Wired Split Solution

LGG160K Single Phase Prepayment Meter

LGG540K Customer Interface Unit

User Manual

DIN-

Page 2: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

2

LGG160K Single Phase Wired Split Solution ................................................................. 4

1. Summary .......................................................................................................................... 5

1.1 Main Application & Scope ................................ ................................ ................... 5

1.2 Reference Standard ................................ ................................ ............................... 5

1.3 Functions & Features ................................ ................................ ............................ 5

1.4 Technical Index ................................ ................................ ................................ ..... 6

1.4.1 Meter Type Specifications ................................ ................................ .................... 6

1.4.2 Electrical Specifications ................................ ................................ ....................... 6

1.4.3 Climate and Environment Condition ................................ ................................ .... 7

2. Main Functions ............................................................................................................... 8

2.1 Metering Function ................................ ................................ ................................ 8

2.2 Demand Function ................................ ................................ ................................ . 8

2.3 Instantaneous Measuring Parameter ................................ ................................ ..... 8

2.4 Display Function ................................ ................................ ................................ ... 8

2.4.1 Display Performance ................................ ................................ ............................ 8

2.4.2 Display Information ................................ ................................ .............................. 8

2.4.3 Display Mode ................................ ................................ ................................ ..... 10

2.4.4 Running Status Display ................................ ................................ ...................... 12

2.5 Prepayment Function ................................ ................................ .......................... 13

2.5.1 Charge Token ................................ ................................ ................................ ...... 13

2.5.2 Management Token................................ ................................ ............................. 13

2.5.3 Balance Alarm ................................ ................................ ................................ .... 14

2.5.4 Shortcut Key Function ................................ ................................ ........................ 15

2.5.5 Emergency Overdraft Function ................................ ................................ .......... 17

2.5.6 Friendly Mode ................................ ................................ ................................ .... 17

2.5.7 Prepaid Mode switchover ................................ ................................ ................... 18

2.6 Split Prepayment ................................ ................................ ................................ . 18

2.6.1 CIU/UIU Pairing ................................ ................................ ................................ . 18

2.6.2 CIU Operating Failed Prompt ................................ ................................ ............. 18

2.6.3 CIU Operating Successful Prompt ................................ ................................ ...... 19

2.7 Billing Function ................................ ................................ ................................ .. 19

2.7.1 Monthly Billing Function ................................ ................................ ................... 19

2.7.2 Daily Billing Function ................................ ................................ ........................ 19

2.8 Relay Operation ................................ ................................ ................................ .. 19

2.9 Event Function ................................ ................................ ................................ .... 21

2.10 Alarm Function ................................ ................................ ................................ ... 21

2.11 Communication Function ................................ ................................ ................... 22

2.11.1 Optical Communication ................................ ................................ ...................... 22

2.11.2 Uplink Remote Communication (Reserved Function) ................................ ........ 22

Table of Contents

www.ruvick.com

User manual

Page 3: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

3

2.11.3 Downlink MBUS Communication ................................ ................................ ..... 22

2.12 Input output Function ................................ ................................ ......................... 22

2.12.1 Input Function................................ ................................ ................................ ..... 22

2.12.2 Output Function ................................ ................................ ................................ .. 23

3. Appearance & Installation ......................................................................................... 24

3.1 Outline Size ................................ ................................ ................................ ........ 24

3.2 Installation Size ................................ ................................ ................................ .. 25

3.3 Terminal Block Size ................................ ................................ ........................... 26

3.4 Wiring Diagram ................................ ................................ ................................ .. 26

3.5 Attention Matters ................................ ................................ ................................ 27

3.6 Installation Instructions ................................ ................................ ...................... 27

4. Analysis&Elimination Of Common Malfunctions ................................................ 28

5. Transportation & Storage .......................................................................................... 29

6. Warranty Services ........................................................................................................ 29

www.ruvick.com

User manual

Page 4: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

4

LGG160K Single Phase Wired Split Solution

Note: Please subject to actual products.

www.ruvick.com

User manual

Page 5: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

5

1.1 Main Application & Scope

LGG160K single phase prepayment meter (Hereinafter referred to as meter) uses large scale integrated circuit,

application of digital sampling technology and SMT technology, has the functions of metering, billing,

communication, prepayment etc. which is mainly usedto low-voltage power users (residential and commercial) for

energy data acquisition, processing, storage and payment.

