22
1 1 DESIGNING ENERGY EFFICIENT SYSTEMS Presented by: Jon Rhodes CFC-Solar, Inc [email protected] Sponsored by:

DESIGNING ENERGY EFFICIENT SYSTEMS

  • Upload
    others

  • View
    3

  • Download
    0

Embed Size (px)

Citation preview

Page 1: DESIGNING ENERGY EFFICIENT SYSTEMS

1 1

DESIGNING ENERGY EFFICIENT SYSTEMS

Presented by: Jon Rhodes

CFC-Solar, Inc [email protected] Sponsored by:

Page 2: DESIGNING ENERGY EFFICIENT SYSTEMS

2

ENERGY EFFICIENT DESIGN

Page 3: DESIGNING ENERGY EFFICIENT SYSTEMS

3

ENERGY EFFICIENT DESIGN

Page 4: DESIGNING ENERGY EFFICIENT SYSTEMS

4

ENERGY EFFICIENT DESIGN

Page 5: DESIGNING ENERGY EFFICIENT SYSTEMS

5

ENERGY EFFICIENT DESIGN

• Oversized motors operating on light loads normally have low efficiency.

• Heat buildup in a motor at a 50% overload is not much more then it is under normal operating conditions.

• If a hydraulic system has fluctuating load requirements, working a smaller horsepower motor harder than a larger motor usually results in improved overall efficiency and power factor.

• This also reduces operating costs, size and weight.

RMS Horse power Calculations

Page 6: DESIGNING ENERGY EFFICIENT SYSTEMS

6

RMS HP = HP1² x t1 + HP2² x t2 + ……… t1 + t2 + ……... Charting Step HP HP² Time sec HP² x Sec 1 3 9.0 3 27.0 2 7.5 56.3 10 563.0 3 2.5 6.3 12 75.6 4 12.5 156.3 3 468.8 Totals 28 1134.4 Divide 1134.4 by 28 then take the square root = 6.4 HP

ENERGY EFFICIENT DESIGN

Page 7: DESIGNING ENERGY EFFICIENT SYSTEMS

7

• Next, check the breakdown torque for the next higher motor offered as a standard. In this case consider a 7½ HP motor,( 80 ft. lbs.)

• Divide the breakdown torque by the full load operating torque of that motor times 80%.

• Example: 80 ft. lbs. / 20 ft. lbs. x .80 = 3.20 or 320% • Then take the maximum HP calculated on your chart

and divide by the motor HP from the RMS formulae times 100 gives the minimum breakdown torque required. This must be less then calculated above.

• Example: 12.5 / 7.5 x 100 = 167% • The 7 ½ HP motor would be more than adequate.

ENERGY EFFICIENT DESIGN

Page 8: DESIGNING ENERGY EFFICIENT SYSTEMS

8

• Using “Service Factors” of electric motors. – Amount over the rated name plate horse

power listed on motor that the motor may be loaded continuously and still carry full warrantee from Mfg.

– Standards 1.00, 1.05, 1.10, 1.20, 1.30 – Example: 10 hp with SF 1.3 = 13 HP – Heat buildup in a motor at a 50% overload is

not much more then it is under normal operating conditions.

ENERGY EFFICIENT DESIGN

Page 9: DESIGNING ENERGY EFFICIENT SYSTEMS

9

ENERGY EFFICIENT DESIGN

Bias Spring High pressure spring

(X)

Page 10: DESIGNING ENERGY EFFICIENT SYSTEMS

10

Compare pressure drop across directional valve with a P to T spool to that of a vented pressure relief valve

ENERGY EFFICIENT DESIGN

Page 11: DESIGNING ENERGY EFFICIENT SYSTEMS

11

ENERGY EFFICIENT DESIGN

Page 12: DESIGNING ENERGY EFFICIENT SYSTEMS

12

Orifice

Load Sense Compensator Spool

Stand-by 200 PSI pressure setting

LOW PRESSURE STAND-BY

ENERGY EFFICIENT DESIGN

Page 13: DESIGNING ENERGY EFFICIENT SYSTEMS

13

800 PSI

600 PSI

200 PSI spring AND 600 PSI Hyd pressure

800 PSI

Pump de-strokes to limit pressure

ENERGY EFFICIENT DESIGN

Load sensing at lower pressure

Page 14: DESIGNING ENERGY EFFICIENT SYSTEMS

14

High Pressure Compensator Spool

Maximum Allowable Pressure

200 PSI spring AND 3000 PSI Hyd pressure

3000 PSI

ENERGY EFFICIENT DESIGN

Page 15: DESIGNING ENERGY EFFICIENT SYSTEMS

15

EM

Gage A

Sol. 1A Sol. 1B

3000 PSI

Set Max Compensator to 2700 PSI

Set Load Sense to 300 PSI

Gage C Gage B

Spool selected provides stand-by pressure when in neutral

Using a true servo flapper type pilot saves 1 to 2 amps of power draw when shifting valve. However, the heat generated by the pilot valve must be considered.

ENERGY EFFICIENT DESIGN

Page 16: DESIGNING ENERGY EFFICIENT SYSTEMS

16

ENERGY EFFICIENT DESIGN

Pressure 0 1000 3000

Flow

0

20

40

High flow until reducing valve setting is reached, then load sense across flow control

Flow control can be a proportional valve of a much smaller size.

Load sense spring setting (PSI) should be adjusted to match the max controlled flow with the flow control fully opened for good resolution.

Directly operated non-relieving reducing valve

Page 17: DESIGNING ENERGY EFFICIENT SYSTEMS

17

HORSE POWER/TORQUE LIMITING PUMP

• This feature allows maximum flow up to a pressure that results in reaching the maximum horse power available.

• Pressure above can continue increasing but the flow rate will drop proportionally.

• Example: doubling the pressure will result in half the maximum flow.

• Requires a pressure compensator limiter to control final maximum pressure.

ENERGY EFFICIENT DESIGN

Page 18: DESIGNING ENERGY EFFICIENT SYSTEMS

18

Maximum compensator PSI

High speed

Maximum limit of Electric motor HP

Horse power / torque limiter control

Pressure

Flow

Flow decreases at same rate PSI increases Maintaining max HP limit

ENERGY EFFICIENT DESIGN

Page 19: DESIGNING ENERGY EFFICIENT SYSTEMS

19

Maximum compensator PSI

High speed

Maximum limit of Electric motor HP

Horse power / torque limiter control with load sense and pressure reducing valve

Pressure

Flow

Flow decreases at same rate PSI increases Maintaining max HP limit

ENERGY EFFICIENT DESIGN

Load sense flow control for varying speeds

Page 20: DESIGNING ENERGY EFFICIENT SYSTEMS

20

ENERGY EFFICIENT DESIGN

Things that can affect the efficiency of systems – Conductor sizes and avoidance of elbows. – Use a single pump of correct flow for each actuator. – Variable speed electric motors with fixed volume

pumps. – Avoid flow controls. – Avoid pressure reducing valves. – Weighted fly wheel for additional peak force.

Page 21: DESIGNING ENERGY EFFICIENT SYSTEMS

21

ENERGY EFFICIENT DESIGN

Sizing considerations for efficient systems – Electronic Control Interaction with other Systems – Use increased controls data to precisely match load

demands with hydraulic HP usage – Maximum and Minimum required flow and pressure

conditions – Power to Weight Ratios – Use Accumulators for overall HP reduction

Page 22: DESIGNING ENERGY EFFICIENT SYSTEMS

22

ENERGY EFFICIENT DESIGN