    Digital Line Protection System

    Microprocessor Based Protection,Control and Monitoring System

    Waveform Sampling

    Proven Protection

    Economical

    Ease of Retrofit

  • 7/29/2019 DigitalLineProtection GE Dlpd

    2/35

    2

    Industrial Systems

    DLP-D Enhancements

    MODEL DLP3512CDH

    Ratings:

    In 5 AMPS

    Vn 120 Vac

    Freq 60 Hz

    GEK 99300

    GREEN: PROTECTION ON

    RED: CHECK STATUSg Digital Line Protection

    GE PROTECTION AND CONTROL

    Malvern, PA

    COMM

    TRIP AC Z 1 50

    01Power

    ON

    OFF

    SET 1/Y 2 3/N CLR

    INF 4 5 6

    ACT 7 8 9

    END PRT 0 ENT.

    ASCII SUBSET

    Three Phase

    & Single Phase

    Tripping

    Continuous Monitor

    Alarm 2 Shot Recloser

    Optional

    DLP-C

    Repackaged

    Unbalance

    Alarm

    Detection

    New Packaging

    3 RU High

    Horizontal or Vertical

    SCADA

    Involved Phases

    Indication

    Standard

    Carrier Start

    Options

    Proven

    Design

  • 7/29/2019 DigitalLineProtection GE Dlpd

    3/35

    3

    Industrial Systems

    Overview of DLP Operation

    Multiple Microprocessors (3)

    Sampling Rate = 16/Cycle

    ANALOG

    TO

    DIGITAL

    CONVERTER

    SETTINGSMMI

    PHASOR

    QUANTITIES

    EMULATION OF:

    PHASE ANGLE

    COMPARATORS,

    AMPLITUDE

    COMPARATORS,ETC.

    MicroPs

    &

    EPROMS

    RECURSIVE

    FOURIER

    TRANSFORM

    MEASURING

    FUNCTIONS

    LOGIC

    DISPLAY

    RS232

    OUTPUTS

    I

    V

  • 7/29/2019 DigitalLineProtection GE Dlpd

    4/35

    4

    Industrial Systems

    DLP Application For Three Phase or Single

    Phase Tripping on anyUncompensatedTransmission Line

    Typical Operating Times are3/4 to 1-1/2 Cycle

    6 Protection Schemes Step Distance

    Directional ComparisonBlocking

    POTT

    PUTT

    Hybrid

    Zone 1 Extension

    G

  • 7/29/2019 DigitalLineProtection GE Dlpd

    5/35

    5

    Industrial Systems

    DLP Operating Times SCR Tripping Times

    PT Potential Source

    0.01 0.1 1 10

    IZ-V

    (Per Unit Volts)

    Mil

    liseconds

    10

    20

    30

    40

    50

    Minimum

    Maximum

  • 7/29/2019 DigitalLineProtection GE Dlpd

    6/35

    6

    Industrial Systems

    DLP Operating Times SCR Tripping Times

    CVT Potential Source

    0.01 0.1 1 10

    IZ-V

    (Per Unit Volts)

    Mil

    liseconds

    10

    20

    30

    40

    50

    Maximum

    Minimum

  • 7/29/2019 DigitalLineProtection GE Dlpd

    7/357

    Industrial Systems

    Settings: Scheme Selection

    STEP

    POTT

    PUTT

    HYBRID

    BLOCKING (BLK1, BLK2, BLK3)

    ZONE 1 EXTENSION

    Zone 2 Ground MeasuringUnit Selection Distance

    Directional Overcurrent

    Distance + Directional O/C

  • 7/29/2019 DigitalLineProtection GE Dlpd

    8/358

    Industrial Systems

    Measuring FunctionsDISTANCE

    Phase Ground

    Zone 1 MHO MHO-or-REACTANCE

    Zone 2 MHO MHO

    (Pilot Zone)

    Zone 3 MHO MHO

    Zone 4 MHO* MHO

    (Reversible/Blocking)

    *Settable Offset

  • 7/29/2019 DigitalLineProtection GE Dlpd

    9/359

    Industrial Systems

    Measuring FunctionsOVERCURRENT

    (3|I0| - KT|I1|) IPT - Pilot Trip

    (3|I0| - KB|I1|) IPB - Pilot Block

    IT - Trip SupervisionIB - Block Supervision

    FD - Fault Detector

    (3|I0| - KD|I1|) IDT - Inst. Direct Trip (Directional Control)

    (3|I0|) GTOC - Time Overcurrent (Directional Control)

    DIRECTIONAL

    NT - Trip

    NB - Block

  • 7/29/2019 DigitalLineProtection GE Dlpd

    10/3510

    Industrial Systems

    Ground TOC Curves

    ?