1.2 Reference Standard

The meter performance index conformed to the following technical requirements:

Chart1 Reference standard table

IEC 62052-11-2003 Electricity metering equipment(a.c.) – General requirements, tests, and test conditions– Part 11: Metering equipment

IEC 62053-21-2003 Electricity metering equipment(a.c.) – Particular requirements – Part 21: Static meters for active energy (class 1 and 2)

IEC 62053-23-2003 Electricity metering equipment(a.c.) – Particular requirements – Part 23: Static meters for reactive energy (class 1 and 2)

IEC 62056-21-2002 Electricity metering – Data exchange for meter reading, tariff and load control – Part 21: Direct local data exchange

IEC 62056-46-2006 Electricity metering – Data exchange for meter reading, tariff and load control –Part 46: Data link layer using HDLC protocol

IEC 62056-53-2006 Electricity metering – Data exchange for meter reading, tariff and load control –Part 53: COSEM application layer

IEC 62056-61-2006 Electricity metering – Data exchange for meter reading, tariff and load control –Part 61: Object identification system (OBIS)

IEC 62055-31-2005 Electricity metering– Payments systems– Part 31: Particular requirements Static payment meters for active energy (classes 1 and 2)

IEC 62055-41-2007 Electricity Metering – Payment Systems – Part 41: Standard TransferSpecification – Application layer protocol for one–way token carrier s s sy tem

IEC 62055-51-2007 Electricity Metering – Payment Systems – Part 51: Standard Transfer Specification – Physical layer protocol for one–way numeric and magnetic card token carriers

1.3 Functions & Features

➢ Forward and reverse active energy and storage functions;

➢ Load control functions (Disconnect and Connect);

➢ Supporting 13-month monthly billing and captured objects can be configured by communication;

Standard No. Standard description

1. Summary

www.ruvick.com

User manual

Page 6: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

6

➢ Instantaneous parameter measurement functions such as current, voltage, power, power factor, demand etc;

➢ DLMS/COSEM communication protocol, for good connectivity and strong compatibility;

➢ Power-off display function, can display back by pressing key button;

➢ Many convenient user interfaces such as optical communication port, LCD display, keybutton and keypad;

➢ Supporting uplink remote communication and the module can be customizable such as GPRS/3G/4G/G3-PLC/PRIME-PLC/Mesh-RF and so on, which can be suitable for different installation site (Reserved function);

➢ The split type supports CIU/UIU communication port, which is convenient for users to charge and query in real time;

➢ The split type supports mainstream communication wired module like MBUS and is convenient for installing on site;

➢ High security mechanism conformed with STS prepayment standard;

➢ Supporting friendly control and various agile friendly mode like holiday, weekend and specified time;

➢ Automatic software calibration technology for simple, fast, high accuracy calibration;

➢ New idea meter structure, which is novel, beautiful and applicable.

1.4 Technical Index

1.4.1 Meter Type Specifications

Chart2 Meter Type Specifications

Meter Type Connectio

n

Reference voltage

(V)

Reference current

(A)

Active pulse constant(imp/

kWh)

Reactive pulse

constant(imp/kvarh)

Accuracy class

LGG160K 1P2W 220/230/240 5(60) 1000 1000

Active class1 Reactive class2

5(80) 1000 1000 Active class1 Reactive class2

Note: Please subject to actual nameplate.

1.4.2 Electrical Specifications

Chart3 Electrical Specifications

Normal working voltage range 0.7Un~1.2Un

Limit working voltage range 0.6Un~1.3Un

Rated operating frequency 50Hz

Starting current 0.4%Ib

No load condition Not more than 1 pulse output within no load condition period

Insulation protection level 2

Voltage circuit power consumption ≤1.5W & 5 VA

Current circuit power consumption <2 VA

Clock battery The battery can be replaced, its voltage is 3.6V

Clock battery capacity ≥1200mAh

www.ruvick.com

User manual

Page 7: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

7

Clock accuracy (daily error) ≤0.5s/d (Clock change rate 0.15s/°C )

Data retention time after power off ≥15year

Relay Up to 10000 times operating limit under rated working current

conditions; Up to 100000 times operating limit under no-load conditions;

1.4.3 Climate and Environment Condition

Chart4 Climate and Environment Condition

Normal working temperature -25℃~55℃

Limit working temperature -40℃~75℃

Storage and transportation temperature -40℃~75℃

Storage and working humidity ≤95%RH

Dust and water proof class IP54

www.ruvick.com

User manual

Page 8: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

8

2.1 Metering Function

Forward and reverse active energy metering function, metering mode:

➢ Total forward active energy:|+A| = |+A|+|-A|;

➢ Reverse active energy:|-A| = |-A|;

2.2 Demand Function

Forward and reverse active demand metering function, supports block and slide mode, slide period and slide

number can be configured. the default slideperiod is 15 minutes, the slide number is one.

