For more information, visit www.fmiproducts.com Installation and service must be performed by a quali- fied installer, service agency or the gas supplier. WARNING: Improper installation, adjustment, altera- tion, service or maintenance can cause injury or prop- erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi- tional information consult a qualified installer, service agency or the gas supplier. This appliance may be installed in an aftermarket,* per- manently located, manufactured (mobile) home, where not prohibited by local codes. * Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts. INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference. DIRECT-VENT CHASSIS OWNER’S INSTALLATION INSTRUCTIONS MODELS (V)DVC36(B)(H) AND (V)DVC42(B)(H) FOR USE WITH DVM SERIES BURNER MODULES Patent Pending PFS ® US

DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

  • Upload
    others

  • View
    4

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

For more information, visit www.fmiproducts.com

Installation and service must be performed by a quali-fied installer, service agency or the gas supplier.

WARNING: Improper installation, adjustment, altera-tion, service or maintenance can cause injury or prop-erty damage. Refer to this manual for correct installation and operational procedures. For assistance or addi-tional information consult a qualified installer, service agency or the gas supplier.

This appliance may be installed in an aftermarket,* per-manently located, manufactured (mobile) home, where not prohibited by local codes.* Aftermarket: Completion of sale, not for purpose of resale, from the manufacturer

State of Massachusetts: The installation must be made by a licensed plumber or gas fitter in the Commonwealth of Massachusetts.

INSTALLER: Leave this manual with the appliance. CONSUMER: Retain this manual for future reference.

DIRECT-VENT CHASSISOWNER’S INSTALLATION INSTRUCTIONS

MODELS (V)DVC36(B)(H) AND (V)DVC42(B)(H)FOR USE WITH DVM SERIES BURNER MODULES

Patent Pending

PFS ®

US

Page 2: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D2

Do not place clothing or other flammable material on or near the appliance. Never place any objects on the appliance.

Do not use this fireplace to cook food or burn paper or other flam-mable material.

This fireplace reaches high tem-peratures. Keep children and adults away from hot surface to avoid burns or clothing ignition. Fireplace will remain hot for a time after shutdown. Allow surface to cool before touching.

Carefully supervise young chil-dren when they are in the room with fireplace.

Keep the area around your fireplace clear of combustible materials, gasoline and other flammable vapor or liquids. Do not run fireplace where these are used or stored.

1. Neverinstallthefireplace• inarecreationalvehicle• inwindyordraftyareaswherecurtainsor

othercombustible(flammable)objectscanmakecontactwiththefireplacefront

• inhightrafficareas2. Turnapplianceoffandletcoolbeforeservic-

ing,installingorrepairing.Onlyaqualifiedservicepersonshouldinstall,serviceorrepairthisfireplace.Havefireplaceinspectedannu-allybyaqualifiedserviceperson.

SAFETy INFORMATION

TABLE OF CONTENTSSafety Information ............................................... 2Local Codes......................................................... 3Product Identification ........................................... 3Product Features ................................................. 3Pre-Installation Preparation ................................. 4Location of Termination Cap ................................ 6

Venting Installation Instructions ........................... 7Replacement Parts ............................................ 16Technical Service............................................... 17Accessories ....................................................... 17Illustrated Parts Breakdown and Parts List........ 18Warranty Information ...........................Back Cover

IMPORTANT: Read this owner’s manual carefully and completely before trying to assemble, operate or service this fireplace. Improper use of this fireplace can cause serious injury or death from burns, fire, explosion, electrical shock and carbon monoxide poisoning.

WARNING: Any change to this fireplace or it’s controls can be dangerous. Do not modify this fireplace under any circum-stances. Any parts removed for servicing must be replaced prior to operating fireplace.

WARNING: Do not use a blow-er insert, heat exchanger insert or other accessory not approved for use with this fireplace.

WARNING: Do not allow fans to blow directly into the fireplace. Avoid any drafts that alter burner flame patterns.

Due to high temperatures, the appliance should be located out of traffic and away from furniture and draperies.

Page 3: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 3

SAFETy INFORMATIONContinued

3. Youmustkeepcontrolcompartments,burn-ersandcirculatingairpassagesclean.Morefrequentcleaningmaybeneededduetoex-cessivelintanddustfromcarpeting,beddingmaterial,etc.Turnoffthegasvalveandpilotlightbeforecleaningfireplace.

4. Haveventingsystem inspectedannuallybya qualified service person. If needed, haveventingsystemcleanedorrepaired.

5. Donotuseanysolidfuels(wood,coal,paper,cardboard,etc.)inthisfireplace.Useonlythegastypeindicatedonfireplacenameplate.

6. Thisappliance,wheninstalled,mustbeelectri-callygroundedinaccordancewithlocalcodesor, in the absence of local codes,with theNational Electrical Code, ANSI/NFPA 70.

7. Donotusefireplaceifanyparthasbeenex-posedtoorunderwater.Immediatelycallaqualifiedservicepersontoarrangeforreplace-mentoftheunit.

8. Donotoperatefireplaceifanylogisbroken.9. Do not operate fireplacewith glass door

removed,crackedorbroken.10. Provide adequate clearances around air

openings.

LOCAL CODESInstallandusefireplacewithcare.Followalllocalcodes.Intheabsencetolocalcodes,usethecurrentNational Fuel Gas Code ANSI Z223.1/NFPA 54*. *Availablefrom:AmericanNationalStandardsInstitute,Inc.

1430BroadwayNewYork,NY10018

NationalFireProtectionAssociation,Inc.BatterymarchParkQuincy,MA02269

Figure 1 - Direct-Vent Fireplace

Glass DoorAssembly

Switch Bracket for Optional Remote and Blower

Upper Louver Panel

Lower Louver Panel

Flue Collar

NailingFlange

PRODUCT FEATURESTheseareafewfactsthatcanhelpyouunderstandandenjoyyourdirect-ventfireplace:• Theventingsystemmayberoutedtotheout-sideofyourhomeinseveralways.Itmayventthroughtheroof(vertical)oritmayventtoanoutside/exteriorwall (horizontal).The ventpipeinstallationisveryimportanttoallowforproperoperation.Youmustfollowtheventinginstructionsverycarefullyforeitherverticalorhorizontalapplications.