    Custom Ground TOC Curves

    From Several Sources Curves generated by GEs TOC curve

    editor

    Any curve from GEs TOC curvedatabase

    The Existing Library of ASPENRelayEditorTM curves

    Any custom curve designed withASPEN RelayEditorTM

    Inverse

    Custom

    Extremely

    Inverse

    Definite

    Time

    Very Inverse

  • 7/29/2019 DigitalLineProtection GE Dlpd

    11/3511

    Industrial Systems

    Additional Protective Relay Features Out-of-Step Blocking

    PT Fuse Failure

    Line Pickup (Close Into Fault)

    Remote Open Detector Line Overload

    Adaptive Reach(Zone 1 Ground Reactance - Supervising MHO)

    Current Unbalance Alarm

    Continuous Monitor Alarm Detects Internal RelayChanges if FD is Not Picked Up

    Carrier Start Options for Improved Coordination inBlocking Schemes with Other Relays.

    Trip Bus Check when Settings are Changed

  • 7/29/2019 DigitalLineProtection GE Dlpd

    12/3512

    Industrial Systems

    Recloser (Optional)

    Single breaker reclosing

    Programmable up to 2 reclose attempts

    Manual Lockout Panel Switch Additional Inputs

    Reclose Initiate, Reclose Inhibit, Reclose Cancel, Reclose Reset

    Additional Outputs

    Zone 1 Reach Reset, Lockout Alarm, Reclose in Progress

  • 7/29/2019 DigitalLineProtection GE Dlpd

    13/3513

    Industrial Systems

    Inputs - Single Phase ModelsIA, IB, IC

    VAG, VBG, VCG

    RI-1P

    RI-3P

    Receiver 1 Output ContactReceiver 2 Output Contact*

    Stop Carrier*

    Block Pilot Tripping*

    (3) 52/b Contacts (w/ Recloser)

    (3) 52/b Contacts (w/o Recloser)

    Reclose Inhibit

    Reclose Cancel

    Reclose Reset

    3 Pole Trip Enable

    * Configurable Inputs

  • 7/29/2019 DigitalLineProtection GE Dlpd

    14/3514

    Industrial Systems

    Inputs - Three Phase ModelsIA, IB, IC

    VAG, VBG, VCG

    (6) Digital Inputs (Contact Converters)

    (2) 52/b Contacts

    Receiver 1 Output ContactReceiver 2 Output Contact*

    Stop Carrier*

    Block Pilot Tripping*

    RI**

    Reclose Inhibit**

    Reclose Cancel**

    Reclose Reset**

    * Configurable Inputs

    ** Inputs for Recloser

  • 7/29/2019 DigitalLineProtection GE Dlpd

    15/35

    15

    Industrial Systems

    Configurable Inputs(1701)

    CONCCI CC4 CC5 CC6

    0 RECEIVER 2 SELECT GROUP BIT 1 SELECT GROUP BIT 0

    1 EXTERNAL TRIGGER SELECT GROUP BIT 1 SELECT GROUP BIT 0

    2 CONFIG. INPUT 1 SELECT GROUP BIT 1 SELECT GROUP BIT 0

    3 RECEIVER 2 STOP CARRIER BLOCK PILOT TRIP

    4 EXTERNAL TRIGGER STOP CARRIER BLOCK PILOT TRIP

    5 CONFIG. INPUT 1 STOP CARRIER BLOCK PILOT TRIP

    6 RECEIVER 2 CONFIG. INPUT 2 CONFIG. INPUT 3

    7 EXTERNAL TRIGGER CONFIG. INPUT 2 CONFIG. INPUT 3

    8 CONFIG. INPUT 1 CONFIG. INPUT 2 CONFIG. INPUT 3

    USER

    INPUT

    DEFAULT

    SELECT

    SETTINGSGROUP

  • 7/29/2019 DigitalLineProtection GE Dlpd

    16/35

    16

    Industrial Systems

    Configurable Inputs / Adaptive Settings

    Settings

    CC5 CC6 Group

    0 0 G1

    0 1 G21 0 G3

    1 1 G4

    SETTINGS GROUP

    G1

    G2

    G3

    G4

    SETTINGS GROUP SWITCH 16SB1______

    CONTACT NUMBER G4 G3 G2 G1

    1 X X

    23 X X

    4

    1 2

    3 4

    CC5 (bit 1)+-

    SG

    1

    CC6(bit 0)