2.3 Instantaneous Measuring Parameter

Instantaneous measuring parameter function, including: voltage, current, power factor, active power, apparent

power, power grid frequency etc.

2.4 Display Function

2.4.1 Display Performance

➢ The size of LCD screen is 60mm×30mm ;the size of main numeral is 5×10mm;

➢ The material of LCD is HTN, the working temperature scope of which is -40℃~+80℃;

➢ The LCD has high contrast ratio and the drive mode of which is 1/4 DUTY,1/3 BIAS;

➢ The best visual angle of LCD is 6 o'clock;

➢ The polaroid of LCD has anti-ultraviolet function.

2.4.2 Display Information

Figure1 LCD full screen display of meter

2. Main Functions

www.ruvick.com

User manual

Page 9: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

9

Figure2 LCD full screen display of CIU/UIU

Introduction of LCD display symbol

Chart5 LCD display symbol

Data display area includesenergy, instantaneous parameters and time etc.

According to the OBIS definition of IEC62056-61, the CDE will be displayed and the historical data which adds F number in the OBIS display area.

Unit display area includes energy, instantaneous parameters, such as: kWh\kvarh\kVh\V\A\Hz etc.

GPRS signal intensity symbol (Reserved symbol)

No battery or battery is low

Communication symbol

Alarm symbol

Tamper symbol

Disconnected relay symbol

Connected relay symbol

Credit symbol means currency symbol or energy balance symbol.

LCD Display Symbol Symbol Description

www.ruvick.com

User manual

Page 10: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

10

Days symbol refers to remaining days

Multi TOU tariff and step tariff symbol (Reserved symbol)

Four quadrant symbols, +P and –P mean active power plus and minus; +Q and –Q mean reactive power plus and minus;

Split phase voltage and split phase current reverse symbols, L2 and L3 are reserved for three phase meter

Successful symbol

Failed symbol

Special alarm symbol

2.4.3 Display Mode

➢ Scroll display mode: The default scroll display cycle is 6 seconds, scroll display contents are as following

chart:

Chart6 Default scroll display table

1 C.60.0 Balance

2 C.60.9 Remaining days

3 35.7.0 Instantaneous active power

4 1.30.0.1 The consumed energy last day

5 1.29.0.1 The consumed energy last month

6 1.8.0 Total active energy

7 C.60.1 Total charge amount

➢ Key display mode: It supports single and multiple lists, switches through the key button. The type of key

operation is shown as the following chart. It will return to scroll display mode when without operation after 64

seconds.

Chart7 Key operation type

No. OBIS display Description

www.ruvick.com

User manual

Page 11: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

11

No OBIS display Description

Key operation Key holding time Operation description

Short press Less than 2 seconds Turn over the current screen by short press, and return to scroll display mode after 64seconds without operation.

Short long press

More than 2 seconds but less than 4 seconds

Turn over display list by short long press, and need to release the key when displays “PAGING”. Return to automatic scroll display mode after 3 minutes without operation.

Long press More than 4 seconds but less than 6 seconds

Retrun to automatic scroll display list by long press, and need to release the key when displays “BACING”

Medium long press

More than 6 seconds but less than 8 seconds

Cancel temporary alarm by medium long press (If the function is actived), and need to release the key when display “CLuuArn”.

