1. THIS STRUCTURE HAS BEEN DESIGNED IN ACCORDANCE WITH THE FOLLOWING LOADING CODES:AS 1170.1 - DEAD & LIVE LOADS & LOAD COMBINATIONS.LIVE LOAD - UNITS - GENERAL.= 1.5kPA.LIVE LOAD - STAIRS, BALCONIES & CORRIDORS. = 3.0kPA.
DESIGN LOADS
1. ALL CONCRETE
WORK SHALL BE IN ACCORDANCE WITH THE CURRENT EDITIONS OF AS 3600 AND AS 1379, EXCEPT WHEREVARIED BY THE CONTRACT DOCUMENTS.2. CONCRETE QUALITY: CONCRETE GRADE TO BE CONCRETE CHARACTERISTIC STRENGTH (f'c) AT 28 DAYS.METHOD OF PLACEMENT - PUMPED TYPE OF ASSESSMENT - PROJECT.3. ALL CONCRETE TO BE ADEQUATELY VIBRATED.4. NO HOLES OR CHASES OTHER THAN THOSE SHOWN ON THE STRUCTURAL DRAWINGS SHALL BE MADE INCONCRETE MEMBERS WITHOUT THE PRIOR APPROVAL OF THE ENGINEER. PIPES OR ELECTRICAL CONDUITSSHALL NOT BE PLACED WITHIN THE CONCRETE COVER TO REINFORCEMENT WITHOUT THE APPROVAL OFTHE ENGINEER. THE CONCRETE COVER TO EMBEDDED PIPES OR CONDUITS SHALL BE A MIN OF 20mm.5. CONSTRUCTION JOINTS SHALL BE MADE ONLY WHERE SHOWN ON THE DRAWINGS OR WHERE APPROVED BYTHE ENGINEER.6. BEAM DEPTHS ARE DESIGNATED FIRST AND INCLUDE SLAB THICKNESS, IF ANY.7. UNDERPINNING WHERE NOT SHOWN ON DRAWINGS MUST BE APPROVED BY THE ENGINEER. FORUNDERPINNING ONLY, f'c = 15MPa.8. ALL CONCRETE SURFACES SHALL BE CURED BY AN APPROVED METHOD FOR SEVEN DAYS IMMEDIATELYAFTER THE CONCRETE IS SET.9. ALL FORMWORK AND PROPPING TO SUSPENDED SLABS AND BEAMS SHALL REMAIN IN POSITION FOR 14DAYS AFTER PLACING CONCRETE UNLESS SPECIFIED OTHERWISE. SUCH FLOOR SHALL REMAIN UNLOADEDFOR 28 DAYS.10. FLOOR SLABS ON GROUND : ALL TOP SOIL AND UPPER STRATA CONTAINING ORGANIC MATTER IS TO BEREMOVED AND REPLACED BY AN APPROVED FILLING MATERIAL COMPACTED AS FOLLOWS:- COHESIONLESSSOILS - MINIMUM DENSITY INDEX = 85% COHESIVE SOILS - ( MAX P.I. = 15%) = 98% STANDARDCOMPACTION.11. BUILDER TO PROVIDE MORTAR UNDER STEEL COLUMNS, BASEPLATES AS SPECIFIED.12. ALL REINFORCEMENT TO COMPLY WITH THE CURRENT EDITIONS OF AS 1302, AS 1303, AS 1304 AND SHALLBE DESIGNATED THUS : N DEFORMED BARS GRADE 500 PLUS Y HOT ROLLED DEFORMED BARS GRADE 400Y RPLAIN ROUND BARS GRADE 250R F WELDED WIRE FABRIC GRADE 450F W STEEL WIRE, PLAIN AND DEFORMED.GRADE 450W ALL FABRIC SHALL BE SUPPLIED IN FLAT SHEETS.13. WELDING OF THE REINFORCEMENT ISN'T PERMITTED UNLESS SHOWN.
ELEMENT CONC. SLUMP MAX. SIZE C'MENT ADMIXTURE GRADE. AGG. TYPE
GROUND LEVELFOUNDATIONSLABS
SUSPENDEDSLABS
CORE FILL
N25 80 20 GP -
-
-
GP
GP
20
10
80
250
INTERNAL N32
EXTERNAL N40
S20
CONCRETE
SITE PREPERATION1. SITE PREPARATION SHALL GENERALLY CONSIST OF CLEARANCE OF VEGETATION FOLLOWED BYEXCAVATION OF TOPSOIL AND MATERIAL TO SUIT FINAL DESIGN LEVELS.2. PROVISION SHALL BE MADE FOR THE DEMOLITION OF ANY EXISTING BUILDINGS INCLUDING BREAKING UPAND REMOVAL OF ANY OLD FOOTINGS, SERVICE PIPES, SEPTIC TANKS ETC WHICH MAY INTERFERE WITH THENEW CONSTRUCTION. ANY SOIL DISTURBED BY DEMOLITION SHALL BE RE-COMPACTED.3. IN THE PROPOSED ON GROUND FLOOR SLAB SUPPORT AND PAVEMENT AREAS, THE EXPOSED SUBGRADESHALL BE UNIFORMLY COMPACTED TO ACHIEVE A DRY DENSITY RATIO OF NOT LESS THAN 98% OF THEMAXIMUM SATURATED VIBRATED DENSITY (AS 1289 TESTS 5.3.1 & 5.5.1). SUBGRADE COMPACTION SHALL BEACCOMPANIED BY GENERAL INSPECTION TO ALLOW DETECTION AND RECTIFICATION OF ANY LOCALISEDCOMPRESSIBLE ZONES WHICH MAY EXIST.4. ANY FILLING PLACED IN THE BUILDING AND PAVEMENT AREAS SHALL BE UNIFORMLY COMPACTED INLAYERS OF NOT MORE THAN 200mm FINAL THICKNESS, UNDER LEVEL 3 SUPERVISION (AS 3798-1990GUIDELINES ON EARTHWORKS FOR COMMERCIAL AND RESIDENTIAL DEVELOPMENTS) TO THE MAX DRYDENSITY RATIO OF 98% SRDD (EXPRESSED AS A % OF THE MAXIMUM VIBRATED DENSITY ESTABLISHED BYTEST METHODS AS 1289 5.3.1, 5.4.1 AND 5.5.1 FOR COHENSIONLESS (SAND) MATERIALS OR ALTERNATIVELY,STANDARD COMPACTION IF APPROPRIATE.)5. ANY IMPORTED FILL SHALL COMPRISE OF LOW PLASTICITY GRANULAR MATERIAL WITH A PLASTICITY INDEXNOT MORE THAN 15%. SAND CUT FROM BASEMENT AREA SHOULD BE SUITABLE FOR REUSE AS FILLING.6. FILLING SHOULD BE RETAINED OR BATTERED TO A SLOPE OF NO STEEPER THAN 1h:1v. ALL EXPOSED FILLINGSHALL BE PROTECTED FROM EROSION. EARTH BATTERS TO BE WHOLLY CONTAINED WITHIN SITEBOUNDARIES & SURFACE DRAINS TO BE INSTALLED TO HIGH SIDE OF ALL STABLE EARTH BATTERS.7. CARE SHALL BE TAKEN TO ENSURE THAT ANY VIBRATORY ROLLING OR CONSTRUCTION ACTIVITIES DO NOTCAUSE DISTRESS (BY WAY OF INDUCED SETTLEMENT) TO ANY ADJACENT MOVEMENT-SENSITIVE FEATURESETC.8. ALL WORK INCLUDING TESTING SHALL BE CARRIED OUT IN ACCORDANCE WITH AUSTRALIAN STANDARDS &RELEVAT CODES OF PRACTICE TO PROVIDE AN ENGINEERED (CONTROLLED) FILLED PLATFORM.9. STRIP BUILDING PLATFORM TO EXTEND 1500mm OUTSIDE BUILDING STRUCTURE FOOTPRINT OF TOPSOIL,DELETERIOUS ORGANICE AND UNCONTROLLED FILL. THE BUILDING PLATFORM SHALL BE RAISED TODESIGNATED LEVEL ABOVE THE NOMINATED Q100 FLOOD LEVEL WITH ENGINEERED FILL & IN ACCORDANCEWITH LOCAL AUTHORITY REQUIREMENTS.10. BUILDING PLATFORM SHALL BE CARRIED OUT IN ACCORDANCE WITH AS 3798 - GUIDELINES ONEARTHWORKS FOR COMMERCIAL & RESIDENTIAL DEVELOPMENT. PLATFORM IMMEDIATELY SURROUNDINGTHE RESIDENCE TO FALL AWAY FROM THE RESIDENCE AT A SLOPE OF 1 : 200 MINIMUM TO AN EARTH DRAIN.THE SURFACE DRAINAGE IS TO DISCHARGE EVENLY WITHIN THE SITE & WITHOUT NUISANCE TO ADJOININGPROPERTIES.11. FOUNDATION MAINTENANCE SHALL BE IN ACCORDANCE WITH THE CSIRO BROCHURE - GUIDE TO HOMEOWNERS ON FOUNDATION MAINTENANCE & FOOTING PERFORMANCES.12. VERIFY ALL BEARING AND DIMENSIONS ON SITE PRIOR TO ANY CONSTRUCTION. ALL MISSING PEGS TO BEREINSTATED PRIOR TO ANY CONSTRUCTION. ALL BUILDERS WORK TO BE CARRIED OUT WITHIN SITEBOUNDARY. THIS NOTE IS TO TAKE PRECEDENCE OVER ANY DOCUMENTATION PROVIDED IN THIS SET OFPLANS. NOTIFY THIS OFFICE IMMEDIATELY OF ANY DISCREPANCIES IN SETOUT DIMENSIONS.13. APPROXIMATE POSITION OF SEWER JUMP UP. VERIFY POSITION ON SITE PRIOR TO CONSTRUCTION.CONNECT 100Dia LINE TO COUNCIL REQUIREMENTS.14. THE FILL USED ON THIS SITE WILL HAVE CONTROLLED PLACEMENT. REFER TO SITE PREPARATION NOTES.15. ALL FENCE LINES, RETAINING WALLS, PATHWAYS, HOT WATER SYSTEM, LETTER BOX, CLOTHESLINE, WATERTANK & DOWNPIPE LOCATIONS TO BE SETOUT BY BUILDER ON-SITE & CONFIRMED BY CLIENT. CLIENT TOPROVIDE NOTICE OF ANY FUTURE SITE WORKS TO PLUMBER TO ENSURE SEWER & STORMWATER CAN BEALIGNED TO ACCOMODATE REQUIREMENTS.16. NEW CONCRETE BOUNDARY CROSS OVER AND COUNCIL INVERT TO LOCAL AUTHORITY SPECIFICATIONS.17. ANY SITE LEVELS PROVIDED ON THIS PLAN HAVE BEEN SUPPLIED BY EXTERNAL CONSULTANTS &TRANSMITTED ONTO THIS SET OF DRAWINGS. THESE LEVELS ARE TO BE TREATED BY THE BUILDER ASAPPROXIMATE ONLY & MUST BE VERIFIED ON SITE PRIOR TO COMMENCING CONSTRUCTION. ANY LEVELDESCREPANCIES ARE TO BE REPORTED TO THIS OFFICE FOR AUTHORIZATION PRIOR TO COMMENCINGCONSTRUCTION. BUILDER TO ARRANGE CONTOUR SURVEY IF REDUCED LEVELS ARE NOT PROVIDED ON THISPLAN.18. DRIVEWAY SLOPE NOT TO EXCEED 1 VERT TO 5 HOR. FOR DRIVEWAY SLOPE REFER TO PART 6.0 OF THE QDCTO ENSURE GRADIENTS & VEHICULAR ACCESS COMPLY WITH STANDARD COUNCIL REGULATIONS.19. SEDIMENT CONTROL MEASURES FOR SOIL & WATER MANAGEMENT MUST BE INSTALLED OR IMPLEMENTEDPRIOR TO DISCHARGE OF WATER FROM THE SITE, SUCH THAT NO EXTERNAL STORMATER FLOW FROM THE SITEADVERSELY AFFECTS SURROUNDING OR DOWNSTREAM PROPERTIES IN ACCORDANCE WITH THEREQUIREMENTS OF THE ENVIRONMENTAL PROTECTION ACT 1994 & THE FNQ ROC DEVELOPMENT MANUAL.20. ALL WATER TO BE DRAINED AWAY FROM BUILDING DURING & AFTER CONSTRUCTION TO COMPLY WITH AS2870.
GENERAL SAFETY NOTES - WPHS1. FALLS, SLIPS, TRIPSa) WORKING AT HEIGHTS DURING CONSTRUCTIONWherever possible, components for this building should be prefabricated off-site or at ground level to minimise the risk ofworkers falling more than two metres. However, construction of this building will require workers to be working at heightswhere a fall in excess of two metres is possible and injury is likely to result from such a fall. The builder should provide asuitable barrier wherever a person is required to work in a situation where falling more than two metres is a possibility.DURING OPERATION OR MAINTENANCECleaning and maintenance of windows, walls, roof or other components of this building will require persons to be situatedwhere a fall from a height in excess of two metres is possible. Where this type of activity is required, scaffolding, ladders ortrestles should be used in accordance with relevant codes of practice, regulations or legislation.Cleaning and maintenance of windows, walls, roof or other components of this building will require persons to be situatedwhere a fall from a height in excess of two metres is possible. Where this type of activity is required, scaffolding, fallbarriers or Personal Protective Equipment should be used in accordance with relevant codes of practice, regulations orlegislation.Anchorage points for portable scaffold or fall arrest devices have been included in the design for use by maintenanceworkers. Any persons engaged to work on the building after completion of construction work should be informed about theanchorage points.b) SLIPPERY OR UNEVEN SURFACESFLOOR FINISHESSpecified finishes have been selected to minimise the risk of floors and paved areas becoming slippery when wet or whenwalked on with wet shoes/feet. Any changes to the specified finish should be made in consultation with the designer or, ifthis is not practical, surfaces with an equivalent or better slip resistance should be chosen.The owner is responsible for the selection of surface finishes in the pedestrian trafficable areas of this building. Surfacesshould be selected in accordance with AS HB 197:1999 and AS/NZ 4586:2004.STEPS, LOOSE OBJECTS AND UNEVEN SURFACESDue to design restrictions for this building, steps and/or ramps are included in the building which may be a hazard to workerscarrying objects or otherwise occupied. Steps should be clearly marked with both visual and tactile warning duringconstruction, maintenance, demolition and at all times when the building operates as a workplace.Building owners and occupiers should monitor the pedestrian access ways and in particular access to areas wheremaintenance is routinely carried out to ensure that surfaces have not moved or cracked so that they become uneven andpresent a trip hazard. Spills, loose material, stray objects or any other matter that may cause a slip or trip hazard should becleaned or removed from access ways.Contractors should be required to maintain a tidy work site during construction, maintenance or demolition to reduce the riskof trips and falls in the workplace. Materials for construction or maintenance should be stored in designated areas away fromaccess ways and work areas.2. FALLING OBJECTS LOOSE MATERIALS OR SMALL OBJECTSConstruction, maintenance or demolition work on or around this building is likely to involve persons working above groundlevel or above floor levels. Where this occurs one or more of the following measures should be taken to avoid objects fallingfrom the area where the work is being carried out onto persons below.1. Prevent or restrict access to areas below where the work is being carried out.2. Provide toeboards to scaffolding or work platforms.3. Provide protective structure below the work area.4. Ensure that all persons below the work area have Personal Protective Equipment.BUILDING COMPONENTSDuring construction, renovation or demolition of this building, parts of the structure including fabricated steelwork, heavypanels and many other components will remain standing prior to or after supporting parts are in place. Contractors shouldensure that temporary bracing or other required support is in place at all times when collapse which may injure persons in thearea is a possibility.Mechanical lifting of materials and components during construction, maintenance or demolition presents a risk of fallingobjects. Contractors should ensure that appropriate lifting devices are used, that loads are properly secured and that accessto areas below the load is prevented or restricted.3. TRAFFIC MANAGEMENTParking of vehicles or loading/unloading of vehicles on this roadway may cause a traffic hazard. During construction,maintenance or demolition of this building designated parking for workers and loading areas should be provided. Trainedtraffic management personnel should be responsible for the supervision of these areas.Construction of this building may require loading and unloading of materials on the roadway. Deliveries should be well plannedto avoid congestion of loading areas and trained traffic management personnel should be used to supervise loading/unloadingareas.Busy construction and demolition sites present a risk of collision where deliveries and other traffic are moving within the site.A traffic management plan supervised by trained traffic management personnel should be adopted for the work site.
