Digital energy meters, multimeters and power analyzers DMG & DME series
Flush-mount expandable digital energy meters & power analyzersWide range of operation
Wide range of voltage measurement20...830VAC L-L
DIGITAL MULTIMETERDIGITAL ENERGY METER DIGITAL POWER ANALYZERS
Expansion modules High expandability
Multiple energy metering with tariff function
Accuracy• Auxiliary power supply: 100-440VAC/110-250VDC• Maximum measured rated voltage: 690VAC L-L (600 UL/CSA rating)• Input current with CT: 5A or 1A for DMG 910801 / 910901• Voltage measurement range: 20...830V L-L; 10...480V L-N• Current measurement range for 5A full scale: 0.01-6A for DMG 910801;
0.01-10A for DMG 910901• Current measurement range for 1A full scale: 0.01-1.2A• Frequency measurement range: 45-66Hz for all types;
360-440Hz for DMG 910901
The wide measurement range of voltage inputs allows DMG multimeters to be used in an infinite number of applications.
96x96mm96x96mm
DMG 910801: More than 344 measured electrical quantities, expandable.DME 912312: Three phase, expandable digital energy meter. DMG 910901: More than 590 measured electrical quantities, expandable.
96x96mm
These DMG can increase their features with the use of the following expansion modules and satisfy the many diverse needs of Customers. They include:
• Digital inputs and outputs, static and relay type
• Analogue inputs and outputs• RS485, Ethernet and Profibus-DP
interface communications• Data storage with clock calendar (RTC)
for events and data logging• Data storage with clock calendar (RTC) for
events, data logging with Energy Quality.
Multifunction analogue inputs and outputs
The programmable analogue outputs can be configured in voltage or current.
Ethernet gateway function
It allows to read data from group of DMGs connected together in a RS485 network, using one Ethernet port.
Storage module with clock calendar
It provides for data logging of the measurement trends and storing events and alarms with time stamp.
Energy Quality (EN 911131) module
It permits to control the energy quality to EN 911131 normative, storing events (micro breakings, voltage dips, etc.) with time stamp.
These expansion modules are common to all the flush-mount models. The fitting on the multimeters is done with no need of tools and the connection is made with plug-in connectors.
More than 20 partial energy meters, clearable.
DMG 910801 / 910901(MID Class B)
• Voltage: ±0.2% (50-830VAC)• Current: ±0.2% (0.1-1.1 In)• Power: ±0.5%• Active energy: Class 0.5S (MID Class B compliant)• Reactive energy: Class 2.
IP65IP54MIDoption
DME 912312 Optical Interface Compact Housing
Maximum of 3 expansion modules
Accuracy
Sealable terminal covers included
Tariffs
Expansion modules for DME 912312Ethernet connection
• Rated current input /5A• Current connection by CT• Backlight LCD screen (128x80 pixels)• Active energy measurement (Class 1)• Multi-measurements• 3 function keys• Tariff selection input (2 tariffs)• 2 programmable static outputs• Expandable with EXM... modules• 4-module housing
The interface between the DME 912312 and expansion modules is obtained by infrared beam. Appropriate connectors provide for a secure fixing of the expansion modules on the energy meter.
The digital energy meter is made to DIN standards. The width is just 4 modules.
Up to 3 EXM... expansion modules can be fitted on a DME 912312 and permit to:• Communicate• Control alarms, pulses and tariffs• Event storage with time stamp
• Active energy measurement accuracy Class 1 per IEC/EN 62053-21
• Reactive energy measurements accuracy Class 2 per IEC/EN 62053-23
The energy meters are duly equipped with a set of two sealable terminal covers.
Consumption and tariffs (kWh) can be monitored with the digital input for instance , considering different day and night time frames.
The DME 912312 type energy meter can integrate additional functions by using the following modules:• Digital inputs and outputs
The EXM 910113 type expansion module permits the DME 912312 energy meter to be connected to a normal internet network and be viewed, in this way, by one or more connected computers online.