Overlong press More than 8 seconds Quitting by long press, and return to automatic scroll display list

Here is the default key display table:

Chart8 Default key display table

1 C.60.7 Overload Threshold value

2 C.60.39 Low credit alarm value (Green to Red)

3 C.60.40 Low credit alarm value (Red to Red Flash)

4 C.7.21 Total power offtimes

5 C.1.0 Meter Serial Number

6 1.29.0.1 The consumed energy last month

7 12.35.0 Overvoltage threshold value

8 12.31.0 Under voltage threshold value

9 32.7.0 Instantaneous voltage

10 31.7.0 Instantaneous phase current

11 14.7.0 Instantaneous frequency

12 C.53.45 Accumulated power on time within 1 month

13 C.51.4 LCD full screen test

www.ruvick.com

User manual

Page 12: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

12

➢ Power off mode: The meter works relying on battery and will display content for 6 seconds when the meter

power off, it will be LCD display when pressing key button, the display contents are the same as the scroll

display mode. The LCD display will be closed automatically after 64 seconds without any operation.

2.4.4 Running Status Display

The meter will take real time function check, operation check and error self-check, meantime it displays check status on the LCD.

Chart9 Running status display table

Status name Status Symbol Status description

Battery Status

Battery Status symbol, the one battery situation: the symbol is showed when the battery is low or no battery;

Voltage and Reversed Current indicator

Lx will be displayed if current phase voltage is ok, Lx flickers if actual phase voltage is high or low;

The reversed symbol will be displayed if actual phase current is reversed.

Smiling face

This symbol will be displayed if operation is successful.

Crying face

This symbol will be displayed if operation is failed.

Paging PAGING The meter’s display list is paging now.

Backing BACKING The meter’s display list is paging back.

Energy clearance CLr-Eng This symbol will be displayed for 2 seconds in the main display area if energy clearance is occurred.

Demand clearance CLr-Ded This symbol will be displayed for 2 seconds in the main display area if demand clearance is occurred.

Event clearance CLr-Ent This symbol will be displayed for 2 seconds in the main display area if event clearance is occurred.

Load clearance CLr-Lod This symbol will be displayed for 2 seconds in the main display area if load clearance is occurred.

Billing clearance CLr-BIL This symbol will be displayed for 2 seconds in the main display area if billing clearance is occurred.

Total clearance CLr-ALL This symbol will be displayed for 2 seconds in the main display area if total clearance is occurred.

EEPROM initialization E2P-Int This symbol will be displayed in the main display area when the EEPROM initialization is occurred.

EEPROM fault E2P-Err This symbol will be displayed in the main display area until meter reset to restart when the EEPROM fault is occurred during power up process.

EEPROM data error E2P-VEr This symbol will be displayed for 2 seconds in the main display area if EEPROM data is error during power up process.

www.ruvick.com

User manual

Page 13: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

13

Charge result Displaying

2.5 Prepayment Function

2.5.1 Charge Token

After charging, user will acquire20 digits TOKEN code, then key in 20 digits TOKEN code correctly through the keypad. Charging results will be displayed on LCD screen as the following chart:

Chart10 Charge information display

Charge successful

Wrong TOKEN

Used TOKEN

ExpiredTOKEN

ExpiredKey

Over Charge

Notes: Depands on different LCD, the display place of contents is different, please subject to real object.

2.5.2 Management Token

Management token: TOKENs are under STS encryption with time and corresponding management informations, which can only be operated to the matched meter. Such as: set up maximum power, clear balance, change key, clear tamper etc.

Change key procedure: The key only can be changed when two TOKEN sinputed at the same time. Users must input two TOKENs within the 120 seconds.

Chart11 Change key operation display

www.ruvick.com

User manual

Page 14: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

14

The first TOKEN is correct

Changing keysuccessfully

2.5.3 Balance Alarm

The meter has balance alarm function that to remind users to charge and avoid power off, the alarm mode is divided into LED light alarm and sound alarm.

LED light alarm:

Chart12 LED light alarm

Green light The balance is sufficient, remaining days are more than 3 days.

Red light The balance is less, remaining days are less than 3 days, but more than 1.5 days.

Red light Flashing The balance is insufficient, remaining days are less than1.5 days

Temporary alarm:

The buzzer sounds if the meter is arrearage,Users can manually cancel temporary alarm by key in “612”.

The sound alarm will be closed automaticly during 18:00~06:00 to avoid disturbing the normal rest of users.

