DIMENSIONAMENTO SCAMBIATORI DI

CALORE A FASCIO TUBIERO

(CENNI)

Page 2: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

PREMESSA

1) NELLA PRATICA INDUSTRIALE SONO UTILIZZATI MOLTO FREQUENTEMENTE

SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO;

POICHE’ I CALCOLI RELATIVI A TALI SCAMBIATORI RISULTANO UN PO’ COMPLICATI,

CI LIMITEREMO ALL’ANALISI DEGLI SCAMBIATORI PIU’ SEMPLICI, OSSIA DEL TIPO

1:1 2) TECNICAMENTE SI POSSONO EFFETTUARE DUE TIPI DI CALCOLI:

CALCOLI DI VERIFICA: SI VERIFICA SE UNO SCAMBIATORE GIA’ ESISTENTE E’ IN

GRADO DI FUNZIONARE (OVVERO RIESCE A FARE LO SCAMBIO TERMICO

VOLUTO);

CALCOLI DI PROGETTO: LO SCAMBIATORE NON C’E’ E QUINDI VA PROGETTATO

EX-NOVO

NOI CI LIMITEREMO SOLO AI CALCOLI DI VERIFICA

3) VERIFICA DELLO SCAMBIATORE: COME GIA’ VISTO PER GLI HAIRPIN E’

NECESSARIA SIA LA VERIFICA TERMICA CHE LA VERIFICA IDRAULICA

Page 3: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

VERIFICA TERMICA DI UN FASCIO TUBIERO

SI CONFRONTA UD TEORICO CON UD SPERIMENTALE

UD TEORICO

UD SPERIMENTALE

lo scambiatore risulta verificato termicamente quando:

Page 4: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

CALCOLO UD TEORICO

CALCOLATO SU UNO DEI DUE FLUIDI

SUP. LATERALE DI UN TUBO * NUMERO TUBI

Page 5: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

CALCOLO UD SPERIMENTALE

IN QUESTO CASO hi SI RIFERISCE AL LATO TUBI MENTRE he AL LATO MANTELLO

hi

he

come si vede la formula lato mantello cambia

leggermente e si introduce ancora il diametro idraulico

equivalente

Page 6: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

CALCOLI LATO TUBO

CONVIENE RISCRIVERE ANCORA LA TABELLA

COSTANTI CALCOLATE ALLA T MEDIA PER OGNI FLUIDO

STESSI CRITERI PER STABILIRE L’INVIO DEI FLUIDI LATO TUBI/MANTELLO

Page 7: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

CALCOLI LATO MANTELLO

DIAMETRO IDRAULICO EQUIVALENTE Deq

NEL CASO DEL FASCIO TUBIERO, IL CALCOLO DEL Deq SI EFFETTUA IN

FUNZIONE DELLA DISPOSIZIONE DEI TUBI NEL FASCIO

PASSO QUADRATO PASSO TRIANGOLARE

y = passo dei tubi (distanza tra i centri di due tubi consecutivi)

c = luce di passaggio (spazio libero tra i tubi)

Page 8: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

CALCOLO Deq IN CASO DI PASSO QUADRATO

AREA DI PASSAGGIO PERIMETRO BAGNATO

SI PROCEDE CON LO STESSO METODO PER IL PASSO TRIANGOLARE

Page 9: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

AREA DI PASSAGGIO PERIMETRO BAGNATO

PASSO TRIANGOLARE

Page 10: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

CALCOLO AREA DI PASSAGGIO LATO MANTELLO

E’ UN CALCOLO NON IMMEDIATO, IN QUANTO RAPPRESENTA L’AREA LIBERA

DI PASSAGGIO A DISPOSIZIONE DEL FLUIDO LATO MANTELLO, CHE

LAMBISCE ESTERNAMENTE I TUBI E SCORRE ATTRAVERSO I DIAFRAMMI

FACCIAMO UNA SEZIONE VERTICALE DI UN FASCIO TUBIERO

SI OTTIENE UNA SEZIONE DI QUESTO TIPO:

Page 11: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

VIA VIA CHE IL LIQUIDO PERCORRE IL

MANTELLO, PASSA PROGRESSIVAMENTE DA

ZONE AD AREA MAGGIORE A ZONE AD AREA

MINORE, CON AREA MASSIMA IN

CORRISPONDENZA DELLA META’ DELLO

SHELL

QUALE AREA DI PASSAGGIO

CONSIDERARE ?

Page 12: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

Dis = diametro dello shell

c = y-de luce di passaggio

lb = distanza tra i diaframmi

NUMERO DI LUCI

AREA DI UNA LUCE

Page 13: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

LATO TUBO LATO MANTELLO

passo dei tubi !!

VERIFICA TERMICA

tubii

tubip nd

A

4

2

,

Page 14: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

VERIFICA IDRAULICA DI UN FASCIO TUBIERO

COME GIA’ DETTO, LA VERIFICA IDRAULICA CONSISTE

NEL CALCOLARE LE PERDITE DI CARICO LATO TUBI E

LATO MANTELLO E CONFRONTARLE CON QUELLE

MASSIME AMMISSIBILI DETERMINATE IN FASE DI

PROGETTO

SE LE PERDITE DI CARICO CALCOLATE SU

ENTRAMBI I LATI SONO INFERIORI A QUELLE

PROGETTUALI

LO SCAMBIATORE E’ VERIFICATO ANCHE DAL

PUNTO DI VISTA IDRAULICO

Page 15: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

CONTINUE LATO TUBI f dal grafico*

Ltot=Ltubo x n

LOCALIZZATE LATO TUBI n= n° passaggi lato tubo

TOTALI LATO SHELL f dal grafico*

Ltot= Dis x n° diaframmi

n° diaframmi = Ltubi / lb

CALCOLO PERDITE DI CARICO

TOTALE LATO TUBI: LA SOMMA DI CONTINUE E LOCALIZZATE

DA CONFRONTARE CON QUELLE FISSATE IN FASE PROGETTUALE

* I diagrammi per il calcolo del coefficiente di attrito f sono i seguenti:

Page 16: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’
Page 17: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’
Page 18: DIMENSIONAMENTO SCAMBIATORI DI CALORE A ...s1ba7968ba6bd47cb.jimcontent.com/download/version/...SCAMBIATORI A FASCIO TUBIERO A PIU’ PASSAGGI LATO TUBO E LATO MANTELLO; POICHE’

ESERCIZIO

20000 kg/h di un distillato a 35°API devono essere

raffreddati da 123 a 65°C mediante acqua di fiume che entra

a 26°C ed esce a 48°C. Si ha disponibile uno scambiatore a

fascio tubero tipo 1:1 avente Dis=49cm e contenente 204

tubi di acciaio ¾”BWG16 di lunghezza 4,85m disposti a

quadrato con passo di 1”. I diaframmi sono distanziati di 5”.

Verificare l’utilizzabilità di questo scambiatore sapendo che

le perdite di carico ammesse sono di 0,7 ata per entrambi i

lati.