Numerical Relays For Protection, Monitoring & Control
Larsen & Toubro
Larsen & Toubro is a technology-driven company that
infuses engineering with imagination. The Company
offers a wide range of advanced solutions in the field
of Engineering, Construction, Electrical & Automation,
Machinery and Information Technology.
L&T Switchgear, a part of the Electrical & Automation
business, is India's largest manufacturer of low
voltage switchgear, with the scale, sophistication and
range to meet global benchmarks. With over five
decades of experience in this field, the Company
today enjoys a leadership position in the Indian market
with a growing international presence.
It offers a complete range of products including
powergear, controlgear, industrial automation,
building electricals & automation, reactive power
management, energy meters, and protective relays.
These products conform to Indian and International
Standards.
L&T limited offers a wide range of Microprocessor
based State-of-the-art digital protective relays
suitable for LV, MV and HV power distribution
systems. These relays are manufactured at L&T’s
Mysore works equipped with modern infrastructure
and employing latest manufacturing and testing
equipments. L&T’s range also include relays for
special applications manufactured by Microelettrica
Scientifica, Italy. The applications include Feeder
Management, Load Sharing, Load Shedding,
Synchronising, Grid Islanding etc.
L&T also manufactures a range of electronic single phase energy meters, three phase energy meters and trivector meters at the Mysore works.
Switchgear Factory, Ahmednagar
Switchgear Factory, Mumbai
Switchgear Factory, Vadodara
ANSI Device Function 1
Time - Current Characteristics 2
Over Current & Earth Fault Relays -
Current Sensing Relays -
Power Factor Control Relays
MC31AnX, MC61AnX 3
MC12A, SC14S 5
Reverse Power Relay - MRP11 7
Voltage Relay - MV12 7
- etaCON Series 9
RPM14 11
Motor Protection Relays - MM30-743, MM30-W74, 13
MCOMP, MPR300 15
Generator Protection Relays - MG30, MG30I, MD32G 17
Transformer Protection Relay - MD32TM 19
Vector Surge Protection Relay - UM30A 21
Voltage and Frequency Relay - MC3V, UFD34 21
Schematic - Relay Application 23
Pages
Contents
Correlation between ANSI/IEEE device function number and relays
Under impedance relay / Distance relay
Auto synchronising
Synchro-check relay
AC under voltage relay
Power directional relay
Under current or under power relay
Field control (loss of field) relay
Reverse phase or phase balance current relay
Phase-sequence or single-phasing voltage relay
Machine or transformer thermal relay
Instantaneous over current (or rate-of-rise) relay
Voltage restrained over current relay
Breaker - failure
Instanteneous earth fault over current relay
AC time over current relay
Ground fault time over current relay
AC over voltage relay
Overexcitation relay V/Hz
Voltage balance relay
Ground detector (insulation to ground failure of machine or other apparatus)
Machine stator ground fault detector relay
AC directional over current relay
Directional ground fault over current relay
DC over current relay
Phase angle measuring or out of-step protection relay
Frequency relay
Lock-out relay
Differential protective relay
Ground fault differential protective relay
Regulating device to adjust a quantity
Vector surge protection relay
Rate of change of frequency
MV12
MRP11
M
MC12A
MC61A
MC12A
MC61A
MC12A
MC61A
MC31A
MC12A
MC61A
MC31A
MV12
--
--
--
--
--
--
–
–
–
--
--
SC14S
--
–
–
–
PR300
MG30 / MG30-I
SPM21
SCM21
UM30-A / MC1V / MC3V
UFD34
MG30 / MW33 / MG30-I
MM30
MW33
MG30 / MG30-I
IM30T
MM30
UM30-A, MC3V
IM30T
MG30 / MG30-I
MM30 / MM30-W
MC20 / MC30
IM30-T / IM30-AP
FMR
MG30 / MG30-I
MG30 / MG30-I
MC20 / MC30 / FMR / IM30T / IM30AP
IM30 AP / IM30-T
MC20 / MC30
FMR / IM30-T
IM30-AP / IM30-T
MC20 / MC30
FMR / IM30-T
--
IM30-AP / IM30-T
MC20 / MC30
FMR
--
--
UFD34, MW33
UM30-A / MG30 / MG30-I
UM30-A
MG30
MG30
UBO / CR
FMR
FMR
–
IM30-GOS
UM30-ASV / MG30
UFD34 / MC1V / MC3V / MW33
--
MD32G
MD32T / MD32TM
MD32G, MD32T
--
UM30-A
UFD34
Function Name
L&T Relays
MS Relays
Device No.
21
25
27
32
37
40
46
47
49
50
51V, 50V
50BF
50N
51
51N-(51G)
59
59/81
60
64
64S
67
67N-(67G)
76
78
81
86
87
87N-(87G)
90
df/dt
ANSI/IEEE
1
Product Design Standards
Reference standards IEC 60255, IEC 61000, IS3231, IS8686Dielectric test : IS 3231 / IEC 60255-5 Impulse test : IS 8686 / IEC 60255- 5 HF disturbance test : IS 8686 / IEC 60255-22-1 Electrostatic discharge test : IEC 61000-4-2Electrical fast transient : IEC 61000-4-4Radiated electro magnetic field test : IEC 61000-4-3Surge immunity : IEC 61000-4-5Ring wave test : IEC 61000-4-12Voltage dips & interruption test : IEC 61000-4-11Power frequency magnetic test : IEC 61000-4-8
:
Time - Current Characteristics
Time - Current Characteristics (At TMS = 1)
A : Normal Inverse 3.0 secB : Normal Inverse 1.3 secC : Very InverseD : Extreme Inverse
For Trip time at TMS other than 1Trip time = (Trip time at TMS = 1) x TMS or 50 msec whichever is more.