Chart13 Cancelling temporary alarm

Cancel successfully

Cancel rejected

Change key result Display

Status of LED light Description

Operation Instruction Diplay

www.ruvick.com

User manual

Page 15: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

15

2.5.4 Shortcut Key Function

The meter has various of shortcut keys for users to acquire the meter’s information. Users can input 3 digits of shortcut keys, the detailed functions of which are shown as the following chart:

Chart14 Query short code table

800 Total active energy 801 Balance

802 Current date 803 Current time

804 Meter No. 805 SGC No.

806 Relay operation reason 807 Tamper status

808 Remaining days 809 Tariff No.

810 Overdraft amount 813 Total active energy last day

814 Total consumed energy in current month

816 Last charged date and time 817 Last charge amount

818 Logout Token 819 Total power off times

820 Accumulated charge amount 821 Accumulated total active energy of last month

822 Accumulated total active energy of latest second month

823 Accumulated total active energy of latest third month

824 Accumulated total active energy of latest 4th month

825 Accumulated total active energy of latest 5th month

826 Accumulated total active energy of latest 6th month

827 Accumulated total active energy of latest 7th month

828 Accumulated total active energy of latest 8th month

829 Accumulated total active energy of latest 9th month

830 Accumulated total active energy of latest 10th month

831 Accumulated total active energy of latest 11th month

832 Accumulated total active energy of latest 12th month

841 Last charge TOKEN 842 Charge TOKEN of latest second time

843 Charge TOKEN of latest third time 844 Charge TOKEN of latest 4th time

845 Charge TOKEN of latest 5th time 846 Charge TOKEN of latest 6th time

847 Charge TOKEN of latest 7th time 848 Charge TOKEN of latest 8th time

Short code No.

Function description Short code No.

Function description

www.ruvick.com

User manual

Page 16: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

16

849 Charge TOKEN of latest 9th time 850 Charge TOKEN of latest 10th time

866 Over voltage threshold 867 Under voltage threshold

868 Maximum current threshold 869 Maximum power threshold

870 Phase A voltage 873 Version of key

874 Version of firmware 875 Key type

877 Accumulated meter running time 880 Phase line current

884 Total instantaneous active power 888 Total power factor

889 Power grid frequency 900 The consumed energy of last day

910 Maximum demand of current month 911 Date and time of maximum demand of current month

921 The consumed energy of last month 922 The consumed energy of latest second month

923 The consumed energy of latest third month

924 The consumed energy of latest 4th month

925 The consumed energy of latest 5th month

926 The consumed energy of latest 6th month

927 The consumed energy of latest 7th month

928 The consumed energy of latest 8th month

929 The consumed energy of latest 9th month

930 The consumed energy of latest 10th month

931 The consumed energy of latest 11th month

932 The consumed energy of latest 12th month

954 Total tamper times 955 Total demand manual reset times

The above is the query short code list, other unmarked short codes are kept and will be released according to users’ needs.

Chart15 Executing short code table

611 Executing emergency overdraft 612 Executing cancellation of temporary alarm

613 Executing cancellation of sound alarm

614 Executingactive meter cover open and terminal cover detecting

620 Executing pairing operation

If corresponding short codes not exist, the following information will be displayed:

Chart16 Short codes non-existent

Short code No.

Function description Short code No.

Function description

www.ruvick.com

User manual

Page 17: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

17

Short codes non-existent

2.5.5 Emergency Overdraft Function

The relay will be disconnected when the current balance of meter is 0, and users couldn’t use electricity unless recharging. For reasons that users can’t recharging, the emergency overdraft function can be turned on so that users can use electricity. The emergency overdraft function is choosable and takes effect only by permision.

Under emergency overdraft mode, the meter balance continues to be accumulated on negative value, and the relay will be disconnected again when the meter balance plus overdraft amount is less than or equal to zero. Emergency overdraft function can only be used 1 time, and recovered until the next recharging, the overdraft amount will be automatically deducted at the next time recharging.

Chart17 Operation prompt of emergency overdraft

Emergency overdraft successful

Overdraft function is activated

Overdraft rejected

Arrears after overdraft

2.5.6 Friendly Mode

The meter has two control modes: Normal mode and friendly mode. Friendly mode is choosable and takes effect only when started. Under friendly mode, the relay can not be disconnected even if current meter balance is insufficient at specified holidays or someday or some time (such as at night) in order to ensure the users basic electricity usage, but the balance continues to be accumulated on negative value.

Friendly holiday: The electricity will be friendly interruption of power supply at specified holidays, the default holidays are 20 days.

Operation Instruction Displaying

Operation Instruction Displaying

www.ruvick.com

User manual

Page 18: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

18

Friendly weekend: The electricity will be friendly interruption of power supplyat some day of a week, the default is off.

