4
The ASCO 5705 8-Device Annunciator makes power management easy: • Consolidates annunciators for up to 8 devices into a single, wall-mountable touch-screen interface. • Monitors and displays critical information from engine-generators, transfer switches, load banks, and surge protection systems. • Provides for remote testing of power genera- tors and transfer switches. • Works with engine-generators from every major manufacturer including: • Caterpillar • Cummins • Generac • Kohler • MTU Provides real-time status and performance insights Provides instant access to critical utility power, engine-generator, transfer switch, load bank, and surge protection information. Trans- mits immediate email and text alerts of alarm conditions and system events. Meets NFPA and Joint Commission compliance requirements Provides required engine-generator and transfer switch safety indicators and shutdowns. Automatically gener- ates NFPA test and utility outage reports. Integrates with Building Monitoring Systems Shares power system data with other monitoring systems, allowing greater analysis of operating data and faster response to changing conditions. Managing critical power equipment can be challenging. Multiple annunciators utilize different interfaces. Generators and transfer switches require local operation for testing. Compliance requires manual data collection and labor-intensive reporting. ASCO PowerQuest ® : 5700 Family Data Sheet

different interfaces. Generators and transfer switches

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: different interfaces. Generators and transfer switches

The ASCO 5705 8-Device Annunciator makes power management easy:

• Consolidates annunciators for up to 8 devices into a single, wall-mountable touch-screen interface.

• Monitors and displays critical information from engine-generators, transfer switches, load banks, and surge protection systems.

• Provides for remote testing of power genera-tors and transfer switches.

• Works with engine-generators from every major manufacturer including: • Caterpillar • Cummins • Generac • Kohler • MTU

Provides real-time status and performance insights

Provides instant access to critical utility power, engine-generator, transfer switch, load bank, and surge protection information. Trans-mits immediate email and text alerts of alarm conditions and system events.

Meets NFPA and Joint Commission compliance requirements

Provides required engine-generator and transfer switch safety indicators and shutdowns. Automatically gener-ates NFPA test and utility outage reports.

Integrates with Building Monitoring Systems

Shares power system data with other monitoring systems, allowing greater analysis of operating data and fasterresponse to changing conditions.

Managing critical power equipment can be challenging. Multiple annunciators utilize different interfaces. Generators and transfer switches require local operation for testing. Compliance requires manual data collection and labor-intensive reporting.

ASCO PowerQuest® : 5700 Family Data Sheet

Page 2: different interfaces. Generators and transfer switches

Alarm Annunciator

• Displays alarm status of all equipment in a single view• Simplifies viewing by intelligently combining alarms• Assesses and displays the most critical alarms• Provides fast access to individual alarm details

Equipment Overview

• Monitors all devices from a single screen• Accesses detailed information about each device• Presents energy usage and load demand data• Tests multiple transfer switches and engine-generators

simultaneously

Generator Annunciator

• Displays NFPA 110 indicators and shutdowns• Activates LED indicator and audible signal whenever

alarm conditions are detected

One-Line Diagrams

• Displays real-time diagrams for each connected device• Displays status of utility and generator power and

bypass transfer switches• Expedites changes to ATS controller settings

Engine Performance Dashboard

• Presents information for each engine-generator• Shows information about engine speed, oil pressure

coolant temp, power output, fuel level, and more• Displays status of utility and generator power and

bypass transfer switches

Dynamic Screens Provide Unparalleled Insight

Page 3: different interfaces. Generators and transfer switches

Automatically generates and distributes reports that comply with NFPA, CALEA,

Joint Commission, and CMS requirements

| Summary of Results |

Created: Jan 13, 2016 05:34:29 AMPeriod: Jan 13, 2016 to Jan 20, 2016

Page 6 of 75Test Report

All Transfer Switches

Name Load Type Total Transfer Time

Calculated Transfer Time

In Emergency(hh:mm:ss)

Transfer Inhibit Conditions

Maximum Passable Time Result

ATS 02 C Critical 8 sec - 01:08:22 - Level 2 (10 sec.)