4. MANUAL TASKSComponents within this design with a mass in excess of 25kg should be lifted by two or more workers or by mechanical liftingdevice. Where this is not practical, suppliers or fabricators should be required to limit the component mass. All materialpackaging, building and maintenance components should clearly show the total mass of packages and where practical all itemsshould be stored on site in a way which minimises bending before lifting. Advice should be provided on safe lifting methods in allareas where lifting may occur. Construction, maintenance and demolition of this building will require the use of portable tools andequipment. These should be fully maintained in accordance with manufacturer’s specifications and not used where faulty or (inthe case of electrical equipment) not carrying a current electrical safety tag. All safety guards or devices should be regularlychecked and Personal Protective Equipment should be used in accordance with manufacturer’s specification.5. HAZARDOUS SUBSTANCES & POWDERED MATERIALSMany materials used in the construction of this building can cause harm if inhaled in powdered form. Persons working on or inthe building during construction, operational maintenance or demolition should ensure good ventilation and wear PersonalProtective Equipment including protection against inhalation while using powdered material or when sanding, drilling, cutting orotherwise disturbing or creating powdered material.TREATED TIMBERThe design of this building includes provision for the inclusion of treated timber within the structure. Dust or fumes from thismaterial can be harmful. Persons working on or in the building during construction, operational maintenance or demolitionshould ensure good ventilation and wear Personal Protective Equipment including protection against inhalation of harmfulmaterial when sanding, drilling, cutting or using treated timber in any way that may cause harmful material to be released. Do notburn treated timber.VOLATILE ORGANIC COMPOUNDSMany types of glue, solvents, spray packs, paints, varnishes and some cleaning materials and disinfectants have dangerousemissions. Areas where these are used should be kept well ventilated while the material is being used and for a period afterinstallation. Personal Protective Equipment may also be required. The manufacturer’s recommendations for use must becarefully considered at all times.SYNTHETIC MINERAL FIBREFibreglass, rockwool, ceramic and other material used for thermal or sound insulation may contain synthetic mineral fibre whichmay be harmful if inhaled or if it comes in contact with the skin, eyes or other sensitive parts or the body. Personal ProtectiveEquipment including protection against inhalation of harmful material should be used when installing, removing or working nearbulk insulation material.TIMBER FLOORSThis building contains timber floors which have an applied finish. Areas where finishes are applied should be kept well ventilatedduring sanding and application and for a period after installation. Personal Protective Equipment may also be required. Themanufacturer’s recommendations for use must be carefully considered at all times.6. CONFINED SPACESEXCAVATION -Construction of this building and some maintenance on the building will require excavation and installation ofitems within excavations. Where practical, installation should be carried out using methods which do not require workers to enterthe excavation. Where this is not practical, adequate support for the excavated area should be provided to prevent collapse.Warning signs and barriers to prevent accidental or unauthorised access to all excavations should be provided.ENCLOSED SPACESEnclosed spaces within this building may present a risk to persons entering for construction, maintenance or any other purpose.The design documentation calls for warning signs and barriers to unauthorised access. These should be maintained throughoutthe life of the building. Where workers are required to enter enclosed spaces, air testing equipment and Personal ProtectiveEquipment should be provided.SMALL SPACESSome small spaces within this building will require access by construction or maintenance workers. The design documentationcalls for warning signs and barriers to unauthorised access. These should be maintained throughout the life of the building.Where workers are required to enter small spaces they should be scheduled so that access is for short periods. Manual liftingand other manual activity should be restricted in small spaces.7. PUBLIC ACCESSPublic access to construction and demolition sites and to areas under maintenance causes risk to workers and public. Warningsigns and secure barriers to unauthorised access should be provided. Where electrical installations, excavations, plant or loosematerials are present they should be secured when not fully supervised.8. OPERATIONAL USE OF BUILDINGThis building has been designed as a residential building. If it, at a later date, is used or intended to be used as a workplace, theprovisions of the Work Health and Safety Act 2011 or subsequent replacement Act should be applied to the new use.9. OTHER HIGH RISK ACTIVITYAll electrical work should be carried out in accordance with Code of Practice: Managing Electrical Risks at the Workplace, AS/NZ3012 and all licensing requirements.All work using Plant should be carried out in accordance with Code of Practice: ManagingRisks of Plant at the Workplace. All work should be carried out in accordance with Code of Practice: Managing Noise andPreventing Hearing Loss at Work. Due to the history of serious incidents it is recommended that particular care be exercisedwhen undertaking work involving steel construction and concrete placement. All the above applies.
LOAD BEARING MASONRY1. ALL LOAD BEARING MASONRY WORK SHALL BE EXECUTED IN ACCORDANCE WITH THE CURRENT EDITION OF AS3700, EXCEPT WHERE VARIED BY THE CONTRACT DOCUMENTS.2. BUILDER TO ALLOW CLEAN OUT OPENINGS AT THE BASE COURSE OF ALL REINFORCED CONCRETE MASONRYWALLS OR AS INDICATED AND ALL CORES TO BE RAKED CLEAN BEFORE FILLING WITH GROUT.3. GROUT MIX TO FILL CAVITY OR REINFORCED CONCRETE MASONRY WALLS TO HAVE A MINIMUMCHARACTERISTIC COMPRESSION STRENGTH OF 20 MPa(f'c). MAXIMUM SLUMP 250mm AND MAXIMUM AGGREGATESIZE 10mm.4. UN-REINFORCED CONCRETE MASONRY AND BRICKWORK SUPPORTING SLABS AND BEAMS SHALL HAVE A LAYEROF MORTAR PLACED ON TOP AND TROWELLED SMOOTH WITH TWO LAYERS OF BITUMINOUS FELT BETWEEN THISSURFACE AND THE CONCRETE.5. MORTAR CLASSIFICATION- M4.6. MINIMUM CHARACTERISTIC UNCONFINED COMPRESSION STRENGTH OF MASONRY UNITS SHALL BE 15MPa.
RETAINING STRUCTURES1. DO NOT BACKFILL RETAINING WALLS UNTIL 21 DAYS AFTER CONCRETE HAS BEEN PLACED IN THEWALLS OF THE RETAINING STRUCTURES UNLESS NOTED OTHERWISE.2. THE BACKFILL MATERIAL BEHIND THE FULL LENGTH OF THE EARTH RETAINING WALLS SHALL CONSISTOF A COARSE GRAINED SOIL OF HIGH PERMEABILITY (ie CLEAN COURSE SAND OR GRAVEL) TO A MAXWIDTH OF 300mm FOR THE FULL RETAINING HEIGHT.
FOUNDATIONS1. EXCAVATION FOR ALL FOOTINGS SHALL BE TAKEN TO THE DEPTHS SHOWN, OR TO A FOUNDATION STRATACAPABLE OF SAFELY SUSTAINING A BEARING PRESSURE OF 100 kPa WHICHEVER IS THE DEEPER. ALL EXCAVATIONSSHALL BE FREE FROM LOOSE MATERIAL, MUD AND WATER. UNDERSIDE OF ALL FOOTINGS SHALL BE A MIN OF 400mmBELOW NATURAL GROUND LEVEL UNLESS SHOWN OTHERWISE.2. EXCAVATIONS FOR BORED PIERS SHALL BE DONE BY MECHANICAL AUGER OR OTHER APPROVED MEANS, SIDES OFHOLES SHALL BE VERTICAL AND SIDES AND BOTTOM SHALL BE FREE FROM LOOSE MATERIAL. CONCRETE SHALL BEPLACED IN EACH HOLE WITHIN 12 HOURS.3. FINISHED SLAB LEVEL TO BE MINIMUM 225mm ABOVE FINISHED GROUND LEVEL. THIS NOTE IS TO TAKEPRECEDENCE OVER ANY DOCUMENTATION PROVIDED IN THIS SET OF PLANS.
STRUCTURAL STEEL1. ALL WORKMANSHIP AND MATERIALS SHALL BE IN ACCORDANCE WITH THE CURRENT EDITION OF AS 4100 AND AS 1554EXCEPT WHERE VARIED BY THE CURRENT DOCUMENTS.2. UNLESS NOTED OTHERWISE ALL STEEL SHALL BE IN ACCORDANCE WITH: AS 1204 GRADE 250 FOR ROLLED SECTIONS AS 1163 GRADE 350 FOR R.H.S. SECTIONS AS 1163 GRADE 200 FOR C.H.S. SECTIONs AS 1163 GRADE 350 FOR C.H.S. SECTIONS AS 1204 GRADE 350 FOR ALL HIGH STRENGTH STEEL.3. UNLESS NOTED OTHERWISE ALL WELDS SHALL BE CATEGORY SP IN ACCORDANCE WITH CLAUSE 1:3:2 AS 1554-PART 1.4. UNLESS NOTED OTHERWISE ALL WELDS SHALL BE 6mm CONTINUOUS FILLET WELDS.5. HIGH STRENGTH FRICTION GRIP BOLTS, NUTS AND WASHERS (8.8/TF) SHALL COMPLY WITH THE RELEVANTREQUIREMENTS OF AS 1252 AND SHALL BE TIGHTENED TO THE CORRECT TENSION USING APPROVED LOAD INDICATINGWASHERS. CONTACT SURFACES OF ALL HIGH STRENGTH FRICTION GRIP BOLTED CONNECTIONS SHALL BE LEFTUNPAINTED OR AS SPECIFIED.6. UNLESS NOTED OTHERWISE ALL BOLTS SHALL BE OF GRADE 4.6/S.7. ALL DIMENSIONS SHALL BE CHECKED BY THE CONTRACTOR ON SITE PRIOR TO FABRICATION.8. UNLESS NOTED OTHERWISE ON PLANS, WHERE STEEL SIZES PERMIT, ALL STEELWORK IS TO BE SUPERGAL OREQUIVALENT. IN ALL OTHER CASES STEEL WORK IS TO BE SAND BLASTED (2.5) AND COATED WITH ZINC SILICATE STEELPRIMER (OR AS SPECIFIED) BEFORE ERECTION.REINSTATE COATING OF ALL WELDS BY BUFFING SURFACE WITH WIRE BRUSH AND APPLY 2 BRUSH COATS OF ZINC RICHCOATING. PAINT FINISH IN ACCORDANCE WITH MANUFACTURERS SPECIFICATION. STEELWORK ENCASED IN CONCRETE IS NOT TO BE PAINTED.9. THE STEEL FABRICATOR SHALL PROVIDE ALL BOLTS NECESSARY FOR THE ERECTION OF THE STEELWORK ANDBOLTHOLES AND CLEATS NECESSARY FOR THE ERECTION OF TIMBER WORK WHETHER OR NOT DETAILED IN THEDRAWINGS.10. ALL LAPS, FIXINGS AND ACCESSORIES TO PURLINS AND GIRTS TO BE STRICTLY IN ACCORDANCE WITH THEMANUFACTURERS REQUIREMENTS.
WATERPROOFING1. ANY EXPOSED STRUCTURAL TIMBER WHICH HAS ANY AREA IN CONTACT WITH ANOTHER MATERIAL AND WHICHWILL BE INACCESSIBLE AFTER FIXING IS TO BE GIVEN A COAT OF PRIMER BEFORE FIXING2. PROVIDE APPROVED WATERPROOFING MEMBRANE TO ALL WET AREA FLOORS & TILED WALLS & TOP OF ALLEXTERNAL SUSPENDED SLAB FLOORS IN ACCORDANCE WITH BUILDING CODE OF AUSTRALIA & A.S. 3740.3. PROVIDE APPROVED WATERPROOFING MEMBRANE TO ALL FLOOR SLABS & FOUNDATION / RETAINING WALLS INCONTACT WITH GROUND & APPLY STRICTLY IN ACCORDANCE WITH MANUFACTURER'S SPECIFICATIONS.
ENERGY EFFICIENCY1. REFER TO ENERGY EFFICIENCY RATING REPORT FOR EXTENT OF INSULATION, CEILING FANS, DRAUGHT SEALS,GLAZING TYPE, WALLS & ROOF COLOUR, ETC. REPORT TO TAKE PRECEDENCE OVER ALL DOCUMENTATIONPROVIDED IN THIS SET OF WORKING DRAWINGS.2. COMPLY WITH THE CURRENT MANDATORY SUSTAINABLE HOUSING MEASURES UNDER THE QUEENSLANDDEVELOPMENT CODE MP-4.1 INCLUDING;* 3 STAR RATED SHOWER ROSES AND TAPWARE TO KITCHEN SINKS, BATHROOM BASINS AND LAUNDRY TUBS.* 4 STAR RATED DUAL FLUSH TOILETS & SHOWER ROSE.* ANY IRRIGATION SYSTEM MUST BE WATER EFFICIENT IN RELATION TO THE CODE.* ENERGY EFFICIENT LIGHTING TO BE UTILISED FOR 80% OF ALL LIGHT FITTINGS TO ILLUMINATE THE INTERNALFLOOR SPACE.* INSTALLATION OF MIN. EER 2.9 FOR HARD WIRED AIR-CONDITIONERS
ELECTRICAL NOTESIF ANY ELECTRICAL OR LIGHTING POSTIONS ARE NOT CLEAR ON PLAN. PLEASE USE OWN DISCRETION OTHERWISECALL THIS OFFICE FOR ASSITANCE IF UNSUREALL ELECTRICAL WORK MUST COMPLY WITH RELEVANT AUSTRALIAN STANDARDS.1. METER BOX LOCATION TO BE DETERMINED BY ELECTRICIAN ON SITE (CLOSEST PRACTICAL LOCATION TOCONNECTION).2. ENERGY EFFICIENT LIGHTING TO COMPLIANCE WITH THE QUEENSLAND DEVELOPMENT CODE MP-4.1 FORLIGHTING. ENERGY EFFICIENT LIGHTING IS TO BE UTILISED FOR 80% OF ALL LIGHT FITTINGS OF THE INTERNAL FLOORSPACE.3. CONTRACTER TO VERIFY HEIGHT OF ALL WALL MOUNTED ELECTRICAL FIXTUERS4. THE PROVISION FOR "A/C" LOCATIONS ARE OPTIONAL ONLY AND MUST BE CONFIRMED ON SITE BEFORECONSTRUCTION OF BLOCKWORK5. LOCATION OF ALL "SPLIT A/C" AS SHOWN TO BE VERIFIED BY BUILDING OWNER, SUPPLY AND INSTALL "SPLIT A/C"BY OTHERS UNLESS NOTED OTHERWISE IN THE BUILDING SPECIFICATION.6. ALL A/C CONDENSATION WASTES TO BE INSTALLED IN WALLS WHERE POSSIBLE, OTHERWISE RUN IN SLAB.7. SELF CONTAINED SMOKE ALARMS MUST BE SUPPLIED, INSTALLED AND MAINTAINED AND SHALL COMPLY WITHA.S. 3786 AND MUST BE CONNECTED TO THE CONSUMERS MAIN POWER. SMOKE DETECTORS SHOWN ON THIS PLANSPECIFIES THE MINIMUM STANDARDS ONLY, AND WE REFER YOU TO THE PUBLICATION "SMOKE ALARMS SAVES LIVES 1997"FOR RECOMMENDED PROCEDURES AND SPECIFICATIONS
TERMITE CONTROLIN ACCORDANCE WITH AS 3660.1.THIS STRUCTURE IS TO BE PROTECTED AGAINST TERMITES BY HAVING THE PRIMARY BUILDING ELEMENTS & ANYTIMBER SKIRTINGS, ARCHITRAVES, WINDOW REVEALS & DOOR JAMBS BUILT OF MATERIALS CONSIDERED NOT TO BESUSCEPTIBLE TO TERMITE ATTACK.ALL ROOF TIMBERS ARE TO BE PRESERVATIVE TREATED IN ACCORDANCE WITH APPENDIX B OF AS 3660.12 DURABILITY NOTICES INDICATING THE METHOD OF PROTECTION, THE DATE THE METHOD PROTECTION WASINSTALLED AND THE SCOPE AND FREQUENCY OF FIXTURE INSPECTIONS FOR TERMITE ACTIVITY IS TO BE INSTALLED INTHE METERBOX & PANTRY.THE RECOMMENDED FREQUENCY OF FIXTURE INSPECTIONS TO BE SPECIFIED ON THE NOTICE IS : EVERY 6 MONTHSMINIMUM, & THE RECOMMENDED SCOPE IS : INSPECTIONS OF THE PERIMETER OF THE BUILDING AT GROUND LEVEL,INSPECTIONS OF ALL AREAS OF THE BUILDING AND IMMEDIATE AREA OF THE BUILDING WHICH CAN BE ACCESSEDINCLUDING THE ROOF SPACE.CONCRETE SLAB TO HAVE TERMITE RESISTANT MATERIALS USED TO ALL SLAB PENETRATIONS OR ALL STRUCTURALTIMBER & TRUSSES TO BE TERMITE RESISTANT GRADE OR BE TREATED FOR TERMITE RESISTANCE (H2 INTERNAL, H3EXTERNAL HAZARD LEVEL) IF CHEMICAL BARRIER USED ON GROUND NOTE LIFE EXPECTANCY KEEP GARDEN BEDS AMINIMUM OF 1 METRE AWAY FROM ALL EXTERNAL WALLS. ALL PRIMARY BUILDING ELEMENTS (SKIRTING, ARCHITRAVES,JAMBS, ETC) ARE TO BE PROTECTED AGAINST TERMITE INFESTATION IN ACCORDANCE WITH A.S 3600.1. OWNER IS TOVISUALLY INSPECT AROUND HOUSE FOR TERMITE ACTIVITY EVERY 12 MONTHS MINIMUM & TAKE PRECAUTIONS IFREQUIRED.