Friendly time: The electricity will be friendly interruption of power supplyat some time of a day, the default time is from 18:00~6:00.

Note: Friendly mode is closed normally.

2.5.7 Prepaid Mode switchover

The meter supports changing over between prepaid mode and post-paid mode by communication, and the prepaid

mode can be activated and closed. The remaining balance of meter will not be deducted and the alarm and

disconnection will not work if the balance is insufficient or in arrear when the prepaid mode is closed. There will be

a billing record when the mode is switched.

2.6 Split Prepayment

2.6.1 CIU/UIU Pairing

The meter and CIU are different devices, they can communicate normally only when they are paired.

Inputting short code 620 on CIU first, pressing enter key, the “step1” will be displayed on LCD, then inputting the meter serial No. and pressing enter key, the “step2” will be displayed on LCD, then inputting the pairing code (password:123456) and pressing enter key. The meter and CIU are pairingwhen the “ConNect” is displaying on the CIU.

The “SS-007” will bedisplayed on CIU means pairing is successful; the “EE-007” means pairing is failed.

2.6.2 CIU Operating Failed Prompt

Chart18 CIU operating failed Prompt

EE--001 When inputting the recharging

mode, Token subclass is error

Token issuing is incorrect, please contact with

the vender or utility.

EE--002 The Token is not the key

changingToken

Illegal input is normal, no need to deal with;

otherwise, please contact with the vender or

utility.

EE--003 The key can not turn into DITK To change the initial key is not allowed on site,

itis correct prompt.

EE--004 The key can not turn into general

key To change the general key is not allowed on

site, itis correct prompt.

EE--005 The test of connecting relay is failed

When the relay is disconnected, the test of

connecting relay is not supported, itis correct

prompt.

EE--006 Changing key is overtime please try to ensure that two Token of changing

key arefinished within 120 seconds

EE--007 Pairing or cancelling pairing is failed Please ensure that the input meter serial

number and the pairing password are correct

Error No. Specied analysis and description Solving methods

www.ruvick.com

User manual

Page 19: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

19

2.6.3 CIU Operating Successful Prompt

Chart19 CIU operated successful prompt

SS--001 Changing key is successful

SS--002 Clearing tamper is successful

SS--003 Prepaid mode changing into post-paid mode is

successful

SS--004 Postpaid mode changing into prepaid mode is

successful

SS--005 Relay test is successful

SS--006 All tests are successful

SS--007 Pairing is successful

SS--008 Data synchronization is successful between meter and

CIU/UIU

SS--009 Enabling meter cover and terminal cover detection is

successful

2.7 Billing Function

2.7.1 Monthly Billing Function

The monthly billing function stores and processes the data of the capture members according to the billing time.

The billing time uses standard time format, it can be changed by communication according to actual need, and the billing time has a day register andhour register for changing. Default register of year\month\week are 0xff, and another default registers are 0; The default billing time is 0:00 on 1st day every month, which means the billing time is on the 0:00 on 1st day of every month and every year.

2.7.2 Daily Billing Function

The daily billing function stores and processes the data of the capture members according to the daily billing time.

The daily billing time uses standard time format, it can be changed by communication according to actual need, and the daily billing time has an hour register and minute register for changing. The default register of year\month\day is 0xff, and another default registers are 0; the default daily billing time is 0:00, which means the daily billing time is on the0:00 on everyday of every month and everyyear.

2.8 Relay Operation

The relay operation has three kinds: remote operation, local operation and manual operation. The meter can record the reason of the last relay operation, and the specific operation reasons are shown in below chart:

Chart20 Reason of the relay operation

Prompt No. Specied analysis and description

www.ruvick.com

User manual

Page 20: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

20

Normal connecting Connected 0

STS test connecting Connected 1

Remote connecting Connected 2

Manufacture mode connecting Connected 3

Manual connecting Connected 4

Friendly period connecting Connected 5

Low credit disconnecting Disconnected 6

Out of emergency overdraft disconnecting Disconnected 7

Over power disconnecting Disconnected 8

STS test disconnecting Disconnected 9

Meter cover removal disconnecting Disconnected 10

Terminal cover removal disconnecting Disconnected 11

Remote disconnecting Disconnected 12

Overcurrent disconnecting Disconnected 13

Overvoltage disconnecting Disconnected 14

Long time without recharging disconnecting Disconnected 15

Low voltage disconnecting Disconnected 16

Current reverse disconnecting Disconnected 17

Relay malfunction disconnecting Disconnected 18

Normal power-off disconnecting Disconnected 19

Meter malfunction disconnecting Disconnected 20

Manual disconnecting Disconnected 21

Module cover removal disconnecting Disconnected 22

Operation reason Relay state Operation No. Operation description

www.ruvick.com

User manual

Page 21: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

21

Meter box removal disconnecting Disconnected 23

Arrearage disconnecting Disconnected 24

Note: some relay operation is reserved, please subject to actual relay operation.