ATS 03 L Life Safety 8 sec - 01:10:44 - Level 1 (10 sec.)

ATS 04 Q Equipment 27 sec - 01:08:00 - Level 3 (30 sec.) Pass

ATS 07 C Critical 9 sec - 01:09:57 - Level 2 (10 sec.)

ATS 08 L 10 sec - 01:09:19 - Level 1 (10 sec.)

ATS 09 C 9 sec - 01:09:11 - Level 2 (10 sec.)

ATS 10 Q 284 sec - 01:08:00 Load Shed Level 3 (30 sec.) Fail

ATS 12 L 7 sec - 01:09:49 - Level 1 (10 sec.)

ATS 13 Q 30 sec - 01:08:13 - Level 3 (30 sec.) Pass

ATS 14 C 10 sec - 01:08:51 - Level 2 (10 sec.)

ATS 15 E 29 sec - 01:04:52 - Level 4 (40 sec.)

ATS 16 E 30 sec - 01:04:53 - Level 4 (40 sec.)

ATS 17 L 9 sec - 01:10:23 - Level 1 (10 sec.)

ATS 18 C 10 sec - 01:09:19 - Level 2 (10 sec.)

ATS 19 Q 14 sec - 01:08:01 - Level 3 (30 sec.) Pass

ATS 20 E 7 sec - 01:07:06 - Level 4 (40 sec.) Pass

ATS 21 E 7 sec.* - 01:07:07 - Level 4 (40 sec.) Pass

ATS 22 E 7 sec - 01:07:06 - Level 4 (40 sec.) Pass

ATS 23 C 10 sec - 01:09:19 - Level 2 (10 sec.)

ATS 24 E 6 sec - 01:07:07 - Level 4 (40 sec.) Pass

Generator's engine start was triggered by: ATS 35 L at 1/13/2016 4:05:59 AM

Name Load Type Total Transfer Time

Calculated Transfer Time

In Emergency(hh:mm:ss)

Transfer Inhibit Conditions

Maximum Passable Time Result

ATS 35 L - 10 sec - 01:20:33 - Level 1 (10 sec.) Pass

Report Created: 1/13/2016 5:35:32 AM

1/13/2016 4:05:59 AM - 1/13/2016 5:32:12 AMReport Period:

Test Report

75 of6Page:ASCO

Summary of Results

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Pass

Life Safety

Life Safety

Life Safety

Critical

Critical

Critical

Critical

Equipment

Equipment

Mechanical

Mechanical

Equipment

Mechanical

Mechanical

Mechanical

Mechanical

Provides real-time alarm and event messages via email and text.

| Transfer Switch Summary |

Created: Jan 13, 2016 05:34:29 AMPeriod: Jan 13, 2016 to Jan 20, 2016

Page 31 of 75Test Report

Statistics for Electrical ParametersElectrical Parameters Minimum Average Maximum Unit

Total Apparent Power 92 111.63 134 kVA

Total Real Power 74 90.01 109 kW

Voltage (A-B) 455 466.58 479 V

Voltage (B-C) 456 465.93 474 V

Voltage (C-A) 460 467.38 473 V

Frequency 59.92 59.98 60.03 Hz

Power Factor 0.75 0.8 0.87

Total Amps 112 137.45 167 A

Current Phase A 115 141.62 168 A

Current Phase B 110 137.04 201 A

Current Phase C 107 134.65 160 A

Load Type Total Transfer Time

Calculated Transfer Time

In Emergency(hh:mm:ss)

Transfer Inhibit Conditions Result

Equipment 14 sec - 01:08:01 - Pass

Name Location (Amps) Maximum Passable Time

ATS 19 Q Dr Parking 400 Level 3 (30 sec.)