TIMBER1. ALL WORK SHALL COMPLY WITH THE RELEVANT BUILDING ACT AND ALL CODES REFERRED TO THEREIN.2. ALL STRUCTURAL TIMBER SHALL BE GRADE F14 UNSEASONED, UNLESS NOTED OTHERWISE.3. THE DESIGN, ERECTION AND BRACING OF PREFABRICATED ROOF TRUSSES SHALL BE IN ACCORDANCEWITH THE MANUFACTURERS REQUIREMENTS. UNLESS NOTED OTHERWISE.4. ALL FRAMING AND CONNECTION DETAILS SHALL BE IN ACCORDANCE WITH - AS1684.3 RESIDENTIAL TIMBER- FRAMED CONSTRUCTION - CYCLONIC.
RAINWATER DRAINAGE
A. PLUMBER AND DRAINER INSTALLATION TO COMPLY WITH THE PLUMBING AND DRAINAGE ACT 2002 (PDA) AND THESTANDARD PLUMBING AND DRAINAGE REGULATION 2003 (SPDR).
B. LICENSED PLUMBER TO INSPECT SITE PRIOR TO QUOTATION & CONFIRM ALL EXISTING PLUMBING WITH COUNCILINSPECTOR. ANY DESCREPANCIES MUST BE REFERRED TO THIS OFFICE FOR AUTHORIZATION PRIOR TOCOMMENCING CONSTRUCTION OTHERWISE NO RESPONSIBILITY WILL BE TAKEN BY BALAY.
C. ALL DRAINAGE SHALL BE 100mm DIA uPVC RUN AT MINIMUM GRADE OF 1.65% (1:60) U.N.O.D. ALL VENT PIPES LOCATIONS TO BE DETERMINED ONSITE BY CONTRACTOR & TERMINATE IN ACCORD. WITH AS
3500 2.2 SECTION 6.7.4.E. ALL IO's UNDER CONCRETE TO BE TAKEN TO SURFACE LEVEL AND FITTED WITH APPROVED SCREW CAP.F. WHERE PVC PIPES PENETRATE OR ARE BUILT INTO WALLS OR SLABS, THE PIPES SHALL BE LAGGED WITH
APPROVED MATERIAL IN ACCORDANCE WITH AUSTRALIAN STANDARDS.G. MAXIMUM DISTANCE OF UN-VENTED BRANCH DRAIN IS 10 METRES TO FIXTURES, ORG's OR DG's.H. MATERIALS, DRAINAGE, SOIL, WASTE AND VENT PIPES AND FITTINGS uPVC CLASS DWV TO AS 1260.I. ALL WC's TO BE SCREW FIXED TO FLOOR WITH NYLON PLUGS AND NON-CORROSIVE METAL SCREWS.J. ALL DISCHARGE PIPES RECEIVING CONDENSATE WASTE INCLUDING TRAPS SHALL BE INSULATED.K. ALL PIPES LAID UNDER SLABS TO BE MINIMUM DEPTH OF 400mm TO INVERT LEVEL AND SHALL BE INSULATED.L. PROVIDE FLOOR WASTES TO ALL WET AREAS.M. PLUMBING AND DRAINAGE INSTALLATION TO COMPLY WITH THE PLUMBING AND DRAINAGE ACT 2002 (PDA) AND
THE STANDARD PLUMBING AND DRAINAGE REGULATION 2003 (SPDR)N. ALL FLOOR WASTES TO HAVE 100mm DIA RISERS AND REMOVABLE SCREW GRATESO. MAX 500kPa WATER PRESSURE. IF GREATER, INSTALL PRESSURE LIMITING DEVICE IN ACCORDANCE WITH
MANUFACTURER'S SPECIFICATIONS.
RAINFALL INTENSITY OF 282mm/hr - CAIRNS
IN ACCORDANCE WITH PART 3.5.2 OF THE BCA, THE ROOF AREA PER DOWNPIPE IS CALCULATED USINGhttp://www.roof-gutter-design.com.au/ IN ACCORDANCE WITH AS 2179 & AS 3500.3.1. SIZE OF UPVC STORMWATER PIPELINES TO SUIT DOWNPIPE & HAVING A SMOOTH (NON-PROFILED) INTERNAL BORE WITHA FALL OF 1:100 MIN AS PER PART 3.1.2 OF THE BCA & IN ACCORDANCE WITH AS 3500.32.2. EXTEND STORMWATER LINES TO STORMWATER EASEMENT, KERB & CHANNEL OR STORMWATER PITS & DISPOSE OF ATLEGAL POINT OF DISCHARGE COMPLYING WITH LOCAL AUTHORITY & INSPECTOR STANDARDS.3. SIZE & LOCATIN OF STORMWATER PITS WITH REMOVABLE GRATED LID VERIFIED BY BUILDER & CONTRACTOR ON SITE.4. PROVISIONS FOR OVERFLOWS MUST BE MADE FOR DOWNPIPES FURTHER THAN 1200mm FROM VALLEY
PLUMBING NOTES
SITE DRAINAGEGRADE FINISHED GROUND LEVEL TO ENSURE WATER IS DIVERTED AWAY FROM NEIGHBOURING PROPERTIES & TOKERB & CHANNEL OR STORMWATER EASEMENT IF AVAILABLE. PLATFORM IMMEDIATELY SURROUNDING THERESIDENCE TO FALL AWAY FROM THE RESIDENCE AT A SLOPE OF 1 : 200. SURFACE DRAINAGE IS TO DISCHARGEEVENLY WITHIN THE SITE & WITHOUT NUISANCE TO ADJOINING PROPERTIES. REFER TO SITE PREPARATION NOTES& COMPLY WITH AS 3798 - GUIDELINES ON EARTHWORKS FOR COMMERCIAL & RESIDENTIAL DEVELOPMENT.
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
As indicated
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
M
54 EVANS ROAD BRAMSTON BEACH
COVER PAGE
matt piromalli
ALAN FLEAY
MP
15595 01
C208-05-2017
02 SCALE 1 : 800
1 LOCALITY MAP
DRAWING SCHEDULE
# SHEET NAME ISSUE REV
01 COVER PAGE 08/05/2017 M
02 FLOOR PLANS & ELEVATIONS 08/05/2017 M
03 CROSS SECTIONS 08/05/2017 J
04 WINDOW & DOOR SCHEDULE 08/05/2017 K
05 FOOTINGS & DRAINAGE PLANS 08/05/2017 B
06 SUSPENDED SLAB & CEILING PLANS 08/05/2017 B
07 LINTEL & BLOCKWORK PLANS 08/05/2017 B
08 ROOF FRAMING PLANS & DETAILS 08/05/2017 B
09 FOOTING DETAILS 08/05/2017 B
SCALE
3 BEACH PERSPECTIVE
SCALE
2 STREET PERSPECTIVE
Issue Revision Description Date
A CONCEPT SKETCHES 19/12/2014
B DESIGN DRAWINGS 06/01/2015
C REDESIGN BASED ON CLIENT SKETCH 30/01/2015
D PRELIMINARY DRAWINGS 05/03/2015
E CLIENT CHANGES 16/03/2015
F REMOVE BOAT GARAGE 18/09/2015
G MIRRORED RESIDENCE 28/10/2015
H CHANGES TO COASTAL WORKS AS REQUESTED BYSTATE DEPARTMENT OF INFASTRUCTURE
05/02/2016
I LODGEMENT TO DEPT INFASTRUCTURE 21/03/2016
J DEPT INFASTRUCTURE CHANGES 16/05/2016
K CLIENT CHANGES - VOID 12/07/2016
L PRELIMINARY WORKING DRAWINGS 20/03/2017
M CONSTRUCTION DRAWINGS 08/05/2017
DN
DN
LOWER FL4.50LOWER FL 4.50
UPPER FL7.90
12
1190128001500
UPPER PITCH10.80UPPER PITCH 10.80
2900
3400
D03
W09
W01
RFG
RNA
A03
A03
RFG
600
6300
SNB
RNB RNC
RNA
SNA
D02
SNA
SNB
TMA
RNA
SNB
DPB
DPE
DPB
GCB
DPB
LOWER FL4.50LOWER FL 4.50
UPPER FL7.90
1500128001190
UPPER PITCH10.80UPPER PITCH 10.80
2900
3400
6300
D04
RFG
RNC
RNB
RNC
BLABLA
SNB
A03
A03
W16 W18
RNA
RNC
W04
SNASNA
SNB
SNB
SNBSNBRNB
BLD
TMATMA
SNC
RNA
GCB
DPB
DPB
LOWER FL4.50
UPPER FL7.90
40240
UPPER PITCH10.80
LOWER PITCH 7.70
3200
3100
W10
W11
W02
RNC
RFG
RNA
B03
B03
C03
C03
RNB
W05
RFG
RNA
2900
3400
front
bou
ndar
y lin
e
r ear
bou
ndar
y lin
e
W06
RNB
SNB
RNCRND
SNASNA
TMATMA
SNA
SNB
2100
2600
DPB
GCB
DPB
SNB
DPB
DPB
DPB
CA B
LOWER FL4.50
UPPER FL7.90
UPPER PITCH10.80
2900
3400
RNBRNB
RFG
W15
W13W12W17
W03
B03
B03
C03
C03
RFG
W14
W08 W07RNA
RNAD01
W02
SNA
SNB
SNB
RNDRNC
SNA
TMA TMA
TMA
2100
1500
1500
2600
1800
GCB
DPB
DPE
DPESNB
GCB
DPBDPBDPB
C AB
17700 7700 4330
02
4
02
3
02
1
02
2
1
2
VOID OVER
GATE
LIN
E O
F V
OID
OV
ER
LIN
E O
F F
LOO
R O
VE
R
FR
BBQ
4330 7700 17700 10510
FL= 4.50
FL= 4.40
PREPBENCH
SHW
27.2
8 P
LD
24.7
8 O
XX
XX
O S
GD
42.1
0 F
14.1
6 A
L
08.08 AL
20.24 F
920
200 7500200
2370 1200 1730 5700200
5000 1800
COASTAL SETBACK
10010
1800 150070
130070
126070
1530200
3600 5000
200
3300
1800
3390
3500
200
6900
1280
094
020
0
B03
B03
A03
A03
C03
C03
LIVING
ENTRY
KITCHEN
PDR
LAUNDRYWORKSHOP
DOUBLE GARAGE
POOL
TERRACE20.10 F
AC CONDENSOR LOCATION
1500
200
6700
200
5700
1190
200
3300
9300
1190
DRIVEWAY
boun
dary
line
27.2
8 P
LD
PR
OP
OS
ED
10M
CO
AS
TA
L S
ET
BA
CK
LIN
E
24.15 XO SGD
LINENPANTRY
CLOTHESDRYING AREA
GATE
GATE
GATE
20.10 F
20.10 F 20.10 F
LANDSCAPED AREA
GATE
PATH
STEPPING STONES
LANDSCAPED AREA
LIN
E O
F F
LOO
R O
VE
R
LINE OF FLOOR OVER
OH
C1120
10
1A
PANTRYAPPLIANCE RECESS
FR
STEPPING STONES
720 720
920
PLANTER
LINE OF AWNING OVER
940 3960 5100
500
900
50 3300 900 2800 900 2800 900 6600 12000
1000
900
3000
900
1300
50
200
880 2300 900
6650
3700
500
3700
500
1840
100
4080
water blade
PATH
PATH
VOID OVER
vent
DPB DPB DPB
DPBDPBDPB
DPB
DPBDPB
DPB
CA
A
B
B
4330 7700 28210
1
2
FL= 7.90
820
9.81
AL
42.1
0 F
9.58 AL
12.24 XO
17.16 AL08.06 AL 08.06 AL 08.06 AL
24.23 RB
24.23 RB
24.2
9 R
B
110 905300 500
200
100070
393070
53070
4630200
1000
5500 70 3290 70 3570 90 4910 200
2001000
702360
702100
705630 200
2500
200
530
7043
0070
4130
200
800
200
3830
70
53070
430
70
1000
70
2830
200
1000
A03
1280
0
C03
C03
VOID
BRIDGE
BATHENSUITE
LINEN
BED 3
ROBE
BED 2
RO
BE
MASTER BED
ROBE
20.3
6 O
XX
O
20.4
0 O
XX
O
9.53 AL
5400
24.37 RB
2 / 7
20 C
SD
820
820
820
720
HE
AD
BO
AR
D
AWNING OVER BBQ
SHELF
fw
fw
vent
DPB DPB
DPBDPE
DPB
DPBDPBDPBDPB
DPE
C
C
B
B
17700
17700
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
1 : 100
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
M
54 EVANS ROAD BRAMSTON BEACH
FLOOR PLANS & ELEVATIONS
matt piromalli
ALAN FLEAY
MP
15595 02
C208-05-2017
02 SCALE 1 : 100
1 ELEVATION 1
02 SCALE 1 : 100
3 ELEVATION 302 SCALE 1 : 100
4 ELEVATION 4
02 SCALE 1 : 100
2 ELEVATION 2
02 SCALE 1 : 100
A LOWER FLOOR PLAN02 SCALE 1 : 100
B UPPER FLOOR PLAN
RESIDENCE AREAS (m2)
LOWER INTERNAL 124.8 m²
UPPER INTERNAL 108.9 m²
GARAGE 61.0 m²
VOID 47.4 m²
TERRACE 45.2 m²
Grand total 387.3 m²
LEGEND - REFER TO INTERIOR DRAWINGS FOR FINISHES...