2.9 Event Function

The events can be divided into: standard events, fraud events, control events, recharge events, power grid events, etc..

Standard events: including poweroff, power on, clock changing, battery is low, manual demand reset, meter malfunction, meter programming etc. 100 standard events records;

Fraud events: including meter cover removal, terminal cover removal, module cover removal, strong magnetic interference, etc. 225 fraud events records;

Control events: including relay disconnecting and connecting events, 100 control events records;

Recharge events: including recharge account and recharge Token, 20 recharge events records;

Grid events: including overvoltage, undervoltage, reversing, bypass, overpower, over current etc. 100 grid events records;

2.10 Alarm Function

The meter has alarm function, alarm prompt by the alarm light (LED), buzzer, liquid crystal alarm sign and so on. The alarms are listed as the following chart.

Chart21 Alarm table

Alarm light Lightening The alarm light is on by default if the following events occured: overpower, total current reversing, module cover removal, strong magnetic interference, terminal cover removal, meter cover removal.it can also be configured for other events;

Buzzer Sound The buzzer sounds by default if the following events occurred: arrearage etc.it can also be configured as other events;

Triangle alarm symbol

The symbol is displayed by default if the following events occurred: overpower, total current reversing, module cover removal, strong magnetic interference, terminal cover removal, meter cover removal. it can also be configured for other events;

Tampering alarm symbol

The symbol is displayed by default if the following events occured: total current reversing, module cover removal, strong magnetic interference, terminal cover removal, meter cover removal. it can also be configured as other events;

Alarm symbol of subscript I

The symbol is displayed by default if the following eventsoccured: meter cover removal; it can also be configured as other events;

Alarm symbol of subscript II

The symbol is displayed by default if the following eventsoccured: terminal cover removal; it can also be

Alarm way Alarm prompt Alarm description

www.ruvick.com

User manual

Page 22: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

22

configured as other events;

Alarm symbol of subscript III

The symbol is displayed by default if the following events occured: overpower; it can also be configured as other events;

Alarm symbol of subscript IV

The symbol is displayed by default if the following events occured: strong magnetic interference; it can also be configured as other events;

Alarm symbol of subscript V

The symbol is displayed by default if the following events occured: module cover removal; it can also be configured as other events;

2.11 Communication Function

2.11.1 Optical Communication

Following IEC62056-21 optical communication physical interface standard.

Conforming to the standard of DLMS (E mode)

The initial baud rate is 300bps, 7 data bits, 1 even bit; 19200bps after successful handshakeing, 8 data

bits, without check bit.

The users can read and modifythe parameters of the meter by PC software or HHU

2.11.2 Uplink Remote Communication (Reserved Function)

The communication way is optional.

Baud rate: 9600bps, 8 data bits, no check bit.

Conforming to DLMS/COSEM protocol.

Communication module is selectable, supporting GPRS/3G/4G/G3-PLC/PRIME-PLC/Mesh-RF etc.

Supporting spot module real-time replacement, real-time switching of automatic registration.

2.11.3 Downlink MBUS Communication

The communication way is optional.

The communication way between energy meter and CIU/UIU is wired MBus.

The maximum communication cable size is 2.52mm

The longest communication distance is 150 meters.

2.12 Input output Function

2.12.1 Input Function

The meter support input function which is shown as the following chart:

Chart22 Input function

1 23 and 24 To communicate with the CIU/UIU

No. Auxiliary Port Description

www.ruvick.com

User manual

Page 23: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

23

2.12.2 Output Function

The meter support Output function, such as the auxiliary port 21 and 22 are for the multi function output. It can be

configured by communication to multi signal output: Active pulse output, Reactive pulse output, Pulse per second

output etc.