    +

    -

    SG

    3

  • 7/29/2019 DigitalLineProtection GE Dlpd

    17/35

    17

    Industrial Systems

    Outputs - Single Phase ModelsDEDICATED

    Trip (SCR or Contact, 2 per phase)..... 6

    BFI (2 per phase)................................... 6

    RI-1P...................................................... 2

    Transmitter Key.................................... 2

    Zone 1 Extension Reset....................... 1

    3 Pole Trip Enable................................ 1

    Reclose in Progress............................. 1

    Alarm (Pwr Supply/Critical)................. 1

    SCADA.................................................. 5

    CONFIGURABLERI-3P (Configurable as pair)................ 2

    BKR Close

    (Independent - Except Reclosing)...... 2

    Line Overload....................................... 1

    Non-Critical Alarm................................ 1

    Reclose Cancel..................................... 1

  • 7/29/2019 DigitalLineProtection GE Dlpd

    18/35

    18

    Industrial Systems

    Outputs - Three Phase ModelsDEDICATED

    Trip (SCR or Contact)........................... 2

    BFI.......................................................... 2

    Transmitter Key.................................... 2

    Alarm (Pwr Supply/Critical)................. 1

    SCADA................................................... 5

    Reclose in Progress

    (recloser models only)......................... 1

    Lockout Alarm & Reach Reset

    (recloser models only)......................... 2

    CONFIGURABLERI............................................................ 2

    BKR Close (Independent).................... 2

    Line Overload....................................... 1

    Non-Critical Alarm................................ 1

    Reclose Cancel..................................... 1

  • 7/29/2019 DigitalLineProtection GE Dlpd

    19/35

    19

    Industrial Systems

    Configurable OutputsEXAMPLE:

    Configure the BC-1 Output to Close when Zone 1 BG, GRD DIRTRIP, and CONF. INPUT 1 are ON and CONF. INPUT 3 is OFF.

    (1801) CONOUT 1 = 2 (AND gate)

    (1802) CO1 IN1 = 2 (Z1BG)

    (1803) CO1 IN2 = 35 (GRD DIR TRIP)

    (1804) CO1 IN3 = 50 (CONF. INPUT 1)

    (1805) CO1 IN4 = 152 (NOT of CONF. INPUT 3)

    (1806) CO1 IN5 = 0

    . .

    . .

    (1809) CO1 IN8 = 0

  • 7/29/2019 DigitalLineProtection GE Dlpd

    20/35

    20

    Industrial Systems

    SCADA Digital to Analog Interface Provides Analog Output Proportional to Distance to

    Fault Location in 0 to 1mA DC or 0 to 5 Vdc Output(Selectable)

    Four (4) Contact Outputs Provide Fault Type

    Example:

    A

    B

    C

    G

    Phase A to

    Neutral Fault

    Indication

  • 7/29/2019 DigitalLineProtection GE Dlpd

    21/35

    21

    Industrial Systems

    Target (Current Actuated)

    Fault Location Algorithm = Lumped Parameter Differential Equation Solution

    Uses Phasor Quantities (Output of Fourier Algorithm) as Inputs

    Eliminates the Effect of Fault Resistance

    TRIP AB Z1 44

  • 7/29/2019 DigitalLineProtection GE Dlpd

    22/35

    22

    Industrial Systems

    Present Value Reporting

    Voltages

    Watts

    Phase Angles

    Currents

    Vars

    Breaker Status

    Automatically Displayed and UpdatedIn Four Second Intervals on LED Display

  • 7/29/2019 DigitalLineProtection GE Dlpd

    23/35

    23

    Industrial Systems

    Communications Local MMI (Standard)

    2 Level Password Protection

    MASTER

    SETTINGS

    16 LED Alphanumeric Display

    Keypad with 20 Keys

    Separate Function Keys for

    Settings

    Action

    Information

    Alarms

    Status LED

  • 7/29/2019 DigitalLineProtection GE Dlpd

    24/35

    24

    Industrial Systems

    Communications Remote Access

    Via RS232 & DLP-LINKSoftware

    Front and Rear RS232 Ports

    3 Level Password Protection

    Access to: Present Values

    Fault Report

    Sequence of Events

    Oscillography

    Manual Breaker Control

    Relay Settings

    Local Functions Setup Help

    [ - ] DLP COMMUNICATIONS 2.80

    Logout

    Change access level

    Hang up phone

    Actions . . .