Multiple of set current (Is)
Tri
p T
ime
(S
ec
.)
A
B
C
D
1,000
100
10
1
01
1 10 20
2
Salient Features • Microcontroller based Numerical relay for Feeder, AC machines,
and transformer protection in LV, MV and HV Systems
Site selectable IEC Curves - 4 nos. of IDMT curves + 3 Definite time characteristics
Universal Aux. supply: 24 - 220 VAC/ DC
Large LCD Display and 4 LED's for fault indication
Built in self supervision and relay test facility
Freely programmable output contacts – 4NO or 2NO + 2NC type with additional relay for IRF
•
•
•
• Last 15 trip records with Date and Time stamping
•
•
Over Current and Earth Fault Relays
• Three phase over current & earth fault relays
Auxiliary supply
CT Rating
Device code
Design
Burden on CT
Burden on PT
Operating temp
Weight
Burden on auxiliary supply
Output contact
Construction
Dim W x H x D in mm
Panel cutout
Output contacts
3 Phase O/C + E/F
0C
51, 51N
Numerical relay
Site selectable trip time char.
Display of currents, trip count
Self supervision feature
� 0.25 VA on CT/Phase
Not applicable00 to 60 C
< 2kg
� 10 VA
1 N/O Contact for self supervision
Drawout
121 x 158 x 224
113 x 142
24 to 240 V AC / DC
1 A or 5 A
(site selectable)
4 NO or 2 NO + 2 NC
3 Phase O/C + E/F + Highset
0 0C
supervision
24 to 240 V AC / DC
51, 51N, 50, 50N
Numerical relay
Site selectable trip time char.
Highset can be disabled
Display of currents, trip count
Self supervision feature
� 0.25 VA on CT/Phase
Not applicable
0 to 60 C
< 2kg
� 10 VA
1 N/O Contact for self
Drawout
121 x 158 x 224
113 x 142
1 A or 5 A
(site selectable)
4 NO or 2 NO + 2 NC
MC61AnXModel MC31AnX
Ordering Information
Other features
Settings
Functions available
Description
3
Lowset O/C - Is
Highset O/C - Ihs
OsLowset E/F -
Highset E/F - Ohs
O/C Is = 20-200% step 1%
E/F Os = 5-80% step 1%
HS O/C = (0.2 to 40) x in step of -
0.1 in or disable
HS E/F = (0.1 to 20) x on step of -
0.1 on or disable
Time characteristics available -
NI, VI, EI, definite time
TMS : 0.01 - 1.6 step of 0.01
O/C Is = 20-200% step 1%
E/F Os = 5-80% step 1%
Time characteristics available -
NI, VI, EI, definite time
TMS 0.01 - 1.6 in step of 0.01
Lowset O/C - Is- OsLowset E/F
MC31AnX
MC61AnX
MC61AnX
MC31AnX
Wiring Diagrams
R Y B R Y B1
2
4
13
5
6
15
16
7
8
3 3
1
2
4
13
5
6
15
16
7
8
22
25
26
21
L/+
N/-
MICRO CONTROLLER
PROTECTION
F51
F51N
R Y B E
PROGERROR
R1
R2
R3
R4
R5
9
10
11
12
17
18
27
28
29
30˜
R Y B R Y B1
2
4
13
5
6
15
16
7
8
3 3
1
2
4
13
5
6
15
16
7
8
22
25
26
21
L/+
N/-
MICRO CONTROLLER
PROTECTION
F51
F51N
F50
F50N
R Y B E
R1
R2
R3
R4
R5
9
10
11
12
17
18
27
28
29
30
PROG.ERROR
4
• Single phase over current / earth fault relay
Salient Features
• Easy setting through front panel DIP switches
• Indication for power ON and trip status
• Test feature - helps in better maintenance • Compact, light weight helps in reducing panel size &
thickness
Current Sensing Relays
Model SC14SDescription
Device code
Design
Burden on CT
Burden on PT
Operating temp
Weight
Burden on auxiliary supply
Output contacts
Construction
Dim W x H x D in mm
Panel cutout
Type 1
Type 2
CT Rating
1 Ph O/C or E/F
0 0C
or
50/51 or 50N/51N
Microcontroller based
Lowset O/C - Is
Highset O/C - Ihs
Lowset E/F - Os
Highset E/F - Is
O/C Is = 50-200% Step 10% or
E/F Is = 10-40% Step 2% or
E/F Is = 20-80% Step 4%
HS O/C = (2-16) xls step 2 Is
HS E/F = (2-16) xls step 2 Is
Time characteristics available-
Nl, VI, EI, Definite time
3 ranges of def time (1, 10,100)
TMS : 0.1 - 1.6 Step 0.1
Site selectable trip time char.
Highset can be disabled
0.25 VA on CT
Not applicable
0 - 60 C
< 1.5kg
5.5 VA
2 C/O Contacts (S/R)
Drawout
71 x 158 x 224
62 x 142
20-110 V AC / DC or
88-264 V AC / DC
1 A or 5 A
10-40% or 20-80% 50-200%
Site selectable
Instantaneous current relay
0 0C
87N/64R
Static
Is = 10-40% step 5%
or 20-80% step 10%
Time characteristics available-
Instantaneous (25ms) or
time delayed 100ms / 200ms
Self powered
Relay testing possible by ext. 24 V -
Supply
Flag indication / LED indication
6 VA
Not applicable
0 to 60 C
< 1.5kg
Not applicable
2 C/O Contacts (S/R)
Drawout
71 x 158 x 224
62 x 142
Not applicable
1 A or 5 A
10-40% or 20-80%
MC12A
Auxiliary supply
Range setting
Other features
Settings
Functions available
Ordering Information
5
MC12A
SC14S
1
2 +VE/PH.