BLA SELECTED FRAMELESS TOUGHENED GLASS BALUSTRADE FIXED TOWALL FACE WITH STAINLESS STEEL SPIGOTS TO BCAREQUIREMENTS
BLD SELECTED GLASS POOL FENCE TO QLD DEVELOPMENT CODE MP 3.4REQUIREMENTS
DPB 125 DIA. UPVC DOWNPIPE. REFER TO PLUMBING NOTES
DPE 125 DIA. UPVC DOWNPIPE WITH SPREADER OVER MULTIPLE PANSBELOW
GCB 175 COLORBOND FLAT BACK HALF ROUND GUTTER WITH MINIMUMCROSS SECTIONAL AREA OF 11010 sq.mm
RFG COLORBOND ULTRA CORRUGATED ROOF SHEETING. SCREW FIXEDTO PURLINS / BATTENS AS PER MANUFACTURERS INSTRUCTIONS
RNA SELECT RENDER FINISH. REFER TO SPECIFICATION
RNB SELECT RENDER FINISH. REFER TO SPECIFICATION
RNC SELECT RENDER FINISH. REFER TO SPECIFICATION
RND SELECT RENDER FINISH WITH EXPRESS JOINTS @ 400CTS
SNA SELECT STONE CLADDING. REFER TO SPECIFICATION
SNB SELECT STONE CLADDING. REFER TO SPECIFICATION
SNC SELECT STONE CLADDING. REFER TO SPECIFICATION
TMA SELECTED TIMBER. REFER TO SPECIFICATION
ROOM SCHEDULE - REFER TO FINISH SCHEULE FOR FLOOR FINISH
Name Area Floor Finish
LIVING 64.2 m² TILED
ENTRY 9.0 m² TILED
KITCHEN 20.3 m² TILED
PDR 2.6 m² TILED
LAUNDRY 5.0 m² TILED
WORKSHOP 16.0 m² CONCRETE
DOUBLE GARAGE 40.2 m² CONCRETE
POOL 39.4 m² CONCRETE
TERRACE 46.3 m² TILED
VOID 42.9 m² NA
BRIDGE 17.8 m² TIMBER
BATH 8.0 m² TILED
ENSUITE 10.1 m² TILED
LINEN 1.0 m² TILED
BED 3 15.1 m² CARPET
ROBE 1.3 m² CARPET
BED 2 19.1 m² CARPET
ROBE 1.6 m² CARPET
MASTER BED 21.8 m² CARPET
ROBE 2.0 m² CARPET
LINEN 2.7 m² TILED
PANTRY 2.6 m² TILED
STATE & LOCAL PRE - APPROVALSTHIS SET OF DRAWINGS IS TO BE READ IN CONJUNCTION WITH
THE SITE SPECIFIC CONDITIONS SET BY CAIRNS REGIONALCOUNCIL IN DECISION NOTICE 8/7/3327 & CONCURRENCE
APPROVAL FROM THE DLIGP SPL-0316-029074 CONTACT THIS OFFICE FOR A COPY OF THIS REPORT
Issue Revision Description Date
A CONCEPT SKETCHES 19/12/2014
B DESIGN DRAWINGS 06/01/2015
C REDESIGN BASED ON CLIENT SKETCH 30/01/2015
D PRELIMINARY DRAWINGS 05/03/2015
E CLIENT CHANGES 16/03/2015
F REMOVE BOAT GARAGE 18/09/2015
G MIRRORED RESIDENCE 28/10/2015
H CHANGES TO COASTAL WORKS AS REQUESTED BYSTATE DEPARTMENT OF INFASTRUCTURE
05/02/2016
I LODGEMENT TO DEPT INFASTRUCTURE 21/03/2016
J DEPT INFASTRUCTURE CHANGES 16/05/2016
K CLIENT CHANGES - VOID 12/07/2016
L PRELIMINARY WORKING DRAWINGS 20/03/2017
M CONSTRUCTION DRAWINGS 08/05/2017
LOWER FL4.50LOWER FL 4.50
UPPER FL 7.90
12
UPPER PITCH10.80UPPER PITCH 10.80
A03
A03
1190128001500
3400
DOUBLE GARAGE
W09
W01
RFG
GCB
RNC
CONCRETE SLAB
600
3400
2900
RNB
CDC
D09
SNB
D05
2900
DPB
TRUSS
BATTENS
200RCM
GCB
SNB100
LOWER FL 4.50 LOWER FL4.50
UPPER FL 7.90 UPPER FL7.90
UPPER PITCH 10.80 UPPER PITCH10.80
LOWER PITCH 7.70 LOWER PITCH7.70
B03
B03
C03
C03
3200
2900
SUSPENDED SLAB
D04
W10
DOUBLE GARAGE
VOID
KITCHENLIVING
TERRACE
MASTER BEDBATHENSUITE
TRUSS
RFG
CONCRETE SLAB
TMA
BLA
RFG
3200
2900
W18
CO
AS
TA
L B
OU
ND
AR
Y L
INE
W09
W05W06
RND
SNB
C AB
17700 7700
10510
510
LOWER FL4.50
UPPER FL7.90
1 2
UPPER PITCH10.80
A03
A03
1500128001190
2900
3400
TRUSS
BATTENS
200RCM
RNA
STUD NONLBW
D11D15
BED 3
LINENROBE
D09
W04
ENSUITE
LIVING
POOL
W11
W02
DPB
RFG
SUSPENDED SLAB
STUD NONLBW
RFG
GCB
CONCRETE SLAB
CEILING CEILING
SNB
200RCM
CEILING
200RCM
POOL
200RCM
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
1 : 50
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
J
54 EVANS ROAD BRAMSTON BEACH
CROSS SECTIONS
matt piromalli
ALAN FLEAY
MP
15595 03
C208-05-2017
02 SCALE 1 : 50
B SECTION B
02 SCALE 1 : 50
A SECTION A
02 SCALE 1 : 50
C SECTION C
LEGEND - REFER TO INTERIOR DRAWINGS FOR FINISHES SPECIFICATION
200RCM 200 SERIES REINFORCED CONCRETE MASONRY WALL. REFER TO WALL NOTES
BATTENS ROOF BATTENS. REFER TO ROOF BATTEN NOTES FOR SIZE AND CTS
BLA SELECTED FRAMELESS TOUGHENED GLASS BALUSTRADE FIXED TO WALL FACE WITH STAINLESSSTEEL SPIGOTS TO BCA REQUIREMENTS
CDC SELECTED FIBRE CEMENT CLADDING. REFER TO SPECIFICATION
CEILING CEILING BATTENS AS SCHEDULED. REFER TO NOTES FOR SIZE & CTS
CONCRETE SLAB REINFORCED CONCRETE SLAB. REFER TO FOOTINGS PLAN & DETAILS
DPB 125 DIA. UPVC DOWNPIPE. REFER TO PLUMBING NOTES
GCB 175 COLORBOND FLAT BACK HALF ROUND GUTTER WITH MINIMUM CROSS SECTIONAL AREA OF11010 sq.mm
POOL REFER TO POOL CONTRACTORS DRAWINGS FOR ENGINEERS DESIGN AND CERTIFICATION
RFG COLORBOND ULTRA CORRUGATED ROOF SHEETING. SCREW FIXED TO PURLINS / BATTENS AS PERMANUFACTURERS INSTRUCTIONS
RNA SELECT RENDER FINISH. REFER TO SPECIFICATION
RNB SELECT RENDER FINISH. REFER TO SPECIFICATION
RNC SELECT RENDER FINISH. REFER TO SPECIFICATION
RND SELECT RENDER FINISH WITH EXPRESS JOINTS @ 400CTS
SNB SELECT STONE CLADDING. REFER TO SPECIFICATION
STUD NONLBW NON LOADBEARING TIMBER STUD FRAMED WALL. INTERNAL WALL FINISH U.N.O. TO BEPLASTERBOARD & FIBRE CEMENT TO ALL WET AREAS TYP
SUSPENDED SLAB REINFORCED CONCRETE SUSPENDED SLAB. REFER TO SUSPENDED SLAB PLANS & DETAILS
TMA SELECTED TIMBER. REFER TO SPECIFICATION
TRUSS PRE-FABRICATED ROOF TRUSSES. REFER TO TRUSS NOTES FOR CTS
Issue Revision Description Date
A PRELIMINARY DRAWINGS 05/03/2015
B CLIENT CHANGES 16/03/2015
C REMOVE BOAT GARAGE 18/09/2015
D MIRRORED RESIDENCE 28/10/2015
E CHANGES TO COASTAL WORKS AS REQUESTED BYSTATE DEPARTMENT OF INFASTRUCTURE
05/02/2016
F LODGEMENT TO DEPT INFASTRUCTURE 21/03/2016
G DEPT INFASTRUCTURE CHANGES 16/05/2016
H CLIENT CHANGES - VOID 12/07/2016
I PRELIMINARY WORKING DRAWINGS 20/03/2017
J CONSTRUCTION DRAWINGS 08/05/2017
DN
TOP OF BANK
TOP OF BANK
KE
RB
& C
HA
NN
EL
METER
OUTDOOR
OUTDOOR
SHOWER
SINK
WATER
POLEPOWER
TELSTRA
2.75 2.75 3.25 3.25 3.75 3.75
3.75
3.25
2.50 2.50 3.00 3.00
3.5
3.50 3.50 4.0 4.00
3.5
3.5
4.0
1
2
4330 7700 17700 10510
1190
1280
0
DEMOLISH BUILDING & REMOVE ALLEXISTING STRUCTURE FROM SITE.
REFER TO SITE PREPARATION NOTES
REMOVE TREE
CA B
NORTH
1 1
2 2
4330 7700 17700 10510
1190
1280
0
FL= 4.50
FL= 4.40
GARAGE
LOWER LEVEL TERRACE
POOL
CROSSOVERin accordancewith FNQROQ
manual
NORTH
EXISTING
EXISTING
PLANTER
CA B
10004
1
2
1280
0
D17
D11
D15
W10
W11
W15W13 W12 W17W14
W18
W16
D14
D16
D18
D10
D19 D13
D12
RFC
RFC
RFG
RFG RFG
RFG
GCB
GCB
GCB
GCBDPB
DPB DPB DPB
DPB DPB
DPB
1°
22°
22°
22°
22°
C
C
A
A
B
B
7700 17700
7700 17700
1
2
D03
D04
D05
W01
W03
W04
W02
1280
0
W05W06
D02
W07 W08
D09
D01
D08
D07
D06
C
C
A
A
B
B
7700 17700
7700 17700
25°
25°
25°
GCB
GCB
RFG
B03
B03
A03
A03
C03
C03
22°
22°
22°
25°
22°
RFG
RFG
RFG
GCBGCB
GCB
DPB
DPB
DPB
DPB
DPB
DPEDPE
DPB
DPB
box gutteroverflow
through pfc
box gutteroverflow
through pfc
RFC
GBA
DPB
1°
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
As indicated
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
K
54 EVANS ROAD BRAMSTON BEACH
WINDOW & DOOR SCHEDULE
matt piromalli
ALAN FLEAY
MP
15595 04
C208-05-2017
SU
MM
ER
BR
EE
ZE
S
WINTER
BREEZES
WINTER SUN
SUMMERSUN
02 SCALE 1 : 200
7 CONTOUR PLAN02 SCALE 1 : 200
6 SITE PLAN
02 SCALE 1 : 100
5 UPPER WINDOW SCHEDULE
02 SCALE 1 : 100
4 LOWER WINDOW SCHEDULE
WINDOW SCHEDULE
Mark Description Ref Width Height Ref Level Sill Height Head Height Frame Material Glazing Finish
01 SINGLE PANEL FIXED GLASS WINDOW F 1,000 mm 4,200 mm LOWER FL 200 mm 4400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
02 SINGLE PANEL FIXED GLASS WINDOW F 2,400 mm 2,000 mm LOWER FL 400 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
03 SINGLE PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 800 mm 800 mm LOWER FL 1,600 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
04 MULTI PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 1,600 mm 1,400 mm LOWER FL 1,000 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
05 SINGLE PANEL FIXED GLASS WINDOW F 1,000 mm 2,000 mm LOWER FL 400 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
06 SINGLE PANEL FIXED GLASS WINDOW F 1,000 mm 2,000 mm LOWER FL 400 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
07 SINGLE PANEL FIXED GLASS WINDOW F 1,000 mm 2,000 mm LOWER FL 400 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
08 SINGLE PANEL FIXED GLASS WINDOW F 1,000 mm 2,000 mm LOWER FL 400 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
09 MULTI PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 8,100 mm 900 mm UPPER FL 1,500 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
10 MULTI PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 5,800 mm 900 mm UPPER FL 1,500 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
11 DOUBLE PANEL SLIDING GLASS WINDOW XO 2,400 mm 1,200 mm UPPER FL 800 mm 2000 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
12 SINGLE PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 600 mm 800 mm UPPER FL 1,600 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
13 SINGLE PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 600 mm 800 mm UPPER FL 1,600 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
14 MULTI PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 5,300 mm 900 mm UPPER FL 1,500 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
15 MULTI PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 1,600 mm 1,700 mm UPPER FL 700 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
16 FOUR PANEL SLIDING GLASS WINDOW OXXO 3,600 mm 2,000 mm UPPER FL 200 mm 2200 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
17 SINGLE PANEL VARIABLE ALUMINIUM BLADE LOUVRE - TIMBER FINISH AL 600 mm 800 mm UPPER FL 1,600 mm 2400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH POWDERCOAT ALUMINIUM - TIMBER FINISH
18 FOUR PANEL SLIDING GLASS WINDOW OXXO 4,000 mm 2,000 mm UPPER FL 200 mm 2200 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
DOOR SCHEDULE
Mark Description Ref Width (Approx.) Height (Approx.) Level Head Height Frame Material Glazing & Finish
01 TWO PANEL SLIDING GLASS DOOR XO SGD 1,500 mm 2,400 mm LOWER FL 2,400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH PAINT
02 METAL PANEL LIFT GARAGE DOOR PLD 2,800 mm 2,700 mm LOWER FL 2,600 mm METAL POWDERCOAT ALUMINIUM - TIMBER FINISH
03 METAL PANEL LIFT GARAGE DOOR PLD 2,800 mm 2,700 mm LOWER FL 2,600 mm METAL POWDERCOAT ALUMINIUM - TIMBER FINISH
04 SIX PANEL SLIDING GLASS DOOR OXXXXO SGD 7,800 mm 2,400 mm LOWER FL 2,400 mm POWDERCOAT ALUMINIUM - TIMBER FINISH GREY GLASS
05 SINGLE 820 HINGED TIMBER DOOR 920 900 mm 2,400 mm LOWER FL 2,400 mm TIMBER PAINT
06 SINGLE 820 HINGED TIMBER DOOR 920 900 mm 2,400 mm LOWER FL 2,400 mm TIMBER PAINT
07 SINGLE 720 HINGED TIMBER DOOR 720 800 mm 2,400 mm LOWER FL 2,400 mm TIMBER PAINT
08 SINGLE 720 HINGED TIMBER DOOR 720 800 mm 2,400 mm LOWER FL 2,400 mm TIMBER PAINT
09 SINGLE 820 HINGED TIMBER DOOR 1120 1,200 mm 2,400 mm LOWER FL 2,400 mm TIMBER POWDERCOAT ALUMINIUM - TIMBER FINISH
10 DOUBLE CAVITY SLIDING DOOR 2 / 720 CSD 1,440 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
11 THREE PANEL SLIDING ROBE DOOR RB 2,300 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
12 SINGLE 720 HINGED TIMBER DOOR 720 800 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
13 THREE PANEL SLIDING ROBE DOOR RB 3,700 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
14 SINGLE 820 HINGED TIMBER DOOR 820 900 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
15 THREE PANEL SLIDING ROBE DOOR RB 2,300 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
16 SINGLE 820 HINGED TIMBER DOOR 820 900 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
17 THREE PANEL SLIDING ROBE DOOR RB 2,930 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
18 SINGLE 820 HINGED TIMBER DOOR 820 900 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
19 SINGLE 820 HINGED TIMBER DOOR 820 900 mm 2,400 mm UPPER FL 2,400 mm TIMBER PAINT
02 SCALE 1 : 100
3 ROOF PLAN
LEGEND - REFER TO INTERIOR DRAWINGS FOR FINISHES...
