DGA Oil Sampling Procedures
Use of Metal Cylinders for the Collection of Gas-
in-Oil Samples
Metal cylinders can be used effectively to collect oilsamples from transformers. To obtain a representative
sample it is necessary to use the proper samplingtechnique. Following the procedure below will ensure
that the sample received by the laboratory is reflective
of the oil in the main tank of the transformer. Refer to
ASTM D3613 for complete instructions on thesampling of transformer insulating fluids.
Hold the cylinder i n a vertical positi on at all times.
This will ensure all ai r bubbles ri se to the top and
exi t the container.
Drain the Sampling Valve
Stagnant oil from the lower drain
valve of the transformer must be
removed before the sample iscollected. Also moisture that may
be present in the depression ofthe drain valve must be removed.To achieve this, remove the plugfrom the drain valve and drain
approximately one-half to one
gallon of oil into an oil-waste
container. To the drain valve,attach a plug fitted with a tubing
connector and a section of clear
plastic tubing.
Attach the Tubing to the
ContainerAttach the cylinder's lower valve
fitting to the tubing connectedthe transformer. Attach the
cylinder's upper valve fitting to
the tubing discharging to the
waste oil container.
Open Valves in Ordered
Sequence
Open the valve on the
transformer.
Open the lower cylinder valve(A).
Open the upper cylinder valve
(B).
Allow about 1 quart of oil toflow through the cylinder into the
waste container. Tap the sides of
the cylinder with a tool todislodge air bubbles. Oil running
though the tubing should be free
of air bubbles.
Shut Valves in Reverse Order
Shut the upper cylinder valve(B).
Shut the lower cylinder valve
(A).
Shut the transformer drainvalve.Shake the cylinder then listen
7/29/2019 DGA Oil Sampling Procedures
2/2
and feel for signs of incomplete
filling. If not completely filled,
redo from step 1 of Open Valvesin Ordered Sequence.
Re-Assemble Tr ansformer Valve
and Plug
Disconnect the tubing and
remove the connector from thedrain valve. Replace the original
plug on the drain valve. Applypipe dope or Teflon tape on the
plug threads to insure a good seal
and to prevent rust.
That's it. You should now have a representative sample of the oil from within the
transformer ready to be shipped to the laboratory.
Complete the information on the sample data sheet and prepare the sample for shipment.
Be sure to write down all pertinent information on the sample data sheet.