    Information . . .Settings . . .

    Relay Functions

    Login

    Phone disconnected

  • 7/29/2019 DigitalLineProtection GE Dlpd

    25/35

    25

    Industrial Systems

    Remote Access - Rear ASCII Port

    ASCII PORT HELP SCREEN

    STATION: MALVERN

    LINE: LINE 1UNIT ID: 0

    DATE: 08/24/96

    TIME: 10:57:51

    STATUS - Request DLP Status

    VALUES - Request Present Values

    MODEL - Request PROM and MODEL numbers

    EVENTS - Request event report

    SHOWSET - Request setting group information

    STLINID - Request station and line ID

    FAULT - Request fault reportFSTATUS - Request status of all faults

    LOGIN - Login request

    LOGOUT - Logout request

    STATION: MALVERN

    LINE: LINE 1

    UNIT ID: 0DATE: 08/24/96

    TIME: 10:57:51

    MODEL NUMBER: DLP3512CDH

    PROM VERSION NUMBER: V002.320B

    INFORMATION ONLY

  • 7/29/2019 DigitalLineProtection GE Dlpd

    26/35

    26

    Industrial Systems

    Fault Report

    Prefault Currents

    Voltages

    Post Fault Currents Voltages

    Trip Targets

    Operating Time

    Selected Events

    Sample DLP 5512

    FAULT REPORT

    Station ID: PLACE TRANSMISSION

    Line ID: CREEK 115KV OCB 5512

    TRIP DATE: 09/11/95 TRIP TIME: 15:16:10.295

    FAULT TYPE: AB DISTANCE: **** MILES

    TRIP TYPE: Z4 OPERATING TIME: 01496

    PREFAULT FAULT

    Ia: 038.40 A Ia: 057.60 A

    Ib: 028.80 A Ib: 048.00 A

    Ic: 057.60 A Ic: 050.40 AIn: 007.20 A In: 014.40 A

    Va: 066.0 KV

    Vb: 066.0 KV

    Vc: 066.1 KV

    15:16:10.295 TRIP SIGNALS ON

    15:16:12.119 TRIP SIGNALS RESET

    15:16:12.119 TRIP CIRCUIT #1 NOT ENERGIZED

  • 7/29/2019 DigitalLineProtection GE Dlpd

    27/35

    27

    Industrial Systems

    Present Values

    Currents

    Voltages

    Angles

    Watts

    Vars

    Breaker Status

    Carrier Status

    Active Setting Group

    Sample DLP 5072

    PRESENT VALUES

    Station ID: CREEK TRANSMISSIONLine ID: 115KV OCB

    09/18/95 14:23:44.455

    IA: 001.16 A -001 DEGS VA: 066.3 V 000 DEGS

    IB: 001.26 A 119 DEGS VB: 066.3 V 121 DEGS

    IC: 001.26 A -119 DEGS VC: 066.3 V -119 DEGS

    IN: 000.03 A **** DEGS

    WATTS: 056.6 MW VARS: 003.1 MVAR

    BREAKER 1: CLOSED BREAKER 2: N/A

    PLC #1 SIGNAL: OFF PLC #2 SIGNAL: OFF

    PLC #1 STATUS: N/A PLC #2 STATUS: N/A

    STOP CARRIER: OFF SETTING GROUP NUMBER: 1

    BLOCK PILOT TRIP: OFF

  • 7/29/2019 DigitalLineProtection GE Dlpd

    28/35

    28

    Industrial Systems

    Sequence of Events

    Operational Events Setting Changes

    Fault Data

    Status

    Diagnostic Self-Test Events

    Warning (Non-Critical Alarm)

    Failure (Critical Alarm)