-VE/NR1
COM
COM
SETTING RANGE (Is)
Aux. Supply
μP. ControlCkt.
F50/50NF51/51N
3
10
11
12
1AIn MC12A
(10-40)% In(20-80)% In(50-200)% In
5A
AUX SUPPLY24 - 110V AC/DC95 - 240V AC/DC
MC12A
11
10
9
7+
8
12
SC14S
Test (24V)Voltage
DC-DC
Convrt.
Test
ControlCkt.
R
2
1
3
5
6
4
In1A5A
CT OPERATED RELAYNO AUXILIARY SUPPLY REQUIRED
SETTING RANGE (Is)(10-40)% IN(20-80)% IN
˜
Wiring Diagrams
6
Salient Features
• Easy setting through front panel DIP switches
• LED indication for power ON and trip status
• Test feature - helps in better maintenance • Compact, light weight helps in reducing panel size &
thickness
Reverse Power Relay, Under Voltage or Over Voltage Relay
Model MRP11 MV12Description
Device code
Design
Burden on PT
Burden on CT
Operating temp
Weight
Burden on auxiliary supply
Output contacts
Construction
Dim W x H x D in mm
Panel cutout
Type 1
Type 2
CT Rating
PT Rating
Microcontroller based
Lowset U/V - Vs
Lowset O/V - Vs
U/V Vs = 95-20% step 5%
O/V Vs = 105-180% step 5%
Time characteristics available-
Inverse time, definite time
TMS : 0.1 - 1.6 Step 0.1
Site selectable U/V or O/V
Site selectable trip time char.
0.075 VA on PT
0 to 60 C
< 1.5kg
8 VA
2 C/O Contacts (S/R)
Drawout
71 x 158 x 224
62 x 142
20-110 V AC / DC
88-264 V AC / DC
Not applicable
110 V / 240 V / 415 V (site selectable)
1 Ph U/V or O/V
27 or 59
< 0.25 VA
0 0C
Microcontroller based
Reverse power level
PT input Vn 110 V, 415 V AC
CT input In 1 A / 5 A
Pick up level 1% - 15%
Min. setting 0.5%
TMS 0 to 1.5 step 0.1
Definite time characteristics
LED indication
Test feature
< 0.25 VA
< 0.05 VA
0 to 60 C
< 1.5kg
< 8 VA
1 N/O + 1 C/O
Drawout
71 x 158 x 224
62 x 142
20-110 V AC / DC
88-264 V AC / DC
1 A 5 A
Upto 380 V AC
Reverse power
32
0 0C
or
Other features
Settings
Functions available
Auxiliary supply
Ordering Information
7
MRP11
R Y
14
5
7
8
6
11
μP.
Control
Ckt.
F32
R1
Vn110 V AC 1 A415 V AC 5 A
In AUX SUPPLY24–110 V AC/DC95–240 V AC/DC
MRP11
12
2 + VE / PH.
– VE / N
Aux. Supply3
9
10
B
MV12
5
4
6
8
9
7
R1μP.Control
Ckt.F27F59
1
2
3
11
12
MV12
+VE/PH.
Aux. Supply
-VE/N4
Wiring Diagrams
8
• Intelligent Power factor controllers with Automatic set-up
Salient Features
•
•
• The last two contacts are programmable as alarm and / or fan control except for etaCON 3
• Capacitor over-current and panel over-heating protection
• Use in co-generation systems - 4 Quadarant operation
• Auto / Manual mode
• Measurement Sensitivity - 2.5%
4 Quadrant / 2 Quadrant operation
• Automatic recognition of current flow direction
Online display of PF, Voltage, Current, kVAr, capacitor overload and Panel temperature
Power Factor Control Monitoring Relays
etaCON L3; etaCON L5; etaCON L7Model
3, 5, 7
96 x 96 x 71 mm
92 x 92 mm
415 V AC
5 A secondary
3; 5; 7 steps
etaCON L8; etaCON L12
8, 12
144 x 144 x 69.7 mm
138.5 x 138.5 mm
415 V AC
5 A secondary
8; 12 steps
Ordering Information
Digital Microprocessor based
3 Digit LED
5 Amp
415 VAC ± 15%
50/ 60 Hz
Instantaneous PF, V, I, kVAr, Capacitor Over load
Panel temperature, Average weekly PF,
Maximum Voltage, current, capacitor overload, panel temperature value
Target PF adjustment: 0.8 inductive to 0.8 capacitive
Reconnection time of same capacitor: 5 - 240 secs
Switching time sensitivity: 5 - 600 secs
Less than 10 VA
Less than 0.8 VA
No.of steps
Design
Display
Current Input
Voltage Input
Rated Frequency
Power consumption
Burden on CT
Dimensions W x H x D in mm
Panel cutout
Voltage Input
CT Input
No.of steps
Setting
AlarmsUnder/ Over compensation; Low/ High Current; Low/ High Voltage; Capacitor Overload due to
harmonic Voltage; Over temperature; No-voltage release
Product etaCON L series APFC relay
eNw
etaCON Series
Inbuilt Controller Set-up feature provides an option of Automatic configuration of etaCON
controller.