71.6mm
Front panel mounting ease Low-profilehousing
Safety
Five voltage and fourcurrent inputs
Programmable alarms withBoolean logic
Wiring diagrams
Main parameters and measurement inputs
DMG 910801 DMG 910901
Being equipped with sealable switches, the models can have set-up and clearing locks.To avoid connection tampering, sealable terminal covers are also included.
Type of connections:
• Single-phase• Two-phase• Three-phase with or without neutral• Three-phase without neutral,
ARON connection• Balanced three-phase, with or without neutral.
Type of connections:
• Single-phase• Two-phase• Two-phase with neutral, measurement of
neutral current and neutral-earth voltage.• Three-phase with or without neutral• Three-phase without neutral,
ARON connection• Balanced three-phase, with or without neutral.• Three-phase with neutral, measurements of
neutral current and neutral-earth voltage.
The DMG 910901 can also provide measurements of neutral current and neutral-earth voltage.
DMG 910801 and DMG 910901 types are only 60 mm deep (51.5mm with the terminals covers in place). With the expansion modules mounted, this becomes 80mm.
The mounting on and removal from the panel door are done with no need of tools. A special fixing system provides a quick and immediate operation during both device installation and removal from the panel.
AUX SUPPLY
12-24-48VDC
N
L3
L2
L1
110_250VDC110_440VDC
VOLTAGECURRENT
L1
A1 A2 GND V1 V2 V3 VN S1 S2 S1 S2 S1 S2
L2 L3
CT1
CT2
CT3
LOAD
AUX SUPPLY
12-24-48VDC
N
L3
L2
L1
110_250VDC110_440VDC
VOLTAGECURRENT
L1
A1 A2 GND V1 V2 V3 V4 VN S1 S2 S1 S2 S1 S2
L2 L3
S1 S2
L3
CT1
CT2
CT3
CT4
LOAD
AUX SUPPLY
12-24-48VDC
N
L3
L2
L1
110_250VDC110_440VDC
VOLTAGECURRENT
L1
A1 A2 GND V1 V2 V3 VN S1 S2 S1 S2 S1 S2
L2 L3
CT1
CT2
CT3
LOAD
AUX SUPPLY
12-24-48VDC
N
L3
L2
L1
110_250VDC110_440VDC
VOLTAGECURRENT
L1
A1 A2 GND V1 V2 V3 V4 VN S1 S2 S1 S2 S1 S2
L2 L3
S1 S2
L3
CT1
CT2
CT3
CT4
LOAD
DMG series
USA: +1 646 512 5727 UK: +44 (0)1582 461123 EUR: +31 (0)413 320031E: [email protected] W: www.Qhigroup.com
Voltage (phase, phase-to-phase and system values)
Neutral-earth voltage
Phase current values
Phase current values (actual neutral current)
Power Factor (PF)
Cosphi for each phase
Frequency
Maximum and minimum value for each function (HIGH/LOW) for reading and storage of peak voltage, current, power, PF and frequency values
Voltage and current asymmetry
Averaging function
Peak values (maximum demand) of power and current
Hour counter (programmable total and partial)
Total Harmonic Distortion (THD) of voltage and current values
Harmonic analysis of voltage and current up to 31° order
Harmonic analysis of voltage and current up to 63° order
Direction of harmonic power flow
Active, reactive, apparent, imported and exported energy meters (partial and total)
Pulse counter for general use (pulse count for consumption of water, gas, etc., with expansion module only)
3ph+N voltage, 690VAC max
3ph+N+GND voltage, 690VAC max
3ph current, CT /5A
3ph current, CT /5A or /1A
3ph+N current, CT /5A or 1/A
SINGLE, TWO, THREE-PHASE INSTRUMENTS WITH OR WITHOUT NEUTRAL
DIGITAL MULTIMETER
DMG 910801
POWER ANALYZERS
DMG 910901
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Measurement Inputs
US 11 10