery, Vol. 20, No.4, October 2005

[Muhamad et al, 2007] Muhamad, N.A. and Phung, B.T. et al, �Compara-tive Study and Analysis of DGAMethods for Trans-former Mineral Oil�, Powertech 2007

[Muhamad et al, 2008] Muhamad, N.A. and Phung, B.T. et al, �Dis-solved Gas Analysis of Faults in BiodegradableOil Transformer Insulating Systems�, 2008 Inter-

national Conference on Condition Monitoring and

Diagnosis, April 21-24, 2008, Beijing, China.

[NTT, 2001a] Northern Technology and Testing, 2001, "SyringeOil Sampling Procedures", www.nttworldwide.

com/tech2104.htm, viewed 13 September 2008

[NTT, 2008b] Northern Technology and Testing, "Glass Syringes,Valves, Plug Caps and Cases", www.nttworldwide.com/docs/NTT-Syringes.pdf, viewed 20 October2008

[Osztermayer at al, 2003] Osztermayer, J. and Cardillo, E. 2003, "Moni-toring Systems Applied to a 110-380kV substa-tion", www.uni-stuttgart.de/ieh/forschung/

veroeffentlichungen/2003_powertech_

osztermayer.pdf, viewed 20 August 2008

[Peni, 2004] Peni, Z. 2004, Miri Crude Oil Terminal (MCOT)Project discussion with MCOT operation sta� ZainiPeni, 2004

[Petronas, 2000] Petronas Technical Standard 63100811, �Field Com-missioning and Maintenance of Electrical Installa-tions and Equipment�, Appendix 16 (TransformerOil), item 6, Petroliam Nasional Berhad, August2000

[POA, 2007] Practicing Oil Analysis, 2007, "TransformerOil Analysis", www.practicingoilanalysis.com/article_detail.asp?articleid=282, viewed 13September 2008

[Reinhausen Grp, 2006] Reinhausen Group, 2006, "On Load",www.reinhausen.com/en/DesktopDefault.

aspx/tabid-204/searchcall-68/68_

keepvisible-true/redirected-1/?/

46

Page 47: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

sid-2947734/mid-68/tid-5/ct-0/q-DGA//k-/

et-4/rpp-3/sar-False/t-/p-0/ap-True/cat-/

cr-0/pr-0/icp-False/icc-False/ifc-False/

sl-2/sp-0/cs-/ (�DGA� search), 20 August 2008

[Rogers, 1975] Rogers, R.R. 1975, �U.K. Experience in the Inter-pretation of Incipient Faults in Power TransformersBy Dissolved Gas-in-Oil. Chromatographic Analy-sis�, Doble Conference Index of Minutes, Sec 10-201,1975

[Schroeder, 2000] Schroeder, D. 2000, "Failure of TR 77 atTSS 114, Northwest on July 30, 1999",www.icc.illinois.gov/downloads/public/

en/000607ComEd1App2.doc, viewed 20 August2008

[Serveron, 2007] Serveron, 2007, "Serveron White Paper � DGADiagnostic Methods", www.bplglobal.net/eng/

knowledge-center/download.aspx?id=216,viewed 13 September 2008

[Shell, 2000] Shell Design and Engineering Practice 63100811,�Field Commissioning and Maintenance of Electri-cal Installations and Equipment�, 8.5.2 and Ap-pendix 16 (Transformer Oil), item 6, Shell Group,August 2000

[Suwarno, 2006] Suwarno, 2006, �The In�uence of arc on dissolvedgases in transformer oils�, Department of ElectricalEngineering Bandung Institute of Technology, Ban-dung, Indonesia

[Thang et al, 2000] Thang, K.F. and Aggarwal, R.K. et al, 2000, � Sta-tistical and Neural Network Analysis of DissolvedGases in Power Transformers�, Dielectric Materials,

Measurements and Applications Conference Publi-

cation No. 473.