Measurement
0 9 6
9
Wiring Diagrams
etaCON L3/L5/L7
Current Voltage
1 2 3 4 5 6 7
1 2 3 4 5 6 7 8
/5A 415V
S1 S2 9 10 C
KM1
FU1 FU2 FU7
FU9 FU10
KM2 KM7
FU8
OS1
CT1
FU11
L1L2 L3
MAINS
K7K2K1
LOAD
etaCON L8/L12
1 2 3 4 5 6 7 8 9 10 11 12
1 2 3 4 5 6 7 8C 9 10 11 12 13 14
Current Voltage
/5A 415V
S1 S2 15 16
OS1
CT1
L3
MAINS
LOAD
L1L2
FU16
FU12
KM12KM2KM1
FU15FU14
K12K2K1
FU13
FU1 FU2
10
• Intelligent power factor controller relay
Salient Features
•
•
•
• On line display of system PF
• Easy setting through - front panel push button
Suitable for non-uniform banks
• LED indication for alarm code, no. of banks selected, PF status-lead / lag / unity
Auto / Manual mode
Measurement sensitivity of 1%
• Automatic C/K correction
• Display of Current, Voltage, kVAr, & Capacitor values
Power Factor Control Monitoring Relays
Model
Device code
Design
Burden on CT
Burden on PT
Operating temp
Weight
Dim W x H x D in mm
Panel cutout
Auxiliary supply
RPM-14
Automatic
Microcontroller based
Automatic PF control upto
14 stage
Switching time 1-255 sec
in step of 1 sec for same
Bank switching
Auto C/K selection
PF control range 1% to 120% of
rated current
Can accept unequal banks
Display of PF, V, l, kVAr
LED indications for faults
Alarm signal for CT reversal,
under current, under compensation,
over compensation, over voltage,
1 A / 5 A field selectable
0.3 VA
15 VA00 to 60 C
< 2kg
14 N/O
1 N/O contact for alarm
144 x 144 x 100
138 x 138
240 V AC
power factor controller
14 stage
0C
Description
Functions available
Settings
Other features
Output contacts
Ordering Information
11
RPM-14
1
2
3
4
5
6
7
8
9
10
11
12
R1
R2
R3
R4
R5
R6
R7
R8
R9
R10
R11
R12
13
14
15
16
17
18
19
20
21
22
23
24
R13
R14
-
++
R
Y
B
N
S2
S1(1A)
S1(5A)
ALA
RM
Ph
240V AC
50 HzN
Bank #1
Bank #14
ToLoad
Wiring Diagrams
12
• Motor protection relay - MM30-743• Motor protection relay with voltage input - MM30-W74
Motor Protection Relay
Salient Features
• Display of various parameters, trip count and trip data
• LEDs for fault indication
• User programmable output relays
• Built in self supervision & self testing feature helps maintenance
• RS485 Port for serial communication with “MSCOM” user friendly software
Description
Design
Burden on CT
Burden on PT
Operating temp
Weight
Burden on auxiliary
Output contacts
Construction
Motor protection
50/51, 51LR, 64, 68,
49, 46, 37, St no, ltr
0 0
Numeric
Trip circuit supervision
Thermal O/L and Pre-alarm
Locked rotor
Current unbalance, phase reversal,
Phase loss
Over current
Earth fault
Repeat and prolonged starts
Restart inhibition
No load running
Blocking function
Auto setting
1 A or 5 A site selectable
(Default 5 Amp)
Selectable motor time constant
(1 - 60 min)
Display of parameters
Built in self supervision
RS485 port
0.2 VA for 5 A, 0.01 VA for 1 A
Not applicable
10 C to 60 C
< 2kg
8.5 VA
4 C/O + 1 C/O for self supervision
Drawout
121 x 158 x 224
113 x 142
20-110 V AC / DC or
88-264 V AC / DC
Model MM30-743Motor protection
50/51, 51LR, 64, 49, 46, 37, St no,
ltr, 55, 68, 81, 47, 12/14, 27/59
0 0
Numeric
Trip circuit supervision
Thermal O/L and Pre-alarm
Locked rotor
Current unbalance, phase reversal,
phase loss
Over current
Earth fault
Repeat and prolonged starts
Restart inhibition
No load running
Blocking function
Under frequency / Over frequency
Under voltage / Over voltage
Running hours
Low PF
Auto setting
1 A or 5 A site selectable
(Default 5 Amp)
Selectable motor time constant
(1 - 60 min)
Display of parameters
Built in self supervision
RS485 port
0.2 VA for 5 A, 0.01 VA for 1 A
10 C to 60 C
< 2kg
8.5 VA
4 C/O + 1 C/O for self supervision
Drawout
121 x 158 x 224
113 x 142
20-110 V AC / DC or
88-264 V AC / DC
0.04 VA
MM30-W74
Device code
Functions available
Other features
Ordering Information
Auxiliary supply
Dim W x H x D in mm
13
MM30
L/+
N/-
A B C A B C
25
26
27
28
29
41
30
32
39
25
26
27
28
39
29
41
30
32
43
31
42
33
43
31
42
33
44
In=1A
In=5A
PRESA/TAP 31:Ion=5A
PRESA/TAP 33:Ion=1A 12
13 ˜˜
˜
˜̃̃
=
Display
Microp.
MM30
Function
F37F46F49F51F51RF64St.No.>AI.0>Itr
Progr.
Int. Fault
Keyboard
R1
R2
R3
R4
R5
R1
R2
R3
R4
R5
9 Pin Male
(21) (10)
N.O. N.O.
N.C. N.C.