• Thisfireplacemaybeinstalledinanyroomofyourhouseprovidedall localcodesand theseinstallationinstructionsarefollowed.

• Thisfireplacerequiresawallswitch,hand-heldremoteorwallthermostat(millivolt)foropera-tion(seeAccessories,page42).

• The use of a blower requires electricity ifinstalled.Ifyouplantoinstallthebloweratalaterdate,outletatbottomoffireplacemustbewiredduringframing.

• Yourdirect-ventgasfireplacesystem(fireplaceandventing)isabalancedandsealedgasop-eratingunit. It requires approximately 10-20minutes of operating time before the flamepatternstabilizes.

PRODUCT IDENTIFICATION

Page 4: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D4

D

RW

FW

Figure 2 - Common Fireplace Locations

Flush with a wall

Through exterior wall enclosed in a chase

Corner installation

Figure 3 - Fireplace Bottom Dimensions

29" (36")36 1/4" (42")

41" (36")48" (42")

teriorfinish.• Theremust not be any obstruction such asbushes, garden sheds, fences, decks or util-itybuildingswithin24"fromthefrontoftheterminationcap.

• Donotlocateterminationcapwhereexcessivesnowor icebuildupmayoccur.Besure toclearventterminationareaaftersnowfallstopreventaccidentalblockageofventingsystem.Whenusingsnowblowers,donotdirectsnowtowardsventterminationarea.

PRE-INSTALLATION PREPARATION

LOCATION AND SPACE REqUIREMENTSDeterminethesafestandmostefficientlocationfor your FMI PRODUCTS, LLC direct-ventfireplace.Make sure that rafters andwall studsarenotinthewayoftheventingsystem.Choosea locationwhere theheatoutput isnotaffectedby drafts, air conditioning ducts,windows ordoors.Figure2showssomecommonlocations.Beawareofallrestrictionsandprecautionsbeforedecidingtheexactlocationforyourfireplaceandterminationcap.When deciding the location of your fireplace,followtheserules:• Donotconnectthisfireplaceventingtoachim-neyflueservingaseparatesolid-fuelburningfireplaceorappliance.

• Due to high temperatures, donot locate thisfireplace inhigh trafficareas,windyordraftyareasornearfurnitureordraperies.

• Properclearancesmustbemaintained.• Ifyourfireplaceistobeinstalleddirectlyoncarpeting,vinyltileoranycombustiblemate-rialotherthanwood,itmustbeinstalledonametalorwoodpanelextendingthefullwidthanddepthofthefireplace.SeeFigure3.

• Yourfireplace isdesigned tobeused inzeroclearanceinstallations.Wallorframingmaterialcanbeplaceddirectlyagainstanyexteriorsur-faceontheback,sidesortopofyourfireplace,exceptwhere standoff spacers are integrallyattached.Ifstandoffspacersareattachedtoyourfireplace,thesespacerscanbeplaceddirectlyagainstwallorframingmaterial.Seeframingdetailsonpage5.

• Ifyouplanoninstallingatelevisionorenter-tainmentcenterrecessedaboveyourfireplace,itisrecommendedthatyoumaintainaminimum18"abovetopoflouveropening.

• Whenlocatingterminationcap,itisimportanttoobservetheminimumclearancesshowninFigure7,page8.

• If recessing into awall, you can avoid extraframingbypositioningyourfireplaceagainstanalreadyexistingframingmember.

• Donot recess terminationcap into awall orsiding.

• Youmaypainttheterminationcapwith450ºFheat-resistantpainttocoordinatewiththeex-

CLEARANCESMinimumclearances tocombustibles for thefire-placeareasfollows:*Backandsides 0"Perpendicularwalls 6"Floor 0"Ceilingtolouveropening 42"Front 36"TopofStandoffs 0"Vent (Seeventinginstructionsfor specificventingclearances.)Combustiblematerialwith amaximum thick-nessof5/8"maybeflushwith the top frontoffireplace.*Forbackand sidesoffireplace,donotpackwith insulation or othermaterials. Zero inchclearancetocombustiblematerialsareforfram-ingpurposeonly.

21 1/8" (36")23 1/4" (42")

Page 5: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 5

PRE-INSTALLATION PREPARATION

ContinuedA

B

E

F

G

H

D C

Nailing Tabs

Figure 4 - Framing Clearances for Installation Against an Exterior Wall

361/8" (36")401/8" (42")

411/4" (36")481/4" (42") 21" Hor. Vent

241/2" Vert. Vent

Figure 5 - Framing Clearances for Corner Installation

41"411/4"

353/4"

15" 49 5/8"

133/4"

681/2"

103/8"

NailingTabs

CB

A

DE

FG

Top of Louver Opening

3

2

1

4

5

6

7

Wall

Ref. Mantel Depth Ref.

Mantel from Top of Louver

Opening1 14" A 16"2 12" B 14"3 10" C 12"4 8" D 10"5 6" E 8"6 4" F 6"7 2" G 4"

Figure 6 - Clearances for Combustible Mantels

23" Hor. Vent26 1/2" Vert. Vent

36"

42"

A

B

E

F

G

H

D C

Nailing Tabs

48"481/4"

415/8"

215/8" 58 1/2"

163/4"

811/2"

131/2"

NailingTabs

36" Models

42" Models

NOTICE: This fireplace is in-tended for use as supplemental heat. Use this fireplace along with your primary heating system. Do not install this fireplace as your primary heat source. If you have a central heating system, you may run system’s circulating blower while using fireplace. This will help circulate the heat through-out the house. In the event of a power outage, you can use this fireplace as a heat source.

FRAMING AND FINIShINGFigure4shows typical framingof thisfireplace.Figure5showsframingforcornerinstallation.Allminimumclearancesmustbemet.For available accessories for this fireplace, seeAccessoriesonpage17.Ifyouareusingasepa-ratecombustiblemantelpiece,refertoFigure6for proper installation height.You can installnoncombustiblemantelsatanyheightabovethefireplace.Note:Noncombustiblemantelsmaydiscolor!