The Pulse LED on the CIU is designing for showing the consumption ratio.

www.ruvick.com

User manual

Page 24: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

24

3.1 Outline Size

Figure3 Outline size of meter

Figure4 Outline size of CIU/UIU

Note:

Outline size of meter:220mm×130mm×72mm.

Outline size of CIU/UIU:147mm×82mm×35mm.

3. Appearance & Installation

www.ruvick.com

User manual

Page 25: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

25

3.2 Installation Size

Figure5 Installation size of meter

Figure6 Installation size of CIU/UIU

Note:

Installation size of meter:105mm×155mm or 105mm×138mm.

www.ruvick.com

User manual

Page 26: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

26

3.3 Terminal Block Size

Figure7 Terminal block size

Aperture size:Main wiring aperture:9mm; Auxiliary wiring aperture:3mm.

3.4 Wiring Diagram

Figure8 Wiring diagram of main terminal

Figure9 Meter and CIU/UIU wiring diagram of auxiliary terminal

www.ruvick.com

User manual

Page 27: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

27

3.5 Attention Matters

Please contact the supplier asap if the meters have obvious damage mark caused by violent impact or dropping when the box is opened.

After getting out from the packing box, the metershould be placed on flat and safeplane, front up, stacked upless than 5 layers. The meter should be wrapped back into the original packing box if it is not installed for usage within a short period.

Please contact the supplierif product type or appearance of meterin the original packing box does not match. Please contact the supplier asap and do not installor power on if the internal packing orexternal cover damaged when the meter getting out from packing box. Please check the lead sealing of both sides is OK or not, for those meters lack of or without lead sealing, do not install for usage and please contact the supplier asap.

3.6 Installation Instructions

The installation of the meter requires experienced electrician or professional person, and make sure that this manual have been read. During installation, if the meters have obvious damage markscaused by violent impact or dropping, please do not install or power on and contact the supplier asap.

The meter should be installed in ventilated and dry place, making sure that the installation and usageare safe、reliable, the meter should be put into protection cabinet in case it may be damaged at foul or other unsafe place.

The meter has two upper hooks, 2 bottom installation holes, which can be fixed with M4 * 15 tapping screws. Making the holes ready on the bottom plate accordingto the back installation size figure, and the base should be fixed on object that is solid, fireproof and not easy to shake.

The meter should be wired correctly according to wiring figure. It is recommended to use copper wire or

copper connectors as the inlead of wiring terminal block, the screws of terminal block should be tightened to

avoid bad contact or fire caused by fever of thin lead wire.

Wiring according to the terminal mark, the main circuit: 1-4 for the entrance and exit lines of phase wire, 2-3

for the entrance and exit lines of neutral wire; Auxiliary terminal: 21-22 for the calibration pulse output

line;23-24 for the MBUS communication port.

www.ruvick.com

User manual

Page 28: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

28

Chart23 Malfunction diagnosis & analysis list

Unnormal communication

Communication addrss, baud rate, checkout bits are not the same as the communication requirements of meter

Configuring correct communication

parameter according to instructions

Unnormal display AC Voltage is ok or not, wiring confirms to wiring figure or not

Checking wiring and voltage of grid

Clock error is incorrect

Battery is low or not Changing battery

Instantaneous parameters are

incorrect

AC voltage is ok or not, wiring confirms to wiring figure or not

Checking wiring and voltage of grid

4. Analysis & Elimination of Common Malfunctions

Malfunction phenomenon

Reason analysis Elimination method Notes

www.ruvick.com

User manual

Page 29: DIN-“PAGING”. Return to automatic scroll display mode after 3 minutes without operation. Long press More than 4 seconds but less than 6 seconds Retrun to automatic scroll display

29

Products should not be impacted violently during transportation and sealing off, transported and stored according to the rule of JB/T 9329-1999《Basic environment conditions and test

methods of instrument meter》

Storing place should be clean, the general environmental temperature is -40℃~55℃, the

limit environmental temperatureis-40℃~70℃, the limit environmental temperature at cold area is

-45℃~70℃, relative humidity not more than 85%, and there are no enough harmful substances

which cause corrosion in the air.

Within 18 months from the delivery date, any quality problems, our company is responsible for free repair or replacement if the users find that the meters do not comply with the above features and technical data requirements under the lead sealing isintact.

5. Transportation & Storage

6. Warranty Services