2110
1122
79
8
1820
19
46
5
1517
16
14
3
2
1
34/382324
CS-S+
IEC 255
Wiring Diagrams
14
•
•
Intelligent motor protection & control relay - MCOMP
Economical motor protection relay - MPR 300
Motor Protection Relay
MPR 300 MCOMP Relay
MCOMPModel MPR 300Motor protection
49, 14, 46, 50N, 3, 59, 27, 47,
81H, 81L, 66, 27LV, 47a, 47b
Numeric
Thermal over load
Locked rotor
Current unbalance
Phase loss
Under current
Over voltage
Under voltage
Over frequency
Under frequency
Max. no. of starts
Reacceleration
Phase reversal
Intelligent relay with separate
protection, display and CT
modules
Suitable for 50/ 60 Hz
Can be used with DOL,
RDOL and Star delta starters
Communication options -
Modbus RTU, Modbus TCP IP and Prof bus
Not applicable
Not applicable0
10 to 60 C
< 2kg
< 8 VA
4 C/O
Split protection unit 92 x 123 x 103.95
80 - 240 V AC/DC
Description
Design
Burden on PT
Burden on CT
Operating temp
Weight
Output contacts
Dim W x H x D in mm
Auxiliary supply
Burden on auxiliary supply
Motor protection
49, 51LR, 64, 46, 37
Numeric
Thermal overload
Locked rotor
Earth fault
Single phasing
No load running
upto 88 A
Trip time characteristics
as per
IEC947
Not applicable
Not applicable0
0-60 C
< 0.5kg
< 8 VA
1NO+1NC
Not applicable
240 V AC
Device code
Other features
Functions available
15
Wiring Diagrams
MCOMP Relay
MPR300 Relay
M
1 2 3 4 5 6 7 8
NC NO
MPR300
Aux
Supply
R Y B N
StartN/O
Stop(N/C)
Typical connection diagramfor ‘Direct Starting’ application
Aux. N/O
240V AC Test Bus
L11 - 201
N11 - 201
PH
N
X-25 X-26 TT
415V, 3PH, 4-wire, 50HzRYB
N
Q1
NL
K
111 112
121 122
131 132
6A
6A
6A
F11
F12
F13
K4
2 4 6
1 3 5
R Y B
T4
CBCT
T1P2
P1 S1
S2
XC1-1
XC1-2XC1-3
XC1-4
XC1-5XC1-6
XC1-7
XC1-8XC1-9
XC1-10
T2
P2
P1 S1
S2
S1
S2
R Y B
T5
CB
CTM COMP
CT UNIT
T3P2
P1
M
X-42
X-43
S
SS2
S1
DriveAvailable Run Trip Unused Do
K3
C1
C2
1 2 3 8N B Y R
Ref. Voltage
8181 82 83 84 85 86 87 88 89 90 91 92
C8
L&T MakeMCOMP
C7C4
C3
Digital Output Relay
C6
61 62 63 64 65 66 67
DIGITAL INPUTS
AUX.VOLT
N PH
71 72
RS485
D1
LEDDISPLAY
75
76
77
P
N
E
Unused DI
Sto
p C
om
ma
nd
Sta
rt C
om
ma
nd
Sta
rt C
om
ma
nd
MotorStatus
K3
106 106 10682 83 85 86
K3 K381 84 87
88 89
Ru
n
K4
Trip
43
44
PH
S111
Stop
P.B12
K4
N
A1
A2
21
22
11
12
H2R
H1GR
un
L
ed
Trip
Le
d
HandRSTP.B.
HandStartP.B.
PMR/CO
AlarmPickup
PMR/COMM
TRIP
ESE
ESC
ELECT
Drive
Ava
ilab
le
M COMP
Typical Dol feeder with M COMP
16
• Multifunction generator protection relays• Percentage based generator differential relay
Generator Protection Relays
Salient Features
• Display of various parameters, trip count & trip data on 8 digit alphanumeric display
• Separate LEDs for various fault indication
• Four user programmable output relays
• Built in self supervision & self testing feature help maintenance
• Easy operation by 5 push buttons
• RS485 Port for serial communication with “MSCOM” user friendly software
Description
Design
Other features
Burden on CT
Burden on PT
Burden on auxiliary supply
Operating temp
Weight
Construction
Dim W x H x D in mm
Panel cutout
Type 1
Type 2
Generator protection
21, 24, 27/59, 32, 37, 40, 46, 49,
0 0C
3 C/O + (1 N/O + N/C) + separate relay
1 C/O for self supervision
50/27,
50V/51V, 51BF, 60FL, 64S, 68, 81
Numeric
Two levels of voltage controlled O/C,
Thermal image with pre-alarm,
Two levels of current unbalance
Two levels of under / over voltage
Two levels of under / over frequency
95% + 100% stator earth fault
Two levels of over excitation
Two levels of under impedance,
Loss of field, under power
PT Fuse failure, breaker failure,
Inadvertent C/B closure etc.
1 A or 5 A site selectable
Display of parameters
Built in self supervision
RS485 port, MODBUS protocol
Blocking inputs & Blocking outputs
0.25 VA for 5 Amp CT
0.01 VA for 1 Amp CT
0.05 VA (MG30)
8.5 VA
10 to 60 C
< 2kg
Drawout
121 x 158 x 224
113 x 142
20-110 V AC / DC or
88-264 V AC / DC
Generator differential
Wave
Built in
0 0C
87, 50/51, 64S/87N, 68
Numeric
Generator differential
Bias % with dual adjustable -
slope
Over current
Stator E/F
CB failure protection
1 A or 5 A site selectable
Display of parameters
form capture feature
self supervision, - RS485 port
0.2 VA for 5 A, 0.01 VA for 1 A
Not applicable
8.5 VA
-10 to 60 C
< 2kg
4 C/O, S/R or H/R or time del
1 C/O for self supervision
Drawout
121 x 158 x 224
113 x 142
20-110 V AC / DC or
88-264 V AC / DC
Model MG30 MD32-GGenerator protection
21, 24, 27/59, 32, 37, 40, 46, 49,
0 0C
3 C/O + (1 N/O + N/C) + separate relay
1 C/O for self supervision
50/27,
50V/51V, 51BF, 60FL, 64S, 68, 81
Numeric
Two levels of voltage controlled O/C,
Thermal image with pre-alarm,
Two levels of current unbalance
Two levels of under / over voltage
Two levels of under / over frequency
95% stator earth fault
Two levels of over excitation
Two levels of under impedance,
Loss of field, under power
PT Fuse failure, breaker failure,
Inadvertent C/B closure etc.
