DETALLES ELECTRICOS

Embed Size (px)

DESCRIPTION

NJKNKJNK

Citation preview

  • ARRANCADOR DIRECTO

    TUBO 3/4" IMC

    CORAZA LIQUID TIGHT 3/4"

    CONECTOR RECTO

    TGB

    CONECTOR RECTO LIQUID TIGHT 3/4"

    CONDUIT SUBTERRANEOCORTE A - A

    CORTE A-A'

    .40

    R.E.M DE .40x.40x.50

    LEVANTE EN LADRILOSENCILLO DE 0.10 x 0.07 x 0.05 M.

    ACERO DE REFUERZO?????????????????????????

    TAPA EN CONCRETO DE3000 PSI E = 0.10 M.

    ???????????????????????

    CON MORTERO 1:4, E = 0.01 M.

    LEVANTE EN LADRILO SENCILLODE 0.10 x 0.07 x 0.05 M.

    .56

    .40

    .40

    DETALLE

    R.E.M DE .40x.40x.50

    .10

    .50

    .10

    MATERIAL SELECCIONADO

    ?????????????????????

    .15

    .35

    .50

    DUCTO ELECTRICO

    MATERIAL DEL SITIO

    3x30 A

    BANCO CONDENSADORES1 MODULOS DE 5 KVAR

    ARRANCADOR YD

    3#10 AWG

    3x30 A

    ????????????????????

    #2 AWG THHN

    ???????????????????

    #6 AWG THHN

    3x30 A

    ??????????????????

    #8 AWG THHN

    3x60 A

    3x30 A

    CONTACTOR

    TABLERO BOMBAS CAPTACION (TBC)

    ARRANCADOR No.4

    TABLERO GENERAL DE BOMBAS (TGB)

    MOTOBOMBA2.5 HP

    ARRANCADOR DIRECTO

    3#10 AWG-CU-THHN +#12 AWG-CU-THHN?????????

    3#10 AWG-CU-THHN +#12 AWG-CU-THHN?????????

    VIENE DE RED AEREA PUNTO DE CONEXION

    3 CORTACIRCUITOS 10 A

    #2 AWG-CU-DDO

    TRANSFORMADOR????????????????????

    13200/220-127V

    10 kVA

    DPS12 kV10 kA

    2 x 3#2/0 AWG-CU-THHN +#2/0 AWG-CU-THHN???????

    3x100A

    3# 4 AWG-CU-THHN +#6 AWG-CU-THHN???????

    TRANSFERENCIAAUTOMATICA 10 kVA

    3x400A

    LIQUID TIGHT 3/4"

    1x20 A 2x20 A 1x20 A 2x20 A

    ALUMBRADO110 V

    TOMAS110 V

    TOMAS220 V

    ALUMBRADO220 V

    MALLA DE TIERRAESC: 1:50

    DATOS DE ENTRADAResistividad del terreno (Ohm.m) p 30Corriente de falla (kA) If 12Tiempo de despeje (s) tc 0,50??????????????????????????????? A 30.09Resistividad capa acabado (Ohm.m) ps 10.000Espesor capa acabado (m) h 0,10Tension de paso permisible 50kg (V) Es50 164???????????????????????????????????????? Et50 164

    CONFIGURACION DE LA MALLALargo de la malla (m) Largo 5,0Ancho de la malla (m) Ancho 5,0????????????????????????????????? 2Espacio entre conductores paralelo (m) D 2,5Profundidad de la malla (m) H 0,50

    RESISTENCIA CALCULADAResistencia de la malla H>0,25 Rg 3,131Resistencia de la malla H