DPB 125 DIA. UPVC DOWNPIPE. REFER TO PLUMBING NOTES
DPE 125 DIA. UPVC DOWNPIPE WITH SPREADER OVERMULTIPLE PANS BELOW
GBA STAINLESS STEEL BOX GUTTER. DEPTH DETERMINED BYROOF STRUCTURE. WIDTH & FALL DETERMINED BYHYDRAULIC CONSULTANT.
GCB 175 COLORBOND FLAT BACK HALF ROUND GUTTER WITHMINIMUM CROSS SECTIONAL AREA OF 11010 sq.mm
RFC STRAMIT COLORBOND ULTRA - SPEED DECK ULTRA ROOFSHEETING OR EQUIVALENT. FIXED TO PURLINS / BATTENSAS PER MANUFACTURERS INSTRUCTIONS
RFG COLORBOND ULTRA CORRUGATED ROOF SHEETING.SCREW FIXED TO PURLINS / BATTENS AS PERMANUFACTURERS INSTRUCTIONS
SITE SURVEY & LEVELSUNDERTAKEN BY:JOB NUMBER:
CONTOURS REPRESENTED ON THIS PLAN WERE TRANSMITTEDDIRECTLY FROM SITE SURVEY SUPPLIED BY COMPANY NAMED ABOVEBUILDER TO VERIFY ALL LEVELS, EXISTING ONSITE SERVICES, EXTENT OFTOPOGROPHY, LANDSCAPING ETC NOTED ON THIS SET OF PLANS &REPORT ANY DESCREPANCIES TO THIS OFFICE FOR AUTHORIZATIONPRIOR TO COMMENCING CONSTRUCTION
STAN NOWAK306 / 12 / 2014
PROPERTY INFORMATION
LOT NUMBERPLAN NUMBERLOCALITYSITE AREA
201B8774BRAMSTON BEACH607 m2
WIND CLASS C1SERVICABILITY WIND PRESSURE
0.80 KPa - GENERAL NOTES1.06 KPa - a1.33 KPa - a / 2
WIND CLASS C2SERVICABILITY WIND PRESSURE
0.96 KPa - GENERAL NOTES1.27 KPa - a1.59 KPa - a / 2a = 2.8m
ULTIMATE WIND PRESSURE
1.85 KPa - GENERAL NOTES2.54 KPa - a3.05 KPa - a / 2
ULTIMATE WIND PRESSURE
2.23 KPa - GENERAL NOTES2.06 KPa - a3.68 KPa - a / 2
WINDOW & DOOR SIZES ARE NOMINAL ONLY.ALL DIMENSIONS TO BE CHECKED ON SITE PRIOR TO FABRICATION.ALL HEAD & SILL HEIGHTS ARE TAKEN FROM THE REFERENCE LEVELPROVIDED.PROVIDE DOOR SEALS TO ALL EXTERNAL DOORS & INTERNAL DOORSINTO ROOMS WITH AIR CONDITIONING.GLAZING TO AS1288-1994. CERTIFICATE TO BE SUPPLIED.APPLY 3 COATS TO ALL DOORS & WINDOWS WITH PAINT NOMINATED ASFINISH. FLYSCREENS TO ALL OPENING SASHES, INCLUDING LOUVERS
WINDOW & DOOR NOTES
Issue Revision Description Date
A REDESIGN BASED ON CLIENT SKETCH 30/01/2015
B PRELIMINARY DRAWINGS 05/03/2015
C CLIENT CHANGES 16/03/2015
D REMOVE BOAT GARAGE 18/09/2015
E MIRRORED RESIDENCE 28/10/2015
F CHANGES TO COASTAL WORKS AS REQUESTED BYSTATE DEPARTMENT OF INFASTRUCTURE
05/02/2016
G LODGEMENT TO DEPT INFASTRUCTURE 21/03/2016
H DEPT INFASTRUCTURE CHANGES 16/05/2016
I CLIENT CHANGES - VOID 12/07/2016
J PRELIMINARY WORKING DRAWINGS 20/03/2017
K CONSTRUCTION DRAWINGS 08/05/2017
1 1
2 2
B03
B03
A03
A03
C03
C03
4.00 3.003.50 3.253.75
4.00
3.75
3.00
2.75
2.50
2.502.75
3.75
NATURAL STONE PATH.REFER TO FINISHES SCHEDULE
SF3 SF5
SF
3
SF5
SF5 SF5 SF5
SF
5
SF6
FW1 FW1
SF
5S
F4
SF
4
1300
900
3000
900
1000
50
50 3300 900 2800 900 2800 900 6600 12000
SF4 SF4 SF4
SF
4
50200
880 2300 900
4330 7700 7700 940 3960 5100
900
500
POOL STRUCTURE TO SUPPORTRESIDENCE'S COLUMNS
REFER TO ENGINEERS DRAWINGS
GARAGE
2-N12 x 1500 LONG BARSSET MID-DEPTH IN SLAB.
40 COVER TO CORNER TYP.
FALL50 mm
STEP
100mm
FL= 4.40
FL= 4.50 FL= 4.45
LOWER FLOOR TERRACE
6000
890
NATURAL STONE PATH.REFER TO FINISHES SCHEDULE
NATURAL STONE PATH.REFER TO FINISHES SCHEDULE
PLANTER
FL= 4.20
CROSSOVERin accordancewith FNQROQ
manual
SF
1S
F1
F1
F7
F7
F7
TILED
F1STEP
300mmFALL
20 mm
F1
F3
F3
F1 FALL
30 mm
STEP
50mm
STEPPINGSTONES
FA
LL F
GL
FALL FGL
F4
F4
F4
F6
F4
F2
F1
F4
F3
F1 F2
SF
1
F8
TH2TH
3
FW1
F2 F2
F2
F2
F2
F3
10480 900
REFER TO ENGINEER'S DETAIL
REFER TO ENGINEER'S DETAIL
SF2
TH1
STEPPING STONES. REFER TO INTERIOR DRAWINGS
CA B
1
2
B03
B03
A03
A03
C03
C03
POOL STRUCTURE TO SUPPORTRESIDENCE'S COLUMNS
REFER TO ENGINEERS DRAWINGS
STEPPING STONES
GARAGEFL= 4.40
FL= 4.50 FL= 4.45
LOWER FLOOR TERRACE
PROPOSED 12m2 WASTE TREATMENT AREAREFER TO WASTE WATER MANAGEMENT REPORT
WASTE WATERTANK
PROPOSED 12m2 WASTE RESERVE AREAREFER TO WASTE WATER MANAGEMENT REPORT
2000
2000
2000
890NATURAL STONE PATH.
REFER TO FINISHES SCHEDULE
FL= 4.20
CROSSOVERin accordancewith FNQROQ
manual
dfw
FALL FGL
FALL FGL
FA
LL F
GL
STEPPINGSTONES
FALL FGLFALL FGL
FA
LL F
GL
S.S GRATEDSTORM WATER
GULLY
FALL FGL
S.S GRATEDSTORM WATER
GULLY
PLANTER
wcfw
van dfw tub
sk
stack
ij ij ij ij ijrj
rj
io
ij
org
2730 6000 2000 900
sew
er li
ne -
refe
r to
note
s
sewer line - refer to notes
DPB
DPB DPB DPB
DPB
DPB
DPBDPBDPB
DPB DPB
7700 1800
3500
8700
3900
800
9300
1190
3600 3000 5200 5000 200
400
1000
3700
7100
250
1840
500
3700
500
3700
800
400
3500
300
1549
0
7700 7800 800 9100 500
400
200
7300200
6200 9000 1400 200
4330 24300
1600
9300
940
9100
4700
CA B
4330 7700 17700
1190
1280
015
00
1200 3000 - RESIDENTIAL (REFER NOTE 10) 1200CONSTRUCTIONJOINT
CONCRETE FOOTPATH, WHERE REQUIRED SHALLBE RECONSTRUCTED TO MATCH NEATLY TODRIVEWAY SKAB (1:14 MAXIMUM GRADE)
PROPERTY BOUNDARY
WID
TH
VA
RIE
S
CONSTRUCTIONJOINT
PLAN
1200 VARIABLE FOOTPATH WIDTH
ROAD
PR
OP
ER
TY
BO
UN
DA
RY
DRIVEWAY AS NOTED75mm MINIMUM COMPACTED GRAVELTO 98% STANDARD UNDER CROSSOVER
VARIABLE SLOPETO SUIT PROPERTY
MAX. GRADE 3%
EXPANSION JOINT
RESIDENTIAL VEHICLE CROSSING
KE
RB
HE
IGH
T
TO
MA
TC
H
KE
RB
INV
ER
T
NOTES1. ALL JOINTS TO EXISTING KERBS SHALL BE SAWCUT PRIOR TO BREAKING OUT CONRETE FOR REMOVAL2. CONCRETE IS TO BE N25 min. IN ACCORDANCE WITH AS1379 AND AS3600.3. ALL CONCRETE TO BE BROOM FINISHED.4. WHERE A CONCRETE FOOTPATH ABUTS A CROSSING AN EXPANSION JOINT SHALL BE INSTALLED.5. EXPANSION JOINTS TO BE 10mm THICK, CLOSED CELL CROSS LINKED POLYETHYLENE FOAM (85-150kg/m)6. DEPTHS OF CONCRETE AND REINFORCING STEEL SHOWN ARE MINIMUM REQUIREMENTS FOR GOOD FOUNDATIONS AND AVERAGE TRAFFIC LOADING.WHERE THIS DOES NOT APPLY, DEPTHS OF CONCRETE AND REINFORCING STEEL SHALL BE INCREASED TO SUIT SPECIFIC CONDITIONS.7. WHERE AN EXISTING FOOTPATH IS PRESENT IT IS TO BE SAWCUT AND AN EXPANSION JOINT PROVIDED.8. SUBGRADE TO BE COMPACTED TO 95% STANDARD.9. ALL DIMENSIONS ARE IN MILLIMETRES.
DRIVEWAYEXTENT OF 100 THICK EXPOSED AGGREGATE DRIVEWAY SLAB SHOWN AS INDICATIVE ONLY, BUILDER TO VERIFY EXACT EXTENT WITHCONTRACTOR ON SITE PRIOR TO COMMENCING CONSTRUCTION. THIS OFFICE IS TO BE NOTIFIED IF DRIVEWAY DOES NOT COMPLY WITH ANYPART OF THE QDC 6.0, OTHERWISE NO RESPONSIBLE WILL BE TAKEN BY BALAY. N20 STRENGTH IN ACCORDANCE WITH AS1379 & AS3600.REINFORCEMENT FABRIC TO BE IN ACCORDANCE WITH AS1304 with 50mm COVER (F82min). EXPANSION JOINTS TO BE 10mm THICK, FULL DEPTHCLOSED CELL CROSS LINKED POLYETHYLENE FOAM (85 - 150 kg/m3
DRIVEWAY AS NOTED
COUNTERSUNK TREAD FIXING
12mm TOP PLATE4 / M12 THRU BOLTS TO SLAB
EX. 150UC30 SITE WELD TO RHS
150 x 100 x 5.0 RHSSTEEL STRINGER
12mm BASE PLATE4 / M12 BOLTS TO SLAB
150 x 100 x 5.0 RHSSTEEL STRINGER
POLISHED HWD TIMBER TREADS
STAIR CONSTRUCTION TO COMPLYWITH PART 3.9 OF THE BCA
max
125
STAIR DETAILSCALE 1 : 10
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
As indicated
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
B
54 EVANS ROAD BRAMSTON BEACH
FOOTINGS & DRAINAGE PLANS
matt piromalli
ALAN FLEAY
MP
15595 05
C208-05-2017
02 SCALE 1 : 100
3 FOOTING PLAN
02 SCALE 1 : 100
4 SLAB SET OUT & DRAINAGE PLAN
PLUMBING LEGENDPLUMBING LAYOUT DIAGRAMMATIC ONLY. LICENCED PLUMBER TO NOTIFYTHIS OFFICE IF DIAGRAMATIC LAYOUTS INDICATED ON THIS SET OF PLANSIS NOT SUITABLE OR NON-COMPLIANT PRIOR TO BUILDER LODGINGBUILDING APPLICATION. REFER TO PLUMBING NOTES IN THIS DRAWING SET
sk SINKvan VANITY BASINshw SHOWERbth BATHwc WATER CLOSET SUITEtub LAUNDRY TUBfw FLOOR WASTE GULLYdfw DRY FLOOR WASTEorg OVERFLOW RELIEF GULLYij INSPECTION JUNCTIONrj RODDING JUNCTIONff FROG PLAPvp VENT PIPEorg OVERFLOW RELIEF GULLYdp DOWN PIPE MIN.100Ø U.N.O.hc HOSE COCKfg STAINLESS STEEL FIELD GULLYhwu LOCATION OF HOT WATER UNIT BY BUILDER. U.N.O.
CONCRETE SLAB ON GROUNDU.N.O. THICK CONCRETE REINFORCED BY SL MESH, 30 TOPCOVER ( INTERNAL ) 40 TOP COVER (EXTERNAL) & 1 / N12 TRIMMERALL ROUND. LAID ON 200um VISQUEEN LAPPED 200mm MIN & SEALEDAT JOINTS & PENETRATIONS WITH AN APPROVED TAPE ONGRANULAR FILL COMPACTED TO 98% SRDD. REFER TOCONSTRUCTION NOTES FOR CONCRETE GRADE
100 82
SOIL REPORT DETAILSUNDERTAKEN BY:
SOIL CLASSIFICATION:REPORT No:
DIRT PROFESSIONALS
CLASS 'S'17079
Issue Revision Description Date
A PRELIMINARY WORKING DRAWINGS 20/03/2017
B CONSTRUCTION DRAWINGS 08/05/2017
B03
B03
A03
C03
C03
VOID UPPER FLOOR
SUSPENDED SLAB
280 TK
FL= 7.90
WALLS UNDER SHOWNDASHED. NOT TOENCROACH INTO
SOFFIT OF SLAB. TYP.