1 A or 5 A site selectable
Display of parameters
Built in self supervision
RS485 port, MODBUS protocol
Blocking inputs & Blocking outputs
0.25 VA for 5 Amp CT
0.01 VA for 1 Amp CT
0.05 VA (MG30)
8.5 VA
10 to 60 C
< 2kg
Drawout
121 x 158 x 224
113 x 142
20-110 V AC / DC or
88-264 V AC / DC
MG30-I
Ordering Information
Device code
Functions available
Output contacts
Auxiliary supply
17
MG30
25
26
27
2839
29
3041
314232
43
33
44
12
13
G
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
Display
Microp.
R1
R2
R3
R4
R5
14
3
2
21
10
1122
79
81820
1946
51517
16
14
3
2
1
Funzioni
1>,Z<,Uo>
R1
R2
R3
R4
R5
12>,T>
Zc<, O>
U,f
W<, Ir>
IC, 60FL
B.I./B.F.
Progr.
Int. Fault
Keyb0ardTastiera
Function
MG30
38(a)
37(b)
To RexRelay
Expansion2324
9 PIN MALE
S–S+
C
(21 – 22)
(10 – 11)
N.O.
N.O.
N.C.
N.C.
CE
MS-SCE 1629-R0 In=1A In=5A Un=100V
MG30
MD32-G
R = Stabilising resistorZ = Protection surge arrester (if required)
L/+
N/-
Display
Microp.
MD32-G
Function
F187GF287GF87N
87G + 87N
A B C
I1A
I1B
I1C
G
25
26
27
28
39
29
30
41
31
4232
43
33
13
12
I2A
I2B
I2C
Z
R Keyboard
Progr.
Int. Fault
=˜˜
˜_
˜̃̃50-60
R5
R4
R3
R2
R1
R3
R2
R1
R4
R5
B3
B2
B1
9 Pin Male
242334/38
1
2
3
14
16
1715
5
6419
2018
8
97
2211
1021
(21)
N.O.
N.C.
(10)
N.O.
N.C.
CS-S+
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
MG30-I
G
In =
In =
13
12
33
43324231
41
30
29
3928
27
26
25
1A
5A MS-SCE1759-R0
Display
Microp.
MG30-I
Funzioni
Function
I>, Z<, Io>
I2>, T>
IC, 60FL
B.I / B.F.
Progr.
Int.fault
KeyboardTastiera
R1
R2
R3
R4
R5
R1
R2
R3
R4
R5
14
3
2
RS485
2110
1122
79
81820
194651517
18
14
3
21
37(b)
38(0)2324
To RexRelay
Expansion
(21 - 22)
N.O. N.C.
(10 - 11)
N.O. N.C.
1/5A
1/5A
1/5A
1/5A
Zc<, >
U, 1
w< Ir>+
cs-s+
Wiring Diagrams
18
• Percentage based transformer differential relay
Transformer Protection Relay
Salient Features
• Display of various parameters, trip count & trip data on 8 digit alphanumeric display
• Separate LEDs for individual fault indication
• Four user programmable output relays
• Built in self supervision & self testing feature help maintenance
• Easy operation by 5 push buttons
• RS485 Port for serial communication with “MSCOM” user friendly software
Model MD32TM
Ordering Information
Description
Device code
Design
Other features
Auxiliary supplyType 1
Type 2
19
Transformer differential
87 RYB
Numeric
Lowset differential
Lowset op time : <=30mS
Highset differential
Highset op time : 6-20mS
Dual slope bias
Highset can be Biased / Unbiased
2nd harmonic restraint setting
5th harmonic restraint setting
Auto correction of CT ratio
Zero sequence compensation
Blocking function
Functions available
Display of parameters
Built in self supervision
RS485 port
1 A or 5 A site selectable
Waveform capture feature
0.2 VA for 5 A, 0.01 VA for 1 A0 010 C to 60 C
< 2kg
8.5 VA
5 C/O, S/R or H/R or Time del
Draw out
121 x 158 x 224
113 x 142
20-110 V AC / DC
88-264 V AC / DC
Burden on CT
Operating temp
Weight
Burden on auxiliary supply
Output contacts
Construction
Dim W x H x D in mm
Panel cutout
MD32T / MD32TM
MD32T
R = Stabilising resistorZ = Protection surgearrester (if required)
L/+
N/-
˜
IEC 255 ˜˜
=
˜̃
˜
87T + 87N
A B C
In1
I1A
I1B
I1C
25
26
27
28
39V1
V2Kv =
V1
V2
29
I2A
I2B
I2C
3041
31423243
Z
33
12
13
R 50-60 Keyboard
Progr.
Int. FaultR5
R4
R3
R2
R1F187TF287TF87N
Function
Microp.
DisplayR1
R2
R3
R4
R5
B3
B2
B1
9 Pin Male
CS-S+
242334/38
1
2
3
14
16
1715
5
6419
2018
8
972211
1021
(21)
N.O.
N.O.
N.C.
N.C.