Page 6: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D6

Figure 7 - Minimum Clearances for Termination Cap

LOCATION OF TERMINATION CAP

FixedClosed Openable Fixed

Closed

V

V

V

V

V V

V

V

X

X

V X

G

G

JF

B

B

K

N

H

I

A

N

E

L

D

B

M

A

C

B

V

V

A

G

G

B

TERMINATION CAP AIR SUPPLY INLET GAS METER RESTRICTED AREA(TERMINATION PROHIBITED)

A = clearance above grade, veranda, porch, deck, or balcony [*12" (30.5 cm) minimum]B = clearance to window or door that may be opened [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000]C = clearance to permanently closed window [minimum 12" (30.5 cm) recommended to prevent condensation on window]D = vertical clearance to ventilated soffit located above the terminal within a horizontal distance of 24" (61 cm) from the center-line of the terminal [18" (45.7 cm) minimum]E = clearance to unventilated soffit [12" (30.5 cm) minimum]F = clearance to outside corner (see below)G = clearance to inside corner (see below)H = *not to be installed above a meter/regulator assembly within 36" (91.4 cm) horizontally from the center line of the regulator

I = clearance to service regulator vent outlet [*72" (182.9 cm) minimum]J = clearance to non-mechanical air supply inlet to building or the combustion air inlet to any other fireplace [6" (15 cm) min. for 10,000 Btu or less; 9" (23 cm) in US if between 10,000 and 50,000, 12" (30 cm) in Canada if between 10,000 and 100,000; 12" (30 cm) in US if greater than 50,000, 36" (91 cm) in Canada if greater than 100,000]K = clearance to a mechanical air supply inlet [*In Canada, 6 ft. (1.83m) minimum; In US 3 ft. (91 cm) above if within 10 ft. (3 m) horizontally]L = † clearance above paved side-walk or a paved driveway located on public property [*84" (213.3 cm) minimum]M = clearance under veranda, porch, deck [*12" (30.5 cm) minimum ‡]N = clearance above a roof shall extend a minimum of 24" (61 cm) above the highest point when it passes through the roof surface and any other obstruction within a horizontal distance of 18" (45.7 cm)

† vent shall not terminate directly above a side-walk or paved driveway which is located between two single family dwellings and serves both dwellings*‡ only permitted if veranda, porch, deck or balconey is fully open on a minimum of 2 sides beneath the floor** as specified in CAN/CSA B149 (.1 or .2) Installation Codes (1991) for Canada and U.S.A. Note: Local codes or regulations may require different clearances

A = 6" (15.2 cm)

Inside Corner

V

B

E

V

B = 6" (15.2 cm)

C = Maximum depth of 48" (121.9 cm) for recessed locationD = Minimum width for back wall of recessed location - Combustible - 38" (965 mm) Noncombustible - 24" (61 cm)E = Clearance from corner in recessed location- Combustible - 6" (15.2 cm) Noncombustible - 2" (5.1 cm)

Outside Corner Recessed Location

G

H

G = 12" (30.5 cm) minimum clearance

Balcony with No Side Wall

V

J

Combustible & NoncombustibleH = 24" (61 cm)J = 20" (50.8 cm)

Balcony with Perpendicular Side Wall

C

D

C

Termination Clearances for Buildings with Combustible and Noncombustible Exteriors

Openable

Page 7: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 7

VENTINg INSTALLATION INSTRUCTIONS

NOTICE: Read these instruc-tions completely before at-tempting installation.

Thesemodels are tested and approved for usewithFMIPRODUCTS,LLC (direct-vent) pipecomponentsandterminations.Theventingsystemmustterminateontheoutsideofthestructureandcannotbeattachedtoachimneyorfluesystemservingaseparatesolidfuelorgasburningappliance.Adirect-vent appliancemusthaveitsownventingsystem.DONOTcommonventthisappliance.Thesemodels are approved to be vented eitherhorizontallythroughanoutsidewallorverticallythrougharooforchaseenclosureusingthefol-lowingguidelines:• Whenventingsystemterminateshorizontallyonanoutsidewall,youmayinstallastandoffiftheterminationcapistobeinstalleddirectlyonacombustiblefinishsuchasvinyl,wood,stucco,etc.

• Never run the vent downward as thismaycause excessive temperatureswhich couldcauseafire.

• Ventpipeairspaceclearancestocombustiblesare 1" on all sides except on the horizontalsections,which requires 2" clearance fromthetopofthepipe.Wheretheterminationcappenetrates a combustiblewall, 1" air spaceclearanceisrequired.

• Snorkel terminations are required whenminimumclearancetogradecannotbemet(seeFigure16onpage11).

• Havefireplaceandselectedventcomponentsonhandtohelpdeterminetheexactmeasurementswhenelbowingoroffsetting.Alwaysusewallfirestopswhenpenetratingwallsandfirestopswhenpenetratingceilingsoratticspaces.

• Ifusingaventingconfigurationofonlyhori-zontalventingwithnoverticalrun,a1/4"riseforevery12"ofruntowardtheterminationisrequired.

• Forinstallationoffireplaceatelevationsof4000feetorgreater,payspecialattentiontoventingrequirementrecommendations.

WARNING: Read all instruc-tions completely and thoroughly before attempting installation. Failure to do so could result in serious injury, property damage or loss of life.

NOTICE: Failure to follow these in-structions will void the warranty.

NOTICE: Do not seal termination cap to vent pipe. Cap must be removable for vent inspection and maintenance.

INSTALLATION PRECAUTIONS• Wearglovesandsafetyglassesforprotection• Use extreme cautionwhen using ladders orwhenonrooftops

• Beawareofelectricalwiringlocationsinwallsandceilings

Thefollowingactionswillvoidthewarrantyonyourventingsystem:• Installationofanydamagedventingcomponent• Unauthorizedmodificationoftheventingsys-tem(Donotcutoralterventcomponents)

• Installationofanycomponentpartnotmanufac-turedorapprovedbyFMIPRODUCTS,LLC

• Installationother than as instructedby theseinstructions

WARNING: This gas fireplace and vent assembly must be vented directly to the outside. The venting system must NEVER be attached to a chimney serving a separate solid fuel burning appliance. Each direct-vent gas appliance must use a separate vent system. Do not use common vent systems.