30mmSHOWERRECESS
30mm SHOWERRECESS
wc wcbth
shw fw
van
fwvan
shw
stack
3 N16 - 300 T/U EXTRA
N12 - 300 T/U
STAGGER LAPS 1500 MIN600 MIN LAPS DRAPEDTHROUGH STEPS & SET DOWNS
N12
- 30
0 T
/O
ST
AG
GE
R L
AP
S 1
500
MIN
600
MIN
LA
PS
DR
AP
ED
TH
RO
UG
H S
TE
PS
& S
ET
DO
WN
S
N12
- 30
0 T
/O
ST
AG
GE
R L
AP
S 1
500
MIN
600
MIN
LA
PS
DR
AP
ED
TH
RO
UG
H S
TE
PS
& S
ET
DO
WN
S
3 N
16 -
300
T/O
EX
TR
A
3000
6000
500 5400 5300 1000 500
200 5300 12700
800
4200
5100
400
1050
0
6700 400 4600 1000
12700
18200
2200
7100
1200
1050
0
B03
B03
A03
A03
C03
3 N20 - 150 B/U EXTRA
4 N
16 -
300
B/O
EX
TR
A
4 N
16 -
300
B/O
EX
TR
A
3 N
16 -
300
B/O
EX
TR
A
3 N16 - 300 B/O EXTRA
6 N20 - 300 B/U EXTRA
6 N20 - 300 B/U EXTRA
4 N
16 -
300
B/O
EX
TR
A
N16 - 150 B/U
N16
- 15
0 B
/O
6000
6000
N16
- 15
0 B
/O
1
2 2
B03
B03
A03
A03
C03
C03
REFER TO UPPERCEILING PLAN
VOID
VERIFY ALL HEIGHTS & DIMENSIONS WITHTHE REFLECTED CEILING PLAN & DETAILS
WITHIN THE INTERIOR DRAWING SET
1100
1100 1100
1110
1280
0
STAIRS
LIVING TERRACE
LAUNDRYPDRPANTRY
DOUBLE GARAGE
PBAPBA
PBA
PBA
from -LOWER FL
cl : 3000 approx
from -LOWER FL
cl : 2700 approx
from -LOWER FL
cl : 2850 approx
PBB
FCB
FCB
from -LOWER FL
cl : 2850 approx
FCA
FCA
FCA
FCA
from -LOWER FL
cl : 3150 approx
from -LOWER FL
cl : 3150 approx
from -LOWER FL
cl : 3150 approx
from -LOWER FL
cl : 3150 approx
PBBPBB PBB
PBA
PBA
from -LOWER FL
cl : 2500 approx
C
C
A
A
B
B
7700 17700
7700 17700
A03
A03
C03
C03
TGB
TGB
PBA
PBA
PBBPBB
PBA
PBA
PBA
PBAPBA
TGB
TGB
TGB
TGB
VERIFY ALL HEIGHTS & DIMENSIONS WITHTHE REFLECTED CEILING PLAN & DETAILS
WITHIN THE INTERIOR DRAWING SET
from -UPPER FL
cl : 2850 approx
from -UPPER FL
cl : 2850 approx
from -UPPER FL
cl : 2850 approx
from -UPPER FL
cl : 2850 approx
from -UPPER FL
cl : 2850 approx
from -UPPER FL
cl : 2850 approx
BATH ENSUITE
VOID
BED 3
BED 2
MASTER BED
from -UPPER FL
cl : 2400 approx
TGB
C
C
B
B
17700
ELEMENT
PILECAPS, PAD & STRIP FOOTINGS
BORED PIERS
STAIRS
SUSPENDED SLABS
BEAMS
COLUMNS
SLAB ON GROUND
65mm 65mm
75mm 75mm
40mm 20mm
40mm 20mm
40mm 40mm
40mm 40mm
40mm 20mm
REINF. COVER REINF. COVER
EXPOSEDTO
WEATHER
NOTEXPOSED TO
WEATHER
U.N.O. IN THE DRAWINGS
BAR
N12
N16
N20
N24
N28
N32
N36
MIN. LAP LENGTHS
LAP LENGTH
600
750
950
1150
1350
1600
1900
SUSPENDED SLABS
TYPICALLY, TOP OF REINFORCED CONCRETE COLUMNS AND CONCRETEMASONRY WALLS SUPPORTING SUSPENDED SLABS NOT TO ENCROACHINTO SOFFIT OF SLAB
TYICALLY, PROVIDE APPROVED WATERPROOFING MEMBRANE TO TOP OFALL EXTERNAL SUSPENDED SLABS
TO
PL
AN
RE
FE
R
REFER TO GENERAL CONCRETE NOTES FORCONCRETE GRADE
TOP OVER (TO)
TOP UNDER (TU)
BOTTOM OVER (BO)
BOTTOM UNDER (BU)
20 COVER INTERNAL40 COVER EXTERNAL
20 COVER INTERNAL
40 COVER EXTERNAL
GENERAL PLACEMENT DIAGRAM U.N.O.SUSPENDED CONCRETE FLOOR
NOTE:ALL 12mm REINFORCEMENTTO BELAPPED A MINIMUM OF 600mm.ALL 16mm REINFORCEMENTTO BELAPPED A MINIMUM OF 750mm.
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
As indicated
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
B
54 EVANS ROAD BRAMSTON BEACH
SUSPENDED SLAB & CEILING PLANS
matt piromalli
ALAN FLEAY
MP
15595 06
C208-05-2017
02 SCALE 1 : 100
1 SUSPENDED SLAB PLAN - TOP STEEL
02 SCALE 1 : 100
2 SUSPENDED SLAB PLAN - BOTTOM STEEL
02 SCALE 1 : 100
3 LOWER CEILING PLAN02 SCALE 1 : 100
4 UPPER CEILING PLAN
LEGEND - REFER TO INTERIOR DRAWINGS FOR FINISHES...
FCA FIBRE CEMENT EAVE LINING - RAKING EAVE - BUTT FINISH(NO PVC STRIPS) INSTALLED TO MANUFACTURERSINSTRUCTIONS
FCB FIBRE CEMENT EAVE LINING - BOXED EAVE - BUTT FINISH(NO PVC STRIPS) INSTALLED TO MANUFACTURERSINSTRUCTIONS
PBA 10mm FLUSH FINISHED PLASTERBOARD INSTALLED TOMANUFACTURERS INSTRUCTIONS
PBB 10mm FLUSH FINISHED HIGH MOISTURE RESISTANTPLASTERBOARD INSTALLED TO MANUFACTURERSINSTRUCTIONS
TGB SELECTED HWD TONGUE & GROOVE TIMBER SOFFIT LINING- BOXED EAVE
CEILING BATTENS
40 x 35mm TIMBER CEILING BATTENS INSTALLEDTO MANUFACTURERS INSTRUCTIONS.
40 x 35mm TIMBER CEILING BATTENS ANDDROPPERS INSTALLED TO MANUFACTURERSINSTRUCTIONS.
40 x 35mm TIMBER CEILING BATTENS INSTALLEDTO MANUFACTURERS SPECIFICATION.
40 x 35mm TIMBER CEILING BATTENS ANDDROPPERS INSTALLED TO MANUFACTURERSINSTRUCTIONS.
RONDO KEYLOCK CONCEALED SUSPENDEDCEILING SYSTEM OR EQUIVELANT or40 x 35mm TIMBER CEILING BATTENS ANDDROPPERS INSTALLED TO MANUFACTURERSINSTRUCTIONS.
PLASTERBOARDTYP:
PLASTERBOARD TOU/S OF SLAB:
EAVES (RAKING):
EAVES BOXED:
DROPPED INTERNALCEILING
Issue Revision Description Date
A PRELIMINARY WORKING DRAWINGS 20/03/2017
B CONSTRUCTION DRAWINGS 08/05/2017
L1SCALE 1 : 20
1-N16 TOP
1-N16 BTM
L8 LIGS @ 1000 CTS
L3SCALE 1 : 20
1-N16 TOP
1-N16 BTM
L8 LIGS @ 200 CTS
L2SCALE 1 : 20
2-N16 TOP
2-N16 BTM
L8 LIGS @ 200 CTS
2-N16 BTM
N12 @ 600 CTS500 LEG
SUSPENED SLABREINFORCEMENT. REFERTO SUSPENDED SLAB PLAN
L4SCALE 1 : 20
1
2
B03
B03
A03
A03
C03
C03
1190
1280
015
00
HATCHED AREA DENOTESEXCTENT OF FLOOR ABOVE
STAIRS
BBQ AWNING
EN
TR
YA
WN
ING
900 1000 4200 1000 2400 1800 800 1700 1500200
500 2400 700 800 400 4600 500 500
500
2800
500
2800
500
2300
1200
200
1000
400
600
500 1000 4500 1000
300
600
400
4600
300
3900
300
1000
7800
500
200
4000
200
4900
200
1200
1190
1050
023
0015
00
1549
0
4330 7300 200 6200 10206 495 1000
900
900
900
900
L1 L1 L1 L1
L1
L3
L3
L1 L1
L1
L1
L1
L4
L4
L4
L4
L4
L4L4
L1
L1
H = 3200
H = 3200
H =
320
0
H =
320
0
H =
320
0
H =
320
0
H = 3200H = 3200
H =
320
0
H =
320
0
H =
490
0
U/S = 2400
U/S
= 2
400
U/S
= 2
400
U/S = 2400
U/S
= 2
400
U/S
= 2
400
U/S = 2600
U/S = 2600
U/S
= 2
400
U/S
= 2
400
U/S
= 3
000
1000
1600
900
U/S
= 2
400
U/S
= 2
800 U
/S =
280
0
U/S = 2800
U/S = 2800
U/S
= 2
800
U/S
= 2
800
U/S = 2400
U/S = 3200
U/S = 2400
U/S = 3200
U/S = 4400
H = 4900
H = 3600H = 3600H = 3600
H = 3120
H = 3120
H =
312
0
H = 3120
H =
312
0
H =
312
0
H = 3120
H = 3120
H =
312
0
H =
312
0
L4
BOX GUTTER
BO
X G
UT
TE
R
C
C
A
B
12030 17700
4330 25400
A03
A03
C03
C03
5500 1500 600 500 600400
600 700 1600 200400 4600 1000
6000 2200 2400 800 5300 1000
800
400
3600
200
400
4000
700
400
1000
1310
9081
0090
1050
0
1050
0
900
900
900
1010
1010
1010
L1 L1 L1 L1
L2
L2
L3
H =
290
0
H =
290
0
H =
290
0
H =
290
0
H =
252
7
H = 2900
H = 2900
H =
290
0
H = 2900
H =
290
0
U/S
= 2
000
U/S = 2200
U/S = 2200
U/S
= 2
400
U/S
= 2
400
U/S
= 2
400
U/S
= 2
400
U/S
= 2
400
U/S = 2400
U/S
= 2
400
C
C
B
B
17700
17700
A03
A03
C03
C03
H =
252
7
H =
290
0
H =
290
0
H = 2900
H =
290
0
H = 2900
H =
290
0
H =
290
0
H = 2811
H =
290
0
H =
280
7
H = 2667
H = 2900
H = 2900
H = 2900
H =
290
0
1010
1010
1010
900
900
900
900
BW1
BW
1
C
C
B
B
1 1
2 2
H = 3600
H =
490
0
H =
312
0
H = 3120
H = 3120
H =
390
0
H = 4900
H = 3120
H = 3120
H =
312
0
H = 3120
H = 3120
H =
312
0
H =
312
0
H =
312
0
H =
490
0
H = 4900
H = 3200
H =
320
0
H = 3200
H = 3200
H =
320
0
H =
312
0
5300
900
900
900
900
C
C
A
A
B
B
4330 7700 17700
1280
0
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
As indicated
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
B
54 EVANS ROAD BRAMSTON BEACH
LINTEL & BLOCKWORK PLANS
matt piromalli
ALAN FLEAY
MP
15595 07
C208-05-2017
02 SCALE 1 : 100
3 LOWER LINTEL PLAN
02 SCALE 1 : 100
4 UPPER LINTEL PLAN
02 SCALE 1 : 100
1 UPPER BLOCK HEIGHT PLAN02 SCALE 1 : 100
2 LOWER BLOCK HEIGHT PLAN
PLYWOOD BRACING WALLSDENOTES PLYWOOD BRACING WALL TO BE FIXED ONONE SIDE OF WALL IN ACCOR WITH MANUF SPEC &AS1684.3 FOR 6.4 kN/m RACKING RESISTANCE.
DENOTES PLYWOOD BRACING WALL TO BE FIXED ONBOTH SIDES OF WALL IN ACCORDANCE WITH MANUFSPEC & AS1684.3 FOR 12 kN/m RACKING RESISTANCE.
- TOP & BOTTOM PLATES - 45 x 90 MGP10- PROVIDE M12 CYCLONE RODS @ EACH END OFBRACING WALL AND AT 1800 CTS MAX. U.N.O.- PROVIDE ANTI-RACKING CLEATS TO TOP OF BRACINGWALLS IN ACCORDANCE WITH 1684.3 - CYCLONIC
BW1
BW2
LINTEL HEIGHT LEGEND
U/S = 12345 12345mm FROMTO UNDERSIDE OF LINTEL UNLESS NOTED OTHERWISE
HEIGHTS ARE APPROXIMATE ONLY AND TO BE USED ASA GUIDE THAT MUST BE VERIFIED BY THE BUILDER.HEIGHTS DO NOT TAKE INTO CONSIDERATION STEPS &FALLS FROM NOMINATED FL - REFER TO FOOTINGS PLAN
LOWER FL
WALL HEIGHT LEGENDH = 12345 12345mm FROM
TO TOP OF WALL UNLESS NOTED OTHERWISE
HEIGHTS ARE APPROXIMATE ONLY AND TO BE USED AS AGUIDE THAT MUST BE VERIFIED BY THE BUILDER.HEIGHTS DO NOT TAKE INTO CONSIDERATION STEPS &FALLS FROM NOMINATED FL - REFER TO FOOTINGS PLAN
LOWER FL
LINTEL HEIGHT LEGEND
U/S = 12345 12345mm FROMTO UNDERSIDE OF LINTEL UNLESS NOTED OTHERWISE
HEIGHTS ARE APPROXIMATE ONLY AND TO BE USED ASA GUIDE THAT MUST BE VERIFIED BY THE BUILDER.HEIGHTS DO NOT TAKE INTO CONSIDERATION STEPS &FALLS FROM NOMINATED FL - REFER TO FOOTINGS PLAN
UPPER FL
WALL HEIGHT LEGENDH = 12345 12345mm FROM
TO TOP OF WALL UNLESS NOTED OTHERWISE
HEIGHTS ARE APPROXIMATE ONLY AND TO BE USED AS AGUIDE THAT MUST BE VERIFIED BY THE BUILDER.HEIGHTS DO NOT TAKE INTO CONSIDERATION STEPS &FALLS FROM NOMINATED FL - REFER TO FOOTINGS PLAN
UPPER FL
LOAD BEARING STUD WALLSEXTERNAL & INTERNAL LOAD BEARING WALLSSTUDS - 90 x 35 MGP12 @ 450 CTS. (HEIGHT< / eq 3000) - 90 x 35 MGP12 @ 300 CTS. (HEIGHT< / eq 3300) - 90 x 45 MGP12 @ 300 CTS. (HEIGHT> 3300) - 90 x 35 MGP12 NOGGINGS @ 1350 CTS
TOP PL - 2 / 45 x 90 MGP12BTM PL. - 35 x 90 MGP12 TO CONCRETE FLOOR - 45 x 90 MGP12 TO TIMBER FLOORS
CYCL RDS- M12 GALV. CYCLONE RODS @ ENDS, CORNERS, EACH SIDE OF OPENINGS AND 1200 CTS MAX BETWEEN U.N.O. - PROVIDE 2 / M12 CYCLONE RODS @ GIRDER TRUSS
BRACING WALLS INSTALLED IN ACCORD WITH DETAILS PROVIDED BYSTRUCTURAL ENGINEER. REFER RELEVANT DRAWINGS FOR INFO.
NUMBER OF STDS BESIDE OPENING1 STUD = 900 WIDTH 2 STUDS = 1200 - 2100 WIDTH3 STUDS = 2400 - 3000 4 STUDS = 3300 - 4000 WIDTH
LINTELS - UNLESS NOTES OTHERWISESPAN (hyneLVL) SPAN (hyneLVL)900 90 x 45 2400 200 x 451200 130 x 45 2700 245 x 451500 150 x 45 3000 2 / 245 x 451800 170 x 45 36002100 170 x 45 4000
NON LOAD BEARING STUD WALLSINTERNAL WALLS
STUDS - 70 x 35 MGP10 @ 450 CTS. - 70 x 35 MGP10 NOGGINGS @ 1350 CTS
TOP & BTM PL. - 35 x 70 MGP10
BLOW IN WALLS
STUDS - 70 x 35 MGP10 @ 350 CTS. - 70 x 35 MGP10 NOGGINGS @ 1350 CTS
TOP PL. - 35 x 70 MGP10 - FIXED TO CEILING BATTENS BY 2 / No. 3.15 dia.x 75 GROOVED NAILS TO EACH
BATTEN PASSING OVER TOP PLATEBTM PL. - 35 x 70 MGP10 RAMSET TO CONCRETE SLAB @ 900 CTS
Issue Revision Description Date
A PRELIMINARY WORKING DRAWINGS 20/03/2017
B CONSTRUCTION DRAWINGS 08/05/2017
150 150
75 x 12 TK TOP PLATE1 / M16 600 LONG HD BOLTCOGGED INTO RCM WALL
SPECIFIED STEEL ROOF BEAM.REFER TO STRUCTURAL LEGENDFOR SIZE8 TK END PLATE
VERTICAL REINFORCINGREFER TO WALLREINFORCEMENT NOTES
200 SERIES REINFORCED CONCRETEMASONRY BLOCK WALLS. REFER TO WALLREINFORCEMENT NOTES
100 x 38 F11 WALL PLATE CHEMSET TOMASONRY WALL WITH 1 /M16 @ EACH TRUSS1 / HOT DIP GALV FRAMING ANCHOR TO TRUSS
VERTICAL REINFORCING REFERTO STRUCTURAL NOTES
200 SERIES REINFORCED CONCRETEMASONRY BLOCK WALLS. REFER TOCONSTRUCTION NOTES
PRE-FABRICATED ROOF TRUSSES AT 900 MAX.CTS. ERECTED & BRACED IN ACCORDANCEWITH MANUFACTURERS SPECIFICATIONS & TOCOMPLY WITH AS 4440. REFER TO TRUSSMANUFACTURERS DRAWINGS
100 x 38 F11 WALL PLATE CHEMSET TO MASONRYWALL WITH 1 /M16 @ EACH TRUSS1 / HOT DIP GALV FRAMING ANCHOR TO TRUSS
COLORBOND FLASHING
HOT DIP GALVANISED CLEAT & BOLTSREFER TO ROOF TIE DOWN DETAILS
FOR CLEAT & BOLT INFORMATION
BOND BEAM, REFER TO WALLREINFORCEMENT NOTES
VERTICAL REINFORCINGREFER TO WALL REINFORCEMENT NOTES
200 SERIES REINFORCED CONCRETEMASONRY BLOCK WALLS. REFER TO WALL
REINFORCEMENT NOTES
PRE-FABRICATED ROOF TRUSSES, REFER TOROOF PLAN FOR PITCH. INSTALL IN ACCORDANCE
WITH TRUSS MANUFACTURERS DRAWINGS
TIMBER CEILING BATTENS AS SCHEDULED.REFER TO CEILING BATTEN NOTES &
CEILING PLAN FOR FINISH
TIMBER CEILING BATTENS ASSCHEDULED. REFER TO CEILING BATTENNOTES & CEILING PLAN FOR FINISH
TIMBER ROOF BATTENS AS SCHEDULED.REFER TO ROOF BATTEN NOTES
COLORBOND ROOF SHEETING ASSCHEDULED SCREW FIX TO
MANUFACTURERS SPECIFICATIONS.