(10)
V1
V2á
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
1/5A
Wiring Diagrams
20
Salient Features :-
•
•
•
•
•
Display of various parameters, trip count & trip data on LCD screen
Separate LEDs for individual fault indication
Built in self supervision & self testing feature
RS485 port for serial communication with “MSCOM” software
Easy operation by push buttons
• With vector shift protection - UM30A• With df/dt protection - UFD34• With zero sequence Over Voltage / Neutral shift Protection - MC3V
UM30A UFD34 MC3V
Description
Functions available
Output Contacts
Auxiliary supply
Other features
3 Phase V and F relay with vector shift
24, 27d/59d, 47, 59, 59Uo, 78, 81
Numeric
Over fluxing
Two levels of under / over voltage
Two levels of under / over frequency
Zero seq. voltage
Voltage unbalance
Vector shift detection
Display of parameters
Built in self supervision
RS485 Port
3 Ph volt ge and
Frequency relay
81, 27, 59, df/dt, dv/dt
Numeric
Selectable 4 stages
of frequency as under/
over frequency
Selectable 2 stages of
voltage as under/over
voltage
Selectable 2 stages of df/dt
Selectable 1 stages of de/dt
Blocking output and
Blocking Input
Time tagged multiple
event recording
100-125 V
Display of parameters
Built in self supervision
Oscillogarphic recording of
input quantities
RS485 serial communication
port on back panel
Not applicable
0.04 VA
0 0-10 C to 60 C
< 2.5kg
8.5 VA
4 C/O contacts + 1 C/O for self supervision
Drawout
121 x 164 x 224
113 x 142
20-110 V AC/DC or
88-264 V AC/DC
a 3 Ph volt ge and
Frequency relay
27, 59, 47, 59 V 0, 81
Numeric
Two under voltage elements
Two over voltage elements
One under frequency element
One over frequency element
One zero sequence over voltage element
One negative sequence under voltage element
One positive sequence over voltage element
Oscillographic wave form capture
Modbus RTU / IEC870-5-103
Communication Protocols
Display LCD 16 (2 x 8) characters
100-125 V
Display of parameters
Built in self supervision
Modbus RTU / IEC870-5-103
Communication protocols
Front RS232 port for local
Programming
Oscillogarphic recording of input
quantities
RS485 serial communication port on
Back panel
0.1 VA for 1 A, 0.3 VA for 5 A
NA
0 0-10 C to 55 C
< 1.5kg
< 7 VA
4 C/O Contacts + 1 C/O for self supervision
Drawout
83 x 164 x 224
64 x 137
20-110 V AC/DC or
88-264 V AC/DC
a
NA
0.2 VA / phase at UN
010 to 60 C
1 C/O for self supervision
Drawout
121 x 158 x 224
113 x 142
20-110 V AC / DC or
88-264 V AC / DC
8.5 VA0C
< 2kg
3 C/O + (1 N/O + 1 N/C) + separate relay
Device code
Design
Rating
Burden on CT
Burden on PT
Operating temp
Weight
Burden on auxiliary
Construction
Dim W x H x D in mm
Panel cutout
Burden on aux. supply
Type 1
Type 2
Model
Ordering Information
21
Voltage and Frequency Relay
UFD34
L/+
N/-
UFD34
A
B
C
25
26
27
28
39
29
4130
12
13
_
˜˜
˜=
Keyboard
Progr.
Int. FaultR5
R4
R3
R5
R4
R3
R2
R1
R2
R1Display
Microp.
Function
F81 - 1
F81 - 2
F81 - 3
F81 - 4
Fdf / dt
F27 / 59
14
BI<
BI>
CS-S+
9 Pin Male
242334/3812
31416
1715
5
6419
2018
8
972211
1021
(21)
N.O.
N.C.
(10)
N.O.
N.C.
BPMC
KeyboardTastiera
RS232
Progr.
Int.fault
R4
R3
R2
R1
F24
F27
F47
F59
F27d
F59d
Funzioni
Functions
MC3V
Microp.
Display
R4
R3
R2
R1
D1
D2
D3
16
18
17
14
15
13
12
20
21
19
22
321
DigitalInputs
IngressiDigitali
Rele’DI Uscita
OutputRelays
C
A (S+)
B (S-)RS485
R5
R3
R2
R1 16
18
17
14
15
Rele’Di Uscita
OutputRelays
20
21
19
22
1312
3
21
DigitalInputs
IngressiDigitali
RS485
ComuneComune
To I/0 RelayExpansionAll EspansioneDI I/0
D3
D1
D2
H
L
C
A (S+)
B (S-)
4
5
6
7
8
9
A
B
C
EA
UAUC
UBEBEC
10
11
Auxiliary Supply
Alimentazione Ausiliaria
MS - SCE 1834 - R1
MS - SCE 1834 - R1Standard Output
MS - SCE 1835 - R1I/O Output
MC3V
IEC 255
UM30A
A
B
C
EA
UC UA
UBEBEC
13
12
44
3041
293928
27
26
25
IEC 255
24 (-20%) - 110 (+20%) Vac 24 (-20%) - 125 (+20%) Vdc 80 (-20%) - 220 (+20%) Vac 90 (-20%) - 250 (+20%) Vdc
_
˜˜
˜ =
Uo ˜̃̃BT 2 50
Display
Microp.
Function
F27 / 59
F27d / 59d
F59s
F59U
F81
F59 / 81
Progr.
Int. Fault
Keyboard
R1
R2
R3
R4
R4
R3
R5
R5
R1
R2
2110
112279
81820
1946
51517
161432134/382324
(21)
N.O.
N.O.
N.C.
N.C.