WARNING: Vent pipe air space clearances to combustibles are 1" on all sides except on the horizontal sections, which require 2" clearances from the top of the pipe. Where the termination cap penetrates a combustible wall, 1" air space clearance is required.

Page 8: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D8

INSTALLATION PLANNINGThere are two basic types of direct-vent in-stallation:• HorizontalTermination• VerticalTermination

horizontal Termination InstallationIMPORTANT: Horizontal square terminationsrequireonlyinnerportionofwallfirestop.Hori-zontalinstallationsusingroundterminationrequireexteriorportionofwallfirestop (seeFigure14,page10.1. Setthefireplaceinitsdesiredlocationanddeter-

minetherouteyourhorizontalventingwilltake.Donotsecurethefireplaceuntilallventinghasbeeninstalled.Someinstallationsrequireslidingthefireplaceinandoutofpositiontomakefinalventingconnections.Figures14through18onpages10through12showdifferentconfigura-tionsforventingwithhorizontalterminationthatwillhelpyoudecidewhichapplicationbestsuitsyourinstallation.Checktoseeifwallstudsorroofraftersareinthepathofyourdesiredvent-ingroute.Iftheyare,youmaywanttoadjustthelocationofthefireplace.

2. Directventpipesectionsandcomponentsaredesignedwithspecialtwist-lockconnections.

Twist-Lock Procedure:Thefemaleendsofthepipeshave locking lugs (indentations).Theselugswillslidestraight intomatchingslotsonthemaleendsofadjacentpipes.Pushpipesec-tionstogetherandtwistonesectionclockwiseapproximatelyone-quarterturnuntilthesectionsarefullylocked(seeFigure8).Note:Horizontalrunsofventmustbesupportedeverythreefeet.Usewallstrapsforthispurpose.

3. Usea45°elbow toconnectventingsystemtofireplacefluecollar.Theelbowisdesignedto be twist-locked onto the flue collar asdescribed in step 2. IMPORTANT:Donotattempttoaltertheconfigurationoftheelbowbycutting,twisting,bending,etc.

4. Assemblethedesiredcombinationofpipeandelbowstothefireplacefluecollar.Iftherearelongportionsofventingrun,pre-assembledpipesectionsmaybeinstalledassubassem-bliesforconvenience.

VENTINg INSTALLATION INSTRUCTIONS

Continued

Figure 8 - Vent Pipe Connections

Female Locking Lugs

Male Slots

(Framing Detail)

11 1/2"

11 1/2" Inside Framing

11 1/2"

8 1/2"

Vent Opening Combustible Wall

Vent Opening Noncombustible Wall

Figure 9 - Vent Opening Requirements

Center of Hole

5. Carefullydeterminethelocationwheretheventpipeassemblywillpenetratetheoutsidewall.Thecenteroftheholeshouldlineupwiththecenter-lineofthehorizontalventpipe.Markthewallfora111/2"x111/2"squarehole.Cutandframethesquareholeintheexteriorwallwheretheventwillbeterminated.Ifthewallbeingpenetrated is constructedofnoncombustiblematerial,suchasmasonryblockorconcrete,a 8 1/2"holewithzeroclearanceisacceptable(seeFigure9).

Page 9: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 9

VENTINg INSTALLATION INSTRUCTIONS

Continued

WARNING: Do not recess vent termination into any wall. This will cause a fire hazard.

6. Noncombustible Exterior Wall:Positionthehorizontalventcapinthecenterofthe81/2"roundholeandattachtotheexteriorwallwithfourwoodscrewsprovided.Beforeattachingtheventcap toexteriorwall, runabeadofnon-hardeningmastic(pliablesealant)aroundtheoutsideedgestomakeasealbetweenitandtheoutsidewall.Note:Thefourwoodscrewsprovidedshouldbereplacedwithappropriatefastenersforstucco,brick,concreteorothertypesofsidings.

Combustible Exterior Wall:Forvinylsiding,stuccoorwoodexteriors,asidingstandoffmaybeinstalledbetweentheventcapandexteriorwall.The siding standoffprevents excessiveheat from damaging the sidingmaterials.Sidingmaterialmustbecuttoaccommodatestandoff.Bolttheventcaptothestandoff.Ap-plynon-hardeningmasticaroundoutsideedgeofstandoff.Positionthestandoff/capassemblyinthecenterofthe111/2"squareholeandattachtoexteriorwallwithwoodscrewsprovided(seeFigure11).Thesidingstandoffmustsitflushagainsttheexteriorfasciamaterial.

7. Connecting Vent Cap with horizintal Vent Pipe:Slidethewallfirestopovertheventpipebeforeconnectinghorizontalruntoventcap(seeFigure12).

8. Carefullymovefireplace,withventassemblyattached, towardwall and insert vent pipeintohorizontaltermination.Thepipeoverlapshouldbeaminimumof11/4"(seeFigure13,page10).

9. Combustible Exterior Wall Only:Slidewallfirestopagainstinteriorwallsurfaceandattachwithscrewsprovided.SeeFigure13,page10,forhorizontalterminationdetails.

10. Placefireplace into position and shimwithnoncombustiblematerial if needed.Nail orscrewsideflangestoframingtosecureunitinplace.IMPORTANT:Makesurefireplaceislevelbeforesecuring.Iffireplaceisnotlevelitwillnotworkproperly.

Figure 10 - Installing Horizontal Vent Cap (Noncombustible Exterior)

Wood Screw

Vent Cap

Figure 11 - Installing Siding Standoff (Combustible Exterior Wall)

Cut Siding Away to Fit Standoff

Wood Screw

Screws

Standoff

Vent Cap

Apply Masticto All Four Sides

Vent Cap(Horizontal Termination)

Interior Wall Surface

Wall Firestop

Horizontal Vent Pipe

Figure 12 - Connecting Vent Cap with Horizontal Vent Pipe

Screw

Page 10: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D10

VENTINg INSTALLATION INSTRUCTIONS

Continued

Figure 13 - Typical Horizontal Termination Cap Mounting with

Additional Siding Standoff Installed

Siding Standoff

Screws

High Wind Termination

Apply Mastic to Outside Edge of Standoff

Exterior Wall with Vinyl Siding

Maintain 1" Minimum Air Space Around Outer Pipe When Penetrating a Wall

Minimum Pipe Overlap 11/4"

Wall Firestop

Direct-Vent Pipe

horizontal Termination ConfigurationsFigures14 through18 showdifferent configura-tionsandalternativesforventingwithhorizontaltermination.Each figure includes a chartwithcriticalminimumandmaximumdimensionswhichMUSTbemet.IMPORTANT:Ifusingaventingconfigurationofonlyhorizontalventingwithnoverticalrun,a1/4"riseforevery12"ofruntowardtheterminationisrequired.