REINFORCED MASONRY LINTEL.REFER TO LINTEL PLAN & WALLREINFORCEMENT NOTES
COLORBOND FLASHING
PRE-FABRICATED ROOF TRUSSES, REFER TOROOF PLAN FOR PITCH. INSTALL IN ACCORDANCEWITH TRUSS MANUFACTURERS DRAWINGS
TIMBER CEILING BATTENS ASSCHEDULED. REFER TO CEILING BATTENNOTES & CEILING PLAN FOR FINISH
TIMBER ROOF BATTENS AS SCHEDULED.REFER TO ROOF BATTEN NOTES
COLORBOND ROOF SHEETING ASSCHEDULED SCREW FIX TOMANUFACTURERS SPECIFICATIONS.
SELECT CLADDING REFER TOFINISHES SCHEDULE
POWER FIX TOP PLATE TOROOF BEAM @ 450 CTS
HOT DIP GALVANISED CLEAT & BOLTSREFER TO ROOF TIE DOWN DETAILSFOR CLEAT & BOLT INFORMATION
M12 BOLTS HD GALVBOLTS @ 1200
PFC ROOF BEAM ASSPECIFIED
PFC ROOFBEAM 1
PLAN VIEW
PFC ROOF BEAMAS SPECIFIED
150
12 TK GUSSETWELD TO CLEAT & PFC
2 / 12 TK GUSSETWELD TO CLEAT & PFC
2 / 12 TK GUSSETWELD TO CLEAT & PFC
12 TK CLEAT WELD TO PFC 3 / M16 GRADE 8.8 BOLTSTHROUGH BOTH CLEATS
PFC ROOFBEAM 2
12 TK CLEAT WELD TO PFC 23 / M16 GRADE 8.8 BOLTSTHROUGH BOTH CLEATS
12 TK GUSSETWELD TO CLEAT & PFC CLAMP & ALIGN MITRE
& SITE WELD
TD1 DETAILSCALE 1 : 20
REFER CMB WALL NOTES.
SINGLE 50x6.0mm CLEAT.1-N16 THREADED THROUGH.
M16 4.6/S BOLT THROUGHGANGNAIL PLATE 40mmCLEAR OF ANY EDGE.
TD2 DETAILSCALE 1 : 20
REFER CMB WALL NOTES.
SINGLE 50x6.0mm CLEAT.1-N16 THREADED THROUGH.
M16 4.6/S BOLTTHROUGH GANGNAIL
PLATE.
50x3.0 G.I. OVERSTRAP.
TD3 DETAILSCALE 1 : 20
REFER CMB WALL NOTES.
DOUBLE 50x6.0mm CLEAT.1-N16 THREADED THROUGH(ONE EACH SIDE OF TRUSS).
M16 4.6/S BOLT THROUGHGANGNAIL PLATE 40mmCLEAR OF ANY EDGE.
TD4 DETAILSCALE 1 : 20
REFER CMB WALL NOTES.
M16 4.6/S BOLTTHROUGH GANGNAIL
PLATE 40mm CLEAROF ANY EDGE.
50x3.0 G.I. OVERSTRAP.
DOUBLE 50x6.0mm CLEAT.1-N16 THREADED THROUGH(ONE EACH SIDE OF TRUSS).
TD5 DETAILSCALE 1 : 20
REFER CMB WALL NOTES.
SINGLE 50x6.0mm CLEAT.1-N16 THREADED THROUGH.
M16 4.6/S BOLT THROUGHGANGNAIL PLATE 40mmCLEAR OF ANY EDGE.
TD6 DETAILSCALE 1 : 20
REFER CMB WALL NOTES.
M16 4.6/S BOLT THROUGHGANGNAIL PLATE 40mmCLEAR OF ANY EDGE.
DOUBLE 50x6.0mm CLEAT.1-N16 THREADED THROUGH(ONE EACH SIDE OF TRUSS).
TD7 DETAILSCALE 1 : 20
REFER CMB WALL NOTES.
2-M16 4.6/S BOLT THROUGHGANGNAIL PLATE 40mmCLEAR OF ANY EDGE.
DOUBLE 50x6.0mm CLEAT.1-N16 THREADED THROUGH(ONE EACH SIDE OF TRUSS).
W8 LIG FOR EACH CLEAT.
80
TD8 DETAILSCALE 1 : 20
REFER CMB WALL NOTES.
PROVIDE ADDITIONALCLEAT BESIDE EACHSIDE OF TRUSS.
DOUBLE 50x6.0mm CLEAT.1-N16 THREADED THROUGH(ONE EACH SIDE OF TRUSS).
W8 LIG FOR EACH CLEAT.
8080
3-M16 4.6/S BOLT TYP.
UPLIFT RESISTANCE kN(ULTIMATE LIMIT STATE)
TYPE
TD1
TD2
TD3
TD4
TD5
TD6
TD7
TD8
TRUSS JOINT GROUP
J2 J3 J4 JD4 JD5 JD6
20 15 10 16 11 8
35 25 16 23 18 15
49 44 28 44 36 28
76 54 34 54 43 34
20 15 10 16 11 8
49 44 28 44 36 28
93 84 53 84 68 53
128 115 73 115 94 73
NOTE:PROVIDE 2-N12 (MIN.) VERTICAL REINFORCING BARS ADJACENT TOCLEATS WITH TIE-DOWN LOADS GREATER THAN 80kN.
404040
4040
4040
4040
4040
40
REFER TO DETAIL FOREXTENT OF BOND BEAMREINFORCING
TIE-DOWN DETAILS TO ROOF BEAM SIMILAR,WELD CLEAT TO TOP OF ROOF BEAM
A03
A03
C03
C03
408
108
208
TR
US
S
RB2
RB
2
RB2
C3C3
C3
RB
2
RB2
900
900
900
900
900
900
900
10TK HD GALV BASE PLATE2 / M16 CHEMSETS INTOBOND BEAM
408
508
C
C
B
B
17700
1
2
B03
B03
A03
A03
C03
C03
1549
0
1190
1280
015
00
RB
1
RB1
RB1
RB
1
RB
1
170 DEEP SS. BOX GUTTER
180
DE
EP
SS
. BO
X G
UT
TE
R
PR
1
PR1
TR
US
S
VOID
FLOOR OVER
REFER TO SUSPENDED SLAB PLAN
TR
US
S
TR
US
S
900
900
900
900
205
108
608
308
GBA
GBA
PR1
10 TK END PLATE2 / M16 HD GALV BOLTS
2/M20
2/M202/M20
2/M20
2/M20
2/M20
608
C
C
A
B
4330 25400
12030 17700
75 x 12 TK TOP PLATE1 / M20 600 LONG HD BOLTCOGGED INTO RCM WALL
SPECIFIED STEEL ROOF BEAM.REFER TO STRUCTURAL LEGEND FOR SIZE8 TK END PLATE
VERTICAL REINFORCINGREFER TO WALLREINFORCEMENT NOTES
200 SERIES REINFORCED CONCRETEMASONRY BLOCK WALLS. REFER TO WALLREINFORCEMENT NOTES
150 150
500
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
As indicated
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
B
54 EVANS ROAD BRAMSTON BEACH
ROOF FRAMING PLANS & DETAILS
matt piromalli
ALAN FLEAY
MP
15595 08
C208-05-2017
08 SCALE 1 : 10
4 BEAM TO BLOCK WALL
08 SCALE 1 : 20
3 TRUSS TO SIDE OF HIGH BLOCK WALL08 SCALE 1 : 20
1 TRUSS TIE DOWN TO RCM WALL08 SCALE 1 : 20
2 RHS BEAM TO TRUSS
08 SCALE 1 : 10
6 PFC MITRE DETAIL
02 SCALE 1 : 100
8 UPPER ROOF FRAMING PLAN02 SCALE 1 : 100
7 LOWER ROOF FRAMING PLAN
ROOF TRUSSESPRE-FABRICATED ROOF TRUSSES @ 900 MAX. CTS. ERECTED &BRACED IN ACCORDANCE WITH MANUFACTURERSSPECIFICATIONS & TO COMPLY WITH AS 4440. REFER TO TRUSSMANUFACTURERS DRAWINGS.
ROOF BATTENS75 x 38 TIMBER ROOF BATTENS @ 650 MAX. CTS. ENDS & 900 MAX.CTS. INTERIM, FIXED TO EACH TRUSS WITH 1-No.14 TYPE 17 BATTENSCREW.
STRUCTURAL STEELALL STEEL THAT IS EXTERNAL OR NOT CONCEALED WITHINTHE WALLS & ROOF OF THE HOME IS O BE SAND BLAST (2.5)AND COAT WITH ZINC SILICATE STEEL PRIMER (OR ASSPECIFIED) BEFORE ERECTION
STRUCTURAL LEGEND
PR1 C150-19 C SECTION PURLIN @ 600 CTS
RB1 250 PFC ROOF BEAM
RB2 200 x 100 x 4.0 RHS ROOF BEAM
C1 500 x 500 RC MASONRY COLUMN
C2 300 x 300 RC MASONRY COLUMN. 4 N16 VERT REINF+ R6 LIGS @ 300 CTS
C3 100 x 100 x 4.0 SHS COLUMN
08 SCALE 1 : 10
5 BEAM BOTH SIDES OF BLOCK WALL
INSULATIONROOFS GENERALLY - BRADFORD ANTICON R1.3 60mm BONDEDBLANKET INSULATION OVER ROOF BATTENS, UNO WITHIN EER REPORT.
CEILINGS - BRADFORD R.30 GOLD BATTS
WALLS EXTERNAL - SISALATION TO EXTERNAL STUD WALLS.WALLS INTERNAL - BRADFORD R2.0 SOUNDCSREEN INSULATION
VENTILATE ROOF CAVITY WITH SOLAR RIDGE VENT & SOFFIT GRILLS
VENTILATION
Issue Revision Description Date
A PRELIMINARY WORKING DRAWINGS 20/03/2017
B CONSTRUCTION DRAWINGS 08/05/2017
LEGEND - REFER TO INTERIOR DRAWINGS FOR FINISHES...
GBA STAINLESS STEEL BOX GUTTER. DEPTH DETERMINED BY ROOFSTRUCTURE. WIDTH & FALL DETERMINED BY HYDRAULICCONSULTANT.
WATER LEVEL 100
1800
REFER TO ENGINEERS DRAWINGSFOR POOL REINFORCEMENT
NGL
200 SERIES REINFORCEDCONCRETE BLOCKWALL
2600
MA
X
1200
SF2 - FOOTINGSCALE 1 : 20
100 200
BO
UN
DA
RY
LIN
E
600
300
RCM WALL CONCRETE FILLALL CORES
N12 VERTICALREINFORCING @ 400 CTS.
NGL
APPROVED WATERPROOFINGMEMBRANE APPLIED STRICTLY IN
ACCORDANCE WITH MANUF. SPECS
N12 @ 200 CTSFGL
50 x 6.0 TK SS CLEATTHREADED OVER BLOCK REINF2 / S.S M12 THRU DRESSED150 x 50 F14 HWD TIMBER UPRIGHT
200
- 60
0
VA
RIE
S
PATH
SF5 - FOOTINGSCALE 1 : 20
NGL
SINGLE BOND BEAM2/N12 LAPPED MIN 500.
N12 VERTICAL REINF @ 600 CTSPLACED CENTRALLY & LAPPED 600
WITH N12 STARTER BARS
200 SERIES REINFORCEDCONCRETE BLOCKWALL
N12 STARTER BARS LAP 600 PLACEDCENTRALLY @ 600 CTS
F82 MESH EACH FACE
SF6 - FOOTINGSCALE 1 : 20
1800
DRIVEWAY
750
300
900
300
N12 VERTICALREINFORCING
@ 400 CTS.
NGL
APPROVED WATERPROOFINGMEMBRANE APPLIED STRICTLY INACCORDANCE WITH MANUF. SPECS
N12 @ 200 CTS
FGL
200
- 60
0
VA
RIE
S
PATH
SF3 - FOOTINGSCALE 1 : 20
1900
MA
X
BO
UN
DA
RY
LIN
E
100 200
COVER
55
FGL
NGL
100 DIA. AGGREGATE DRAIN WITHRUBBLE SURROUND IN FILTERFABRIC GRADED 1:100 OUTLET
N12 @ 400 CTS
N12 @ 400 CTS600 MIN LAPS
APPROVED WATERPROOFINGMEMBRANE APPLIED STRICTLY INACCORDANCE WITH MANUF. SPECS
N12 STARTER BARS @ 400 CTSLAPPED 600
4N12 500 MIN LAP
N12 @ 400 CTS
COMPACTED BACKFILL TO 98% SRDD
COMPACTEDGRANDULAR
BACKFILL
ALL STORMWATER TO DRAINAWAY FROM WALL TO A
LAWFULL POINT OF DISCHARGE
PROVIDE WALLCONTROL JOINTS
AT 10m MAX.
1200 - FOR 800< H ≤1000
800 - FOR H ≤ 600900 - FOR 600< H ≤800
FW1 - FOUNDATION WALLSCALE 1 : 20
250
4016
050
300 LEG
1N12
NOTE:ALL AGG. DRAINS TO DISCHARGEINDEPENDANTLY TO STORMWATER OUTLET.DO NOT CONNECT TO DOWNPIPES OFSURFACE DRAINAGE SYSTEM
1000
MA
X
"H"
MA
X
1600
SINGLE BOND BEAM2/N12 LAPPED MIN 500.
N12 VERTICAL REINF @ 600 CTSPLACED CENTRALLY & LAPPED 600WITH N12 STARTER BARS
200 SERIES REINFORCEDCONCRETE BLOCKWALL
N12 STARTER BARS LAP 600 PLACEDCENTRALLY @ 600 CTS
MA
X
2600
200 SERIES MASONRY WALLCONCRETE CORE FILLED. PROPWALL UNTIL SLAB POURED & SET
APPROVEDWATERPROOFING
MEMBRANEAPPLIED STRICTLY
IN ACCORDANCEWITH MANUF. SPECS
5-11TM REINFORCING.50 BOTTOM COVER.LAP 500 AS REQUIRED.