(10)
14
BI<
BI>
CS-S+
9 Pin Male
UM30A
L/+
N/-
Wiring Diagrams
22
MV
12
/MC
3V
MC
61
An
X
MC
12
MD
32
TM
MC
31
An
X/
MC
61
An
X
MV
12
/MC
3V
SC
M2
1
UF
D3
4, U
M3
0
MG
30
/M
G3
0I
SP
M2
1
MV
12
MR
P11
MD
32
GS
C1
4S
MP
R3
00
G1
G2
Mo
tor
Mo
tor
MM
30
/M
CO
MP
eta
CO
N L
/R
PM
14
AP
FC
Pa
ne
l
schem
e -
1
MC
61
An
X
sch
em
e -
2sch
em
e -
1sch
em
e -
2
Schematic - Relay Application
23
SP 50297 R2
Registered Office: L&T House, N. M. Marg, Ballard Estate, Mumbai 400 001, INDIA
Khairasol, Degaul AvenueDurgapur 713 212Tel: 2559848, 2559849, 2559844Fax: 0343-2553614e-mail: [email protected]
5, Milanpur Road, Bamuni MaidanGuwahati 781 021Tel: +91 8876554410 / 8876554417Fax: 361-2551308e-mail: [email protected]
II Floor, Vasantha Chambers5-10-173, Fateh Maidan RoadHyderabad 500 004Tel: 040-67015052Fax: 040-23296468e-mail: [email protected]
Monarch Building, 1st FloorD-236 & 237, Amrapali MargVaishali NagarJaipur 302 021Tel: 0141-4385914 to 18Fax: 0141-4385925e-mail: [email protected]
Akashdeep Plaza, 2nd FloorP. O. GolmuriJamshedpur 831 003JharkhandTel: 0657-2312205 / 38Fax: 0657-2341250e-mail: [email protected]
Skybright Bldg; M. G. RoadRavipuram Junction, ErnakulamKochi 682 016Tel: 0484-4409420 / 4 / 5 / 7Fax: 0484-4409426e-mail: [email protected]
3-B, Shakespeare SaraniKolkata 700 071Tel: 033-44002572 / 3 / 4 Fax: 033-22821025 / 7587e-mail: [email protected]
A28, Indira Nagar, Faizabad Road Lucknow 226 016Tel: 0522-4929905 / 04Fax: 0522-2311671e-mail: [email protected]
No: 73, Karpaga Nagar, 8th StreetK. PudurMadurai 625 007Tel: 0452-2537404, 2521068Fax: 0452-2537552e-mail: [email protected]
EBG North Wing Office-Level 2 Gate 7, Powai CampusMumbai 400 072Tel: 022-67052874 / 2737 / 1156Fax: 022-67051112e-mail: [email protected]
12, Shivaji NagarNorth Ambajhari RoadNagpur 440 010Tel: 0712-2260012 / 6606421Fax: 2260030 / 6606434e-mail: [email protected]
32, Shivaji Marg P. O. Box 6223New Delhi 110 015Tel: 011-41419514 / 5 / 6Fax: 011-41419600e-mail: [email protected]
L&T House P. O. Box 119 191/1, Dhole Patil RoadPune 411 001Tel: 020-66033395 / 66033279Fax: 020-26164048 / 26164910e-mail: [email protected]
Crystal Tower, 4th Floor, G. E. RoadTelibandhaRaipur - 492 006Tel: 0771-4283214e-mail: [email protected]
3rd Floor Vishwakarma ChambersMajura Gate, Ring RoadSurat 395 002Tel: 0261-2473726Fax: 0261-2477078e-mail: [email protected]
Radhadaya ComplexOld Padra RoadNear Charotar SocietyVadodara 390 007Tel: 0265-6613610 / 1 / 2Fax: 0265-2336184e-mail: [email protected]
48-8-16, DwarakanagarVisakhapatnam 530 016Tel: 0891-6701125 to 30Fax: 0891-6701139e-mail: [email protected]
Product improvement is a continuous process. For the latest information and special applications, please contact any of our offices listed here.
Electrical Standard Products (ESP) Branch Offices:
REGISTERED OFFICE AND HEAD OFFICEL&T House, Ballard EstateP. O. Box 278Mumbai 400 001Tel: 022-67525656Fax: 022-67525858Website: www.Larsentoubro.com
ELECTRICAL STANDARD PRODUCTS (ESP)501, Sakar Complex I Opp. Gandhigram Rly. Station Ashram RoadAhmedabad 380 009Tel: 079-66304006-11Fax: 079-66304025e-mail: [email protected]
38, Cubbon Road, P. O. Box 5098Bangalore 560 001Tel: 080-25020100 / 25020324Fax: 080-25580525e-mail: [email protected]
131/1, Zone IIMaharana Pratap NagarBhopal 462 011Tel: 0755-3080511 / 05 / 08 / 13 / 17 / 19 Fax: 0755-3080502e-mail: [email protected]
Plot No. 559, Annapurna ComplexLewis RoadBhubaneswar 751 014Tel: 0674-6451342, 2436690, 2436696Fax: 0674-2537309e-mail: [email protected]
SCO 32, Sector 26-D Madhya Marg, P. O. Box 14Chandigarh 160 019Tel: 0172-4646840, 4646853Fax: 0172-4646802e-mail: [email protected]
L&T Construction CampusTC-1 Building, II FloorMount-Poonamallee RoadManapakkamChennai 600 089Tel: 044-2270 6800Fax: 044-22706940e-mail: [email protected]
67, Appuswamy RoadPost Bag 7156 Opp. Nirmala CollegeCoimbatore 641 045Tel: 0422-2588120 / 1 / 5Fax: 0422-2588148e-mail: [email protected]
Larsen & Toubro Limited Electrical Standard ProductsPowai Campus, Mumbai 400 072Customer Interaction Center (CIC)BSNL / MTNL (toll free) : 1800 233 5858Reliance (toll free) : 1800 200 5858Tel : 022 6774 5858, Fax : 022 6774 5859E-mail : [email protected] Website : www.LNTEBG.com