NOTICE: Do not seal termination cap to vent pipe. Cap must be removable for vent inspection and maintenance.

WARNING: Never run vent downward as this may cause excessive temperatures which could cause a fire. Operation of improperly installed and main-tained venting system could result in serious injury, property damage or loss of life.

GROUND FLOOR INSTALLATIONRecommendedApplications:• Installationusingcabinetsurrounds• Throughthewallusingroundorsquaretermina-tion(upto12"Adjustablepipe)

• NOTFORCORNERINSTALLATION

Horizontal High Wind Square Termination

Wall Firestop

45° Elbow

Figure 14 - Horizontal Termination Configuration for Square or Round

Terminations

45° Elbow

Wall Firestop

Horizontal Round Termination

Exterior Portion of Wall Firestop (Round Termination Only)

Adjustable Pipe 12" Max.

Round Termination

Square Termination

Vertical (V) horizontal (h)

32 3/4" min. 17" max.

* If installing this fireplace at altitudes of 4000 feet and above, it is recommended that an additional vertical height of 6" be added to the vent system.

111/2" X 111/2" Frame Opening

Page 11: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 11

CORNER INSTALLATIONRecommendedApplications:• Cornergroundfloorinstallation• Groundfloorinstallationwherepipeventshorizon-tallythroughwall(over12"horizontalpipe)

• Basementinstallationwhereonefootclearancefromgroundtoterminationispossible

VENTINg INSTALLATION INSTRUCTIONSContinued

Figure 15 - Horizontal Termination Configuration for Corner Installation Using One 90° Elbow

Square Termination

Wall Firestop

Not to Exceed (H) Limits

As Required for (V), See Chart for Pipe Section Required

45° Elbow

90° Elbow

90° Elbow

Square Termination

Wall Firestop

45° Elbow

12" Min.

RequiredVertical (V) Vertical Pipe horizontal (h)

*43 1/2" min. None 30" max.54 1/2" min. 1 ft. 48" max.66 1/2" min. 2 ft. 60" max.78 1/2" min. 3 ft. 84" max.90 1/2" min. 4 ft. 20' max.

* Ground Floor Corner Venting

Not to Exceed (H) Limits

SNORKEL TERMINATION INSTALLATIONRecommendedApplications:• Installationsrequiringaverticalriseonbuildingexterior• AnyinstallationusingsnorkelterminationtoachieveonefootabovegroundSnorkelterminationsareavailableforinstallationsrequiringaverticalriseontheexteriorofthebuilding.Ifinstallingsnorkelterminationbelowgrade,youmustprovideproperdrainagetopreventwaterfromenteringsnorkeltermination(seeFigure16).Donotbackfillaroundsnorkeltermination.

Snorkel Termination

12" Min.

Snorkel Termination

Wall Firestop

90° Elbow

45° Elbow

Figure 16 - Snorkel Termination Configurations for Below Ground Installation

Snorkel Termination

Adequate Drainage

12" Min.

12" Min.

Page 12: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D12

VENTINg INSTALLATION INSTRUCTIONSContinued

Venting with Two 90° Elbows

Vertical (V) horizontal (h1)

horizontal (h1) +

horizontal (h2)

5' min. 2' max. 6' max.6' min. 4' max. 12' max.7' min. 6' max. 18' max.8' min. 8' max. 20' max.

20' max. 8' max. 20' max.

Figure 17 - Horizontal Termination Configuration for Venting Using Two 90° Elbows

45° Elbow

hORIZONTAL SYSTEM INSTALLATION USING TWO 90° ELBOWSThefollowingconfigurationsshowtheminimumverticalriserequirementsforahorizontalsystemusingtwo90°elbows.

Venting with Two 90° Elbows

Vertical (V)horizontal (h

1) +

horizontal (h2)

5' min. 6' max.6' min. 12' max.7' min. 18' max.8' min. 20' max.

20' max. 20' max.

Figure 18 - Horizontal Termination Configuration for Venting Using Two 90° Elbows with Termination at 90° with Fireplace

45° Elbow

Page 13: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 13

INSTALLATION FOR VERTICAL TERMINATIONNote:Vertical restrictormustbe installed inallverticalinstallations.1. Determine the route your vertical venting

willtake.Ifceilingjoists,roofraftersorotherframingwill obstruct the venting system,consideranoffset(seeFigure19)toavoidcut-tingloadbearingmembers.Note:Payspecialattentiontotheseinstallationinstructionsforrequiredclearances(airspace)tocombustibleswhenpassingthroughceilings,walls,roofs,enclosures,atticrafters,etc.Donotpackairspaceswithinsulation.Alsonotemaximumvertical rise of the venting systemand anymaximumhorizontaloffsetlimitations.

2. Setthefireplaceindesiredlocation.Dropaplumblinedownfromtheceilingtotheposi-tionofthefireplaceexitflue.Markthecenterpointwheretheventwillpenetratetheceiling.Drillasmalllocatingholeatthispoint.

Dropaplumblinefromtheinsideoftherooftothelocatingholeintheceiling.Markthecenterpointwheretheventwillpenetratetheroof.Drillasmalllocatingholeatthispoint.

Flat Ceiling Installation1. Cuta111/2"squareholeintheceilingusing

thelocatingholeasacenterpoint.Theopen-ingshouldbeframedto111/2"x111/2"(29.21cmx29.21cm)insidedimensions,asshowninFigure9onpage8usingframing lumberthesamesizeastheceilingjoists.Iftheareaabovetheceilingisaninsulatedceilingoranatticspace,nailfirestopfromthetopside.Thispreventslooseinsulationfromfallingintotherequiredclearancespace.Iftheareaabovetheceilingisalivingspace,installfirestopbelowtheframedhole.Thefirestopshouldbeinstalledwithnolessthanthreenailsperside(seeFigure20).