Total Transfer Time is from loss of normal source to transferring to the alternate source. Calculated Transfer Time is the alternate source availability time plus preconfigured time delays. Time used to evaluate if the transfer of the load to the alternate source is at or under the Maximum Passable Time.

Page: 31 of 75

Test Report

Report Period: 1/13/2016 4:05:59 AM - 1/13/2016 5:32:12 AM

Jan 13, 2016 05:34:29 AMReport Created:

ASCO

ASCO

Transfer Switch Summary

LTE 7:48 PM

ALARM NOTIFICATION

To: John Smith Details

See more

4/30/17

ALARM NAME : Low Fuel AlarmALARM OCCURED DATE : 04/30/201711:24:12DEVICE NAME : GEN G1

[email protected]

Search

100%

P

TEST REPORT

TEST REPORT

Automatically Generated

Created: Jan 13, 2016 05:34:29 AM

Period: Jan 13, 2016 to Jan 20, 2016

Saint Dismas University Hospital

160 Park Avenue, Florham Park, NJ 07932

| Generator Run Summary |

Created: Jan 13, 2016 05:34:29 AMPeriod: Jan 13, 2016 to Jan 20, 2016

Page 9 of 75Test Report

Name Location Load Type Power Rating (kW) Current Rating (Amps)

Gen 3 Gen Paralleling System - 2500 434

Total Run Time Total Duration (hh:mm:ss) Minimum Required Test Time

Start: 01/13/2016 04:06:02 AM Stop: 01/13/2016 05:32:11 AM 01:26:09 30 Mins

Run Time Greater Than 30% Nameplate kW Duration Above 30% (hh:mm:ss)

Minimum Required kW

ThresholdkW Result

Start: 1/13/2016 4:17:25 AM Stop: 1/13/2016 4:51:59 AM 00:34:34 750 kW

Page: 13 of 75

Test Report

Report Period: 1/13/2016 4:05:59 AM - 1/13/2016 5:32:12 AM

Jan 13, 2016 05:34:29 AMReport Created: ASCO

Generator Run Summary

Pass

Pass

ASCO Connectivity Units

The ASCO 8-Device Annunciator connects to devices using Ethernet, RS-485 and discrete inputs. Extend network reach using its integrated Ethernet copper or fiber ports.

• UL Type 3R wall-mounted enclosure• 24VDC or 120VAC control power• 30 seconds of power ride-through

Ethernet RS-485 Discrete Inputs Fiber

5160 10 0 0 25161 5 4 0 25162 5 0 64 25163 5 4 64 2

Page 4: different interfaces. Generators and transfer switches

[email protected] • 1-800-800-ASCO (2726)

© April 2017. Publication 2029

ASCO Power Technologies160 Park Avenue, Florham Park, NJ 07932

GeneralCertifications UL 1008 and cUL 1008

Dimensions 20.36 in x 20.30 in x 8.62 in

Mounting UL Type-1 Wall Mount

Weight 45 Lbs

Power Requirement 24 VDC or 120 VAC

CommunicationsWeb Interface HTTP/HTTPS

Open Protocols BACnet/IP and Modbus/TCP

Security AES 128-Bit Encryption

Email SMTP

InterfaceLED Indicators Common Alarm, Battery and LAN Status

Storage 128GB Solid State Drive

Ports 2x Ethernet and USB

Operating Temperatures:

Controller -4° to 140°F

HMI Display 32° to 140°F

Shock Protection IEC 60068-2-27, 50G

Vibration Protection IEC 60068-2-64

Remote PC Access Yes

Specifications

Building Management

System

Engine-Generator Brand A

ATS ASCO

ATS ASCO

ATS Brand C

Load Bank ASCO

Power Meter UnitASCO

SurgeMonitoring System

ASCO

5705 8-Device Annunciator

ASCO Connectivity

Unit

Engine-Generator Brand B

Connects with Power Equipment from Every Major Manufacturer