[Transgrid, 2007] Transgrid, 2007, "Network Management Plan",www.transgrid.com.au/trim/trim211409.pdf,p67-68, viewed 16 September 2008

[Ward et al, 2000] , Ward, B.H. and Lindgren, S. 2000, �A Sur-vey of Developments in Insulation Monitoring ofPower Transformers�, EPRI, Conference Record of

the 2000 IEEE Intemational Symposium on Electri-

cal Insulation, April 2-5, 2000, Anaheim, CA USA

47

Page 48: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

[Ward, 2003] Ward, S.A. 2003, �Evaluating Transformer Condi-tion Using DGA Oil Analysis�, Conference on Elec-

trical Insulation and Dielectric Phenomena, 2003

[Waukesha Electric, 2004] Waukesha Electric, 2004, "RMV-II LTC FieldRetro�t", www.waukeshaelectric.com/pdf/

Service/RMV-II_LTC_Field_Retro_Flyer_rev.

pdf, viewed 20 August 2008

[Weidmann-ACTI, 2008] Weidman-ACTI, 2008, "Weidmann-ACTIInc. Engineering and Analytical Services",www.transformerscommittee.org/info/S02/

S02-LTCpart1.pdf, viewed 14 September 2008

[Wikipedia, 2008a] Wikipedia, 2008a, "Dissolved Gas Analysis", en.wikipedia.org/wiki/Dissolved_gas_analysis ,viewed 20 August 2008

[Wikipedia, 2008b] Wikipedia, 2008b, "Condition Monitoring",en.wikipedia.org/wiki/Condition_monitoring

, viewed 29 August 2008

[Wikipedia, 2008c] Wikipedia, 2008c, Buchholz Relay en.wikipedia.

org/wiki/Buchholz_relay, viewed 13 September2008

[Wikipedia, 2008d] Wikipedia, 2008d, Fuller's Earth en.wikipedia.

org/wiki/Fuller's_earth, viewed 13 September2008

[Wikipedia, 2008e] Wikipedia, 2008e, "Chromatography",en.wikipedia.org/wiki/Chromatography,viewed 13 September 2008

[Wikipedia, 2008f] Wikipedia, 2008f, "Pyrolysis", en.wikipedia.org/wiki/Pyrolysis, viewed 13 September 2008

[Wikipedia, 2008g] Wikipedia, 2008g, "Furan", //en.wikipedia.org/wiki/Furan, viewed 13 September 2008

[Wikipedia, 2008i] Wikipedia, 2008h, "Beta scission", en.wikipedia.org/wiki/Beta_scission, viewed 20 September2008

[Woolley et al, 2994] Woolley, T. and Fetherston, F. et al, 1994, �Changesin Levels of Dissolved Gas in Normally OperatingGenerator Transformers, the E�ect of a NitrogenBreathing System and the E�ects on Interpretationof Dissolved Gas Analysis�, Proceedings of the 4th

48

Page 49: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

International Conference on Roperties and Applica-

tions of Dielectric Materials, July 3-8, 1994, Bris-bane Australia

[Wong, 2000] Wong, N. 2000, "Power Transform-ers Up-Rating: A Practical Example",www.eea.co.nz/images/Events/APEX/APEX%

2008%20Southern/13%20Wong,%20Nic%20-%

20Power%20Transformers.pdf, viewed 20 August2006

[Yamada et al, 1981] Yamada, M. and Nomura, Y. et al, 1981, �Auto-matic �eld monitoring of dissolved gases in trans-former oil�, IEEE Transactions on Power Apparatus

and Systems, Vol. PAS-100, No. 4, April 1981

[Youngblood, 2003] Youngblood, R. and Baker, C. et al, �Applicationof Dissolved Gas Analysis to Load Tap Changers�as quoted in [Jakob et al, 2003]

[Zama et al, 2008] Zama, S. and Kobayashi, T. et al, 2008, �Improve-ment for Diagnosing Internal Abnormalities in Oil-Filled Transformers�, International Conference on

Condition Monitoring and Diagnosis, April 21-24,2008, Beijing, China

49

Page 50: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Appendix A

Graphical representation of IEC 60599 DGA ratios39

Figure 31: Graphical representation of IEC 60599 DGA ratios (Taken from[IEC 60599, 2007, Annex B])

39Gas volume production is nearly quadratic with voltage, and linear with arc duration

50

Page 51: Dissolved Gas Analysis and Its Interpretation Techniques for Power Transformers No Cover)

Appendix B

IEC 60599 DGA interpretation �owchart

Figure 32: IEC 60599 DGA interpretation technique �owchart (Taken from[IEC 60599, 2007, Figure 1])

51