2. Assemble the desired lengths of pipe andelbowsnecessarytoreachfromthefireplaceflueupthroughthefirestop.Besureallpipeandelbowconnectionsarefullytwist-locked(seeFigure8,page8).

3. Cutaholeintheroofusingthelocatingholeasacenterpoint. (Coveranyexposedopenventpipesbeforecuttinghole inroof.)The11 1/2" x 11 1/2" holemust bemeasuredonthe horizontal; actual lengthmaybe largerdepending on the pitch of the roof.Theremustbea1"clearancefromtheventpipetocombustiblematerials.FrametheopeningasshowninFigure9,page8.

4. Connect a section of pipe and extend upthroughthehole.

Note:Ifanoffsetisneededtoavoidobstruc-tions,youmustsupporttheventpipeevery3feet.Usewallstrapsforthispurpose(seeFig-ure19).Wheneverpossible,use45°elbowsinsteadof90°elbows.The45°elbowoffersless restriction to theflowof thefluegasesandintakeair.

VENTINg INSTALLATION INSTRUCTIONS

Continued

Figure 19 - Offset with Wall Strap and 45° Elbows

45° Elbow

Wall Strap

Roof Flashing

Ceiling Firestop

Figure 20 - Installing Firestop

If area above is a living space, install firestop below framed hole.

If area above is an attic space or insulated area, install firestop above framed hole.

Page 14: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D14

5. Place the flashing over the pipe section(s)extendingthroughtheroof.Securethebaseoftheflashingtotheroofandframingwithroof-ingnails.BesureroofingmaterialoverlapsthetopedgeoftheflashingasshowninFigure19,page13.Theremustbea1"clearancefromtheventpipetocombustiblematerials.

6. ContinuetoaddpipesectionsuntiltheheightoftheventcapmeetstheminimumbuildingcoderequirementsdescribedinFigure7onpage6.Note:Youmustincreaseventheightforsteeproofpitches.Nearbytrees,adjoiningrooflines,steeppitchedroofsandothersimilarfactorsmaycausepoordraftordown-draftinginhighwinds.Increasingtheventheightmaysolvethisproblem.

7. Twist-locktheventcapontothelastsectionofventpipe.

Note:Iftheventpipepassesthroughanyoccupiedareasabovethefirstfloor,includingstoragespacesand closets, youmust enclose pipe.Youmayframeandsheetrocktheenclosurewithstandardconstructionmaterial.Make sure andmeet theminimumallowableclearancestocombustibles.Do not fill any of the required air spaceswithinsulation.

VENTINg INSTALLATION INSTRUCTIONS

Continued

Vertical Termination ConfigurationsFigures21 through24showfourdifferentcon-figurationsforverticaltermination.

Venting with Two 90° Elbows

Vertical (V)

horizontal (h1) +

horizontal (h2)

5' min. 2' max.6' min. 4' max.7' min. 6' max.8' min. 8' max.

20' max. 8' max.

Figure 21 - Vertical Venting Configuration Using Two 90° Elbows with Two Horizontal Runs (Vertical

Round High Wind Termination Shown)

Note: Install restrictor into inner collar of

fireplace as shown.

45° Elbow

Venting with One 90° ElbowVertical (V) horizontal (h)

5' min. 2' max.6' min. 4' max.7' min. 6' max.8' min. 8' max.

20' max. 8' max.

Figure 22 - Vertical Venting Configuration Using One 90° Elbow

(Vertical Round High Wind Termination Shown)

45° Elbow

Note: Install restrictor into inner collar of fireplace as shown.

Page 15: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 15

VENTINg INSTALLATION INSTRUCTIONS

Continued

Note: Install restrictor into inner collar of fireplace as shown.

Venting with Two 90° ElbowsVertical (V

1) horizontal (h)

5' min. 6' max.6' min. 12' max.7' min. 18' max.8' min. 20' max.

Note: Vertical (V1) + Vertical (V

2) = 40' max.

Figure 23 - Vertical Venting Configuration Using Two 90° Elbows

(Vertical Round High Wind Termination Shown)

45° Elbow

Vertical VentingV = 40' max.

Figure 24 - Vertical Venting Configuration With No Horizontal Run (Vertical Round High Wind Termination

Shown)

Note: Install restrictor into inner collar of fireplace as shown.

45° Elbow

Page 16: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D16

PARTS LIST FOR VENTING KITS AND COMPONENTS

FMI PRODUCTS, LLC (5"/8") Pipe & Vent KitsNumber DescriptionP58-6 6" Section Double Wall Pipe, GalvanizedP58-12 12" Section Double Wall Pipe, GalvanizedP58-24 24" Section Double Wall Pipe, GalvanizedP58-36 36" Section Double Wall Pipe, GalvanizedP58-48 48" Section Double Wall Pipe, GalvanizedPA58-712 Adjustable 7"-12" Section Double Wall Pipe, GalvanizedE58-45 45° Elbow, GalvanizedE58-90 90° Elbow, GalvanizedVKG-58 Ground Floor Vent Kit, Galvanized (Includes: 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop, Horizontal Square Termination, 16 Screws)VKB-58 Basement Vent Kit, Galvanized (Includes: 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop, Horizontal Square Termination, 4' Pipe, 90° Elbow, 20 Screws)VKS-58 Snorkel Vent Kit, Galvanized (Includes: 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop, 36" Snorkel Termination, 4' Pipe, 1' Pipe, 90° Elbow, 26 Screws)VKR-58 Roof Vent K i t , Galvanized (Includes: 45° Elbow, 7"-12" Adjustable Pipe, Flue Restrictor, Vertical High Wind Termination, 2' Pipe, 4' Pipe, Wall Firestop, Storm Collar, Roof Flashing [0/12 - 6/12], 26 Screws)VKC-58 Corner Vent Kit, Galvanized (Includes 45° Elbow, 7"-12" Adjustable Pipe, Wall Firestop, Horizontal Termination, 6" Pipe, 90° Elbow, 18 Screws)HHTK-58 High Wind Round Horizontal Termination Kit (Includes Round Termination,