600
N12 @ 400 CTS
55 COVER
300
MA
X
1200
NGL
N12 STARTER BARS PLACED TOCOINCIDE WITH VERICALREINFORCEMENT
COMPACTED BACKFILL98% SRDD ABOVE NGL
N12 TRIMMER - 500 MIN LAPS
500 LEG
N12 @ 400 CTS500 MIN LAPS
SF1 - FOOTINGSCALE 1 : 20
FGL.
N12 TRIMMER
REINFORCING MESHREFER FOOTING PLAN.
F1 - FOOTINGF3 - FOOTINGSCALE 1 : 20SCALE 1 : 20
5-11TM REINFORCING.50 BOTTOM COVER.LAP 500 AS REQUIRED.
FGL.
REINFORCING MESHREFER FOOTING PLAN.
F2 - FOOTINGSCALE 1 : 20
5-11TM REINFORCING.50 BOTTOM COVER.LAP 500 AS REQUIRED.
300
600
100
600600
VA
RIE
S
N12 TRIMMER
REINFORCING MESHREFER FOOTING PLAN.
5-11TM REINFORCING.50 BOTTOM COVER.LAP 500 AS REQUIRED.
100
350
100
COMPACTED SAND FILL &VISQUEEN AS PERCONCRETE SLAB NOTES
COMPACTED SAND FILL &VISQUEEN AS PERCONCRETE SLAB NOTES
COMPACTED SAND FILL &VISQUEEN AS PERCONCRETE SLAB NOTES
300 FGL.
N12 TRIMMER
REINFORCING MESHREFER FOOTING PLAN.
F4 - FOOTING F6 - FOOTINGSCALE 1 : 20
SCALE 1 : 20
4-11TM REINFORCING.50 BOTTOM COVER.LAP 500 AS REQUIRED.
FGL.
REINFORCING MESHREFER FOOTING PLAN.
F5 - FOOTINGSCALE 1 : 20
4-11TM REINFORCING.50 BOTTOM COVER.LAP 500 AS REQUIRED.
300
450
100
450 450
VA
RIE
S
N12 TRIMMER
REINFORCING MESHREFER FOOTING PLAN.
4-11M REINFORCING.50 BOTTOM COVER.LAP 500 AS REQUIRED.
100
300
100
COMPACTED SAND FILL &VISQUEEN AS PERCONCRETE SLAB NOTES
COMPACTED SAND FILL &VISQUEEN AS PERCONCRETE SLAB NOTES
COMPACTED SAND FILL &VISQUEEN AS PERCONCRETE SLAB NOTES
300
450
500
300
N12 TRIMMER
REINFORCING MESHREFER FOOTING PLAN.
COMPACTED SAND FILL &VISQUEEN AS PER
CONCRETE SLAB NOTES
F7 - FOOTINGSCALE 1 : 20
4-11M REINFORCING.50 BOTTOM COVER.LAP 500 AS REQUIRED.
WATER LEVEL100
REFER TO ENGINEERS DRAWINGSFOR POOL REINFORCEMENT
TH1 - THICKENINGSCALE 1 : 20
COMPACTED SAND FILL &VISQUEEN AS PER
CONCRETE SLAB NOTES
S.S. POOL FENCINGSPIGOT
TOUGHENED GLASSPOOL FENCING
N16 @ 400 CTS500 MIN LAPS
COMPACTED BACKFILLTO 98% SRDD
100mm
THROAT
SL82 MESH30 TOP COVER
4-L11 TM
25mm REBATE
STAIR CONSTRUCTIONTO COMPLY WITH PART
3.9 OF THE BCA
450
200
NGL
F8 - FOOTINGSCALE 1 : 20
R10 x 300 LONG GALVDOWELS @ 500 CTS
N12 TRIMMER
200
REINFORCING MESHREFER FOOTING PLAN.
300 LONG R10 DOWELS@ 500 CTS
200 10
0
TH2 - THICKENINGSCALE 1 : 20
TH3 - THICKENINGSCALE 1 : 20
N12 TRIMMER
200
REINFORCING MESHREFER FOOTING PLAN.
COMPACTED SAND FILL &VISQUEEN AS PERCONCRETE SLAB NOTES
FGL
REFER TO POOL DRAWINGS
REFER TO POOL DRAWINGS
55 COVER
N12 @ 300 CTS
900
300
N12 VERTICALREINFORCING@ 400 CTS.
NGL
APPROVED WATERPROOFINGMEMBRANE APPLIED STRICTLY IN
ACCORDANCE WITH MANUF. SPECS
N12 @ 200 CTS
FGL
200
- 60
0
VA
RIE
S
PATH
SF4 - FOOTINGSCALE 1 : 20
55 COVER
2200
MA
X
BO
UN
DA
RY
LIN
E
50200
N12 @ 300 CTS
N12 @ 300 CTS
90 x 35 DRESSED HWD NOGGINGS.S SCREW FIX BETWEEN EACH UPRIGHT
3010
050
20
200
Drawing Title...
Designer...
Scale @ A1...
Project Name...
Issue...
WE HERBY CERTIFY THE STRUCTURAL DETAILSAS SHOWN ON THESE DRAWINGS FORCONSTRUCTION IN WIND CLASSIFIATION
C.M.G.ACN 011 065 375
208 BUCHAN ST.CARINS QLD 4870PH (07) 4031 2775FAX. (07) 4051 9013
CONSULTINGENGINEERS PTY LTD
THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTYOF BALAY BUILDING DESIGN AND IS COPYRIGHT . THIS DESIGN REMAINS THE
COPYRIGHT OF BALAY BUILDING DESIGN & SHALL NOT BE RETAINED, REPRODUCEDOR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THE
AUTHOR & OWNER OF THESE DRAWINGS - MATT PIROMALLI
Drawn...
Job #...
WIND CLASS
(CYCLONIC)
GENERAL NOTES
208 BUCHAN STREET CAIRNS PO BOX 7206 CAIRNSPHONE: 07 4051 8228 FAX: 4051 8229 www.balay.com.au qbsa1060131
THIS DRAWING IS COPYRIGHT TO Cba lay building design
1. ALL DESIGN, CONSTRUCTION METHODS AND MATERIALS TO BE IN ACCORDANCE WITH: * THE BUILDING CODE OF AUSTRALIA (BCA). * THE QUEENSLAND DEVELOPMENT CODE (QDC). * BUILDING REGULATIONS. * CURRENT ISSUES OF AUSTRALIAN STANDARDS * MANUFACTURERS SPECIFICATIONS AND INSTALLATION DETAILS FOR MATERIALS USED.2. ALL PLANS ARE TO BE READ IN CONJUNCTION WITH THE CONSTRUCTION NOTES PROVIDED INTHIS SET OF DRAWINGS.3. REFER TO BUILDERS SPECIFICATION WHERE A FINISH OR BUILDING COMPONENT HAS NOTBEEN NOMINATED WITHIN THE DOCUMENTATION PREPARED BY THIS OFFICE. THIS SET OFDRAWINGS AND ALL ACCOMPANING DOCUMENTATION TO TAKE PRECIDENCE OVER INCLUSIONSNOMINATED IN BUILDRS SPECIFICATION.4. DO NOT SCALE FROM DRAWINGS, ONLY FIGURED DIMENSIONS SHALL BE USED. ANYDESCREPANCIES MUST BE REFERRED TO THIS OFFICE OTHERWISE NO RESPONSIBILITY WILL BETAKEN BY BALAY. IF IN DOUBT - JUST ASK.5. ALL DIMENSIONS SHALL BE CHECKED ON SITE PRIOR TO COMMENCING CONSTRUCTION.6. THIS DRAWING AND THE MANUFACTURER OF IT'S CONTENTS IS THE PROPERTY OF BALAY ANDIS COPYRIGHT. THIS DESIGN REMAINS THE COPYRIGHT OF BALAY & SHALL NOT BE RETAINED,REPRODUCED OR TRANSMITTED WITHOUT WRITTEN PERMISSION & AUTHOIRITY FROM THEOWNER & PRINCIPAL BUILDING DESIGNER - MATT PIROMALLI
CONSTRUCTION ISSUE
DATE
1 : 20
Z:\M
y D
oc
um
en
ts (
Z)\
Bà
lay B
uil
din
g D
esig
n\B
àla
y 1
5\1
55
95
-Fle
ay\c
Dra
win
gs &
Sp
ec
ific
ati
on
s\c
.1 D
raw
ing
s -
Cu
rre
nt\
15
59
5-M
.rvt
B
54 EVANS ROAD BRAMSTON BEACH
FOOTING DETAILS
matt piromalli
ALAN FLEAY
MP
15595 09
C208-05-2017
BLOCK WALL REINF UNDER ROOF
BLOCK WALL REINF UNDER SLAB1. PROVIDE SINGLE COURSE BOND BEAM IMMEDIATLY BELOW FIRSTFLOOR LEVEL SLAB. REINF. WITH 2N12 OR 1N16 BAR 500 MIN. LAP.2. PROVIDE SINGLE COURSE BOND BEAM IMMEDIATLY BELOW ALLWINDOW OPENINGS.REINF. WITH 1N12 .EXTEND BOND BEAM 200 PAST EACH SIDE OF OPENING.3. U.N.O. ON PLAN ALL LINTELS TO BE REINF WITH 2N16 ALL LINTELS TOBE TIED TO SLAB OVER WITH N12-600 BARS COGGED 500 INTO TOP OFSLAB.4. U.N.O. ON PLAN ALL 200 C.M.B. WALLS TO BE REINF. WITH N16VERTICAL BARS AT ENDS, CORNERS, INTERSECTIONS, AT EACH SIDE OFOPENINGS AND AT 800 MAX. CENTRES BETWEEN.5. W.C.J. DENOTES WALL CONTROL JOINT U.N.O. TO BE REINFORCEDWITH 1N16 VERTICAL EACH SIDE OF JOINT. EXTEND BOND BEAMREINFORCEMENT THROUGH JOINT FILL JOINT WITH COMPRESSIBLEBACKING ROD AND APPROVED SEALANT BOTH SIDES TO ARCHITECTSSPECIFICATION.6. 300x300 C.M.B PIERS TO BE REINF. WITH 4-N16 VERT. REINF. AND R6LIGS AT 300CTS7. 400x400 C.M.B PIERS TO BE REINF. WITH 4-N16 VERT. REINF. AND R6LIGS AT 300CTS8. WALL PANELS LESS THAN OR EQUAL TO 800LG TO BE REINF. WITH N16VERT. BARS IN EACH CORE
1. PROVIDE DOUBLE COURSE BOND BEAM TO TOP OF WALLUNDER ROOF. REINFORCED WITH 1 / N16 BAR EACH COURSE 500MIN. LAPS.2. PROVIDE SINGLE COURSE BOND BEAM IMMEDIATELY BELOWALL WINDOW OPENINGS. REINFORCED WITH 1 / N12 HORIZONTAL,COGGED 500 INTO CORES EACH SIDE OF OPENINGS. EXTENDBOND BEAM 200 PAST EACH SIDE OF OPENING.3. U.N.O. ON THIS PLAN ALL LINTELS TO BE REINFORCED WITH1 /N16 BAR AND L8 LIGS @ 1000 CTS. MAX.
7. U.N.O. ON THIS PLAN CONCRETE FILL ALL CORES CONTAININGREINFORCEMENT, HOLDING DOWN BOLTS AND MASONRYANCHORS. ALL CONCRETE MASONRY CORES CONTAININGREINFORCEMENT, HOLDING DOWN BOLTS AND MASONRYANCHORSTO BE CLEANED & FILLED WITH S20 GRADE CONCRETE,10mm MAX. AGGREGATE & 230 SLUMP.8. 100 SERIES WALLS TIED TO EXTERNAL WALLS WITH APPROVEDMASONRY MESH EVERY 2nd COURSE. WHERE APPLICABLE, NEW200 SERIES MASONRY WALLS TIED WITH 300 LONG R10 DOWELSEVERY 2nd COURSE INTO EXISTING CORE FILLED 200 SERIESMASONRY WALLS9. N16 STARTER BARS TO COINCIDE WITH EACH VERTICAL BAR.STARTER BARS COGGED 200 INTO FOOTING & LAPPED 600 MIN.WITH ALL VERTICAL BARS
4. U.N.O. ON THIS PLAN ALL 200 C.M.B. WALLS TO BEREINFORCED WITH N16 VERTICAL BARS AT ENDS, CORNERS,
INTERSECTIONS AND AT EACH SIDE OF OPENINGS AND AT800 CTS. MAX BETWEEN5. PROVIDE ADDITIONAL N16 VERTICAL REINFORCEMENT TOCORES ADJACENT TO OPENINGS GREATER THAN 1800 WIDE
6. W.C.J. DENOTES WALL CONTROL JOINT U.N.O. TO BEREINFORCED WITH N16 VERTICAL BAR EACH SIDE OF JOINT.EXTEND BOND BEAM REINFORCEMENT THROUGH JOINT FILLJOINT WITH COMPRESSIBLE BACKING ROD AND APPROVEDSEALANT BOTH SIDES TO BUILDERS SPECIFICATION.
Issue Revision Description Date
A PRELIMINARY WORKING DRAWINGS 20/03/2017
B CONSTRUCTION DRAWINGS 08/05/2017
NOTE This is to be used for the purposes of section 10 of the Building Act 1975 and/or section 46 of the Building Regulation 2006. RESTRICTION: A building certifier (class B) can only give a compliance certificate about whether building work complies with the BCA or a provision of the QDC. A building certifier (Class B) can not give a certificate regarding QDC boundary clearance and site cover provisions.
1. Property description This section need only be completed if details of street address and property description are applicable. EG. In the case of (standard/generic) pool design/shell manufacture and/or patio and carport systems this section may not be applicable. The description must identify all land the subject of the application. The lot & plan details (eg. SP / RP) are shown on title documents or a rates notice. If the plan is not registered by title, provide previous lot and plan details.
Street address (include no., street, suburb / locality & postcode) Evans Road ( 37912L1 ) Bramston Beach Lot & plan details (attach list if necessary) Lot 28
In which local government area is the land situated? Cairns Regional Council
2. Description of component/s certified Clearly describe the extent of work covered by this certificate, e.g. all structural aspects of the steel roof beams.
Footings/Ground Slab Bracing Tie-Down Concrete Masonry Wall & Roof Framing Structural Steel Suspended Concrete Slab Reinforced Concrete Swimming Pool
3. Basis of certification Detail the basis for giving the certificate and the extent to which tests, specifications, rules, standards, codes of practice and other publications, were relied upon.
Wind Classification – C2 Australian Standard Codes- AS 3600, AS3700, AS4100, AS4600, AS 1684.3 AS/NZS 1170 Parts 1, Local Authority Regulations Site Classification – Class S
4. Reference documentation Clearly identify any relevant documentation, e.g. numbered structural engineering plans.
Balay Building Design drawings 15595-M Sheets 1-9 CMG Consulting Engineers drawings 37912 sheets 1-2
5. Building certifier reference number ..
Building certifier reference number
6. Competent person details A competent person for building work, means a person who is assessed by the building certifier for the work as competent to practise in an aspect of the building and specification design, of the building work because of the individual’s skill, experience and qualifications in the aspect. The competent person must also be registered or licensed under a law applying in the State to practice the aspect.
If no relevant law requires the individual to be licensed or registered to be able to give the help, the certifier must assess the individual as having appropriate experience, qualifications or skills to be able to give the help.
If the chief executive issues any guidelines for assessing a competent person, the building certifier must use the guidelines when assessing the person.
Name (in full) Charles Gianarakis RPEQ 1370
Company name (if applicable) Contact person CMG Consulting Engineers Pty Ltd Charles Gianarakis
Phone no. business hours Mobile no. Fax no. 07 40 312775 07 40 519013
Email address [email protected]
Postal address P.O. Box 5901, Cairns Qld 4870
Licence or registration number (if applicable)
RPEQ 1370
7. Signature of competent person This certificate must be signed by the individual assessed by the building certifier as competent.
Signature Date 4 May 2017
Form 15 -Compliance Certificate for building Design or Specification Version 3 March 2013