    Time Tagged to 1msResolution

    Last 100 Events Stored

    Sample DLP 5072

    Events

    Station ID: CREEK TRANSMISSION

    Line ID: 115KV OCB

    07/25/95 19:06:21.121 TRIP SIGNALS RESET

    07/25/95 19:06:21.121 TRIP CIRCUIT #1 NOT ENERGIZED

    07/25/95 19:06:21.048 TRIP SIGNALS ON07/25/95 19:06:21.038 OSC TRIGGER

    05/31/95 12:16:42.091 TRIP CIRCUIT #1 MONITOR ALARM ON

    05/31/95 12:16:41.915 TRIP CIRCUIT #1 MONITOR ALARM ON

    05/31/95 12:16:41.879 REMOTE COMM - SETTINGS CHANGE DONE

    05/31/95 12:16:30.720 REMOTE COMM - SETTINGS CHANGE STARTED

    05/31/95 12:13:48.392 REMOTE COMM - PASSWORD CHANGED

    05/31/95 12:11:53.383 REMOTE COMM - PASSWORD CHANGED

    05/31/95 12:10:37.847 UNBALANCED SYSTEM DETECTION ALARM ON

    05/31/95 12:10:29.930 REMOTE COMM - PASSWORD CHANGED05/31/95 12:09:35.302 FUSE FAILURE ALARM ON

    05/31/95 12:09:35.175 LOCAL - SETTINGS CHANGE DONE

    05/31/95 12:09:30.826 LOCAL - SETTINGS CHANGE STARTED

    05/31/95 12:07:22.109 UNBALANCED SYSTEM DETECTION ALARM ON

    05/31/95 12:06:00.042 FUSE FAILURE ALARM ON

    05/31/95 12:06:00.000 SSP BOARD: QUEUES REINITIALIZED

    05/31/95 12:05:30.210 FAIL - TRIP BUS CHECK

    05/31/95 12:05:30.177 FUSE FAILURE ALARM ON

  • 7/29/2019 DigitalLineProtection GE Dlpd

    29/35

    29

    Industrial Systems

    Oscillography Triggers

    None

    Fault Detector

    Any Zone 2

    Any Zone 3

    Any Zone 4

    Out-of-Step

    V1 Detector

    External Contact Input

  • 7/29/2019 DigitalLineProtection GE Dlpd

    30/35

    30

    Industrial Systems

    Flexible Oscillography Data Storage

    # Faults Stored Cycles

    2 72

    4 367 18

    14 9

    Pre-fault Cycles Selectable from 1 to 8

    Settings and Fault Report are stored withOscillography Data

  • 7/29/2019 DigitalLineProtection GE Dlpd

    31/35

    31

    Industrial Systems

    Oscillography Data

    Internal and ExternalOscillography Triggering

    ASCII File Format(Readable byEXCEL/LOTUS/DL-DATA)

    For Each Sample4 Currents (IA, IB, IC, IN)

    3 Voltages (VA, VB, VC)

    6 Flag Groups

    Digital Inputs

    Outputs

    Phase Zone Flags

    Breaker Status and Gnd. Zone Flags

    Protection Logical Input Flags

    Output Status of Protection Timers

  • 7/29/2019 DigitalLineProtection GE Dlpd

    32/35

    32

    Industrial Systems

    d i l S

  • 7/29/2019 DigitalLineProtection GE Dlpd

    33/35

    33

    Industrial Systems

    Hardware and Packaging Draw-Out Modular Construction with Removable Door

    Front Panel Power Switch

    Information Access MMI

    RS232 Front & Rear (GE Modem) RS232 Rear (ASCII)

    Target Clearing Through Door

    Optional Mounting Flanges for L2 and KD cutouts andMoveable Mounting Brackets

    Self-Test Diagnostics Critical Alarm

    Non-Critical Alarm

    I d i l S

  • 7/29/2019 DigitalLineProtection GE Dlpd

    34/35

    34

    Industrial Systems

    Hardware and Packaging Magnetics are easily accessible, but not part of Drawout

    Assembly Improves reliably by eliminating CT shorting bars

    I d t i l S t

  • 7/29/2019 DigitalLineProtection GE Dlpd

    35/35

    Industrial Systems

    Nomenclature Selection GuideDLP * * * * * * *1 1 AMP Rated

    5 5 AMP Rated

    0 48 Vdc Battery Voltage

    1 110/125 Vdc Battery Voltage

    2 220/250 Vdc Battery Voltage

    1 SCR Tripping Output

    2 Relay Tripping Output

    3 C Three Phase Tripping, Without Recloser

    1 J Single Phase Tripping, Without Recloser

    1 K Single Phase Tripping, With Recloser

    3 K Three Phase Tripping, With Recloser

    D Revision Level

    H Horizontal Mounting

    V Vertical Mounting