VENTINg INSTALLATION INSTRUCTIONS

Continued

Wall Firestop, 45° Elbow)Number DescriptionHHT-58 High Wind Round Horizontal Termination Kit, GalvanizedHTS-58 Horizontal Square Termination, GalvanizedHTKS-58 Horizontal Square Termination Kit (Includes: Square Termination, Wall Firestop, 45° Elbow)VT-58 Vertical Round Termination, GalvanizedST-58-14 14" Snorkel Termination, GalvanizedST-58-36 36" Snorkel Termination, GalvanizedSC-58 Storm Collar, GalvanizedWF-58 Wall Firestop, GalvanizedRF-58-6 Roof Flashing - 0 to 6/12 Pitch, GalvanizedRF-58-12 Roof Flashing - 6/12 to 12/12 Pitch, GalvanizedVR-58 Vertical Restrictor, GalvanizedS-58 Vinyl Siding Standoff, GalvanizedWS-58 Wall StrapCS-58 Cathedral Ceiling SupportFP-58 Firestop PlateSF-58 Stucco Flashing - For use with HTS-58RF-58 Flat Roof Flashing

REPLACEMENT PARTSNote: Useonlyoriginalreplacementparts.Thiswill protect yourwarranty coverage for partsreplacedunderwarranty.

PARTS UNDER WARRANTYContact authorized retailers of this product. Iftheycannotsupplyoriginalreplacementpart(s),callFMIPRODUCTS,LLC’sCustomerServiceDepartmentat1-866-328-4537.Whencalling,haveready• yourname• youraddress• modelandserialnumbersofyourfireplace• howfireplacewasmalfunctioning• typeofgasused(propane/LPornaturalgas)• purchasedateUsually,wewillaskyoutoreturntheparttothefactory.

Page 17: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 17

FACE/LOUVER PANEL KIT (Not Shown) FPD36-Filigree,BlackFPD36B-Filigree,BrushedBrassFPD36P-Filigree,PlatinumRLD42-RolledLouver,BlackFPD42-Filigree,BlackFPD42B-Filigree,BrushedBrassFPD42P-Filigree,Platinum

LOUVER TRIM KIT (Rolled Louvers Only) (Not Shown) LT36B-BrushedBrassLT36P-PlatinumLT42B-BrushedBrassLT42P-Platinum

DEFLECTION hOODS (Not Shown)hD36-Black(2"Brow)hD42-Black(2"Brow)

PERIMETER TRIM KIT (Not Shown)PT36-BlackPT36B-BrushedBrassPT36P-PlatinumPT42-BlackPT42B-BrushedBrassPT42P-Platinum

MANUAL BLOWER KIT - BKManualvariablecontrolbloweraccessoryprovidesbetter heat distribution.Complete installationand operation instructionsincludedinthismanual.

ThERMOSTATICALLY CONTROLLED BLOWER KIT - BKTProvides better heat distribution.Blower turnsoff and on automatically, as needed.Completeinstallation and operation instructions includedinthismanual.

PARTS NOT UNDER WARRANTYContactauthorizedretailersofthisproduct.Iftheycannotsupplyoriginalreplacementpart(s),callFMIPRODUCTS,LLCat 1-866-328-4537 forreferralinformation.Whencalling,haveready• modelnumberofyourfireplace• thereplacementpartnumber

TECHNICAL SERVICEYoumayhavefurtherquestionsaboutinstallation,operationortroubleshooting.Ifso,contactFMIPRODUCTS,LLC’sCustomerServiceDepart-ment at 1-866-328-4537.When calling, pleasehave yourmodel and serial numbers of yourheaterready.YoucanalsovisitFMIPRODUCTS,LLC’swebsiteat www.fmiproducts.com.

ACCESSORIES

NOTICE: All accessories may not be available for all fireplace models.

Purchasethesefireplaceaccessoriesfromyourlocalretailer. If theycannotsupply theseaccessories,callFMIPRODUCTS,LLC’sSalesDepartmentat1-866-328-4537for information.Youcanalsowritetotheaddresslistedonthebackpageofthismanual.

BRICK LINER KIT(Not Shown)BL36DA -TexturedRefractoryBL36DSA -StandardRefractoryBL36DhA-TexturedRefractoryHerringboneBL36DhSA-StandardRefractoryHerringboneBL42DA-TexturedRefractoryBL42DSA-StandardRefractoryBL42DhA-TexturedRefractoryHerringboneBL42DhSA-StandardRefractoryHerringboneThisbricklineraddsatouchofstyletoyourdirect-ventfireplace.Completeinstallationinstructionsincludedinthismanual.

REPLACEMENT PARTSContinued

Page 18: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com 118197-01D18

ILLUSTRATED PARTS BREAkDOWN

MODELS (V)DVC36(B)(h) AND (V)DVC42(B)(h)

6

7

10

17

18

13

2

12 19

8

1

4

11

9

14

3

16

5

15

Page 19: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

www.fmiproducts.com118197-01D 19

PARTS LISTMODELS (V)DVC36(B)(h) AND (V)DVC42(B)(h)Thislistcontainsreplaceablepartsusedinyourfireplace.Whenorderingparts,followtheinstructionslistedunderReplacement Parts onpage16ofthismanual.

REFRACTORY BRICK PANELS

PART NO. DESCRIPTION qTY110989-02 Left Refractory Brick Panel • 1111215-02 Left Refractory Brick Panel • 1111299-02 Left Refractory Brick Panel • 1111302-02 Left Refractory Brick Panel • 1110989-01 Left Refractory Brick Panel • 1111215-01 Left Refractory Brick Panel • 1111299-01 Left Refractory Brick Panel • 1111302-01 Left Refractory Brick Panel • 1110991-02 Rear Refractory Brick Panel • 1111217-02 Rear Refractory Brick Panel • 1111297-02 Rear Refractory Brick Panel • 1111330-02 Rear Refractory Brick Panel • 1110991-01 Rear Refractory Brick Panel • 1111217-01 Rear Refractory Brick Panel • 1111297-01 Rear Refractory Brick Panel • 1111300-01 Rear Refractory Brick Panel • 1110990-02 Right Refractory Brick Panel • 1

111216-02 Right Refractory Brick Panel • 1

111298-02 Right Refractory Brick Panel • 1

111301-02 Right Refractory Brick Panel • 1

110990-01 Right Refractory Brick Panel • 1

111216-01 Right Refractory Brick Panel • 1

111298-01 Right Refractory Brick Panel • 1

111301-01 Right Refractory Brick Panel • 1

KEY NO. (V)DVC36(B)(h) (V)DVC42(B)(h) DESCRIPTION qTY.

1 ** ** Firebox Assembly 12 ** ** Face Weldment 13 108010-01 108328-01 Door Assembly 1

— 108328-02 Door Assembly (V Models Only) 14 108011-01 108331-01 Top Louver Assembly 15 108011-02 108331-02 Bottom Louver Assembly 16 ** ** Fireplace Top 17 ** ** Fireplace Top Insulation 18 ** ** Fireplace Surround 19 109082-01 109082-02 Heat Shield 1

10 24460 24460 Gas Conduit Assembly 1

11 See Below See Below Left Refractory Brick Panel 1

12 See Below See Below Rear Refractory Brick Panel 1

13 See Below See Below Right Refractory Brick Panel 114 108719-01 108455-01 Screen Rod 115 12105 107840-01 Screen 216 11418 11418 Push-On Nut 217 14123 14123 Strain Relief 118 21171 21171 Gas Knock-Out Cover 219 24353 24353 Handy Box Assembly 1

PARTS AVAILABLE - NOT SHOWN27253 27253 Notice Label 155240 55240 Vent Label 1

** Part not available for field replacement.

DV

C36

B

DV

C42

BD

VC

42h

VD

VC

36B

VD

VC

36h

VD

VC

42B

VD

VC

42h

DV

C36

h

Page 20: DIRECT-VENT CHASSIS OWNER’S INSTALLATION …lib.store.yahoo.net/lib/elitedeals/vhdvc36and46versafirechassismanu… · Installation and service must be performed by a quali-fied

118197-01Rev. D03/10

WARRANTykEEP THIS WARRANTy

FMI PRODUCTS, LLC LIMITED WARRANTIESNew Products

Standard Warranty:FMIPRODUCTS,LLCwarrantsthisnewproductandanypartsthereoftobefreefromdefectsinmaterialandworkmanshipforaperiodoftwo(2)yearsfromthedateoffirstpurchasefromanauthorizeddealerprovidedtheproducthasbeeninstalled,maintainedandoperatedinaccordancewithFMIPRODUCTS,LLC’swarningsandinstructions.Forproductspurchasedforcommercial,industrialorrentalusage,thiswarrantyislimitedto90daysfromthedateoffirstpurchase.

Factory Reconditioned ProductsLimited Warranty:FMIPRODUCTS,LLCwarrantsfactoryreconditionedproductsandanypartsthereoftobefreefromdefectsinmaterialandworkmanshipfor30daysfromthedateoffirstpurchasefromanauthorizeddealerprovidedtheproducthasbeeninstalled,maintainedandoperatedinaccordancewithFMIPRODUCTS,LLC’swarningsandinstructions.

Terms Common to All WarrantiesThefollowingtermsapplytoalloftheabovewarranties:Alwaysspecifymodelnumberandserialnumberwhencontactingthemanufacturer.Tomakeaclaimunderthiswarrantythebillofsaleorotherproofofpurchasemustbepresented.Thiswarrantyisextendedonlytotheoriginalretailpurchaserwhenpurchasedfromanauthorizeddealer,andonlywheninstalledbyaqualifiedinstallerinaccordancewithalllocalcodesandinstructionsfurnishedwiththisproduct.Thiswarrantycoversthecostofpart(s)requiredtorestorethisproducttoproperoperatingconditionandanallowanceforlaborwhenprovidedbyaFMIPRODUCTS,LLCAuthorizedServiceCenteroraproviderapprovedbyFMIPRODUCTS,LLC.Warrantypartsmustbeobtainedthroughauthorizeddealersofthisproductand/orFMIPRODUCTS,LLCwhowillprovideoriginalfactoryreplacementparts.Failuretouseoriginalfactoryreplacementpartsvoidsthiswarranty.Travel,handling,transportation,diagnostic,material,laborandincidentalcostsassociatedwithwarrantyrepairs,unlessexpresslycoveredbythiswarranty,arenotreimbursableunderthiswarrantyandaretheresponsibilityoftheowner.Excludedfromthiswarrantyareproductsorpartsthatfailorbecomedamagedduetomisuse,accidents,improperinstallation,lackofpropermaintenance,tampering,oralteration(s).ThisisFMIPRODUCTS,LLC’sexclusivewarranty,andtothefullextentallowedbylaw;thisexpresswarrantyexcludesanyandallotherwarranties,expressorimplied,writtenorverbalandlimitsthedurationofanyandallimpliedwarranties,includingwarran-tiesofmerchantabilityandfitnessforaparticularpurposetotwo(2)yearsonnewproductsand30daysonfactoryreconditionedproductsfromthedateoffirstpurchase.FMIPRODUCTS,LLCmakesnootherwarrantiesregardingthisproduct.FMIPRODUCTS,LLC’sliabilityislimitedtothepurchasepriceoftheproduct,andFMIPRODUCTS,LLCshallnotbeliableforanyotherdamageswhatsoeverunderanycircumstancesincludingindirect,incidental,orconsequentialdamages.Somestatesdonotallowlimitationsonhowlonganimpliedwarrantylastsortheexclusionorlimitationofincidentalorconse-quentialdamages,sotheabovelimitationorexclusionmaynotapplytoyou.Thiswarrantygivesyouspecificlegalrights,andyoumayalsohaveotherrightswhichvaryfromstatetostate.Forinformationaboutthiswarrantycontact:

Model (located on product or identification tag) _____________________________

Serial No. (located on product or identification tag) __________________________

Date Purchased __________________________

Keep receipt for warranty verification.

2701 S. Harbor Blvd.Santa Ana, CA 92704

1-866-328-4537www.fmiproducts.com